KVA:
Three-phase substation shall have the following self-cooled ratings: 300 - 3750 kVA with LV rating of < 601 volts. 750 - 7500 kVA with LV rating of >600 volts . ( __ ) 65 degree Centigrade rise.. (Standard). ( __ ) 55/65 degree Centigrade rise. Allows for 12% additional capacity when operated at 65 degree Centigrade. ( __ ) ( __ ) ( __ ) OA, self-cooled ; No fans available < 750 kVA. OA/FFA, self-cooled/future fan cooling capacity. OA/FA, self-cooled / fan-cooled increased capaci ( 15% additional capacity.750kVA-2000kVA) ( 25% additional capacity.2500kVA-7500kVA) ( __ ) 50 Hertz Silicone ( __ ) Third party fluid..(ex. R-Temp, FR3)
WINDING RISE:
FAN COOLING:
FREQUENCY:
( __ ) 60 Hertz.Standard ( __ )
Delta or Wye *
( __ ) StandardHV 15KV Class, BIL= 95KV 5KV Class, BIL= 60KV ( __ ) Optional. HV 15KV Class, BIL= 110KV 5KV Class, BIL= 75KV ( __ ) Standard LV 480V Class, BIL= 30KV ( __ ) Optional. LV 480V Class, BIL= 45KV 5KV Class, BIL= 60KV 5KV Class, BIL= 75 KV
( __ ) Standard . 5.75% for LV < 601 V through 501kVA, < 501kVA 4.5% Min or 5.50% for LV > 600 V and HV BIL 110KV and below. ( __ ) Special _______ Note: ANSI allows the tested impedance to vary 7.5% above or below the designed impedance.
GENERAL CONSTRUCTION
GE Prolec Guide Form Specification
The liquid insulated, secondary type substation transformer shall be designed, manufactured and tested in accordance with the latest ANSI Standards. Impedance,
1/3100
with
STANDARD FEATURES
OPTIONAL FEATURES
(liquid)
INCOMING SECTION
( __ ) HV flange, 90 full-height ( Standard ) ( __ ) Air filled terminal compartment: 26.40 deep and 38.40 wide. Compartments are full height. Space heaters in outdoor units as standard. ( __ ) Coordinated to HV Switch (supplier )____________________________
OUTGOING SECTION
( __ ) LV flange, 90 full-height (Standard ) ( __ ) Air filled terminal compartment: 26.40 deep and 38.40 wide. Compartments are full height. Space heater in outdoor units as standard. ( __ ) Coordinated to GE LV equipment ______________________________ Includes copper flexible connectors. Each transformer shall receive all standard commercial tests in accordance with ANSI C57.12.90 (latest revision), with tests report available by serial number of the transformer. Routine tests include: - Resistance measurements of all windings - Ratio tests on the rated voltage connection and all tap connections - Polarity and phase relation tests on the rated voltage connection - No load loss at rated voltage - Impedance and load loss - Exciting current at rated voltage - Applied and Induced potential test
TEST REQUIREMENTS
1/3100