With 40RM016-034
Commercial Air-Cooled
Split Systems
50 Hz
Product
Data
Features/Benefits
40RM016-034
Up to 4 compressors and 2
independent refrigerant circuits provide design flexibility; size 044-134 condensing
units can supply one or 2 air
handlers
Efficient 38AH Series units
save energy
Variable air volume units
operate at as low as 8% of
nominal capacity without the
use of energy-inefficient hot
gas bypass.
Constant volume units operate at as low as 16% of nominal capacity (standard) or
8% of nominal capacity (with
accessory unloader)
Weatherized steel cabinet
ensures corrosion protection
Protection against high
discharge and low suction
refrigerant pressure, and low
oil pressure ensure compressor reliability
Timed bypass of low pressure switch on start-up of
024-034 size units.
Crankcase heaters prevent
oil dilution and ensure
compressor lubrication
Form 38AH-C4PD
Versatility
38AH Series condensing units feature
up to 4 compressors and 2 refrigerant circuits, and can be matched with
a wide variety of air-handling units.
All condensing unit circuits can supply
a single air handler; size 044-134
units can supply 2 separate air
handlers.
Standard units have constant volume control. A variable air volume
(VAV) option is available. The VAV
units have electric unloaders on the
compressors to closely match building
loads. The VAV option requires only
a simple connection to the Carrier
ModuPanel discharge air controller,
thereby saving installation time and
cost. (NOTE: Unit sizes 024-034
require field supplied and installed
accumulator.)
Durable construction
All 38AH units have weatherized cabinets constructed of heavy-duty galvanized steel prepainted with corrosionresistant baked enamel. Inside and
outside surfaces are protected to ensure long life and good looks. The
durable, galvanized steel, prepainted
components exceed the requirements
of the 500-hour salt spray test per
ASTM B117.
The units coils have aluminum fins
mechanically bonded to copper tubes
for long-term reliability and improved
heat transfer. An inert epoxy barrier is available on precoated fins to
provide improved durability in mildly
corrosive coastal environments. Copper fins on copper tubes are available for harsh industrial or coastal
conditions.
Reliability
The 38AH condensing units feature
time-proven, highly reliable 06D and
06E semi-hermetic compressors.
Unloading capability is a standard feature on the lead compressor of each
circuit. Each compressor has vibration
isolators to provide quiet operation
and reduced component stress.
Table of contents
Page
Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Model Number Nomenclature 38AH024-034 . . . . . . . . . . . . . . . . . . .
4
Model Number Nomenclature 40RM . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
Ratings Summary 38AH024-034/40RM . . . . . . . . . . . . . . . . . . . . . . . . 5
Options and Accessories 38AH024-034/40RM . . . . . . . . . . . . . . . . . 6-8
Physical Data 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9,10
Physical Data 40RM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11,12
Dimensions 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Dimensions 40RM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14,15
Selection Procedure 38AH024-034/40RM . . . . . . . . . . . . . . . . . . . . . 16,17
Performance Data 38AH024-034/40RM . . . . . . . . . . . . . . . . . . . . . . . 18-31
Typical Piping and Wiring 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . 32,33
Electrical Data 38AH024-034/40RM . . . . . . . . . . . . . . . . . . . . . . . . . . 34-36
Controls 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Typical Control Wiring Schematic 38AH024-034 . . . . . . . . . . . . . . . . 38
Application Data 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39,40
Application Data 40RM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41-43
Model Number Nomenclature 38AH044-134 . . . . . . . . . . . . . . . . . . . 44
Ratings Summary 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Options and Accessories 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . 45,46
Physical Data 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47-50
Dimensions 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51-57
Selection Procedure, 2-Circuit Units 38AH044-134 . . . . . . . . . . . . . . 58
Selection Procedure, Single-Circuit Units 38AH044-084 Only . . . . . 58
Performance Data 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59-84
Typical Piping and Wiring 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . 85,86
Electrical Data 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87,88
Controls 38AH044-084 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Controls 38AH094-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Typical Control Wiring Schematic 38AH044-134 . . . . . . . . . . . . . . . . 91-93
Application Data 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94-100
Guide Specifications 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . . . . 101-103
Guide Specifications 40RM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104,105
Guide Specifications 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . 106-108
Feature/Benefits (cont)
Innovative Carrier 40RM airhandling units in sizes 016034: ideal matches for
38AH024-034 condensing
units
The 40RM Series has excellent fan
performance, efficient direct-expansion
(DX) coils, a unique combination of
indoor air quality features, and easy
installation. Its versatility and state-ofthe-art features help to ensure that
your split system provides economical
performance now and in the future.
Economy
The 40RM Series packaged air
handlers save money by providing
reduced installation expense and
energy-efficient performance.
Quick installation is ensured by the
multiposition design. Units can be
installed in either the horizontal or
vertical (upflow) configuration without
modifications. All units have drainpan connections on both sides, and
pans can be pitched for right- or lefthand operation with a simple adjustment. Fan motors and contactors
are prewired and thermostatic expansion valves (TXVs) are factoryinstalled on all 40RM models.
High efficiency, precision-balanced
fans minimize air turbulence, surging, and unbalanced operation, cutting
operating expenses.
The economizer accessory precisely
controls the blend of outdoor air and
room air to achieve comfort levels.
When the outside air enthalpy is suitable, outside air dampers can fully
open to provide free cooling.
Coil flexibility
Model 40RM direct-expansion coils
have galvanized steel tube sheets; inlet
and outlet connections are on the
same end. The coils are designed for
use with Refrigerant 22 and have copper tubes mechanically bonded to
aluminum sine-wave fins. The coils
include matched, factory-installed
TXVs with matching distributor
nozzles. Accessory hot water and
steam coils and electric heaters are
also available.
Rugged dependability
40RM units are made to last. The
die-formed galvanized steel panels
ensure structural integrity under all
operating conditions. Galvanized steel
fan housings are securely mounted
to a die-formed galvanized steel deck.
Mechanically bonded coil fins provide improved heat transfer. Rugged
pillow-block bearings are securely fastened to the solid steel fan shaft
with split collets and clamp locking
devices.
024
A
Compressors
A Standard Compressors One Suction
Pressure-Actuated Unloader on Lead
Compressor
C Variable Air Volume (VAV) Option
Includes 2 Electric Unloaders on Lead
Compressor and Control Box
Modifications
Not Used
Condenser Coil Fin Material
Aluminum (Standard)
C
Copper (Optional)
K
Precoated Aluminum (Optional)
SO Post-Coated Aluminum (Contact Factory)
SO Post-Coated Copper (Contact Factory)
Voltage Designation
3 346-3-50
8 230-3-50
9 400-3-50
SO Special Order
UL Underwriters Laboratories (U.S.A.)
016
GC
Factory-Installed Options
GC Unpainted, Standard Motor, and
Standard Drive
HC Unpainted, Standard Motor, and
Medium-Static Drive
(Not available for sizes 016-028)
TC Unpainted, Alternate Motor, and
Medium-Static Drive
(sizes 016-028)
YC Unpainted, Alternate Motor, and
High-Static Drive*
ED Painted, Standard Motor, and
Standard Drive
FD Painted, Standard Motor, and
Medium-Static Drive
(Not available for sizes 016-028)
RD Painted, Alternate Motor, and
Medium-Static Drive
(sizes 016-028)
WD Painted, Alternate Motor, and
High Static Drive*
Cooling Coil
Direct Expansion
Nominal Capacity kW (Tons)
016 52 (15)
024 70 (20)
028 87 (25)
034 105 (30)
Not Used
Expansion Device
B Thermostatic Expansion Valve
Voltage Designation (V-Ph-Hz)
8 230-3-50
9 400-3-50
Revision Number
0 Original Model
Packaging
3 Export Packaging
*YC and WD option codes for all 034 size units designate standard motor and high-static drive.
INDOOR
UNIT
40RM
016
024
028
024
028
034
028
034
AIRFLOW
L/s
2,800
3,800
4,700
3,800
4,700
5,650
4,700
5,650
Cfm
6,000
8,000
10,000
8,000
10,000
12,000
10,000
12,000
SYSTEM GROSS
CAPACITY
kW
Btuh**
57.3
195,000
62.5
214,000
66.3
227,000
68.9
236,000
73.5
251,000
77.6
265,000
82.6
283,000
87.7
300,000
216,000
73
250,000
87
297,000
*Condensing unit only ratings are at 7.2 C (45 F) saturated suction temperature and 36 C (95 F) entering-air
temperature.
Total gross system capacity (kW) is based on 20 C wet bulb and 26.7 C dry bulb air entering indoor unit, and
36 C dry bulb air entering outdoor unit.
**Total gross system capacity (Btuh) is based on 67 F wet bulb and 80 F dry bulb air entering indoor unit, and
95 F dry bulb air entering outdoor unit.
Standard,
Non-Corrosive
Mild
Coastal
Moderate
Coastal
Severe
Coastal
Combined
Coastal
and Industrial
X
X
X
X
X
LEGEND
Al/Cu
Aluminum Fin with Copper Tube Coil
Cu/Cu
Copper Fin with Copper Tube Coil
Enviro-Shield Family of Coil Protection Options
Post-Coated Organic Coating applied to Entire Coil Assembly
Pre-Coated
Epoxy Coating Applied to Fin Stock Material
*See Selection Guide: Environmental Corrosion Protection Catalog No. 811-839 for more information.
Industrial
the CO2 level in the space exceeds the set point. A Carrier
Comfort System programmable thermostat can be used to
override the sensor if the outside-air temperature is too high
or too low.
CO2 sensors can be connected to the Carrier Comfort
System relay pack or to the economizer accessory. Connection to the economizer requires field-supplied and installed Honeywell dc adapter no. Q769C1004.
Condensate drain trap includes an overflow shutoff switch
than can be wired to turn off the unit if the trap becomes
plugged. The kit also includes a wire harness that can be
connected to an alarm if desired. The transparent trap is
designed for easy service and maintenance.
CARRIER THERMOSTATS
COMMERCIAL ELECTRONIC THERMOSTAT
Carrier
Pm
COOL
AUTO
HEAT
NON-PROGRAMMABLE THERMOSTAT
H
DISCHARGE
PLENUM
RETURN-AIR
GRILLE
SUBBASE
FAN
COIL
UNIT
ECONOMIZER
FAN COIL
UNIT
024
Circuit 1
028
Circuit 2
Circuit 1
034
Circuit 2
Circuit 1
Circuit 2
63
73
87
798.3
872.3
825.6
899.0
Reciprocating Semi-Hermetic
06DH328
06DA328
6
6
24.3
24.3
853.0
951.2
06DH824
6
24.3
06DA824
6
24.3
100
67*
33
100
524
400
1.36
9.1
2...762
1.0
7870
2...748
3.64
17.4
06DH328
6
24.3
100
100
100
67*
67*
33
33
Factory Installed
524
524
400
400
4.73
R-22
1.36
1.36
1.36
1.36
9.1
9.1
9.1
11.4
Propeller Type Direct Driven
2...762
1.0
7870
16
3100
Enhanced Copper Tubes, Aluminum Lanced Fin
2...748
3.64
17.4
06DA537
6
24.3
100
1.36
11.4
2...762
1.0
7400
3...670
3.64
26.0
2937 6 48
2206 6 138
186 6 21
303 6 34
Manual Reset
41.4
60.7
21.1 6 1.6
15.6 6 1.6
Fusible Plug
Liquid Line, Suction Line, Compressor
99
138
5 8
*Standard unit single pressure-actuated suction unloader on compressor no. 1.
VAV FIOP double electrically actuated unloaders on compressor
no. 1.
**With 7.6 m of interconnecting piping.
Condenser 80% full of liquid R-22 at 48.8 C.
10
024
Circuit 1
028
Circuit 2
Circuit 1
034
Circuit 2
Circuit 1
Circuit 2
18
21
25
1760
1923
1820
1982
Reciprocating Semi-Hermetic
06DH328
06DA328
6
6
1450
1450
1880
2097
06DH824
6
1450
06DA824
6
1450
100
67*
33
100
76
58
3
20
2...30
1.0
16,700
2...19
39.20
37.7
06DH328
6
1450
100
100
100
67*
67*
33
33
Factory Installed
76
76
58
58
10
R-22
3
3
3
3
20
20
20
25
Propeller Type Direct Driven
2...30
1.0
16,700
950
3100
Enhanced Copper Tubes, Aluminum Lanced Fin
2...19
39.20
37.7
06DA537
6
1450
100
3
25
2...30
1.0
15,700
3...17
39.20
56.6
426 6 7
320 6 20
27 6 3
44 6 5
Manual Reset
6.0
8.8
70 6 3
60 6 3
Fusible Plug
Liquid Line, Suction Line, Compressor
210
138
58
*Standard unit single pressure-actuated suction unloader on compressor no. 1.
VAV FIOP double electrically actuated unloaders on compressor
no. 1.
**With 25 ft of interconnecting piping.
Condenser 80% full of liquid R-22 at 120 F.
016
52
024
70
028
87
034
105
311
63
313
63
463
82
467
82
2...381
2831
2124-3539
2...381
3775
2831-4719
2...457
4719
3539-5899
2...457
5663
4247-7079
2.16
3.73
5.60
7.46
23.8
23.8
23.8
23.8
2.04/2.04
2.27/2.27
R-22
1.13/1.13
1.64
2
12
3...591
1.59/1.59
2.77
2
18
3...591
1207
1.24
1...394
1.24
1...394
1.24
2...335
1.24
2...335
1.39
1...394
1.39
1...394
1.39
2...493
1.39
2...493
1034
52.6
0.052
2...118
54.1
0.054
2...118
2...138
2...138
2...58
1...212
1...212
1...2
1...2
1
1...1 4 ODM/1 IDF
Throwaway Factory Supplied
4...406 508 51
4...508 x 610 x 51
4...406 610 51
4...508 x 635 x 51
Right or Left Side
LEGEND
DX Direct Expansion
TXV Thermostatic Expansion Valve
*Units are shipped without refrigerant charge.
11
12
016
15
024
20
028
25
034
30
685
140
690
140
1020
180
1030
180
2...15
6000
4500-7500
2...15
8000
6000-10,000
2...18
10,000
7500-12,500
2...18
12,000
9000-15,000
2.9
5.0
7.5
10.0
4.5/4.5
5.0/5.0
1425
R-22
2.5/2.5
17.67
2
12
3...15
3.5/3.5
29.83
2
18
3...15
175
13.33
1...10
13.33
1...10
13.33
2...8.5
13.33
2...8.5
15.0
1...10
15.0
1...10
15.0
2...12.5
15.0
2...12.5
150
13.9
1.85
2...118
14.3
1.90
2...118
2...138
2...138
2...58
1...212
1...212
1...2
1...2
1
1...1 4 ODM/1 IDF
Throwaway Factory Supplied
4...16 20 2
4...20 x 24 x 2
4...16 24 2
4...20 x 25 x 2
Right or Left Side
Dimensions 38AH024-034
NOTES:
1. There must be 4 ft [1220 mm] for service and for unrestricted airflow on all
sides of unit.
2. There must be minimum 8 ft [2440 mm] clear air space above unit.
3. C in the package number indicates copper coils.
4. Dimensions in [ ] are in millimeters.
5. The approximate operating weight of the unit is shown below.
6. Certified dimensional drawing is available on request.
024
024C
028
028C
034
034C
631.6
[286.5]
666.5
[302.3]
658.7
[298.8]
693.0
[314.3]
667.0
[302.5]
718.3
[325.8]
577.6
[262.0]
609.5
[276.5]
602.4
[273.3]
633.8
[287.5]
610.0
[276.7]
656.8
[297.9]
263.1
[119.3]
309.0
[140.2]
267.0
[121.1]
313.0
[142.0]
288.0
[130.7]
344.8
[156.4]
287.7
[130.5]
337.9
[153.3]
291.9
[132.4]
342.2
[155.2]
315.0
[142.9]
377.0
[171.0]
CENTER OF
GRAVITY
A Dim.
in.
[mm]
40.00
[1016]
43.00
[1092]
39.25
[997]
42.25
[1073]
41.00
[1041]
44.00
[1117]
B Dim.
in.
[mm]
32.75
[832]
TOTAL
UNIT WT
lb [kg]
1760
[798.3]
1923
[872.3]
1820
[825.6]
1982
[899.0]
1880
[853.0]
2097
[951.2]
13
Dimensions 40RM
40RM016,024
14
UNIT WEIGHT
lb (kg)
685 (311)
690 (313)
40RM028,034
15
Selection procedure
38AH024-034/40RM SI
NOTE: Pages 22 and 23 contain combination ratings
for 38AH024-034 units and matching 40RM air handlers. If the 38AH units are matched with 39L or 39NX air
handlers, use the Carrier AHU (Air-Handling Unit) selection program software package for combination ratings. If
Totalinet P702 water coolers are used, determine the performance by cross-plotting the condensing unit performance
found in this book against the P702 performance in the
P702 product data book. If the 38AH condensing units are
matched with 2 independent 40RM units, cross-plot for performance ratings or contact Carrier Application Engineering for assistance.
I Determine cooling load, evaporator-air temperature and quantity.
Given:
Total Cooling Capacity
Required (TC) . . . . . . . . . . . . . . . . . . . . . . . . . 60 kW
Sensible Heat Capacity
Required (SHC) . . . . . . . . . . . . . . . . . . . . . . . 48 kW
Temperature Air Entering
Condenser (Edb) . . . . . . . . . . . . . . . . . . . . . . . . 36 C
Temperature Air Entering
Evaporator (db/wb) . . . . . . . . 26.7 C db, 20 C wb
Evaporator Air Quantity . . . . . . . . . . . . . . . 3800 L/s
External Static Pressure . . . . . . . . . . . . . . . . . . 150 Pa
Length of Interconnecting
Refrigerant Piping . . . . . . . . . . . . . . . 18 m (Linear)
II Select condensing unit air-handler combination.
For this example, select a 38AH024 matched with a
40RM024. (See Combination Ratings table, page 22)
This 38AH024/40RM024 condensing unit-air handler combination provides 62.5 kW of total cooling
capacity and 49.2 kW of sensible capacity at the given
conditions. If other temperatures or airflow values are
required, interpolate the values from the combination
ratings.
16
Selection procedure
38AH024-034/40RM English
NOTE: Pages 24 and 25 contain combination ratings for
38AH024-034 units and matching 40RM air handlers. If
the 38AH units are matched with 39L or 39NX air
handlers, use the Carrier AHU (Air-Handling Unit) selection
program software package for combination ratings. If
Totalinet P702 water coolers are used, determine the performance by cross-plotting the condensing unit performance
found in this book against the P702 performance in the
P702 product data book. If the 38AH condensing units are
matched with 2 independent 40RM units, cross-plot for performance ratings or contact Carrier Application Engineering for assistance.
I Determine cooling load, evaporator-air temperature and quantity.
Given:
Total Cooling Capacity
Required (TC) . . . . . . . . . . . . . . . . . . 210,000 Btuh
Sensible Heat Capacity
Required (SHC) . . . . . . . . . . . . . . . . . 175,000 Btuh
Temperature Air Entering
Condenser (Edb) . . . . . . . . . . . . . . . . . . . . . . . . 95 F
Temperature Air Entering
Evaporator (db/wb) . . . . . . . . . . . 80 F db, 67 F wb
Evaporator Air Quantity . . . . . . . . . . . . . . . 8000 cfm
External Static Pressure . . . . . . . . . . . . . . . 1.0 in. wg
Length of Interconnecting
Refrigerant Piping . . . . . . . . . . . . . . . . 30 ft (Linear)
II Select condensing unit air-handler combination.
For this example, select a 38AH024 matched with a
40RM024. (See Combination Ratings table, page 24.)
This 38AH024/40RM024 condensing unit-air handler combination provides 214,500 Btuh of total cooling capacity and 179,000 Btuh of sensible capacity at
the given conditions. If other temperatures or airflow
values are required, interpolate the values from the combination ratings.
17
10
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
38AH034
24
42.9
11.3
35.2
47.0
11.5
35.2
51.4
11.7
35.2
55.5
11.9
35.6
59.9
12.1
36.2
64.3
12.3
36.9
69.2
12.5
37.7
74.1
12.8
38.5
78.9
13.0
39.2
52
25.7
14.2
63.2
28.8
14.9
63.2
31.8
15.6
63.2
35.5
16.3
63.2
39.3
16.9
63.2
42.9
17.5
63.1
46.8
18.1
63.6
50.7
18.8
64.1
54.7
19.4
64.7
38AH028
SST
(C)
6
10
18
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
24
51.1
13.4
35.4
55.2
13.8
36.0
59.7
14.1
36.5
64.5
14.4
37.1
69.3
14.7
37.8
74.0
15.0
38.8
79.4
15.3
39.6
85.0
15.7
40.5
90.6
16.0
41.5
52
33.3
17.7
63.1
37.0
18.4
63.0
40.5
19.1
63.1
43.9
19.8
63.4
47.9
20.6
64.0
51.6
21.3
64.4
55.6
22.2
65.1
59.8
22.9
65.7
64.0
23.6
66.4
SST
(C)
6
10
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
24
59.8
16.6
35.9
65.5
17.0
36.1
70.8
17.3
36.2
76.4
17.6
36.8
82.2
18.0
37.5
88.0
18.4
38.2
94.4
18.9
39.0
100.8
19.4
39.9
107.3
19.6
40.9
LEGEND
CMP Compressor Power, kW
SDT Saturated Discharge Temperature (leaving compressor) (C)
SST Saturated Suction Temperature (entering condensing unit)
TCG Total Cooling Capacity, Gross (kW)
NOTES:
1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.
52
39.5
21.8
63.8
43.5
22.7
63.8
47.7
23.5
63.9
52.2
24.5
63.8
57.0
25.3
64.0
61.7
26.2
64.2
66.7
27.1
64.8
71.7
28.0
65.4
76.8
29.0
66.0
CMP
SDT
SST
TCG
LEGEND
Compressor Power, kW
Saturated Discharge Temperature (leaving compressor) (C)
Saturated Suction Temperature (entering condensing unit)
Total Cooling Capacity, Gross (kW)
52
12.8
7.1
63.2
14.4
7.5
63.2
15.9
7.8
63.2
17.7
8.2
63.2
19.7
8.5
63.2
21.4
8.8
63.1
23.4
9.1
63.6
25.4
9.4
64.1
27.3
9.7
64.7
52
15.6
8.9
63.2
17.4
9.2
63.2
19.1
9.6
63.4
21.2
9.9
63.2
23.4
10.2
63.0
25.5
10.5
62.9
27.7
10.9
63.4
29.9
11.2
63.8
32.3
11.5
64.3
52
16.7
8.9
63.1
18.5
9.2
63.0
20.3
9.5
63.1
22.0
9.9
63.4
23.9
10.3
64.0
25.8
10.7
64.4
27.8
11.1
65.1
29.9
11.4
65.7
32.0
11.8
66.4
52
23.9
13.0
64.4
26.1
13.4
64.5
28.6
13.9
64.3
31.0
14.5
64.4
33.6
15.1
65.0
36.1
15.7
65.4
38.9
16.2
66.2
41.7
16.8
66.9
44.5
17.4
67.7
NOTES:
1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.
19
25
30
35
40
45
50
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
38AH034
75
141.8
11.4
95.0
161.6
11.7
95.0
181.6
11.9
95.0
202.4
12.2
97.0
223.0
12.5
98.0
247.6
12.8
101.0
268.0
13.1
103.0
Air Temperature
85
95
130.6
119.0
11.7
12.4
105.0
115.0
149.4
136.8
12.1
12.9
105.0
115.0
168.2
154.8
12.5
13.5
105.0
115.0
188.4
174.4
12.9
14.0
107.0
116.0
208.0
194.0
13.4
14.5
108.0
117.0
232.0
216.0
13.8
15.0
110.0
119.0
254.0
236.0
14.2
15.6
112.0
121.0
Entering
100
113.2
12.7
120.0
130.6
13.3
120.0
148.0
13.9
120.0
167.4
14.5
121.0
186.8
15.0
122.0
208.0
15.6
123.0
228.0
16.2
125.0
Condenser (F)
105
115
107.4
96.2
12.9
13.3
125.0
135.0
124.4
112.0
13.6
14.2
125.0
135.0
141.4
128.0
14.3
15.0
125.0
135.0
160.4
146.4
14.9
15.8
126.0
135.0
179.6
165.0
15.6
16.5
126.0
136.0
200.0
184.4
16.2
17.3
128.0
137.0
220.0
204.0
16.8
18.0
130.0
139.0
125
84.8
13.8
145.0
99.6
14.8
145.0
114.6
15.8
145.0
132.4
16.6
145.0
150.5
17.5
146.0
168.6
18.4
146.0
188.0
19.3
148.0
38AH028
SST
(F)
20
25
30
35
40
45
50
20
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
75
168.4
13.5
95.0
189.0
13.9
97.0
210.2
14.3
98.0
231.6
14.8
99.0
256.8
15.1
102.0
284.0
15.7
104.0
306.0
16.0
106.0
Air Temperature
85
95
157.6
145.6
14.1
15.0
105.0
115.0
177.4
164.6
14.6
15.7
106.0
116.0
197.4
183.8
15.2
16.3
107.0
117.0
220.0
204.0
15.7
17.0
109.0
118.0
242.0
226.0
16.3
17.7
111.0
120.0
266.0
250.0
16.9
18.3
113.0
122.0
292.0
272.0
17.4
19.0
115.0
124.0
Entering
100
139.8
15.4
120.0
158.4
16.1
121.0
177.2
16.8
121.0
197.6
17.6
123.0
218.0
18.3
125.0
242.0
19.0
127.0
264.0
19.8
129.0
Condenser (F)
105
115
134.0
122.8
15.8
16.6
125.0
135.0
152.2
140.2
16.6
17.4
126.0
135.0
170.6
157.4
17.3
18.3
126.0
136.0
190.4
176.4
18.1
19.2
128.0
137.0
210.0
195.2
18.9
20.2
129.0
138.0
232.0
216.0
19.7
21.0
131.0
140.0
256.0
238.0
20.6
22.0
133.0
142.0
125
111.4
17.4
145.0
128.0
18.3
145.0
144.2
19.3
146.0
162.6
20.3
147.0
179.8
21.5
147.0
199.0
22.3
149.0
221.0
23.5
151.0
SST
(F)
20
25
30
35
40
45
50
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
75
198.0
16.6
97.0
223.5
17.1
97.0
249.4
17.6
97.0
276.2
18.0
99.0
304.5
18.7
101.0
335.0
19.3
103.0
367.0
19.7
106.0
Air Temperature
85
95
185.5
171.2
17.4
18.5
107.0
117.0
209.4
194.4
18.1
19.3
107.0
117.0
234.3
217.7
18.7
20.1
107.0
117.0
260.0
243.0
19.4
20.8
109.0
118.0
287.0
269.0
20.0
21.7
110.0
119.0
316.0
297.0
20.7
22.6
112.0
121.0
346.0
325.0
21.4
23.4
115.0
124.0
Entering
100
164.4
19.0
122.0
187.0
19.8
122.0
210.0
20.7
122.0
235.5
21.5
123.0
260.0
22.4
124.0
287.0
23.3
126.0
314.0
24.3
128.0
Condenser (F)
105
115
157.6
144.4
19.5
20.4
127.0
137.0
179.6
165.3
20.5
21.5
127.0
137.0
202.3
186.0
21.3
22.5
127.0
137.0
226.5
209.8
22.2
23.6
128.0
137.0
251.0
233.5
23.2
24.7
129.0
138.0
278.0
259.0
24.2
25.8
130.0
140.0
305.0
283.0
25.2
27.0
133.0
141.0
LEGEND
CMP Compressor Power, kW
SDT Saturated Discharge Temperature (leaving compressor) (F)
SST Saturated Suction Temperature (entering condensing unit)
TCG Total Cooling Capacity, Gross (1000 Btuh)
NOTES:
1. Ratings are based on 15 F superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.
125
131.0
21.4
147.0
150.8
22.6
147.0
170.2
23.8
147.0
193.2
25.0
147.0
215.8
26.2
147.0
240.0
27.4
149.0
262.0
28.8
150.0
Entering
100
56.6
6.3
120.0
65.3
6.7
120.0
74.0
7.0
120.0
83.7
7.2
121.0
93.4
7.5
122.0
104.0
7.8
123.0
114.0
8.1
125.0
Condenser (F)
105
115
53.7
48.1
6.5
6.7
125.0
135.0
62.2
56.0
6.8
7.1
125.0
135.0
70.7
64.0
7.2
7.5
125.0
135.0
80.2
73.2
7.5
7.9
126.0
135.0
89.8
82.5
7.8
8.3
126.0
136.0
100.0
92.2
8.1
8.6
128.0
137.0
110.0
102.0
8.4
9.0
130.0
139.0
Entering
100
69.9
7.7
120.0
79.2
8.1
121.0
88.6
8.4
121.0
98.8
8.8
123.0
109.0
9.2
125.0
121.0
9.5
127.0
132.0
9.9
129.0
Condenser (F)
105
115
67.0
61.4
7.9
8.3
125.0
135.0
76.1
70.1
8.3
8.7
126.0
135.0
85.3
78.7
8.7
9.2
126.0
136.0
95.2
88.2
9.1
9.6
128.0
137.0
105.0
97.6
9.5
10.1
129.0
138.0
116.0
108.0
9.9
10.5
131.0
140.0
128.0
119.0
10.3
11.0
133.0
142.0
CMP
SDT
SST
TCG
LEGEND
Compressor Power, kW
Saturated Discharge Temperature (leaving compressor) (F)
Saturated Suction Temperature (entering condensing unit)
Total Cooling Capacity, Gross (1000 Btuh)
125
42.4
6.9
145.0
49.8
7.4
145.0
57.3
7.9
145.0
66.2
8.3
145.0
75.3
8.8
146.0
84.3
9.2
146.0
94.0
9.6
148.0
Entering
100
67.1
7.7
120.0
77.0
8.0
120.0
87.0
8.4
120.0
98.5
8.6
121.0
110.0
8.9
121.0
122.0
9.2
123.0
134.0
9.5
125.0
Condenser (F)
105
115
64.0
58.0
7.9
8.3
125.0
135.0
73.6
67.0
8.3
8.7
125.0
135.0
83.3
76.0
8.6
9.1
125.0
135.0
94.5
86.8
8.9
9.5
126.0
135.0
106.0
97.5
9.2
9.9
126.0
135.0
118.0
109.0
9.6
10.3
127.0
137.0
130.0
120.0
9.9
10.7
129.0
138.0
125
51.9
8.7
145.0
60.3
9.2
145.0
68.7
9.7
145.0
79.2
10.1
145.0
89.3
10.5
145.0
100.0
11.0
147.0
110.5
11.5
147.0
125
55.7
8.7
145.0
64.0
9.2
145.0
72.1
9.7
146.0
81.3
10.2
147.0
89.9
10.7
147.0
99.5
11.2
149.0
110.5
11.8
151.0
Entering
100
97.3
11.3
123.0
110.0
11.8
123.0
123.0
12.3
123.0
137.0
12.9
125.0
150.0
13.5
127.0
165.0
14.1
129.0
180.0
14.8
131.0
Condenser (F)
105
115
93.6
86.4
11.6
12.1
128.0
138.0
106.0
98.3
12.2
12.8
128.0
138.0
119.0
110.0
12.7
13.4
128.0
138.0
132.0
123.0
13.3
14.1
129.0
139.0
145.0
136.0
14.0
14.8
131.0
140.0
160.0
150.0
14.6
15.5
133.0
142.0
175.0
163.0
15.3
16.3
136.0
144.0
125
79.1
12.7
148.0
90.5
13.5
148.0
101.5
14.1
148.0
114.0
14.9
149.0
126.5
15.7
149.0
140.0
16.4
151.0
151.5
17.4
153.0
NOTES:
1. Ratings are based on 15 F superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.
21
28
32
36
40
44
48
52
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
28
32
36
40
44
48
52
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
LEGEND
BF
Bypass Factor
Edb Entering Dry Bulb
Ewb Entering Wet-Bulb
kW Compressor Motor Power Input
Ldb Leaving Dry Bulb
Lwb Leaving Wet Bulb
SHC Sensible Heating Capacity (kW)
TC
Total Capacity (kW)
NOTES:
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate.
