The NZ Handbook

2011 Edition

Safety Warning

Cables are insulated and sheathed with stable materials which may contain
certain toxic substances including lead. Insulation and sheathing materials
should not be chewed or ingested.
When XLPE coloured cores are exposed to sunlight or outdoors the UV rays
will break down the XLPE. Therefore they should be made safe from the
effects of the UV by adding some form of UV protection.

Installation
Cables must be installed in accordance with the requirements of the latest
issue of AS/NZS 3000 or the appropriate ruling standard in the country of
installation. Cables must also be connected by a licensed electrician, as
ruled in the state or country of installation.
Olex New Zealand Limited has taken every precaution to ensure that the
information contained in the booklet is in line with the requirements of the
appropriate New Zealand Standards and correct electrical practice. However,
we accept no liability of any kind with respect to the information presented
here.

Note
Current carrying capacity tables stated in this handbook are based on
AS/NZS 3008.1.2, Electrical Installations Selection of Cables. Part 1.2:
Cables for alternating voltages up to and including 0.6/1 kV Typical New
Zealand Installation conditions.

All information is subject to change without notice.

Supplier Declaration of Conformity (SDoC)


In accordance with ISO/IEC 17050-1:2004

SDoC identification Number -29-20-300


Issuer details
Name2 (of New Zealand manufacturer or importer)
Olex New Zealand Limited

Contact Address
Paraite Road, Bell Block
New Plymouth

New Zealand Company Number (if applicable)


AK/960396
Telephone
06 7559800

Fax
06 755 9890

Email address
dgriffiths@olex.co.nz

Medium Risk Article Details (Product name, type, rating, brand, model, batch numbers, and serial numbers, as applicable)
Conduit Wires, Cantol, Cempex, Neutral-Screen, Armoured Mains,
Vintols & L.V URD

The medium risk article listed above, fully complies with the standard(s), as listed:Standard number & issue year:-AS/NZS 5000.1 : 2005, AS/NZS 4026 : 2008 Section 4&5, AS/NZS 4961 : 2003 Section 2.
Standard Title:-Electric cables Polymeric insulated Part 1: For working voltages up to and including 0.6/1 (1.2) kV.
-Electric cables For underground residential distribution systems.
-Electric cables Polymeric insulated-For distribution and service applications.
Edition / Amendment status:Or complies with the Conformity Cooperation Agreement - No
Names and addresses of any testing organisation or body
Name(s)
Olex New Zealand

Address(es)
Paraite Road, Bell Block, New Plymouth

Test Safe Australia

919 Londonderry Road, Londonderry, NSW 2753 Australia

Reference to relevant test reports/certification, and issue date of the reports/certification, that show how compliance is achieved:Report/Certification N(s)
Issue date(s)
Olex NZ Quality doc # 29-20-300 QTR Test Report for L.
06/03/2009, Issue 1.0
V. Cable to AS/NZS 5000.1
Olex NZ Quality doc # 29-20-303 QTR Test Report for L.
28/04/2010, Issue 1.0
V. Cable to AS/NZS 4026
Reference to any management systems involved:Additional4 information
Declaration
I hereby declare that the above specified fittings or electrical
appliances comply with the requirements of Regulation 83 of
the Electricity (Safety) Regulations 2010

Issuer Identification:

OLEX (NZ)
CANTOL

Signed for and on behalf of:


Olex New Zealand
Name5 & position, as authorized by the issuer
David Griffiths, Technical Manager
Signature

Date

(as affixed to the article)


12/08/2010

Every declaration of conformity should be uniquely identified.


The responsible issuer must be unequivocally specified.
The Article must be unequivocally described so that the declaration of conformity may be related to the article in question. For mass-produced
products, it is not necessary to give individual serial numbers. Where variants of an article are to be covered, these must be detailed.
4
Text should appear here only if any limitation on the validity of the declaration of conformity and/or any additional information are given.
5
Full name and function of the signing person(s) authorised by the issuer's management to sign on its behalf should be given. The number of
signatures, or equivalent, included will be the minimum determined by the legal form of the issuers organization.
2
3

Supplier Declaration of Conformity (SDoC)


In accordance with ISO/IEC 17050-1:2004

SDoC identification Number -29-20-301


Issuer details
Name2 (of New Zealand manufacturer or importer)
Olex New Zealand Limited

Contact Address
Paraite Road, Bell Block
New Plymouth

New Zealand Company Number (if applicable)


AK/960396
Telephone
06 7559800

Fax
06 755 9890

Email address
dgriffiths@olex.co.nz

Medium Risk Article Details (Product name, type, rating, brand, model, batch numbers, and serial numbers, as applicable)
TPS & REMOLEX

The medium risk article listed above, fully complies with the standard(s), as listed:Standard number & issue year:-AS/NZS 5000.2: 2006
Standard Title:-Electric cables Polymeric insulated Part 2: For working voltages up to and including 450/750V.
Edition / Amendment status:Or complies with the Conformity Cooperation Agreement - No
Names and addresses of any testing organisation or body
Name(s)
Olex New Zealand

Address(es)
Paraite Road, Bell Block, New Plymouth

Test Safe Australia

919 Londonderry Road, Londonderry, NSW 2753 Australia

Reference to relevant test reports/certification, and issue date of the reports/certification, that show how compliance is achieved:Report/Certification N(s)
Issue date(s)
Olex NZ Quality doc # 29-20-301 QTR Test Report for L.
11/03/2009, Issue 2.0
V. Cable to AS/NZS 5000.2

Reference to any management systems involved:Additional4 information


Declaration
I hereby declare that the above specified fittings or electrical
appliances comply with the requirements of Regulation 83 of
the Electricity (Safety) Regulations 2010

Name5 & position, as authorized by the issuer


David Griffiths, Technical Manager
Signature

Issuer Identification:
(as affixed to the article)

Signed for and on behalf of:


Olex New Zealand

OLEX (NZ)
Cu Remolex

Date
20/05/2010

Every declaration of conformity should be uniquely identified.


The responsible issuer must be unequivocally specified.
The Article must be unequivocally described so that the declaration of conformity may be related to the article in question. For mass-produced
products, it is not necessary to give individual serial numbers. Where variants of an article are to be covered, these must be detailed.
4
Text should appear here only if any limitation on the validity of the declaration of conformity and/or any additional information are given.
5
Full name and function of the signing person(s) authorised by the issuer's management to sign on its behalf should be given. The number of
signatures, or equivalent, included will be the minimum determined by the legal form of the issuers organization.
2
3

Contents

Low Voltage
Alsecure Envirolex Cables............................................................................................... 6
Conduit Wires ..................................................................................................................... 8
Cu Strand Soft Drawn .................................................................................................... 10
TPS Cables....................................................................................................................... 11
Alsecure Envirolex TPS Cables..................................................................................... 14
Remolex Cables.............................................................................................................. 15
Cempex Cables............................................................................................................... 16
Cu Distribution Cables ...................................................................................................... 17
Al Neutral-Screened Cables..18
PVC Neutral-Screened Cables ........................................................................................ 19
XLPE Neutral-Screened Cables....................................................................................... 21
Cu Cantols ........................................................................................................................ 22
Cu Vintols.......................................................................................................................... 23
Al Cantols.......................................................................................................................... 24
Al Vintols ........................................................................................................................... 25
Single Core Aluminium Cables ........................................................................................ 26
Al URD Cables.................................................................................................................. 27
PVC Armoured Mains Cables .......................................................................................... 28
XLPE Armoured Mains Cables ........................................................................................ 29
Control Cables .................................................................................................................. 30
Armoured Control Cables................................................................................................. 31
Irrigation Cable Single Core ............................................................................................. 32
Industrial
Flexible Power Cable Selection Criteria ........................................................................... 34
TM
Powerlex PVC Appliance Wires .................................................................................... 35
PowerlexTM PVC Flexible Cords ....................................................................................... 37
PVC Flexible Trurip ........................................................................................................... 38
Versolex HD Single Core ................................................................................................ 39
Versolex Multi Cords & Cables ....................................................................................... 41
Versolex Braided Cords & Cables................................................................................... 43

Titanex Multicore (H07RN-F) .......................................................................................... 44


Buflex XPrem Reeling Cable .......................................................................................... 46
Varolex Variable Speed Drive Cables ............................................................................. 48
PVC Flexible Control......................................................................................................... 49
PVC-EMC Flexible Control................................................................................................ 51
Silicone Single Core.......................................................................................................... 52
Silicone Multicore.............................................................................................................. 53
Instrolex Instrumentation Cable....................................................................................... 54
PVC Flat Crane Cable....................................................................................................... 57
Notes................................................................................................................................. 58

Page 3

Contents

Data & Communication


Security Cable................................................................................................................... 60
Audiolex ............................................................................................................................ 61
Figure 8 Speaker Trurip ................................................................................................... 62
Coaxial Cable.................................................................................................................... 63
Composite Coaxial & Control Core .................................................................................. 65
LAN ................................................................................................................................... 66
Optical Fibre...................................................................................................................... 67
Telephone Internal ............................................................................................................ 68
Telephone External........................................................................................................... 69
Garden Lighting ................................................................................................................ 70
Fire Alarm Cable ............................................................................................................... 71
Data Cables ...................................................................................................................... 72
Fire Rated

Alsecure Premium Ceramifiable Single Core ................................................................ 74


Alsecure Premium Ceramifiable Multi Core ................................................................... 75

Alsecure Premium FRP Ceramifiable ........................................................................... 76

Alsecure Premium Flex Ceramifiable ............................................................................ 77


Aerial
AAC Aerial Conductors ..................................................................................................... 79
AAAC Aerial Conductors................................................................................................... 80
ACSR Aerial Conductors................................................................................................... 81
Al Aerial Bundled Cables (ABC)....................................................................................... 82
Al Binder Wire ................................................................................................................... 83
Cu Aerial - Hard Drawn .................................................................................................... 84
Cu Aerial - Trurip............................................................................................................... 85
Cu Aerial Neutral Screens.............................................................................................. 85
Cu Binder Wire.................................................................................................................. 86
Notes................................................................................................................................. 87
Glands & Accessories
A2 Industrial Glands.......................................................................................................... 89
A2F Dual Certified EExd & EExe Glands....................................................................... 89
VSD Glands ...................................................................................................................... 89
A4 Industrial Glands.......................................................................................................... 90
CW Industrial Glands ........................................................................................................ 90
E1FW Dual Certified EExd & EExe Glands ..................................................................... 91
CX/Z Industrial Glands ...................................................................................................... 91
PX2K Flameproof EExd Glands ...................................................................................... 92
Gland Accessories ............................................................................................................ 92
PVC Shrouds .................................................................................................................... 93
Notes...................................................................................................................................94
Page 4

Contents

General Technical Information


Installation Information ...................................................................................................... 96
Minimum Spacings in Air to Avoid Derating ...................................................................... 99
Single Core Cables in Parallel ........................................................................................ 100
Bending Radii.................................................................................................................. 101
Duct Sizes....................................................................................................................... 103
Pulling Tension ............................................................................................................... 104
Copper Conductor Dimensions ....................................................................................... 106
Aluminium Conductor Dimensions .................................................................................. 107
Cable Selection
Four Main Factors........................................................................................................... 108
Procedures...................................................................................................................... 109
Current Ratings............................................................................................................... 111
Simple Cable Selection Chart ......................................................................................... 113
Low Voltage (0.6/1 kV) Rating Factors............................................................................ 116
Current Ratings
Single Conductor PVC (Single Phase)............................................................................ 118
Single Conductor XLPE (Single Phase) .......................................................................... 119
Two Conductor PVC (Single Phase)............................................................................... 120
Two Conductor XLPE (Single Phase) ............................................................................. 121
Single Conductor PVC (Three Phase) ............................................................................ 122
Single Conductor XLPE (Three Phase)........................................................................... 123
Single Conductor Ceramifiable (Three Phase).............................................................. 124
Three & Four Conductor PVC (Three Phase) ................................................................. 125
Three & Four Conductor XLPE (Three Phase) ............................................................... 126
PVC Flexible Cords......................................................................................................... 127
Versolex Single Core Flexible Cables (Single Phase)................................................... 128
Versolex Single Core Flexible Cables (Three Phase) ................................................... 129
Versolex Two Core Flexible Cables (Single Phase) ...................................................... 130
Versolex Three & Four Core Flexible Cables (Three Phase) ....................................... 131
AAC Aerial Conductors ................................................................................................... 132
AAAC Aerial Conductors................................................................................................. 133
ACSR Aerial Conductors................................................................................................. 134
Al Aerial Bundled Cables (ABC)...................................................................................... 135
Cu Aerial Hard Drawn .................................................................................................. 136
General Data
Useful 3 Phase Formulae................................................................................................ 137
Wire & Cable Size Comparison....................................................................................... 138
Motor Current Table (Amperes approx) .......................................................................... 139
Abbreviations .................................................................................................................. 140
Copper Earthing Conductors........................................................................................... 141
Page 5

Alsecure Envirolex Cables

Alsecure Envirolex cables are an extensive range of enhanced


performance cables for the construction industry engineered to dramatically
reduce environmental impact, particularly under fire conditions, while
retaining the excellent mechanical and electrical properties designed into
Olex cables. Olex uses a variety of inorganically filled polyolefin based
materials to engineer the cables in the Alsecure Envirolex range to meet a
wide variety of end uses and performance requirements.
Advantages of Alsecure Envirolex cables

Cable types from building wires to SWA, to multicore control

90C rated superior thermal performance


Improved performance under fire conditions:
Flame retardant/self-extinguishing
Reduced acid, gas and smoke generation
Non-corrosive in fire situations
Reduced toxicity of fumes during fire
Halogen free (i.e. no chlorine, bromine etc)

Lead free
No special termination or installation requirements
Made in accordance with Australian and New Zealand Standards

Alsecure Envirolex cables have been tested according to and comply with
the requirements of the single flame tests specified in AS1660.
Alsecure Envirolex products include readily strippable cables for general
construction purposes as well as the tougher products commonly found in
cables with higher fire performance capability.
Information on the Alsecure Envirolex range of 2 core plus earth and 3 core
flat cables can be found on page 14 of this handbook. Alsecure Envirolex
materials can also be used as alternatives to all other low voltage power and
control cables. Cables are available on request, subject to minimum
production run.

Page 6

Page 7

Conduit Wires

Cu conductor, PVC insulation. 0.6/1 kV. Made to AS/NZS 5000.1.

Material No.
V90HT Insulation
BAAP01AD001AABK
V90 Insulation
BAAP02C1001AABK
BAAP02C1001AABE
BAAP02C1001AAGN
BAAP02C1001AARD
BAAP02C1001AAWT
BAAP05C1001AABK
BAAP05C1001AABE
BAAP05C1001AAHN
BAAP05C1001AARD
BAAP05C1001AAWT
BAAP07C1001AABK
BAAP07C1001AABE
BAAP07C1001AAHN
BAAP07C1001AARD
BAAP07C1001AAWT
BAAP09A1001AABK
BAAP09C1001AABE
BAAP09C1001AAHN
BAAP09C1001AARD
BAAP09C1001AAWT
V75 Insulation
BAAP11A1001AABK
BAAP11A1001AABE
BAAP11A1001AAHN
BAAP11A1001AARD
BAAP11A1001AAWT

Area
mm

Colour

Nom Dia
mm

8143

0.5

BK

2.5

0.11

1210
8153
5984
7974
3318
8439
9137
3682
7322
3317
2111
2215
3898
5786
4732
8484
4640
8495
6347
8207

1.0
1.0
1.0
1.0
1.0
1.5
1.5
1.5
1.5
1.5
2.5
2.5
2.5
2.5
2.5
4
4
4
4
4

BK
BU
GN
RD
WH
BK
BU
GNYE
RD
WH
BK
BU
GNYE
RD
WH
BK
BU
GNYE
RD
WH

2.8
2.8
2.8
2.8
2.8
3.3
3.3
2.8
3.3
3.3
3.8
3.8
3.6
3.8
3.8
4.7
4.7
4.7
4.7
4.7

0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.03
0.03
0.03
0.03
0.03
0.06
0.06
0.06
0.06
0.06

7852
8105
6112
9844
4875

6
6
6
6
6

BK
BU
GNYE
RD
WH

5.3
5.3
5.3
5.3
5.3

0.08
0.08
0.08
0.08
0.08

Note: Conductors 1.5 mm and above are circular stranded.

continued

Page 8

Approx
Mass
kg/m

Old
Code

Conduit Wires

Cu conductor, PVC insulation. 0.6/1 kV. Made to AS/NZS 5000.1.

Material No.
V75 Insulation
BAAP13A1001AABK
BAAP13A1001AABE
BAAP13A1001AAHN
BAAP13A1001AARD
BAAP13A1001AAWT
BAAP15AA001AABK
BAAP15AA001AABE
BAAP15AA001AAHN
BAAP15AA001AARD
BAAP15AA001AAWT
BAAP16AA001AACX
BAAP16AA001AABF
BAAP16AA001AAHT
BAAP16AA001AAJB
BAAP16AA001AAWV
BAAP18AA001AACX
BAAP18AA001AABF
BAAP18AA001AAHT
BAAP18AA001AAJB
BAAP18AA001AAWV
BAAP19AA001AAHT
BAAP19AA001AAJB
BAAP20AA001AAHT
BAAP21AA001AAHT
BAAP23AA001AAHT

Old
Code

Area
mm

Colour

Nom Dia
mm

3271
8883
3513
8770
4096
7077
7481
4462
1499
3114
3897
5672
6320
3825
7361
7395
8067
2057
4928
9190
9988
3629
5680
5987
7379

10
10
10
10
10
16
16
16
16
16
25
25
25
25
25
35
35
35
35
35
50
50
70
95
120

BK
BU
GNYE
RD
WH
BK
BU
GNYE
RD
WH
BK
BU
GNYE
RD
WH
BK
BU
GNYE
RD
WH
GNYE
RD
GNYE
GNYE
GNYE

6.2
6.2
6.2
6.2
6.2
7.2
7.2
7.3
7.2
7.2
8.9
8.9
8.9
8.9
8.9
10.1
10.1
10.1
10.1
10.1
11.8
11.8
13.5
15.8
17.5

Approx
Mass
kg/m
0.12
0.12
0.12
0.12
0.12
0.18
0.18
0.18
0.18
0.18
0.28
0.28
0.28
0.28
0.28
0.38
0.38
0.38
0.38
0.38
0.51
0.51
0.72
1.00
1.23

Note: Conductors 1.5 mm and above are circular stranded.

Page 9

Cu Strand Soft Drawn

Cu conductor. Made to AS/NZS 1125.

Material No.
ACUP15AA001AAAA
ACUP17AA001AAAA
ACUP18AA001AAAA
ACUP19AA001AAAA
ACUP20AA001AAAA
ACUP21AA001AAAA
ACUP23AA001AAAA

Page 10

Old
Code

Area
mm

Nom Dia
mm

1641
9211
9733
5979
3350
7934
5301

16
25
35
50
70
95
120

5.0
6.3
7.6
8.8
10.5
12.4
14.1

Approx
Mass
kg/m
0.15
0.23
0.32
0.43
0.62
0.86
1.09

TPS Cables

Cu conductor, PVC insulation, PVC sheath. 450/750 V. Made to AS/NZS 5000.2.

Material No.
Single Core
AABP02A1001WVBK
AABP02A1001WVRD
AABQ05A1001WVBK
AABQ05A1001WVRD
AABP07A1001WVBK
AABP07A1001WVRD
AABP09A1001WVBK
AABP09A1001WVRD
AABP11A1001WVBK
AABP11A1001WVRD
AABP13A1001WVBK
AABP13A1001WVRD
AABP15A1001WVBK
AABP15A1001WVRD

Old
Code

Area
mm

Colour

Nom
Dia
mm

1748
1176
9050
6766
7923
1635
7242
2889
8579
5022
1343
6104
1121
2627

1.0 *
1.0 *
1.5
1.5
2.5
2.5
4
4
6
6
10
10
16
16

BK WH
RD WH
BK WH
RD WH
BK WH
RD WH
BK WH
RD WH
BK WH
RD WH
BK WH
RD, WH
BK WH
RD WH

3.8
3.8
4.4
4.4
4.9
4.9
6.0
6.0
6.5
6.5
7.8
7.8
9.3
9.3

Approx
Mass
A2 or A2F
kg/m
Gland
Size

20S/16
20S/16
20S/16
20S/16
20S/16
20S/16
20S/16
20S/16
20S/16
20S/16
20S/16
20S/16
20S
20S

0.03
0.03
0.04
0.04
0.05
0.05
0.07
0.07
0.10
0.10
0.15
0.15
0.22
0.22

Note: Conductors 1.5 mm and above are circular stranded.


* Solid conductor

Page 11

TPS Cables

Cu conductors, PVC insulation, PVC sheath. 450/750 V. Made to AS/NZS 5000.2.

Material No.
Two Core
CACP02A1002JBHF
CACP02A1002WVHF
CACP02AA002ASWV
CACQ05A1002JBHF
CACQ05A1002WVHF
CACP05AA002ASWV
CACP07A1002JBHF
CACP07A1002WVHF
CACP07A1002WVAB
CACP09A1002WVHF
CACP11A1002WVHF
CACP15AA002CXHF
Two Core Plus Pilot
QCPP15AA002CXHF
QCQP16AA002CXHF
Two Core Plus Earth
CNZP02A1002WVHF
CNZQ05A1002WVHF
CNZP07A1002WVHF
CNZP09A1002WVHF
CNZP11AA002WVHF
CNZP13EC002WVHF
CNZP15AA002CXHF

Nom Dim
mm

Approx
Mass
kg/m

RD
4.0 x 6.3
WH
4.0 x 6.3
WH (R+R)
4.0 x 6.3
RD
4.7 x 7.4
WH
4.7 x 7.4
WH (R+R)
4.7 x 7.4
RD
5.3 x 8.7
WH
5.3 x 8.7
WH (R+W)
5.3 x 8.7
WH
6.3 x 10.5
WH
7.0 x 11.6
BK
10.0 x 17.2

0.05
0.05
0.05
0.07
0.07
0.07
0.10
0.10
0.10
0.15
0.20
0.46

Old
Code

Cores x Area
mm

8757
3524
1539
1049
7373
2651
8313
9880
8717
5212
8552
6331

2 x 1.0 *
2 x 1.0 *
2 x 1.0 *
2 x 1.5
2 x 1.5
2 x 1.5
2 x 2.5
2 x 2.5
2 x 2.5
2x4
2x6
2 x 16

1291
2399

2 x 16 + 2.5 P
2 x 25 + 4 P

BK
BK

9.9 x 20.4
11.8 x 24.8

0.50
0.77

9779
2521
1080
6646
3146
4121
6565

2 x 1.0 + 1.0 E*
2 x 1.5 + 1.5 E
2 x 2.5 + 2.5 E
2 x 4 + 2.5 E
2 x 6 + 2.5 E
2 x 10 + 4 E
2 x 16 + 6 E

WH
WH
WH
WH
WH
WH
BK

4.0 x 8.6
4.7 x 10.2
5.3 x 12.0
6.4 x 14.8
6.9 x 16.4
8.5 x 20.4
9.9 x 24.3

0.07
0.09
0.14
0.19
0.27
0.42
0.63

Sheath

Note: Conductors 1.5 mm and above are circular stranded.


* Solid conductor

continued

Page 12

TPS Cables

Cu conductors, PVC insulation, PVC sheath. 450/750 V. Made to AS/NZS 5000.2.

Material No.
Three Core
EACP02A1003YXRJ
EACQ05A1003YXRJ
EACP07A1003WVHF
Three Core Plus Earth
ENZP02A1003WVRJ
ENZQ05A1003WVRJ
ENZP07A1003WVRJ
ENZP09A1004WVPF
ENZP11AA003WVRJ
Four Core
GACP07A1004WVEM
GACP09A1004WVEM

Sheath

Nom Dim
mm

Approx
Mass
kg/m

3 x 1.0 *
3 x 1.5
3 x 2.5

YE
YE
WH

4.0 x 8.6
4.6 x 10.2
5.3 x 12.0

0.07
0.09
0.14

1719
4191
4169
1103
1529

3 x 1.0 + 1.0 E*
3 x 1.5 + 1.5 E
3 x 2.5 + 2.5 E
3 x 4 + 2.5 E
3 x 6 + 2.5 E

WH
WH
WH
WH
WH

4.0 x 10.9
4.7 x 13.0
5.3 x 15.4
6.5 x 19.1
7.2 x 21.4

0.09
0.12
0.18
0.29
0.38

2305
4253

4 x 2.5
4x4

WH
WH

5.3 x 15.4
6.5 x 19.1

0.18
0.29

Old
Code

Cores x Area
mm

5510
3171
1560

Note: Conductors 1.5 mm and above are circular stranded.


* Solid conductor

Page 13

Alsecure Envirolex
TPS Cables
Cu conductors, X-HF-90 insulation, Green HFS-90-TP sheath. 450/750V.
Made to AS/NZS 5000.2.

Material No.
Two Core Plus Earth
CTCP05JA002
CTCP07JA002
CTCP09JA002
CTCP11JA002
Three Core
EECP05J1003GGRJ

Nom Dim
mm

Approx
Mass
kg/m

Old
Code

Cores x Area
mm

1462
6724
3334
3404

2 x 1.5 + 1.5 E
2 x 2.5 + 2.5 E
2 x 4 + 2.5 E
2 x 6 + 2.5 E

4.6 x 10.0
5.3 x 11.7
6.2 x 13.4
6.8 x 14.5

0.07
0.11
0.15
0.19

4818

3 x 1.5

4.6 x 10.0

0.07

Note: Alsecure Envirolex cables are lead and halogen free and are suitable for green
building installations.

Page 14

Remolex Cables

Cu conductors, PVC insulation, Laid up, Black PVC sheath. 450/750 V.


Made to AS/NZS 5000.2. Circular multicore with integral earth.

