High Efficiency High Performance

Floor Mounted Packaged Airconditioners & Ducted Split Airconditioners

Floor Mounted Models :


DPA 661BS, 1052BS, 1322BS, 1983BS, 2642S DPW 661AS, 1322AS, 1983AS DPAY 1321S, 1982S DPAP 661S, 1052S, 1322S, 1983S DPAN 661S, 1052S, 1322S, 1983S

Ducted Split Models :


DSA 361D, 601D, 903B, 661DS, 1001BS, 1052BS, 1322DS, 2642S DSW 361, 661S, 1052S, 1322S

TECHNICAL MANUAL

First published June 2006 No part of this publication may be reproduced in any manner whatsoever without permission in writing from the Sr. General Manager, Packaged Airconditioning Division, Blue Star Limited. While due care has been taken to avoid errors or misinterpretation, Blue Star Limited is neither liable nor responsible for consequence of any action taken, on the basis of this publication. Since ASHRAE standards use the FPS system, FPS nomenclature is used in some places in this publication for convenient reference. Published by Blue Star Limited, 9, Bazullah Road, TNagar, Chennai 600 017, India. For restricted circulation only. Not for sale.

TECHNICAL MANUAL

Contents
Basics ....................................................................................... 2
What is airconditioning? What is a Packaged Airconditioner? Main Components General layout of components within the IDU What is a Split Airconditioner? What is a Ducted Split Airconditioner? HiPer+ Packaged ACs HiSen Packaged ACs Scroll Compressor Technology The Tandem Scroll 2 3 4 4 5 5 6 8 10 10

Operating Instructions: Floor-Mounted Packaged ACs ............................................. 12


Controller Specifications 12

Operating Instructions: Ducted Split ACs .................................................................... 16


Controller Specifications 16

Inspection & Maintenance .................................................... 19


A healthy supply Regular inspection 19 19

Troubleshooting ..................................................................... 22
Diagnosing faults Quick-check Troubleshooting Chart 22 22

Condenser Water Piping Schematic ............................................................................... 25 Troubleshooting the Water Circuit ........................................................................... 26 Technical Specifications ....................................................... 27 Schematics & Wiring Diagrams .......................................... 37 Warranty & Service ................................................................ 73

PACKAGED ACs & DUCTED SPLITS

Basics
What is airconditioning?
An airconditioning system consists of many pieces of mechanical and electrical equipment assembled together to produce in an enclosed space acceptable conditions of Temperature, Humidity, Air purity and Air motion. The basic compression refrigeration cycle, the most important part of an airconditioning system, is explained in the schematic diagram given below:

TECHNICAL MANUAL

What is a Packaged Airconditioner?


When all the mechanical and electrical components of an airconditioning system are assembled in a single package this is referred to as a Packaged Airconditioner. They are generally floor-standing units. Packaged ACs can be either air-cooled or water-cooled.

Air-cooled Packaged Airconditioners


Air-cooled Packaged ACs use air to cool the refrigerant. The IDU contains all the AC components except the condenser and its fan, which are separately housed in the Outdoor Unit (ODU). Electrical control of Aircooled Packaged AC models is at the bottom section of the unit. The new facia controller is mounted on the upper panel section.

Water-cooled Packaged Airconditioners


Water-cooled Packaged Airconditioners are compact floor standing units. All components including the condenser are included in the unit. Water is pumped into the unit to cool the refrigerant and the hot water is returned to external cooling towers, cooled and recirculated. Only the piping connections for the water cycle and the water cooling system are external. The electrical control panel is inbuilt at the bottom of the unit. The new facia controller is mounted on the upper panel section.
Indoor Unit

Outdoor Units

DPAP 5.5, 8.75, 11, 16.5 TR Models

22 TR Model

DPA, DPAN, DPAY 5.5, 8.75, 11, 16.5 TR Models

PACKAGED ACs & DUCTED SPLITS

Main Components
Air-cooled Packaged AC
A. Indoor Unit (IDU) COMPRESSOR COOLING COIL EXPANSION VALVE BLOWER FAN BLOWER FAN MOTOR FILTER CONTROL PANEL B. Outdoor Unit (ODU) CONDENSER COIL CONDENSER FAN WITH MOTOR

Water-cooled Packaged AC
A. Indoor Unit (IDU) B. Water cooled condenser (EXTRA)

General layout of components within the IDU

TECHNICAL MANUAL

What is a Split Airconditioner?