3. The SHC is based on 26.7 C db temperature of air entering the indoor unit. At
any other temperature, correct the SHC reading from the table of cooling capacities as follows:
Correction factor = 1.23 x 10-3 x (1 BF) x (db 26.7)
Above 26.7 C, add SHC correction to SHC. Below 26.7 C, subtract SHC correction from SHC.
22
28
32
36
40
44
48
52
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
3500/0.06
22
77.3
43.2
13.00
75.1
42.4
13.87
72.8
41.5
14.97
70.4
40.6
15.98
68.3
39.9
17.15
65.8
38.9
18.30
63.2
38.0
19.28
60.8
37.1
20.25
20
70.6
51.6
12.58
68.1
50.9
13.43
65.5
50.2
14.34
62.9
49.5
15.30
60.4
48.8
16.25
57.7
48.0
17.14
55.0
47.2
18.04
52.3
46.5
18.94
28
32
36
40
44
48
52
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
2900/0.06
22
77.4
40.4
15.16
75.6
39.7
16.26
73.4
38.8
17.36
71.3
38.0
18.51
69.1
37.1
19.61
66.9
36.2
20.78
64.7
35.4
21.75
62.0
34.3
23.63
20
71.9
47.5
14.77
70.1
46.8
15.96
68.1
45.9
16.95
66.0
45.1
17.98
63.9
44.2
18.96
61.7
43.4
20.11
59.6
42.5
21.06
57.2
41.5
22.55
28
32
36
40
44
48
52
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
28
32
36
40
44
48
52
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
LEGEND
BF
Bypass Factor
Edb Entering Dry Bulb
Ewb Entering Wet-Bulb
kW Compressor Motor Power Input
Ldb Leaving Dry Bulb
Lwb Leaving Wet Bulb
SHC Sensible Heating Capacity (kW)
TC
Total Capacity (kW)
NOTES:
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate.
3. The SHC is based on 26.7 C db temperature of air entering the indoor unit. At
any other temperature, correct the SHC reading from the table of cooling capacities as follows:
Correction factor = 1.23 x 10-3 x (1 BF) x (db 26.7)
Above 26.7 C, add SHC correction to SHC. Below 26.7 C, subtract SHC correction from SHC.
28
32
36
40
44
48
52
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
3500/0.06
22
93.1
49.1
18.80
90.8
48.2
20.03
88.5
47.4
21.40
86.0
46.5
22.88
83.6
45.6
24.24
81.1
44.6
25.66
78.4
43.6
27.17
75.8
42.7
28.74
20
88.9
56.8
18.47
86.1
56.0
19.66
83.4
55.2
20.89
80.5
54.4
22.30
77.6
53.6
23.49
74.7
52.8
24.72
71.7
51.9
25.99
68.7
51.1
27.45
28
32
36
40
44
48
52
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
4250/0.06
22
100.3
54.4
19.36
97.8
53.4
20.59
95.1
52.4
22.06
92.3
51.3
23.53
89.6
50.3
24.99
86.8
49.2
26.50
83.7
48.0
28.11
80.9
46.9
29.65
20
92.2
65.3
18.73
89.6
64.2
19.93
86.9
63.1
21.24
84.1
61.9
22.67
81.3
60.7
23.95
78.5
59.6
25.28
75.5
58.3
26.66
72.6
57.1
28.16
23
95
100
105
115
125
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
95
100
105
115
125
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
LEGEND
BF
Bypass Factor
Edb Entering Dry Bulb
Ewb Entering Wet-Bulb
kW Compressor Motor Power Input
Ldb Leaving Dry Bulb
Lwb Leaving Wet Bulb
SHC Sensible Heating Capacity (1000 Btuh)
TC
Total Capacity (1000 Btuh)
NOTES:
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate.
3. The SHC is based on 80 F dry-bulb temperature of air entering the evaporator
coil.
Below 80 F dry-bulb, subtract (correction factor cfm) from SHC.
Above 80 F dry bulb, add (correction factor cfm) to SHC.
79
81
0.10
0.20
0.30
0.99
0.88
0.77
Interpolation is permissible.
Correction Factor = 1.1 x (1 BF) x (db 80).
24
85
95
100
105
115
125
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
7500/0.04
72
252.4
140.1
14.14
240.2
135.6
15.55
234.0
133.3
16.34
227.7
131.0
17.01
215.5
126.6
18.58
202.4
121.8
20.08
67
229.4
181.8
13.76
218.3
177.3
15.05
212.6
175.0
15.73
206.7
172.6
16.40
195.1
167.9
17.74
182.9
163.0
19.11
BYPASS
FACTOR
Temp (F)
Air
Entering
Condenser
Temp (F)
Air
Entering
Condenser
85
95
100
105
115
125
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
6,000/0.03
72
256.2
131.8
16.65
246.0
127.9
18.20
240.9
126.0
18.97
234.4
123.5
19.79
223.6
119.4
21.29
196.6
109.1
23.11
67
235.7
166.7
16.14
225.8
162.6
17.70
220.9
160.6
18.38
215.6
158.5
19.10
205.8
154.4
20.61
180.3
144.0
22.43
1.1 x cfm
tlwb = wet-bulb temperature corresponding to enthalpy of air leaving
evaporator coil (hlwb)
hlwb = hewb
95
100
105
115
115
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
95
100
105
115
125
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
LEGEND
BF
Bypass Factor
Edb Entering Dry Bulb
Ewb Entering Wet-Bulb
kW Compressor Motor Power Input
Ldb Leaving Dry Bulb
Lwb Leaving Wet Bulb
SHC Sensible Heating Capacity (1000 Btuh)
TC
Total Capacity (1000 Btuh)
NOTES:
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate.
3. The SHC is based on 80 F dry-bulb temperature of air entering the evaporator
coil.
Below 80 F dry-bulb, subtract (correction factor cfm) from SHC.
Above 80 F dry bulb, add (correction factor cfm) to SHC.
79
81
0.10
0.20
0.30
0.99
0.88
0.77
85
95
100
105
115
125
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
7,500/0.04
72
307.8
160.5
20.50
295.9
156.1
22.57
289.5
153.7
23.38
283.7
151.6
24.41
271.0
146.9
26.32
257.9
142.1
28.29
67
283.0
203.4
19.90
271.4
198.7
21.78
265.4
196.3
22.58
259.5
193.9
23.52
247.4
189.0
25.30
234.9
184.0
27.15
BYPASS
FACTOR
Temp (F)
Air
Entering
Condenser
Temp (F)
Air
Entering
Condenser
85
95
100
105
115
125
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
267.4 264.1
234.6 183.6 243.5 251.1
267.4 264.1
27.14 29.48 28.28 27.95
28.76 28.59
9,000/0.04
72
328.6
176.4
21.00
315.5
171.4
23.19
308.2
168.7
24.01
302.1
166.3
25.09
287.9
161.0
27.05
273.5
155.5
29.06
67
301.1
228.6
20.34
288.3
223.5
22.32
281.5
220.8
23.12
275.2
218.3
24.10
261.8
213.0
25.92
247.9
207.5
27.79
1.1 x cfm
tlwb = wet-bulb temperature corresponding to enthalpy of air leaving
evaporator coil (hlwb)
hlwb = hewb
Interpolation is permissible.
Correction Factor = 1.1 x (1 BF) x (db 80).
25
UNIT AIRFLOW
40RM
(L/s)
2100
2800
3500
2900
3800
4700
3500
4700
5900
4250
5650
7050
016
024
028
034
1-ROW
STEAM*
2-ROW
HOT WATER COIL
Water
PD
Cap. (kW) Ldb Cap. (kW) Ldb Flow (kPa)
(L/s)
117
61
120
62
2.6
13.3
129
53
137
55
3.0
16.2
140
48
154
51
3.3
19.5
135
53
150
58
3.3
15.6
140
46
170
52
3.7
18.6
146
41
191
49
4.1
22.3
149
50
189
60
4.1
16.9
166
44
218
53
4.7
20.8
183
41
247
50
5.4
25.4
164
47
215
57
4.7
18.5
180
41
247
51
5.4
22.8
196
38
278
48
6.0
27.7
LEGEND
Cap. Capacity (kW)
Ldb Leaving-Air Dry-Bulb Temp (C)
PD
Pressure Drop (kPa)
*Based on 34.5 kPag steam, 15.6 C entering-air temperature. All steam
coils are non-freeze type.
Based on 93.3 C entering-water temperature, 11.1 C water temperature drop, 15.6 C entering-air temperature.
NOTES:
1. Maximum operating limit for heating coils: 1207 kPag at 204.4 C.
Capacity (kW)
2. Leaving db = ent db (C) +
1.23 x 10-3 x L/s
3. See Heating Correction Factors table.
11
16
HOT
Ent Water
Temp
(C)
60
70
80
90
100
60
70
80
90
100
60
70
80
90
100
Steam Pressure
(kPag)
0
14
35
AIRFLOW
(Cfm)
4,500
6,000
7,500
6,000
8,000
10,000
7,500
10,000
12,500
9,000
12,000
15,000
016
024
028
034
10
16
20
25
0.72
0.87
1.02
1.17
1.32
0.65
0.80
0.95
1.10
1.26
0.56
0.72
0.87
1.02
1.18
0.64
0.79
0.94
1.09
1.24
0.56
0.72
0.87
1.02
1.18
0.48
0.63
0.79
0.94
1.10
0.55
0.71
0.86
1.01
1.16
0.48
0.63
0.79
0.94
1.09
0.39
0.55
0.70
0.86
1.02
0.50
0.65
0.80
0.95
1.10
0.42
0.58
0.73
0.89
1.04
0.33
0.49
0.65
0.81
0.97
0.43
0.58
0.73
0.89
1.04
0.35
0.51
0.66
0.82
0.97
0.26
0.42
0.58
0.74
0.90
STEAM COIL
Entering-Air Temp (C)
4
10
16
20
1.07
0.99
0.91
0.86
1.10
1.02
0.95
0.90
1.14
1.07
0.99
0.95
1-ROW
STEAM*
Cap. Ldb
402
141
458
129
479
118
458
129
487
115
499
105
511
122
575
112
626
106
560
117
621
107
670
101
2-ROW
HOT WATER COIL
Cap.
Ldb Gpm
PD
412.0
145
41.2
4.5
471.0
133
47.1
5.5
529.0
125
52.9
6.6
506.0
138
50.6
5.1
584.0
128
58.4
6.3
652.0
120
65.2
7.5
649.0
140
64.9
5.7
752.0
130
75.2
7.1
842.0
122
84.2
8.5
735.0
136
73.5
6.2
850.0
126
85.0
7.8
950.0
119
95.0
9.3
LEGEND
Cap. Capacity (Btuh in thousands)
Ldb Leaving-Air Dry-Bulb Temp (F)
PD
Pressure Drop (ft water)
*Based on 5 psig steam, 60 F entering-air temperature. All steam coils
are non-freeze type.
Based on 200 F entering water, 20 F water temperature drop, 60 F
entering-air temperature.
NOTES:
1. Maximum operating limit for heating coils: 175 psig at 400 F.
Capacity (Btuh)
2. Leaving db = ent db (F) +
1.1 x cfm
3. See Heating Correction Factors table.
WATER COIL
25
0.80
0.84
0.89
26
UNIT
40RM
Water Temp
Drop
(F)
10
20
30
HOT
Ent Water
Temp
(F)
140
160
180
200
220
140
160
180
200
220
140
160
180
200
220
Steam Pressure
(psig)
0
2
5
WATER COIL
Entering-Air Temp (F)
40
50
60
70
80
0.72
0.89
1.06
1.22
1.39
0.64
0.81
0.98
1.15
1.32
0.56
0.74
0.91
1.08
1.25
0.64
0.81
0.98
1.15
1.32
0.57
0.74
0.91
1.08
1.25
0.49
0.66
0.83
1.00
1.18
0.57
0.74
0.90
1.07
1.24
0.49
0.66
0.83
1.00
1.17
0.41
0.58
0.76
0.93
1.10
0.49
0.66
0.83
1.00
1.17
0.41
0.58
0.75
0.93
1.10
0.33
0.51
0.68
0.85
1.03
0.41
0.58
0.75
0.92
1.09
0.33
0.51
0.68
0.85
1.02
0.24
0.43
0.60
0.78
0.95
STEAM COIL
Entering-Air Temp (F)
40
50
60
70
1.06
0.98
0.91
0.85
1.09
1.02
0.95
0.89
1.13
1.06
1.00
0.93
80
0.78
0.82
0.87
016
024
028
034
AIRFLOW
(L/s)
50
2100
r/s
6.43
kW
0.37
r/s
8.19
kW
0.55
2450
7.51
0.57
9.06
0.77
0.97
250
r/s
kW
13.10
1.30
300
r/s
kW
14.10
1.50
11.60
1.18
12.70
1.39
13.70
1.60
14.60
1.81
2800
8.58
0.82
9.96
1.05
11.20
1.27
12.30
1.49
13.30
1.72
14.30
1.95
15.10
2.18
3150
9.65
1.14
10.90
1.38
12.00
1.63
13.10
1.87
14.00
2.12
14.90
2.36
15.80
2.61
3500
10.70
1.52
11.90
1.78
12.90
2.05
13.90
2.31
14.80
2.58
15.60
2.84
16.40
3.11
2900
8.58
0.86
9.96
1.09
11.20
1.32
12.30
1.55
13.30
1.78
14.20
2.01
15.10
2.25
3350
9.91
1.28
11.10
1.53
12.20
1.79
13.20
2.04
14.20
2.30
15.10
2.55
15.90
2.81
3800
11.30
1.81
12.30
2.09
13.30
2.37
14.30
2.64
15.10
2.93
16.00
3.21
16.80
3.49
4250
12.60
2.46
13.60
2.76
14.50
3.07
15.30
3.37
16.10
3.67
16.90
3.98
17.70
4.28
4700
13.90
3.24
14.80
3.57
15.60
3.90
16.40
4.22
17.20
4.55
17.90
4.88
18.60
5.21
3500
6.79
0.84
8.14
1.12
9.42
1.47
10.70
1.89
11.80
2.39
12.90
2.96
14.00
3.61
4100
7.95
1.29
9.12
1.60
10.20
1.96
11.30
2.38
12.40
2.86
13.40
3.40
14.30
4.00
4700
9.12
1.88
10.10
2.21
11.10
2.59
12.10
3.02
13.00
3.49
13.90
4.02
14.80
4.60
5300
10.30
2.62
11.20
3.00
12.10
3.37
12.90
3.81
13.80
4.29
14.60
4.82
15.40
5.38
5900
11.40
3.52
12.30
3.90
13.10
4.32
13.90
4.77
14.60
5.26
15.40
5.79
16.10
6.35
4250
7.86
1.33
8.99
1.63
10.10
1.97
11.10
2.37
12.20
2.83
13.20
3.34
14.10
3.92
4950
9.15
2.03
10.10
2.35
11.10
2.72
12.00
3.12
12.90
3.58
13.80
4.08
14.70
4.62
5650
10.40
2.92
11.30
3.27
12.20
3.66
13.00
4.08
13.80
4.54
14.60
5.04
15.40
5.57
6350
11.70
4.02
12.50
4.40
13.30
4.81
14.00
5.25
14.70
5.72
15.50
6.23
16.20
6.77
7050
13.00
5.37
13.70
5.77
14.40
6.21
15.10
6.66
15.70
7.15
16.40
7.67
17.10
8.21
LEGEND
ESP External Static Pressure
UNIT
40RM
016
024
028
034
AIRFLOW
(L/s)
2100
2800
3500
2900
3800
4700
3500
4700
5900
4250
5650
7050
PRESSURE DROP
(Pa)
20
30
42
32
47
64
36
55
76
47
71
98
27
016
024
028
034
AIRFLOW
(L/s)
350
400
2100
r/s
15.00
kW
1.70
r/s
15.80
kW
1.90
2450
15.50
2.03
16.30
2.25
17.10
2800
16.00
2.42
16.80
2.66
17.60
2.90
3150
16.60
2.87
17.40
3.12
18.10
3.38
3500
17.20
3.38
18.00
3.65
18.70
3.93
2900
16.00
2.49
16.80
2.73
17.50
3350
16.70
3.08
17.50
3.34
3800
17.50
3.77
18.20
4.06
18.60
2.93
19.30
3.16
18.30
3.14
19.00
3.38
19.70
3.63
18.80
3.64
19.50
3.90
19.40
4.20
2.97
18.30
3.22
19.00
3.47
19.70
18.20
3.61
18.90
3.87
19.60
4.14
18.90
4.35
19.60
4.64
3.72
4250
18.40
4.59
19.10
4.90
19.80
5.21
4700
19.30
5.54
20.00
5.87
3500
15.10
4.33
16.10
5.12
17.10
5.98
18.00
6.92
4100
15.30
4.67
16.20
5.39
17.10
6.18
18.00
7.02
4700
15.70
5.23
16.50
5.91
17.40
6.64
18.20
7.43
5300
16.20
5.99
17.00
6.65
17.80
7.35
5900
16.90
6.95
17.60
7.59
18.30
8.27
4250
15.00
4.55
16.00
5.24
16.80
5.99
17.70
6.79
4950
15.50
5.22
16.30
5.86
17.10
6.56
17.90
7.30
5650
16.10
6.16
16.90
6.77
17.60
7.43
18.30
8.13
6350
16.90
7.34
17.50
7.94
18.20
8.58
7050
17.70
8.79
18.30
9.39
LEGEND
ESP External Static Pressure
28
kW
2.74
2.70
2.47
17.80
600
r/s
18.90
UNIT
40RM
016
024
028
034
AIRFLOW
(L/s)
2100
2800
3500
2900
3800
4700
3500
4700
5900
4250
5650
7050
PRESSURE DROP
(Pa)
20
30
42
32
47
64
36
55
76
47
71
98
016
024
028
034
4,500
Rpm
391
Bhp
0.51
Rpm
495
Bhp
0.75
5,300
460
0.80
551
1.08
629
1.35
700
1.63
764
AIRFLOW
(Cfm)
0.0
0.2
1.0
1.2
Rpm
787
Bhp
1.76
Rpm
845
Bhp
2.02
1.91
823
2.20
878
2.48
6,000
521
1.13
602
1.43
675
1.73
741
2.04
801
2.34
858
2.65
911
2.96
6,800
590
1.60
663
1.93
730
2.26
791
2.59
847
2.92
901
3.26
951
3.60
7,500
651
2.10
718
2.45
779
2.81
837
3.16
890
3.52
941
3.88
990
4.24
6,000
503
1.07
587
1.37
661
1.67
727
1.97
789
2.28
846
2.59
900
2.90
7,000
586
1.64
660
1.98
726
2.31
787
2.65
844
2.99
898
3.33
948
3.67
8,000
670
2.37
735
2.74
795
3.12
851
3.49
904
3.86
954
4.23
1001
4.61
9,000
754
3.28
812
3.69
867
4.09
918
4.50
967
4.90
1014
5.31
1059
5.72
10,000
838
4.39
891
4.83
941
5.27
988
5.70
1034
6.14
1077
6.85
1120
7.02
7,500
412
1.15
492
1.53
568
2.00
640
2.56
710
3.22
776
3.98
840
4.83
8,750
481
1.76
550
2.17
616
2.66
680
3.22
742
3.86
802
4.58
860
5.38
10,000
549
2.55
610
2.99
669
3.50
726
4.07
782
4.70
836
5.40
889
6.17
11,250
618
3.52
672
4.00
725
4.53
777
5.12
827
5.76
876
6.45
925
7.21
12,500
687
4.71
735
5.22
783
5.78
830
6.38
876
7.04
922
7.74
966
8.49
9,000
471
1.78
539
2.17
604
2.63
667
3.17
728
3.78
788
4.46
845
5.22
10,500
550
2.72
608
3.15
665
3.64
720
4.18
774
4.79
827
5.45
878
6.18
12,000
628
3.93
679
4.40
730
4.92
779
5.48
827
6.09
874
6.76
921
7.47
13,500
707
5.44
752
5.94
797
6.49
841
7.08
885
7.71
928
8.38
970
9.10
15,000
785
7.27
826
7.81
867
8.39
907
9.01
947
9.66
986
10.35
1024
11.07
LEGEND
ESP External Static Pressure
UNIT
40RM
016
024
028
034
AIRFLOW
(Cfm)
4,500
6,000
7,500
6,000
8,000
10,000
7,500
10,000
12,500
9,000
12,000
15,000
PRESSURE DROP
(in. wg)
0.08
0.12
0.17
0.12
0.19
0.26
0.15
0.22
0.30
0.19
0.29
0.40
29
016
024
028
034
AIRFLOW
(Cfm)
1.4
1.6
4,500
Rpm
899
Bhp
2.29
Rpm
951
5,300
930
2.78
980
6,000
961
3.28
6,800
999
3.94
7,500
1036
6,000
2.4
Bhp
3.41
Rpm
1133
Bhp
3.70
3.08
1027
3.38
1072
3.68
1116
3.99
1157
4.30
1009
3.60
1055
3.92
1098
4.24
1141
4.57
1181
4.91
1045
4.28
1089
4.63
1132
4.98
1173
5.33
4.60
1080
4.97
1123
5.34
1164
5.71
950
3.21
999
3.53
1045
3.85
1089
4.17
1131
4.50
1172
4.83
7,000
996
4.02
1042
4.37
1086
4.72
1129
5.07
1169
5.43
8,000
1047
4.99
1091
5.37
1133
5.75
1173
6.13
9,000
1102
6.13
1143
6.54
1183
6.96
10,000
1160
7.46
1200
7.91
7,500
903
5.79
963
6.83
1021
7.98
1078
9.21
8,750
917
6.26
972
7.22
1025
8.26
1078
9.38
10,000
941
7.01
991
7.91
1040
8.89
1089
9.93
11,250
972
8.02
1019
8.89
1064
9.83
12,500
1010
9.29
1053
10.15
1095
11.05
9,000
901
6.07
955
6.98
1008
7.98
1060
9.05
10,500
928
6.98
978
7.84
1026
8.76
1073
9.74
12,000
966
8.24
1011
9.07
1055
9.95
1098
10.88
13,500
1011
9.86
1052
10.67
1092
11.52
15,000
1062
11.84
LEGEND
ESP External Static Pressure
UNIT
40RM
Refer to fan motor and drive tables, pages 41-43, to complete the
selection.
016
NOTES:
1. Maximum allowable fan speed is 1100 rpm for unit sizes 028 and
034; 1200 rpm for all other sizes.
2. Fan performance is based on deductions for wet coil, clean 2-in.
filters, and unit casing. See right for factory-supplied filter pressure
drop.
3. The standard motor and medium-static drive combination is not available for 40RM016-028 units. Use the alternate motor if the mediumstatic drive is required for these sizes.
30
2.2
Rpm
1091
024
028
034
AIRFLOW
(Cfm)
4,500
6,000
7,500
6,000
8,000
10,000
7,500
10,000
12,500
9,000
12,000
15,000
PRESSURE DROP
(in. wg)
0.08
0.12
0.17
0.12
0.19
0.26
0.15
0.22
0.30
0.19
0.29
0.40
AIRFLOW
(L/s)
016
024
028
034
2800
3800
4700
5650
VANE DEFLECTION
Straight
2212
45
15.41
13.25
9.55
18.17
15.44
11.20
23.26
19.89
14.38
25.97
22.00
15.89
NOTE: Throw distances shown are for 0.381 m/sec terminal velocity.
Use the following multipliers to determine throw values for other terminal velocities.
TERMINAL VELOCITY
(m/sec)
0.254
0.508
0.762
UNIT
40RM
AIRFLOW
(Cfm)
016
024
028
034
6,000
8,000
10,000
12,000
VANE DEFLECTION
Straight
2212
45
50
43
31
60
51
37
76
65
47
85
72
52
NOTE: Throw distances shown are for 75 fpm terminal velocity. Use
the following multipliers to determine throw values for other terminal
velocities.
TERMINAL VELOCITY
(Fpm)
50
100
150
THROW FACTOR
X
X
X
1.50
0.75
0.50
THROW FACTOR
X
X
X
1.50
0.75
0.50
AIRFLOW
(L/s)
DISCHARGE
PLENUM
RETURN AIR
GRILLE
2100
2800
3500
2900
3800
4700
3500
4700
5900
4250
5650
7050
24
39
56
41
64
91
37
59
86
50
80
114
2
5
7
5
10
15
5
7
12
7
12
17
Hot Water
36
57
82
60
93
132
67
109
157
92
147
210
HEATING COILS
Steam
36
57
82
60
93
132
67
109
157
92
147
210
Electric
14
24
37
26
43
65
22
39
60
32
56
85
ECONOMIZER
15
22
37
23
43
69
15
22
35
20
35
52
AIRFLOW
(Cfm)
DISCHARGE
PLENUM
RETURN AIR
GRILLE
4,500
6,000
7,500
6,000
8,000
10,000
7,500
10,000
12,500
9,000
12,000
15,000
0.10
0.16
0.23
0.16
0.26
0.37
0.15
0.24
0.34
0.20
0.32
0.46
0.01
0.02
0.03
0.02
0.04
0.06
0.02
0.03
0.05
0.03
0.05
0.07
Hot Water
0.15
0.23
0.33
0.23
0.37
0.53
0.28
0.44
0.63
0.37
0.59
0.85
HEATING COILS
Steam
0.15
0.23
0.33
0.23
0.37
0.53
0.28
0.44
0.63
0.37
0.59
0.85
Electric
0.06
0.10
0.15
0.10
0.17
0.26
0.09
0.16
0.24
0.13
0.22
0.34
ECONOMIZER
0.06
0.09
0.15
0.09
0.17
0.28
0.06
0.09
0.14
0.08
0.14
0.21
31
LEGEND
TXV Thermostatic Expansion Valve
Piping
Double Riser Piping (If Required)
*Field supplied.
If double suction riser is required for piping system, size pipe diameter of 3 ft (maximum) riser
according to application data on page 40.
32
NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer to
Carrier System Design Manual for details.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are
not intended for, or to include all details for, a specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent
refrigerant migration to the compressor.
5. Internal factory-supplied TXVs not shown.
LEGEND
TXV Thermostatic Expansion Valve
Piping
*Field supplied.
NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer to
Carrier System Design Manual for details.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are
not intended for, or to include all details for, a specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent
refrigerant migration to the compressor.
33
VOLTAGE
DESIGNATION
NAMEPLATE
VOLTAGE
(3 Ph, 50 Hz)
803
903
303
803
903
303
803
903
303
230
400
346
230
400
346
230
400
346
024
028
034
SUPPLY
VOLTAGE*
POWER SUPPLY
COMPRESSOR
Min
Max
MCA
MOCP
ICF
198
342
311
198
342
311
198
342
311
254
400
380
254
400
380
254
400
380
101.2
46.5
62.8
110.9
55.7
68.2
135.9
65.1
78.1
125
60
80
150
70
90
175
90
110
268.8
204.0
194.8
298.8
234.0
216.8
355.8
240.0
257.8
RLA
Ckt 1 Ckt 2
39.3
39.3
18.0
18.0
24.0
24.0
43.6
43.6
22.1
22.1
26.4
26.4
43.6
63.6
22.1
30.0
26.4
34.3
LRA
Ckt 1 Ckt 2
128
128
99
99
93
93
143
143
114
114
104
104
143
200
114
120
104
145
FAN MOTORS
QTY
2
2
2
2
2
2
2
2
2
FLA
(ea)
6.4
3.0
4.4
6.4
3.0
4.4
6.4
3.0
4.4
Nominal
Hp
Nominal
kW
0.75
0.75
0.75
*Units are suitable for use on electrical systems where voltage supplied
to unit terminals is not below or above listed minimum and maximum.
All fans are protected by a single circuit breaker.
LEGEND
Full Load Amps
Maximum Instantaneous Current Flow During Starting. (The
point in the starting sequence where the sum of the LRA
for the starting compressor, plus the total RLA for all running compressors, plus the total FLA for all running fan
motors is maximum.)
LRA
Locked Rotor Amps
MCA Minimum Circuit Amps (complies with National Electrical
Code [NEC] Section 430-24) (U.S.A. Standard)
MOCP Maximum Overcurrent Protection
RLA
Rated Load Amps
FLA
ICF
V*-PH-HZ
VOLTAGE
LIMITS
230-3-50
400-3-50
230-3-50
400-3-60
230-3-50
400-3-50
230-3-50
400-3-50
207-253
360-440
207-253
360-440
207-253
360-440
207-253
360-440
LEGEND
FLA
Full Load Amps
MOCP Maximum Overcurrent Protection
*Motors are designed for satisfactory operation within 10% of nominal
voltages shown. Voltages should not exceed the limits shown in the
Voltage Limits column.
NOTES:
1. Minimum circuit amp and MOCP values are calculated in accordance
with NEC (National Electrical Code) (U.S.A. standard), Article 440.
2. Motor FLA values are established in accordance with UL (Underwriters Laboratories) Standard 1995 (U.S.A. standard).
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percentage of voltage imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
EXAMPLE: Supply voltage is 400-3-50.
AB = 393 v
BC = 403 v
AC = 396 v
393 + 403 + 396
Average Voltage =
3
1192
=
3
= 397
34
kW (Hp)
2.16
2.16
3.73
3.73
5.59
5.59
7.46
7.46
POWER SUPPLY
Minimum
Circuit
MOCP
Amps
9.4
15
4.3
15
19.0
30
9.5
15
28.5
50
14.3
25
40.3
70
20.1
30
FLA
(2.9)
(2.9)
(5.0)
(5.0)
(7.5)
(7.5)
(10.0)
(10.0)
7.5
3.4
15.2
7.6
22.8
11.4
32.2
16.1
V*-PH-HZ
VOLTAGE
LIMITS
230-3-50
400-3-50
230-3-50
400-3-50
230-3-50
400-3-50
207-253
360-440
207-253
360-440
207-253
360-440
LEGEND
FLA
Full Load Amps
MOCP Maximum Overcurrent Protection
*Motors are designed for satisfactory operation within 10% of nominal
voltages shown. Voltages should not exceed the limits shown in the
Voltage Limits column.
NOTES:
1. Minimum circuit amp and MOCP values are calculated in accordance
with NEC (National Electrical Code) (U.S.A. standard), Article 440.
2. Motor FLA values are established in accordance with UL (Underwriters Laboratories) Standard 1995 (U.S.A. standard).
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percentage of voltage imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
EXAMPLE: Supply voltage is 400-3-50.