Material No.
Two Core Plus Earth
CNHQ05AA002CXHF
CNHP07AA002CXHF
CNHP09AA002CXHF
CNHP11AA002CXHF
CNHP15AA002CXHF
Three Core Plus Earth
ENHQ05AA003CXRJ
ENHP07AA003CXRJ
ENHP09AA003CXRJ
ENHP11AA003CXRJ
ENHP13AA003CXRJ
ENHP15AA003CXRJ
Four Core Plus Earth
GNHQ05AA004CXEM
GNHP07AA004CXEM
GNHP09AA004CXEN

Old
Code

Cores x Area
mm

Nom
Dia
mm

A2 or A2F

4948
5312
1024
2160
9617

2 x 1.5 + 1.5 E
2 x 2.5 + 2.5 E
2 x 4 + 2.5 E
2 x 6 + 2.5 E
2 x 16 + 6 E

8.9
10.0
11.3
12.2
18.7

20S
20S
20
20
25

0.12
0.17
0.21
0.26
0.61

3145
6978
1750
8214
7025
5101

3 x 1.5 + 1.5 E
3 x 2.5 + 2.5 E
3 x 4 + 2.5 E
3 x 6 + 2.5 E
3 x 10 + 4 E
3 x 16 + 6 E

9.7
11.0
12.4
14.6
16.6
20.7

20S
20S
20
25
25
32

0.15
0.21
0.27
0.40
0.54
0.81

4131
7325
9465

4 x 1.5 + 1.5 E
4 x 2.5 + 2.5 E
4 x 4 + 2.5 E

10.6
12.1
14.0

20
25
25

0.18
0.25
0.34

Gland
Size

Approx
Mass
kg/m

Core Colours
No. Cores
3
4
5

Colour
RD, BK, GNYE
RD, WH, BU, GNYE
RD, WH, BU, BK, GNYE

Note: Conductors 1.5 mm and above are circular stranded.

Page 15

Cempex Cables

Cu conductors, XLPE insulation, Laid up, Black PVC sheath. 0.6/1 kV.
Made to AS/NZS 5000.1. Circular multicore with integral earth.

Material No.
Three Core Plus Earth
FTHC17AA003CXRJ
FTHC38AA003CXRJ
FTHC19AA003CXRJ
Four Core Plus Earth
HTHP11AA004CXEM
HTHP13AA004CXEM
HTHP15AA004CXEM
HTHC17AA004CXEM
HTHC18AA004CXEM
HTHC19AA004CXEM
HTHC20AA004CXEM
HTHC21AA004CXEM

Old
Code

Cores x Area
mm

Nom
Dia
mm

A2 or A2F

1701
5200
6560
1530

3 x 25 ^ + 6 E
3 x 35 ^ + 10 E
3 x 50 ^ + 16 ^ E
3 x 70 ^ + 25 ^ E

21.6
24.1
27.2
31.2

32
32
40
40

1.01
1.37
1.82
2.59

1139
2658
7656
5243
2230
2403
2060
7214

4 x 6 + 2.5 E
4 x 10 + 4 E
4 x 16 ^ + 6 E
4 x 25 ^ + 6 E
4 x 35 ^ + 10 E
4 x 50 ^ + 16 ^ E
4 x 70 ^ + 25 ^ E
4 x 95 ^ + 25 ^ E

17.0
19.2
21.5
23.9
26.8
30.3
34.9
39.1

25
25
32
32
40
40
50S
50

0.43
0.66
0.90
1.29
1.74
2.32
3.20
4.36

Gland
Size

Core Colours
No. Cores
4
5

Colour
RD, WH, BU, GNYE
RD, WH, BU, BK, GNYE

Note: ^ Conductors 16 mm and above are compact circular stranded.


Conductors 10 mm and below are circular stranded.

Page 16

Approx
Mass
kg/m

Cu Distribution Cables

Cu conductors, XLPE insulation, Black PVC sheath. Vector specification.

Material No.
Conductor Size 16 mm
DEVP15VT002CXHF
HEVP15VT004CXEM
Conductor Size 25 mm
DEVC16VT002CXHF
HEVC16VT004CXEM
Conductor Size 35 mm
DEVC38VT002CXHF

Nom Dia
mm

Approx
Mass
kg/m

Old
Code

Cores x Area
mm

6988
3996

2 x 16
4 x 16

19.1
22.5

0.37
0.87

3799
9663

2 x 25
4 x 25

23.2
25.8

0.73
1.29

1005

2 x 35

24.0

0.84

Core Colours
No. Cores
2
4

Colour
RD, BK
RD, WH, BU, BK

Note: Conductors are circular stranded.

Page 17

Al Neutral-Screened
Cables
Al conductors, XLPE insulation, Laid up, Cu neutral screen, Black PVC sheath.
0.6/1 kV. Made to AS/NZS 4961.

Material No.
Single Core
BDGH20PX001CXRD
BDGH21PX001CXRD
BDGH43PX001CXRD
BDGH25PX001CXRD
Single Core Plus Pilot
QDQH20PX001CXRD
Three Core
FEGH38PX003CXRJ
FEGH39PX003CXRJ
FEGG20PX003CXRJ
FEGG21PX003CXRJ
Three Core Plus Pilot
QDZG23PX003CXRJ
QDZG25PX003CXRJ
QDZG27PX003CXRJ

Old
Code

Cores x Area
mm

9123
1369
6550
5150

1 x 70 ^
1 x 95 ^
1 x 120 ^
1 x 185 ^

5808

1 x 70 ^ + 4 P

6229
1039
8351
8365
3164
4774
1891

Nom Dia
mm
21.5
23.9
26.2
31.4

0.89
1.15
1.41
2.08

29.2 x 21.9

1.06

3 x 35
3 x 50
3 x 70
3 x 95

28.1
31.0
32.3
35.9

1.00
1.24
1.56
2.01

3 x 120 + 10 P
3 x 185 + 10 P
3 x 300 + 10 P

39.6
48.5
57.7

2.59
3.79
5.76

Core Colours
No. Cores
3
3 (Plus Pilot)
4
Note:

Page 18

Approx
Mass
kg/m

Colour
RD, WH, BU
RD, WH, BU, OG
RD, WH, BU, BK

Single Core - ^ Conductors are compact circular stranded.


Three Core - Conductors are shaped stranded.
3.2 mm sheath, unless indicated by * which is 1.8 mm sheath

PVC Neutral-Screened
Cables
Cu conductors, PVC insulation, Cu wire neutral screen, Black PVC sheath.
0.6/1 kV. Made to AS/NZS 4961.

Material No.
Single Core
BAGP07AA001CXRD
BAGP09PX001CXRD
BAGP11PX001CXRD
BAGP13PX001CXRD
BAGP15PX001CXRD
BAGP16PX001CXRD
BAGP18PX001CXRD
BAGP19PX001CXRD
Single Core Plus Pilot
QDBP15PX001CXRD
QDBP16PX001CXRD
Two Core
DAEP07AA002CXAB
DAEP07PX002CXAB
DAEP09AA002CXAB
DAEP11AA002CXAB
DAEP11PX002CXAB
DAEP13PX002CXAB
DAEP15PX002CXAB
DAEP17PX002CXAB
DAEP18PX002CXAB

Old
Code

Cores x
Area
mm

Nom
Dim
mm

Gland
Size

Approx
Mass
kg/m

CX/Z

A2

9217
5643
6102
2850
3358
4061
4620
1682

1 x 2.5 *
1x4
1x6
1 x 10
1 x 16
1 x 25
1 x 35
1 x 50

8.6
12.5
13.0
14.2
15.9
18.2
19.4
21.8

20S/16
20S
20S
20S
20
20
20
25

20S
20
25
25
25
25
25
32

7817
6998

1 x 16 + 4 P
1 x 25 + 4 P

15.5 x 22.5
17.6 x 26.4

0.67
0.94

4097
5862
2267
6092
4348
6585
1520
5242
2135

2 x 2.5 *
2 x 2.5
2x4*
2x6*
2x6
2 x 10
2 x 16
2 x 25
2 x 35

8.6 x 12.4
11.6 x 15.2
9.6 x 14.2
10.1 x 15.4
13.0 x 18.0
14.1 x 20.1
15.5 x 22.5
17.6 x 26.4
18.8 x 28.9

0.20
0.28
0.26
0.32
0.42
0.56
0.76
1.10
1.40

0.13
0.24
0.28
0.38
0.51
0.74
0.96
1.22

Note: Conductors are circular stranded.


3.2 mm sheath, unless indicated by * which is 1.8 mm sheath

continued

Page 19

PVC Neutral-Screened
Cables
Cu conductors, PVC insulation, Cu wire neutral screen, Black PVC sheath.
0.6/1 kV. Made to AS/NZS 4961.

Material No.
Two Core Plus Pilot
QDIP15PX002CXAB
Three Core
FAGP07AA003CXRJ
FAGP09AA003CXRJ
FAGP11AA003CXRJ
FAGP13PX003CXRJ
Four Core
HAGP07AA004CXEM
HAGP09AA004CXEM
HAGP11AA004CXEM
HAGP13PX004CXEM

Old
Code

Cores x
Area
mm

Nom
Dia
mm

Gland
Size
CX/Z

A2

Approx
Mass
kg/m

7286

2 x 16 + 4 P

23.4

25

32

0.92

2307
4895
5156
6337

3 x 2.5 *
3x4*
3x6*
3 x 10

13.3
15.1
16.2
21.0

20S
20S
20
25

20
25
25
32

0.26
0.35
0.45
0.74

8291
6562
2811
7823

4 x 2.5 *
4x4*
4x6*
4 x 10

14.2
16.4
17.6
22.6

20S
20
20
25

25
25
25
32

0.31
0.43
0.53
0.88

Core Colours
No. Cores
1
1 (Plus Pilot)
2
2 (Plus Pilot)
3
4

Colour
RD
RD, OG
RD, WH
RD, WH, OG
RD, WH, BU
RD, WH, BU, BK

Note: Conductors are circular stranded.


3.2 mm sheath, unless indicated by * which is 1.8 mm sheath

Page 20

XLPE Neutral-Screened
Cables
Cu conductors, XLPE insulation, Laid up, Cu wire neutral screen, 3.2mm Black PVC
sheath.
0.6/1 kV. Made to AS/NZS 4961.

Material No.
Three Core
FEGP15PX003CXRJ
FEGC16PX003CXRJ
FEGV18PX003CXRJ
FEGV19PX003CXRJ
FEGV20PX003CXRJ
FEGV21PX003CXRJ
Three Core Plus Pilot
QDXP15AA003CXRJ
Four Core
HEGP15PX004CXEM
HEGC17PX004CXEM
HEGV35PX004CXEM
HEGV36PX004CXEM
HEGV20PX004CXEM
HEGV23PX004CXEM

Old
Code

Cores x
Area
mm

Nom
Dia
mm

Gland
Size

Approx
Mass
kg/m

CX/Z

A2

6807
8090
3281
4140
1616
7500

3 x 16 *
3 x 25 ^
3 x 35
3 x 50
3 x 70
3 x 95

22.9
25.4
26.1
29.4
33.5
37.1

25
25
32
32
40
40

32
32
40
40
50S
50S

0.97
1.35
1.72
2.25
3.12
4.18

5687

3 x 16 + 4 P

24.8

25

32

1.05

7626
1559
3176
7610
5203
6214
4119

4 x 16 *
4 x 25 ^
4 x 35
4 x 50
4 x 70
4 x 95
4 x 120

24.7
27.9
29.5
33.0
37.1
40.3
44.8

25
32
32
32
40
50S
50

32
40
40
50S
50S
50
63S

1.13
1.65
2.11
2.78
3.85
5.15
6.55

Core Colours
No. Cores
3
3 (Plus Pilot)
4

Colour
RD, WH, BU
RD, WH, BU, OG
RD, WH, BU, BK

Note: Conductors 35 mm and above are shaped stranded.


* Circular stranded
^ Compact circular stranded

Page 21

Cu Cantols

Cu conductor, XLPE insulation, Black PVC sheath. 0.6/1 kV.


Made to AS/NZS 5000.1.

Material No.
BDBP15AA001CXNA
BDBC17AA001CXNA
BDBC18AA001CXNA
BDBC19AA001CXNA
BDBC20AA001CXNA
BDBC21AA001CXNA
BDBC23AA001CXNA
BDBC44AA001CXNA
BDBC25AA001CXNA
BDBC26AA001CXNA
BDBC47AA001CXNA
BDBC28AA001CXNA
BDBC30AA001CXNA
BDBC32AA001CXNA

Old
Code

Area
mm

5373
4676
8252
8881
2893
5689
2440
4778
2081
2038
5941
2640
2340
4711

16 ^
25 ^
35 ^
50 ^
70 ^
95 ^
120 ^
150 ^
185 ^
240 ^
300 ^
400 ^
500 ^
630 ^

Note: ^ Conductors are compact circular stranded.

Page 22

Nom
Dia
mm
9.8
10.9
12.0
13.3
15.0
16.9
18.6
20.6
22.8
25.5
28.1
31.8
35.7
40.2

Gland
Size
A2 or A2F

20S
20S
20
20
25
25
25
32
32
32
40
50S
50S
50

Approx
Mass
kg/m
0.21
0.31
0.41
0.54
0.75
1.01
1.27
1.55
1.93
2.50
3.11
3.96
4.98
6.40

Cu Vintols

Cu conductor, PVC insulation, PVC sheath. Made to AS/NZS 5000.1.

Material No.

Old
Code

Area
mm

Sheath

BABP09AA001OMNA
BABP15AA001CXNA
BABP15AA001BFNA
BABP15AA001JBNA
BABP15AA001WVNA
BABP16AA001CXNA
BABP16AA001BFNA
BABP16AA001JBNA
BABP16AA001WVNA
BABP18AA001CXNA
BABP18AA001BFNA
BABP18AA001JBNA
BABP18AA001WVNA
BABP20AA001CXNA
BABP20AA001BFNA
BABP20AA001JBNA
BABP20AA001WVNA

2642
5560
3818
4354
8131
8124
4321
7522
6139
3844
9624
8058
8224
1693
7116
8611
9981

4
16
16
16
16
25
25
25
25
35
35
35
35
70
70
70
70

OG
BK
BU
RD
WH
BK
BU
RD
WH
BK
BU
RD
WH
BK
BU
RD
WH

Nom
Dia
mm
7.7
10.0
10.0
10.0
10.0
11.8
11.8
11.8
11.8
13.0
13.0
13.0
13.0
16.4
16.4
16.4
16.4

Approx
Mass
A2 or A2F
kg/m
20S/16
0.10
20
0.23
20
0.23
20
0.23
20
0.23
20
0.35
20
0.35
20
0.35
20
0.35
20
0.45
20
0.45
20
0.45
20
0.45
25
0.82
25
0.82
25
0.82
25
0.82
Gland
Size

Note: Conductors are circular stranded.

Page 23

Al Cantols

Al conductor, XLPE insulation, Black PVC sheath. 0.6/1 kV. Made to AS/NZS 5000.1.

Material No.
Stranded Al Conductor
BDBH20AA001CXNA
BDBH21AA001CXNA
BDBH43AA001CXNA
BDBH44AA001CXNA
BDBH25AA001CXNA
BDBH26AA001CXNA
BDBH27AA001CXNA
BDBH28AA001CXNA
BDBH30AA001CXNA
BDBH32AA001CXNA
BDBH33AA001CXNA

Old
Code

Area
mm

Nom
Dia
mm

A2 or A2F

7763
1879
9269
7344
3244
2974
8270
4468
4658
8554
4864

70 ^
95 ^
120 ^
150 ^
185 ^
240 ^
300 ^
400 ^
500 ^
630 ^
800 ^

15.0
16.9
18.5
20.6
22.8
25.5
27.9
31.3
35.0
39.4
44.7

25
25
25
32
32
32
40
40
50S
50
63S

Note: ^ Conductors are compact circular stranded.

Page 24

Gland
Size

Approx
Mass
kg/m
0.32
0.42
0.51
0.62
0.76
0.97
1.19
1.50
1.87
2.38
3.01

Al Vintols

Al conductor, PVC insulation, PVC sheath. 0.6/1 kV. Made to AS/NZS 5000.1.

Material No.

Old
Code

Area
mm

Sheath

BABA20AA001CXNA
BABA20AA001BFNA
BABA20AA001JBNA
BABA20AA001WVNA
BABA21AA001CXNA
BABA21AA001BFNA
BABA21AA001JBNA
BABA21AA001WVNA
BABA23AA001CXNA
BABA23AA001BFNA
BABA23AA001JBNA
BABA23AA001WVNA
BABA25AA001CXNA
BABA25AA001BFNA
BABA25AA001JBNA
BABA25AA001WVNA
BABH26AA001CXNA
BABH26AA001BFNA
BABH26AA001JBNA
BABH26AA001WVNA

2877
2684
8949
3493
5065
8568
5433
8295
4679
7218
5360
3709
6464
9940
7192
4079
6944
4464
2929
5520

70
70
70
70
95
95
95
95
120
120
120
120
185
185
185
185
240 ^
240 ^
240 ^
240 ^

BK
BU
RD
WH
BK
BU
RD
WH
BK
BU
RD
WH
BK
BU
RD
WH
BK
BU
RD
WH

Nom
Dia
mm
16.4
16.4
16.4
16.4
19.0
19.0
19.0
19.0
20.7
20.7
20.7
20.7
25.1
25.1
25.1
25.1
26.8
26.8
26.8
26.8

Approx
Mass
A2 or A2F
kg/m
25
0.39
25
0.39
25
0.39
25
0.39
25
0.52
25
0.52
25
0.52
25
0.52
32
0.62
32
0.62
32
0.62
32
0.62
32
0.92
32
0.92
32
0.92
32
0.92
40
1.11
40
1.11
40
1.11
40
1.11
Gland
Size

Note: Conductors are circular stranded.


^ Compact circular stranded

Page 25

Single Core
Aluminium Cables
Al conductor, PVC insulation, PVC sheath. 0.6/1 kV. Made to AS/NZS 5000.1.

Material No.

Old
Code

Conductor
Code Name

Area
mm

Sheath

BABA42AA001CXNA
BABA42AA001JBNA
BABA42AA001PPNA
BABA44AA001CXNA
BABA44AA001BFNA
BABA44AA001JBNA
BABA44AA001WVNA
BABA46AA001CXNA
BABA46AA001BFNA
BABA46AA001JBNA
BABA46AA001WVNA
BABA47AA001CXBK
BABA47AA001CXRD

5998
4358
7436
4762
2739
3369
5771
1994
4369
3177
4847
5622
3863

Namu
Namu
Namu
Kutu
Kutu
Kutu
Kutu
Beetle
Beetle
Beetle
Beetle
Weta
Weta

24
24
24
49
49
49
49
106
106
106
106
167
167

BK
RD
VT
BK
BU
RD
WH
BK
BU
RD
WH
BK BK
RD BK

Note: Conductors are circular stranded.

Page 26

Nom
Dia
mm
11.8
11.8
11.8
14.9
14.9
14.9
14.9
19.8
19.8
19.8
19.8
23.6
23.6

Approx
Mass
kg/m
0.19
0.19
0.19
0.32
0.32
0.32
0.32
0.57
0.57
0.57
0.57
0.82
0.82

Al URD Cables

Al conductors, XLPE insulation, Black PVC sheath. 0.6/1 kV. Made to AS/NZS 4026.

Material No.

Old
Code

Cores x Area
mm

XDDH39AA004CXAA
XDDG20AA004CXAA
XDDG21AA004CXAA
XDDG23AA004CXAA
XDDG25AA004CXAA
XDDG26AA004CXAA
XDDG27AA004CXAA

8086
6325
4388
2221
8674
5423
4514

4 x 50 ^
4 x 70
4 x 95
4 x 120
4 x 185
4 x 240
4 x 300

Nom Dia
mm
29.1
31.4
36.0
39.1
48.9
54.6
60.2

Approx
Mass
kg/m
0.94
1.25
1.62
1.99
3.10
3.91
4.87

Note: Conductors are shaped stranded.


^ Compact circular stranded

Page 27

PVC Armoured Mains


Cables
Cu conductors, PVC insulation, Laid up, Extruded bedding, GSW armour,
Black PVC sheath. 0.6/1 kV. Made to AS/NZS 5000.1.

Material No.
Two Core Plus Earth
DNMP07AA002CXHF
DNMP09AA002CXHF
Three Core
FAMP07AA003CXRJ
FAMP09AA003CXRJ
FAMP11AA003CXRJ
FAMP13AA003CXRJ
FAMP15AA003CXRJ
FAMV16AA003CXRJ
Three Core Plus Earth
FNMP07AA003CXRJ
Four Core
HAMP07AA004CXEM
HAMP09AA004CXEM
HAMP11AA004CXEM
Four Core Plus Earth
HNMP09AA004CXEM

Old
Code

Cores x Area
mm

Nom
Dia
mm

CW or E1FW

1993
2518

2 x 2.5 + 2.5 E
2 x 4 + 2.5 E

15.8
17.9

20
20

0.55
0.66

4044
9512
1341
6770
4898
4566

3 x 2.5
3x4
3x6
3 x 10
3 x 16
3 x 25

15.8
18.5
19.7
21.6
23.8
26.0

20
20
20
25
25
32

0.48
0.71
0.83
1.04
1.26
1.77

1558

3 x 2.5 + 2.5 E

17.3

20

0.62

6865
2462
5161

4 x 2.5
4x4
4x6

16.7
19.7
21.1

20
25
25

0.54
0.81
0.96

3288

4 x 4 + 2.5 E

20.5

25

0.87

Core Colours
No. Cores
2
2 (Plus Earth)
3
3 (Plus Earth)
4
4 (Plus Earth)

Colour
RD, BK
RD, BK, GNYE
RD, WH, BU
RD, WH, BU, GNYE
RD, WH, BU, BK
RD, WH, BU, BK, GNYE

Note: Conductors are circular stranded.


Conductors 25 mm and above are shaped stranded.

Page 28

Gland
Size

Approx
Mass
kg/m

XLPE Armoured Mains


Cables
Cu conductors, XLPE insulation, Laid up, Extruded bedding, GSW armour,
Black PVC sheath. 0.6/1 kV. Made to AS/NZS 5000.1.

Material No.
Four Core
HEMP15AA004CXEM
HEMC16AA004CXEM
HEMV35AA004CXEM
HEMV36AA004CXEM
HEMV20AA004CXEM
HEMV24AA004CXEM
HEMV25AA004CXEM

Old
Code

Cores x
Area
mm

Nom
Dia
mm

CW or E1FW

3578
5789
8874
1346
7912
1225
6541

4 x 16 *
4 x 25
4 x 35
4 x 50
4 x 70
4 x 150
4 x 185

25.1
28.3
29.9
33.0
38.3
54.1
57.6

25
32
32
32
40
63S
63S

Gland
Size

Approx
Mass
kg/m
1.39
2.03
2.47
3.11
4.41
8.85
10.55

Core Colours
No. Cores
4

Colour
RD, WH, BU, BK

Note: Conductors 25 mm and above are shaped stranded.


* Circular stranded

Page 29

Control Cables

Cu conductors, PVC insulation (numbered cores), Laid up, Black PVC sheath. 450/750 V.
Made to AS/NZS 5000.3.

Material No.
Conductor Size 1.5 mm
CAHQ05AA002CXWW
EAHQ05AA003CXWW
GAHQ05AA004CXWW
APAQ05AA007CXWW
APAQ05AA012CXWW
APAQ05AA019CXWW
APAQ05AA027CXWW
APAQ05AA037CXWW
Conductor Size 2.5 mm
CAHP07AA002CXWW
EAHP07AA003CXWW
GAHP07AA004CXWW
APAP07AA007CXWW
APAP07AA012CXWW
APAP07AA019CXWW

Page 30

Old
Code

Cores x
Area
mm

Nom
Dia
mm

A2 or A2F

2481
1134
4258
4511
8983
3593
5035
4595

2 x 1.5
3 x 1.5
4 x 1.5
7 x 1.5
12 x 1.5
19 x 1.5
27 x 1.5
37 x 1.5

8.5
8.9
9.7
11.7
15.3
18.1
22.0
24.6

20S
20S
20S
20
25
25
32
32

0.11
0.12
0.15
0.23
0.38
0.56
0.75
0.99

4014
1328
4089
2943
2452
7667

2 x 2.5
3 x 2.5
4 x 2.5
7 x 2.5
12 x 2.5
19 x 2.5

9.6
10.2
11.3
13.3
17.9
21.1

20S
20S
20
25
25
32

0.14
0.17
0.21
0.32
0.55
0.80

Gland
Size

Approx
Mass
kg/m

Armoured Control
Cables
Cu conductors, PVC insulation (numbered cores), Laid up, Extruded bedding,
GSW armour, Black PVC sheath. 0.6/1 kV. Made to BS 6346.

Material No.
Conductor Size 1.5 mm
DAMQ05NG002CXWW
FAMQ05NG003CXWW
HAMQ05NG004CXWW
BPCQ05NG007CXWW
BPCQ05NG012CXWW
BPCQ05NG019CXWW
BPCQ05NG027CXWW
Conductor Size 2.5 mm
FAMP07NG003CXWW
HAMP07NG004CXWW
BPCP07NG007CXWW
BPCP07NG012CXWW
BPCP07NG019CXWW
BPCP07NG027CXWW
BPCP07NG037CXWW

Old
Code

Cores x
Area
mm

Nom
Dia
mm

CW or E1FW

7655
2059
5841
6688
5505
2581
1421

2 x 1.5
3 x 1.5
4 x 1.5
7 x 1.5
12 x 1.5
19 x 1.5
27 x 1.5

12.4
12.9
13.7
15.4
19.7
22.5
27.5

20S
20S
20S
20
25
25
32

0.32
0.33
0.38
0.49
0.85
1.09
1.57

2721
5326
7223
4840
4606
1848
7377

3 x 2.5
4 x 2.5
7 x 2.5
12 x 2.5
19 x 2.5
27 x 2.5
37 x 2.5

14.1
15.0
18.0
22.3
26.6
31.2
34.4

20S
20S
20
25
32
32
40

0.41
0.47
0.73
1.08
1.62
2.05
2.52

Gland
Size

Approx
Mass
kg/m

Page 31

Irrigation Cable
Single Core
Annealed Cu wire, Polypropylene insulation. 0.6/1 kV.