A split airconditioner has two parts the Indoor Unit (IDU) and the Outdoor Unit (ODU). The IDU is a concealed box that houses the cooling coil, centrifugal blower fan, electrical motor, expansion device, dryer etc. assembled in a single box. The ODU, which is the condensing unit, comprises of the compressor, aircooled condenser and a cooling fan. The ODU and IDU are interconnected by refrigerant piping and power cables. This keeps the noise of the compressor out of the airconditioned space.

What is a Ducted Split Airconditioner?


A ducted split airconditioner is a split airconditioner, in which the IDU is housed in a concealed box, usually mounted above the false ceiling. The air-flow from the IDU is directed into a ducted air distribution network. Ducting therefore is a key design aspect of these ACs. The ODU is conveniently located on the skirting, sunshade, roof-top or mounted on a special platform to be grouted into the wall.
Indoor Unit

Outdoor Units

3 TR Model

7.5 TR Model

5, 5.5, 8.75, 11 TR Models

22 TR Model

PACKAGED ACs & DUCTED SPLITS

HiPer+ Packaged ACs


Blue Star's HiPer Plus Packaged Airconditioners offer high performance machines even at high sensible loads and at 45o C ambients! The HiPer Plus is specially designed to aircondition IT/ITES/BPO premises situated in cities with harsh summers. Blue Star's HiPer Plus Packaged Airconditioners feature: Indoor units upsized to handle 90% sensible load delivering 550 CFM/ton, and Outdoor condenser upsized and system balanced to deliver full capacity at 45o C. Hence, 100 tons of Hi Per Plus will suffice, where 125 tons of conventional airconditioning was needed. That makes 1 Ton load of Hi Per Plus equivalent to 1.25 nominal ton.

Features
Here are some of the features that make the Hi Per Plus Packaged Airconditioner a high-end, superior quality product: Efficient heat transfer: The upsized evaporator offering enhanced surface area ensures removal of the high sensible heat and handles a higher indoor air volume of 550 CFM per ton. The inner grooved copper tubes with mechanically bonded slit aluminium fins ensure efficient heat transfer. Higher capacity evaporator fan: Optimally selected DIDW forward curved centrifugal type fan exclusively designed for delivering more air volume at 550 CFM/ton, with low noise levels. Optimum expansion valve: Optimally selected expansion valve with accurate preset super heat settings, minimizes splash gas and eliminates the problem of improper cooling in the evaporator. Condenser with higher heat rejection capability: The upsized condenser coil and twin fan condenser with higher heat rejection capability, ensures lower condensing temperature, thereby delivering full capacity even at temperatures as high as 45o C with extraordinary energy efficiency and substantially lower power consumption. Corrosion resistant blue fin condenser: The special precoated Blue Fin Condensers are resistant to both chemical and saline corrosion. They are tested for 500 hours of salt spray as per international standard JIS-Z-2371.

TECHNICAL MANUAL

Energy efficient scroll compressors: Scroll type, hermetically sealed highly energy efficient Copeland compressors. Acoustically treated and polyester powder painted panels: High-density EPE Insulation dampens the unit noise in the plant room.The panels are finished with glossy polyster powder paint, for longer life. Safety alarms and controls: Built-in safety features in the compressor and in the refrigeration circuits ensure high level of protection to the unit. Advanced Microcomputer Controller: A feature-packed microcomputer controller with Run Time Equalization, Auto Restart after power failure, Fuzzy Logic, Self-Fault Diagnostics and much more.