AB = 393 v
BC = 403 v
AC = 396 v
393 + 403 + 396
Average Voltage =
3
1192
=
3
= 397
kW (Hp)
3.73
3.73
5.59
5.59
7.46
7.46
FLA
(5.0)
(5.0)
(7.5)
(7.5)
(10.0)
(10.0)
15.2
7.6
22.8
11.4
32.2
16.1
POWER SUPPLY
Minimum
Circuit
MOCP
Amps
19.0
30
9.5
15
28.5
50
14.3
25
40.3
60
20.1
30
VOLTAGE
(vac)
24
MAXIMUM
HOLDING
VA
10
35
HEATER
PART NO.
V-PH-Hz
CAELHEAT016A00
240-3-50
CAELHEAT017A00
400-3-50
CAELHEAT019A00
240-3-50
CAELHEAT020A00
400-3-50
CAELHEAT022A00
240-3-50
CAELHEAT023A00
400-3-50
CAELHEAT025A00
240-3-50
CAELHEAT026A00
400-3-50
CAELHEAT028A00
240-3-50
CAELHEAT029A00
400-3-50
CAELHEAT031A00
240-3-50
CAELHEAT032A00
400-3-50
CAELHEAT034A00
240-3-50
CAELHEAT035A00
400-3-50
CAELHEAT037A00
240-3-50
CAELHEAT038A00
400-3-50
016,024
028,034
ELECTRIC HEATERS(S)
FAN MOTOR
Hp
kW
FLA
2.9
5.0
7.5
2.9
5.0
7.5
2.9
5.0
7.5
2.9
5.0
7.5
2.9
5.0
7.5
2.9
5.0
7.5
2.9
5.0
7.5
2.9
5.0
7.5
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
2.16
3.73
5.59
2.16
3.73
5.59
2.16
3.73
5.59
2.16
3.73
5.59
2.16
3.73
5.59
2.16
3.73
5.59
2.16
3.73
5.59
2.16
3.73
5.59
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
7.5
15.2
22.8
3.4
7.6
11.4
7.5
15.2
22.8
3.4
7.6
11.4
7.5
15.2
22.8
3.4
7.6
11.4
7.5
15.2
22.8
3.4
7.6
11.4
22.8
32.2
11.4
16.1
22.8
32.2
11.4
16.1
22.8
32.2
11.4
16.1
22.8
32.2
11.4
16.1
Nominal
Capacity
(kW)
10
10
10
10
10
10
20
20
20
20
20
20
30
30
30
30
30
30
50
50
50
50
50
50
20
20
20
20
40
40
40
40
50
50
50
50
70
70
70
70
LEGEND
FLA
Full Load Amps
Hp
Horsepower
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection (Amps)
*Values shown are for single-point connection of electric heat accessory and air handler.
Single-phase motors. All other motors are 3-phase.
HEATER
RATING
VOLTAGE
240
480
575
36
Stage 2
Total
10.0
10.0
10.0
6.9
6.9
6.9
20.0
20.0
20.0
13.9
13.9
13.9
20.0
20.0
20.0
13.9
13.9
13.9
30.0
30.0
30.0
20.8
20.8
20.8
20.0
20.0
13.9
13.9
20.0
20.0
13.9
13.9
30.0
30.0
20.8
20.8
40.0
40.0
27.8
27.8
10.0
10.0
10.0
6.9
7.9
7.9
20.0
20.0
20.0
13.9
13.9
13.9
20.0
20.0
13.9
13.9
20.0
20.0
13.9
13.9
30.0
30.0
20.8
20.8
10.0
10.0
10.0
6.9
6.9
6.9
20.0
20.0
20.0
13.9
13.9
13.9
30.0
30.0
30.0
20.8
20.8
20.8
50.0
50.0
50.0
34.7
34.7
34.7
20.0
20.0
13.9
13.9
40.0
40.0
27.8
27.8
50.0
50.0
34.7
34.7
70.0
70.0
48.6
48.6
208
230
0.694
0.751
0.918
240
1
24.1
24.1
24.1
10.0
10.0
10.0
48.1
48.1
48.1
20.0
20.0
20.0
72.2
72.2
72.2
30.1
30.1
30.1
120.3
120.3
120.3
50.1
50.1
50.1
48.1
48.1
20.0
20.0
96.2
96.2
40.1
40.1
120.3
120.3
50.1
50.1
168.4
168.4
70.2
70.2
MCA*
MOCP*
39.4
49.1
58.6
16.8
22.0
26.8
69.5
79.1
86.4
29.3
45.1
49.2
99.6
109.2
118.7
41.8
47.1
51.8
159.7
169.4
178.9
66.9
72.1
76.9
88.6
100.4
39.3
45.2
148.8
160.5
64.4
70.2
178.9
190.6
76.9
82.8
196.9
208.6
84.4
90.3
40
50
70
20
25
35
70
80
90
30
50
50
100
110
125
50
50
60
175
175
200
70
80
80
90
110
40
50
150
175
70
80
200
200
80
90
200
225
90
100
NOTES:
1. Electrical resistance heaters are rated at 240 v, or 480 v. To determine heater capacity (kW) at unit nameplate multiply the 240-v, or
480-v, capacity (kW) by the factor shown in the table below for the
unit voltage.
2. The following equation converts kW of heat energy to Btuh:
kW x 3,412 = Btuh.
3. Heater contactor coils are 24 v and require 8 va holding current.
4. Electric heaters are tested and ETL approved at maximum total
external static pressure of 1.9 in. wg.
5. MCA and MOCP values apply to both standard and alternate factorysupplied motors.
FLA
400
440
460
480
0.694
0.84
0.918
Controls 38AH024-034
Operating sequence
Within 6 seconds to 5 minutes (depending on timing logic)
from a thermostat call for the first stage of cooling, compressor no. 1 and the condenser fans start. The no. 2 fan
only starts if the outdoor ambient temperature is above
21.1 C (70 F). The oil pressure switch and the low pressure
switch are bypassed for the first 2 minutes. If either the low
pressure switch or oil pressure switch remain open after
2 minutes, the unit shuts down and goes into a lockout mode.
The evaporator-fan motor starts immediately whenever there
is a call for cooling. If a liquid line solenoid valve has been
installed (for refrigerant control during the off cycle), then
the solenoid valve for compressor no. 1 opens immediately
upon a call for cooling.
On standard units, compressor no. 1 operates either fully
loaded or at one step of unloading, depending on the suction pressure, which is dependent on the evaporator load
conditions.
As the cooling demand increases, the thermostat calls for
the second stage of cooling. Within 6 seconds to 5 minutes
(depending on timing logic) from a call for the second stage
of cooling, compressor no. 2 starts. The oil switch and low
pressure switch for circuit no. 2 are bypassed for the first
two minutes.
37
38
230-3-50
346-3-50
400-3-50
230-1-50
**For a single air handler, LLS valve 1 is to be used on the lower (no. 1)
evaporator circuit. The LLS valve 2 is to be used on the upper (no. 2) evaporator circuit.
Only one indoor-fan contactor is required on single air-handler applications.
Use Carrier accessory part no. 40RR900181 for indoor-fan contactor.
UNIT
(V-Ph-Hz)
CONTROL CIRCUIT
PROTECTED AT:
(V-Ph-Hz)
NOTES:
1. CB4 protects TB3 circuit; CB5 protects TB2 circuits.
2. LLS1 and LLS2 are field supplied.
3. TB2 and TB3 are in 24-v circuits.
4. On the 33CSUCE-06 Relay Pack, the outside-air sensor, supply-air sensor, and direct expansion coil sensor are available as options.
CB
COM
IFC
LLS
NEC
RV
TB
LEGEND
Circuit Breaker
Common
Indoor-Fan Contactor
Liquid Line Solenoid
National Electrical Code
Reversing Valve
Terminal Block
Field Control Wiring
Factory Wiring
Field Power Wiring
Indicates Common
Potential; Does Not
Indicate Wiring
Installation
Select equipment to match or to be slightly less than peak
load. This provides better humidity control, less unit cycling,
and less part-load operation.
When selecting vapor line sizes, oil return must be evaluated, particularly at part-load conditions.
The indoor fan must always be operating when outdoor
unit is operating.
OPERATING LIMITS
Maximum Outdoor Ambient
Minimum Outdoor Ambient
Minimum Return-Air Temperature
Maximum Return-Air Temperature
Normal Acceptable Saturation
Suction Temperature Range
Maximum Discharge Temperature
Minimum Discharge Superheat
52C (125 F)
See Minimum OutdoorAir Operating Temperature
table below.
12.8 C (55 F)
35 C (95 F)
6.6 to 10.0 C (20 to 50 F)
135.0 C (275 F)
15.6 C (60 F)
UNLOADING SEQUENCES
CAPACITY/STAGE (%)
CV Units (Standard)*
VAV Units (Optional)
100, 83, 50, 33
100, 83, 67, 50, 33, 17
100, 83, 50, 33
100, 83, 67, 50, 33, 17
100, 85, 43, 28
100, 85, 77, 43, 28, 14
UNIT
38AH
024
028
034
LEGEND
CV Constant Volume
VAV Variable Air Volume
*Additional unloading available with field-installed accessory unloader.
NOTE: Capacities are based on 7.2 C (45 F) saturated suction temperature and 35 C (95 F) outdoor
air temperature.
024
028
034
SYSTEM
CAPACITY (%)
100
83
67
50
33
17
100
83
67
50
33
17
100
81
62
43
29
14
20
*
39
0-25 (0-7.6)
L
S
12
118
12
118
12
118
12
118
12
118
58
138
024 Ckt 1
Ckt 2
028 Ckt 1
Ckt 2
034 Ckt 1
Ckt 2
LEGEND
L Liquid Line
S Suction Line
*Double suction riser required if evaporator is below condensing unit
and 2 unloaders are used on that circuit.
Double suction riser required if evaporator is below condensing unit
and compressor is equipped with 2 unloaders. Note the only time
circuit no. 2 may be equipped with 2 unloaders is if it is serving its
own air handler and the unit does not require low ambient operation
(MotormasterT III control).
100-200 (30.5-61.0)
L
S
7 8
158*
7 8
158*
7 8
158*
7 8
158*
7 8
158*
7 8
218*
NOTES:
1. All line sizes are inches OD.
2. Standard unit comes with one pressure-operated unloader on circuit
no. 1. If unit serves one air handler, an additional unloader may be
field installed on circuit no. 1 compressor only. If the unit serves
2 separate air handlers and low ambient operation is required (Motormaster III control), each circuits compressor may only be equipped
with one unloader.
3. Equivalent line sizes in mm follow:
in.
12
58
78
118
mm
12.7
15.9
22.2
28.6
in.
138
158
218
mm
34.9
41.3
54.0
1
2
1
2
1
2
LEGEND
Suction Riser without Trap
Suction Riser with Trap
Suction Line to Condensing Unit
Pipe Diameter to be Same Size as Riser A
40
General
Select equipment to match or to be slightly less than peak
load. This provides better humidity control, less unit cycling,
and less part-load operation. Equipment should be selected
to perform at no less than 40 L/s per kW (300 cfm/ton).
TXV
Qty...Part No.
2...XVE-8
2...XVE-10
2...EBSVE-11
2...SVE-15
DISTRIBUTOR
Qty...Part No.
2...1116
2...1116
2...1126
2...1126
FEEDER TUBES
PER DISTRIBUTOR*
12
13
15
18
NOZZLE
Qty...Part No.
2...E6
2...E8
2...C10
2...C12
STANDARD MOTOR SI
UNIT
016
40RM
230-3-50 and 400-3-50
Speed (r/s)
23.75
Shaft kW
2.16
Frame (NEMA)
56Y
Shaft Dia (mm)
22.2
024
028
034
23.75
3.73
184T
28.6
23.75
5.59
S213T
34.9
23.75
7.46
S215T
34.9
ALTERNATE MOTOR SI
UNIT
40RM
230-3-50 and 400-3-50
Speed (r/s)
Shaft kW
Frame (NEMA)
Shaft Dia (mm)
UNIT
016
40RM
230-3-50 and 400-3-50
Speed (rpm)
1425
Hp
2.9
Frame (NEMA)
56Y
78
Shaft Dia (in.)
024
028
034
1425
5.0
184T
118
1425
7.5
S213T
138
1425
10.0
S215T
138
016
024
028
23.75
3.73
S184T
28.6
23.75
5.59
S213T
34.9
23.75
7.46
S215T
34.9
UNIT
40RM
230-3-50 and 400-3-50
Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)
016
024
028
1425
5.0
S184T
118
1425
7.5
S213T
138
1425
10.0
S215T
138
41
HIGH-STATIC DRIVE SI
016
024
028
034
86.4111.8
109.2134.6
109.2134.6
109.2134.6
2.5
3.0
3.0
3.0
229
36.5
1A
1074
218
36.5
1B
1062
279
49.2
2B
1113
279
49.2
2B
1113
10.3
9.011.6
20.0
13.3
11.914.6
20.0
10.4
9.311.5
18.3
10.4
9.311.5
18.3
0.265
0.230
0.180
0.180
265313
232279
169240
169240
MEDIUM-STATIC DRIVE SI
UNIT
40RM
MOTOR DRIVE
Motor Pulley Pitch Diameter
(mm)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. Section
Belt Pitch (mm)
FAN SPEEDS (r/s)
Factory Setting
Range
Max Allowable Speed (r/s)
Change per 12 Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE
(mm)
42
UNIT
40RM
MOTOR DRIVE
Motor Pulley Pitch Diameter
(mm)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. Section
Belt Pitch (mm)
FAN SPEEDS (r/s)
Factory Setting
Range
Max Allowable Speed (r/s)
Change per 12 Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE
(mm)
016
024
028
034
101.6127.0
101.6127.0
109.2134.6
109.2134.6
3.0
3.0
3.0
3.0
178
36.5
2A
998
163
36.5
2A
871
203
49.2
2B
935
218
49.2
2B
960
15.3
13.617.0
20.0
16.7
14.918.6
20.0
14.3
12.815.7
18.3
13.3
11.914.6
18.3
0.283
0.308
0.247
0.230
232279
207255
169240
169240
016
024
028
034
94.0119.4
101.6127.0
109.2134.6
109.2134.6
3.0
2.5
3.0
3.0
201
36.5
1B
1011
178
36.5
2A
922
239
49.2
2B
1011
239
49.2
2B
1011
12.6
11.114.1
20.0
15.3
13.617.0
20.0
12.1
10.913.4
18.3
12.1
10.913.4
18.3
0.252
0.340
0.210
0.210
232279
232279
169240
169240
UNIT
016
024
028
034
40RM
MOTOR DRIVE
Motor Pulley Pitch Diameter 3.4-4.4 4.3-5.3 4.3-5.3 4.3-5.3
(in.)
Pulley Factory Setting
2.5
3.0
3.0
3.0
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
9.0
8.6
11.0
11.0
Pulley Bore (in.)
1716
1716
11516
11516
Belt No. Section
1A
1B
2B
2B
Belt Pitch (in.)
42.3
41.8
43.8
43.8
FAN SPEEDS (rpm)
Factory Setting
618
795
622
622
538713557557Range
697
878
687
687
Max Allowable Speed (rpm)
1200
1200
1100
1100
Change per 12 Turn of
Moveable Motor Pulley
15.9
13.8
10.8
10.8
Flange
MAX FULL TURNS FROM
5
6
6
6
CLOSED POSITION
SHAFTS CENTER DISTANCE
10.449.12- 6.676.67(in.)
12.32
10.99
9.43
9.43
UNIT
016
024
028
034
40RM
MOTOR DRIVE
Motor Pulley Pitch Diameter 3.7-4.7 4.0-5.0 4.3-5.3 4.3-5.3
(in.)
Pulley Factory Setting
3.0
2.5
3.0
3.0
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
7.9
7.0
9.4
9.4
Pulley Bore (in.)
1716
1716
11516
11516
Belt No. Section
1B
2A
2B
2B
Belt Pitch (in.)
39.8
36.8
39.8
39.8
FAN SPEEDS (rpm)
Factory Setting
756
916
728
728
667814652652Range
848
1018
803
803
Max Allowable Speed (rpm)
1200
1200
1100
1100
Change per 12 Turn of
Moveable Motor Pulley
15.1
20.4
12.6
12.6
Flange
MAX FULL TURNS FROM
6
5
6
6
CLOSED POSITION
SHAFTS CENTER DISTANCE
9.169.16- 6.676.67(in.)
10.99
10.99
9.43
9.43
UNIT
016
024
028
034
40RM
MOTOR DRIVE
Motor Pulley Pitch Diameter 4.0-5.0 4.0-5.0 4.3-5.3 4.3-5.3
(in.)
Pulley Factory Setting
3.0
3.0
3.0
3.0
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
7.0
6.4
8.0
8.6
Pulley Bore (in.)
1716
1716
11516
11516
Belt No. Section
2A
2A
2B
2B
Belt Pitch (in.)
39.3
34.3
36.8
37.8
FAN SPEEDS (rpm)
Factory Setting
916
1002
855
795
814891766713Range
1018
1113
944
878
Max Allowable Speed (rpm)
1200
1200
1100
1100
Change per 12 Turn of
Moveable Motor Pulley
17.0
18.5
14.8
13.8
Flange
MAX FULL TURNS FROM
6
6
6
6
CLOSED POSITION
SHAFTS CENTER DISTANCE
9.168.16- 6.676.67(in.)
10.99
10.02
9.43
9.43
43
094
AA
Factory-Installed Options
044-084:
Standard Unit
AA Class F Fan Motors
BA VAV Control Box Modification
and Electric Unloaders
CA VAV Modifications and
Class F Fan Motors
DA Single-Circuit Piping
EA Single-Circuit Piping with
Class F Fan Motors
FA Single-Circuit Piping and VAV
Modifications
GA Single-Circuit Piping, VAV
Modifications, and Class F
Fan Motors
094,104:
Standard Unit
AA Class F Fan Motors
BA VAV (Variable Air Volume) Modifications
CA Class F Fan Motors with VAV
Modifications
124,134:
DA Standard Unit
EA Class F Fan Motors
FA VAV Modifications
GA Class F Fan Motors with VAV
Modifications
Start Options
Across-the-Line Start
P Part-Wind Start
Nominal Capacity
044 123 kW (35 Tons)
054 144 kW (41 Tons)
064 175 kW (50 Tons)
074 214 kW (61 Tons)
084 242 kW (69 Tons)
094 274 kW (78 Tons)
104 305 kW (87 Tons)
124 351 kW (100 Tons)
134 390 kW (111 Tons)
Not Used
Condenser Fin Material
Aluminum (Standard)
C
Copper (Optional)
K
Pre-Coated Aluminum (Optional)
SO Post-Coated Aluminum (Contact Factory)
SO Post-Coated Copper (Contact Factory)
Voltage Designation
3 346-3-50 (Part Wind)
8 230-3-50 (Part-Wind, 044 Size)
9 380/415-3-50
Packaging
2 Coil Protection Only (For Closed Container
Shipments)
3 Standard Export (Top and Bottom Skid,
Coil Protector and Full Plastic Bag
Enclosure)
4 Optional Export (Full Export Box)
Revision Number
SO Special Order
NOMINAL CAPACITY
kW
Tons
123
35
144
41
175
50
214
61
242
69
274
78
305
87
351
100
390
111
EER*
10.8
10.7
10.8
10.3
10.6
10.6
10.9
10.8
10.6
LEGEND
EER Energy Efficiency Ratio
*Rated in accordance with ARI (Air Conditioning & Refrigeration
Institute) standard 365-87 (U.S.A.).
NOTE: Ratings are based on 7.2 C (45 F) suction temperature and
35 C (95 F) outside-air temperature, and include suction line losses.
44
Field-installed accessories
Transformer relay package for remote-control (24-v)
thermostat. One 2-stage thermostat is required for use with
the relay package.
Additional electric unloader package includes hardware to add an additional step of unloading (coil not
included).
Standard,
Non-Corrosive
Mild
Coastal
Moderate
Coastal
Severe
Coastal
Industrial
Combined
Coastal
and Industrial
X
X
X
X
X
LEGEND
Al/Cu
Aluminum Fin with Copper Tube Coil
Cu/Cu
Copper Fin with Copper Tube Coil
Enviro-Shield Family of Coil Protection Options
Post-Coated Organic Coating applied to Entire Coil Assembly
Pre-Coated
Epoxy Coating Applied to Fin Stock Material
*See Selection Guide: Environmental Corrosion Protection Catalog No. 811-839 for more information.
45
Carrier
Pm
COOL
AUTO
HEAT
NON-PROGRAMMABLE THERMOSTAT
H
46
Cu-Al Coils
Cu-Cu Coils
Cu-Al Coils
Cu-Cu Coils
044
123
1480
1609
1474
1605
28.1
(4) A
250
8.0
at 48.9 C
064
175
1617
1813
1601
1798
074
214
1729
1918
1715
1904
084
242
1840
2148
1814
2122
32.7
39.9
47.2
58.9
Reciprocating Semi-Hermetic...24.3 @ 50 Hz
(4) A
(6) B
(6) A
(6) B
(6) A
(6) B
250
265
265
275
275
299
8.0
9.9
9.9
9.9
9.9
9.0
4
(4) B
250
8.0
2...669
7.48
16
054
144
1501
1632
1492
1623
(6) A
299
9.0
(6) B
299
9.0
4...762
6...762
16 500
24 500
24 100
15.8
15.8
6.2
9.3
Enhanced Copper Tubes, Lanced Aluminum Fins
2...669
3...669
2...782
3...669
7.48
7.48
10.84
10.84
16
25
25
36
1758 69
1103 69
218
Ckt A
58
58
Ckt B
78
58
218
78
58
LEGEND
Cu-Al Copper Tube, Aluminum Fin
Cu-Cu Copper Tube, Copper Fin
ODF
Outside Diameter, Female
*06E250 compressors have 4 cylinders; all others have 6.
Circuit A compressor is lead on standard units; circuit B compressor is lead on optional single-circuit
units.
**Capacity control steps listed are for constant volume units with no accessories. Refer to Minimum
Outdoor-Air Operating Temperature and Unloading Sequences tables, pages 94-96, for additional
system capacity information.
On all 044-134 units, fan no. 3 and 4; also on 38AH074,084 (dual-circuit units only) and 38AH094,104,
fans no. 5 and 6.
\For single-circuit units, suction ODF is 258 in. and liquid ODF is 118 inches. Single circuit units
have a factory-installed manifold; no field modification is required.
NOTES:
1. Certified dimensional drawings available on request.
2. Equivalent connection values in mm are as follows:
in.
mm
1
1
2 8
258
58
78
18
15.9
22.2
28.6
54.0
66.7
47
094
104
124
124A
175.5
134
134B
NOMINAL CAPACITY (kW)
274
305
214.5
OPERATING WEIGHT WITH
REFRIGERANT (Approx.) (kg)
Cu-Al
2308
2465
1647*
1647*
1647*
1759*
Cu-Cu
2637
2794
1843*
1843*
1843*
1843*
SHIPPING WEIGHT WITH
COIL PROTECTION AND SKID
(Approx.) (kg)
Cu-Al
2554
2717
1860*
1860*
1860*
1851
Cu-Cu
2883
3046
1968*
1968*
1968*
2040
TYPICAL OPERATING
R-22
REFRIGERANT
Charge (Approx.) (kg)
67.1
61.2
39.9
39.9
39.9
47.2
Qty of Circuits
2
2
1
1
1
1
COMPRESSOR Type...R/s
Reciprocating Semi-Hermetic...24.3
(Qty Cylinder)/Compressor
(6)A1 (4)A2 (6)B1 (6)A1 (4)A2 (6)B1 (6)B2 (6)A1 (6)A2 (6)A1 (6)A2 (6)A1 (6)A2 (6)A1 (6)A2
Model No. 06E
275 250 299 265 250 265 265 275 265 275 265 275 265 299 275
Oil Charge (L)
10
8
9
10
8
10
10
10
10
10
10
10
10
9
10
Circuit Capacity (%) (Approx.)
55
45
47
53
50
50
45
55
Capacity Control Steps**
6
8
4
4
4
4
CONDENSER FANS (6 Blade)
Qty...Dia (mm)
6...762
6...762
4...762
4...762
4...762
6...762
Airflow (L/s)
24 544
24 544
16 520
16 520
16 520
24 544
Speed (R/s)
15.8
15.8
15.8
15.8
15.8
15.8
Total Power (kW)
9.4
9.5
6.4
6.4
6.4
9.2
CONDENSER COIL
Enhanced Copper Tubes, Lanced Aluminum Fins
Rows...Fins per m
3...669.3
3...669.3
3...669.3
3...669.3
3...669.3
2...781.6
Face Area (sq m)
11.9
11.9
7.5
7.5
7.5
10.8
Storage Capacity
(kg per circuit, approx.)
81
81
50
50
50
50
at 49 C
FAN CYCLING CONTROLS
Close (kPa)
1758 69
Open (kPa)
1103 69
CONNECTIONS
Suction, ODF (in.)
218
218
258
258
258
258
78
78
Liquid, ODF (in.)
118
118
118
118
58
58
5 8
58
58
58
Hot Gas Bypass, ODF (in.)
LEGEND
Cu-Al Copper Tube, Aluminum Fin
Cu-Cu Copper Tube, Copper Fin
ODF
Outside Diameter, Female
VAV
Variable Air Volume
*Includes piping and trim kit.
Compressor A1 is lead compressor on all circuits except circuit B on units 38AH094 and 104. Compressor B1 is lead on circuit B on units 38AH094 and 104. Compressors are shipped with minimum
oil charge.
**Capacity control steps listed are for constant volume units with no accessories. Refer to Minimum
Outdoor-Air Operating Temperature and Unloading Sequences tables, pages 94-96, for additional
system capacity information.
On all 044-134 units, fan no. 3 and 4; also on 38AH074,084 (dual-circuit units only) and 38AH094,104,
fans no. 5 and 6.
NOTES:
1. Unit 38AH124 consists of one 124A module and one 124B module. Unit 38AH134 consists of one
134A module and one 134B module.
2. Certified dimensional drawings available on request.
48
124B
175.5
134A
175.5
ENGLISH
38AH
NOMINAL CAPACITY (Tons)
OPERATING WEIGHT WITH
REFRIGERANT (lb) (Approx.)
SHIPPING WEIGHT WITH
COIL PROTECTION ONLY (lb) (Approx.)
TYPICAL OPERATING REFRIGERANT
CHARGE (lb, approx.) R-22
COMPRESSOR Type...Rpm
(Qty Cylinder)* Circuit
Model No. 06EOil Charge (pt)
Capacity Control Steps**
CONDENSER FANS (6 Blade)
Qty...Dia (in.)
Airflow (cfm)
Speed (rpm)
Total Power (kW)
CONDENSER COIL Rows
Fins per...in.
Face Area (ft2)
Storage Capacity (lb per circuit, approx.)
FAN CYCLING CONTROLS
Close (psig)
Open (psig)
CONNECTIONS
Suction, ODF (in.)
Liquid, ODF (in.)
Hot Gas Bypass, ODF (in.)
Cu-Al Coils
Cu-Cu Coils
Cu-Al Coils
Cu-Cu Coils
044
35
3259
3547
3250
3538
054
41
3309
3597
3290
3578
064
50
3565
3998
3530
3963
074
61
3812
4229
3780
4197
084
69
4057
4735
4000
4678
72
88
104
130
62
(4) A
250
17
at 120 F
Reciprocating Semi-Hermetic...1458 @ 50 Hz
(4) A
(6) B
(6) A
(6) B
(6) A
(6) B
250
265
265
275
275
299
17
21
21
21
21
19
4
(4) B
250
17
4...30
35,000
950
6.2
2
17
80.5
35
2
17
80.5
35
(6) A
299
19
(6) B
299
19
6...30
52,000
51,000
950
9.3
3
17
80.5
55
2
19
116.7
55
3
17
116.7
80
255 10
160 10
218
Ckt A
58
58
Ckt B
78
58
218
78
58
LEGEND
Cu-Al Copper Tube, Aluminum Fn
Cu-Cu Copper Tube, Copper Fn
ODF
Outside Diameter, Female
*06E250 compressors have 4 cylinders; all others have 6.
Circuit A compressor is lead on standard units; circuit B compressor is lead on optional single-circuit
units.
**Capacity control steps listed are for constant volume units with no accessories. Refer to Minimum
Outdoor-Air Operating Temperature and Unloading Sequences tables, pages 94-96, for additional
system capacity information.
On all 044-134 units, fan no. 3 and 4; also on 38AH074,084 (dual-circuit units only) and 38AH094,104,
fans no. 5 and 6.
\For single-circuit units, suction ODF is 258 in. and liquid ODF is 118 inches. Single circuit units
have a factory-installed manifold; no field modification is required.
NOTE: Certified dimensional drawings available on request.
49
094
104
124
124A
50
134
134B
NOMINAL CAPACITY (Tons)
78
87
61
OPERATING WEIGHT WITH
REFRIGERANT (Approx.) (lb)
Cu-Al
5088
5435
3630*
3630*
3630*
3877*
Cu-Cu
5813
6160
4063*
4063*
4063*
4294*
SHIPPING WEIGHT WITH
COIL PROTECTION AND SKID
(Approx.) (lb)
Cu-Al
5630
5990
3907*
3907*
3907*
4080
Cu-Cu
6355
6715
4340*
4340*
4340*
4497
TYPICAL OPERATING
R-22
REFRIGERANT
Charge (Approx.) (lb)
148
135
88
88
88
104
Qty of Circuits
2
2
1
1
1
1
COMPRESSOR Type...Rpm
Reciprocating Semi-Hermetic...1450
(Qty Cylinder)/Compressor
(6)A1 (4)A2 (6)B1 (6)A1 (4)A2 (6)B1 (6)B2 (6)A1 (6)A2 (6)A1 (6)A2 (6)A1 (6)A2 (6)A1 (6)A2
Model No. 06E
275 250 299 265 250 265 265 275 265 275 265 275 265 299 275
Oil Charge (pt)
21
17
19
21
17
21
21
21
21
21
21
21
21
19
21
Circuit Capacity (%) (Approx.)
55
45
47
53
50
50
45
55
Capacity Control Steps**
6
8
4
4
4
4
CONDENSER FANS (6 Blade)
Qty...Dia (in.)
6...30
6...30
4...30
4...30
4...30
6...30
Airflow (cfm)
52,000
52,000
35,000
35,000
35,000
52,000
Speed (rpm)
950
950
950
950
950
950
Total Power (kW)
9.4
9.5
6.4
6.4
6.4
9.2
CONDENSER COIL
Enhanced Copper Tubes, Lanced Aluminum Fin
Rows...Fins per in.
3...17
3...17
3...17
3...17
3...17
2...19
Face Area (sq ft)
128.3
128.3
80.5
80.5
80.5
116.7
Storage Capacity
(lb per ckt, approx.)
178
178
110
110
110
110
at 120 F
FAN CYCLING CONTROLS
Close (psig)
255 10
Open (psig)
160 10
CONNECTIONS
Suction, ODF (in.)
218
218
258
258
258
258
78
78
Liquid, ODF (in.)
118
118
118
118
58
58
5 8
58
58
58
Hot Gas Bypass, ODF (in.)
LEGEND
Cu-Al Copper Tube, Aluminum Fin
Cu-Cu Copper Tube, Copper Fin
ODF
Outside Diameter, Female
VAV
Variable Air Volume
*Includes piping and trim kit.