Material No.
Conductor Size 1.5 mm
QADP05AA001AAJB
QADP05AA001AACX
QADP05AA001AAYF
QADP05AA001AABF
Conductor Size 2.5 mm
QADP07AA001AAJB
QADP07AA001AACX
QADP07AA001AAYF
QADP07AA001AAWT

Page 32

Max DC
Approx
Resist.
Mass
@ 20C
kg/m
Ohm/km

Old
Code

Area
mm

Sheath

Nom
Dia
mm

1256
4458
7662
9353

1.5
1.5
1.5
1.5

RD
BK
YE
BU

3.2
3.2
3.2
3.2

13.6
13.6
13.6
13.6

0.02
0.02
0.02
0.02

4779
9281
7362
3322

2.5
2.5
2.5
2.5

RD
BK
YE
WH

4.2
4.2
4.2
4.2

7.41
7.41
7.41
7.41

0.03
0.03
0.03
0.03

Page 33

Flexible Power Cable Selection Criteria

Flexibility

Does not kink

Operating
Temperature

Fixed -40C to +90C

Water Immersion

Submersible to 500m

Physical
Toughness

Durable and resistant to crush


and abrasion

Oils/fuels/ Solvents

Resistant to common oils and


solvents

Acids/ Bases

Resistant to common acid and


alkaline chemicals

Heat Environment

Flame retardant. Tested to IEC


60332.1 and AS/NZS 1660.56

Environmental
Exposure

Resistant to ozone and UV

Electromagnetic
Compatibility

Screened range designed for


applications with EMC
requirements

Lead Free

Pb

Lead Free

Note: Selection criteria graphs are a guide only. For further data, please contact
the Olex Technical Support on 0800 OLEX NZ.

Page 34

Powerlex PVC
Appliance Wires

Flexible tinned Cu conductor, PVC insulation. 0.6/1 kV. Made to AS/NZS 3191.

Material No.
Conductor Size 0.5 mm
BAAR51D1001AABK
BAAR51D1001AABN
BAAR51D1001AABE
BAAR51D1001AAHN
BAAR51D1001AAGY
BAAR51D1001AAOG
BAAR51D1001AARD
BAAR51D1001AAWT
Conductor Size 0.75 mm
BAAR52D1001AABK
BAAR52D1001AABN
BAAR52D1001AABE
BAAR52D1001AAHN
BAAR52D1001AAGY
BAAR52D1001AAOG
BAAR52D1001AAPK
BAAR52D1001AARD
BAAR52D1001AAVL
BAAR52D1001AAWT
Conductor Size 1.0 mm
BAAR53D1001AABK
BAAR53D1001AABN
BAAR53D1001AABE
BAAR53D1001AAHN
BAAR53D1001AAGY
BAAR53D1001AAOG
BAAR53D1001AAPK
BAAR53D1001AARD
BAAR53D1001AAVL
BAAR53D1001AAWT

Approx
Mass
kg/m

Old
Code

Area
mm

Colour

Nom Dia
mm

1643
3498
3447
5005
6351
1410
2168
1205

0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5

BK
BN
BU
GNYE
GY
OG
RD
WH

2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6

0.010
0.010
0.010
0.010
0.010
0.010
0.010
0.010

2501
8078
4494
6514
3650
5871
9299
4593
7518
1496

0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75

BK
BN
BU
GNYE
GY
OG
PK
RD
VT
WH

2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8

0.015
0.015
0.015
0.015
0.015
0.015
0.015
0.015
0.015
0.015

4098
7203
8808
8290
3149
4375
2158
4926
4288
7629

1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0

BK
BN
BU
GNYE
GY
OG
PK
RD
VT
WH

3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0

0.017
0.017
0.017
0.017
0.017
0.017
0.017
0.017
0.017
0.017

continued

Page 35

Powerlex PVC
Appliance Wires

Flexible tinned Cu conductor, PVC insulation. 0.6/1 kV. Made to AS/NZS 3191.

Material No.
Conductor Size 1.5 mm
BAAR54D1001AABK
BAAR54D1001AABN
BAAR54D1001AABE
BAAR54D1001AAHN
BAAR54D1001AAGY
BAAR54D1001AAOG
BAAR54D1001AARD
BAAR54D1001AAVL
BAAR54D1001AAWT
Conductor Size 2.5 mm
BAAR55D1001AABK
BAAR55D1001AABE
BAAR55D1001AAHN
BAAR55D1001AAGY
BAAR55D1001AAOG
BAAR55D1001AARD
BAAR55D1001AAWT
Conductor Size 4 mm
BAAR56D1001AABK
BAAR56D1001AABE
BAAR56D1001AAHN
BAAR56D1001AARD
BAAR56D1001AAWT
Conductor Size 6 mm
BAAR57D1001AABK
BAAR57D1001AABE
BAAR57D1001AAHN
BAAR57D1001AARD
BAAR57D1001AAWT

Page 36

Approx
Mass
kg/m

Old
Code

Area
mm

Colour

Nom Dia
mm

4477
1618
6192
9444
9506
5816
2370
8112
7977

1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5

BK
BN
BU
GNYE
GY
OG
RD
VT
WH

3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2

0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.02

3657
7083
8882
6659
1519
6503
1330

2.5
2.5
2.5
2.5
2.5
2.5
2.5

BK
BU
GNYE
GY
OG
RD
WH

3.8
3.8
3.8
3.8
3.8
3.8
3.8

0.03
0.03
0.03
0.03
0.03
0.03
0.03

1944
4176
3690
2042
2426

4
4
4
4
4

BK
BU
GNYE
RD
WH

4.6
4.6
4.6
4.6
4.6

0.05
0.05
0.05
0.05
0.05

5988
9516
6570
6211
7433

6
6
6
6
6

BK
BU
GNYE
RD
WH

5.6
5.6
5.6
5.6
5.6

0.07
0.07
0.07
0.07
0.07

Powerlex PVC
Flexible Cords
Flexible Cu conductors, PVC insulation, Laid up, PVC sheath. 250/440V.
Made to AS/NZS 3191.

Material No.
Two Core
CAHR01A1002BKAA
CAHR01A1002WTAA
CAHR02A9002BKAA
CAHR02A1002KKAA
CAHR03A1002BKAA
CAHR03A1002KKAA
CAHR04A1002BKAA
CAHR04A1002WTAA
Two Core Plus Earth
EAHR01A1003BKAA
EAHR01A1003WTAA
EAHR02A1003BKAA
EAHR02A1003KKAA
EAHR03A1003BKAA
EAHR03A1003KKAA
EAHR04A1003BKAA
EAHR04A1003KKAA
EAHR05A1003BKAA
EAHR05A1003WTAA
Three Core Plus Earth
GAHR02A1004BKAA
GAHR02A1004WTAA
GAHR03A1004BKDV
GAHR03A1004WTAA
GAHR04A1004BKDV
GAHR04A1004WTAA
GAHR05A1004BKDV
Four Core Plus Earth
GNHR03A1005BKAA
GNHR05A1005BKAA

Old
Code

Cores x
Area
mm

Sheath

Nom
Dia
mm

Gland
Size
A2

Approx
Mass
kg/m

1516
8647
9537
6309
2491
6372
7480
7143

2 x 0.5
2 x 0.5
2 x 0.75
2 x 0.75
2 x 1.0
2 x 1.0
2 x 1.5
2 x 1.5

BK
WH
BK
WH
BK
WH
BK
WH

6.1
6.1
6.3
6.3
6.6
6.6
7.6
7.6

20S/16
20S/16
20S/16
20S/16
20S/16
20S/16
20S
20S

0.04
0.04
0.06
0.06
0.07
0.07
0.09
0.09

5690
1931
2639
8734
9369
8615
5057
8414
9483
4835

2 x 0.5 + E
2 x 0.5 + E
2 x 0.75 + E
2 x 0.75 + E
2 x 1.0 + E
2 x 1.0 + E
2 x 1.5 + E
2 x 1.5 + E
2 x 2.5 + E
2 x 2.5 + E

BK
WH
BK
WH
BK
WH
BK
WH
BK
WH

6.4
6.4
6.6
6.6
7.0
7.0
8.3
8.3
10.1
10.1

20S/16
20S/16
20S/16
20S/16
20S/16
20S/16
20S
20S
20
20

0.04
0.04
0.07
0.07
0.08
0.08
0.11
0.11
0.17
0.17

7320
9500
4429
7718
7006
8651
6261

3 x 0.75 + E
3 x 0.75 + E
3 x 1.0 + E
3 x 1.0 + E
3 x 1.5 + E
3 x 1.5 + E
3 x 2.5 + E

BK
WH
BK
WH
BK
WH
BK

7.2
7.2
7.8
7.8
9.2
9.2
11

20S/16
20S/16
20S
20S
20S
20S
20

0.08
0.08
0.10
0.10
0.14
0.14
0.21

7501
6302

4 x 1.5 + E
4 x 2.5 + E

GY
GY

10.3
12.3

20
20

0.17
0.26

Core Colours
No. Cores
2
2 (Plus Earth)

Colour
BN, BU
BN, BU, GNYE

No. Cores
3 (Plus Earth)
4 (Plus Earth)

Colour
BN, WH, BU, GNYE
BN, WH, BU, BK, GNYE
Page 37

PVC Flexible Trurip

Figure 8 construction, Flexible Cu conductors, PVC insulation. 250/250V.


Made to AS/NZS 3191.

Material No.

Old
Code

Conductor Size 0.75 mm


JSF.75BK1
3899
JSF.75WT1
8051

Page 38

Cores x Area
mm
2 x 0.75
2 x 0.75

Colour

Nom Dim
mm

Approx
Mass
kg/m

BK
WH

3.1 x 5.9
3.1 x 5.9

0.03
0.03

Versolex HD
Single Core
Cu conductors, Flexible XLPE insulation, TPE sheath. 0.6/1 kV.
Designed to AS/NZS 5000.1 and AS/NZS 1995. Cut to length.

Material No.
Single Core
BDSR07AA001OMNA
BDSR07AA001CXNA
BDSX01AA001OMNA
BDSX01AA001CXNA
BDSX01AA001HTNA
BDSX01AA001JBNA
BDSX02AA001OMNA
BDSX02AA001CXNA
BDSX02AA001HTNA
BDSX02AA001JBNA
BDSX03AA001OMNA
BDSX03AA001CXNA
BDSX03AA001HTNA
BDSX03AA001JBNA
BDSX04AA001OMNA
BDSX04AA001CXNA
BDSX04AA001HTNA
BDSX04AA001JBNA
BDSX05AA001OMNA
BDSX05AA001CXNA
BDSX05AA001HTNA
BDSX05AA001JBNA

Old
Code

Area
mm

Sheath

4690
9230
1642
3637
2210
3932
4279
1091
3165
9287
7843
2239
4229
3139
1542
4065
5033
8171
5944
5426
6595
2018

6*
6*
10
10
10
10
16
16
16
16
25
25
25
25
35
35
35
35
50
50
50
50

OG
BK
OG
BK
GNYE
RD
OG
BK
GNYE
RD
OG
BK
GNYE
RD
OG
BK
GNYE
RD
OG
BK
GNYE
RD

Nom
Dia
mm

A2 or A2F

7.4
7.4
8.6
8.6
8.6
8.6
9.8
9.8
9.8
9.8
11.3
11.3
11.3
11.3
12.5
12.5
12.5
12.5
14.1
14.1
14.1
14.1

20S/16
20S/16
20S
20S
20S
20S
20S
20S
20S
20S
20
20
20
20
20
20
20
20
25
25
25
25

Gland
Size

Approx
Mass
kg/m
0.09
0.09
0.14
0.14
0.14
0.14
0.20
0.20
0.20
0.20
0.30
0.30
0.30
0.30
0.39
0.39
0.39
0.39
0.54
0.54
0.54
0.54

* Complies only to AS/NZS 5000.1

continued

Page 39

Versolex HD
Single Core
Cu conductors, Flexible XLPE insulation, TPE sheath. 0.6/1 kV.
Designed to AS/NZS 5000.1 and AS/NZS 1995. Cut to length.

Material No.
Single Core
BDSX06AA001OMNA
BDSX06AA001CXNA
BDSX06AA001HTNA
BDSX06AA001JBNA
BDSX07AA001OMNA
BDSX07AA001CXNA
BDSX07AA001HTNA
BDSX07AA001JBNA
BDSE87AA001OMNA
BDSE87AA001CXNA
BDSE87AA001HTNA
BDSE88AA001OMNA
BDSE88AA001CXNA
BDSE89AA001OMNA
BDSE89AA001HTNA
BDSE90AA001OMNA
BDSE91AA001OMNA
BDSE91AA001CXNA
BDSE92AA001OMNA
BDSE92AA001CXNA
BDSE93AA001OMNA
BDSE94AA001OMNA
BDSE94AA001CXNA

Old
Code

Area
mm

Sheath

2703
7045
7557
1500
6004
8513
8790
3395
8938
9871
9705
3295
9327
1052
3439
3600
6574
6406
9730
5788
9595
8156
3939

70
70
70
70
95
95
95
95
120
120
120
150
150
185
185
240
300 *
300 *
400 *
400 *
500 *
630 *
630 *

OG
BK
GNYE
RD
OG
BK
GNYE
RD
OG
BK
GNYE
OG
BK
OG
GNYE
OG
OG
BK
OG
BK
OG
OG
BK

* Complies only to AS/NZS 5000.1

Page 40

Nom
Dia
mm

A2 or A2F

16.2
16.2
16.2
16.2
18.1
18.1
18.1
18.1
20.6
20.6
20.6
22.5
22.5
24.8
24.8
28.0
30.8
30.8
35.5
35.5
40.0
44.6
44.6

25
25
25
25
25
25
25
25
32
32
32
32
32
32
32
40
40
40
50S
50S
50
63S
63S

Gland
Size

Approx
Mass
kg/m
0.75
0.75
0.75
0.75
0.99
0.99
0.99
0.99
1.25
1.25
1.25
1.51
1.51
1.80
1.80
2.41
2.92
2.92
3.91
3.91
5.00
6.33
6.33

Versolex Multicore
Cords & Cables
Cu conductors, Flexible XLPE insulation, TPE sheath. 0.6/1 kV.
Designed to AS/NZS 3191 (Cords), AS/NZS 5000.1 (Cables). Cut to length.

Material No.

Old
Code

Cores x Area
Sheath
mm

Two Core
CFGR03AA002CXJJ
7355 2 x 1.0
BK
CFGR04AA002CXJJ
1006 2 x 1.5
BK
CFGR05AA002CXJJ
1027 2 x 2.5
BK
Two Core Plus Earth
EFGR03AA003CXKA
1130 2 x 1.0 + 1.0 E
BK
EFGR03AA003OMKA
9576 2 x 1.0 + 1.0 E OG
EFGR04AA003CXKA
1228 2 x 1.5 + 1.5 E
BK
EFGR04AA003OMKA
4491 2 x 1.5 + 1.5 E OG
EFGR05AA003CXKA
1260 2 x 2.5 + 2.5 E
BK
EFGR05AA003OMKA
9653 2 x 2.5 + 2.5 E OG
EFGR06AA003CXKA
1376 2 x 4 + 4 E
BK
EFGR06AA003OMKA
6947 2 x 4 + 4 E
OG
FEHR07AA003CXTD
1430 2 x 6 + 6 E
BK
FEHR07AA003OMTD
9078 2 x 6 + 6 E
OG
Three Core Plus Earth or Three Core Plus Three Earths
GFGR03AA004CXSA
3811 3 x 1.0 + 1.0 E
BK
GFGR03AA004OMSA
1373 3 x 1.0 + 1.0 E OG
GFGR04AA004CXSA
2595 3 x 1.5 + 1.5 E
BK
GFGR04AA004OMSA
4271 3 x 1.5 + 1.5 E OG
GFGR05AA004CXSA
2621 3 x 2.5 + 2.5 E
BK
GFGR05AA004OMSA
3724 3 x 2.5 + 2.5 E OG
GFGR06AA004CXSA
2693 3 x 4 + 4 E
BK
GFGR06AA004OMSA
5015 3 x 4 + 4 E
OG
FTAR07AA003CXRW
2751 3 x 6 + 4.5 SE* BK
FTAR07AA003OMPF
5116 3 x 6 + 4.5 SE* OG

Nom
Dia
mm

A2 or A2F

7.9
8.9
10.2

20S
20S
20S

0.07
0.09
0.13

8.5
8.5
9.5
9.5
10.9
10.9
12.4
12.4
13.4
13.4

20S
20S
20S
20S
20
20
20
20
25
25

0.09
0.09
0.12
0.12
0.16
0.16
0.23
0.23
0.30
0.30

9.4
9.4
10.5
10.5
12.0
12.0
13.6
13.6
15.3
15.3

20S
20S
20S
20S
20
20
25
25
25
25

0.11
0.11
0.14
0.14
0.20
0.20
0.29
0.29
0.38
0.38

Gland
Size

Approx
Mass
kg/m

Core Colours
No. Cores
Colour
2
BN, Lt BU
3 ( 4mm)
BN, Lt BU, GNYE
3 ( 6mm)
RD, BK, GNYE
4 ( 4mm)
BN, WH, Lt BU, GNYE
4 ( 6mm)
RD, NAT, BU, GNYE
* Combined Earth Size
continued
Page 41

Versolex Multicore
Cords & Cables
Cu conductors, Flexible XLPE insulation, Black TPE sheath. 0.6/1 kV.
Designed to AS/NZS 3191 (Cords), AS/NZS 5000.1 (Cables). Cut to length.

Nom
Dia
mm
Three Core Plus Earth or Three Core Plus Three Earths
FTAX01AA003CXRW
3915
3 x 10 + 4.5 SE*
16.6
FTAX02AA003CXRW
3960
3 x 16 + 7.5 SE*
18.9
FTAX03AA003CXRW
4615
3 x 25 + 12 SE*
22.0
FTAX04AA003CXRW
4004
3 x 35 + 18 SE*
24.7
FTAX05AA003CXRW
4041
3 x 50 + 30 SE*
28.4
FTAX06AA003CXRW
4128
3 x 70 + 30 SE*
33.0
FTAX07AA003CXRW
4214
3 x 95 + 48 SE*
36.7
Four Core Plus Earth
BWBR03AA005CXSB
7875
4 x 1.0 + 1.0 E
10.4
BWBR04AA005CXSB
5180
4 x 1.5 + 1.5 E
11.5
BWBR05AA005CXSB
6482
4 x 2.5 + 2.5 E
13.2
BWBR06AA005CXSB
6534
4x4+4E
15.2
BWBR07AA005CXLR
6669
4x6+6E
16.4
BWBX01AA005CXLR
6830
4 x 10 + 10 E
19.1
BWBX02AA005CXLR
7016
4 x 16 + 16 E
22.1
BWBX03AA005CXLR
7227
4 x 25 + 25 E
26.3
BWBX04AA005CXLR
7386
4 x 35 + 35 E
31.1
BWBX05AA005CXLR
9116
4 x 50 + 50 E
34.7
Old
Code

Material No.

Cores x Area
mm

Core Colours
No. Cores
4 ( 4mm)
4 ( 6mm)
5 ( 4mm)
5 ( 6mm)

Colour
BN, WH, Lt BU, GNYE
RD, NAT, BU, GNYE
BN, OG, WH, Lt BU, GNYE
RD, NAT, BU, BK, GNYE

* Combined Earth Size

Page 42

Gland
Size
A2 or A2F

Approx
Mass
kg/m

25
25
32
40
40
50S
50

0.50
0.72
1.08
1.47
2.05
2.79
3.71

20
20
25
25
25
32
32
40
40
50S

0.13
0.17
0.24
0.36
0.45
0.70
1.01
1.52
2.07
2.85

Versolex Braided
Cords & Cables
Cu conductors, Flexible XLPE insulation, TPE bedded, Cu wire braid screen, TPE sheath.
0.6/1 kV. Designed to AS/NZS 3191 (Cords), AS/NZS 5000.1 (Cables). Cut to length.

Old
Code

Material No.

Cores x Area
mm

Sheath

Two Core Plus Earth


EATR04AA003BKKA
1844
2 x 1.5 + 1.5 E
BK
EATR04AA003OGAA
4518
2 x 1.5 + 1.5 E
OG
Three Core Plus Earth or Three Core Plus Three Earths
GETR04AA004CXSA
9895
3 x 1.5 + 1.5 E
BK
GETR04AA004OGSA
1030
3 x 1.5 + 1.5 E
OG
GETR05AA004CXSA
1127
3 x 2.5 + 2.5 E
BK
GETR06AA004CXSA
3230
3x4+4E
BK
FTTR07AA003CXPF
2983
3 x 6 + 4.5 SE*
BK
FTTX01AA003CXPF
5506
3 x 10 + 4.5 SE*
BK
FTTX02AA003CXPF
7310
3 x 16 + 7.5 SE*
BK
FTTX03AA003CXPF
4067
3 x 25 + 12 SE*
BK
FTTX04AA003CXPF
9296
3 x 35 + 18 SE*
BK
FTTX05AA003CXPF
6118
3 x 50 + 30 SE*
BK
FTTX06AA003CXPF
5393
3 x 70 + 30 SE*
BK
FTTX07AA003CXPF
9786
3 x 95 + 48 SE*
BK
Four Core Plus Earth
BWTR06AA005CXLR
4308
4x4+4E
BK
BWTR07AA005CXLR
6740
4x6+6E
BK
BWTX01AA005 CXLR
3684
4 x 10 + 10 E
BK

Nom
Dia
mm

Gland
Size
CX/Z

Approx
Mass
kg/m

11.3
11.3

20S
20S

0.21
0.21

13.4
13.4
14.9
16.4
18.1
19.4
22.1
25.3
27.9
30.1
37.5
41.6

20S
20S
20S
20
25
25
25
32
32
40
50S
50S

0.24
0.24
0.31
0.40
0.41
0.65
0.95
1.33
1.73
2.29
3.25
4.26

18.1
20.1
22.1

20
25
25

0.47
0.58
0.83

Core Colours
No. Cores
3 ( 4mm)
3 ( 6mm)
4 ( 4mm)
4 ( 6mm)
5 ( 4mm)
5 ( 6mm)

Colour
BN, Lt BU, GNYE
RD, BK, GNYE
BN, WH, Lt BU, GNYE
RD, NAT, BU, GNYE
BN, OG, WH, Lt BU, GNYE
RD, NAT, BU, BK, GNYE

* Combined Earth Size

Page 43

Titanex Multicore
(H07RN-F)

Cu conductors to DIN VDE 0295 Class 5, Cross-linked synthetic EPR rubber insulation
and sheath (black), Lead free. 450/750V. Core identification to HD 308 S2.
Pb

Material No.
Two Core
HAR2X2.5
Two Core Plus Earth
HAR3G1
HAR3G1.5
HAR3G2.5
HAR3G4
HAR3G6
HAR3G10
HAR3G16
Three Core Plus Earth
HAR4G1.5
HAR4G2.5
HAR4G4
HAR4G6
HAR4G10
HAR4G16
HAR4G25
HAR4G35
HAR4G70

Cores x Area
mm

6894

2 x 2.5

11.7

0.16

4202
4046
4222
5694
6387
6519
6712

2 x 1.0 + E
2 x 1.5 + E
2 x 2.5 + E
2x4+E
2x6+E
2 x 10 + E
2 x 16 + E

9.5
10.6
12.5
14.5
16.1
21.7
24.7

0.12
0.13
0.20
0.29
0.35
0.66
0.92

1536
3918
1853
6061
2228
2560
3174
8296
9564

3 x 1.5 + E
3 x 2.5 + E
3x4+E
3x6+E
3 x 10 + E
3 x 16 + E
3 x 25 + E
3 x 35 + E
3 x 70 + E

11.7
13.8
16.0
17.9
23.7
27.0
32.8
36.8
48.4

0.17
0.25
0.36
0.44
0.82
1.15
1.70
2.18
3.99

Core Colours
No. Cores
2
3
4

continued
Page 44

Colour
BN, BU
BN, BU, GNYE
BN, BK, GY, GNYE

Nom Dia
mm

Approx
Mass
kg/m

Old
Code

Titanex Multicore
(H07RN-F)

Cu conductors to DIN VDE 0295 Class 5, Cross-linked synthetic EPR rubber insulation
and sheath (black), Lead free. 450/750V. Core identification to HD 308 S2.
Pb

Material No.

Old
Code

Four Core Plus Earth


HAR5G1.5
1063
HAR5G2.5
1092
HAR5G4
1208
HAR5G6
3425
HAR5G10
8476
HAR5G16
1388
HAR5G25
8606
HAR5G35
4591
Six Core Plus Earth
HAR7G1.5
9008
HAR7G2.5
9142
Eleven Core Plus Earth
HAR12G1.5
6075
HAR12G2.5
6202
Seventeen Core Plus Earth
HAR18G1.5
5523
Core Colours
No. Cores
5
6 & above

Cores x Area
mm

Nom Dia
mm

Approx
Mass
kg/m

4 x 1.5 + E
4 x 2.5 + E
4x4+E
4x6+E
4 x 10 + E
4 x 16 + E
4 x 25 + E
4 x 35 + E

12.8
15.2
17.8
19.9
26.0
29.9
36.2
39.4

0.24
0.30
0.45
0.56
1.00
1.43
2.10
2.75

6 x 1.5 + E
6 x 2.5 + E

15.5
17.5

0.38
0.52

11 x 1.5 + E
11 x 2.5 + E

19.3
23.4

0.51
0.76

17 x 1.5 + E

23.5

0.73

Colour
BN, BK, GY, BU, GNYE
GNYE, BK with white numbering

Page 45

Buflex XPrem
Reeling Cable

Cu conductors to IEC 60228 Class 5, XLPE insulation, Double layer anti-twisting


reinforced polyurethane sheath. 0.6/1 kV. Includes central strength member.
Pb

Power
Material No.

Cores x Area
mm

Outer
Diameter mm
Min
Max

Three Core Plus Earth


BXP4G2.5
BXP4G4
BXP4G6
BXP4G10
BXP4G16
BXP3 x 25.3G6
BXP3 x 35.3G6
BXP3 x 50.3G10
BXP3 x 70.3G16

3 x 2.5 + E
3x4+E
3x6+E
3 x 10 + E
3 x 16 + E
3 x 25 + 6SE
3 x 35 + 6SE
3 x 50 + 10SE

10.0
11.5
13.0
15.5
19.5
23.5
27.0
30.0

11.5
13.0
14.5
17.0
21.5
25.5
29.5
32.5

250
400
600
1000
1600
1960
2650
3750

3 x 70 + 16SE

35.0

37.5

5250

3.10

3 x 95 + 16SE
3 x 120 + 25SE
3 x 150 + 25SE
3 x 185 + 35SE
3 x 240 + 50SE
3 x 300 + 50SE

39.0
44.0
49.0
54.5
60.5
68.5

42.0
47.0
52.5
58.5
64.5
72.5

7150
9000
11250
13800
18000
22500

3.89
5.08
6.16
7.68
9.87
12.30

4 x 2.5 + E
4x4+E
4x6+E
4 x 10 + E
4 x 16 + E
4 x 25 + E
4 x 35 + E

11.0
13.0
15.0
18.0
22.0
27.0
31.0

12.5
14.5
16.5
20.0
24.0
29.5
33.5

310
500
750
1250
2000
3100
4350

0.22
0.32
0.45
0.70
1.10
1.55
2.05

(Old Code 9376)

BXP3 x 95.3G16
BXP3 x 120.3G25
BXP3 x 150.3G25
BXP3 x 185.3G35
BXP3 x 240.3G50
BXP3 x 300.3G50
Four Core Plus Earth
BXP5G2.5
BXP5G4
BXP5G6
BXP5G10
BXP5G16
BXP5G25
BXP5G35
Core Colours
No. Cores
4
5
continued
Page 46

Colour
BN, BK, GY, GNYE
BN, BK, GY, BU, GNYE

Max Approx
Tensile
Mass
Load (N)
kg/m
0.18
0.26
0.37
0.58
0.92
1.24
1.64
2.24

Buflex XPrem
Reeling Cable

Cu conductors to IEC 60228 Class 5, XLPE insulation, Double layer anti-twisting


reinforced polyurethane sheath. 0.6/1 kV. Includes central strength member.

