Venting facility shall be provided for any pressure measuring instruments line either with tee & plug or 2 valve manifold. The trapped air at any point of instruments line may cause serious error.
CORRECTION FOR GAUGE LOCATION Pressure instruments located below the trapping points will indicate higher than the desired pressure due to pressure created by the column of liquid between instrument and tapping points. The correction is negative and is equal to hd is difference in height and d is density. For instruments mounted above tapping point, similar correction is required, but the correction must be added in the column of liquid, that creates a pressure which oppose the desired pressure. Without any correction the instruments will give a low reading.