Compressor A1 is lead compressor on all circuits except circuit B on units 38AH094 and 104. Compressor B1 is lead on circuit B on units 38AH094 and 104. Compressors are shipped with minimum
oil charge.
**Capacity control steps listed are for constant volume units with no accessories. Refer to Minimum
Outdoor-Air Operating Temperature and Unloading Sequences tables, pages 94-96, for additional
system capacity information.
On all 044-134 units, fan no. 3 and 4; also on 38AH074,084 (dual-circuit units only) and 38AH094,104,
fans no. 5 and 6.
NOTES:
1. Unit 38AH124 consists of one 124A module and one 124B module. Unit 38AH134 consists of one
134A module and one 134B module.
2. Certified dimensional drawings available on request.
50
124B
50
134A
50
Dimensions 38AH044-134
SIZES 044-064 (See Page 53 for Corner Weights)
UNIT
38AH
044
044C
054
054C
064
064C
DIMENSION
Y
38-2349
[984 mm]
38-3189
[994 mm]
38-2129
[978 mm]
38-39
[991 mm]
38-2129
[978 mm]
38-33169
[995 mm]
DIMENSION
X
48-129
[1232 mm]
48-9169
[1234 mm]
48-3169
[1224 mm]
48-389
[1229 mm]
48-129
[1232 mm]
48-589
[1235 mm]
LEGEND
C
Copper Fin Coils
MTG Mounting
SAE Society of Automotive Engineers
VOLTAGE
230
346
346
380/415
380/415
Hz
50
50
50
50
50
DIAMETER
3589 [92 mm]
2129 [63 mm]
3589 [92 mm]
2129 [63 mm]
3589 [92 mm]
QTY.
1
1
1
1
1
NOTES:
1. The approximate operating weight of the unit is:
38AH044
3259 lb (1480 kg)
38AH044C
3547 lb (1609 kg)
38AH054
3309 lb (1501 kg)
38AH054C
3597 lb (1632 kg)
38AH064
3565 lb (1617 kg)
38AH064C
3998 lb (1813 kg)
2. Unit must have clearances for airflow as follows:
Top Do not restrict in any way.
Ends 5 ft [153 cm]
Sides 6 ft [183 cm]
3. Mounting holes may be used to mount unit to concrete pad. They are not recommended for
mounting unit to spring isolators.
4. Two 51 mm (2 in.) dia holes are recommended for parallel conductors on 044 (230-V) units.
5. Circled numerals in Top View refer to condenser fans; refer to Electrical Data section, Fans
table, page 88 and Wiring Diagram book.
6. If spring isolators are used, a perimeter support channel between the unit and the isolators is
recommended.
51
DIMENSION
Y
38-3189
[994 mm]
38-3589
[1006 mm]
38-39
[991 mm]
38-311169
[1008 mm]
DIMENSION
X
48-8131688
[1443 mm]
48-8189
[1425 mm]
48-99
[1448 mm]
48-89
[1422 mm]
LEGEND
C
Copper Fin Coils
MTG Mounting
SAE Society of Automotive
Engineers
VOLTAGE
346
380/415
Hz
50
50
DIAMETER
3589 [92 mm]
3589 [92 mm]
QTY.
1
1
NOTES:
1. The approximate operating weight of the unit is:
38AH074
38AH074C
38AH084
38AH084C
4735 lb (2148 kg)
2. Unit must have clearances for airflow as follows:
Top Do not restrict in any way.
Ends 5 ft [153 cm]
Sides 6 ft [183 cm]
3. Mounting holes may be used to mount unit to concrete pad. They are not
recommended for mounting unit to spring isolators.
4. Circled numerals in Top View refer to condenser fans; refer to Electrical
Data section, Fans table, page 88 and Wiring Diagram book.
5. If spring isolators are used, a perimeter support channel between the unit
and the isolators is recommended.
52
TOTAL
WEIGHT
044
044C
054
054C
064
064C
074
074C
084
084C
1480
1609
1501
1632
1617
1813
1729
1918
1840
2148
TOTAL
WEIGHT
044
044C
054
054C
064
064C
074
074C
084
084C
3259
3547
3309
3597
3565
3998
3812
4229
4057
4735
53
UNIT
38AH
LEGEND
C
Copper Fin Coils
MTG Mounting
SAE Society of Automotive
Engineers
54
NOTES:
1. The approximate operating weight of the unit is:
38AH094 5088 lb [2308 Kg]
38AH094C 5813 lb [2637 Kg]
2. Unit must have clearances for airflow as follows:
Top Do not restrict in any way.
Ends 5 ft [153 cm]
Sides 6 ft [183 cm]
094
VOLTAGE
346
380/415
DIAMETER
in. [mm]
358
92]
QUANTITY
1
UNIT 38AH104
DIMENSIONS
OPERATIONAL CORNER
ft-in. [mm]
WEIGHTS lb [kg]
X
Y
A
B
C
D
104
5-3 [1600] 2-912 [851] 1240 [562] 2138 [970] 1302 [591] 755 [342]
104C 5-3 [1600] 2-912 [851] 1405 [637] 2423 [1099] 1476 [670] 856 [388]
UNIT
38AH
LEGEND
C
Copper Fin Coils
MTG Mounting
SAE Society of Automotive
Engineers
NOTES:
1. The approximate operating weight of the unit is:
38AH104 5435 lb [2465 Kg]
38AH104C 6160 lb [2794 Kg]
2. Unit must have clearances for airflow as follows:
Top Do not restrict in any way.
Ends 5 ft [153 cm]
Sides 6 ft [183 cm]
VOLTAGE
346
380/415
DIAMETER
in. [mm]
358
[92]
QUANTITY
1
55
DIMENSIONS
ft-in. [mm]
X
Y
K
L
LEGEND
C
Copper Fin Coils
MTG Mounting
SAE Society of Automotive
Engineers
56
OPERATIONAL CORNER
WEIGHTS lb [kg]
A
B
C
D
1037 1030 779 785
[470] [467] [353] [356]
VOLTAGE
DIAMETER
in. [mm]
QUANTITY
346, 380/415
358
[92]
NOTES:
1. The approximate operating weight of the unit is:
38AH124 7260 lb [3293 Kg]
38AH124C 8126 lb [3686 Kg]
2. Unit must have clearances for airflow as follows:
Top Do not restrict in any way.
Ends 5 ft [153 cm]
Sides 6 ft [183 cm]
3. Mounting holes may be used to mount unit to concrete
pad. They are not recommended for mounting unit to
spring isolators.
UNIT 38AH134
UNIT
38AH
MODULE
134A
134B
134A-C
134B-C
DIMENSIONS
ft-in. [mm]
X
Y
K
L
4-158 [1260] 3-218 [968]
OPERATIONAL CORNER
WEIGHTS lb [kg]
A
B
C
D
1037 [470] 1030 [467] 779 [353] 785 [356]
1167 [529] 997 [452] 789 [358] 924 [419]
1144 [519] 1137 [516] 889 [403] 894 [406]
1293 [587] 1080 [490] 874 [396] 1047 [475]
VOLTAGE
346
380/415
DIAMETER
in. [mm]
358
[92]
QUANTITY
1
LEGEND
C
Copper Fin Coils
MTG Mounting
SAE Society of Automotive
Engineers
NOTES:
1. The approximate operating weight of the unit is:
38AH134 7507 lb [3405 Kg]
38AH134C 8357 lb [3791 Kg]
2. Unit must have clearances for airflow as follows:
Top Do not restrict in any way.
Ends 5 ft [153 cm]
Sides 6 ft [183 cm]
3. Mounting holes may be used to mount unit to concrete pad. They are
not recommended for mounting unit to spring isolators.
4. Circled numerals in Top View refer to condenser fans; refer to Electrical Data section, Fans
table, page 88 and Wiring Diagram book.
5. If spring isolators are used, a perimeter support channel between the assembled unit and the
isolators is required. Do not support each module separately.
6. Each module must be rigged into position separately. The unit must not be rigged after modules have been connected.
7. Suction and liquid connections can exit on either side of the unit.
8. Field power supply connections are required for each module.
57
ENGLISH
I Determine required cooling capacity of each circuit, saturated suction temperature (SST) for
each circuit, and the temperature of the air entering the condensing unit.
Given:
Circuit A
Circuit B
Cooling Load . . . . 252,000 Btuh . . . 281,000 Btuh
Saturated suction
temperature . . . . . . . . . . . . 40 F . . . . . . . . . . . 40 F
Entering-air temperature . . . 95 F . . . . . . . . . . . 95 F
ENGLISH
58
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
21
105.5
24.2
33.3
114.2
24.7
33.7
123.6
25.1
34.2
133.1
25.6
34.7
143.1
26.1
35.3
153.5
26.6
35.9
164.1
27.0
36.6
27
96.9
26.3
39.2
105.4
27.0
39.5
114.3
27.7
39.9
123.6
28.4
40.5
133.1
29.0
41.0
143.1
29.7
41.6
153.3
30.4
42.3
30
92.6
27.3
42.1
100.8
28.2
42.4
109.6
28.9
42.8
118.7
29.7
43.3
128.0
30.5
43.9
137.9
31.2
44.5
147.9
31.9
45.1
32
89.6
27.9
44.0
97.8
28.8
44.3
106.5
29.7
44.8
115.4
30.5
45.2
124.7
31.4
45.7
134.3
32.2
46.4
144.2
32.9
47.0
Air Temperature
35
85.1
28.8
46.9
93.2
29.8
47.2
101.7
30.8
47.7
110.4
31.7
48.1
119.5
32.7
48.6
128.9
33.6
49.2
138.6
34.5
49.8
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
21
123.0
29.5
35.7
133.3
30.2
36.0
144.2
30.9
36.5
155.4
31.6
36.5
167.0
32.5
37.6
178.9
33.2
38.4
191.2
33.9
39.2
27
113.2
32.0
41.6
123.0
32.9
41.8
133.4
33.8
42.2
144.2
34.7
42.7
155.3
35.7
43.3
166.8
36.6
44.0
179.0
37.6
44.7
30
108.1
33.0
44.5
117.8
34.2
44.8
128.0
35.1
45.2
138.5
36.2
45.5
149.4
37.2
46.1
160.7
38.3
46.7
172.2
39.3
47.4
32
104.9
33.7
46.5
114.3
34.9
46.7
124.4
36.0
47.1
134.7
37.1
47.5
145.5
38.3
48.0
156.6
39.4
48.6
168.0
40.5
49.3
Air Temperature
35
100.0
34.6
49.5
109.1
36.0
49.6
119.0
37.2
50.0
129.1
38.5
50.3
139.6
39.7
50.8
150.5
41.0
51.4
161.6
42.2
52.0
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
21
148.5
35.7
34.7
160.3
36.6
35.1
172.9
37.5
35.7
185.8
38.4
36.4
199.4
39.3
37.2
213.0
40.2
38.0
227.0
41.1
38.9
27
137.2
38.6
40.5
148.6
39.8
40.9
160.7
41.0
41.5
173.1
42.2
42.1
185.9
43.4
42.8
198.9
44.5
43.6
213.0
45.7
44.4
30
131.7
40.0
43.5
142.8
41.3
43.8
154.6
42.6
44.3
166.6
43.9
44.9
179.2
45.3
45.6
192.4
46.5
46.4
205.8
47.9
47.2
32
127.9
40.8
45.5
138.9
42.3
45.7
150.5
43.6
46.3
162.4
45.0
46.8
174.7
46.4
47.5
187.5
47.8
48.2
200.3
49.3
49.1
Air Temperature
35
122.4
42.0
48.3
133.1
43.5
48.6
144.4
45.0
49.1
156.1
46.6
49.7
168.1
48.2
50.3
180.6
49.7
51.1
193.7
51.3
51.8
SST
(C)
2
10
46
68.4
30.9
57.7
75.9
32.4
57.9
83.9
33.8
58.3
92.0
35.3
58.6
100.4
36.7
59.0
109.1
38.0
59.6
117.9
39.3
60.1
49
63.8
31.2
60.7
71.1
32.9
60.9
78.9
34.4
61.1
86.8
36.0
61.5
95.1
37.5
61.9
103.5
39.0
62.4
112.2
40.5
62.9
52
59.2
31.3
63.6
66.4
33.1
63.7
73.9
34.9
64.0
81.7
36.6
64.4
89.7
38.3
64.8
98.0*
39.9*
65.3*
106.5*
41.5*
65.8*
49
77.4
37.6
63.3
85.4
39.6
63.5
94.1
41.5
63.6
103.0
43.4
63.9
112.3
45.1
64.2
122.0
47.0
64.7
132.0*
48.8*
65.2*
52
72.6*
38.0*
66.3*
80.4*
40.1*
66.4*
88.8*
42.2*
66.6*
97.4*
44.1*
66.9*
106.5*
46.1*
67.2*
116.0*
48.0*
67.5*
125.5*
50.0*
68.0*
49
97.0
46.0
62.1
106.4
48.2
62.3
116.4
50.4
62.7
126.7
52.6
63.1
137.3
54.7
63.6
148.4
57.0
64.2
159.6
59.1
64.8
52
91.6
46.5
65.1
100.7
48.9
65.2
110.5
51.2
65.6
120.5
53.5
66.0
130.8*
55.9*
66.4*
141.6*
58.2*
67.0*
152.5*
60.5*
67.6*
38AH054
SST
(C)
2
10
46
82.2
37.3
60.3
90.4
39.1
60.5
99.4
40.7
60.7
108.5
42.4
61.0
118.1
44.2
61.3
128.2
45.9
61.8
138.3
47.5
62.3
38AH064
SST
(C)
2
10
CMP
SDT
SST
TCG
LEGEND
Compressor Power, kW
Saturated Discharge Temperature (leaving compressor) (C)
Saturated Suction Temperature (entering condensing unit)
Total Cooling Capacity, Gross (kW)
46
102.3
45.4
59.2
112.1
47.4
59.3
122.4
49.5
59.8
133.0
51.5
60.2
143.8
53.5
60.7
155.2
55.6
61.4
166.8
57.6
62.0
59
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
21
181.6
45.2
34.1
194.7
46.5
34.6
209.1
47.8
35.3
224.6
49.1
36.0
239.0
50.4
36.8
257.0
51.6
37.6
273.0
52.8
38.5
27
169.2
48.7
39.8
182.1
50.2
40.3
196.3
51.8
41.0
210.5
53.4
41.6
225.1
55.0
42.4
241.0
56.6
43.2
257.0
58.3
44.0
30
163.2
50.2
42.8
176.1
51.9
43.2
189.3
53.7
43.8
203.5
55.4
44.4
217.9
57.2
45.2
234.0
59.0
45.9
248.0
60.7
46.8
32
159.1
51.1
44.7
171.9
53.0
45.0
185.3
54.8
45.7
199.4
56.7
46.3
212.8
58.5
47.0
228.4
60.4
47.8
243.0
62.3
48.6
Air Temperature
35
153.1
52.4
47.6
165.6
54.5
47.9
178.4
56.5
48.5
192.4
58.4
49.1
205.6
60.5
49.8
221.0
62.6
50.6
236.0
64.6
51.4
46
131.0
56.6
58.4
142.5
59.1
58.5
154.6
61.6
58.9
166.9
64.2
59.4
179.6
66.7
60.0
192.5
69.4
60.7
206.6
71.9
61.5
49
125.0
57.4
61.3
136.2
60.1
61.4
148.1
62.8
61.8
160.1
65.4
62.2
172.5
68.1
62.8
185.1
71.0
63.5
198.0
73.7
64.2
52
118.9
58.1
64.3
129.8
61.0
64.4
141.4
63.8
64.7
153.2
66.6
65.1
165.3
69.5
65.6
177.6*
72.4*
66.2*
190.4*
75.3*
66.9*
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
21
204.0
54.1
36.2
221.0
55.6
36.3
238.0
57.0
36.7
256.0
58.5
37.1
274.0
60.0
37.7
294.0
61.6
38.4
314.0
63.2
39.2
27
190.6
57.9
42.2
206.0
59.7
42.3
223.0
61.5
42.6
240.0
63.3
42.9
258.0
65.1
43.4
276.0
67.1
44.1
294.0
69.1
44.8
30
183.9
59.5
45.2
198.9
61.5
45.3
215.0
63.5
45.5
232.0
65.5
45.8
250.0
67.5
46.3
268.0
69.7
46.9
286.0
71.7
47.6
32
179.3
60.6
47.2
194.2
62.7
47.3
210.0
64.9
47.5
226.0
66.9
47.8
244.0
69.1
48.2
262.0
71.3
48.8
280.0
73.5
49.5
Air Temperature
35
172.7
62.1
50.2
187.1
64.4
50.3
203.0
66.7
50.4
219.0
68.9
50.7
236.0
71.3
51.1
252.0
73.7
51.7
270.0
76.1
52.3
46
148.9
66.6
61.2
161.7
69.6
61.2
175.7
72.4
61.4
190.1
75.3
61.5
205.0
78.3
61.9
221.0
81.3
62.3
236.0
84.3
62.7
49
142.5
67.7
64.2
154.9
70.8
64.2
168.5
73.8
64.3
182.5
76.9
63.5
197.0
79.9
64.8
212.0
83.1
65.2
228.0
86.3
65.6
52
136.2*
68.6*
67.2*
148.2*
71.8*
67.2*
161.3*
75.0*
67.3*
174.9*
78.2*
67.4*
189.0*
81.5*
67.7*
204.0*
84.8*
68.1*
219.0*
88.1*
68.5*
SST
(C)
2
10
38AH084
SST
(C)
2
10
CMP
SDT
SST
TCG
60
LEGEND
Compressor Power, kW
Saturated Discharge Temperature (leaving compressor) (C)
Saturated Suction Temperature (entering condensing unit)
Total Cooling Capacity, Gross (kW)
10
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
21
233.0
58.1
35.5
33.8
33.6
32.3
251.0
59.7
36.2
34.2
34.0
32.4
269.0
61.5
37.1
34.9
34.6
32.8
289.0
63.3
38.0
35.6
35.2
33.3
309.0
65.1
39.0
36.4
35.8
33.8
329.0
66.9
40.1
37.3
36.5
34.3
350.0
68.7
41.1
38.2
37.2
34.9
27
216.5
62.3
41.2
39.6
39.7
38.5
234.0
64.3
41.8
39.9
40.1
38.6
252.0
66.5
42.6
40.5
40.6
39.0
270.0
68.6
43.5
41.2
41.2
39.4
290.0
70.8
44.4
41.9
41.9
39.9
309.0
73.0
45.4
42.7
42.6
40.4
329.0
75.2
46.4
43.6
43.3
41.0
30
209.1
64.3
44.0
42.5
42.8
41.5
226.0
66.6
44.5
42.8
43.1
41.7
243.0
68.9
45.3
43.4
43.7
42.0
261.0
71.3
46.2
44.0
44.3
42.4
279.0
73.6
47.1
44.7
44.9
42.9
299.0
76.0
48.0
45.5
45.6
43.5
319.0
78.4
49.1
46.3
46.4
44.1
32
202.9
65.6
45.9
44.5
44.8
43.6
220.2
67.9
46.4
44.8
45.1
43.7
237.0
70.4
47.2
45.3
45.7
44.0
255.0
72.9
48.0
45.9
46.3
44.4
274.0
75.4
48.9
46.5
46.9
44.9
292.0
77.9
49.8
47.3
47.6
45.5
312.0
80.5
50.8
48.2
48.4
46.1
Air Temperature
35
195.6
67.4
48.8
47.4
47.8
46.7
211.7
69.9
49.2
47.7
48.1
46.8
228.0
72.5
49.9
48.2
48.6
47.1
246.0
75.2
50.7
48.7
49.2
47.4
264.0
77.9
51.6
49.3
49.9
47.9
282.0
80.6
52.5
50.1
50.6
48.4
301.0
83.3
53.5
50.9
51.3
49.0
LEGEND
CMP
Compressor Power (kW)
SCT(A) Saturated Condensing Temperature (C) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SCT(B) Saturated Condensing Temperature (C) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SDT(A) Saturated Discharge Temperature (C) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SDT(B) Saturated Discharge Temperature (C) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SST
Saturated Suction Temperature Entering Condensing Unit
TCG
Gross Cooling Capacity (kW)
46
164.8
72.2
59.4
58.3
58.9
57.9
180.0
75.6
59.6
58.4
59.0
57.9
196.0
78.9
60.2
58.8
59.4
58.1
211.9
82.3
60.8
59.2
59.9
58.4
228.0
85.6
61.5
59.7
60.5
58.8
246.0
89.1
62.3
60.3
61.1
59.3
263.0
92.5
63.2
61.0
61.8
59.8
49
156.5
73.2
62.3
61.3
61.9
60.9
171.4
76.7
62.5
61.4
62.0
60.9
186.4
80.2
63.0
61.7
62.3
61.1
202.2
83.8
63.5
62.1
62.7
61.3
219.2
87.5
64.2
62.5
63.3
61.7
235.0
91.0
65.0
63.1
64.0
62.2
253.0
94.7
65.9
63.8
64.7
62.7
52
148.2
73.9
65.3
64.3
64.9
63.9
162.7
77.7
65.4
64.4
64.9
63.9
177.9
81.5
65.8
64.6
65.3
64.1
193.4
85.2
66.3
65.0
65.6
64.3
209.3
89.1
66.9
65.4
66.2
64.7
225.0
92.9
67.7*
66.0
66.8
65.1
242.0
96.8
68.5*
66.6
67.5*
65.6
61
10
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
21
265.0
62.8
34.4
35.7
32.6
33.5
285.0
64.9
35.1
36.5
33.1
34.0
307.0
66.9
36.0
37.5
33.6
34.7
328.0
68.9
36.9
38.5
34.2
35.3
351.0
71.0
37.9
39.6
34.8
36.0
375.0
73.1
38.9
40.7
35.5
36.7
400.0
75.4
39.9
41.9
36.2
37.5
27
245.0
67.7
40.0
41.2
38.6
39.5
264.0
70.1
40.6
41.9
39.1
40.0
285.0
72.6
41.4
42.9
39.6
40.7
306.0
75.0
42.3
43.8
40.2
41.4
328.0
77.5
43.2
44.8
40.8
42.1
351.0
80.0
44.1
45.9
41.5
42.8
374.0
82.6
45.2
47.0
42.2
43.6
30
235.0
70.1
42.8
43.9
41.7
42.6
254.0
72.6
43.4
44.7
42.1
43.1
273.0
75.3
44.1
45.5
42.6
43.7
294.0
78.0
44.9
46.4
43.2
44.4
316.0
80.7
45.8
47.4
43.8
45.1
338.0
83.5
46.8
48.5
44.5
45.8
361.0
86.3
47.8
49.5
45.2
46.6
32
229.0
71.6
44.7
45.8
43.7
44.5
247.0
74.3
45.2
46.5
44.0
45.0
267.0
77.0
46.0
47.3
44.6
45.7
287.0
79.8
46.7
48.2
45.1
46.3
308.0
82.7
47.6
49.2
45.8
47.1
330.0
85.6
48.6
50.2
46.5
47.8
353.0
88.5
49.5
51.3
47.2
48.6
Air Temperature
35
219.0
73.6
47.5
48.6
46.7
47.5
237.0
76.5
48.0
49.2
47.0
48.0
256.0
79.5
48.7
50.0
47.5
48.6
275.0
82.5
49.5
50.9
48.1
49.3
296.0
85.6
50.3
51.8
48.7
50.0
317.0
88.6
51.2
52.8
49.4
50.7
340.0
91.7
52.2
53.9
50.1
51.5
LEGEND
CMP
Compressor Power (kW)
SCT(A) Saturated Condensing Temperature (C) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SCT(B) Saturated Condensing Temperature (C) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SDT(A) Saturated Discharge Temperature (C) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SDT(B) Saturated Discharge Temperature (C) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SST
Saturated Suction Temperature Entering Condensing Unit
TCG
Gross Cooling Capacity (kW)
62
46
183.1
79.7
58.1
59.1
57.7
58.5
199.8
83.4
58.4
59.5
57.8
58.8
217.0
87.1
58.9
60.1
58.2
59.3
235.0
90.9
59.5
60.8
58.7
59.8
254.0
94.7
60.2
61.7
59.2
60.5
273.0
98.6
61.0
62.6
59.9
61.2
292.0
102.4
61.9
63.5
60.6
62.0
49
173.6
81.0
61.1
61.9
60.7
61.4
190.0
84.9
61.3
62.3
60.8
61.7
207.3
88.8
61.7
62.9
61.1
62.2
225.0
92.8
62.3
63.6
61.5
62.7
242.0
96.8
63.0
64.4
62.1
63.4
261.0
100.8
63.7
65.2
62.7
64.1
281.0
105.0
64.5
66.1
63.4
64.8
52
164.2
82.1
64.0
64.9
63.7
64.4
180.1
86.2
64.1
65.2
63.7
64.6
197.2
90.4
64.6
65.7
64.0
65.1
213.4
94.5
65.1
66.3
64.4
65.6
231.0
98.8
65.7
67.1*
64.9
66.2
250.0
103.0
66.4
67.9*
65.5
66.9
268.0
107.4
67.2
68.7*
66.2
67.6*
10
TCG
CMP
SDT(A OR (B)
SCT(A) OR (B)
TCG
CMP
SDT(A) OR (B)
SCT(A) OR (B)
TCG
CMP
SDT(A) OR (B)
SCT(A) OR (B)
TCG
CMP
SDT(A) OR (B)
SCT(A) OR (B)
TCG
CMP
SDT(A) OR (B)
SCT(A) OR (B)
TCG
CMP
SDT(A) OR (B)
SCT(A) OR (B)
TCG
CMP
SDT(A) OR (B)
SCT(A) OR (B)
21
298.0
71.4
34.7
33.9
322.0
73.4
35.2
34.3
346.0
75.2
35.8
34.7
372.0
77.0
36.5
35.3
400.0
78.8
37.2
35.9
428.0
80.6
38.1
36.6
456.0
82.6
39.0
37.3
27
276.0
77.2
40.5
39.9
298.0
79.6
40.9
40.2
322.0
82.0
41.5
40.7
348.0
84.2
42.1
41.2
372.0
86.6
42.9
41.8
400.0
89.2
43.7
42.4
426.0
91.6
44.5
43.1
30
264.0
80.0
43.4
42.9
286.0
82.6
43.8
43.2
310.0
85.2
44.4
43.6
334.0
88.0
45.0
44.1
360.0
90.6
45.7
44.7
386.0
93.2
46.5
45.3
412.0
96.0
47.3
46.0
32
258.0
81.6
45.4
44.9
280.0
84.4
45.8
45.2
302.0
87.4
46.3
45.6
326.0
90.2
46.9
46.1
350.0
93.0
47.6
46.6
376.0
95.8
48.3
47.3
402.0
98.8
49.1
48.0
Air Temperature
35
246.0
84.0
48.3
47.9
268.0
87.2
48.7
48.1
290.0
90.2
49.2
48.5
314.0
93.2
49.7
49.0
338.0
96.4
50.4
49.5
362.0
99.6
51.1
50.2
388.0
102.6
51.9
50.8
LEGEND
CMP
Compressor Power (kW)
SCT(A) Saturated Condensing Temperature (C) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SCT(B) Saturated Condensing Temperature (C) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SDT(A) Saturated Discharge Temperature (C) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SDT(B) Saturated Discharge Temperature (C) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SST
Saturated Suction Temperature Entering Condensing Unit
TCG
Gross Cooling Capacity (kW)
46
206.0
90.8
59.1
58.9
226.0
94.8
59.4
59.0
246.0
99.0
59.7
59.3
268.0
103.0
60.2
59.7
290.0
107.2
60.7
60.2
312.0
111.2
61.4
60.7
334.0
115.4
62.1
61.3
49
195.6
92.0
62.1
61.9
214.0
96.4
62.3
62.0
234.0
100.8
62.7
62.3
254.0
105.2
63.1
62.6
276.0
109.6
63.6
63.1
298.0
114.0
64.2
63.6
320.0
118.4
64.8
64.2
52
185.0
93.2
65.1
64.8
204.0
97.8
65.2
65.0
222.0
102.4
65.6
65.2
242.0
107.2
65.9
65.5
264.0
111.8
66.4
66.0
284.0
116.4
67.0
66.5
306.0
121.2
67.6
67.0
63
10
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
21
330.0
80.9
34.7
34.0
33.9
31.9
356.0
83.2
35.2
34.5
34.3
32.4
383.0
85.4
35.8
35.2
34.7
33.0
410.0
87.5
36.5
36.0
35.3
33.6
440.0
89.7
37.2
36.7
35.9
34.3
470.0
91.8
38.1
37.6
36.6
34.9
501.0
94.1
39.0
38.4
37.3
35.6
27
307.0
87.2
40.5
39.8
39.9
37.7
331.0
90.0
40.9
40.2
40.2
38.2
357.0
92.8
41.5
40.9
40.7
38.8
385.0
95.5
42.1
41.6
41.2
39.5
412.0
98.3
42.9
42.3
41.8
40.1
441.0
101.2
43.7
43.1
42.4
40.7
470.0
104.0
44.5
44.0
43.1
41.4
30
295.0
90.1
43.4
42.7
42.9
40.7
319.0
93.1
43.8
43.1
43.2
41.2
345.0
96.2
44.4
43.7
43.6
41.7
371.0
99.4
45.0
44.4
44.1
42.3
398.0
102.4
45.7
45.1
44.7
43.0
426.0
105.5
46.5
45.9
45.3
43.6
455.0
108.7
47.3
46.7
46.0
44.3
32
288.0
91.9
45.4
44.6
44.9
42.6
312.0
95.1
45.8
45.0
45.2
43.1
336.0
98.5
46.3
45.6
45.6
43.7
362.0
101.7
46.9
46.3
46.1
44.3
388.0
105.0
47.6
47.0
46.6
44.9
416.0
108.3
48.3
47.8
47.3
45.5
445.0
111.6
49.1
48.6
48.0
46.2
Air Temperature
35
276.0
94.5