Control
Material No.
Conductor Size 1.5 mm
BXP7 x 1.5
BXP12 x 1.5
BXP18 x 1.5
BXP24 x 1.5
BXP36 x 1.5
Conductor Size 2.5 mm
BXP7 x 2.5
BXP12 x 2.5
BXP18 x 2.5
BXP24 x 2.5
BXP36 x 2.5
BXP42 x 2.5

Cores x Area
mm

Outer
Diameter mm
Min
Max

7 x 1.5
12 x 1.5
18 x 1.5
24 x 1.5
36 x 1.5

11.5
16.0
16.0
19.0
22.0

13.0
17.5
17.5
21.5
24.0

260
450
670
900
1350

0.21
0.33
0.41
0.68
0.90

7 x 2.5
12 x 2.5
18 x 2.5
24 x 2.5
36 x 2.5
42 x 2.5

12.5
18.5
18.5
22.5
25.0
27.0

14.0
20.5
20.5
24.5
28.0
29.5

430
750
1120
1500
2250
2620

0.30
0.61
0.74
1.05
1.43
1.50

Max Approx
Tensile
Mass
Load (N)
kg/m

Core Colours
No. Cores
7 & above

Colour
WH with black numbering

Page 47

Varolex Variable
Speed Drive Cables
Fixed Cu conductors, XLPE insulation, Laid up with three earths disposed in the interstices
of the power cores, PVC bedding, Collective Cu tape screen, Black PVC sheath. 0.6/1 kV.
Made to AS/NZS 5000.1.

Material No.
FTDP07AA003CXRJ
FTDP09AA003CXRJ
FTDP11AA003CXRJ
FTDP13AA003CXRJ
FTDP15AA003CXRJ
FTDC17AA003CXRJ
FTDC18AA003CXRJ
FTDC19AA003CXRJ
FTDC20AA003CXRJ
FTDC21AA003CXRJ
FTDC43AA003CXRJ
FTDP24AA003CXRJ
FTDP25AA003CXRJ
FTDC46AA003CXRJ

Old
Code

Cores x Area
mm

6175
4005
5206
6307
1196
7408
8451
2200
4466
9651
3569
6548
5985
4015

3 x 2.5 + 2.5 E *
3 x 4 + 4.5 SE
3 x 6 + 4.5 SE
3 x 10 + 4.5 SE
3 x 16 + 7.5 SE
3 x 25 + 12 SE
3 x 35 + 18 SE
3 x 50 + 30 SE
3 x 70 + 30 SE
3 x 95 + 48 SE
3 x 120 + 48 SE
3 x 150 + 75 SE
3 x 185 + 75 SE
3 x 240 + 105 SE

(combined earth size)

Nom
Dia
mm
14.6
16.6
17.5
18.5
20.6
22.8
25.6
28.8
32.0
38.0
43.2
47.3
52.0
58.9

Gland
Size
(Gland Type)

25 (VSD)
25 (VSD)
25 (A4)
25 (A4)
32 (A4)
32 (A4)
32 (A4)
40 (A4)
50S (A4)
50 (A4)
50 (A4)
63S (A4)
63 (A4)
75S (A4)

Approx
Mass
kg/m
0.32
0.44
0.51
0.62
0.86
1.21
1.60
2.11
2.77
3.90
4.67
5.85
7.11
9.18

Core Colours
No. Cores
4

Colour
RD, WH, BU, GNYE

Note: Conductors are circular stranded, sizes 16 mm and above are compact circular
stranded.
* Single Earth

Page 48

PVC Flexible Control

Flexible PVC insulation, Grey PVC sheath to DIN VDE 0281 part 1 and HD 21.1.
PVC self extinguishing and flame retardant. 300/500V. Cu conductors.
Flexing -5C to 80C, fixed -40C to 80C. Min. bending radius 7.5 x cable o.d.

Material No.

Old
Code

Conductor Size 0.5 mm


CC4G0.5
1045
CC5G0.5
1070
CC7G0.5
1104
CC8G0.75
8449
CC12G0.5
1135
CC18G0.5
2373
CC25G0.5
2420
Conductor Size 0.75 mm
CC3G0.75
3034
CC4G0.75
3162
CC5G0.75
3233
CC7G0.75
3260
CC12G0.75
3307
CC18G0.75
3372
CC42G0.75
1897
Conductor Size 1.0 mm
CC3G1
4295
CC4G1
4349
CC5G1
4435
CC7G1
5554
CC12G1
5688
CC18G1
5850
CC25G1
5916

Cores x Area
mm

Nom Dia
mm

Approx
Mass
kg/m

3 x 0.5 + E
4 x 0.5 + E
6 x 0.5 + E
7 x 0.5 + E
11 x 0.5 + E
17 x 0.5 + E
24 x 0.5 + E

5.7
6.2
7.4
8.0
9.1
10.7
13.0

0.06
0.07
0.08
0.10
0.14
0.20
0.27

2 x 0.75 + E
3 x 0.75 + E
4 x 0.75 + E
6 x 0.75 + E
11 x 0.75 + E
17 x 0.75 + E
41 x 0.75 + E

5.5
6.2
6.8
8.1
9.9
11.9
17.6

0.05
0.07
0.08
0.11
0.18
0.26
0.61

2 x 1.0 + E
3 x 1.0 + E
4 x 1.0 + E
6 x 1.0 + E
11 x 1.0 + E
17 x 1.0 + E
24 x 1.0 + E

6.0
6.6
7.2
8.6
10.7
12.7
15.6

0.07
0.09
0.10
0.14
0.23
0.34
0.49

Note: Black cores with continuous white numbering according to DIN VDE 0293, plus
green/yellow earth. Not suitable for open air applications.
continued
Page 49

PVC Flexible Control

Flexible PVC insulation, Grey PVC sheath to DIN VDE 0281 part 1 and HD 21.1.
PVC self extinguishing and flame retardant. 300/500V. Cu conductors.
Flexing -5C to 80C, fixed -40C to 80C. Min. bending radius 7.5 x cable o.d.

Material No.
Conductor Size 1.5 mm
CC3G1.5
CC4G1.5
CC5G1.5
CC7G1.5
CC12G1.5
CC14G1.5
CC18G1.5
CC25G1.5
Conductor Size 2.5 mm
CC3G2.5
CC5G2.5
CC7G2.5
CC12G2.5
Conductor Size 6 mm
CC4G6

Nom Dia
mm

Approx
Mass
kg/m

Old
Code

Cores x Area
mm

6143
6220
6327
5186
5410
2338
3703
6687

2 x 1.5 + E
3 x 1.5 + E
4 x 1.5 + E
6 x 1.5 + E
11 x 1.5 + E
13 x 1.5 + E
17 x 1.5 + E
24 x 1.5 + E

6.7
7.3
8.2
9.8
12.1
12.9
14.5
17.8

0.09
0.11
0.13
0.18
0.31
0.35
0.44
0.62

4305
7880
7651
8170

2 x 2.5 + E
4 x 2.5 + E
6 x 2.5 + E
11 x 2.5 + E

8.3
10.2
12.1
15.2

0.15
0.22
0.31
0.50

1385

3x6+E

13.0

0.42

Note: Black cores with continuous white numbering according to DIN VDE 0293, plus
green/yellow earth. Not suitable for open air applications.

Page 50

PVC-EMC
Flexible Control

Flexible PVC insulation, Tinned Cu braid, Transparent PVC sheath. 300/500V.


Cu conductors to DIN VDE 0295 class 5 and IEC 60228 class 5.
Flexing -5C to 80C, fixed -40C to 80C. Min. bending radius 10 x cable o.d.

Material No.

Old
Code

Conductor Size 0.5 mm


CY3G0.5
6013
CY4G0.5
7128
CY5G0.5
5642
Conductor Size 0.75 mm
CY3G0.75
8840
CY4G0.75
5677
CY5G0.75
7503
CY12G0.75
9557
Conductor Size 1.0 mm
CY4G1
6188
CY5G1
6771
CY12G1
6122
Conductor Size 1.5 mm
CY3G1.5
1678
CY4G1.5
2856
CY7G1.5
9702
Conductor Size 2.5 mm
CY3G2.5
4157
CY4G2.5
5061
CY7G2.5
3180
Conductor Size 4 mm
CY5G4
3048

Cores x Area
mm

Nom Dia
mm

Approx
Mass
kg/m

2 x 0.5 + E
3 x 0.5 + E
4 x 0.5 + E

7.2
7.8
8.3

0.08
0.09
0.11

2 x 0.75 + E
3 x 0.75 + E
4 x 0.75 + E
11 x 0.75 + E

7.8
8.3
9.1
12.5

0.10
0.11
0.13
0.29

3 x 1.0 + E
4 x 1.0 + E
11 x 1.0 + E

8.9
9.5
13.1

0.15
0.17
0.35

2 x 1.5 + E
3 x 1.5 + E
6 x 1.5 + E

9.0
9.6
12.1

0.15
0.17
0.30

2 x 2.5 + E
3 x 2.5 + E
6 x 2.5 + E

10.7
11.4
15.0

0.22
0.27
0.41

4 x 4.0 + E

14.8

0.50

Note: Black cores with continuous white numbering according to DIN VDE 0293, plus
green/yellow earth. Not suitable for open air applications
Page 51

Silicone Single Core

Flexible tinned Cu conductors, Silicone insulation, Halogen free to IEC 60754-2. 500V.
Fixed -60C to 180C. Min. bending radius 15 x cable o.d.

Material No.

Old
Code

Cores x Area
mm

SIF23501A1
SIF23502A1
SIF2361.5BK
SIF2361.5RDA1
SIF23701A1
SIF2372.5RD
SIF2384BKA1
SIF2384RDA1
SIF2396BKA1
SIF2396RDA1

7865
7547
1588
7483
4883
5311
5492
7066
6853
2187

1 x 1.0
1 x 1.0
1 x 1.5
1 x 1.5
1 x 2.5
1 x 2.5
1x4
1x4
1x6
1x6

Page 52

Colour

Nom Dia
mm

BK
RD
BK
RD
BK
RD
BK
RD
BK
RD

2.5
2.5
2.8
2.8
3.4
3.4
4.2
4.2
5.2
5.2

Approx
Mass
kg/m
0.01
0.01
0.02
0.02
0.03
0.03
0.05
0.05
0.07
0.07

Silicone Multicore

Tinned Cu conductors, Silicone insulation, Brown Silicone sheath, Halogen free to IEC
60754-2. 300/500V. Fixed -60C to 180C (peak 220C).
Min. bending radius 7.5 x cable o.d.

Material No.

Old
Code

Conductor Size 1.0 mm


SF2X1
6571
SF3G1
2786
SF4G1
2270
SF7G1
8854
SF12G1
3058
Conductor Size 1.5 mm
SF2X1.5
9502
SF3G1.5
6607
SF4G1.5
7396
SF5G1.5
7298
SF12G1.5
8288
Conductor Size 2.5 mm
SF3G2.5
4409
SF4G2.5
8829
SF5G2.5
6181
Conductor Size 6 mm
SF4G6
9517
Conductor Size 10 mm
SF4G10
6338

Cores x Area
mm

Nom Dia
mm

Approx
Mass
kg/m

2 x 1.0
2 x 1.0 + E
3 x 1.0 + E
6 x 1.0 + E
11 x 1.0 + E

6.6
7.4
8.0
9.5
11.5

0.06
0.08
0.09
0.14
0.23

2 x 1.5
2 x 1.5 + E
3 x 1.5 + E
4 x 1.5 + E
11 x 1.5 + E

7.6
8.0
8.8
9.6
14.6

0.08
0.10
0.12
0.15
0.31

2 x 2.5 + E
3 x 2.5 + E
4 x 2.5 + E

9.7
10.6
11.6

0.15
0.19
0.23

3 x 6.0 + E

16.2

0.44

3 x 10 + E

20.4

0.71

Core Colours
No. Cores
2
3
4
5
6 & above

Colour
BN, BU
BN, BU, GNYE
BN, BU, BK, GNYE
BN, BU, BK, GY, GNYE
BK with white numbering

Page 53

Instrolex
Instrumentation Cable
Plain annealed Cu conductors, V-90 RP PVC insulation, Twisted pairs, Al/Polyester
screen, Stranded tinned annealed Cu drain wire, Rip cord, 5V-90 RP Black PVC sheath.

Overall Screen (CS)


Material No.

Old
Code

Conductor Size 0.5 mm


IEB183AA001CXAA
2946
IEC183AA002CXAA
7908
IEC183AA004CXAA
1673
IEC183AA006CXAA
4881
IEC183AA008CXAA
9131
IEC183AA010CXAA
4512
IEC183AA012CXAA
8982
IEC183AA016CXAA
3592
IEC183AA020CXAA
5034
IEC183AA024CXAA
4013
IEC183AA036CXAA
9183
Conductor Size 1.5 mm
IEB184AA001CXAA
1995
IEC184AA002CXAA
9212
IEC184AA004CXAA
5210
IEC184AA006CXAA
1788
IEC184AA008CXAA
7726
IEC184AA010CXAA
4230
IEC184AA012CXAA
1734
IEC184AA036CXAA
3850
IGB184AA001CXAA
7130

Area
mm

No.
Pairs

Nom
Dia
mm

A2 or A2F

0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5

1
2
4
6
8
10
12
16
20
24
36

5.2
7.8
8.4
10.0
11.2
12.5
13.4
15.1
16.8
18.1
22.0

20S/16
20S
20S
20S
20
20
25
25
25
25
32

0.04
0.06
0.09
0.13
0.17
0.21
0.24
0.31
0.38
0.45
0.66

1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5

1
2
4
6
8
10
12
36
1 Triple

6.6
9.9
10.9
13.0
14.6
16.3
17.5
29.2
6.9

20S/16
20
20
20
25
25
25
40
20S/16

0.06
0.11
0.18
0.26
0.33
0.41
0.48
1.37
0.08

0.5 mm is equalivalent to 7/0.30 and 20 AWG


1.5 mm is equalivalent to 7/0.50 and 16 AWG
* Also available as intrinsically safe blue sheathed Instrolex

Page 54

Gland
Size

Approx
Mass
kg/m

*
*

*
*
*
*
*
*

Instrolex
Instrumentation Cable
Plain annealed Cu conductors, V-90 RP PVC insulation, Twisted pairs, Al/Polyester
screen, Stranded tinned annealed Cu drain wire, Rip cord, 5V-90 RP Black PVC sheath.

Individual and Overall Screen (ESCS)


Material No.

Old
Code

Conductor Size 0.5 mm


IED183AA002CXAA
7380
IED183AA004CXAA
2522
IED183AA006CXAA
9883
IED183AA008CXAA
8877
IED183AA010CXAA
3095
IED183AA012CXAA
5222
IED183AA016CXAA
3482
IED183AA024CXAA
3445
Conductor Size 1.5 mm
IED184AA002CXAA
3643
IED184AA004CXAA
7478
IED184AA012CXAA
1309
IED184AA016CXAA
7905

Area
mm

No.
Pairs

Nom
Dia
mm

A2 or A2F

0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5

2
4
6
8
10
12
16
24

8.1
10.4
12.2
13.9
14.6
16.0
18.0
21.9

20S
20
20
25
25
25
25
32

0.07
0.12
0.17
0.22
0.26
0.31
0.39
0.57

1.5
1.5
1.5
1.5

2
4
12
16

10.3
13.4
20.9
23.9

20
25
32
32

0.13
0.22
0.57
0.75

Gland
Size

Approx
Mass
kg/m

0.5 mm is equalivalent to 7/0.30 and 20 AWG


1.5 mm is equalivalent to 7/0.50 and 16 AWG
* Also available as intrinsically safe blue sheathed Instrolex

Page 55

Instrolex
Instrumentation Cable
Plain annealed Cu conductors, V-90 RP PVC insulation, Twisted pairs, Al/Polyester
screen, Stranded tinned annealed Cu drain wire, Rip cord, PVC bedding, Steel wire
armour, 5V-90 RP Black PVC sheath.

Overall Screen, Steel Wire Armour (CS SWA)


Material No.

Old
Code

Conductor Size 0.5 mm


IEG183AA002CXAA
8731
IEG183AA004CXAA
1655
IEG183AA006CXAA
9291
IEG183AA008CXAA
5519
IEG183AA010CXAA
6704
IEG183AA012CXAA
4463
IEG183AA016CXAA
5512
IEG183AA024CXAA
1497
Conductor Size 1.5 mm
IEF184AA001CXAA
3610
IEG184AA002CXAA
7991
IEG184AA006CXAA
2976
IGF184AA001CXAA
5213

Area
mm

No.
Pairs

Nom
Dia
mm

Approx
Mass
CW or E1FW
kg/m

0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5

2
4
6
8
10
12
16
24

11.4
12.0
13.6
14.8
16.1
17.0
18.9
22.7

20S
20S
20S
20S
20
20
25
32

0.25
0.28
0.36
0.42
0.48
0.54
0.65
0.97

1.5
1.5
1.5
1.5

1
2
6
1 Triple

10.2
13.6
16.6
10.6

20S/16
20S
20
20S/16

0.22
0.34
0.55
0.24

Gland
Size

Individual and Overall Screen, Steel Wire Armour (ESCS SWA)


Material No.

Old
Code

Conductor Size 0.5 mm


IEH183AA002CXAA
3144
IEH183AA004CXAA
2185
IEH183AA006CXAA
1292
IEH183AA008CXAA
2791
IEH183AA010CXAA
7560
IEH183AA012CXAA
3572
IEH183AA024CXAA
3040
IGH183AA012CXAA
9632

Area
mm

No.
Pairs

Nom
Dia
mm

CW or E1FW

0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5

2
4
6
8
10
12
24
12 Triple

11.7
14.0
16.0
17.5
18.2
19.6
26.2
21.3

20S
20S
20
20
25
25
32
32

0.5 mm is equalivalent to 7/0.30 and 20 AWG


1.5 mm is equalivalent to 7/0.50 and 16 AWG
* Also available as intrinsically safe blue sheathed Instrolex
Page 56

Gland
Size

Approx
Mass
kg/m
0.26
0.35
0.45
0.52
0.58
0.66
1.18
0.88

*
*

PVC Flat Crane Cable

PVC insulation, Black PVC sheath. 450/750V.

Material No.
Power
FC4G4
FC4G6
FC4G10
FC4G16
FC4G25
FC4G35
FC5G6
FC7G4
Control
FC4G1.5
FC4G2.5
FC5G1.5
FC5G2.5
FC8G1.5
FC8G2.5
FC12G1.5
FC12G2.5
FC16G1.5
FC18G1.0
FC24G0.75

Old
Code

Cores x Area
mm

Outer Dim
mm

Approx
Mass
kg/m

6648
7828

3x4+E
3x6+E
3 x 10 + E
3 x 16 + E
3 x 25 + E
3 x 35 + E
4x6+E
6x4+E

6.5 x 21.0
7.0 x 23.0
9.0 x 29.0
11.0 x 37.0
13.5 x 46.0
14.8 x 51.0
7.0 x 28.0
6.5 x 37.0

0.30
0.39
0.62
0.99
1.55
2.03
0.48
0.55

5355
1171
8444
2254
9541

3 x 1.5 + E
3 x 2.5 + E
4 x 1.5 + E
4 x 2.5 + E
7 x 1.5 + E
7 x 2.5 + E
11 x 1.5 + E
11 x 2.5 + E
15 x 1.5 + E
17 x 1.0 + E
23 x 0.75 + E

5.0 x 15.0
6.0 x 18.5
5.0 x 18.0
6.0 x 22.0
5.0 x 29.0
6.0 x 35.0
5.0 x 40.5
6.0 x 50.5
5.0 x 54.0
4.5 x 52.8
4.3 x 65.6

0.15
0.21
0.18
0.26
0.30
0.41
0.42
0.62
0.56
0.44
0.51

Page 57

Notes

Page 58

Page 59

Security Cable

Unscreened
Stranded Cu conductor, PVC insulation, Cores laid up, White PVC sheath.

Material No.

Old
Code

No.
Cores

Conductor Size 0.22 mm (7/0.20mm)


JSC.2WT4C1
1794
4
JSC.2WT6C1
6642
6
Conductor Size 0.44 mm (14/0.20mm)
JSC.5WT4C1
6599
4
JSC.5WT6C*
5252
6
JSC.5WT8C*
2613
8

Nom
Dia
mm

Max DC
Resist.
@ 20C
Ohms/km

Pack
Size *

Approx
Mass
kg/m

3.6
4.9

86.5
86.5

100m
100m

0.01
0.03

4.7
5.6
6.5

44.5
44.5
44.5

100m
A, B
A, D

0.03
0.05
0.06

Screened
Stranded Cu conductor, PVC insulation, Cores laid up, Aluminium foil overall tape,
Stranded tinned annealed Cu drain wire, Grey PVC sheath.

Material No.

Old
Code

No.
Cores

Conductor Size 0.44 mm (14/0.20mm)


JSS.5GY7C1
3729
7

Nom
Dia
mm

Max DC
Resist.
@ 20C
Ohms/km

Pack
Size

Approx
Mass
kg/m

6.8

44.5

100m

0.07

Core Colours
No. Cores
4
6
7
8

Colour
RD, BU, WH, BK
RD, BU, WH, BK, YW, GN
RD, BU, WH, BK, OG, YW, GN
RD, BU, WH, BK, VT, YW, GN, BN

* Pack Size
Reference
A
B
D
E
F
Page 60

Size
100m Spool
250m Spool
500m Spool
200m Box
300m Box

Code
1
250
5
B20
B30

Audiolex

High Definition (HD) Vision


RG59 coaxial cable with braid (95% coverage). 3 and 6 core includes 4 x 0.2mm PVC
control cores, White PVC sheath.

Material No.

Old
Code

JPLAS3PREMA1
JPLAS6PREMA1

1860
4776

Control
Coaxial
Core Nom Dia
No.
Nom Dia
Nom Dia mm
Cores
mm
mm
3
4.5
1.35
12.0
6
4.5
1.35
16.0

Pack
Size

Approx
Mass
kg/m

100m
100m

0.16
0.29

Oxygen Free Copper (OFC) Audio


Stranded Cu conductor, PVC insulation, Violet PVC sheath.

Material No.
Two Core
JTS1.2VT2CA3
JTS2.5VT2C*
JTS4VT2CA1
Four Core
JTS1.2VT4CA3
JTS2.5VT4CA1
JTS4VT4CA1

Old
Code

Cores
x Area
mm

Stranding
No./mm

Nom
Dia
mm

Nom Con.
Resist.
@ 20C
Ohm/km

Pack
Size *

Approx
Mass
kg/m

5472
1534
3766

2 x 1.2
2 x 2.5
2 x 4.0

70/0.15
140/0.15
225/0.15

6.5
8.5
11.0

17.2
7.8
5.4

300m
A, C
100m

5.8
10.0
16.0

2978
6527
3760

4 x 1.2
4 x 2.5
4 x 4.0

70/0.15
140/0.15
225/0.15

6.9
9.9
12.4

17.2
7.8
5.4

300m
100m
100m

8.6
17.0
27.0

* Pack Size
Reference
A
C

Size
100m Spool
300m Spool

Code
A1
A3

Page 61

Figure 8
Speaker Trurip
Flexible Cu conductors, PVC insulation.

Standard
Material No.

Old
Code

Cores
x Area
mm

Colour

Conductor Size 0.50 mm (14/0.20mm)


JSF.5WTBK1
6121
2 x 0.5
BK/WH
JSF.5GYBK*
1878
2 x 0.5
GY/BK
Conductor Size 0.75 mm (24/0.20mm)
JSF.75BKWT*
7555
2 x 0.75
BK/WH
JSF.75BEWT5
8602
2 x 0.75
BU/WH
JSF.75RDBK*
3221
2 x 0.75
RD/BK
JSF.75CL1
8056
2 x 0.75
Clear
JSF.75BK1
3899
2 x 0.75
BK
JSF.75WT1
8051
2 x 0.75
WH

Nom
Dim
mm

Max DC
Resist.
@ 20C
Ohms/km

Pack
Size *

Approx
Mass
kg/m

1.8 x 4.3
1.8 x 4.3

44.5
44.5

100m
A, D

0.02
0.02

2.9 x 5.9
2.9 x 5.9
2.9 x 5.9
2.9 x 5.9
2.9 x 5.9
2.9 x 5.9

26
26
26
26
26
26

B, D
500m
A, B, D
100m
100m
100m

0.03
0.03
0.03
0.03
0.03
0.03

Oxygen Free Copper


Material No.

Old
Code

Cores
x Area
mm

JSF1.0CL
JSF2.0CL*
JSF2.6CL1

6288
3865
6563

2 x 1.0
2 x 2.0
2 x 2.6

Material No.
JSF1.0CL
JSF2.0CL*
JSF2.6CL1

Colour

Clear 2.6 x 5.7


Clear 3.4 x 7.0
Clear/RD 4.5 x 9.0

Stranding
No./mm
91/0.12
64/0.20
84/0.20

* Pack Size
Reference
A
B
D

Page 62

Size
100m Spool
250m Spool
500m Spool

Nom
Dim
mm

Code
1
250
5

Max DC
Resist.
@ 20C
Ohms/km

Pack
Size

Approx
Mass
kg/m

17.2
10.9
7.4

100m
A, D
100m

0.03
0.05
0.08

Coaxial Cable

Tinned or plain Cu conductor, solid PE insulation, tinned Cu wire braid,


Black PVC sheath.

