Liquid Secondary Substation Transformers

GUIDE FORM SPECIFICATIONS


GENERAL ARRANGEMENT
This specification covers a complete three phase secondary substation-type transformer. The transformer shall be ( Check One ): ( __ ) Standard Arrangement: When facing the front (nameplate) of the transformer, the incoming section shall be on the left and the outgoing section on the right. ( __ ) Reverse Arrangement: When facing the front (nameplate) of the transformer, the incoming section shall be on the right and the outgoing section on the left.

RATING
KVA:

Three-phase substation shall have the following self-cooled ratings: 300 - 3750 kVA with LV rating of < 601 volts. 750 - 7500 kVA with LV rating of >600 volts . ( __ ) 65 degree Centigrade rise.. (Standard). ( __ ) 55/65 degree Centigrade rise. Allows for 12% additional capacity when operated at 65 degree Centigrade. ( __ ) ( __ ) ( __ ) OA, self-cooled ; No fans available < 750 kVA. OA/FFA, self-cooled/future fan cooling capacity. OA/FA, self-cooled / fan-cooled increased capaci ( 15% additional capacity.750kVA-2000kVA) ( 25% additional capacity.2500kVA-7500kVA) ( __ ) 50 Hertz Silicone ( __ ) Third party fluid..(ex. R-Temp, FR3)

WINDING RISE:

FAN COOLING:

FREQUENCY:

( __ ) 60 Hertz.Standard ( __ )

INSULATING FLUIDS: ( __ ) Mineral Oil HV Rating: LV Rating: HV BIL: LV BIL: Impedance: ( __ ) ( __ )

Delta or Wye *

* HV Wye LV Wye available for 2500KVA and below. ( __ ) Wye* or ( __ ) Delta

( __ ) StandardHV 15KV Class, BIL= 95KV 5KV Class, BIL= 60KV ( __ ) Optional. HV 15KV Class, BIL= 110KV 5KV Class, BIL= 75KV ( __ ) Standard LV 480V Class, BIL= 30KV ( __ ) Optional. LV 480V Class, BIL= 45KV 5KV Class, BIL= 60KV 5KV Class, BIL= 75 KV

( __ ) Standard . 5.75% for LV < 601 V through 501kVA, < 501kVA 4.5% Min or 5.50% for LV > 600 V and HV BIL 110KV and below. ( __ ) Special _______ Note: ANSI allows the tested impedance to vary 7.5% above or below the designed impedance.

GENERAL CONSTRUCTION
GE Prolec Guide Form Specification

The liquid insulated, secondary type substation transformer shall be designed, manufactured and tested in accordance with the latest ANSI Standards. Impedance,
1/3100

Data subject to change without notice 1

Liquid Secondary Substation Transformers


sound level and voltage connections shall be in accordance with NEMA Standards. The core shall be constructed of high-grade gain oriented silicone steel laminations to reduce size, sound and losses. The coils shall be of rectangular construction utilizing extra strong, electrical grade, adhesive coated paper between turns. The core and coil assembly shall be installed in a sealed tank, immersed in insulated liquid to prevent dirt, moisture and corrosive elements from deteriorating the electrical and mechanical integrity of the transformer. Transformer shall have four approximately 2.5 percent rated kVA taps, two above and two below rated primary voltage. These taps shall be available by means of an externally operated manual tap changer for operation only when transformer is de-energized, provisions for padlocking the tap changer. - Windings : HV Copper / LV Aluminum - Provisions for lifting and jacking - Cover vent plug - Drain and sampling device - No Load tap changer with handle on - Pressure test valve front wall of transformer - Two tank grounding pads - Tank hand hole on transformer cover - Pressure vacuum gauge - Top filter-press connection - Anodized Aluminum - Liquid level gauge - Dial type - Pressure relief device (Silicone units) - 12 PSI tank ( __ ) Windings : All Copper ( __ ) Pressure relief device * ( __ ) Fault pressure relay* ( __ ) Winding temperature indicator* ( __ ) Pressure relief device (Oil Units) ( __ ) Liquid level gauge * ( __ ) Dial type thermometer* *Device with electrical contacts

with

STANDARD FEATURES

Nameplate thermometer (liquid) ANSI 61 Gray finish coat paint

OPTIONAL FEATURES
(liquid)

INCOMING SECTION

( __ ) HV flange, 90 full-height ( Standard ) ( __ ) Air filled terminal compartment: 26.40 deep and 38.40 wide. Compartments are full height. Space heaters in outdoor units as standard. ( __ ) Coordinated to HV Switch (supplier )____________________________

OUTGOING SECTION

( __ ) LV flange, 90 full-height (Standard ) ( __ ) Air filled terminal compartment: 26.40 deep and 38.40 wide. Compartments are full height. Space heater in outdoor units as standard. ( __ ) Coordinated to GE LV equipment ______________________________ Includes copper flexible connectors. Each transformer shall receive all standard commercial tests in accordance with ANSI C57.12.90 (latest revision), with tests report available by serial number of the transformer. Routine tests include: - Resistance measurements of all windings - Ratio tests on the rated voltage connection and all tap connections - Polarity and phase relation tests on the rated voltage connection - No load loss at rated voltage - Impedance and load loss - Exciting current at rated voltage - Applied and Induced potential test

TEST REQUIREMENTS

GE Prolec Guide Form Specification

Data subject to change without notice 2