48.3
47.5
47.9
45.5
300.0
98.0
48.7
47.8
48.1
46.0
324.0
101.5
49.2
48.4
48.5
46.5
349.0
105.1
49.7
49.1
49.0
47.1
375.0
108.7
50.4
49.8
49.5
47.7
402.0
112.3
51.1
50.5
50.2
48.4
430.0
115.9
51.9
51.3
50.8
49.0
LEGEND
CMP
Compressor Power (kW)
SCT(A) Saturated Condensing Temperature (C) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SCT(B) Saturated Condensing Temperature (C) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SDT(A) Saturated Discharge Temperature (C) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SDT(B) Saturated Discharge Temperature (C) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SST
Saturated Suction Temperature Entering Condensing Unit
TCG
Gross Cooling Capacity (kW)
64
46
234.0
102.0
59.1
58.3
58.9
56.3
256.0
106.5
59.4
58.4
59.0
56.5
278.0
111.1
59.7
58.9
59.3
57.0
301.0
115.6
60.2
59.3
59.7
57.5
325.0
120.3
60.7
60.0
60.2
58.1
349.0
124.9
61.4
60.7
60.7
58.7
374.0
129.6
62.1
61.4
61.3
59.3
49
222.8
103.4
62.1
61.3
61.9
59.3
243.0
108.3
62.3
61.4
62.0
59.4
265.0
113.1
62.7
61.8
62.3
59.9
287.0
118.0
63.1
62.2
62.6
60.3
311.0
122.9
63.6
62.8
63.1
60.9
335.0
127.9
64.2
63.4
63.6
61.5
359.0
132.9
64.8
64.2
64.2
62.1
52
211.5
104.8
65.1
64.3
64.8
62.2
232.0
109.9
65.2
64.3
65.0
62.4
253.0
114.9
65.6
64.6
65.2
62.7
274.0
120.1
65.9
65.0
65.5
63.1
297.0
125.3
66.4
65.5
66.0
63.7
320.0
130.6
67.0
66.2
66.5
64.2
344.0
135.9
67.6*
66.9
67.0
64.8
10
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
SCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
21
52.7
12.0
32.8
56.9
12.3
33.4
61.4
12.5
34.0
66.0
12.8
34.7
70.8
13.1
35.5
75.8
13.4
36.3
80.9
13.7
37.1
27
48.5
13.0
38.5
52.6
13.4
39.0
56.9
13.8
39.6
61.4
14.2
40.3
66.0
14.5
41.0
70.8
14.9
41.8
75.7
15.3
42.6
30
46.4
13.5
41.3
50.4
14.0
41.8
54.6
14.4
42.4
59.0
14.8
43.0
63.5
15.2
43.8
68.3
15.6
44.5
73.1
16.0
45.3
32
44.9
13.8
43.2
48.9
14.3
43.7
53.1
14.8
44.3
57.4
15.2
44.9
61.9
15.7
45.6
66.5
16.1
46.4
71.3
16.5
47.1
Air Temperature
35
42.7
14.3
46.1
46.7
14.8
46.5
50.8
15.3
47.1
55.0
15.8
47.7
59.4
16.3
48.4
63.9
16.8
49.1
68.6
17.3
49.9
21
53.0
12.4
35.0
57.6
12.6
35.1
62.5
12.8
35.3
67.5
13.0
35.6
72.6
13.3
36.0
77.9
13.5
36.6
83.2
13.7
37.3
27
48.7
13.5
41.0
53.1
13.8
41.0
57.8
14.1
41.2
62.7
14.4
41.4
67.7
14.7
41.8
72.8
15.0
42.3
78.0
15.3
42.8
30
46.4
13.9
44.0
50.8
14.4
44.1
55.4
14.7
44.2
60.2
15.1
44.3
65.1
15.4
44.7
70.2
15.8
45.1
75.3
16.1
45.6
32
44.9
14.2
46.0
49.2
14.7
46.0
53.8
15.1
46.1
58.5
15.5
46.3
63.4
15.9
46.6
68.4
16.3
47.0
73.5
16.6
47.5
Air Temperature
35
42.7
14.6
49.0
46.8
15.2
49.0
51.4
15.6
49.1
56.0
16.1
49.2
60.8
16.5
49.5
65.7
17.0
49.9
70.8
17.4
50.3
46
34.5
15.4
56.7
38.2
16.1
57.0
42.1
16.8
57.5
46.0
17.6
57.9
50.1
18.3
58.5
54.3
18.9
59.2
58.5
19.6
59.9
49
32.2
15.6
59.7
35.8
16.4
59.9
39.6
17.1
60.3
43.5
17.9
60.8
47.5
18.7
61.3
51.6
19.4
61.9
55.8
20.2
62.6
52
29.9
15.6
62.6
33.5
16.5
62.7
37.2
17.4
63.1
41.0
18.2
63.6
44.9
19.1
64.1
48.9*
19.9*
64.7*
53.0*
20.7*
65.3*
49
31.9
15.6
63.0
35.6
16.5
63.0
39.7
17.4
63.0
43.9
18.2
63.1
48.3
18.9
63.2
52.8
19.7
63.4
57.5*
20.4*
63.7*
52
29.5*
15.6*
66.0*
33.2*
16.6*
66.0*
37.2*
17.6*
66.0*
41.2*
18.4*
66.1*
45.5*
19.3*
66.2*
50.0*
20.1*
66.3*
54.5*
20.9*
66.5*
49
45.8
21.9
62.2
50.1
22.9
62.5
54.8
23.9
62.8
59.6
24.9
63.2
64.6
25.9
63.8
69.8
27.0
64.4
75.1
28.0
65.1
52
43.3
22.2
65.1
47.5
23.3
65.3
52.1
24.3
65.7
56.7
25.4
66.1
61.5*
26.5*
66.6*
66.6*
27.6*
67.2*
71.7*
28.7*
67.9*
38AH054 CIRCUIT A
SST
(C)
2
10
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TDG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
46
34.2
15.6
60.0
38.0
16.4
60.0
42.2
17.1
60.0
46.5
17.8
60.1
51.0
18.5
60.2
55.7
19.2
60.5
60.4
19.8
60.8
38AH064 CIRCUIT A
SST
(C)
2
10
CMP
SDT
SST
TCG
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
21
70.7
16.7
34.9
76.4
17.2
35.4
82.5
17.7
36.1
88.8
18.1
36.8
95.4
18.6
37.7
102.0
19.1
38.6
109.0
19.6
39.5
27
65.0
18.1
40.7
70.5
18.7
41.1
76.3
19.3
41.7
82.3
19.9
42.4
88.5
20.5
43.2
94.9
21.1
44.1
102.0
21.7
44.9
30
62.3
18.8
43.6
67.5
19.4
44.0
73.2
20.1
44.6
79.0
20.7
45.2
85.1
21.4
46.0
91.4
22.0
46.8
97.8
22.7
47.7
LEGEND
Compressor Power, kW
Saturated Discharge Temperature (leaving compressor) (C)
Saturated Suction Temperature (entering condensing unit)
Total Cooling Capacity, Gross (kW)
32
60.4
19.2
45.5
65.7
19.9
45.9
71.2
20.5
46.5
76.9
21.2
47.1
82.8
21.9
47.8
89.0
22.6
48.6
95.3
23.4
49.5
43
50.8
21.1
56.3
55.5
21.9
56.5
60.5
22.8
57.0
65.6
23.7
57.5
70.9
24.7
58.1
76.5
25.6
58.8
82.1
26.5
59.6
46
48.2
21.5
59.2
52.8
22.4
59.4
57.6
23.4
59.9
62.6
24.4
60.3
67.7
25.3
60.9
73.1
26.3
61.6
78.6
27.3
62.3
65
10
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
21
52.8
12.2
33.8
57.3
12.4
34.0
62.2
12.6
34.3
67.1
12.8
34.7
72.3
13.0
35.1
77.7
13.2
35.5
83.2
13.3
36.0
27
48.4
13.3
39.8
52.8
13.6
40.0
57.4
13.9
40.2
62.2
14.2
40.6
67.1
14.5
41.0
72.3
14.8
41.4
77.6
15.1
41.9
21
70.0
17.1
36.4
75.7
17.6
36.9
81.7
18.1
37.6
87.9
18.6
38.4
94.4
19.2
39.2
101.0
19.7
40.2
108.0
20.2
41.1
27
64.5
18.5
42.1
69.9
19.1
42.6
75.6
19.7
43.2
81.5
20.3
43.9
87.6
21.0
44.7
94.0
21.6
45.6
101.0
22.3
46.5
30
46.2
13.8
42.8
50.4
14.2
42.9
55.0
14.5
43.2
59.7
14.9
43.5
64.5
15.3
43.9
69.6
15.6
44.4
74.8
15.9
44.8
32
44.7
14.1
44.8
48.9
14.5
44.9
53.4
14.9
45.2
58.0
15.3
45.5
62.8
15.7
45.8
67.8
16.1
46.3
72.9
16.4
46.8
Air Temperature
35
42.4
14.5
47.7
46.5
15.0
47.9
50.9
15.5
48.2
55.4
15.9
48.4
60.1
16.4
48.8
65.0
16.8
49.2
70.0
17.2
49.7
46
33.9
15.5
58.7
37.7
16.3
58.8
41.8
17.0
59.0
46.0
17.7
59.2
50.3
18.4
59.5
54.8
19.1
59.9
59.4
19.7
60.3
49
31.6
15.6
61.6
35.3
16.5
61.8
39.3
17.3
61.9
43.3
18.1
62.2
47.6
18.8
62.5
51.9
19.6
62.8
56.4
20.3
63.2
52
29.3
15.7
64.6
32.9
16.6
64.7
36.7
17.5
64.9
40.7
18.4
65.1
44.8
19.2
65.4
49.1*
20.0*
65.8*
53.5*
20.8*
66.1*
46
48.0
21.7
60.6
52.4
22.7
60.9
57.2
23.6
61.3
62.0
24.6
61.8
67.1
25.7
62.4
72.5
26.7
63.1
77.9
27.7
63.8
49
45.5
22.0
63.6
49.8
23.1
63.9
54.4
24.1
64.2
59.1
25.2
64.7
64.0
26.2
65.2
69.2
27.3
65.9
74.5*
28.4*
66.6*
52
43.1*
22.4*
66.5*
47.2*
23.5*
66.8*
51.6*
24.6*
67.2*
56.2
25.7*
67.6*
61.0*
26.8*
68.1
66.0*
27.9*
68.7*
71.0*
29.1*
69.4*
49
51.2
24.1
62.0
56.3
25.3
62.2
61.6
26.5
62.5
67.1
27.7
62.9
72.7
28.8
63.3
78.6
30.0
63.9
84.5
31.1
64.5
52
48.3
24.3
65.0
53.2
25.6
65.1
58.4
26.9
65.4
63.8
28.1
65.8
69.3*
29.4*
66.2*
75.0*
30.6*
66.7*
80.8*
31.8*
67.3*
38AH054 CIRCUIT B
SST
(C)
2
10
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
30
61.7
19.1
45.0
67.0
19.8
45.5
72.6
20.4
46.1
78.3
21.1
46.7
84.3
21.8
47.5
90.5
22.5
48.3
96.9
23.2
49.2
32
60.0
19.5
47.0
65.1
20.2
47.4
70.6
20.9
48.0
76.2
21.6
48.6
82.1
22.4
49.3
88.2
23.1
50.1
94.5
23.9
51.0
38AH064 CIRCUIT B
SST
(C)
2
10
CMP
SDT
SST
TCG
66
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
21
77.8
19.0
34.5
83.9
19.4
34.8
90.4
19.8
35.3
97.0
20.3
35.9
104.0
20.7
36.6
111.0
21.1
37.4
118.0
21.5
38.2
27
72.2
20.5
40.3
78.1
21.1
40.7
84.4
21.7
41.2
90.8
22.3
41.7
97.4
22.9
42.4
104.0
23.4
43.1
111.0
24.0
43.9
30
69.4
21.2
43.3
75.2
21.9
43.6
81.4
22.5
44.0
87.6
23.2
44.6
94.1
23.9
45.2
101.0
24.5
45.9
108.0
25.2
46.7
LEGEND
Compressor Power, kW
Saturated Discharge Temperature (leaving compressor) (C)
Saturated Suction Temperature (entering condensing unit)
Total Cooling Capacity, Gross (kW)
43
57.0
23.5
56.1
62.3
24.5
56.3
67.9
25.5
56.7
73.6
26.5
57.1
79.6
27.5
57.6
85.7
28.5
58.2
91.9
29.5
58.9
46
54.1
23.9
59.1
59.3
25.0
59.2
64.8
26.1
59.6
70.4
27.1
60.0
76.1
28.2
60.4
82.1
29.3
61.1
88.2
30.3
61.7
10
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
21
78.6
18.8
33.9
84.7
19.3
34.4
91.1
19.7
35.0
97.6
20.2
35.7
104.0
20.6
36.4
112.0
21.0
37.2
119.0
21.4
38.0
27
73.2
20.4
39.7
79.1
20.9
40.1
85.3
21.5
40.7
91.5
22.1
41.3
98.1
22.7
42.0
105.0
23.3
42.7
112.0
23.9
43.5
30
70.5
21.1
42.7
76.3
21.7
43.0
82.3
22.4
43.5
88.5
23.0
44.1
94.9
23.7
44.8
102.0
24.4
45.5
108.0
25.0
46.3
43
58.2
23.4
55.5
63.6
24.4
55.5
69.3
25.4
55.9
75.0
26.3
56.3
80.9
27.3
56.9
87.0
28.3
57.5
93.1
29.3
58.2
46
55.3
23.8
58.5
60.6
24.9
58.5
66.2
25.9
58.7
71.8
27.0
59.1
77.6
28.0
59.6
83.5
29.1
60.3
89.6
30.1
61.0
49
52.4
24.1
61.4
57.6
25.3
61.4
63.1
26.4
61.6
68.6
27.5
61.9
74.3
28.6
62.4
80.1
29.8
63.0
86.0
30.9
63.7
52
49.5
24.3
64.4
54.5
25.6
64.4
59.9
26.8
64.6
65.4
28.0
64.8
70.9
29.2
65.3
76.6*
30.4*
65.8*
82.4*
31.6*
66.4*
49
71.0
33.9
64.7
77.2
35.5
64.7
84.0
37.0
64.8
91.0
38.6
65.0
98.3
40.1
65.2
106.0
41.7
65.6
114.0*
43.3*
66.0*
52
67.8*
34.4*
67.7*
73.8*
36.0*
67.7*
80.4*
37.6*
67.8*
87.2*
39.2*
67.9*
94.3*
40.9*
68.2*
102.0*
42.5*
68.5*
109.0*
44.2*
68.9*
38AH084 CIRCUIT A
SST
(C)
2
10
CMP
SDT
SST
TCG
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
21
102.0
27.2
36.7
110.0
28.0
36.8
119.0
28.7
37.1
128.0
29.4
37.5
137.0
30.2
38.0
147.0
31.0
38.7
157.0
31.8
39.5
27
95.0
29.1
42.7
103.0
30.0
42.8
111.0
30.9
43.0
120.0
31.8
43.3
129.0
32.7
43.8
138.0
33.7
44.4
147.0
34.7
45.1
30
91.7
29.9
45.7
99.2
30.9
45.8
107.0
31.9
46.0
116.0
32.9
46.2
125.0
33.9
46.7
134.0
35.0
47.3
143.0
36.0
47.9
32
89.4
30.4
47.7
96.8
31.5
47.8
105.0
32.6
48.0
113.0
33.6
48.2
122.0
34.7
48.6
131.0
35.8
49.2
140.0
36.9
49.8
LEGEND
Compressor Power, kW
Saturated Discharge Temperature (leaving compressor) (C)
Saturated Suction Temperature (entering condensing unit)
Total Cooling Capacity, Gross (kW)
Air Temperature
35
86.1
31.2
50.7
93.3
32.3
50.8
101.0
33.5
50.9
109.0
34.6
51.2
118.0
35.8
51.5
126.0
37.0
52.0
135.0
38.2
52.6
46
74.2
33.4
61.7
80.6
34.9
61.7
87.6
36.3
61.9
94.8
37.8
62.0
102.0
39.3
62.3
110.0
40.8
62.7
118.0
42.3
63.1
67
10
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
21
103.0
26.4
34.2
110.0
27.2
34.8
118.0
28.1
35.6
127.0
28.9
36.3
135.0
29.8
37.1
145.0
30.6
38.0
154.0
31.4
38.9
27
96.0
28.3
39.9
103.0
29.3
40.5
111.0
30.3
41.2
119.0
31.3
41.9
127.0
32.3
42.7
136.0
33.3
43.6
145.0
34.4
44.4
30
92.7
29.1
42.8
99.8
30.2
43.3
107.0
31.3
44.0
115.0
32.4
44.7
123.0
33.5
45.5
132.0
34.6
46.3
140.0
35.7
47.2
32
90.5
29.6
44.7
97.5
30.8
45.2
105.0
31.9
45.9
113.0
33.1
46.6
120.0
34.2
47.4
129.0
35.4
48.2
137.0
36.6
49.0
Air Temperature
35
87.3
30.4
47.6
94.1
31.6
48.0
101.0
32.8
48.7
109.0
34.0
49.4
116.0
35.3
50.2
125.0
36.6
51.0
133.0
37.8
51.8
46
75.7
32.8
58.2
81.9
34.2
58.5
88.4
35.7
59.1
95.1
37.2
59.7
102.0
38.7
60.4
109.0
40.3
61.1
117.0
41.8
61.9
49
72.6
33.3
61.2
78.6
34.8
61.4
85.0
36.4
61.9
91.5
37.9
62.5
98.2
39.5
63.1
105.0
41.2
63.9
112.0
42.8
64.6
52
69.4
33.8
64.1
75.3
35.4
64.3
81.5
37.0
64.8
87.8
38.6
65.3
94.4
40.3
65.9
101.0*
42.0*
66.6*
108.0*
43.7*
67.4*
21
102.0
26.9
35.7
111.0
27.6
35.8
119.0
28.3
36.2
128.0
29.1
36.7
137.0
29.8
37.3
147.0
30.6
38.1
157.0
31.4
38.9
27
95.6
28.8
41.6
103.0
29.7
41.8
112.0
30.6
42.1
120.0
31.5
42.5
129.0
32.4
43.0
138.0
33.4
43.7
147.0
34.4
44.5
30
92.2
29.6
44.6
99.7
30.6
44.7
108.0
31.6
45.0
116.0
32.6
45.4
125.0
33.6
45.9
134.0
34.7
46.5
143.0
35.7
47.3
32
89.9
30.2
46.6
97.4
31.2
46.7
105.0
32.3
47.0
113.0
33.3
47.3
122.0
34.4
47.8
131.0
35.5
48.4
140.0
36.6
49.1
Air Temperature
35
86.6
30.9
49.6
93.8
32.1
49.7
102.0
33.2
49.9
110.0
34.3
50.2
118.0
35.5
50.7
126.0
36.7
51.3
135.0
37.9
51.9
46
74.7
33.2
60.6
81.1
34.7
60.6
88.1
36.1
60.8
95.3
37.5
61.0
103.0
39.0
61.4
111.0
40.5
61.8
118.0
42.0
62.3
49
71.5
33.8
63.6
77.7
35.3
63.6
84.5
36.8
63.7
91.5
38.3
63.9
98.7
39.8
64.3
106.0
41.4
64.7
114.0
43.0
65.2
52
68.4*
34.2*
66.6*
74.4*
35.8*
66.6*
80.8*
37.4*
66.7*
87.7*
39.0*
66.9*
94.7*
40.6*
67.2*
102.0*
42.3*
67.6*
110.0*
43.9*
68.1*
38AH084 CIRCUIT B
SST
(C)
2
10
CMP
SDT
SST
TCG
68
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
LEGEND
Compressor Power, kW
Saturated Discharge Temperature (leaving compressor) (C)
Saturated Suction Temperature (entering condensing unit)
Total Cooling Capacity, Gross (kW)
10
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
21
130.0
31.8
35.5
33.6
140.0
32.7
36.2
34.0
150.0
33.7
37.1
34.6
161.0
34.7
38.0
35.2
172.0
35.7
39.0
35.8
183.0
36.7
40.1
36.5
195.0
37.7
41.1
37.2
27
120.0
34.2
41.2
39.7
130.0
35.3
41.8
40.1
140.0
36.5
42.6
40.6
150.0
37.7
43.5
41.2
161.0
38.9
44.4
41.9
172.0
40.1
45.4
42.6
183.0
41.3
46.4
43.3
30
116.0
35.3
44.0
42.8
125.0
36.6
44.5
43.1
135.0
37.9
45.3
43.7
145.0
39.2
46.2
44.3
155.0
40.5
47.1
44.9
166.0
41.8
48.0
45.6
177.0
43.1
49.1
46.4
32
112.0
36.0
45.9
44.8
122.0
37.3
46.4
45.1
131.0
38.7
47.2
45.7
141.0
40.1
48.0
46.3
152.0
41.5
48.9
46.9
162.0
42.9
49.8
47.6
173.0
44.3
50.8
48.4
Air Temperature
35
108.0
37.0
48.8
47.8
117.0
38.4
49.2
48.1
126.0
39.9
49.9
48.6
136.0
41.4
50.7
49.2
146.0
42.9
51.6
49.9
156.0
44.4
52.5
50.6
167.0
45.9
53.5
51.3
21
124.0
28.9
34.4
32.6
134.0
29.8
35.1
33.1
144.0
30.7
36.0
33.6
154.0
31.5
36.9
34.2
165.0
32.4
37.9
34.8
176.0
33.3
38.9
35.5
188.0
34.3
39.9
36.2
27
115.0
31.2
40.0
38.6
124.0
32.3
40.6
39.1
134.0
33.4
41.4
39.6
144.0
34.4
42.3
40.2
154.0
35.5
43.2
40.8
165.0
36.6
44.1
41.5
176.0
37.7
45.2
42.2
30
110.0
32.4
42.8
41.7
119.0
33.5
43.4
42.1
128.0
34.7
44.1
42.6
138.0
35.9
44.9
43.2
148.0
37.1
45.8
43.8
159.0
38.3
46.8
44.5
170.0
39.5
47.8
45.2
32
107.0
33.1
44.7
43.7
116.0
34.3
45.2
44.0
125.0
35.5
46.0
44.6
135.0
36.7
46.7
45.1
145.0
38.0
47.6
45.8
155.0
39.3
48.6
46.5
166.0
40.6
49.5
47.2
Air Temperature
35
102.0
34.0
47.5
46.7
111.0
35.3
48.0
47.0
120.0
36.7
48.7
47.5
129.0
38.0
49.5
48.1
139.0
39.4
50.3
48.7
149.0
40.7
51.2
49.4
160.0
42.1
52.2
50.1
46
89.1
39.4
59.4
58.9
97.9
41.4
59.6
59.0
107.0
43.3
60.2
59.4
116.0
45.2
60.8
59.9
125.0
47.1
61.5
60.5
135.0
49.1
62.3
61.1
145.0
51.0
63.2
61.8
49
84.0
39.8
62.3
61.9
92.6
41.9
62.5
62.0
101.0
43.9
63.0
62.3
110.0
46.0
63.5
62.7
120.0
48.1
64.2
63.3
129.0
50.1
65.0
64.0
139.0
52.2
65.9
64.7
52
78.8
40.0
65.3
64.9
87.3
42.3
65.4
64.9
96.0
44.5
65.8
65.3
105.0
46.7
66.3
65.6
114.0
48.9
66.9
66.2
123.0
51.1
67.7
66.8
132.0
53.3
68.5*
67.5
38AH104 CIRCUIT A
SST
(C)
2
10
CMP
SCT
SDT
SST
TCG
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
LEGEND
Compressor Power, kW
Saturated Condensing Temperature (C)
Saturated Discharge Temperature (leaving compressor) (C)
Saturated Suction Temperature (entering condensing unit)
Total Cooling Capacity, Gross (kW)
46
84.7
36.8
58.1
57.7
92.8
38.5
58.4
57.8
101.0
40.2
58.9
58.2
110.0
42.0
59.5
58.7
119.0
43.7
60.2
59.2
128.0
45.5
61.0
59.9
137.0
47.2
61.9
60.6
49
80.0
37.3
61.1
60.7
88.0
39.2
61.3
60.8
96.3
41.0
61.7
61.1
105.0
42.8
62.3
61.5
113.0
44.7
63.0
62.1
122.0
46.5
63.7
62.7
132.0
48.4
64.5
63.4
52
75.3
37.7
64.0
63.7
83.1
39.7
64.1
63.7
91.2
41.7
64.6
64.0
99.4
43.6
65.1
64.4
108.0
45.6
65.7
64.9
117.0
47.5
66.4
65.5
126.0
49.5
67.2
66.2
69
10
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
21
103.0
26.3
33.8
32.3
111.0
27.0
34.2
32.4
119.0
27.8
34.9
32.8
128.0
28.6
35.6
33.3
137.0
29.4
36.4
33.8
146.0
30.2
37.3
34.3
155.0
31.0
38.2
34.9
27
96.5
28.1
39.6
38.5
104.0
29.0
39.9
38.6
112.0
30.0
40.5
39.0
120.0
30.9
41.2
39.4
129.0
31.9
41.9
39.9
137.0
32.9
42.7
40.4
146.0
33.9
43.6
41.0
30
93.1
29.0
42.5
41.5
101.0
30.0
42.8
41.7
108.0
31.0
43.4
42.0
116.0
32.1
44.0
42.4
124.0
33.1
44.7
42.9
133.0
34.2
45.5
43.5
142.0
35.3
46.3
44.1
32
90.9
29.6
44.5
43.6
98.2
30.6
44.8
43.7
106.0
31.7
45.3
44.0
114.0
32.8
45.9
44.4
122.0
33.9
46.5
44.9
130.0
35.0
47.3
45.5
139.0
36.2
48.2
46.1
Air Temperature
35
87.6
30.4
47.4
46.7
94.7
31.5
47.7
46.8
102.0
32.6
48.2
47.1
110.0
33.8
48.7
47.4
118.0
35.0
49.3
47.9
126.0
36.2
50.1
48.4
134.0
37.4
50.9
49.0
21
141.0
33.9
35.7
33.5
151.0
35.1
36.5
34.0
163.0
36.2
37.5
34.7
174.0
37.4
38.5
35.3
186.0
38.6
39.6
36.0
199.0
39.8
40.7
36.7
212.0
41.1
41.9
37.5
27
130.0
36.5
41.2
39.5
140.0
37.8
41.9
40.0
151.0
39.2
42.9
40.7
162.0
40.6
43.8
41.4
174.0
42.0
44.8
42.1
186.0
43.4
45.9
42.8
198.0
44.9
47.0
43.6
30
125.0
37.7
43.9
42.6
135.0
39.1
44.7
43.1
145.0
40.6
45.5
43.7
156.0
42.1
46.4
44.4
168.0
43.6
47.4
45.1
179.0
45.2
48.5
45.8
191.0
46.8
49.5
46.6
32
122.0
38.5
45.8
44.5
131.0
40.0
46.5
45.0
142.0
41.5
47.3
45.7
152.0
43.1
48.2
46.3
163.0
44.7
49.2
47.1
175.0
46.3
50.2
47.8
187.0
47.9
51.3
48.6
Air Temperature
35
117.0
39.6
48.6
47.5
126.0
41.2
49.2
48.0
136.0
42.8
50.0
48.6
146.0
44.5
50.9
49.3
157.0
46.2
51.8
50.0
168.0
47.9
52.8
50.7
180.0
49.6
53.9
51.5
46
75.7
32.8
58.3
57.9
82.1
34.2
58.4
57.9
89.0
35.6
58.8
58.1
95.9
37.1
59.2
58.4
103.0
38.5
59.7
58.8
111.0
40.0
60.3
59.3
118.0
41.5
61.0
59.8
49
72.5
33.4
61.3
60.9
78.8
34.8
61.4
60.9
85.4
36.3
61.7
61.1
92.2
37.8
62.1
61.3
99.2
39.4
62.5
61.7
106.0
40.9
63.1
62.2
114.0
42.5
63.8
62.7
52
69.4
33.9
64.3
63.9
75.4
35.4
64.4
63.9
81.9
37.0
64.6
64.1
88.4
38.5
65.0
64.3
95.3
40.2
65.4
64.7
102.0
41.8
66.0
65.1
110.0
43.5
66.6
65.6
38AH104 CIRCUIT B
SST
(C)
2
10
CMP
SCT
SDT
SST
TCG
70
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
LEGEND
Compressor Power, kW
Saturated Condensing Temperature (C)
Saturated Discharge Temperature (leaving compressor) (C)
Saturated Suction Temperature (entering condensing unit)
Total Cooling Capacity, Gross (kW)
46
98.4
42.9
59.1
58.5
107.0
44.9
59.5
58.8
116.0
46.9
60.1
59.3
125.0
48.9
60.8
59.8
135.0
51.0
61.7
60.5
145.0
53.1
62.6
61.2
155.0
55.2
63.5
62.0
49
93.6
43.7
61.9
61.4
102.0
45.7
62.3
61.7
111.0
47.8
62.9
62.2
120.0
50.0
63.6
62.7
129.0
52.1
64.4
63.4
139.0
54.3
65.2
64.1
149.0
56.6
66.1
64.8
52
88.9
44.4
64.9
64.4
97.0
46.5
65.2
64.6
106.0
48.7
65.7
65.1
114.0
50.9
66.3
65.6
123.0
53.2
67.1
66.2
133.0
55.5
67.9
66.9
142.0
57.9
68.7*
67.6
10
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
21
149.0
35.7
34.7
33.9
161.0
36.7
35.2
34.3
173.0
37.6
35.8
34.7
186.0
38.5
36.5
35.3
200.0
39.4
37.2
35.9
214.0
40.3
38.1
36.6
228.0
41.3
39.0
37.3
27
138.0
38.6
40.5
39.9
149.0
39.8
40.9
40.2
161.0
41.0
41.5
40.7
174.0
42.1
42.1
41.2
186.0
43.3
42.9
41.8
200.0
44.6
43.7
42.4
213.0
45.8
44.5
43.1
30
132.0
40.0
43.4
42.9
143.0
41.3
43.8
43.2
155.0
42.6
44.4
43.6
167.0
44.0
45.0
44.1
180.0
45.3
45.7
44.7
193.0
46.6
46.5
45.3
206.0
48.0
47.3
46.0
32
129.0
40.8
45.4
44.9
140.0
42.2
45.8
45.2
151.0
43.7
46.3
45.6
163.0
45.1
46.9
46.1
175.0
46.5
47.6
46.6
188.0
47.9
48.3
47.3
201.0
49.4
49.1
48.0
Air Temperature
35
123.0
42.0
48.3
47.9
134.0
43.6
48.7
48.1
145.0
45.1
49.2
48.5
157.0
46.6
49.7
49.0
169.0
48.2
50.4
49.5
181.0
49.8
51.1
50.2
194.0
51.3
51.9
50.8
27
169.0
48.6
39.8
37.7
182.0
50.2
40.2
38.2
196.0
51.8
40.9
38.8
211.0
53.4
41.6
39.5
226.0
55.0
42.3
40.1
241.0
56.6
43.1
40.7
257.0
58.2
44.0
41.4
30
163.0
50.1
42.7
40.7
176.0
51.8
43.1
41.2
190.0
53.6
43.7
41.7
204.0
55.4
44.4
42.3
218.0
57.1
45.1
43.0
233.0
58.9
45.9
43.6
249.0
60.7
46.7
44.3
32
159.0
51.1
44.6
42.6
172.0
52.9
45.0
43.1
185.0
54.8
45.6
43.7
199.0
56.6
46.3
44.3
213.0
58.5
47.0
44.9
228.0
60.4
47.8
45.5
244.0
62.2
48.6
46.2
Air Temperature
35
153.0
52.5
47.5
45.5
166.0
54.4
47.8
46.0
179.0
56.4
48.4
46.5
192.0
58.5
49.1
47.1
206.0
60.5
49.8
47.7
221.0
62.5
50.5
48.4
236.0
64.6
51.3
49.0
46
103.0
45.4
59.1
58.9
113.0
47.4
59.4
59.0
123.0
49.5
59.7
59.3
134.0
51.5
60.2
59.7
145.0
53.6
60.7
60.2
156.0
55.6
61.4
60.7
167.0
57.7
62.1
61.3
49
97.8
46.0
62.1
61.9
107.0
48.2
62.3
62.0
117.0
50.4
62.7
62.3
127.0
52.6
63.1
62.6
138.0
54.8
63.6
63.1
149.0
57.0
64.2
63.6
160.0
59.2
64.8
64.2
52
92.5
46.6
65.1
64.8
102.0
48.9
65.2
65.0
111.0
51.2
65.6
65.2
121.0
53.5
65.9
65.5
132.0
55.9
66.4
66.0
142.0
58.2
67.0
66.5
153.0
60.6
67.6*
67.0
10
CMP
SCT
SDT
SST
TCG
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
21
181.0
45.2
34.0
31.9
195.0
46.5
34.5
32.4
210.0
47.8
35.2
33.0
224.0
49.0
36.0
33.6
240.0
50.3
36.7
34.3
256.0
51.5
37.6
34.9
273.0
52.8
38.4
35.6
LEGEND
Compressor Power, kW
Saturated Condensing Temperature (C)
Saturated Discharge Temperature (leaving compressor) (C)
Saturated Suction Temperature (entering condensing unit)
Total Cooling Capacity, Gross (kW)
46
131.0
56.6
58.3
56.3
143.0
59.1
58.4
56.5
155.0
61.6
58.9
57.0
167.0
64.1
59.3
57.5
180.0
66.7
60.0
58.1
193.0
69.3
60.7
58.7
207.0
71.9
61.4
59.3
49
125.0