Coaxial 50 0hm
Material No.

Old
Code

Type

Stranding
No./mm

Nom Dia
mm

Pack
Size

JBCRG58CUMIL1
JBCRG213MIL1

8896
2783

RG58
RG213

19/0.18 T/C
7/0.7 B/C

5.0
10.3

100m
100m

Approx
Mass
kg/m
0.04
0.16

Electrical Characteristics

Material No.

Shielding

Dielectric

Max DC
Resist.
@ 20C
Ohm/km

Nom Cap
pF/m

Nom
Velocity
Prop %

JBCRG58CUMIL1
JBCRG213MIL1

95% T/C
97% B/C

Solid PE
Solid PE

32.6
6.53

101
101

66
66

continued

Page 63

Coaxial Cable

Plain annealed Cu conductor, PE insulation, Cu wire braid (either 85% or 95% coverage),
Black PVC sheath.

Coaxial 75 0hm
Material No.

Old
Code

Nom
Dia
mm

Pack
Size *

Approx
Mass
kg/m

1/0.60
1/0.60

6.1
6.2

A, B, D
100m

0.05
0.06

1/1.0

7.5

A, F

0.05

Stranding
No./mm

Type

RG59 Closed Circuit Television (CCTV)


JBCRG59BUCCTV*
3179
RG59
JBCRG59PREMA1
8234
RG59
RG6 TV Antenna / TV Lead-in
JBCRG6QUAD*
5921
RG6
Electrical Characteristics

Material No.
JBCRG59BUCCTV
JBCRG59PREMA1
JBCRG6QUAD

Shielding

Dielectric

86% B/C Braid


Solid PE
95% B/C Braid
Solid PE
Quad Shield
Al Foil, 60% Braid Foamed PE
Al Foil, 40% Braid

* Pack Size
Reference
A
B
D
F

Page 64

Size
100m Spool
250m Spool
500m Spool
300m Box

Code
1
25
5
B30

Max DC
Resist.
@ 20C
Ohm/km

Nom Cap
pF/m

Nom
Velocity
Prop %

62.2
62.2

67
67

66
66

100

53

84

Composite Coaxial
& Control Core
RG59 coaxial with braid (85% coverage) with two 24/0.20mm power cores,
PVC insulation positioned either side of coaxial, Black PVC sheath. 250V/250V.

Material No.

Old
Code

Nom
Dim
mm

Nom Ins
Thickness
mm

JCOMP85*

1231

7.8 x 13

0.75

Max DC
Resist.
@ 20C
Ohms/km
26

Pack
Size *

Approx
Mass
kg/m

A, B, D

0.12

* Pack Size
Reference
A
B
D

Size
100m Spool
250m Spool
500m Spool

Code
A1
BA25
BA5

Page 65

LAN

Cu conductor, Polyolefin insulation, Twisted pairs, PVC sheath.


Compatible with RJ type connector.

Material No.

Old
Code

Category 5E (Solid)
CAT5E04RDB
4030
CAT5E04YWB
2004
Category 5E (Underground)
JCAT5EFPA3
2697
Category 5E (Screened)
JCAT5ESCRB30 1188
Category 6
JCAT604GYB30 6626

Description
Category 5E (Solid)
Category 5E (Underground)
Category 5E (Screened)
Category 6

Page 66

Area
mm

Sheath

Nom
Dia
mm

Pack
Size

4
4

0.22
0.22

RD
YE

5.3
5.3

300m Box
300m Box

0.03
0.03

0.22

BK

5.7

300m Spool

0.03

0.22

GY

5.3

300m Box

0.05

0.22

GY

6.3

300m Box

0.04

No.
Pairs

Stranding
No./mm
1/0.50
1/0.50
1/0.50
1/0.50

Max DC
Resist.
@ 20C
Ohm/km

93.8
93.8
93.8
93.8

Approx
Mass
kg/m

Nom Imped. Mutual Cap


Ohms
pF/m
100
100
100
100

51
51
50
51

Optical Fibre

Nylon Underground

Material No.

Single Mode (OS1)


FIB06SMJN
2436
FIB12SMJN
9921
FIB24SMJN
9428
Multi Mode (OM1)
FIB06MMJN
3163
FIB08MMJN
2184
FIB12MMJN
1084
FIB24MMJN
7078

Max
Min Bending
Pulling
Radius mm
Tension During
Installed
Installation
kN

No.
Fibres

Nom
Dia
mm

10/125 m SM
10/125 m SM
10/125 m SM

6
12
24

8.5
8.5
11.0

1.5
1.5
2.3

170
170
220

85
85
110

62.5/125 m MM
62.5/125 m MM
62.5/125 m MM
62.5/125 m MM

6
8
12
24

8.5
8.5
8.5
8.5

1.5
1.5
1.5
1.5

170
170
170
170

85
85
85
85

Old
Des.
Code

Page 67

Telephone Internal

Solid Cu conductor, PVC insulation, Cream PVC sheath.

Material No.

Old
Code

No.
Pairs

Wire Size
mm

Nom Dia
mm

Pack
Size

TINT002AA
TINT025A9
TINT002B30

3309
5464
2087

2
25
1 Quad

0.5
0.5
0.5

4.1
12.8
3.3

100m
Bulk
300m Box

Approx
Mass
kg/m
0.01
0.18
TBC

Pair Colours
Pair No.
1
2
3
4
5
6
7
8
9
10
11
12
13

Wire 1
WH
WH
WH
WH
WH
RD
RD
RD
RD
RD
BK
BK
BK

Wire 2
BU
OG
GN
BN
GY
BU
OG
GN
BN
GY
BU
OG
GN

Pair No.
14
15
16
17
18
19
20
21
22
23
24
25

Note: TINT002 colour sequence is WH/BU, RD/BK.

Page 68

Wire 1
BK
BK
YE
YE
YE
YE
YE
PU
PU
PU
PU
PU

Wire 2
BN
GY
BU
OG
GN
BN
GY
BU
OG
GN
BN
GY

Telephone External

Aerial
Solid Cu conductor, Polyethylene insulation, Twisted unit pair, Black polyethylene sheath
incorporating a galvanised solid high tensile steel bearer wire in figure 8 construction.
10 Pair has aluminium foil screen and stranded drain wire for high interference areas.

Material No.

Old
Code

No.
Pairs

Wire
Size
mm

Nom
Dim
mm

Max DC
Resist.
@ 20C
Ohm/km

Pack
Size

Approx
Mass
kg/m

TEXT64IB002A5

3018

0.64

8.2 x 5.2

58.6

500m

0.05

Underground
Solid Cu conductor, Polyethylene insulation, Twisted unit pair jelly filled, Paper tape wrap,
Black polyethylene sheath.

Material No.

Old
Code

No.
Pairs

Wire
Size
mm

Nom
Dia
mm

Max DC
Resist.
@ 20C
Ohm/km

Pack
Size *

Approx
Mass
kg/m

TEXT64FP002*
TEXT64FP004
TEXT64FP010

5658
6526
5757

2
4
10

0.64
0.64
0.64

5.7
6.6
9.6

58.6
58.6
58.6

A, D, G
Bulk
Bulk

0.03
0.06
0.13

Pair Colours
Pair No.
1
2
3
4
5

Wire 1
WH
WH
WH
WH
WH

Wire 2
BU
OG
GN
BN
GY

Pair No.
6
7
8
9
10

Wire 1
RD
RD
RD
RD
RD

Wire 2
BU
OG
GN
BN
GY

* Pack Size
Reference
A
D
G

Size
100m Spool
500m Spool
Bulk

Code
A1
A5

Page 69

Garden Lighting

Figure 8, Stranded Cu conductors, Black PVC insulation (parallel web), Water resistant.

Material No.
JSF1.3GLBK100
JSF4GLBK100
JSF6GLBK100
JSF10GLBK100

Material No.
JSF1.3GLBK100
JSF4GLBK100
JSF6GLBK100
JSF10GLBK100

Page 70

Old
Code
2592
4775
6923
9750

Cores x Area
mm
2 x 1.3
2x4
2x6
2 x 10

Approx Mass
kg/m
0.07
0.12
0.16
0.25

Standing
No./mm
26/0.25
84/0.25
81/0.30
348/0.20

Max DC
Resist. @
20C Ohm/km
15.30
4.95
3.30
1.91

Nom Dim
mm
4.0 x 8.6
5.0 x 10.4
6.0 x 12.5
6.7 x 13.9

Pack
Size
100m
100m
100m
100m

Voltage Drop
Single Phase @
45C mV/A.m
33.60
10.90
7.25
4.20

Fire Alarm Cable

Analogue
Stranded Cu conductor, PVC insulation, Twisted Pair, PVC sheath. 450/750V.
Material No.
QACR50A2002GXJB
QACR50A2002GXHF

Old
Code
5578
2405

Cores x Area
mm
2 x 1.25 (RD)
2 x 1.25 (GY)

Nom Dia
mm

Material No.
QACR50A2002GXJB
QACR50A2002GXHF

7.3
7.3

Standing
No./mm
16/0.32
16/0.32

Max DC
Resist. @
20C Ohm/km
15.6
15.6

Pack
Size
200m
200m

Approx Mass
kg/m
0.06
0.06

Halogen Free Fire Alarm System Telecommunication Cable


Solid Cu conductor, Silicone insulation, Glass fibre tape, Laminated aluminium tape
screen, Solid tinned Cu drain wire, Halogen free flame retardant sheath.
Material No.
OLX34148

Old
Code
7661

No.
Pairs
2

Nom Dim
mm
2 x 0.8

Pack
Size
Bulk

Approx Mass
kg/m
0.07

Page 71

Data Cables

RS422 Screened Data (Pair)


Stranded tinned Cu conductors, HDP insulation, Aluminium foil overall tape screened with
a stranded drain wire, Cream PVC sheath.

Material
No.

Old
Code

No. of
Pairs

Stranding
No./mm

Nom
Dia
mm

Max DC
Resist.
@ 20C
Ohms/km

Nom.
Pair Cap.
pF/m

JD1PS
JD2PS
JD3PS
JD4PS

3417
3406
2478
7090

1
2
3
4

7/0.20
7/0.20
7/0.20
7/0.20

4.4
5.5
6.0
6.2

93.3
93.3
93.3
93.3

70
70
70
70

Approx
Mass
kg/m
0.02
0.03
0.04
0.05

Pair Colours
Pair No.
1
2
3

Wire 1
WH
WH
WH

Wire 2
BU
OG
GN

Pair No.
4
5
6

Wire 1
WH
WH
RD

Wire 2
BN
GY
BU

RS232 Screened Data (Cores)


Stranded tinned Cu conductors, PVC insulation, Cores laid up, Aluminium foil overall tape
screened with a stranded drain wire, Grey PVC sheath.

Material No.

Old
Code

No. of
Cores

Conductor Size 0.22 mm


JD6CSAAA1
4240
6
Conductor Size 0.5 mm
SD2CSA3
9435
2
SD3CSA3
9476
3

Nom
Dia
mm

Max DC
Resist.
@ 20C
Ohms/km

Pack
Size

Approx
Mass
kg/m

7/0.20

5.5

93.3

100m

0.04

7/0.30
7/0.30

5.2
5.6

37.9
37.9

300m Box
300m Box

0.02
0.02

Stranding
No./mm

Core Colours
No. Cores
1
2
3
4
Page 72

Colour
RD
BU
GN
YE

No. Cores
5
6
7
8

Colour
WH
BK
BN
VT

The cables New Zealanders trust to stay


safe and secure have a new name
Alsecure.
Alsecure is now the name to specify for the
cables youve always relied on for safety and
security to maintain circuit integrity for
lighting, alarms, pumps and other essential
services, even under fire.

Page 73

Alsecure Premium
Ceramifiable Single Core

Cu conductor, Ceramifiable insulation, Black HFS-110-TP sheath to AS/NZS 5000.1.


110C. 0.6/1 kV. WS52W fire rate to AS/NZS 3013:2005

Material No.

Old
Code

Area
mm

Nom Ins
Thick
mm

Nom
Sheath
Thick
mm

Nom
Dia
mm

Approx
Mass
kg/m

PEKP15AA001CXAA
PEKP17AA001CXAA
PEKP18AA001CXAA
PEKP19AA001CXAA
PEKP20AA001CXAA
PEKP22AA001CXAA
PEKP23AA001CXAA
PEKP24AA001CXAA
PEKP25AA001CXAA
PEKP26AA001CXAA
PEKP28AA001CXAA
PEKP30AA001CXAA
PEKP32AA001CXAA

4571
5661
6909
7180
8506
9630
2607
9979
5413
7592
8965
7981
3159

16
25
35
50
70
95
120
150
185
240
400
500
630

1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.6
2.8
2.8

1.4
1.4
1.4
1.4
1.4
1.5
1.5
1.6
1.7
1.8
2.0
2.1
2.2

11.7
13.0
14.2
15.8
16.8
18.9
20.5
22.3
23.8
26.8
33.1
36.6
40.2

0.27
0.37
0.48
0.63
0.83
1.09
1.37
1.66
1.99
2.60
4.20
5.25
6.45

Page 74

Alsecure Premium
Ceramifiable Multicore

Cu conductor, Ceramifiable insulation, Orange HFS-110-TP sheath to AS/NZS 5000.1.


110C. 0.6/1 kV. WS52W fire rated to AS/NZS 3013:2005.

Material No.
Two Core
PEKP07AA002OMAA
Two Core Plus Earth
PDKP05AA002OMAA
PDKP07AA002OMAA
PDKP09AA002OMAA
PDKP11AA002OMAA
PDKP13AA002OMAA
Three Core Plus Earth
PDKP05AA003OMAA
PDKP07AA003OMAA
PDKP09AA003OMAA
PDKP11AA003OMAA
PDKP13AA003OMAA
PDKP15AA003OMAA
Four Core Plus Earth
PDKP05AA004OMAA
PDKP07AA004OMAA
PDKP09AA004OMAA
PDKP11AA004OMAA
PDKP13AA004OMAA
PDKP15AA004OMAA
PDKP17AA004OMAA
PDKP18AA004OMAA
PDKP19AA004OMAA

Old
Code

Cores x Area
mm

Nom Dia
mm

Approx Mass
kg/m

4345

2 x 2.5

12.3

0.21

7067
5502
8404
3792
9169

2x 1.5 + E
2 x 2.5 + E
2x4+E
2x6+E
2 x 10 + E

11.8
13.0
13.8
14.7
16.3

0.19
0.25
0.29
0.35
0.48

6651
3934
4614
1221
6960
5768

3 x 1.5 + E
3 x 2.5 + E
3x4+E
3x6+E
3 x 10 + E
3 x 16 + E

12.8
14.0
15.0
16.0
17.9
20.1

0.22
0.30
0.36
0.44
0.60
0.84

3725
9805
8361
9773
4844
7068
7799
3708
3909

4 x 1.5 + E
4 x 2.5 + E
4x4+E
4x6+E
4 x 10 + E
4 x 16 + E
4 x 25 + E
4 x 35 + E
4 x 50 + E

13.8
15.2
16.4
17.6
19.7
22.2
25.0
28.0
32.3

0.26
0.35
0.43
0.53
0.74
1.03
1.45
1.95
2.65

Page 75

Alsecure Premium FRP


Ceramifiable

Stranded Plain Annealed Copper conductor, HFI-90-TP Ceramifiable Insulated, twisted


pairs black and white numbered, overall screened with aluminium polyester laminate tape
plus Stranded Tinned Annealed Copper drain wire, Red HFS-90-TP Sheathed Alsecure
FRP Cable, 90C, WS51W Fire rated to AS/NZS 3013:2005.

Material No.
Conductor 0.75mm
PBKP03AA001
PBKP03AA002
PBKP03AA004
PBKP03AA006
PBKP03AA008
PBKP03AA010
PBKP03AA012
PBKP03AA016
PBKP03AA020
PBKP03AA024
Conductor 1.5mm
PBK184AA001
PBK184AA002
PBK184AA004
PBK184AA006
PBK184AA008
PBK184AA010
PBK184AA012
PBK184AA016
PBK184AA020
PBK184AA024

Page 76

Number
of Pairs

Nom. overall
cable dia (mm)

Approx Mass
kg/m

1
2
4
6
8
10
12
16
20
24

7.7
12.2
13.5
16.3
18.6
20.4
22.3
25.5
28.3
30.9

0.065
0.122
0.205
0.293
0.382
0.462
0.550
0.717
0.885
1.052

1
2
4
6
8
10
12
16
20
24

8.
13.2
14.7
17.6
20.2
22.4
24.5
28.0
31.2
33.9

0.079
0.158
0.256
0.369
0.482
0.596
0.710
0.927
1.145
1.362

Alsecure Premium Flex


Ceramifiable

Cu conductor, flexible X-HF-110 XLPE insulation, Black HFS-110-TP sheath to AS/NZS


5000.1. 110C. 0.6/1 kV. WS52W fire rated to AS/NZS 3013:2005.

Material No.
PEKX01AA001
PEKX02AA001
PEKX03AA001
PEKX04AA001
PEKX05AA001
PEKX06AA001
PEKX07AA001
PEKX08AA001
PEKX09AA001
PEKX10AA001
PEKX11AA001
PEKX68AA001
PEKX69AA001
PEKX70AA001
PEKX71AA001

Area
mm
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630

Nom Dia
mm
9.4
10.4
12.0
13.6
15.6
17.3
19.6
21.7
23.8
26.4
29.6
32.7
36.8
41.9
45.6

Approx Mass
kg/m
0.18
0.24
0.35
0.45
0.61
0.82
1.09
1.31
1.60
1.94
2.55
3.10
3.98
5.17
6.57

Page 77

Page 78

AAC Aerial Conductors

Bare
Aluminium conductor. Made to AS 1531.

Material No.

Old
Code

Cross Sec.
Area mm

Namu
Poko
Ladybird
Kutu
Fly
Rango
Grasshopper
Wasp
Beetle
Weke
Bee
Cricket
Weta
Mata
Cockroach
Butterfly
Centipede
Cicada

2205
3361
2375
9656
5187
6263
6723
7430
6665
9320
4486
5769
6335
2954
1288
1997
9418
4180

24.5
30.6
42.8
49.5
63.6
73.6
84.1
106
106
122
132
158
167
222
266
323
415
628

Stranding
No./mm

Approx
Mass
kg/m
0.07
0.08
0.12
0.14
0.17
0.20
0.23
0.29
0.29
0.34
0.36
0.43
0.46
0.61
0.73
0.89
1.12
1.73

Nom Dia
mm

7/2.11
7/2.36
7/2.79
7/3.00
7/3.40
7/3.66
7/3.91
7/4.39
19/2.67
7/4.72
7/4.90
7/5.36
19/3.35
19/3.86
19/4.22
19/4.65
37/3.78
37/4.65

6.3
7.1
8.4
9.0
10.2
11.0
11.7
13.2
13.4
14.2
14.7
16.1
16.8
19.3
21.1
23.3
26.3
32.6

Covered
Aluminium conductor, PVC covered. Made to AS/NZS 5000.1.

Material No.

Old
Code

Code
Name

BAAB53AA001CXAA
BAAB32AA001CXAA
BAAB57AA001CXAA
BAAB59AA001CXAA
BAAB61AA001CXAA
BAAB66AA001CXAA
BAAB36AA001CXAA
BAAB67AA001CXAA

4373
2511
3416
4421
9751
5605
5912
5032
2395

Namu CVD
Ladybird CVD
Kutu CVD
Fly CVD
Rango CVD
Wasp CVD
Beetle CVD
Weke CVD
Weta CVD

Cross
Sec.
Area
mm

24.5
42.8
49.5
63.6
73.6
106
106
122
167

Stranding
No./mm

Nom
Dia
mm

Approx
Mass
kg/m

7/2.11
7/2.79
7/3.00
7/3.40
7/3.66
7/4.39
19/2.67
7/4.72
19/3.35

8.9
11.4
12.0
13.2
14.0
16.6
16.8
18.0
20.7

0.12
0.20
0.22
0.28
0.31
0.44
0.44
0.52
0.65
Page 79

AAAC Aerial Conductors

Bare
1120 Aluminium alloy conductor. Made to AS 1531.

Material No.

Old
Code

Cross Sec.
Area mm

Chlorine
Chlorine GC
Flurone
Flurone GC
Helium
Helium GC
Hydrogen
Hydrogen GC
Iodine
Iodine GC
Krypton
Krypton GC
Neon
Neon GC
Nitrogen GC

6854
3478
5467
9654
6532
2789
1854
5867
4521
9621
3579
7523
5632
1235
6080

34.4
34.4
49.5
49.5
77.3
77.3
111
111
124
124
158
158
210
210
262

Stranding
No./mm
7/2.50
7/2.50
7/3.00
7/3.00
7/3.75
7/3.75
7/4.50
7/4.50
7/4.75
7/4.75
19/3.25
19/3.25
19/3.75
19/3.75
37/3.00

Approx
Mass
kg/m
0.09
0.09
0.14
0.14
0.21
0.21
0.30
0.30
0.34
0.34
0.43
0.43
0.58
0.58
0.72

Nom Dia
mm
7.5
7.5
9.0
9.0
11.3
11.3
13.5
13.5
14.3
14.3
16.3
16.3
18.8
18.8
21.0

GC = Greased core

Covered
1120 Aluminium alloy conductor, PVC covered. Made to AS/NZS 5000.1.

Material No.

Old
Code

Code
Name

BAAJ80AA001CXAA
BAAJ60AA001CXAA
BAAJ85AA001CXAA

8169
8662
8585

Fluorine CVD
Hydrogen CVD
Krypton CVD

Page 80

Cross
Sec.
Area
mm

49.5
111
158

Stranding
No./mm

Nom
Dia
mm

Approx
Mass
kg/m

7/3.00
7/4.50
19/3.25

12.0
16.9
19.7

0.22
0.46
0.61

ACSR Aerial Conductors

Bare
Aluminium conductor, galvanised steel reinforced. Made to AS 3607.

Material No.

Old
Code

Equ Alu
Cross
Sec Area
mm

Ali

Steel

Magpie
Squirrel
Gopher
Ferret
Mink
Raccoon
Dog
Dingo
Wolf
Jaguar
Goat

4684
1974
2686
8966
9316
8209
6801
3914
4499
8079
3198

12.7
20.7
26.0
41.8
62.2
77.7
103.0
155.0
155.0
207.0
317.0

3/2.11
6/2.11
6/2.36
6/3.00
6/3.66
6/4.09
6/4.72
18/3.35
30/2.59
18/3.86
30/3.71

4/2.11
1/2.11
1/2.36
1/3.00
1/3.66
1/4.09
7/1.57
1/3.35
7/2.59
1/3.86
7/3.71

Stranding
No./mm

Nom Dia
mm
6.3
6.3
7.1
9.0
11.0
12.3
14.2
16.8
18.1
19.3
26.0

Approx
Mass
kg/m
0.14
0.09
0.11
0.17
0.26
0.31
0.40
0.51
0.72
0.67
1.49

Covered
Aluminium conductor, galvanised steel reinforced, PVC covered.
Made to AS/NZS 5000.1.

Material No.

Old
Code

Code
Name

BAAM39AA001CXAA
BAAM01AA001CXAA

8620 Squirrel CVD


5504 Ferret CVD

Equ Al
Cross
Sec Area
mm

20.7
41.8

Stranding
No./mm
Steel

Nom
Dia
mm

Approx
Mass
kg/m

6/2.11 1/2.11
6/3.00 1/3.00

9.1
12.2

0.14
0.27

Ali

Page 81

Al Aerial Bundled
Cables (ABC)
Aluminium conductor, XLPE insulation. Made to AS/NZS 3560.1.

Material No.
Two Core
XDAB17AA002AALL
XDAB18AA002AALL
XDAB19AA002AALL
XDAB22AA002AALL
Three Core
XDAB18AA003AALM
Four Core
XDAB17AA004AALP
XDAB18AA004AALP
XDAB19AA004AALP
XDAB20AA004AALP
XDAB22AA004AALP
Four Core Plus Pilot
XDAB18AAP04AALP
XDAB20AAP04AALP
XDAD22AAP04AALP
XDAB22AAL04AALP

Page 82

Nom
Ins.
Approx
Dia of
Thick.
Mass
Bundle
mm
kg/m
mm

Old Cores x Area


Code mm

Cond.
Dia
mm

6166
1566
2259
6877

2 x 25
2 x 35
2 x 50
2 x 95

5.99
6.90
8.05
11.40

1.3
1.3
1.5
1.7

18.4
20.6
23.8
31.8

0.20
0.26
0.35
0.68

1991

3 x 35

6.90

1.3

22.2

0.39

1152
4001
5517
9523
8256

4 x 25
4 x 35
4 x 50
4 x 70
4 x 95

5.99
6.90
8.05
9.69
11.40

1.3
1.3
1.5
1.5
1.7

22.2
24.9
28.7
32.8
38.4

0.40
0.52
0.70
0.96
1.35

3635
4520
5742
4940

4 x 35 + 16 P
4 x 70 + 16 P
4 x 95 + 16 P

6.90
8.05
11.40
11.40

1.3
1.5
1.7
1.7

25.4
33.3
39.1
39.1

0.61
1.05
1.44
1.44

4 x 95 + 16 P (x2)

Al Binder Wire

Bare
Solid aluminium wire. Made to OS 19:2001 (Olex Standard).
Material No.
ACBL47AA001AAAA
ACBL36AA001AAAA
ACBL39AA001AAAA
ACBL42AA001AAAA

Old
Code
4371
8858
5256
7477
5392

Wire Dia
mm
2.6
3.2
4.2
4.7
5.2

Approx Mass
kg/m
0.01
0.02
0.04
0.05
0.06

Covered
Solid aluminium wire, PVC covered. Made to OS 18:2001 (Olex Standard).
Material No.
ACCL47AA001BKAA
ACCL36AA001BKAA

Old
Code
9210
9795

Wire Dia
mm
2.6
3.2

Approx Mass
kg/m
0.03
0.04

Page 83

Cu Aerial Hard Drawn


Bare
Cu conductor. Made to AS 1746.

Material No.