PACKAGED ACs & DUCTED SPLITS

HiSen Packaged ACs


The HiSen Packaged Airconditioner is designed optimally with an upsized cooling coil for 90% sensible heat load removal, and higher capacity indoor fan for delivering 550 CFM per ton. The upsized-cooling coil ensures a 10% improvement in cooling capacity and hence leads to a 10% power saving as well.

Features
Here are some of the features that make the HiSen Packaged Airconditioner a high-end, superior quality product. Efficient heat transfer cooling coil, with enhanced surface area: The inner grooved copper tubes with mechanically bonded slit aluminum fins ensure efficient heat transfer. The upsized-cooling coil offering enhanced surface area ensures removal of the high sensible heat and handles a higher indoor air volume of 550 CFM per ton. Higher capacity evaporator fan: Optimally selected DIDW forward curved centrifugal type fan exclusively designed for delivering more air volume at 550 CFM/ton with low noise levels. Optimum expansion valve: Optimally selected expansion valve with accurate preset super heat settings, minimizes splash gas and eliminates the problem of improper cooling in the evaporator. Corrosion resistant blue fin condenser: The special precoated Blue Fin Condensers can take on the harsh combination of salty air, rain and other corrosive atmospheres. They are tested for 500 hours of salt spray as per international standard JIS-Z-2371. Energy efficient scroll compressors: Scroll type, hermetically sealed highly energy efficient Copeland compressors. Acoustically treated and polyester powder painted panels: High density rigid acoustic board insulation, with over layer protection, dampens the unit noise in the plant room. The panels are finished with glossy polyester powder paint, for longer life. Ready-made air outlet flange connections: Units are provided with readymade flanged air outlets, to enable ease of connection to the canvas or the duct flange. Safety alarms and controls: Built in safety features in the compressor and in the refrigeration circuits ensure high level of protection to the unit.

TECHNICAL MANUAL

Advanced Microcomputer Controller


The advanced microcomputer controller offers the following user-friendly features: Run time equalization: Calculates and ensures equal run time for all compressors. Auto restart after power failure: No inconvenience of manual restart. Memory back up: Keeps settings intact during power failures and stoppages. Built-in-time delay: Protects compressor from instant stops and starts. Single phasing and reverse phase protection: Protects compressors from damage. Fuzzy logic: Cools intelligently based on the heat load, and hence increases efficiency. Self-fault diagnostics: Displays system trips, facilitating faster corrective action. Easy hook-up with fire alarm system: Potential free contacts provided for hooking on to the fire alarm system, for stopping the units in the event of a fire.

PACKAGED ACs & DUCTED SPLITS

Scroll Compressor Technology


The scroll technology is the most advanced compression technology with only three moving parts and with 100 % volumetric efficiency ideally suitable for most rugged commercial and industrial applications. Scroll compressors have much better liquid refrigerant handling capability than the other types of compressors due to the nature of scroll design. Scroll compressor durability and reliability as well as its quiet operation are inherent with the design of the scroll compressor.

The Tandem Scroll


Scroll-compressor-driven Packaged Airconditioners a few years ago paved the way for the migration of the AC industry to a more energy efficient cooling platform, the Tandem Scroll airconditioning system.

Tandem Compressor

A tandem scroll compressor consist of two individual compressors, mounted on a common base, manifolded in to a single refrigerant circuit. A tandem compressor (set) has the common suction, discharge, oil and also additional crank gas equalizer lines between the two compressors. For example, two scroll compressors are linked in tandem to form one tandem scroll compressor.

10

TECHNICAL MANUAL

In a conventional multi-circuit air conditioning system (as in a 11 ton Scroll Packaged AC), two 5.5-ton compressors drive two independent circuits, each with its own evaporator and condenser, each circuit rated to 5.5 tons. In a tandem scroll air conditioner, the 11-ton tandem scroll drives just one circuit, which therefore consists of just one condenser and evaporator, both of which are however designed for the full capacity of 11 tons.

Full Load Operation


Under full load conditions, the tandem scroll machine and the conventional scroll machine behave almost identically.