57.4
61.3
59.3
136.0
60.1
61.4
59.4
148.0
62.7
61.8
59.9
160.0
65.4
62.2
60.3
173.0
68.1
62.8
60.9
186.0
70.9
63.4
61.5
199.0
73.7
64.2
62.1
52
119.0
58.2
64.3
62.2
130.0
61.0
64.3
62.4
142.0
63.7
64.6
62.7
153.0
66.6
65.0
63.1
165.0
69.4
65.5
63.7
178.0
72.4
66.2
64.2
191.0
75.3
66.9
64.8
71
25
30
35
40
45
50
90
242.0
25.8
111.0
279.0
27.1
111.5
317.0
28.4
112.0
357.0
29.6
113.0
400.0
30.9
113.5
444.0
32.0
115.0
491.0
33.1
117.0
Air Temperature
95
230.0
26.2
116.0
265.0
27.8
116.0
303.0
29.2
116.5
342.0
30.6
118.0
384.0
31.9
118.5
427.0
33.2
120.0
473.0
34.5
121.5
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
70
293.0
22.9
91.0
332.0
23.7
91.6
373.0
24.4
92.4
416.0
25.1
93.6
462.0
25.8
94.9
509.0
26.4
96.4
560.0
27.0
98.0
80
268.0
24.4
102.0
305.0
25.5
101.5
345.0
26.5
102.0
387.0
27.5
103.5
431.0
28.4
104.5
477.0
29.3
106.0
525.0
30.2
107.5
85
255.0
25.1
106.0
292.0
26.3
106.5
331.0
27.5
107.0
372.0
28.6
108.0
415.0
29.7
109.5
460.0
30.6
111.0
508.0
31.7
112.5
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
70
341.0
27.8
95.5
387.0
28.9
96.0
435.0
29.9
96.7
485.0
30.9
97.7
538.0
31.9
99.2
593.0
32.9
100.9
652.0
34.0
102.7
80
313.0
29.5
105.5
357.0
30.9
105.5
403.0
32.3
106.5
451.0
33.5
107.0
503.0
34.8
108.5
555.0
36.1
110.0
611.0
37.4
112.0
85
299.0
30.2
110.5
342.0
31.8
110.5
386.0
33.3
111.0
434.0
34.8
112.0
485.0
36.1
113.0
537.0
37.6
114.5
592.0
39.1
116.5
90
286.0
30.9
115.5
327.0
32.6
115.5
371.0
34.3
116.0
417.0
35.9
117.0
467.0
37.5
118.0
518.0
39.1
119.5
571.0
40.6
121.0
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
70
415.0
33.6
93.4
468.0
34.9
94.0
523.0
36.2
95.0
582.0
37.4
96.3
644.0
38.7
98.0
708.0
40.0
100.0
776.0
41.2
102.0
80
383.0
35.7
103.0
434.0
37.4
104.0
487.0
39.0
104.5
544.0
40.6
105.5
603.0
42.2
107.5
664.0
43.9
109.0
729.0
45.5
111.0
85
368.0
36.7
108.0
417.0
38.6
109.0
469.0
40.3
109.5
525.0
42.1
110.5
582.0
43.9
112.5
642.0
45.7
114.0
706.0
47.5
116.0
90
352.0
37.5
113.0
401.0
39.6
113.5
451.0
41.5
114.5
505.0
43.5
115.5
562.0
45.5
116.5
620.0
47.4
118.5
682.0
49.4
120.5
Air Temperature
95
337.0
38.3
118.0
384.0
40.6
118.5
434.0
42.7
119.0
487.0
44.8
120.5
542.0
47.0
121.5
600.0
49.1
123.5
660.0
51.3
125.0
115
175.9
27.1
135.5
210.0
29.4
136.0
244.0
31.6
136.5
281.0
33.6
136.5
320.0
35.6
138.0
359.0
37.5
139.0
401.0
39.3
140.5
120
162.6
27.0
140.5
195.1
29.6
141.0
230.0
31.9
141.0
265.0
34.1
141.5
303.0
36.3
142.5
343.0
38.4
144.0
384.0
40.4
145.5
125
149.1
26.7
145.5
180.8
29.5
146.0
214.0
32.1
146.0
250.0
34.5
146.5
287.0
36.9
147.5
325.0
39.2
148.5
366.0
41.3
149.5
120
204.9
33.0
145.5
239.2
35.9
145.5
277.0
38.5
145.5
316.0
41.1
146.0
359.0
43.7
146.5
403.0
46.3
148.0
450.0*
48.8*
149.0*
125
191.2*
33.0*
150.5*
225.1*
36.0*
150.5*
261.0*
38.9*
150.5*
300.0*
41.7*
151.0*
341.0*
44.5*
151.5*
385.0*
47.1*
153.0*
431.0*
49.8*
153.5*
120
261.0
40.8
143.0
302.0
43.9
143.0
346.0
47.0
144.0
393.0
50.0
144.5
442.0
53.0
145.5
493.0
56.1
146.6
546.0
59.1
148.5
125
246.0
41.0
148.0
285.0
44.3
148.0
328.0
47.5
149.0
374.0
50.7
149.5
421.0*
54.0*
150.5*
471.0*
57.1*
151.5*
523.0*
60.3*
153.5*
38AH054
SST
(F)
20
25
30
35
40
45
50
115
217.6
32.9
140.5
253.0
35.6
140.5
292.0
38.0
141.0
333.0
40.5
141.0
377.0
42.9
142.0
423.0
45.2
143.0
471.0
47.5
144.5
38AH064
SST
(F)
20
25
30
35
40
45
50
CMP
SDT
SST
TCG
72
LEGEND
Compressor Power, kW
Saturated Discharge Temperature (leaving compressor) (F)
Saturated Suction Temperature (entering condensing unit)
Total Cooling Capacity, Gross (1000 Btuh)
115
275.0
40.5
138.0
318.0
43.4
138.0
363.0
46.3
139.0
410.0
49.2
139.5
461.0
52.0
140.5
514.0
54.9
142.5
569.0
57.7
143.5
25
30
35
40
45
50
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
70
513.0
42.4
92.1
574.0
44.1
92.7
638.0
45.8
93.9
706.0
47.7
95.5
776.0
49.5
97.3
850.0
51.2
99.3
930.0
53.0
101.5
80
478.0
44.9
102.0
538.0
47.0
102.5
600.0
49.1
103.5
664.0
51.3
104.5
731.0
53.6
106.5
803.0
55.8
108.5
879.0
57.9
110.5
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
70
574.0
50.7
97.1
644.0
52.9
97.2
721.0
54.9
97.4
802.0
56.9
98.1
887.0
58.9
99.2
976.0
61.1
100.5
1067.0
63.3
102.5
80
536.0
53.3
107.0
604.0
55.9
107.0
676.0
58.5
107.0
754.0
60.9
108.0
835.0
63.5
109.0
920.0
66.1
110.5
1009.0
68.7
112.0
85
461.0
46.0
107.0
520.0
48.3
107.0
580.0
50.6
108.0
643.0
53.0
109.5
710.0
55.4
111.5
780.0
57.8
113.0
853.0
60.3
115.0
90
444.0
47.1
112.0
501.0
49.6
112.0
561.0
52.1
113.0
623.0
54.6
114.5
688.0
57.2
116.0
756.0
59.8
118.0
828.0
62.5
120.0
Air Temperature
95
427.0
48.1
117.0
482.0
50.7
117.0
541.0
53.4
118.0
603.0
56.1
119.0
666.0
58.9
120.5
733.0
61.8
122.5
803.0
64.6
124.5
115
360.0
50.8
136.5
410.0
54.3
137.0
463.0
57.8
137.0
520.0
61.3
138.0
578.0
64.8
139.5
640.0
68.4
141.0
703.0
72.1
143.0
120
342.0
51.2
142.0
392.0
54.9
142.0
444.0
58.6
142.0
499.0
62.3
143.0
557.0
66.0
144.0
616.0
69.8
145.5
678.0
73.7
147.0
125
326.0
51.6
147.0
373.0
55.4
147.0
425.0
59.3
147.0
479.0
63.2
148.0
534.0
67.1
148.5
593.0*
71.1*
150.0*
653.0*
75.1*
152.0*
115
412.0
59.9
142.0
467.0
64.0
142.0
526.0
68.0
142.0
590.0
72.0
143.0
659.0
76.1
143.0
731.0
80.2
144.0
807.0
84.4
145.0
120
395.0
60.6
147.0
448.0
64.8
147.0
506.0
69.0
147.0
568.0
73.2
147.0
634.0
77.5
148.0
705.0
81.8
149.0
779.0
86.2
150.0
125
378.0*
61.1*
152.0*
430.0*
65.5*
152.0*
486.0*
69.9*
152.0*
546.0*
74.4*
152.0*
610.0*
78.8*
153.0*
679.0*
83.3*
154.0*
750.0*
87.9*
154.5*
38AH084
SST
(F)
20
25
30
35
40
45
50
CMP
SDT
SST
TCG
85
518.0
54.5
112.0
584.0
57.3
112.0
654.0
60.1
112.0
730.0
62.9
113.0
809.0
65.5
113.5
893.0
68.3
115.0
980.0
71.3
116.5
90
500.0
55.6
117.0
564.0
58.7
117.0
632.0
61.7
117.0
706.0
64.7
118.0
785.0
67.5
118.5
866.0
70.6
119.5
950.0
73.7
121.5
LEGEND
Compressor Power, kW
Saturated Discharge Temperature (leaving compressor) (F)
Saturated Suction Temperature (entering condensing unit)
Total Cooling Capacity, Gross (1000 Btuh)
73
20
25
30
35
40
45
50
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
70
657.0
54.3
93.9
92.1
91.7
90.4
738.0
56.5
95.0
92.4
92.1
90.2
821.0
58.8
96.7
93.3
93.0
90.5
907.0
61.3
98.7
94.7
94.3
91.2
999.0
63.8
101.0
96.5
95.7
92.3
1093.0
66.3
104.0
98.6
97.4
93.6
1193.0
68.9
106.0
101.0
99.1
95.1
80
611.0
57.4
104.0
102.0
102.0
101.0
689.0
60.2
105.0
102.0
102.0
100.0
769.0
62.9
106.0
103.0
103.0
101.0
853.0
65.8
108.0
104.0
104.0
101.0
940.0
68.8
110.0
106.0
106.0
102.0
1031.0
71.8
112.0
108.0
108.0
104.0
1127.0
74.8
115.0
110.0
109.0
105.0
85
588.0
59.0
109.0
107.0
107.0
106.0
663.0
62.0
109.0
107.0
108.0
106.0
743.0
65.0
111.0
108.0
108.0
106.0
825.0
68.1
112.0
109.0
109.0
107.0
911.0
71.3
115.0
111.0
111.0
108.0
1001.0
74.6
117.0
112.0
113.0
109.0
1095.0
77.8
119.0
114.0
114.0
110.0
LEGEND
CMP
Compressor Power (kW)
SCT(A) Saturated Condensing Temperature (F) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SCT(B) Saturated Condensing Temperature (F) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SDT(A) Saturated Discharge Temperature (F) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SDT(B) Saturated Discharge Temperature (F) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SST
Saturated Suction Temperature Entering Condensing Unit
TCG
Gross Cooling Capacity (1000 Btuh)
74
110
470.0
63.9
134.0
132.0
133.0
131.0
538.0
68.3
134.0
132.0
133.0
131.0
611.0
72.7
134.0
132.0
133.0
131.0
686.0
77.0
136.0
133.0
134.0
132.0
764.0
81.4
137.0
134.0
135.0
132.0
845.0
86.0
139.0
136.0
137.0
134.0
929.0
90.5
142.0
137.0
139.0
135.0
115
446.0
64.4
139.0
137.0
138.0
136.0
514.0
69.1
139.0
137.0
138.0
136.0
585.0
73.8
139.0
137.0
138.0
136.0
658.0
78.4
140.0
138.0
139.0
137.0
734.0
83.1
142.0
139.0
140.0
137.0
814.0
87.9
144.0
140.0
142.0
138.0
896.0
92.7
146.0
142.0
143.0
140.0
120
423.0
64.7
144.0
142.0
143.0
142.0
488.0
69.8
144.0
142.0
143.0
141.0
557.0
74.7
144.0
142.0
143.0
141.0
630.0
79.6
145.0
143.0
144.0
142.0
704.0
84.5
146.0
144.0
145.0
142.0
782.0
89.6
148.0
145.0
146.0
143.0
862.0
94.7
150.0
147.0
148.0
145.0
125
400.0
64.8
149.0
147.0
148.0
147.0
463.0
70.2
149.0
147.0
148.0
146.0
531.0
75.5
149.0
147.0
148.0
146.0
602.0
80.7
150.0
148.0
149.0
147.0
675.0
85.9
151.0
149.0
150.0
147.0
751.0
91.2
153.0
150.0
151.0
148.0
829.0
96.6
155.0*
151.0
153.0
149.0
20
25
30
35
40
45
50
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
70
747.0
58.4
91.9
93.5
89.8
90.9
837.0
61.0
93.0
95.1
90.2
91.7
932.0
63.8
94.7
97.1
91.2
92.9
1032.0
66.7
96.7
99.4
92.5
94.4
1137.0
69.5
98.9
102.0
94.0
96.0
1247.0
72.4
101.0
105.0
95.6
97.8
1363.0
75.5
104.0
108.0
97.3
99.6
80
689.0
62.2
102.0
103.0
100.0
101.0
777.0
65.2
102.0
104.0
100.0
102.0
869.0
68.5
104.0
106.0
101.0
103.0
964.0
71.8
106.0
108.0
103.0
104.0
1065.0
75.2
108.0
111.0
104.0
106.0
1170.0
78.7
110.0
113.0
106.0
108.0
1281.0
82.2
113.0
116.0
107.0
110.0
85
661.0
63.9
107.0
108.0
105.0
106.0
747.0
67.3
107.0
109.0
105.0
107.0
837.0
70.8
109.0
111.0
106.0
108.0
930.0
74.4
110.0
113.0
108.0
109.0
1029.0
78.1
112.0
115.0
109.0
111.0
1132.0
81.8
115.0
118.0
111.0
113.0
1240.0
85.6
117.0
120.0
112.0
115.0
90
633.0
65.6
112.0
113.0
110.0
111.0
718.0
69.2
112.0
114.0
111.0
112.0
805.0
72.9
113.0
115.0
111.0
113.0
896.0
76.8
115.0
117.0
112.0
114.0
993.0
80.7
117.0
120.0
114.0
116.0
1094.0
84.7
119.0
122.0
116.0
118.0
1199.0
88.8
122.0
125.0
117.0
120.0
LEGEND
CMP
Compressor Power (kW)
SCT(A) Saturated Condensing Temperature (F) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SCT(B) Saturated Condensing Temperature (F) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SDT(A) Saturated Discharge Temperature (F) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SDT(B) Saturated Discharge Temperature (F) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SST
Saturated Suction Temperature Entering Condensing Unit
TCG
Gross Cooling Capacity (1000 Btuh)
110
523.0
70.5
131.0
133.0
131.0
132.0
599.0
75.2
132.0
133.0
131.0
132.0
680.0
80.0
132.0
134.0
131.0
133.0
763.0
84.9
133.0
136.0
132.0
134.0
851.0
89.9
135.0
137.0
133.0
135.0
942.0
94.9
137.0
140.0
135.0
137.0
1037.0
100.1
139.0
142.0
137.0
139.0
115
495.0
71.3
136.0
138.0
136.0
137.0
571.0
76.4
137.0
138.0
136.0
137.0
649.0
81.4
137.0
139.0
136.0
138.0
731.0
86.6
138.0
140.0
137.0
139.0
816.0
91.8
140.0
142.0
138.0
140.0
905.0
97.1
141.0
144.0
140.0
142.0
998.0
102.6
144.0
146.0
141.0
144.0
120
469.0
71.9
141.0
142.0
141.0
142.0
541.0
77.4
141.0
143.0
141.0
142.0
619.0
82.7
142.0
144.0
141.0
143.0
698.0
88.1
143.0
145.0
142.0
144.0
781.0
93.6
144.0
147.0
143.0
145.0
868.0
99.2
146.0
149.0
144.0
147.0
958.0
104.9
148.0
151.0
146.0
148.0
125
443.0
72.4
146.0
147.0
146.0
147.0
513.0
78.1
146.0
148.0
146.0
147.0
588.0
83.8
147.0
148.0
146.0
148.0
665.0
89.5
148.0
150.0
147.0
148.0
747.0
95.3
149.0
151.0
148.0
150.0
831.0
101.2
150.0
153.0
149.0
151.0
919.0
107.1
152.0
155.0*
151.0
153.0
75
25
30
35
40
45
50
TCG
CMP
SDT(A)
SCT(A)
TCG
CMP
SDT(A)
SCT(A)
TCG
CMP
SDT(A)
SCT(A)
TCG
CMP
SDT(A)
SCT(A)
TCG
CMP
SDT(A)
SCT(A)
TCG
CMP
SDT(A)
SCT(A)
TCG
CMP
SDT(A)
SCT(A)
OR (B)
OR (B)
OR (B)
OR (B)
OR (B)
OR (B)
OR (B)
OR (B)
OR (B)
OR (B)
OR (B)
OR (B)
OR (B)
OR (B)
70
834.0
67.2
93.3
92.4
940.0
69.8
94.0
92.8
1050.0
72.4
95.0
93.5
1168.0
75.0
96.4
94.6
1290.0
77.6
98.1
95.9
1418.0
80.0
100.0
97.5
1552.0
82.6
102.0
99.3
80
772.0
71.4
103.0
103.0
872.0
74.6
104.0
103.0
980.0
78.0
105.0
103.0
1092.0
81.2
106.0
104.0
1208.0
84.4
108.0
106.0
1332.0
87.8
109.0
107.0
1460.0
91.0
112.0
109.0
85
740.0
73.4
108.0
108.0
840.0
77.0
109.0
108.0
944.0
80.6
110.0
108.0
1052.0
84.2
111.0
109.0
1168.0
87.8
112.0
111.0
1288.0
91.6
114.0
112.0
1414.0
95.2
116.0
114.0
90
710.0
75.2
113.0
113.0
806.0
79.2
114.0
113.0
908.0
83.2
114.0
113.0
1014.0
87.0
116.0
114.0
1126.0
91.0
117.0
116.0
1244.0
95.0
119.0
117.0
1368.0
99.0
121.0
119.0
Air Temperature
95
678.0
76.8
118.0
118.0
772.0
81.0
119.0
118.0
872.0
85.4
119.0
118.0
978.0
89.6
120.0
119.0
1086.0
94.0
122.0
120.0
1202.0
98.2
123.0
122.0
1322.0
102.6
125.0
123.0
LEGEND
CMP
Compressor Power (kW)
SCT(A) Saturated Condensing Temperature (F) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SCT(B) Saturated Condensing Temperature (F) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SDT(A) Saturated Discharge Temperature (F) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SDT(B) Saturated Discharge Temperature (F) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SST
Saturated Suction Temperature Entering Condensing Unit
TCG
Gross Cooling Capacity (1000 Btuh)
76
115
558.0
81.0
138.0
138.0
642.0
86.8
138.0
138.0
732.0
92.6
139.0
138.0
828.0
98.4
140.0
139.0
926.0
104.0
141.0
140.0
1032.0
109.8
142.0
141.0
1140.0
115.6
144.0
143.0
120
528.0
81.6
143.0
143.0
610.0
87.8
143.0
143.0
698.0
94.0
144.0
143.0
790.0
100.0
144.0
144.0
888.0
106.0
146.0
145.0
988.0
112.2
147.0
146.0
1096.0
118.2
149.0
147.0
125
498.0
82.0
148.0
148.0
578.0
88.6
148.0
148.0
662.0
95.0
149.0
148.0
752.0
101.4
149.0
149.0
848.0
108.0
150.0
150.0
946.0
114.4
152.0
151.0
1050.0
120.8
153.0
152.0
20
25
30
35
40
45
50
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TCG
CMP
SDT(A)
SDT(B)
SCT(A)
SCT(B)
70
930.0
76.0
93.3
92.0
92.4
87.6
1045.0
79.0
94.0
92.7
92.8
88.6
1164.0
82.0
95.0
93.8
93.5
90.0
1290.0
85.1
96.4
95.4
94.6
91.5
1422.0
88.2
98.1
97.2
95.9
93.0
1561.0
91.2
100.0
99.2
97.5
94.6
1707.0
94.2
102.0
101.0
99.3
96.3
80
864.0
80.6
103.0
102.0
103.0
97.7
974.0
84.3
104.0
102.0
103.0
98.5
1090.0
88.1
105.0
103.0
103.0
99.7
1211.0
91.9
106.0
105.0
104.0
101.0
1337.0
95.7
108.0
107.0
106.0
103.0
1470.0
99.6
109.0
109.0
107.0
104.0
1610.0
103.4
112.0
111.0
109.0
106.0
85
831.0
82.8
108.0
107.0
108.0
103.0
940.0
86.8
109.0
107.0
108.0
103.0
1052.0
90.9
110.0
108.0
108.0
105.0
1170.0
95.1
111.0
110.0
109.0
106.0
1294.0
99.3
112.0
111.0
111.0
107.0
1425.0
103.6
114.0
113.0
112.0
109.0
1562.0
107.8
116.0
115.0
114.0
111.0
90
799.0
84.7
113.0
112.0
113.0
108.0
905.0
89.1
114.0
112.0
113.0
108.0
1015.0
93.6
114.0
113.0
113.0
109.0
1130.0
98.1
116.0
114.0
114.0
111.0
1252.0
102.7
117.0
116.0
116.0
112.0
1379.0
107.3
119.0
118.0
117.0
114.0
1513.0
111.9
121.0
120.0
119.0
116.0
Air Temperature
95
766.0
86.4
118.0
117.0
118.0
113.0
869.0
91.2
119.0
117.0
118.0
113.0
978.0
96.1
119.0
118.0
118.0
114.0
1092.0
100.9
120.0
119.0
119.0
116.0
1210.0
105.9
122.0
121.0
120.0
117.0
1335.0
110.8
123.0
122.0
122.0
119.0
1465.0
115.9
125.0
124.0
123.0
120.0
LEGEND
CMP
Compressor Power (kW)
SCT(A) Saturated Condensing Temperature (F) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SCT(B) Saturated Condensing Temperature (F) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SDT(A) Saturated Discharge Temperature (F) for Circuit A (38AH094,104),
or Module 38AH124A or 134A
SDT(B) Saturated Discharge Temperature (F) for Circuit B (38AH094,104),
or Module 38AH124B or 134B
SST
Saturated Suction Temperature Entering Condensing Unit
TCG
Gross Cooling Capacity (1000 Btuh)
115
638.0
91.3
138.0
137.0
138.0
133.0
731.0
97.7
138.0
137.0
138.0
133.0
830.0
104.0
139.0
137.0
138.0
134.0
934.0
110.4
140.0
138.0
139.0
135.0
1042.0
116.7
141.0
139.0
140.0
136.0
1156.0
123.2
142.0
141.0
141.0
137.0
1274.0
129.8
144.0
143.0
143.0
139.0
120
606.0
92.1
143.0
142.0
143.0
138.0
697.0
98.8
143.0
142.0
143.0
138.0
794.0
105.6
144.0
142.0
143.0
139.0
895.0
112.2
144.0
143.0
144.0
139.0
1001.0
119.0
146.0
144.0
145.0
141.0
1111.0
125.8
147.0
145.0
145.0
142.0
1227.0
132.7
149.0
147.0
147.0
144.0
125
575.0
92.6
148.0
147.0
148.0
143.0
663.0
99.8
148.0
147.0
148.0
143.0
756.0
106.8
149.0
147.0
148.0
144.0
855.0
113.9
149.0
148.0
149.0
144.0
959.0
121.1
150.0
149.0
150.0
145.0
1066.0
128.3
152.0
150.0
150.0
147.0
1179.0
135.5
153.0
152.0
152.0
148.0
77
25
30
35
40
45
50
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
90
122.0
12.8
109.0
140.0
13.4
110.0
159.0
14.1
111.0
178.0
14.7
112.0
199.0
15.4
113.0
220.0
16.0
115.0
243.0
16.6
117.0
Air Temperature
95
116.0
13.0
114.0
133.0
13.8
114.0
152.0
144.5
115.0
171.0
15.2
117.0
191.0
15.9
118.0
212.0
16.6
120.0
234.0
17.3
122.0
70
147.0
11.3
89.4
166.0
11.7
90.3
186.0
12.1
91.6
207.0
12.5
93.2
229.0
12.9
95.0
252.0
13.3
96.9
276.0
13.7
99.0
80
135.0
12.1
99.1
153.0
12.6
99.9
172.0
13.1
101.0
193.0
13.7
103.0
214.0
14.2
104.0
236.0
14.7
106.0
259.0
15.2
108.0
85
128.0
12.4
104.0
147.0
13.0
105.0
166.1
13.6
106.0
185.0
14.2
107.0
206.0
14.8
109.0
228.0
15.3
111.0
251.0
15.9
113.0
70
146.0
11.8
95.1
166.0
12.2
95.1
188.0
12.5
95.3
210.0
12.8
95.7
234.0
13.1
96.4
258.0
13.4
97.7
284.0
13.7
99.3
80
133.0
12.5
105.0
153.0
13.1
105.0
174.0
13.6
105.0
195.0
14.0
105.0
219.0
14.4
106.0
242.0
14.8
107.0
267.0
15.2
109.0
85
127.0
12.8
110.0
146.0
13.5
110.0
166.0
14.0
110.0
188.0
14.6
110.0
211.0
15.0
111.0
234.0
15.5
112.0
259.0
16.0
113.0
90
121.0
13.1
115.0
139.0
13.8
115.0
159.0
14.5
115.0
180.0
15.1
115.0
203.0
15.6
116.0
226.0
16.2
117.0
250.0
16.7
118.0
70
197.0
15.7
93.5
222.0
16.3
94.2
249.0
17.0
95.4
278.0
17.6
96.9
308.0
18.3
98.8
339.0
19.0
101.0
372.0
19.6
103.0
80
181.0
16.7
103.0
205.0
17.5
104.0
231.0
18.3
105.0
258.0
19.1
106.0
287.0
19.9
108.0
316.0
20.8
110.0
348.0
21.6
112.0
85
174.0
17.2
108.0
197.0
18.1
109.0
222.0
18.9
110.0
249.0
19.8
111.0
276.0
20.7
113.0
305.0
21.6
115.0
336.0
22.5
117.0
90
166.0
17.6
113.0
189.0
18.6
114.0
213.0
19.5
115.0
239.0
20.5
116.0
266.0
21.5
117.0
294.0
22.4
119.0
324.0
23.4
121.0
Air Temperature
95
159.0
18.0
118.0
181.0
19.1
119.0
205.0
20.1
119.0
230.0
21.1
121.0
256.0
22.2
122.0
284.0
23.2
124.0
313.0
24.3
126.0
115
88.9
13.6
134.0
106.0
14.7
134.0
123.0
15.7
135.0
141.0
16.7
135.0
160.0
17.7
137.0
179.0
18.7
138.0
199.0
19.6
140.0
120
82.2
13.5
139.0
98.6
14.8
139.0
116.0
15.9
139.0
133.0
17.0
140.0
152.0
18.1
141.0
171.0
19.1
143.0
191.0
20.1
145.0
125
75.5
13.4
144.0
91.5
14.8
144.0
108.0
16.0
144.0
126.0
17.2
145.0
144.0
18.4
146.0
162.0
19.5
147.0
182.0
20.6
149.0
120
80.9
13.4
145.0
97.2
14.8
145.0
115.0
16.0
145.0
133.0
17.2
145.0
153.0
18.3
145.0
174.0
19.4
146.0
196.0*
20.4*
146.0*
125
74.2*
13.2*
150.0*
90.1*
14.7*
150.0*
107.0*
16.1*
150.0*
125.0*
17.4*
150.0*
145.0*
18.6*
150.0*
166.0*
19.7*
151.0*
187.0*
20.8*
151.0*
120
124.0
19.5
143.0
143.0
20.9
143.0
163.0
22.3
144.0
185.0
23.7
145.0
208.0
25.1
146.0
232.0
26.6
147.0
257.0
28.0
149.0
125
117.0
19.7
148.0
135.0
21.2
148.0
155.0
22.6
149.0
176.0
24.1
150.0
198.0*
25.6*
151.0*
221.0*
27.1*
152.0*
246.0*
28.6*
154.0*
38AH054 CIRCUIT A
SST
(F)
20
25
30
35
40
45
50
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
115
87.6
13.5
140.0
104.0
14.8
140.0
122.0
15.9
140.0
141.0
17.0
140.0
162.0
18.0
140.0
183.0
18.9
141.0
206.0
19.8
142.0
38AH064 CIRCUIT A
SST
(F)
20
25
30
35
40
45
50
CMP
SDT
SST
TCG
78
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
LEGEND
Compressor Power, kW
Saturated Discharge Temperature (leaving compressor) (F)
Saturated Suction Temperature (entering condensing unit)
Total Cooling Capacity, Gross (1000 Btuh)
115
130.0
19.3
138.0
150.0
20.6
138.0
171.0
21.9
139.0
193.0
23.3
140.0
217.0
24.6
141.0
242.0
26.0
143.0
268.0
27.3
144.0
25
30
35
40
45
50
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
90
120.0
13.0
113.0
139.0
13.7
113.0
158.0
14.3
113.0
179.0
14.9
114.0
201.0
15.5
114.0
224.0
16.0
115.0
248.0
16.5
117.0
Air Temperature
95
114.0
13.2
118.0
132.0
14.0
118.0
151.0
14.7
118.0
171.0
15.4
119.0
193.0
16.0
119.0
215.0
16.6
120.0
239.0
17.2
121.0
70
146.0
11.6
92.6
166.0
12.0
92.9
187.0
12.3
93.2
209.0
12.6
93.9
233.0
12.9
94.7
257.0
13.1
95.8
284.0
13.3
97.0
80
133.0
12.3
103.0
152.0
12.9
103.0
173.0
13.4
103.0
194.0
13.8
104.0
217.0
14.2
105.0
241.0
14.6
106.0
266.0
15.0
107.0
85
127.0
12.7
108.0
145.0
13.3
108.0
165.0
13.9
108.0
187.0
14.4
109.0
209.0
14.9
110.0
232.0
15.3
111.0
257.0
15.8
112.0
70
195.0
16.0
96.0
221.0
16.7
96.8
247.0
17.4
98.1
275.0
18.1
99.7
304.0
18.8
102.0
335.0
19.5
104.0
368.0
20.3
106.0
80
180.0
17.0
106.0
204.0
17.8
106.0
229.0
18.7
108.0
256.0
19.5
109.0
284.0
20.4
111.0
313.0
21.3