Old
Code

Area
mm

ACUT11AA001AAAA
ACUT75AA001AAAA
ACUT13AA001AAAA
ACUT15AA001AAAA
ACUT17AA001AAAA
ACUT18AA001AAAA
ACUT70AA001AAAA
ACUT19AA001AAAA
ACUT20AA001AAAA
ACUT22AA001AAAA

1095
2577
1525
5513
2258
9778
6174
9530
1413
1319

6
7
10
16
25
35
40
50
70
95

Stranding
No./mm
7/1.04
7/1.12
7/1.35
7/1.70
7/2.14
19/1.53
19/1.63
19/1.83
19/2.14
37/1.83

Nom
Dia
mm
3.1
3.4
4.1
5.1
6.4
7.7
8.2
9.2
10.7
12.8

Approx
Mass
kg/m
0.05
0.06
0.09
0.14
0.23
0.31
0.36
0.45
0.62
0.88

Covered
Cu conductor, PVC cover. Made to AS/NZS 5000.1.

Material No.

Old
Code

Area
mm

BAAT11AA001AABK
BAAT13AA001AABK
BAAT15AA001AABK
BAAT16AA001AABK
BAAT18AA001AABK
BAAT70AA001AABK
BAAT19AA001AABK
BAAT20AA001AABK
BAAT22AA001AABK

7089
1775
3019
4277
4241
4647
5940
7378
1695

6
10
16
25
35
40
50
70
95

Page 84

Stranding
No./mm
7/1.04
7/1.35
7/1.70
7/2.14
19/1.53
19/1.63
19/1.83
19/2.14
37/1.83

Nom
Cover
Thick mm

1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.4
1.6

Nom
Dia
mm
5.3
6.2
7.2
9.3
10.2
11.2
12.2
13.7
16.2

Approx
Mass
kg/m
0.08
0.12
0.18
0.30
0.37
0.43
0.54
0.71
1.01

Cu Aerial - Trurip

Cu conductor, PVC insulation. Made to AS/NZS 5000.1.

Material No.

Old
Code

Cores x Area
mm

DAAT15AA002AABK
FAAT15AA003AABK

6668
7980

2 x 16
3 x 16

Nom Dia
mm
15.4
23.5

Approx
Mass
kg/m
0.35
0.53

Cu Aerial - Neutral Screens


Cu conductor, PVC insulation, Cu neutral screen, PVC sheath.
Made to AS/NZS 4961.

Material No.
Single Core
BAGT11AA001CXRD
BAGT15AA001CXRD
Two Core
QDAT15AA001CXRD
DAET15AA002CXAB
Three Core
QDHT15AA002CXRD
FAGT11AA003CXRJ
FAGT13AA003CXRJ
FAGT15AA003CXRJ
Four Core
QDHT15AA003CXRJ

Old
Code

Cores x Area
mm

Nom Dia
mm

Approx Mass
kg/m

2559
3481

1x6
1 x 16

10.1
12.8

0.20
0.41

9643
6831

1 x 16 + 2.5 P
2 x 16

19.5
19.6

0.53
0.63

8280
4674
7695
6234

2 x 16 + 2.5 P
3x6
3 x 10
3 x 16

21.0
16.2
18.2
20.7

0.78
0.43
0.59
0.87

3771

3 x 16 + 2.5 P (x 2)

22.8

0.99

Page 85

Cu Binder Wire

Bare
Solid Cu wire. Made to OS 19:2001 (Olex Standard).
Material No.
ACUL03A2001AAAA
ACUL04A2001AAAA
ACUL08A1001AAAA

Old
Code
4725
7034
4973

Wire Dia
mm
1.70
2.03
2.52

Approx Mass
kg/m
0.02
0.03
0.05

Covered
Solid Cu wire, PVC covered. Made to OS 18:2001 (Olex Standard).
Material No.
ACCL03A1001AABK
ACCL04A1001AABK
ACCL08A1001AABK
ACCL0A19001AABK

Page 86

Old
Code
7872
9565
5538
8541

Wire Dia
mm
1.70
2.03
2.52
2.64

Approx Mass
kg/m
0.03
0.04
0.05
0.06

Notes

Page 87

Page 88

Glands

A2 Industrial Glands - Sets


Indoor/outdoor gland for all types of unarmoured cable providing a seal on the outer sheath.
Gland Sets include a locknut and sealing washer.
Material No.
GLAND674
GLAND979
GLAND005
GLAND333
GLAND224
GLAND431
GLAND615
GLAND701
GLAND860
GLAND442

Gland
Size
A2 20S/16 (SET)
A2 20S (SET)
A2 20 (SET)
A2 25 (SET)
A2 32 (SET)
A2 40 (SET)
A2 50S (SET)
A2 50 (SET)
A2 63S (SET)
A2 63 (SET)

Cable Dia (mm)


min A max
3.1
8.7
6.1
11.7
6.5
14.0
11.1
20.0
17.0
26.3
22.0
32.2
29.5
38.2
35.6
44.1
40.1
50.0
47.2
56.0

Shroud
Ref
04
04
05
09
10
13
14
17/230
20
22

A2F Dual Certified EExd & EExe Glands


Indoor and outdoor cable gland for use in Zone 1, 2, 21 and 22 Hazardous Areas with all
types of unarmoured cable, providing a flameproof seal on the cable outer sheath.
Material No.
GLAND919
GLAND028
GLAND918
GLAND676
GLAND671
GLAND511
GLAND100
GLAND277

Gland
Size
A2F 20S/16
A2F 20S
A2F 20
A2F 25
A2F 32
A2F 40
A2F 50
A2F 63S

Cable Dia (mm)


min A max
3.1
8.7
6.1
11.6
6.5
13.9
11.1
19.9
17.0
26.2
22.0
32.1
35.6
44.0
40.1
49.9

Shroud
Ref
TBC
03
05
08
10
12
17/230
20

VSD Glands
For use with Varolex cables.
Material No.
GLAND020

Gland
Size
VSD 25

Cable Dia (mm)


min
max
13.0
18.0

Shroud
Ref
06

Page 89

Glands

A4 Industrial Glands
For use with Varolex cables. Indoor and outdoor cable gland for all types of steel tape
armour (STA) cable providing a seal on the cable outer sheath and a continuity seal on the
tape armour.
Material No.
GLAND247
GLAND530
GLAND823
GLAND610
GLAND135
GLAND437
GLAND531

Gland
Size
A4 25
A4 32
A4 40
A4 50S
A4 50
A4 63S
A4 63

Cable Dia (mm)


min A max
11.6
19.9
19.0
26.2
25.0
32.1
27.5
38.1
33.1
44.0
40.1
49.9
47.2
55.9

Cable Dia (mm)


min B max
11.1
19.9
17.0
26.2
22.0
32.1
29.5
38.1
35.6
44.0
40.1
49.9
47.2
55.9

Shroud
Ref
09
10
13
15
18
21
23

CW Industrial Glands - Sets


Indoor and outdoor gland for all types of SWA cable, providing environmental seal on the
cable outer sheath. The gland also provides mechanical cable retention and electrical
continuity via armour wire termination.
Gland Sets include a locknut and sealing washer.
Cable
Dia (mm)
A max
20S/16 (SET)
8.7
20S (SET)
11.7
20 (SET)
14.0
25 (SET)
20.0
32 (SET)
26.3
40 (SET)
32.2
50S (SET)
38.2
50 (SET)
44.1
63 (SET)
56.0
75S (SET)
62.0
75 (SET)
68.0

Material No.

Gland
Size

GLAND830
GLAND572
GLAND780
GLAND428
GLAND210
GLAND561
GLAND332
GLAND731
GLAND976
GLAND865
GLAND703

CW
CW
CW
CW
CW
CW
CW
CW
CW
CW
CW

Page 90

Cable Dia
(mm)
min B max
6.1
11.5
9.5
15.9
12.5
20.9
17.0
26.2
22.9
33.9
26.0
40.4
35.0
46.7
38.0
53.1
54.6
65.9
57.0
72.1
60.4
78.5

Wire Armour
(mm)
min
max
0.90
1.00
0.90
1.25
0.90
1.25
1.25
1.60
1.60
2.00
1.60
2.00
2.00
2.50
2.00
2.50
2.00
2.50
2.00
2.50
2.00
2.50

Shroud
Ref
04
04
06
09
11
15
18
21
25
28
30

Glands

E1FW Dual Certified EExd & EExe Glands


Indoor and outdoor cable gland for use in Zone 1, 2, 21 and 22 Hazardous Areas with all
types of SWA cable providing a flameproof seal on the cable inner sheath and an
environmental seal on the cable outer sheath.

Material No.

Gland
Size

GLAND978
GLAND770
GLAND766
GLAND008
GLAND999
GLAND658
GLAND982
GLAND436
GLAND018

E1FW
E1FW
E1FW
E1FW
E1FW
E1FW
E1FW
E1FW
E1FW

20S/16
20S
20
25
32
40
50S
50
63S

Cable Dia
(mm)
min A max
3.1
8.7
6.1
11.7
6.5
14.0
11.1
20.0
17.0
26.3
22.0
32.2
29.5
38.2
35.6
44.1
40.1
50.0

Cable Dia
(mm)
min B max
6.1
11.5
9.5
15.9
12.5
20.9
18.2
26.2
23.7
33.9
27.9
40.4
35.2
46.7
40.4
53.1
45.6
59.4

Wire Armour
(mm)
min
max
0.90
1.00
0.90
1.25
0.90
1.25
1.25
1.60
1.60
2.00
1.60
2.00
2.00
2.50
2.00
2.50
2.00
2.50

Shroud
Ref
04
04
06
09
11
15
18
21
23

CX/Z Industrial Glands


Indoor and outdoor cable gland for all types of braided or steel tape armour (STA) cables
providing environmental seal on the cable outer sheath. The gland also provides
mechanical cable retention and electrical continuity via wire braid or tape armour
termination.

Material No.

Gland
Size

GLAND742
GLAND174
GLAND651
GLAND125
GLAND862
GLAND221
GLAND533
GLAND231

CX/Z 20S/16
CX/Z 20S
CX/Z 20
CX/Z 25
CX/Z 32
CX/Z 40
CX/Z 50S
CX/Z 50

Cable Dia
(mm)
A max
8.7
11.6
13.9
19.9
26.2
32.1
38.1
44.0

Cable Dia
(mm)
min B
max
6.1
11.5
9.5
15.9
12.5
20.9
17.0
26.2
22.9
33.9
26.0
40.4
35.0
46.7
38.0
53.1

Armour Range
Grooved Max
(mm)

Shroud
Ref

1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0

04
04
06
09
11
15
18
21

Page 91

Glands

PX2K Flameproof EExd Glands


For all types of armoured cables providing an inner Flameproof compound compound
barrier seal around the individual cable cores and an environmental seal on the cable
outer sheath. Also equipped with an integral Deluge Protection seal to prevent premature
armour corrosion and an armour clamping facility suitable for SWA, Braided or Steel Type
cables. The cable gland also provides electrical continuity via armour termination.
Suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22 Hazardous Areas.

Material No.

Gland
Size

GLAND260
GLAND190
GLAND162
GLAND120
GLAND089
GLAND051
GLAND338
GLAND460

PX2K 20S
PX2K 20
PX2K 25S
PX2K 25
PX2K 32
PX2K 40
PX2K 50S
PX2K 75

Cable Dia
(mm)
A max
12.6
12.6
17.5
17.5
23.6
30.0
36.6
64.3

Cable Dia (mm)


min B max
9.5
12.5
14.0
18.0
22.9
26.0
35.0
60.4

15.9
20.9
22.0
26.2
33.9
40.4
46.7
78.5

Wire Armour (mm)


min
max
0.90
0.90
1.25
1.25
1.60
1.60
2.00
2.50

1.25
1.25
1.60
1.60
2.00
2.00
2.50
2.50

Gland Accessories
Entry Thread
Size
20
25
32
40
50
63
75

Page 92

Locknuts

Earth Tags

GLAND433
GLAND102
GLAND568
GLAND110
GLAND308
GLAND863
GLAND099

GLAND666
GLAND209
GLAND082
GLAND226
GLAND319
GLAND523
GLAND186

Entry Thread
Seals
GLAND038
GLAND387
GLAND791
GLAND173
GLAND577
GLAND839
GLAND180

Glands

PVC Shrouds
Shroud
Ref
02
04
05
06
09
10
11
13
14
15
17/230
18
20
21
22
23
28

Material No.
GLAND840
GLAND606
GLAND848
GLAND217
GLAND097
GLAND267
GLAND282
GLAND526
GLAND010
GLAND192
GLAND242
GLAND850
GLAND438
GLAND585
GLAND620
GLAND337
GLAND458

Page 93

Notes

Page 94

Page 95

General Technical Information

Installation Information
General
All cables must be installed to comply with the latest New Zealand Wiring Regulations.
Moisture
Olex cables are manufactured in conditions that exclude moisture, as it is difficult to
remove from a finished cable. It is important that precautions are taken during installation
to ensure that moisture is not permitted to enter the cable. Cut ends or opened areas
must be protected from moisture at all times, including during pulling in. Cables, after
cutting, must be re-sealed for storage, by an effective method such as a heat shrinkable
cable cap.
Single Core Cables
The following points relating to single core cables should be noted:
1.

Single core cables carrying the phase currents of a single circuit must be installed as
closely as possible together, to minimise inductive reactance and voltage drop. The
preferred formation for three phase conductors is a "trefoil" or cloverleaf pattern
although flat touching formation is also acceptable. Sheaths should be in contact
with one another in either case.

2.

A single core cable generates an alternating magnetic field around itself which can
cause large increases in voltage drop and power loss due to "transformer effect"
when ferrous metal (iron and steel) is allowed to encircle the cable. Steel racking or
ladder will not induce this effect, but the following must be observed:
a.

Cable cleats may be of wood, plastic, or non-ferrous metal but steel saddles
should not be used on single cores.

b.

Where three single phase cables pass through a steel bulkhead, they must all
pass through the same hole. Where glanding is required, it is usual to cut out a
panel and replace this with a non-ferrous (metal or plastic) plate in which the
three or four glands are mounted.

Cable Support
Under fault conditions, single core cables used as phase conductors in a multi-phase
system may be subjected to large electromechanical forces which tend to drive them
apart. Generally, properly designed cleats spaced at 1500 mm intervals will provide
adequate support to the cable under normal operating conditions. However special
consideration may be required if fault currents in excess of 15 kA are anticipated.
continued
Page 96

General Technical Information

Installation Information (continued)


Green Goo
Also known as Green Slime, this phenomenon is characterised by the appearance of a
sticky green exudate leaking out of PVC-insulated wiring at locations such as switches, hot
points and light fittings. It is a common occurrence in both Australia and New Zealand.
The green goo problem is predominantly associated with older (25+ years) TPS-type
cables operating in a warm environment. The exudate comprises a plasticiser that has
migrated out of the PVC insulation, coloured due to reaction with the copper conductor,
and that has subsequently travelled - by capillary action and/or gravity along the
conductor to emerge at a termination point.
Due to its stickiness and unsightly colour, the goo has a high nuisance value, however it
poses no significant health hazard. It may be cleaned from surfaces by wiping with a rag
soaked in a petroleum- or alcohol-based solvent (such as meths).
The long-term consequence of the exudate is that it represents a de-plasticising of the
insulation, meaning that as the process continues, the PVC will eventually become brittle,
and crack.
TPS Cables in Polystyrene Thermal Insulation
With the increasing use of polystyrene block insulation in houses and caravans, it is
important to explain the potential problem that arises when PVC sheathed and insulated
cables come into direct contact with this material.
The plasticiser that is added to PVC to make it flexible has a tendency to migrate out of the
PVC and into materials with which it is in contact, particularly where those materials such
as polystyrene and polyurethane - have a great affinity for the plasticiser. This will lead to
the PVCs becoming progressively harder and more brittle, while in contrast the
polystyrene will appear to melt as it absorbs the plasticiser.
The rate of migration is dependent upon the relative thickness of the materials, the
temperature, and the amount of surface area in direct contact. Accordingly, the rate of
deterioration of the PVC cable can vary considerably under different circumstances.
To mitigate the problem it is recommended that the amount of direct contact between the
cable and the polystyrene be reduced as much as possible. Effective ways of achieving
this include positioning the cable with an air gap between the sheath and the polystyrene,
or installing the cable within a rigid PVC or PE conduit.
continued

Page 97

General Technical Information

Installation Information (continued)


UV Resistance
Many polymers, due to their molecular structure, are prone to attack by UV radiation, and
because of this will degrade upon continued exposure to sunlight, eventually cracking and
splitting. The polyolefin family of materials, such as PE (including XLPE or X-90) and PP
is particularly susceptible to deterioration in this manner. PVC is also at risk but noticeably
less so, partly because of its structure but also due to the mitigating effects of the fillers,
plasticisers and stabilisers that are compounded with it.
A simple, effective and cheap material that can be added to plastic compounds to absorb
UV radiation is carbon black. However, while this approach is appropriate for sheathing
materials, it is not necessarily so for insulating materials as the carbon masks the core
colour.
Olex New Zealand Limited recommends that the insulation of its cables be protected
(covered) from solar radiation at all times, except in those instances where the material
has been deliberately modified to guard against the effects of UV, eg, Aerial Bundled
Cables (ABC). This covering may simply be the sheath of the cable.
Lugs and Links
Stranded compacted conductors, either round or sector shaped, must have lugs and links
fitted that are manufactured for the same nominal cross-sectional area as the conductor.
For example, a 150 mm conductor must have a 150 mm lug or link fitted, and the correct
dies, as stated by the manufacturer, used to compress it.
Although the lug or link will appear to be loose on the conductor, this is simply because the
initial compression of the joint has already taken place during the manufacture of the
conductor; the final compression of the joint will be correct.
If, for example, a 120 mm lug or link was fitted to a 150 mm conductor, the joint would be
over-compressed and likely to fail in service. In addition, the smaller lug in itself would be
unable to carry the same maximum current as the larger conductor, particularly with
respect to fault currents.
Olex New Zealand Limited manufactures conductors to be compatible with lugs and links
normally available in New Zealand.

Page 98

General Technical Information

Minimum Spacings in Air to Avoid Derating

Table 1A - Minimum Spacings in Air to Avoid Derating


Method of Installation

Horizontal Spacings

Vertical Spacings

Single Core Cables


Cables spaced away
from surfaces and
supported on ladders,
racks, etc. or suspended
from a catenary wire,
such that impedance to
air flow around the
cables is not greater
than 10%.

D
4D

4D

Cables spaced away


from surfaces and
supported on perforated
or unperforated trays
such that air flow around
the cables is partially
restricted.

2D
4D

2D

2D

Cables fixed directly to a


wall, floor, ceiling or
similar surface such that
air circulation is
restricted.

2D

6D

6D

continued

Page 99

General Technical Information

Minimum Spacings in Air to Avoid Derating (continued)

Table 1B - Minimum Spacings in Air to Avoid Derating


Method of Installation

Horizontal Spacings

Vertical Spacings

Multicore Cables
Cables spaced away
from surfaces and
supported on ladders,
racks, etc. or suspended
from a catenary wire,
such that impedance to
air flow around the
cables is not greater
than 10%.

0.5D
4D
2D

4D

Cables spaced away


from surfaces and
supported on perforated
or unperforated trays
such that air flow around
the cables is partially
restricted.
Cables fixed directly to a
wall, floor, ceiling or
similar surface such that
air circulation is
restricted.

Page 100

2D

4D

2D
6D

General Technical Information

Single Core Cables in Parallel


The following are the recommended arrangements of single core cables in parallel. Nonsymmetrical arrangements result in different impedances and hence unequal current
sharing between parallel legs of the same phase. This should be avoided as it could lead
to overheating of some cables.
Neutral conductors of Three phase circuits should be located so as not to disturb the
symmetry of the groups.
Table 2 Arrangements for Equal Current Sharing of Single Core Cables in Parallel
Single Phase

Three Phase
Two Conductors per Phase

or

or

Three Conductors per Phase

Not Recommended

Four Conductors per Phase

or
or

Page 101

General Technical Information

Bending Radii
The safe bending radius for an electric cable is limited by the flexibility of its insulation and
sheathing material. When a cable is being installed it may be pulled around several
curves in different directions and subjected to dynamic stresses which could cause
damage. Consequently the bending radius around which a cable may be pulled is greater
than that into which it can be set in its final position.
The following recommended minimum bending radii are expressed as a function of the
cable diameter and refer to the inside of the curve. In all cases, bending radii should be as
large as practicable.
Cable Type (choose the highest value of all
relevant construction features)
All Cable Types

Factor (F)
During
Installation

Installed
20

Nylon Covered

30

HDPE Sheath

25

15

Helical Copper or Brass


Taped

18

12

Steel Wire Armoured

18

12

Solid Aluminium Conductors

12

Compacted or Shaped
Stranded Conductors

12

MV XLPE
Cables

Single Core and Multicore


Cables

18

12

LV (0.6/1kV)
Cables

PVC/XLPE Insulation

R=FxD
where:

Page 102

R
D
F

=
=
=

Minimum Internal Bending Radius mm)


Cable Diameter (mm)
Factor from above table

General Technical Information

Duct Sizes
Ducts are another important consideration affecting the pulling operation. Selection of the
appropriate duct should be based on internal duct diameter to suit a cable size and wall
thickness to prevent deformation during duct installation. The internal finish of the installed
ducting should be smooth to prevent cable sheath damage during installation. During
cable installation the use of graphite or other commercially available pulling lubricants can
also prevent sheath damage and reduce pulling tensions. The following duct sizes are
recommended:
Heavy Duty Rigid PVC
Conduit Nominal Size
(mm)

Single Cable
(mm)

50

Up to 30

63

30 to 38

65

38 to 47

Up to 24

Up to 21

80

47 to 52

24 to 27

21 to 23

100

52 to 69

27 to 35

23 to 31

Three Cables
(mm)

Four Cables
(mm)

150

69 to 99

35 to 51

31 to 44

200

99 to 142

51 to 73

44 to 63

250

Above 142

Above 73

Above 63

Page 103

General Technical Information

Pulling Tension
Where a cable is to be pulled in using a winch and steel wire rope, the rope may be
secured to the cable by any of the following:

A cable stocking of steel wire braid


A pulling eye attached to the cable conductor
A pulling eye over the complete cable end
A pulling eye formed from the armour wires

The maximum tension which may be used is limited by the tensile strength of the
conductors or armour wires, or by the gripping capability of the cable stocking, depending
on the method used.
Maximum Safe Tensile Stress (S)
kN/mm

Material
Stranded Copper Conductor

0.07

Stranded Aluminium Conductor

0.05

Solid Aluminium Conductor

0.03

Galvanised Mild Steel Armour

0.13

Aluminium Wire Armour

0.04

Method of Calculation
Using values of S from table above:

a)

Limited by Conductor
Tc = N * Ac * S
where:

continued

Page 104

Tc
N
Ac
S

=
=
=
=

Maximum Pulling Tension (kN)


No. of Conductors
Cross-sectional Area of one Conductor (mm)
Maximum Safe Tensile Stress for Conductor (kN/mm)

General Technical Information

Pulling Tension (continued)


b)

Limited by Armour
Ta = 2.47 * da * (Da + da) * S
where:

c)

Ta
S
da
Da

=
=
=
=

Maximum Pulling Tension (kN)


Maximum Safe Tensile Stress for Armour (kN/mm)
Nominal Diameter of Armour Wire (mm)
Nominal Diameter under Armour (mm).

Limited by Stocking
Ts = 0.120 * D
where:

Ts
D

=
=

Maximum Pulling Tension (kN)


Overall Diameter of the Cable (mm)

Overall Limiting Tension


Cable OD (mm)

Maximum Pulling Tension (kN)

0 to 15

15 to 25

10

25 to 50

15

50 and over

20

The safe pulling tension is the smallest of the calculated values.

Page 105

General Technical Information

Copper Conductor Dimensions

Nominal
Cross
Sec. Area
mm

Circular
Nominal
Diameter
mm

Compacted
Minimum
Diameter
mm

16
25
35
50
70
95
120
150
185
240
300
400
500
630

4.95
6.30
7.55
8.75
10.50
12.40
14.10
15.55
17.40
20.00
22.35
25.25
28.30
-

4.85
5.99
7.00
8.30
9.69
11.40
12.81
14.22
15.97
18.25
20.47
23.40
26.76
30.44

Three Core, 120


Sectored
Nominal
Max
Depth
Width
mm
mm
5.22
8.48
5.97
9.85
7.02
11.51
8.50
14.40
10.02
17.00
11.22
18.90
12.17
20.90
13.65
23.10
15.57
26.75
17.67
29.85
19.84
33.96
-

Four Core, 90
Sectored
Nominal
Max
Depth
Width
mm
mm
5.87
7.68
6.91
9.20
7.97
10.50
9.37
13.09
10.97
15.55
12.25
17.10
13.62
18.92
15.37
21.30
17.48
24.50
19.57
27.60
22.29
31.21
-

Note
1

Lugs and links must always be selected to match the nominal cross sectional area
of the conductor. A lug or link for a 185 mm2 circular conductor may fit on a 240 mm2
compacted conductor but may not be rated to carry the load current associated with
the larger conductor size; nor will it compress correctly if it is of the compression
type.

Page 106

General Technical Information

Aluminium Conductor Dimensions

Nominal
Cross
Sec. Area
mm

Circular
Nominal
Diameter
mm

Compacted
Minimum
Diameter
mm

16
25
35
50
70
95
120
150
185
240
300
400
500
630
800

5.15
6.30
7.60
8.80
10.45
12.40
14.15
15.60
17.35
20.25
22.50
25.40
28.55
-

5.99
6.95
8.20
9.69
11.40
12.81
14.22
15.97
18.32
20.33
23.06
26.10
29.70
34.30

Three Core, 120


Sectored
Nominal
Max
Depth
Width
mm
mm
5.22
8.48
5.97
9.85
7.02
11.51
8.50
14.40
10.02
17.00
11.22
18.90
12.17
20.90
13.65
23.10
15.57
26.75
17.67
29.85
19.84
33.96
-

Four Core, 90
Sectored
Nominal
Max
Depth
Width
mm
mm
5.87
7.68
6.91
9.20
7.97
10.50
9.37
13.09
10.97
15.55
12.25
17.10
13.62
18.92
15.17
21.30
17.48
24.50
19.57
27.60
22.29
31.21
-

Note
1

Lugs and links must always be selected to match the nominal cross sectional area
of the conductor. A lug or link for a 185 mm2 circular conductor may fit on a 240 mm2
compacted conductor but may not be rated to carry the load current associated with
the larger conductor size; nor will it compress correctly if it is of the compression
type.