Part Load Operation


The entire picture changes dramatically under part-load conditions. Part-load conditions are those that prevail when an air-conditioned space is not fully occupied or used with less occupancy, as for example a half-full theatre or an empty showroom. In such cases, the entire capacity of the installed air conditioning system is not required to cool the premises. In both conventional and tandem scroll machines, one of the two compressors switches off under part-load conditions. However, in the tandem scroll system, the compressor that remains on utilizes the entire fully rated condenser for cooling purposes. This seemingly minor fact is a significant air conditioning innovation, remarkably increasing operating efficiency to the extent of 23%! The tandem scroll advantage Under favourable conditions, a compressor not only delivers higher tonnage, but consumes less power thus giving a dramatic increase in EER Under part-load conditions, using the double-capacity rated condenser is a favourable operating condition for the compressor. Tandem Scroll compressors should therefore deliver a higher EER under part-load conditions.

11

PACKAGED ACs & DUCTED SPLITS

Operating Instructions: Floor-Mounted Packaged ACs


CONTROLLER SPECIFICATIONS A) Salient Features
1. Digital control and setting of temperature values in 1o C. 2. Automatic selection of compressors with run time Equalization. 3. Non Volatile Memory backup for all set value parameters. 4. Automatic starting of unit in case of power failure. 5. Built-in time delays for Compressor and fan. 6. Built-in Single phase/phase reversal protection.

B) Specifications
1. Power supply Single phase, Voltage: 175 to 260 V AC. Frequency: 50 Hz + 3% 2. Operating temperature limit 3. Display 0 - 65o C 2 Digit 7-Segment LED Display, LED indicators and touch key pad 4. Temperature control accuracy 5. Set temperature range 6. Temperature sensors + 1% 19 - 32o C NTC thermister bit sensor with 5 meter long cable

7. LED Display & Keypad HANDSET Pendant mounting 8. Micro Computer Base unit Base mounting (enclosed in fire-retardant box)

C) Description of LED Indicators & Keys on Handset


LED indicators & keys available on keypad of the PKG unit handset are as follows: Reset LED : This LED indicator flashes green once if any key is pressed. In case of any fault, green flashes continuously. FAN (Ev) LED FAN MODE LED : If Blower Fan is ON, this LED indicator is Green and Red if it is OFF. : If Fan Mode is Selected, then only this LED indicator glows blue.

COOL MODE LED : If Cool Mode is Selected, then only this LED indicator glows blue. COMPR 1,2,3 LED : If Compr 1, 2, 3 are ON, this LED indicator is Green, and Red it it is OFF. ON/OFFLED UP/DN Key : This indicator is green if the unit is in ON mode and Red if it is in OFF. : These keys are used to increment values of the selected parameter.

12

TECHNICAL MANUAL

AC MODE Key ON/OFF Key RESET Key

: This key is used for selecting either Fan or Cool Mode. : This key is used for switching ON or OFF the unit. : This key is used for resetting a Fault or for restarting the unit after removing the existing fault.

D) Setting of Temperature
The 2-digit seven-segment display shows Actual Return Air Temperature. To view Set Temp, press UP/DN key once. At any time of operation, if no key is pressed for next successive 10 seconds, the display will show Actual Return Air Temperature. Temperature can be set between 19 to 32o C by pressing the UP/ DN keys. After you press UP or DN key Display will indicate the old setting. Press desired key to set new values. As soon as you reach the desired Temperature stop adjusting the keys. The digits will start blinking for 5 seconds. When the blinking stops the LED will show the Actual Return Air Temperature. Recommended Temperature for optimum comfort and power saving is 24 +/- 1o C.