113.0
344.0
22.2
115.0
85
172.0
17.4
111.0
196.0
18.3
111.0
220.0
19.3
112.0
246.0
20.2
114.0
274.0
21.1
115.0
303.0
22.1
117.0
333.0
23.1
120.0
90
165.0
17.8
116.0
188.0
18.8
116.0
212.0
19.8
117.0
237.0
20.8
119.0
264.0
21.9
120.0
292.0
22.9
122.0
321.0
23.9
124.0
70
218.0
17.9
93.2
246.0
18.6
93.7
274.0
19.2
94.5
304.0
19.8
95.7
336.0
20.4
97.1
369.0
21.0
98.9
404.0
21.6
101.0
80
202.0
19.0
103.0
229.0
19.9
104.0
256.0
20.7
104.0
286.0
21.5
105.0
316.0
22.3
107.0
348.0
23.1
108.0
381.0
23.9
110.0
85
194.0
19.5
108.0
220.0
20.5
109.0
247.0
21.4
109.0
276.0
22.3
110.0
306.0
23.2
112.0
337.0
24.1
113.0
370.0
25.0
115.0
90
186.0
19.9
113.0
212.0
21.0
113.0
238.0
22.0
114.0
266.0
23.0
115.0
296.0
24.0
116.0
326.0
25.0
118.0
358.0
26.0
120.0
Air Temperature
95
178.0
20.3
118.0
203.0
21.5
118.0
229.0
22.6
119.0
257.0
23.7
120.0
286.0
24.8
121.0
316.0
25.9
123.0
347.0
27.0
124.0
115
87.0
13.5
137.0
104.0
14.7
138.0
121.0
15.9
138.0
140.0
16.9
138.0
160.0
17.9
139.0
180.0
18.8
140.0
202.0
19.7
141.0
120
80.4
13.5
142.0
96.5
14.8
143.0
114.0
16.0
143.0
132.0
17.1
143.0
151.0
18.2
144.0
172.0
19.3
145.0
193.0
20.3
146.0
125
73.6
13.3
147.0
89.3
14.7
148.0
106.0
16.1
148.0
124.0
17.3
148.0
143.0
18.5
149.0
163.0
19.7
150.0
184.0
20.7
150.0
120
124.0
19.6
146.0
142.0
21.1
146.0
162.0
22.5
146.0
183.0
23.9
147.0
206.0
25.4
148.0
229.0
26.9
150.0
254.0*
28.4*
152.0*
125
117.0*
19.8*
151.0*
135.0*
21.3*
151.0*
154.0*
22.8*
151.0*
175.0*
24.3*
152.0*
196.0*
25.9*
153.0*
219.0*
27.4*
155.0*
244.0*
29.0*
156.0*
120
137.0
21.3
143.0
159.0
23.0
143.0
183.0
24.7
144.0
208.0
26.3
144.0
234.0
27.9
145.0
261.0
29.5
146.0
289.0
31.1
148.0
125
129.0
21.3
148.0
150.0
23.1
148.0
173.0
24.9
149.0
198.0
26.6
149.0
223.0*
28.4*
150.0*
250.0*
30.0*
151.0*
277.0*
31.7*
153.0*
38AH054 CIRCUIT B
SST
(F)
20
25
30
35
40
45
50
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
115
130.0
19.4
141.0
149.0
20.8
141.0
170.0
22.1
142.0
192.0
23.5
142.0
215.0
24.9
144.0
240.0
26.3
145.0
265.0
27.7
147.0
38AH064 CIRCUIT B
SST
(F)
20
25
30
35
40
45
50
CMP
SDT
SST
TCG
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
LEGEND
Compressor Power, kW
Saturated Discharge Temperature (leaving compressor) (F)
Saturated Suction Temperature (entering condensing unit)
Total Cooling Capacity, Gross (1000 Btuh)
115
145.0
21.2
138.0
168.0
22.8
138.0
192.0
24.4
139.0
217.0
25.9
139.0
244.0
27.4
140.0
272.0
28.9
142.0
301.0
30.4
143.0
79
25
30
35
40
45
50
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
70
221.0
17.8
92.4
249.0
18.4
92.7
277.0
19.0
93.6
307.0
19.7
95.0
338.0
20.3
96.7
370.0
20.9
98.6
405.0
21.5
101.0
80
205.0
18.9
102.0
232.0
19.7
103.0
260.0
20.5
103.0
288.0
21.3
104.0
318.0
22.2
106.0
350.0
23.0
108.0
383.0
23.7
110.0
85
197.0
19.4
107.0
224.0
20.3
107.0
251.0
21.2
108.0
279.0
22.1
109.0
309.0
23.0
111.0
340.0
23.9
112.0
372.0
24.8
114.0
90
189.0
19.9
112.0
215.0
20.9
112.0
242.0
21.9
113.0
270.0
22.8
114.0
299.0
23.8
115.0
329.0
24.8
117.0
361.0
25.8
119.0
Air Temperature
95
181.0
20.3
117.0
206.0
21.4
117.0
233.0
22.5
118.0
261.0
23.5
119.0
289.0
24.6
120.0
319.0
25.7
122.0
350.0
26.8
124.0
70
286.0
25.5
98.1
321.0
26.6
98.1
360.0
27.6
98.3
400.0
28.6
98.9
443.0
29.6
99.9
488.0
30.7
101.0
534.0
31.8
103.0
80
267.0
26.8
108.0
301.0
28.1
108.0
337.0
29.4
108.0
376.0
30.6
109.0
417.0
31.9
110.0
460.0
33.2
111.0
505.0
34.5
113.0
85
258.0
27.4
113.0
291.0
28.8
113.0
326.0
30.2
113.0
364.0
31.6
114.0
404.0
32.9
114.0
446.0
34.3
116.0
490.0
35.8
117.0
90
249.0
27.9
118.0
281.0
29.5
118.0
315.0
31.0
118.0
352.0
32.5
119.0
392.0
33.9
119.0
433.0
35.5
120.0
475.0
37.0
122.0
115
149.0
21.2
137.0
172.0
22.8
137.0
196.0
24.3
137.0
222.0
25.8
138.0
249.0
27.2
139.0
277.0
28.7
140.0
305.0
30.2
142.0
120
140.0
21.3
142.0
163.0
23.0
142.0
187.0
24.6
142.0
212.0
26.2
143.0
239.0
27.7
143.0
266.0
29.3
145.0
294.0
30.9
146.0
125
132.0
21.3
147.0
154.0
23.1
147.0
178.0
24.8
147.0
203.0
26.5
148.0
228.0
28.2
148.0
255.0*
29.9*
149.0*
282.0*
31.5*
151.0*
120
197.0
30.4
148.0
223.0
32.5
148.0
252.0
34.6
148.0
283.0
36.7
148.0
316.0
38.9
149.0
352.0
41.0
150.0
389.0*
43.2*
151.0*
125
188.0*
30.6*
153.0*
214.0*
32.8*
153.0*
242.0*
35.0*
153.0*
272.0*
37.3*
153.0*
304.0*
39.5*
154.0*
339.0*
41.8*
155.0*
375.0*
44.1*
155.0*
38AH084 CIRCUIT A
SST
(F)
20
25
30
35
40
45
50
CMP
SDT
SST
TCG
80
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
LEGEND
Compressor Power, kW
Saturated Discharge Temperature (leaving compressor) (F)
Saturated Suction Temperature (entering condensing unit)
Total Cooling Capacity, Gross (1000 Btuh)
115
205.0
30.0
143.0
233.0
32.1
143.0
262.0
34.1
143.0
294.0
36.1
144.0
329.0
38.2
144.0
365.0
40.2
145.0
403.0
42.3
146.0
25
30
35
40
45
50
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
70
292.0
24.6
91.7
325.0
25.7
92.7
361.0
26.8
94.2
399.0
28.0
96.0
438.0
29.2
97.9
480.0
30.3
100.0
525.0
31.5
102.0
80
273.0
26.0
102.0
306.0
27.3
102.0
340.0
28.6
104.0
376.0
30.0
105.0
413.0
31.4
107.0
453.0
32.8
109.0
496.0
34.2
111.0
85
264.0
26.6
107.0
296.0
28.0
107.0
329.0
29.4
108.0
364.0
30.9
110.0
401.0
32.4
112.0
440.0
33.9
114.0
481.0
35.5
116.0
90
255.0
27.2
112.0
286.0
28.7
112.0
319.0
30.2
113.0
353.0
31.8
115.0
389.0
33.4
117.0
427.0
35.0
119.0
467.0
36.7
121.0
Air Temperature
95
246.0
27.8
117.0
276.0
29.3
117.0
308.0
30.9
118.0
342.0
32.6
119.0
377.0
34.3
121.0
414.0
36.1
123.0
453.0
37.8
125.0
115
211.0
29.6
136.0
238.0
31.5
137.0
267.0
33.5
137.0
298.0
35.5
138.0
329.0
37.6
140.0
363.0
39.7
142.0
398.0
41.9
144.0
120
202.0
29.9
142.0
229.0
31.9
142.0
257.0
34.0
142.0
287.0
36.1
143.0
318.0
38.3
145.0
350.0
40.5
146.0
384.0
42.8
148.0
125
194.0
30.3
147.0
219.0
32.3
147.0
247.0
34.5
147.0
276.0
36.7
148.0
306.0
38.9
149.0
338.0*
41.2*
151.0*
371.0*
43.6*
153.0*
70
288.0
25.2
96.1
323.0
26.3
96.2
361.0
27.3
96.5
402.0
28.3
97.3
444.0
29.3
98.5
488.0
30.4
100.0
533.0
31.5
102.0
80
269.0
26.5
106.0
303.0
27.8
106.0
339.0
29.1
106.0
378.0
30.3
107.0
418.0
31.6
108.0
460.0
32.9
110.0
504.0
34.2
111.0
85
260.0
27.1
111.0
293.0
28.5
111.0
328.0
29.9
111.0
366.0
31.3
112.0
405.0
32.6
113.0
447.0
34.0
114.0
490.0
35.5
116.0
90
251.0
27.7
116.0
283.0
29.2
116.0
317.0
30.7
116.0
354.0
32.2
117.0
393.0
33.6
118.0
433.0
35.1
119.0
475.0
36.7
121.0
Air Temperature
95
242.0
28.2
121.0
273.0
29.8
121.0
306.0
31.4
121.0
342.0
33.0
122.0
380.0
34.6
123.0
420.0
36.2
124.0
461.0
37.9
125.0
115
207.0
29.9
141.0
234.0
31.9
141.0
264.0
33.9
141.0
296.0
35.9
142.0
330.0
37.9
142.0
366.0
40.0
143.0
404.0
42.1
144.0
120
198.0
30.2
146.0
225.0
32.3
146.0
254.0
34.4
146.0
285.0
36.5
146.0
318.0
38.6
147.0
353.0
40.8
148.0
390.0
43.0
149.0
125
190.0*
30.5*
151.0*
216.0*
32.7*
151.0*
244.0*
34.9*
151.0*
274.0*
37.1*
151.0*
306.0*
39.3*
152.0*
340.0*
41.5*
153.0*
375.0*
43.8*
154.0*
38AH084 CIRCUIT B
SST
(F)
20
25
30
35
40
45
50
CMP
SDT
SST
TCG
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
TCG
CMP
SDT
LEGEND
Compressor Power, kW
Saturated Discharge Temperature (leaving compressor) (F)
Saturated Suction Temperature (entering condensing unit)
Total Cooling Capacity, Gross (1000 Btuh)
81
25
30
35
40
45
50
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
70
366.0
29.7
93.9
91.7
411.0
30.9
95.0
92.1
457.0
32.2
96.7
93.0
505.0
33.6
98.7
94.3
556.0
35.0
101.0
95.7
608.0
36.4
104.0
97.4
663.0
37.8
106.0
99.1
80
338.0
31.4
104.0
102.0
382.0
33.0
105.0
102.0
427.0
34.5
106.0
103.0
474.0
36.1
108.0
104.0
522.0
37.8
110.0
106.0
573.0
39.4
112.0
108.0
626.0
41.1
115.0
109.0
85
324.0
32.3
109.0
107.0
367.0
34.0
109.0
108.0
412.0
35.7
111.0
108.0
458.0
37.4
112.0
109.0
506.0
39.2
115.0
111.0
556.0
41.0
117.0
113.0
608.0
42.8
119.0
114.0
90
310.0
33.0
114.0
113.0
352.0
34.8
114.0
113.0
396.0
36.7
115.0
113.0
442.0
38.6
117.0
114.0
489.0
40.5
119.0
116.0
538.0
42.4
121.0
118.0
589.0
44.4
124.0
119.0
Air Temperature
95
295.0
33.6
119.0
118.0
337.0
35.6
119.0
118.0
381.0
37.6
120.0
118.0
426.0
39.6
122.0
119.0
472.0
41.7
124.0
121.0
520.0
43.8
126.0
123.0
570.0
45.9
128.0
124.0
70
349.0
27.0
91.9
89.8
392.0
28.1
93.0
90.2
437.0
29.3
94.7
91.2
484.0
30.6
96.7
92.5
534.0
38.1
98.9
94.0
586.0
33.0
101.0
95.6
640.0
34.3
104.0
97.3
80
321.0
28.8
102.0
100.0
363.0
30.1
102.0
100.0
407.0
31.6
104.0
101.0
452.0
33.0
106.0
103.0
500.0
34.5
108.0
104.0
550.0
36.0
110.0
106.0
602.0
37.5
113.0
107.0
85
308.0
29.6
107.0
105.0
349.0
31.1
107.0
105.0
392.0
32.7
109.0
106.0
436.0
34.3
110.0
108.0
483.0
35.9
112.0
109.0
532.0
37.5
115.0
111.0
583.0
39.2
117.0
112.0
90
294.0
30.4
112.0
110.0
335.0
32.0
112.0
111.0
377.0
33.7
113.0
111.0
420.0
35.4
115.0
112.0
466.0
37.1
117.0
114.0
514.0
38.9
119.0
116.0
564.0
40.7
122.0
117.0
Air Temperature
95
280.0
31.0
116.0
116.0
320.0
32.8
117.0
116.0
361.0
34.6
118.0
116.0
404.0
36.4
119.0
117.0
449.0
38.3
121.0
119.0
495.0
40.2
124.0
120.0
544.0
42.1
126.0
122.0
115
236.0
34.8
139.0
138.0
276.0
37.6
139.0
138.0
317.0
40.3
139.0
138.0
359.0
43.0
140.0
139.0
402.0
45.7
142.0
140.0
447.0
48.4
144.0
142.0
493.0
51.1
146.0
143.0
120
221.0
34.7
144.0
143.0
260.0
37.8
144.0
143.0
300.0
40.7
144.0
143.0
342.0
43.6
145.0
144.0
384.0
46.4
146.0
145.0
428.0
49.3
148.0
146.0
473.0
52.2
150.0
148.0
125
207.0
34.5
149.0
148.0
244.0
37.8
149.0
148.0
284.0
41.0
149.0
148.0
325.0
44.1
150.0
149.0
367.0
47.1
151.0
150.0
410.0
50.1
153.0
151.0
454.0
53.2
155.0*
153.0
38AH104 CIRCUIT A
SST
(F)
20
25
30
35
40
45
50
CMP
SCT
SDT
SST
TCG
82
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
LEGEND
Compressor Power, kW
Saturated Condensing Temperature (F)
Saturated Discharge Temperature (leaving compressor) (F)
Saturated Suction Temperature (entering condensing unit)
Total Cooling Capacity, Gross (1000 Btuh)
115
226.0
32.8
136.0
136.0
263.0
35.2
137.0
136.0
301.0
37.6
137.0
136.0
340.0
40.0
138.0
137.0
381.0
42.4
140.0
138.0
424.0
44.8
141.0
140.0
468.0
47.3
144.0
141.0
120
213.0
32.9
141.0
141.0
248.0
35.6
141.0
141.0
286.0
38.1
142.0
141.0
324.0
40.7
143.0
142.0
364.0
43.2
144.0
143.0
406.0
45.8
146.0
144.0
449.0
48.4
148.0
146.0
125
200.0
33.0
146.0
146.0
234.0
35.8
146.0
146.0
271.0
38.6
147.0
146.0
308.0
41.3
148.0
147.0
348.0
44.0
149.0
148.0
388.0
46.7
150.0
149.0
431.0
49.4
152.0
151.0
25
30
35
40
45
50
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
70
291.0
24.6
92.1
90.4
327.0
25.6
92.4
90.2
364.0
26.6
93.3
90.5
402.0
27.7
94.7
91.2
443.0
28.8
96.5
92.3
485.0
29.9
98.6
93.6
530.0
31.1
101.0
95.1
80
273.0
26.0
102.0
101.0
307.0
27.2
102.0
100.0
342.0
28.4
103.0
101.0
379.0
29.7
104.0
101.0
418.0
31.0
106.0
102.0
458.0
32.4
108.0
104.0
501.0
33.7
110.0
105.0
85
264.0
26.7
107.0
106.0
296.0
28.0
107.0
106.0
331.0
29.3
108.0
106.0
367.0
30.7
109.0
107.0
405.0
32.1
111.0
108.0
445.0
33.6
112.0
109.0
487.0
35.0
114.0
110.0
90
254.0
27.2
112.0
111.0
286.0
28.7
112.0
111.0
320.0
30.1
113.0
111.0
356.0
31.6
114.0
112.0
393.0
33.1
115.0
113.0
432.0
34.7
117.0
114.0
473.0
36.3
119.0
115.0
Air Temperature
95
245.0
27.8
117.0
116.0
277.0
29.3
117.0
116.0
310.0
30.9
118.0
116.0
345.0
32.4
119.0
117.0
381.0
34.1
120.0
118.0
419.0
35.7
122.0
119.0
459.0
37.4
124.0
120.0
70
398.0
31.4
93.5
90.9
445.0
32.9
95.1
91.7
495.0
34.5
97.1
92.9
548.0
36.1
99.4
94.4
603.0
37.7
102.0
96.0
661.0
39.4
105.0
97.8
723.0
41.2
108.0
99.6
80
368.0
33.4
103.0
101.0
414.0
35.1
104.0
102.0
462.0
36.9
106.0
103.0
512.0
38.8
108.0
104.0
565.0
40.7
111.0
106.0
620.0
42.7
113.0
108.0
679.0
44.7
116.0
110.0
85
353.0
34.3
108.0
106.0
398.0
36.2
109.0
107.0
445.0
38.1
111.0
108.0
494.0
40.1
113.0
109.0
546.0
42.2
115.0
111.0
600.0
44.3
118.0
113.0
657.0
46.4
120.0
115.0
90
339.0
35.2
113.0
111.0
383.0
37.2
114.0
112.0
428.0
39.2
115.0
113.0
476.0
41.4
117.0
114.0
527.0
43.6
120.0
116.0
580.0
45.8
122.0
118.0
635.0
48.1
125.0
120.0
Air Temperature
95
324.0
36.0
118.0
116.0
367.0
38.1
119.0
117.0
412.0
40.3
120.0
118.0
459.0
42.5
122.0
119.0
508.0
44.9
124.0
121.0
559.0
47.2
126.0
123.0
614.0
49.6
129.0
125.0
115
210.0
29.6
137.0
136.0
238.0
31.5
137.0
136.0
268.0
33.5
137.0
136.0
299.0
35.4
138.0
137.0
332.0
37.4
139.0
137.0
367.0
39.5
140.0
138.0
403.0
41.6
142.0
140.0
120
202.0
30.0
142.0
142.0
228.0
32.0
142.0
141.0
257.0
34.0
142.0
141.0
288.0
36.0
143.0
142.0
320.0
38.1
144.0
142.0
354.0
40.3
145.0
143.0
389.0
42.5
147.0
145.0
125
193.0
30.3
147.0
147.0
219.0
32.4
147.0
146.0
247.0
34.5
147.0
146.0
277.0
36.6
148.0
147.0
308.0
38.8
149.0
147.0
341.0
41.1
150.0
148.0
375.0
43.4
151.0
149.0
38AH104 CIRCUIT B
SST
(F)
20
25
30
35
40
45
50
CMP
SCT
SDT
SST
TCG
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
LEGEND
Compressor Power, kW
Saturated Condensing Temperature (F)
Saturated Discharge Temperature (leaving compressor) (F)
Saturated Suction Temperature (entering condensing unit)
Total Cooling Capacity, Gross (1000 Btuh)
115
269.0
38.5
138.0
137.0
308.0
41.2
138.0
137.0
348.0
43.8
139.0
138.0
391.0
46.6
140.0
139.0
435.0
49.4
142.0
140.0
481.0
52.3
144.0
142.0
530.0
55.3
146.0
144.0
120
256.0
39.0
142.0
142.0
293.0
41.8
143.0
142.0
333.0
44.6
144.0
143.0
374.0
47.4
145.0
144.0
417.0
50.4
147.0
145.0
462.0
53.4
149.0
147.0
509.0
56.5
151.0
148.0
125
243.0
39.4
147.0
147.0
279.0
42.3
148.0
147.0
317.0
45.2
148.0
148.0
357.0
48.2
150.0
148.0
399.0
51.3
151.0
150.0
443.0
54.5
153.0
151.0
488.0
57.7
155.0*
153.0
83
25
30
35
40
45
50
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
70
417.0
33.6
93.3
92.4
470.0
34.9
94.0
92.8
525.0
36.2
95.0
93.5
584.0
37.5
96.4
94.6
645.0
38.8
98.1
95.9
709.0
40.0
100.0
97.5
776.0
41.3
102.0
99.3
80
386.0
35.7
103.0
103.0
436.0
37.3
104.0
103.0
490.0
39.0
105.0
103.0
546.0
40.6
106.0
104.0
604.0
42.2
108.0
106.0
666.0
43.9
109.0
107.0
730.0
45.5
112.0
109.0
85
370.0
36.7
108.0
108.0
420.0
38.5
109.0
108.0
472.0
40.3
110.0
108.0
526.0
42.1
111.0
109.0
584.0
43.9
112.0
111.0
644.0
45.8
114.0
112.0
707.0
47.6
116.0
114.0
90
355.0
37.6
113.0
113.0
403.0
39.6
114.0
113.0
454.0
41.6
114.0
113.0
507.0
43.5
116.0
114.0
563.0
45.5
117.0
116.0
622.0
47.5
119.0
117.0
684.0
49.5
121.0
119.0
Air Temperature
95
339.0
38.4
118.0
118.0
386.0
40.5
119.0
118.0
436.0
42.7
119.0
118.0
489.0
44.8
120.0
119.0
543.0
47.0
122.0
120.0
601.0
49.1
123.0
122.0
661.0
51.3
125.0
123.0
115
279.0
40.5
138.0
138.0
321.0
43.4
138.0
138.0
366.0
46.3
139.0
138.0
414.0
49.2
140.0
139.0
463.0
52.0
141.0
140.0
516.0
54.9
142.0
141.0
570.0
57.8
144.0
143.0
120
264.0
40.8
143.0
143.0
305.0
43.9
143.0
143.0
349.0
47.0
144.0
143.0
395.0
50.0
144.0
144.0
444.0
53.0
146.0
145.0
494.0
56.1
147.0
146.0
548.0
59.1
149.0
147.0
125
249.0
41.0
148.0
148.0
289.0
44.3
148.0
148.0
331.0
47.5
149.0
148.0
376.0
50.7
149.0
149.0
424.0
54.0
150.0
150.0
473.0
57.2
152.0
151.0
525.0
60.4
153.0
152.0
80
478.0
44.9
102.0
97.7
538.0
47.0
102.0
98.5
600.0
49.1
103.0
99.7
665.0
51.3
105.0
101.0
733.0
53.5
107.0
103.0
804.0
55.7
109.0
104.0
880.0
57.9
111.0
106.0
85
461.0
46.1
107.0
103.0
520.0
48.3
107.0
103.0
580.0
50.6
108.0
105.0
644.0
53.0
110.0
106.0
710.0
55.4
111.0
107.0
781.0
57.8
113.0
109.0
855.0
60.2
115.0
111.0
90
444.0
47.1
112.0
108.0
502.0
49.5
112.0
108.0
561.0
52.0
113.0
109.0
623.0
54.6
114.0
111.0
689.0
57.2
116.0
112.0
757.0
59.8
118.0
114.0
829.0
62.4
120.0
116.0
Air Temperature
95
427.0
48.0
117.0
113.0
483.0
50.7
117.0
113.0
542.0
53.4
118.0
114.0
603.0
56.1
119.0
116.0
667.0
58.9
121.0
117.0
734.0
61.7
122.0
119.0
804.0
64.6
124.0
120.0
115
359.0
50.8
137.0
133.0
410.0
54.3
137.0
133.0
464.0
57.7
137.0
134.0
520.0
61.2
138.0
135.0
579.0
64.7
139.0
136.0
640.0
68.3
141.0
137.0
704.0
72.0
143.0
139.0
120
342.0
51.3
142.0
138.0
392.0
54.9
142.0
138.0
445.0
58.6
142.0
139.0
500.0
62.2
143.0
139.0
557.0
66.0
144.0
141.0
617.0
69.7
145.0
142.0
679.0
73.6
147.0
144.0
125
326.0
51.6
147.0
143.0
374.0
55.5
147.0
143.0
425.0
59.3
147.0
144.0
479.0
63.2
148.0
144.0
535.0
67.1
149.0
145.0
593.0
71.1
150.0
147.0
654.0
75.1
152.0
148.0
25
30
35
40
45
50
CMP
SCT
SDT
SST
TCG
84
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
TCG
CMP
SDT
SCT
70
513.0
42.4
92.0
87.6
575.0
44.1
92.7
88.6
639.0
45.8
93.8
90.0
706.0
47.6
95.4
91.5
777.0
49.4
97.2
93.0
852.0
51.2
99.2
94.6
931.0
52.9
101.0
96.3
LEGEND
Compressor Power, kW
Saturated Condensing Temperature (F)
Saturated Discharge Temperature (leaving compressor) (F)
Saturated Suction Temperature (entering condensing unit)
Total Cooling Capacity, Gross (1000 Btuh)
LEGEND
TXV Thermostatic Expansion Valve
Line Voltage
Piping
Double Riser Piping
(If Required)
*Field supplied.
NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System Design Manual
for details.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not intended for, or to
include all details for, a specific installation. Face-split connection shown; row-split connection also
possible.
4. Liquid line solenoid valve (solenoid drop control) is required to minimize refrigerant migration to the
compressor.
85
LEGEND
TXV Thermostatic Expansion Valve
Line Voltage
Piping
*Field supplied.
NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System Design Manual for details.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not intended for, or to include all
details for, a specific installation. Face-split connection shown; row-split connection also possible.
4. Liquid line solenoid valve (solenoid drop control) is required to minimize refrigerant migration to the compressor.
86
VOLTAGE
DESIGNATION
044
054
064
074
084
COMPRESSOR
MODEL
(A/B DUAL-CIRCUIT)
(A1/A2 SINGLE-CIRCUIT)
800 (PW)
900
300 (PW)
900
300 (PW)
900
300 (PW)
900
300 (PW)
900
300 (PW)
NAMEPLATE
VOLTS-PH-Hz
SUPPLY
VOLTAGE*
06E-250/265
06E-265/275
06E-275/299
06E-299/299
COMPRESSOR
Min
Max
MCA
MOCP
ICF
198
348
325
342
325
342
325
342
325
342
325
254
440
367
440
367
440
367
440
367
440
367
174.6
100.0
100.0
101.1
107.0
114.1
129.8
140.6
170.8
165.2
205.3
225
100
125
125
150
150
175
200
250
225
250
296.7
219.6
165.9
269.6
198.9
335.6
230.5
403.8
300.4
428.4
334.9
230-3-50
380/415-3-50
346-3-50
380/415-3-50
346-3-50
380/415-3-50
346-3-50
380/415-3-50
346-3-50
380/415-3-50
346-3-50
06E-250/250
POWER SUPPLY
A
RLA
67.9
34.6
33.3
34.6
33.3
43.6
44.9
46.8
53.8
65.4
79.5
B
LRA
207
173
115
173
115
223
148
280
168
345
229
RLA
67.9
34.6
33.3
43.6
44.9
46.8
53.8
65.4
79.5
65.4
79.5
LRA
207
173
115
223
148
280
168
345
229
345
229
38AH094,104
SUPPLY
COMPRESSOR NAMEPLATE VOLTAGE*
UNIT
VOLTAGE
A1/A2/B1/B2
38AH DESIGNATION
VOLTS-PH-Hz
MODEL NO.
Min Max
094
104
300 (PW)
900
300 (PW)
900
06E-275/250/
299/
06E-265/250/
265/265
346-3-50
380/415-3-50
346-3-50
380/415-3-50
325
342
325
342
380
440
380
440
POWER SUPPLY
MCA MOCP ICF
212.9
181.2
205.6
194.3
250
225
250
225
343
444
298
363
COMPRESSOR
A1
RLA LRA
53.8 168
46.8 280
44.9 148
43.6 223
A2
RLA LRA
33.3 115
34.6 173
33.3 229
34.6 173
B1
B2
RLA LRA RLA LRA
79.5 229
65.4 345
38AH124,134
UNIT
38AH
MODULE
124A
124B
134A
134B
VOLTAGE
DESIGNATION
300 (PW)
900
300 (PW)
900
COMPRESSOR
A1/A2
MODEL NO.
06E-275/265
06E-299/275
NAMEPLATE
VOLTS-PH-Hz
SUPPLY
VOLTAGE*
POWER SUPPLY**
Min
Max
MCA
MOCP
ICF
346-3-50
325
367
129.8
175
380/415-3-50
346-3-50
380/415-3-50
342
325
342
440
367
440
114.1
170.8
140.6
150
250
200
COMPRESSOR
A1
A2
231
RLA
53.8
LRA
168
RLA
44.9
LRA
148
336
300
404
46.8
79.5
65.4
280
229
345
43.6
53.8
46.8
223
168
280
87
CONTROL CIRCUIT
124A
124B
134A
380/415-3-50
346-3-50
6.4
(1-4) 4.4
(1-4) 3.0
134B
380/415-3-50
346-3-50
9.2
(1-6) 4.4
(1-6) 3.0
38AH
044-134
-800
-300
-900
UNIT POWER
V-Ph-Hz
230-3-50
346-3-50
380/415-3-50
CONTROL POWER
V-Ph-Hz
Min
Max
230-1-50
207
253
200-1-50
180
220
230-1-50
207
253
AMPS
2.0
2.4
2.0
88
VA
(Each Stage)
AMPS
CONTROL
CIRCUIT
VOLTAGE
044-084
094
104
124
134
300
275
325
300
300
1.30
1.15
1.35
1.30
1.30
240
Controls 38AH044-084
Operating sequence
Circuits A1 and B1 are controlled by independent circuitry.
It is therefore possible to maintain partial cooling capability
even if one compressor is inoperable.
NOTE: Single-circuit units do not have independent control circuitry.