Page 107

Cable Selection

Four Main Factors


In accordance with AS/NZS 3008.1.2 and AS/NZS 3000, the four main factors which
affect the minimum size of cable required for a particular installation are:
1.

The cable current-carrying capacity, which is influenced by the cable materials and
construction, the conditions of the cable environment and the method of installation
due to their effects on the dissipation of heat from the conductors.

2.

The voltage drop in the cable circuit, which is a function of load current, load power
factor, and length of the cable run.

3.

The temperature rise under short-circuit conditions, which is a function of both the
magnitude and duration of the short-circuit current and is limited by the cable
materials.

4.

The maximum fault loop impedance which will still allow the protective device to trip
within the specified time.

Page 108

Cable Selection

Procedures
To select the cable size required based on the above considerations, follow the steps
listed:
Current-Carrying Capacity
1

Determine the minimum current for which the cable is to be rated, taking account of
the maximum demand of the circuit and the type and rating of the overcurrent
protection device.

Ascertain how the cables are to be installed, and the conditions in the cable
environment. From the tables of rating factors, select any rating factor(s) which are
applicable.

Divide the rating from step 1 by the appropriate factor(s).

From the current rating tables, select a cable which, for the appropriate method of
installation, has a tabulated rating not less than the value obtained from 3.

Voltage Drop
1

Determine the Load Current I (A) to be carried by the cable, and the Route Length L
(m) of the circuit.

Establish the maximum voltage drop Vd (V) permitted in the circuit (taking account of
any other voltage drops in series).

Evaluate the equation Vc = 1000 * Vd (mV/A.m). This value is the maximum mV/A.m
I*L
figure which will give the required voltage drop.

From the voltage drop tables, select a cable for the appropriate method of installation
which has a tabulated mV/A.m figure not greater than this value.

continued

Page 109

Cable Selection

Procedures (continued)
Short Circuit Temperature
1

Determine the Maximum Duration t (s) and Magnitude Isc (A) of the prospective
Short Circuit Current.

Evaluate the equation I1 = Isc *

t (A). This is the required short circuit rating

converted to a one second basis.


3

From the conductor short-circuit ratings tables, select a cable with a rating not less
than the value obtained from 2.

Fault Loop Impedance


1

Determine the maximum fault loop impedance which will still allow the protective
device to trip within the specified time.

From the above calculate the maximum length of cable run to comply with the
maximum fault loop impedance. Refer to AS/NZS 3000:2007, Clause 1.5.5.3 and
Appendix B.

General
For any circuit, the cable size selected should not be less than the largest of the sizes
calculated to meet the above limitations (this is the smallest size which will meet all of the
requirements).
In practice, the current-carrying capacity will be found to prevail in short-run/high-current
circuits while voltage drop considerations will usually prevail in long-run/low-current
circuits. It is unusual for short-circuit temperature requirements to determine the conductor
size required for 0.6/1 kV cable circuits.

Page 110

Cable Selection

Current Ratings
The current carrying capacity of a cable is determined by the following factors:
1.

Current flowing in a conductor generates heat and causes the conductor temperature
to rise above the ambient temperature.

2.

Different methods of installation or the presence of external heat sources such as


adjacent cables vary the rate of heat dissipation.

3.

The insulation material determines the maximum conductor temperature which can
be sustained continuously over the expected life of the cable.

The continuous current ratings for Low Voltage (LV) 0.6/1 kV cables given in this
handbook have been obtained from AS/NZS 3008.1.2. In all cases, the ratings given are
the single circuit ratings, corresponding to continuous loading at the maximum conductor
temperature appropriate to the insulation material.
Environmental Conditions
The current ratings are based on the following operational conditions:
Ambient Air Temperature
Soil Temperature
Soil Thermal Resistivity
Depth of Burial

30C
15C
1.2 K.m/W
0.5 m

Where conditions vary from those on which the ratings are based, appropriate rating
factors from Tables 3 to 6 (page 116), need to be applied.
Methods of Installation
Earthing conductors and lightly loaded neutral conductors of three phase circuits are
ignored for current rating purposes and are generally not shown in the graphical
representations of the cable and installation methods. Thus, where two single core cables
or a two core cable is shown the current rating applies to single phase operation; where
three single core cables or a three core cable is shown the current rating applies to two or
three phase operation.
continued

Page 111

Cable Selection

Current Ratings (continued)


Groups of Circuits
For groups of circuits unenclosed in air, the spacings and arrangements which need to be
maintained to prevent derating are given on Tables 1A & 1B (page 99 & 100). Where
underground circuits are spaced by more than 2m from adjacent circuits, no derating
applies. Also, if adjacent circuits are operated at less than 35% of their current carrying
capacity they may be excluded from considerations as their contribution to mutual heating
will be small.
Where a number of circuits are installed in close proximity in such a way that they are not
thermally independent, the appropriate rating factors from Tables 7 and 8 (page 117) need
to be applied.
Cables in Parallel
For cables operated in parallel, each parallel leg is regarded as a separated circuit for
current rating purposes and the appropriate rating factors for grouping are applicable.
Refer also to Table 2 (page 101) for the arrangements of single core cables so as to
ensure equal current sharing between parallel legs of the same phase.
Solar Radiation
For cables exposes to direct sunlight, the effect of solar radiation is to increase the surface
temperature of the cable and hence limit the temperature rise due to the load in the
conductors. Where possible, cables should be shielded from the direct rays of the sun
without restricting ventilation. Otherwise, the effect of solar radiation should be taken into
account, either by calculation in accordance with IEC 60287, or as an approximation by
adding 20C to the ambient air temperature and applying the appropriate rating factor.

Page 112

Cable Selection

Simple Cable Selection Chart


The tables below and on the next page are based on data obtained from AS/NZS 3008.1.2
and assume the following conditions:

Single core, XLPE insulated cables, installed in flat configuration, directly


buried in ground;

1-phase 230 V supply, or 3-phase 400 V supply, as applicable;

Maximum volt drop limited to 2.5% of supply voltage.


For longer runs, different cable configurations or other more specific conditions, please
contact our nearest Olex NZ representative.

30 amps per phase


Maximum Run length (meters)
Cable Size
mm

Aluminium
1-Phase

Copper

3-Phase

1-Phase

3-Phase

16

n/a

n/a

66

131

25

n/a

n/a

103

206

35

86

172

143

282

50

117

231

191

380

70

168

333

272

535

95

230

455

366

714

120

288

566

449

866

150

347

679

530

1010

185

425

825

622

1170

240

533

1019

738

1361

300

630

1186

830

1502

400

741

1372

916

1626

500

848

1543

986

1727

630

948

1684

1051

1832

continued

Page 113

Cable Selection

Simple Cable Selection Chart (continued)


63 amps per phase
Maximum Run length (meters)
Cable Size
mm

Aluminium
1-Phase

3-Phase

Copper
1-Phase

3-Phase

16

n/a

n/a

31

62

25

n/a

n/a

49

98

35

41

82

68

135

50

56

110

91

181

70

80

159

130

255

95

110

217

174

340

120

137

269

214

412

150

165

323

252

481

185

202

393

296

557

240

254

485

351

648

300

300

565

395

715

400

353

653

436

774

500

404

735

470

822

630

451

802

500

872

100 amps per phase


Maximum Run length (meters)
Cable Size
mm

Aluminium
1-Phase
3-Phase

1-Phase

Copper
3-Phase

25

n/a

n/a

31

35

26

52

43

62
85

50

35

69

57

114

70

50

100

82

161

95

69

136

110

214

120

86

170

135

260

150

104

204

159

303

185

127

248

186

351

240

160

306

221

408

300

189

356

249

450

400

222

412

275

488

500

254

463

296

518

630

284

505

315

549

continued

Page 114

Cable Selection

Simple Cable Selection Chart (continued)


150 amps per phase
Maximum Run length (meters)
Cable Size
mm

Aluminium
1-Phase
3-Phase

1-Phase

Copper
3-Phase

35

17

34

29

50

23

46

38

56
76

70

34

67

54

107

95

46

91

73

143

120

58

113

90

173

150

69

136

106

202

185

85

165

124

234

240

107

204

148

272

300

126

237

166

300

400

148

274

183

325

500

170

309

197

345

630

190

337

210

366

200 amps per phase


Maximum Run length (meters)
Cable Size
mm

Aluminium
1-Phase
3-Phase

1-Phase

Copper
3-Phase

70

25

50

41

80

95

35

68

55

107

120

43

85

67

130

150

52

102

79

152

185

64

124

93

175

240

80

153

111

204

300

94

178

124

225

400

111

206

137

244

500

127

231

148

259

630

142

253

158

275

Page 115

Cable Selection

Low Voltage (0.6/1 kV) Rating Factors


Table 3 - Ambient Air Temperature Variation
Insulation
Type
PVC
XLPE

15
1.18
1.15

20
1.12
1.09

Air Temperature (C)


30
35
40
1.00
0.94
0.88
1.00
0.95
0.91

25
1.06
1.05

45
0.80
0.85

50
0.72
0.80

55
0.63
0.74

Table 4 - Soil Temperature Variation


Insulation
Type
PVC
XLPE

10
1.04
1.04

Soil Temperature (C)


20
25
30
0.95
0.91
0.86
0.96
0.93
0.91

15
1.00
1.00

35
0.81
0.87

40
0.75
0.83

Table 5 - Depth of Burial Variation


Depth of
Burial
0.5
0.6
0.8
1.0
1.25
1.5
1.75
2.0
2.5
3.0 (or deeper)

Up to
50mm
1.00
0.99
0.97
0.95
0.94
0.93
0.92
0.91
0.90
0.89

Laid Direct
Above 50mm
Up to 300mm
1.00
0.98
0.96
0.94
0.92
0.91
0.89
0.88
0.87
0.86

Above
300mm
1.00
0.97
0.94
0.92
0.90
0.89
0.87
0.86
0.85
0.83

In Underground Ducts
Single
Multicore
Core
1.00
1.00
0.98
0.99
0.95
0.97
0.93
0.96
0.90
0.95
0.89
0.94
0.88
0.94
0.87
0.93
0.86
0.93
0.85
0.92

Table 6 - Soil Thermal Resistivity Variation


Soil
Thermal
Resistivity
(K.m/W)
0.8
0.9
1.0
1.2
1.5
2.0
2.5
3.0

continued
Page 116

1.09
1.07
1.04
1.00
0.92
0.81
0.74
0.69

1.16
1.11
1.07
1.00
0.90
0.80
0.72
0.66

1.03
1.02
1.02
1.00
0.95
0.88
0.83
0.78

1.06
1.04
1.03
1.00
0.94
0.86
0.80
0.75

1.08
1.06
1.04
1.00
0.92
0.83
0.77
0.71

Cable Selection

Low Voltage (0.6/1 kV) Rating Factors (continued)

Table 7 - Groups of Circuits Laid Direct in Ground


Multicore Cables

Single Core Cables


No. of
Circuits

2
3
4
5
6
7
8
9
10
11
12

spacing

spacing

Touching
Trefoil
Flat
0.78
0.81
0.66
0.70
0.61
0.64
0.56
0.60
0.53
0.57
0.50
0.54
0.49
0.53
0.47
0.51
0.46
0.50
0.44
0.49
0.43
0.48

0.15
0.83
0.73
0.68
0.64
0.61
0.59
0.57
0.56
0.55
0.54
0.53

Spacing (m)
0.30 0.45
0.88 0.91
0.79 0.84
0.74 0.81
0.73 0.79
0.71 0.78
0.69 0.76
0.68 0.76
0.67 0.75
0.67 0.75
0.66 0.74
0.66 0.74

0.60
0.93
0.87
0.85
0.83
0.82
0.82
0.81
0.81
0.80
0.80
0.80

spacing
Touching

0.81
0.70
0.63
0.59
0.55
0.52
0.50
0.48
0.47
0.45
0.44

0.15
0.87
0.78
0.74
0.70
0.68
0.66
0.64
0.63
0.62
0.61
0.60

Spacing (m)
0.30
0.45
0.91
0.93
0.84
0.88
0.81
0.86
0.78
0.84
0.77
0.83
0.75
0.82
0.75
0.81
0.74
0.81
0.73
0.80
0.73
0.80
0.72
0.80

0.60
0.95
0.90
0.89
0.87
0.87
0.86
0.86
0.85
0.85
0.85
0.84

Table 8 - Groups of Circuits In Underground Ducts


Single Core Cables in Multiway Ducts or
Multicore Cables in Single-way Ducts
No. of
Circuits

Touching

2
3
4
5
6
7
8
9
10
11
12

spacing

spacing

0.90
0.83
0.79
0.75
0.73
0.71
0.70
0.68
0.67
0.66
0.66

0.30
0.93
0.88
0.85
0.83
0.82
0.81
0.80
0.79
0.79
0.78
0.78

Spacing (m)
0.45
0.95
0.91
0.89
0.88
0.87
0.86
0.85
0.85
0.85
0.84
0.84

0.60
0.96
0.93
0.92
0.91
0.90
0.89
0.89
0.89
0.89
0.88
0.88

Single Core Cables in Single-way


Ducts

spacing

Touching
0.87
0.78
0.74
0.70
0.69
0.67
0.66
0.65
0.64
0.63
0.63

Spacing (m)
0.45
0.60
0.91
0.93
0.84
0.87
0.81
0.85
0.79
0.83
0.78
0.82
0.76
0.82
0.76
0.81
0.75
0.81
0.75
0.80
0.74
0.80
0.74
0.80

Page 117

Current Ratings

Single Conductor PVC (Single Phase)

Conductor
Size
mm2

PVC insulation
Unarmoured
Sheathed or unsheathed
For cables up to and including 0.6/1 kV @ 50 Hz AC.
Unenclosed
Spaced from
Touching
Surface

Single Phase
Cu
1.0
18
1.5
24
2.5
33
4
44
6
56
10
76
16
101
25
136
35
165
50
202
70
254
95
315
120
366
150
418
185
483
240
576
300
663
400
771
500
889
630
1023

Al
79
105
129
156
197
244
284
325
377
449
520
610
711
832

Cu
15
18
26
35
46
62
82
111
136
166
210
262
304
351
408
488
564
658
762
878

Al
64
86
105
129
163
203
237
272
318
381
442
520
610
715

Enclosed
Conduit in
Air

Cu
15
21
27
36
47
62
80
107
128
157
194
242
276
321
365
434
-

Al
62
83
99
122
150
187
214
250
284
340
-

Buried
Direct

Cu
24
31
43
56
71
94
134
174
209
248
305
365
416
466
528
612
691
784
886
994

Al
105
135
162
191
237
283
323
362
411
477
540
620
708
811

Underground
Single Phase
Ducts
Voltage Drop
mV/A.m

Cu
20
25
35
45
57
76
98
128
153
185
227
277
316
362
410
482
546
633
714
825

Al
76
99
119
143
176
215
245
281
320
376
427
499
572
672

Cu
51.6
33.0
18.0
11.2
7.50
4.46
2.81
1.78
1.29
0.963
0.680
0.507
0.415
0.352
0.301
0.255
0.229
0.209
0.194
0.181

Al
4.68
2.95
2.14
1.58
1.10
0.804
0.644
0.535
0.439
0.352
0.300
0.256
0.226
0.202

The values in this table have been obtained from AS/NZS 3008.1.2 for typical New
Zealand installation conditions:
Ambient Air Temperature: 30C
Soil Thermal Resistivity: 1.2 K.m/W
Example Product Range

Single core TPS

Vintol

Page 118

Soil Temperature:
Depth of Burial:

15C
0.5 m

Current Ratings

Single Conductor XLPE (Single Phase)

Conductor
Size
mm2

XLPE insulation
Unarmoured
Sheathed or unsheathed
For cables up to and including 0.6/1 kV @ 50 Hz AC.
Unenclosed
Spaced from
Touching
Surface

Single Phase
Cu
2.5
40
4
52
6
66
10
90
16
119
25
160
35
195
50
238
70
300
95
372
120
432
150
496
185
574
240
684
300
790
400
920
500
1063
630
1224

Al
92
123
151
184
233
288
336
385
447
534
618
726
849
994

Cu
31
41
52
72
95
129
158
194
246
306
358
413
480
574
666
779
903
1045

Al
74
100
122
150
191
238
278
320
374
449
520
615
722
849

Enclosed
Conduit in
Air

Cu
33
42
52
72
92
124
149
183
224
281
321
362
426
507
-

Al
72
96
116
142
175
218
249
281
331
396
-

Buried
Direct

Cu
39
49
62
83
149
192
230
273
335
401
457
514
581
674
761
865
977
1098

Al
114
149
179
212
260
311
355
398
453
526
595
683
780
891

Underground
Single Phase
Ducts
Voltage Drop
mV/A.m

Cu
39
49
62
83
107
140
168
202
249
305
348
391
453
532
601
699
791
916

Al
83
109
131
157
194
236
270
303
352
415
471
552
631
744

Cu
18.9
11.8
7.87
4.68
2.95
1.87
1.35
1.01
0.710
0.528
0.431
0.365
0.311
0.262
0.233
0.211
0.196
0.184

Al
4.91
3.08
2.24
1.65
1.15
0.840
0.672
0.557
0.455
0.363
0.307
0.261
0.228
0.204

The values in this table have been obtained from AS/NZS 3008.1.2 for typical New
Zealand installation conditions:
Ambient Air Temperature: 30C
Soil Thermal Resistivity: 1.2 K.m/W

Soil Temperature:
Depth of Burial:

15C
0.5 m

Example Product Range

Cantol

Page 119

Current Ratings

Two Conductor PVC (Single Phase)

Conductor
Size
mm2

PVC insulation
Armoured or unarmoured
For cables up to and including 0.6/1 kV @ 50 Hz AC.
Unenclosed
Spaced from
Touching
Surface

Single Phase
Cu
1.0
17
1.5
22
2.5
31
4
42
6
52
10
73
16
97
25
129
35
158
50
194
70
245
95
302
120
350
150
400
185
459
240
544
300
624
400
719

Al
75
100
123
150
190
234
272
310
358
425
489
570

Cu
16
21
30
39
50
68
91
122
149
181
229
283
328
374
430
508
583
671

Al
71
95
115
141
178
219
255
291
335
398
457
532

Enclosed
Conduit in
Air

Cu
15
18
26
34
44
59
78
103
128
152
194
233
275
309
357
415
483
549

Al
59
80
99
117
150
180
213
239
278
325
380
437

Buried
Direct

Cu
19
23
33
43
55
73
125
162
196
232
285
342
391
438
494
572
645
729

Al
97
125
152
179
221
265
304
340
385
447
506
579

Underground
Single Phase
Ducts
Voltage Drop
mV/A.m

Cu
19
23
33
43
55
73
95
123
150
178
222
267
310
349
399
463
531
603

Al
73
96
117
139
173
208
242
271
311
362
417
477

Cu
51.6
33.0
18.0
11.2
7.50
4.46
2.81
1.78
1.28
0.958
0.673
0.498
0.405
0.342
0.290
0.243
0.215
0.194

Al
4.67
2.93
2.13
1.57
1.09
0.798
0.638
0.528
0.431
0.343
0.290
0.245

The values in this table have been obtained from AS/NZS 3008.1.2 for typical New
Zealand installation conditions:
Ambient Air Temperature: 30C
Soil Thermal Resistivity: 1.2 K.m/W
Example Product Range

TPS

Remolex

PVC Armoured Mains

PVC Neutral Screen

Page 120

Soil Temperature:
Depth of Burial:

15C
0.5 m

Current Ratings

Two Conductor XLPE (Single Phase)

Conductor
Size
mm2

XLPE insulation
Armoured or unarmoured
For cables up to and including 0.6/1 kV @ 50 Hz AC.
Unenclosed
Spaced from
Touching
Surface

Single Phase
Cu
2.5
37
4
50
6
63
10
86
16
114
25
154
35
190
50
232
70
295
95
364
120
424
150
485
185
560
240
664
300
763
400
884

Al
89
120
147
179
229
283
329
376
436
519
598
700

Cu
34
46
58
80
107
144
178
217
275
340
395
452
520
618
710
820

Al
83
112
138
168
213
263
307
351
406
483
556
649

Enclosed
Conduit in
Air

Cu
31
41
51
69
90
121
145
178
220
275
314
365
415
493
575
656

Al
69
94
112
139
171
213
244
283
322
385
451
519

Buried
Direct

Cu
36
48
60
80
141
182
219
261
321
385
439
492
556
645
728
825

Al
109
141
170
202
249
299
341
382
433
504
570
653

Underground
Single Phase
Ducts
Voltage Drop
mV/A.m

Cu
36
48
60
80
105
137
165
198
244
299
340
391
442
519
597
677

Al
80
106
127
154
189
231
264
303
345
406
468
536

Cu
18.9
11.8
7.85
4.68
2.95
1.86
1.35
1.00
0.703
0.520
0.423
0.355
0.299
0.249
0.219
0.198

Al
4.90
3.08
2.23
1.65
1.15
0.835
0.666
0.550
0.448
0.355
0.298
0.249

The values in this table have been obtained from AS/NZS 3008.1.2 for typical New
Zealand installation conditions:
Ambient Air Temperature: 30C
Soil Thermal Resistivity: 1.2 K.m/W

Soil Temperature:
Depth of Burial:

15C
0.5 m

Example Product Range

Cempex

XLPE Armoured Mains

XLPE Neutral Screen

Page 121

Current Ratings

Single Conductor PVC (Three Phase)

Conductor
Size
mm2

PVC insulation
Unarmoured
Sheathed or unsheathed
For cables up to and including 0.6/1 kV @ 50 Hz AC.
Unenclosed
Enclosed
Spaced
Conduit
from
Touching
in Air
Surface

Three Phase
Cu
1.0
16
1.5
19
2.5
29
4
38
6
48
10
66
16
88
25
117
35
145
50
178
70
225
95
280
120
327
150
376
185
437
240
521
300
603
400
701
500
809
630
931

Buried
Direct

Three Phase
Voltage Drop
mV/A.m

Underground
Ducts

Trefoil

Al
67
91
112
138
174
218
254
292
341
408
473
556
651
762

Cu
15
18
26
35
46
62
82
111
136
166
210
262
304
351
407
486
561
653
754
866

Al
64
86
105
129
163
203
237
272
317
381
441
519
606
709

Cu
14
17
24
32
40
54
71
92
114
136
173
209
247
278
324
377
442
504
596
670

Al
55
72
89
105
135
162
193
217
253
307
348
400
480
548

Cu
18
22
30
40
50
65
114
147
176
209
256
307
349
392
442
512
576
652
735
823

Al
89
114
136
162
199
238
272
304
344
400
453
518
591
673

Cu
18
22
30
40
50
65
86
110
134
158
198
239
277
311
358
415
477
541
628
703

Al
66
86
103
123
154
185
216
242
278
325
375
430
505
575

Cu
44.7
28.6
15.6
9.71
6.49
3.86
2.43
1.54
1.12
0.834
0.589
0.439
0.359
0.305
0.261
0.221
0.198
0.181
0.168
0.157

Al
4.05
2.55
1.85
1.37
0.952
0.696
0.558
0.463
0.380
0.305
0.260
0.222
0.196
0.175

Flat

Cu
44.7
28.6
15.6
9.71
6.49
3.86
2.43
1.55
1.12
0.840
0.597
0.449
0.371
0.319
0.277
0.240
0.219
0.202
0.191
0.181

Al
4.05
2.55
1.85
1.37
0.956
0.702
0.565
0.472
0.391
0.319
0.276
0.240
0.216
0.197

The values in this table have been obtained from AS/NZS 3008.1.2 for typical New
Zealand installation conditions:
Ambient Air Temperature: 30C
Soil Thermal Resistivity: 1.2 K.m/W
Example Product Range

Single core TPS

Vintol
Page 122

Soil Temperature:
Depth of Burial:

15C
0.5 m

Current Ratings

Single Conductor XLPE (Three Phase)

Conductor
Size
mm2

XLPE insulation
Unarmoured
Sheathed or unsheathed
For cables up to and including 0.6/1 kV @ 50 Hz AC.
Unenclosed
Spaced
from
Touching
Surface

Three Phase
Cu
2.5
33
4
44
6
55
10
76
16
101
25
138
35
169
50
207
70
264
95
328
120
384
150
443
185
515
240
616
300
713
400
832
500
961
630
1111

Enclosed
Conduit
in Air

Buried
Direct

Three Phase
Voltage Drop
mV/A.m

Underground
Ducts

Trefoil

Al
78
107
131
161
205
255
298
344
402
482
559
659
773
906

Cu
31
41
52
72
95
129
158
194
246
306
358
413
479
573
662
772
893
1032

Al
74
100
122
150
191
238
278
320
373
448
519
613
717
842

Cu
28
36
46
62
79
107
132
157
201
242
287
325
369
439
516
587
696
785

Al
62
83
102
122
156
188
223
252
287
343
405
466
560
641

Cu
33
43
54
72
125
162
193
229
280
335
381
428
484
560
630
715
805
902

Al
97
125
150
178
217
260
296
332
377
438
495
567
646
736

Cu
33
43
54
72
92
121
147
174
217
261
304
342
388
456
525
596
693
778

Al
71
93
113
135
169
203
236
266
303
356
412
473
556
635

Cu
16.4
10.2
6.81
4.05
2.55
1.62
1.17
0.872
0.615
0.457
0.373
0.316
0.269
0.227
0.202
0.183
0.170
0.159

Al
4.25
2.67
1.94
1.43
0.997
0.727
0.582
0.482
0.394
0.314
0.266
0.226
0.197
0.177

Flat

Cu
16.4
10.2
6.81
4.05
2.55
1.62
1.18
0.878
0.623
0.467
0.385
0.330
0.285
0.245
0.222
0.205
0.193
0.182

Al
4.25
2.67
1.94
1.44
1.00
0.733
0.589
0.491
0.404
0.327
0.281
0.243
0.216
0.198

The values in this table have been obtained from AS/NZS 3008.1.2 for typical New
Zealand installation conditions:
Ambient Air Temperature: 30C
Soil Thermal Resistivity: 1.2 K.m/W

Soil Temperature:
Depth of Burial:

15C
0.5 m

Example Product Range

Cantol

Page 123

Current Ratings

Single Conductor Ceramifiable (Three Phase)

Conductor
Size
mm2

Copper conductor
R-E-110/HFS-110-TP 110C
For cables up to and including 0.6/1 kV @ 50 Hz AC.
Unenclosed
Spaced
from
Touching
Surface

Three Phase
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630

92
122
164
201
246
311
388
452
520
603
721
835
974
1127
1302

87
114
153
188
230
291
363
422
485
563
673
778
906
1050
1211

Enclosed
Conduit
in Air

76
100
134
162
195
250
305
361
409
480
586
670
768
926
1052

Buried
Direct

75
138
178
213
251
308
369
420
472
533
618
696
791
894
1004

Three Phase
Voltage Drop
mV/A.m

Underground
Ducts

82
105
138
164
195
244
294
341
384
440
522
589
669
780
877

Trefoil

Flat

4.30
2.70
1.72
1.24
0.924
0.650
0.481
0.392
0.331
0.280
0.235
0.208
0.187
0.172
0.160

4.30
2.71
1.72
1.25
0.929
0.657
0.491
0.403
0.344
0.296
0.252
0.227
0.208
0.195
0.184

The values in this table have been obtained from AS/NZS 3008.1.2 for typical New
Zealand installation conditions:
Ambient Air Temperature: 30C
Soil Thermal Resistivity: 1.2 K.m/W
Example Product Range

Alsecure Premium Ceramifiable Single Core

Page 124

Soil Temperature:
Depth of Burial:

15C
0.5 m

Current Ratings

Three & Four Conductor PVC (Three Phase)

Conductor
Size
mm2

PVC insulation
Armoured or unarmoured
For cables up to and including 0.6/1 kV @ 50 Hz AC.
Unenclosed
Spaced from
Touching
Surface

Three Phase
Cu
1.0
15
1.5
18
2.5
26
4
35
6
46
10
62
16
82
25
111
35
137
50
166
70
211
95
260
120
302
150
345
185
397
240
470
300
538
400
620

Al
64
86
106
129
163
202
235
268
310
368
424
495

Cu
14
17
25
33
42
58
78
104
128
156
196
243
282
321
369
437
499
575

Al
60
81
99
121
153
188
219
250
288
343
393
458

Enclosed
Conduit
in Air

Cu
13
16
23
29
38
50
66
87
107
128
162
202
230
260
300
360
-

Al
51
67
83
99
127
156
179
202
235
283
-

Buried
Direct

Cu
15
20
28
36
46
61
106
138
165
196
241
289
330
370
417
482
542
613

Al
83
107
129
152
187
224
256
287
326
378
427
488

Underground
Ducts

Three Phase
Voltage
Drop
mV/A.m

Cu
15
20
28
36
46
61
80
103
125
150
187
229
261
293
334
395
444
515

Cu
44.7
28.6
15.6
9.71
6.49
3.86
2.43
1.54
1.11
0.829
0.583
0.431
0.351
0.296
0.251
0.210
0.186
0.168

Al
62
80
98
116
145
177
202
228
261
309
350
411

Al
4.04
2.54
1.84
1.36
0.948
0.691
0.552
0.457
0.373
0.297
0.251
0.212

The values in this table have been obtained from AS/NZS 3008.1.2 for typical New
Zealand installation conditions:
Ambient Air Temperature: 30C
Soil Thermal Resistivity: 1.2 K.m/W

Soil Temperature:
Depth of Burial:

15C
0.5 m

Example Product Range

Remolex

PVC Armoured Mains

PVC Neutral Screen

Page 125

Current Ratings

Three & Four Conductor XLPE (Three Phase)

Conductor
Size
mm2

XLPE insulation
Armoured or unarmoured
For cables up to and including 0.6/1 kV @ 50 Hz AC.
Unenclosed
Spaced from
Touching
Surface

Three Phase
Cu
2.5
31
4
42
6
53
10
73
16
97
25
131
35
162
50
198
70
252
95
311
120
363
150
415
185
480
240
569
300
653
400
754

Al
75
102
125
154
196
242
282
322
374
446
514
601

Cu
29
39
50
68
91
122
151
185
234
289
337
385
444
527
604
695

Al
70
95
117
143
182
224
262
299
347
413
475
554

Enclosed
Conduit
in Air

Cu
26
33
42
58
75
100
125
150
190
230
271
305
354
425
-

Al
58
78
97
116
147
178
211
238
276
333
-

Buried
Direct

Cu
31
40
49
67
118
153
184
218
269
323
368
412
465
539
607
685

Al
91
119
142
170
209
250
286
320
364
423
477
546

Underground
Ducts

Three Phase
Voltage
Drop
mV/A.m

Cu
31
40
49
67
87
114
139
166
207
249
289
325
372
440
495
561

Cu
16.4
10.2
6.80
4.05
2.55
1.61
1.17
0.868
0.609
0.450
0.366
0.307
0.259
0.216
0.190
0.171

Al
67
89
108
128
161
194
225
253
291
345
391
446

Al
4.24
2.67
1.93
1.43
0.993
0.723
0.577
0.476
0.388
0.307
0.258
0.216

The values in this table have been obtained from AS/NZS 3008.1.2 for typical New
Zealand installation conditions:
Ambient Air Temperature: 30C
Soil Thermal Resistivity: 1.2 K.m/W
Example Product Range

Cempex

XLPE Armoured Mains

XLPE Neutral Screen

Aluminium URD Cables

Page 126

Soil Temperature:
Depth of Burial:

15C
0.5 m

Current Ratings

PVC Flexible Cords


Copper conductors
PVC insulation and sheath

Conductor
Size
mm

Max DC Resist.
@ 20C Ohm/km

Current
Rating
amps

PACW

TACW

3
7.5
10
16
20
25

39.0
26.0
19.5
13.3
7.98
4.95

40.1
26.7
20.0
13.7
8.21
5.09

0.5
0.75
1.0
1.5
2.5
4.0

Voltage Drop
mV/A.m
Single
Three
Phase
Phase
94.9
82.2
63.3
54.8
47.5
41.1
32.3
28.0
19.4
16.8
12.0
10.4

The values in this table have been obtained from AS/NZS 3008.1.2 for typical New
Zealand installation conditions:
Ambient Air Temperature:

25C

Page 127

Current Ratings

Versolex Single Core Flexible Cables (Single Phase)


Installed as fixed wiring
Flexible copper conductor
Flexible XLPE insulation
For cables up to and including 0.6/1 kV @ 50 Hz AC.

Conductor
Size
mm2

Unenclosed
Spaced from
Surface

Single Phase
6
64
10
89
16
117
25
155
35
191
50
240
70
301
95
361
120
428
150
493
185
563
240
674
300
776
400
927
500
1073
630
1249

Touching

Exposed to
Sun

Enclosed
Conduit
in Air

Underground
Ducts

51
70
94
125
155
196
248
298
354
410
471
567
653
787
913
1066

37
53
69
91
113
141
177
211
249
286
326
388
444
528
607
703

51
70
90
120
145
184
224
273
315
370
415
497
-

60
82
105
136
165
203
248
295
341
394
441
520
586
696
784
920

Single
Phase
Voltage
Drop
mV/A.m

8.42
4.87
3.10
2.00
1.43
1.00
0.718
0.558
0.448
0.375
0.323
0.269
0.239
0.211
0.195
0.181

The values in this table have been obtained from AS/NZS 3008.1.2 for typical New
Zealand installation conditions:
Ambient Air Temperature: 30C
Soil Thermal Resistivity: 1.2 K.m/W

Page 128

Soil Temperature:
Depth of Burial:

15C
0.5 m

Current Ratings

Versolex Single Core Flexible Cables (Three Phase)

Conductor
Size
mm2

Installed as fixed wiring


Flexible copper conductor
Flexible XLPE insulation
For cables up to and including 0.6/1 kV @ 50 Hz AC.

Spaced
from
Surface

Three Phase
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630

54
76
100
133
166
210
265
319
381
440
505
608
701
840
972
1133

Unenclosed
Enclosed
Underground
Exposed to
Conduit
Ducts
Touching
Sun
in Air

51
70
94
125
155
196
248
298
354
409
470
565
650
780
903
1052

37
53
69
91
113
141
177
211
249
286
326
387
442
525
601
693

45
61
80
103
130
158
201
235
282
320
367
430
504
586
693
791

52
71
91
117
143
174
217
254
299
338
382
445
513
593
687
780

Three Phase
Voltage Drop
mV/A.m
Trefoil

Flat

7.29
4.22
2.68
1.73
1.24
0.869
0.622
0.483
0.388
0.325
0.280
0.233
0.207
0.183
0.169
0.157

7.29
4.22
2.68
1.74
1.24
0.875
0.630
0.492
0.399
0.338
0.295
0.251
0.227
0.204
0.192
0.181

The values in this table have been obtained from AS/NZS 3008.1.2 for typical New
Zealand installation conditions:
Ambient Air Temperature: 30C
Soil Thermal Resistivity: 1.2 K.m/W

Soil Temperature:
Depth of Burial:

15C
0.5 m

Page 129

Current Ratings

Versolex Two Core Flexible Cables (Single Phase)


Installed as fixed wiring
Flexible copper conductor
Flexible XLPE insulation
For cables up to and including 0.6/1 kV @ 50 Hz AC.

Conductor
Size
mm2

Unenclosed
Spaced from
Surface

Single Phase
1.0
21
1.5
26
2.5
35
4
47
6
61
10
86
16
113
25
150
35
186
50
234
70
296
95
354
120
419
150
482
185
549
240
656
300
750
400
892
500
1025

Touching

Exposed to
Sun

Enclosed
Conduit
in Air

Underground
Ducts

Single
Phase
Voltage
Drop
mV/A.m

20
25
33
44
56
79
106
141
174
219
276
330
391
449
510
609
696
826
948

18
22
29
39
48
68
90
119
147
184
230
273
321
366
415
491
558
657
747

18
22
30
39
48
68
88
117
142
179
228
266
318
361
413
483
562
655
769

21
27
35
46
58
79
102
133
161
199
247
290
340
385
435
508
582
675
780

49.8
34.0
20.3
12.6
8.42
4.87
3.10
2.00
1.42
1.00
0.714
0.551
0.442
0.367
0.315
0.260
0.229
0.201
0.185

The values in this table have been obtained from AS/NZS 3008.1.2 for typical New
Zealand installation conditions:
Ambient Air Temperature: 30C
Soil Thermal Resistivity: 1.2 K.m/W

Page 130

Soil Temperature:
Depth of Burial:

15C
0.5 m

Current Ratings

Versolex Three & Four Core Flexible Cables


(Three Phase)
Installed as fixed wiring
Flexible copper conductor
Flexible XLPE insulation
For cables up to and including 0.6/1 kV @ 50 Hz AC.

Conductor
Size
mm2

Unenclosed
Spaced from
Surface

Three Phase
1.0
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500

18
22
30
40
51
73
96
128
158
200
253
303
360
413
471
562
642
761
873

Touching

Exposed to
Sun

Enclosed
Conduit
in Air

Underground
Ducts

Three
Phase
Voltage
Drop
mV/A.m

17
21
29
37
47
67
89
119
149
187
235
282
333
383
436
519
593
702
803

14
19
24
32
41
57
76
101
124
156
195
232
273
311
352
417
473
554
630

15
19
25
32
41
57
74
98
122
150
190
222
266
301
345
417
-

18
22
30
39
48
66
85
110
136
166
207
242
285
321
363
430
484
575
644

43.1
29.4
17.6
10.9
7.29
4.22
2.68
1.73
1.23
0.866
0.618
0.477
0.383
0.318
0.273
0.225
0.198
0.174
0.160

The values in this table have been obtained from AS/NZS 3008.1.2 for typical New
Zealand installation conditions:
Ambient Air Temperature: 30C
Soil Thermal Resistivity: 1.2 K.m/W

Soil Temperature:
Depth of Burial:

15C
0.5 m

Page 131

Current Ratings

AAC Aerial Conductors


Aluminium conductor
Bare and PVC covered

Code
Name
Bare
Namu
Poko
Ladybird
Kutu
Fly
Rango
Grasshopper
Wasp
Beetle
Weke
Bee
Cricket
Weta
Mata
Cockroach
Butterfly
Cicada
Covered
Namu
Ladybird
Kutu
Fly
Rango
Wasp
Beetle
Weke
Weta

Area
mm

Calculated DC
Resist. @ 20C
Ohm/km

Reactance at
50Hz with 300
mm Spacing
Ohm/km

Still Air
(amps)

1.0 m/s wind


(amps)

24.5
30.6
42.8
49.5
63.6
73.6
84.1
106
106
122
132
158
167
222
266
323
628

1.17
0.936
0.670
0.579
0.451
0.389
0.342
0.271
0.271
0.234
0.217
0.181
0.172
0.130
0.108
0.0895
0.0460

0.321
0.314
0.303
0.299
0.291
0.286
0.282
0.275
0.271
0.270
0.268
0.262
0.257
0.248
0.242
0.236
0.214

85
98
121
132
155
170
184
213
213
233
244
275
286
345
390
443
689

164
189
232
253
295
323
350
403
404
441
461
515
533
632
707
792
1178

24.5
42.8
49.5
63.6
73.6
106
106
122
167

1.17
0.670
0.579
0.451
0.389
0.271
0.271
0.234
0.172

0.321
0.303
0.299
0.291
0.286
0.275
0.271
0.270
0.257

90
130
142
168
185
234
235
258
317

152
212
232
271
297
368
369
399
484

Current Rating

Note
1
2
3

Coefficient of linear expansion 23.0 x 10-6/C.


Modulus of elasticity 65 GPa except for Cicada which is 64 GPa.
Current ratings are based on an ambient temperature of 30C, a maximum conductor
temperature of 75C, rural weathered, summer noon and intensity of solar radiation
1000 W/m.

Page 132

Current Ratings

AAAC Aerial Conductors


1120 Aluminium alloy conductor

Code
Name

Area
mm

Calculated
DC Resist.
@ 20C
Ohm/km

Reactance at
50Hz with 300
mm Spacing
Ohm/km

Still Air
(amps)

1.0 m/s wind


(amps)

Bare
Chlorine
Fluorine
Helium
Hydrogen
Iodine
Krypton
Neon
Nitrogen

34.4
49.5
77.3
111
124
158
210
262

0.864
0.599
0.383
0.266
0.239
0.189
0.142
0.114

0.310
0.299
0.285
0.273
0.270
0.259
0.250
0.242

104
131
173
217
231
271
328
381

200
250
328
410
438
507
603
690

Current Rating

Note
1
2
3

Coefficient of linear expansion 23.0 x 10-6/C.


Modulus of elasticity 65 GPa except for Nitrogen which is 64 GPa.
Current ratings are based on an ambient temperature of 30C, a maximum conductor
temperature of 75C, rural weathered, summer noon and intensity of solar radiation
1000 W/m.

Page 133

Current Ratings

ACSR Aerial Conductors


Aluminium conductor
Galvanised steel reinforced

Code
Name
Bare
Magpie
Squirrel
Gopher
Ferret
Mink
Raccoon
Dog
Dingo
Wolf
Jaguar
Goat

Equ Alu.
Area
mm

Calculated
DC Resist.
@ 20C
Ohm/km

Reactance at
50Hz with 300
mm Spacing
Ohm/km

Still Air
(amps)

1.0 m/s wind


(amps)

12.7
20.7
26.0
41.8
62.2
77.7
103
155
155
207
317

2.23
1.37
1.09
0.677
0.455
0.364
0.274
0.182
0.183
0.137
0.0893

0.349
0.322
0.315
0.299
0.287
0.280
0.271
0.257
0.252
0.248
0.229

59
75
86
117
152
175
210
274
280
336
462

113
145
167
223
285
326
387
494
501
616
814

Current Rating

Note
Current ratings are based on an ambient temperature of 30C, a maximum conductor
temperature of 75C, rural weathered, summer noon and intensity of solar radiation 1000
W/m.

Page 134

Current Ratings

Al Aerial Bundled Cables (ABC)


Aluminium conductor
XLPE insulated

Area
mm
Two Core
25
35
50
95
Three Core
35
Four Core
25
35
50
70
95

Calculated DC
Resist. @ 20C
Ohm/km

Max AC
Resistance @
80C
Ohm/km

Positive
Sequence
Reactance at
50Hz Ohm/km

Current
Rating
amps

1.20
0.868
0.641
0.320

1.49
1.08
0.796
0.398

0.102
0.0982
0.0924
0.0868

118
140
168
258

0.868

1.08

0.0982

134

1.20
0.868
0.641
0.443
0.320

1.49
1.08
0.796
0.551
0.398

0.102
0.0982
0.0924
0.0893
0.0868

109
134
157
196
241

Note
1
2
3

Coefficient of linear expansion 23.0 x 10-6/C.


Modulus of elasticity 59 GPa up to and including 50 mm and 56 GPa for conductors
above 50 mm.
Current ratings are based on an ambient temperature of 30C, a maximum conductor
temperature of 80C, wind speed of 1 m/s and intensity of solar radiation 1000 W/m.

Page 135

Current Ratings

Cu Aerial Hard Drawn


Hard Drawn copper conductor
Bare and PVC covered

Area
mm

Calculated DC
Resist. @ 20C
Ohm/km

Bare Made to AS 1746:1991


6
3.03
10
1.80
16
1.13
25
0.716
35
0.516
50
0.361
70
0.264
95
0.186
Covered Made to AS/NZS 5000.1
6
3.17
10
1.88
16
1.18
25
0.749
35
0.540
50
0.399
70
0.276
95
0.198

Reactance at
50Hz with 300
mm Spacing
Ohm/km

Still Air
(amps)

1.0 m/s wind


(amps)

0.365
0.349
0.334
0.320
0.306
0.295
0.285
0.273

44
61
82
110
135
169
206
256

87
120
160
212
260
323
392
486

0.365
0.349
0.334
0.314
0.306
0.295
0.285
0.273

45
63
84
115
141
172
218
266

81
110
147
194
235
281
353
421

Current Rating

Note
1
2

Coefficient of linear expansion 17.0 x 10-6/C.


Modulus of elasticity for bare conductors:
119 GPa for 6, 10, 16 & 25 mm
118 GPa for 35, 50 & 70 mm
117 GPa for 95 mm
Modulus of elasticity for covered conductors:
112 GPa for 6, 10 & 16 mm
110 GPa for 25, 35, 50 & 70 mm
108 GPa for 95 mm
Current ratings are based on an ambient temperature of 30C, a maximum conductor
temperature of 75C, rural weathered, summer noon and intensity of solar radiation
1000 W/m.

Page 136

General Data

Useful 3 Phase Formulae

kW

kVA x pf

kW

hp * 746
1000 * Eff

kW

Line Amps * Line Volts * 1.732 * pf


1000

kVA

kW
pf

kVA

hp * 746
a
1000 * Eff * pf

kVA

Lines Amps * Line Volts * 1.732


1000

Line Amps

kW * 1000
a
Line Volts * 1.732 x pf

Line Amps

kVA * 1000
a
Line Volts * 1.732

Line Amps

hp *746
a
Line Volts * 1.732 * Eff * pf

Horsepower
(hp)

kW * 1000 * Eff
746

hp

kVA * 1000 * Eff * pf


746

hp

Line Amps * Line Volts * 1.732 * Eff * pf


746

Page 137

General Data

Wire & Cable Size Comparison

AWG
24
22
20
18
16
14
12
10
9
8
7
6
5
4
3
2
1
1/0
2/0
3/0
4/0

Page 138

kcmil
0.40
0.64
1.02
1.62
2.58
4.11
6.53
10.38
13.09
16.51
20.82
26.24
33.09
41.74
52.62
66.36
83.69
105.6
133.1
167.8
211.6
250
300
350
400
480
500

mm
0.2
0.3
0.5
0.8
1.3
2.1
3.3
5.3
6.6
8.4
10.6
13.3
16.1
21.2
26.7
33.6
42.4
53.5
67.4
85.0
107.2
126.7
152.0
177.3
202.7
228.0
253.4

inch
0.0032
0.0051
0.0082
0.0103
0.01296
0.01635
0.02061
0.02598
0.03278
0.04133
0.05212
0.06573
0.08294
0.10454
0.13179
0.16619
0.19635
0.23562
0.27489
0.31416
0.35343
0.39270

General Data

Motor Current Table (Amperes approx)

Power kW
0.37
0.55
0.75
1.1
1.5
2.2
4
5.5
7.5
9.3
11
15
18.5
22

hp
0.5
0.75
1.0
1.5
2
3
5
7.5
10
12.5
15
20
25
30

Single
Phase
230V
4.2
5.2
7.2
10.0
10.1
13.8
26.1
34.5

Three
Phase
400V
0.9
1.3
1.7
2.4
3.1
4.6
7.9
11.2
14.9
18.7
22.4
29.9
38.0
44.8

Single
Phase
240V
4.0
5.0
6.9
9.6
9.7
13.3
25.0
33.0

Three
Phase
415V
0.9
1.3
1.7
2.3
3.0
4.5
7.6
10.8
14.4
18.0
21.6
28.8
36.6
43.2

Page 139

General Data

Abbreviations

Abv.
A.m.
AC
Al
AS

Cu
dB
DC

Description
Ampere metre
Alternating current
Aluminium
Australian Standard
Australian and New
Zealand Standard
Core
Degrees Celsius
Chlorinated Polyethylene
Cross-sectional Area
Chlorosulphinated
Polyethylene
Copper
Decibel
Direct Current

Earth

PILC

EA

Ethylene Acrylic

Eff

Efficiency

PVC
R-CPE90

AS/NZS
C
C
CPE
CSA
CSP

ELV

Extra Low Voltage

HD

Ethylene Propylene
Rubber
Hard Drawn

H.D.

Heavy Duty

EPR

Abv.
kV
kVA
kW
L.D.

Description
Kilovolt
Kilovoltamp
Kilowatt
Light Duty

mm

Millimetre

nF/km
NZS
OD
O.D.

Nanofarad/kilometre
New Zealand Standard
Outside diameter
Ordinary Duty

PACW

plain annaled copper wire

PE
pf
pF/m

Polyethylene
Power factor
Picofarad/metre
Paper insulated lead
covered
Polyvinyl Chloride
Rubber Chlorinated
Polyethylene - 90C
Rubber Ethylene
Propylene - 90C
Rubber - Halogen Free
110C
Steel Wire Armoured
Tinned Annealed Cooper
Wire

R-EP-90
R-HF-110
SWA
TACW

Halogen Free Sheath


90C Thermoplastic
Halogen Free 110C
Rubber
Horse power
Heat Resistant

UTP

Unshielded twisted pair

V
V75

HRC

High Rupture Capacity

V90

ISDN

Integrated Services Digital


Network

V90HT

kg

Kilogram

X-HF-90

kN

Kilonewton

XLPE

Volt
75C rated PVC
90C rated PVC
(for restricted periods)
90C rated PVC 105C
(for restricted periods)
XLPE halogen free 90C
Cross linked Polyethylene

HFS-90-TP
HF-110-R
hp
HR

Page 140

TPW

Thermoplastic welding

General Data

Copper Earthing Conductors


Minimum size of Copper earthing conductors.
Nominal area
active conductors
mm
1.0
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300

For Copper
active conductors
mm
1.0*
1.5*
2.5
2.5
2.5
4
6
6
10
16
25
25
35
50
70
95
120

For Aluminium
active conductors
mm
4
6
6
10
10
16
25
25
35
50
70

* Refer Wiring Rules AS/NZS 3000 regarding 1.0 and 1.5 earthing conductors.

Page 141

The Olex Range

Low Voltage Power


and Control Cables

Flexible Power &


Control Cables

Building Wires
Flats
PVC/PVC SDIs
XLPE/PVC Single Cores
PVC/PVC Circulars
XLPE/PVC Multicores
Armoured PVC/PVC Circulars
Armoured XLPE/PVC Multicores
Multicore Control
Armoured Multicore Control
Neutral Screened
Aerial

Varolex Screened VSD/EMC

Versolex
- XLPE/TPE
- Power
- Welding
- EMC/VSD
- Submersible

Flexolex EPR/CPE Power

Titanex
PVC/PVC Power
PVC/PVC Control

Fire Performance Cables


Alsecure Premium Ceramifiable
Fire Rated (FR)
- single core ES110
- multicore ES90
- flex
- FRP
Fire Safe (FS) Power
Rolling Stock
Locomotive

Alsecure Envirolex
Instrolex
Instrumentation Cables
Overall screened
Overall screened armoured
Individual & overall screened
Individual & overall screened
armoured
Thermocouple extension wire

Page 142

Data & Communications


Cables
Datolex
- Security
- Figure 8
- Category 5E LAN
- Category 6 LAN
- Coaxial
Gardolex Garden Lighting

Audiolex
- Speaker
- Coaxial
Fibre
- Multi Mode
- Single Mode
Telephone
- Internal
- External
Data

The Olex Range

Mining Cables
(flexible) to 33kV

Bare Overhead
Conductors

Reeling and Trailing Cables


to AS/NZS 1802 and 2802
Feeder Cables
Machine Cables

All Aluminium
All Aluminium Alloy 1120
ACSR
Steel Earth Wire and Stay Wire
(galvanised or aluminium clad)

Specialised Industrial Cables


HV Distribution Cables
Airport Lighting Cables
- Primary & Secondary cables
Automation Cables
Offshore Oil & Gas Cables
Defence Cables
- AO 14,000
- VG cables
- Milspec cables
Rolling Stock Cables
Materials Handling Cables
Marine Cables
Wind Turbine Cables

HV Transmission Cables
Extra High Voltage U/G XLPE to
330kV
(joints, terminations, engineering
services,
condition monitoring)

U/G XLPE to 33kV


Paper Insulated Lead Covered to
33kV
Aerial Bundled Cable XLPE to 33kV
(metallic and non-metallic screened)
Covered Conductor
Single Point Suspension
HV Submarine Cables
11kV to 33kV (EHV also)
XLPE, EPR or PILC Insulation
Radial Water Barrier
- Al/HDPE, LAS, Stainless Steel
Sheath
Mechanical Protection
- Single, Double Wire Armour,
HDPE,
- Hessian-Served

Page 143

Olex Branch Locations

Head Office
Paraite Road Bell Block New Plymouth 4373
Private Bag 2021 New Plymouth 4342
Phone +64 6 755 9800
Facsimile +64 6 755 9890

Auckland
105 Hugo Johnson Drive Penrose Auckland 1061
P O Box 13 493 Onehunga Auckland 1643
Phone +64 9 571 9000
Facsimile +64 9 571 9001

Christchurch
35 Phillips Street Phillipstown Christchurch 8011
P O Box 24 022 Linwood Christchurch 8642
Phone +64 3 353 7540
Facsimile +64 3 353 7545