On a call for cooling, the first-stage cooling thermostat
TC1 closes, energizing the first stage of the condenser fans
and timer motor TM-A (TM for single-circuit units). After
12 seconds, the timer energizes lead compressor contactor
C-A1 and the lead compressor starts. (Circuit A compressor is the lead on dual-circuit units, and compressor A1 is
the lead on single-circuit units.) At the same time, solenoid
drop relay SDR2 energizes and closes its contacts, which
energizes and opens liquid line solenoid valve LLS-A (LLS-A1
for single-circuit units). Circuit A (compressor A1 for singlecircuit units) is now operational.
A set of bypass contacts in timer TM-A allows the
circuit A compressor (compressor A1 for single-circuit units)
40 seconds to build sufficient oil pressure. If the oil pressure is insufficient after 40 seconds, circuit A (compressor
A1 for single-circuit units) shuts down and must be reset
manually.
A second set of bypass contacts in timer TM-A (TM for
single-circuit units) allows the refrigerant circuit 212 minutes
to build sufficient low-side pressure. This time delay is a
start-up feature for low ambient conditions; no accessory is
required. If refrigerant circuit pressure is insufficient to close
the low-pressure switch after 212 minutes, the circuit A compressor (compressor A1 for single-circuit units) shuts down
for 512 minutes and then automatically attempts to restart.
No manual reset is required.
Dual-circuit units If circuit A is insufficient for the cooling requirements, second-stage thermostat TC2 closes to
bring circuit B on line. Circuit B follows the same sequence
of operation as circuit A, except a relay delays circuit B
compressor start-up for 40 seconds after a call for cooling.
Because circuit A has a 12-second delay after TC1 closes,
and circuit B has a 40-second delay after TC2 closes, the
two compressors cannot start at the same time.
Optional single-circuit units If compressor A1 is insufficient for the cooling requirements, second-stage thermostat TC2 closes, which opens liquid line solenoid valve
LLS-A2. Compressor A2 starts only after the D-D2 contacts in timer TM close (approximately 212 minutes after
compressor A1 is energized) and the suction pressure is sufficient to close capacity control pressure switches CCPS1
and CCPS2.
All units When the fan switch on the thermostat is set
for automatic operation (AUTO), the field-supplied indoorfan contactor (IFC) is cycled with the lead compressor. If the
fan switch is set at the continuous position (CONT), the IFC
is energized as long as the unit power is on.
NOTE: Liquid line solenoid valves must be field-supplied
and installed at the evaporator for both dual- and optional
single-circuit units.
89
Controls 38AH094-134
Operating sequence
Units are controlled with electromechanical components.
Each refrigeration circuit is operated by an independent timer
motor which controls the operation sequence of each circuit. It is possible to maintain partial cooling capability even
if one circuit is inoperable.
On a call for cooling, first stage cooling thermostat TC1
closes. Condenser fans and timer motor (TM) are energized. After approximately 7 seconds, timer contacts E-E1
close. Approximately 12 seconds after TC1 closes, normally open timer contacts B-B1 close for 1 second. This
energizes compressor A1 contacts CA1 and starts the compressor. At the same time, solenoid drop relays (SDRs) and
liquid line solenoid valve no. 1 (LLS-A1) open, and timer
relay no. 1 (TR1) is energized. Normally open TR1 contacts close, completing a circuit around B-B1 and through
compressor A1 contactors to maintain compressor operation when B-B1 contacts open. Contacts E-E1 remain closed
for approximately 40 seconds to bypass the oil pressure
switch. If oil pressure is insufficient when contacts E-E1 open,
the compressor stops, the timer cycles off, and the control
circuit locks out. At start-up, timer motor contacts D-D1 are
closed, bypassing low-pressure relay contacts LPR-A for
212 minutes. This provides a winter start-up feature.
Approximately 212 minutes after TC1 closes, timer contacts D-D1 open and D-D2 close. If pressure is insufficient
to close the low-pressure switch, the low-pressure switch
relay remains open, the compressor shuts down, and the
Time Guardt control is initiated. Time Guard control prevents compressor from restarting for 5 minutes after the
demand for cooling is satisfied.
90
CR
HD
IFC
IFR
kcmil
LLS
R
RV
TB
LEGEND
Control Relay
Heating Device
Indoor Fan Contactor
Indoor-Fan Relay
Thousand Circular Mils
Liquid Line Solenoid
Heating Relay (fieldsupplied 24-v sealed coil,
10 va maximum rating)
Reversing Valve
Terminal Block
Factory Wiring
Field Wiring
91
CR
HD
IFC
IFR
LLS
R
RV
TB
92
LEGEND
Control Relay
Heating Device
Indoor Fan Contactor
Indoor-Fan Relay
Liquid Line Solenoid
Heating Relay (fieldsupplied 24-v sealed coil,
10 va maximum rating)
Reversing Valve
Terminal Block
Factory Wiring
Field Wiring
CR
HD
IFC
IFR
LLS
R
RV
TB
LEGEND
Control Relay
Heating Device
Indoor Fan Contactor
Indoor-Fan Relay
Liquid Line Solenoid
Heating Relay (fieldsupplied 24-v sealed coil,
10 va maximum rating)
Reversing Valve
Terminal Block
Factory Wiring
Field Wiring
93
6. For VAV systems, the total building load is NOT the sum
of the individual peak loads. Equipment selected for the
sum of the individual peak loads will be oversized.
7. For VAV systems with supply- to return-air recycling, use
the equipment room as a return-air plenum.
8. To minimize air recirculation, do not use concentric supply and return grilles.
LIQUID LINE DATA
UNIT
38AH
044
054
064
074
084
094
104
124
134
MAXIMUM
ALLOWABLE
LIQUID LIFT
m
17.5
23.0
19.8
11.4
23.0
14.0
12.8
19.8
11.4
ft
57.5
75.0
65.0
37.5
75.0
46.0
42.0
65.0
37.5
044
054
064
074
084
094
104
124
134
CAPACITY/STAGE (%)
Standard Dual-Circuit Units
Optional Single-Circuit Units
100, 75, 50, 25
100, 75, 50, 25
100, 79, 42, 21
100, 80, 56, 37
100, 84, 48, 32
100, 82, 55, 36
100, 86, 43, 29
100, 81, 57, 38
100, 83, 50, 33
100, 83, 50, 33
100, 85, 55, 44, 33, 22
CAPACITY/STAGE (%)
Standard Dual-Circuit Units
Optional Single-Circuit Units
100, 75, 50, 25
100, 75, 50, 25
100, 79, 58, 42, 21
100, 80, 61, 56, 37
100, 84, 69, 48, 32, 16
100, 82, 64, 55, 36, 18
100, 86, 71, 43, 29, 14
100, 81, 62, 57, 38, 19
100, 83, 67, 50, 33, 17
100, 83, 67, 50, 33, 17
100, 85, 70, 55, 44, 33, 22
100, 91, 82, 77, 68, 50, 41, 32, 27, 18, 9
100, 90, 79, 76, 66, 45, 37, 28, 25, 16, 8
NOTES:
1. Capacities are based on 7.2 C (45 F) saturated suction temperature and 35 C (95 F) outdoor-air
temperature.
2. Single-circuit option available for sizes 044-084 only.
94
48.3
1.1
NOTE: Values shown are for units operating at 7.2 C (45 F) saturated
suction at condensing unit and 35 C (95 F) entering outdoor air.
LIQUID LINE
Max Allowable
Max Allowable
Pressure Drop
Temp Loss
kPa
Psi
C
F
044
054
064
074
084
QUANTITY OF LOADED
COMPRESSOR CYLINDERS
Ckt A
4
2
4
2
4
2
2
4
2
6
4
2
6
4
2
6
4
2
6
4
2
6
4
2
6
4
2
Ckt B
4
4
0
0
6
6
4
0
0
6
6
6
0
0
0
6
6
6
0
0
0
6
6
6
0
0
0
SYSTEM
CAPACITY
(%)
Total
8
6
4
2
10
8
6*
4
2
12
10
8*
6
4
2*
12
10
8*
6
4
2*
12
10
8*
6
4
2*
100
75
50
25
100
79
58*
42
21
100
84
69*
48
32
16*
100
86
71*
43
29
14*
100
83
67*
50
33
17*
10.0
50
28.9
20
8.9
48
28.9
20
3.9
39
28.9
20
0.6
31
28.9
20
6.7
20
28.9
20
044
054
064
074
084
QUANTITY OF LOADED
CYLINDERS
SYSTEM
CAPACITY
(%)
8
6
4
2
10
8
6*
6
4
12
10
8*
6
4
2*
12
10
8*
6
4
2*
12
10
8*
6
4
2*
100
75
50
25
100
80
61*
56
37
100
82
64*
55
36
18*
100
81
62*
57
38
19*
100
83
67*
50
33
17*
47
28.9
20
5.0
41
28.9
20
3.3
38
28.9
20
5.6
22
28.9
20
6.7
20
28.9
20
95
094
104
124
134
Ckt B
Total
SYSTEM
CAPACITY
(%)
10
10
10
10
8
6
4
10
10
10
10
10
10
10
8
6
4
2
12
12
12
12
12
12
12
10
8
6
4
2*
12
12
12
12
12
12
12
10
8
6
4
2*
6
4
2*
0
0
0
0
12
10
8
6
4
2
0
0
0
0
0
12
10
8
6
4
2
0
0
0
0
0
0
12
10
8
6
4
2
0
0
0
0
0
0
16
14
12
10
8
6
4
22
20
18
16
14
12
10
8
6
4
2
24
22
20
18
16
14
12
10
8
6
4
2
24
22
20
18
16
14
12
10
8
6
4
2
100
85
70*
55
44
33
22
100
91
82
74
65
56
47
38
26
17
9
100
91
82*
77
68
59
50
41
32*
27
18
9*
100
90
79*
76
66
56
45
37
28*
25
16
8*
96
13.9
3.9
25
28.9
20
10.0
14
15.0
28.9
20
3.3
38
3.3
38
28.9
20
3.3
38
5.6
22
28.9
20
NOTES:
1. Temperatures calculated with the minimum number of fans operating
per circuit.
2. For 38AH124 and 134 units, circuit A is Module 38AH124A or 134A.
Circuit B is Module 38AH124B or 134B.
3. Minimum outdoor-air operating temperature is based on 32 C (90 F)
saturated condensing temperature and 100% capacity.
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
15-25
(4.6-7.6)
L
S
5 8
138
5 8
138
5 8
138
7 8
158
7 8
158
7 8
158
7 8
158
7 8
218
7 8
218
7 8
218
LEGEND
L Liquid Line
S Suction Line
*Double suction riser required on units with field installed unloader on
circuit B compressor if condensing unit is elevated above
evaporator.
Double suction riser required on units with field installed unloader on
circuit B compressor if condensing unit is elevated above
evaporator.
**Double suction riser required on all unit configurations if condensing
unit is elevated above evaporator.
NOTES:
1. Addition of 2 unloaders to circuit B compressor is not
recommended.
2. 38AH094 and 38AH104 piping sizes apply only to factory supplied
unit configurations. They do NOT take into account any field installed
unloaders.
3. Piping sizes are based on unit operation above 40 F (4.4 C) saturated suction temperature (SST). When operating below 40 F
(4.4 C), refer to Carrier System Design Manual, E20-IIT piping
design program, or ASHRAE Handbook to select proper line sizes.
4. Pipe sizes are based on the total linear length shown for each column, plus a 50% allowance for fittings.
150-200
(45.7-61.0)
L
S
7 8
218
7 8
218
7 8
218
118
258*
118
258**
118
258*
118
258
118
258
118
258
118
258
mm
15.9
22.2
28.6
34.9
41.3
54.0
66.7
79.4
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
138
50-75
(15.2-22.9)
B
158
218
138
158
158
218
LEGEND
Not Required
Pipe A Suction Riser Without Trap
Pipe B Suction Riser With Trap
Pipe C Suction Line to Condensing Unit
NOTES:
1. See Refrigerant Piping Requirements table at top of page to
determine need for double suction risers.
2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings.
3. Suction and liquid line sizing is based on pressure drop equivalent to
2 F (1.1 C) at nominal rating conditions. Higher design pressure drop
criteria may allow selection of smaller pipe sizes but at a penalty of
decreased system capacity and efficiency.
158
218
158
158
218
158
158
218
258
158
158
218
258
158
258
158
218
258
158
150-200
(45.7-61.0)
B
218
218
218
218
218
258
258
258
258
258
mm
15.9
22.2
28.6
34.9
41.3
54.0
66.7
79.4
97
15-20
(4.6-6.1)
L
S
78
218
78
218
044
054
064;
Modules 124A,
124B, 134A
074;
Module 134B
084
150-200
(45.7-61.0)
L
S
138
258*
138
318*
78
218
118
258
118
258
118
78
218
118
258
118
258
138
118
218
118
258
138
318*
138
LEGEND
CV Constant Volume
L
Liquid Line
S
Suction Line
VAV Variable Air Volume
*Double suction riser required on all units configurations if condensing
unit is elevated above evaporator.
Double suction riser required on units with factory installed VAV option
or CV units with additional field installed unloader on circuit A1 (lead)
compressor if condensing unit is elevated above evaporator.
NOTES:
1. Double risers are required if condensing unit is elevated above evaporator. See footnotes and double suction riser table below.
2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings.
3. Suction line sizing is based on 1.1 C (2 F) pressure drop at nominal
rating conditions. Liquid line sizing is based on 1.1 C (2 F) pressure
drop. Higher design pressure drop criteria may allow selection of
smaller pipe sizes but at a penalty of decreased system capacity and
efficiency.
258
138
318*
138
318*
318*
138
318*
138
318*
318*
138
318*
158
358*
4. Suction line sizing is based on using the same diameter tube from
the evaporator riser outlet to the condensing unit.
5. Suction line riser selections are based on using maximum possible
unloaders.
6. Refer to Carrier System Design Manual or to E20-IIT design programs for further information on selecting pipe sizes for split systems.
7. All pipe sizes are OD inches; equivalent sizes in millimeters follow:
in.
58
78
118
138
158
218
258
318
358
mm
15.9
22.2
28.6
34.9
41.3
54.0
66.7
79.4
92.1
Pipe A
Pipe B
Pipe C
15-20
(4.6-6.1)
A
B
C
158
218
258
158
258
258
158
218
258
158
218
258
158
218
258
150-200
(45.7-61.0)
A
B
C
158
258
258
158
258
318
158
218
258
158
218
258
158
218
258
158
258
318
158
258
318
158
218
258
158
218
258
158
258
318
158
258
318
158
318
358
158
218
258
158
258
318
158
258
318
158
258
318
158
318
358
LEGEND
Not Required
Suction Riser Without Trap
Suction Riser With Trap
Suction Line to Condensing Unit
NOTES:
1. See Refrigerant Piping Requirements table at top of page to determine need for double suction risers.
2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings.
3. Suction line sizing is based on 1.1 C (2 F) pressure drop at nominal
rating conditions. Liquid line sizing is based on 1.1 C (2 F) pressure
drop. Higher design pressure drop criteria may allow selection of
smaller pipe sizes but at a penalty of decreased system capacity and
efficiency.
4. Suction line sizing is based on using the same diameter tube from
the evaporator riser outlet to the condensing unit.
98
mm
15.9
22.2
28.6
34.9
41.3
54.0
66.7
79.4
92.1
094
104
15-25
(4.6-7.6)
L
S
78
218
78
218
78
218
78
218
LEGEND
L Liquid Line
S Suction Line
*Double suction riser required on units with field installed unloader on
circuit B compressor if condensing unit is elevated above
evaporator.
Double suction riser required on units with field installed unloader on
circuit B compressor if condensing unit is elevated above
evaporator.
**Double suction riser required on all unit configurations if condensing
unit is elevated above evaporator.
NOTES:
1. Double risers are required if condensing unit is elevated above evaporator. See footnotes and double suction riser table below.
2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings.
3. Suction line sizing is based on 1.1 C (2 F) pressure drop at nominal
rating conditions. Liquid line sizing is based on 1.1 C (2 F) pressure
drop. Higher design pressure drop criteria may allow selection of
smaller pipe sizes but at a penalty of decreased system capacity and
efficiency.
150-200
(45.7-61.0)
L
S
138
318**
118
258*
138
318**
138
318**
4. Suction line sizing is based on using the same diameter tube from
the evaporator riser outlet to the condensing unit.
5. Suction line riser selections are based on using maximum possible
unloaders.
6. Refer to Carrier System Design Manual or to E20-II design programs
for further information on selecting pipe sizes for split systems.
7. All pipe sizes are OD inches; equivalent sizes in millimeters follow:
in.
58
78
118
138
158
218
258
318
358
mm
15.9
22.2
28.6
34.9
41.3
54.0
66.7
79.4
92.1
094
104
Pipe A
Pipe B
Pipe C
A
138
50-75
(15.2-22.9)
B
218
138
218
218
138
LEGEND
Not Required
Suction Riser Without Trap
Suction Riser With Trap
Suction Line to Condensing Unit
NOTES:
1. See Refrigerant Piping Requirements table at top of page to determine need for double suction risers.
2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings.
3. Suction line sizing is based on 1.1 C (2 F) pressure drop at nominal
rating conditions. Liquid line sizing is based on 1.1 C (2 F) pressure
drop. Higher design pressure drop criteria may allow selection of
smaller pipe sizes but at a penalty of decreased system capacity and
efficiency.
4. Suction line sizing is based on using the same diameter tube from
the evaporator riser outlet to the condensing unit.
158
150-200
(45.7-61.0)
B
258
218
258
258
C
318
258
318
318
mm
15.9
22.2
28.6
34.9
41.3
54.0
66.7
79.4
92.1
99
A
B
C
D
RED.
STR
LEGEND
Pipe A, Suction Riser, Lower Trap
Pipe B, Suction Riser with Trap
Suction Line to Condensing Unit
Pipe D, Suction Riser Short Lift
Reducer
Street
NOTE: Short riser, pipe D, is used when routing suction line to condensing unit connection. See table below:
UNIT
38AH
044
054
064
074
084
094
104
124A,B
134A,B
PIPE D DIAMETER*
Dual Circuit
Single Circuit
A
B
5
5
1 8
218
1 8
158
158
218
158
218
218
218
218
218
218
218
258
218
218
218
218
1
1
2 8
2 8
1
1
2 8
2 8
100
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized steel,
bonderized and coated with a prepainted, baked
enamel finish.
2. Unit access panels shall be hinged for control box
service access.
3. Lifting holes shall be provided to facilitate rigging.
C. Fans:
1. Condenser fans shall be direct-drive propeller type,
discharging air vertically upward.
2. Condenser fan motors shall be 3-phase type
with class B insulation and permanently lubricated
bearings. Class F fan motors shall be available as
a factory-installed option.
3. Shafts shall have inherent corrosion resistance.
4. Fan blades shall be statically and dynamically
balanced.
5. Condenser fan openings shall be equipped with
PVC-coated steel wire safety guards.
D. Compressors:
1. Compressors shall be manufactured by the condensing unit manufacturer, and shall be serviceable, reciprocating, semi-hermetic type.
2. Compressors shall be equipped with an automatically reversible oil pump, operating oil charge,
suction and discharge shutoff valves, and an inserttype factory-sized crankcase heater to control oil
dilution.
3. Compressors shall be mounted on spring vibration isolators with an isolation efficiency of no less
than 95%.
4. Compressor speed shall not exceed 24.3 r/s
(1460 rpm).
5. Lead compressor shall unload using suction cutoff
unloading (electrical solenoid unloading shall be
available as an accessory).
E. Condenser Coils:
1. Condenser coils shall be air cooled, circuited for
integral subcooler.
2. Coil shall be constructed of aluminum fins mechanically bonded to internally grooved, seamless
copper tubes which are then cleaned, dehydrated,
and sealed. Copper fins and precoated aluminum
fins shall be available as options.
F. Refrigeration Components:
Refrigeration circuit components shall include hot gas
muffler, high-side pressure relief device, liquid line shutoff valve, suction and discharge shutoff valves, holding charge, and compressor oil.
101
102
I. Electrical Requirements:
1. Nominal unit electrical characteristics shall be
v, 3-ph, 50 Hz. The unit shall be capable
of satisfactory operation within voltage limits of
v to
v.
2. Unit electrical power shall be single point
connection.
3. Unit control circuit shall be 230 v for 380/415 v
and 230 v units, or 200 v for 346 v units.
J. Special Features:
Certain standard features are not applicable when the
features designated * are specified. For assistance in
amending the specifications, your local Carrier Sales
Office should be contacted.
*
1. Unloader Conversion Kit:
Unloader valve, piston, and hardware shall be
supplied to convert any pressure-operated compressor unloader to electrical unloading.
Accessory ModuPanel or field-supplied step controller shall be provided for electrical unloading.
*
2. Gage Panel:
A gage panel package shall be provided which
includes a suction and discharge pressure gage
for each refrigerant circuit.
3. Thermostat Controls:
a. Debonair programmable multi-stage thermostat with 7-day clock, holiday scheduling,
large Thermoglow display, remote sensor
capability, and Title 24 compliance.
b. TEMP System programmable communicating multi-stage thermostat with fan switch,
timeclock, LCD display, F/C capability,
and CCN (Carrier Comfort Network)
compatibility.
c. Commercial Electronic Thermostat with 7-day
timeclock, auto-changeover, multi-stage capability, and large LCD temperature display.
d. Non-programmable thermostat with fan switch
subbase.
4. Electric Unloader Package:
Electric unloader shall provide an additional step
of electric unloading.
5. Pressure Unloader Package:
Pressure unloader shall provide an additional step
of pressure unloading.
6. ModuPanel Control:
Control shall provide 10-step microprocessorbased control for variable air volume
applications.
7. Motormastert III Control:
Control shall maintain correct condensing pressure at low ambient temperatures.
8. VAV (Variable Air Volume) Modification:
Unit shall be supplied from the factory with necessary wiring modifications for connection to a
field-supplied ModuPanel discharge air controller. The VAV modification shall include 2 electric
unloaders on the lead compressor.
9. Optional Condenser Coil Materials:
a. Pre-Coated Aluminum-Fin Coils:
Shall have a durable epoxy-phenolic coating
to provide protection in mildly corrosive coastal
environments. Coating shall be applied to the
aluminum fin stock prior to the fin stamping
process to create an inert barrier between the
aluminum fin and copper tube. Epoxy-phenolic
barrier shall minimize galvanic action between
dissimilar metals.
b. Copper-Fin Coils:
Shall be constructed of copper fins mechanically bonded to copper tubes. All copper
construction shall provide protection in moderate coastal applications.
103
104
A. Base Unit:
1. Cabinet shall be constructed of mill-galvanized steel.
2. Cabinet panels shall be fully insulated with
12.7-mm (12-in.) fire-retardant material. Insulation shall contain a U.S.A. EPA-registered immobilized antimicrobial agent to effectively resist the
growth of bacteria and fungi as proven by tests in
accordance with ASTM standards G21 and 22
(U.S.A.).
3. Unit shall contain PVC condensate drain pans for
both vertical and horizontal applications. Drain
pans shall have connections on right and left sides
of unit to facilitate field connection. Drain pans
shall have the ability to be sloped toward the right
or left side of the unit to prevent standing water
from accumulating in pans.
4. Unit shall have factory-supplied 51-mm (2-in.)
throwaway-type filters installed upstream from the
cooling coil. Filter access shall be from either the
right or left side of the unit.
B. Coils:
Coils shall consist of 3 rows of copper tubes with sinewave aluminum fins bonded to the tubes by mechanical expansion. Coil tubing shall be internally rifled to
maximize heat transfer. Suction and liquid line connections or supply and discharge connections shall be
made on the same side of the coil.
Direct-expansion coils shall feature factory-installed
thermostatic expansion valves (TXVs) for refrigerant
control. The TXVs shall be capable of external
adjustment.
C. Operating Characteristics:
L/s (cfm)
Unit shall be capable of providing
airflow at an external static pressure of
kPag
(in. wg).
D. Motor:
Fan motor of the size and electrical characteristics
specified on the equipment schedule shall be factory
supplied and installed.
E. Factory-Installed Options:
1. Alternate Motor and Drive:
An alternate motor and/or medium- or high-static
drive shall be available to meet the airflow and external static pressure requirements specified on the
equipment schedule.
2. Painted Cabinet:
Where conditions require, units shall be painted
with an American Sterling Gray finish.
F. Field-Installed Accessories:
1. Hot Water Coil:
Coil shall be 2-row, U-bend coil with copper
tubes and aluminum plate fans bonded to the
tubes by mechanical expansion. Coil shall be
mounted in a galvanized steel housing that shall
be fastened to the units fan deck for blow-thru
heating operation. Coil shall have maximum working pressure of 1034 kPag (150 psig).
2. Steam Distributing Coil:
Coil shall consist of 1 row of copper tubes with
aluminum plate fins, and shall have inner steam
distributing tubes. Coil shall be mounted in a galvanized steel housing that shall be fastened to the
units fan deck for blow-thru heating operation.
Coil shall have maximum working pressure of
1207 kPag at 204.4 C (175 psig at 400 F).
3. Electric Heaters:
Heaters for nominal 230 or 400-volt, 3-phase
power supply shall be factory-supplied for field
installation as shown on the equipment drawings. Electric heat assembly shall be ETL (U.S.A.)
and ETL, Canada agency approved, and shall
have single-point power wiring. Heater assembly shall include contactors with 24-v coils, power
wiring, 24-v control wiring terminal blocks, and
a hinged access panel. Electric heaters shall not
be used with discharge plenum.
4. Air Discharge Plenum:
Plenum shall be provided to provide free-blow air
distribution for vertical floor-mounted units. A
grille with moveable vanes for horizontal or vertical airflow adjustment shall be included. Plenum
shall be field-assembled and field-installed on the
units fan deck for blow-thru air distribution. Plenum shall not be used with electric heaters.
5. Return-Air Grille:
Grille shall be factory supplied for field installation on the units return air opening.
6. Unit Subbase:
Subbase assembly shall be factory supplied for
field installation. Subbase shall elevate floormounted vertical units to provide access for correct condensate drain connection.
7. Economizer:
Economizer for ventilation or free cooling shall
be factory provided for field installation. For free
cooling applications, economizer shall be compatible with factory-supplied thermostat; economizer dampers shall open when outdoor air enthalpy is suitable for free cooling. Economizer shall
be compatible with separate CO2 sensor accessory; economizer dampers shall open when indoor CO2 level rises above predetermined set
point. Economizer shall include enthalpy control
and damper actuator with controls.
8. Thermostat Controls:
a. Debonair programmable multi-stage thermostat with 7-day clock, holiday scheduling,
large Thermoglow display, remote sensor
capability, and Title 24 compliance.
b. TEMP System programmable communicating multi-stage thermostat with fan
switch, timeclock, LCD display, F/C capability, and CCN (Carrier Comfort Network)
compatibility.
c. Commercial Electronic Thermostat with 7-day
timeclock, auto-changeover, multi-stage capability, and large LCD temperature display.
d. Non-programmable thermostat with fan switch
subbase.
9. Overhead Suspension Brackets:
Package shall include necessary brackets to support units in a horizontal ceiling installation.
10. CO2 Sensor:
Sensor shall provide the ability to signal the economizer to open when the space CO2 level exceeds
the predetermined set point. Sensor shall have
the capability of being connected to comfort system relay pack or to economizer using fieldsupplied and installed Honeywell dc adapter no.
Q769C1004.
11. Condensate Drain Trap:
Trap shall have transparent, serviceable design
for easy cleaning. Kit shall include overflow shutoff switch and wiring harness for connection to
an alarm if desired.
105
106
C. Fans:
1. Condenser fans shall be direct-drive propeller type,
discharging air vertically upward.
2. Condenser fan motors shall be 3-phase type
with class B insulation and permanently lubricated
bearings. Motors shall be drip proof with sealed
bearings. Class F fan motors shall be available as
a factory-installed option.
3. Shafts shall have inherent corrosion resistance.
4. Fan blades shall be statically and dynamically
balanced.
5. Condenser-fan openings shall be equipped with
PVC-coated steel wire safety guards.
D. Compressors:
1. Compressors shall be manufactured by the condensing unit manufacturer, and shall be serviceable, reciprocating, semi-hermetic type.
2. Compressors shall be equipped with an automatically reversible oil pump, operating oil charge,
suction and discharge shutoff valves, and an inserttype factory-sized crankcase heater to control oil
dilution.
3. Compressors shall be mounted on spring vibration isolators with an isolation efficiency of no less
than 95%.
4. Compressor speed shall not exceed 24.3 r/s
(1460 rpm).
5. Lead compressors on each circuit shall unload using suction cutoff unloading (electric solenoid unloading shall be available as an accessory).
E. Condenser Coils:
1. Condenser coils shall be air cooled and circuited
for integral subcooler.
2. Coil shall be constructed of aluminum fins mechanically bonded to internally grooved, seamless
copper tubes which are then cleaned, dehydrated,
and sealed. Copper fins and precoated aluminum
fins shall be available as options.
F. Refrigeration Components:
Refrigeration circuit components shall include hot gas
muffler, suction line accumulator, hot gas bypass stub
tubes, high-side pressure relief device, liquid line shutoff valve, suction and discharge shutoff valves, holding charge of refrigerant R-22, and compressor oil.
38AH094-134 and all 38AH044-084 single-circuit
units shall have suction line accumulators. The VAV
units shall also have suction line accumulators.
I. Electrical Requirements:
1. Nominal unit electrical characteristics shall be
v, 3-ph, 50 Hz. The unit shall be capable
of satisfactory operation within voltage limits of
v to
v.
2. Unit or module electrical power shall be singlepoint connection.
3. Unit control circuit shall be 230 v for 230 and
380/415 v units, and 200 v for 346 v units.
J. Special Features:
1. Unloader Conversion Kit:
Unloader valve, piston, and hardware shall be
supplied to convert any pressure-operated compressor unloader to electrical unloading. Accessory ModuPanel control or field-supplied step
controller shall be required for electrical unloading.
2. Gage Panel:
A gage panel package shall be provided which
includes a suction and discharge pressure gage
for each refrigerant circuit.
3. Accessory Transformer Relay Package:
Relay shall be provided for use with a remotecontrol 24-v thermostat.
4. Electric Unloader Package:
Electric unloader shall provide an additional step
of electric unloading.
5. Pressure Unloader Package:
Pressure unloader shall provide an additional step
of pressure unloading.
6. ModuPanel Control:
Indoor mounted control shall provide 10-step
microprocessor-based control for variable air
volume (VAV) applications.
7. Low-Ambient Motormastert III Control:
Control shall maintain correct condensing pressure at low ambient temperatures.
8. Optional Condenser Coil Materials:
a. Pre-Coated Aluminum-Fin Coils:
Shall have a durable epoxy-phenolic coating
to provide protection in mildly corrosive coastal
environments. Coating shall be applied to the
aluminum fin stock prior to the fin stamping
process to create an inert barrier between the
aluminum fin and copper tube. Epoxy-phenolic
barrier shall minimize galvanic action between
dissimilar metals.
b. Copper-Fin Coils:
Shall be constructed of copper fins mechanically bonded to copper tubes. All copper
construction shall provide protection in moderate coastal applications.
107
11-98
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 2
Tab 3a 1a
Page 108
Printed in U.S.A.
Printed in U.S.A.
Form 38AH-C4PD
Replaces: 38AH-C3PD