E) Fault & Alarms Display


LED indicators display various faults occurring in the unit as follows. Nature of Fault SPPR Fault Display on LED SP Pr (scrolling) LED indication on Keypad & correction of Fault. RESET LED indicators will flash after the fault is cleared, now press Reset Key to restart the unit. Co LED indicators will flash Red if the fault exists. After the fault is cleared, unit restarts automatically. Ev LED indicator will flash Red if the fault exists. After the fault is cleared, unit restarts automatically. COMPR 1 LED indicator will flash Red if the fault exists. After the fault is cleared, unit restarts automatically. COMPR 2 LED indicator will flash Red if the fault exists. After the fault is cleared, unit restarts automatically. COMPR 3 LED indicator will flash Red if the fault exists. After the fault is cleared, unit restarts automatically.

Cooling Tower Fault Fan Overload Fault Cond Fan1 MCB trip/off Fault Cond Fan2 MCB trip/off Fault Cond Fan3 MCB trip/off Fault

Ct

BF

CF

CF

CF

13

PACKAGED ACs & DUCTED SPLITS

Compr 1 Fault High/Lo Pressure

HP LP (scrolling)

COMPR 1 LED indicator will flash Red if the fault exists. RESET LED indicator will flash after the fault is cleared, now press Reset Key to restart the unit. COMPR 2 LED indicator will flash Red if the fault exists. RESET LED indicator will flash after the fault is cleared, now press Reset Key to restart the unit. COMPR 3 LED indicator will flash Red if the fault exists. RESET LED indicator will flash after the fault is cleared, now press Reset Key to restart the unit. IF Temp sensor is open or bad then only LED will display Fault. This fault is Auto reset.

Compr 2 Fault High/Lo Pressure

HP LP (scrolling)

Compr 3 Fault High/Lo Pressure

HP LP (scrolling)

Temp sensor is open or bad.

tH

14

TECHNICAL MANUAL

F) Operating Instructions
Switch ON the unit by pressing ON/OFF key. ON LED will glow Green.

ON/OFF Key

Fan Mode LED

Cool Mode LED

To Start Evaporator Blower (FAN Mode) Press AC MODE Key to select the FAN Mode. FAN Mode LED will glow. The Blower Fan will come on immediately (if fan overload relay is not tripped.) To Start Compressor (COOL Mode) Press AC MODE Key once again to select the COOL Mode. COOL Mode LED will glow & Fan Mode LED will be Off. The compressor will come on with pre-set delay of 2 minutes. In case of multi compressor system the 2nd & 3rd compr. will come on after additional 15 sec. delay per compressor. Simultaneously the compressor indication starts blinking Green & then glow continuously thereafter. The Controller will select the number of compressors to be on based on Actual Room Temp & Set Temp. as follows: If actual Temp =/> Set Value + 3, all the Compressors will be ON. If actual Temp =/< Set Value + 2, only two Compressors will be ON. If actual Temp =/< Set Value + 1, only one Compressor will be ON. If actual Temp =/< Set Value - 1, all the Compressors will be OFF.

15

PACKAGED ACs & DUCTED SPLITS

Operating Instructions: Ducted Split ACs


CONTROLLER SPECIFICATIONS A) Salient Features
1. Digital control and setting of Temperature values in 1 Deg. C. 2. Automatic selection of compressors with run time Equalization. 3. Non Volatile Memory backup for all set value parameter. 4. Automatic starting of unit in case of power failure. 5. Built-in time delays for Compressor and Fan.

B) Specifications
1. Powers supply 2. Operating temperature limit 3. Display 4. Temperature control accuracy 5. Set temperature range 6. Temperature sensors 7. LED Display & Keypad HANDSET 8. Micro Computer Base Unit Single Phase, Voltage: 185 to 260 V AC. Frequency: 50 Hz 3% 0 - 65C 2 Digit 7-Segament LED Display, LED indicators and touch key pad 1% 19 - 32C NTC thermister Bit sensor with 5 meter long cable Pendant mounting Base mounting (enclosed in fire-retardant box)

C) Description of LED Indicators & Keys on Handset


Reset LED FAN (Ev) LED FAN MODE LED FAN SPEED LED : This LED indicator flashes once green if any key is pressed, or in case of any fault, flashes green continuously. : If Blower Fan is ON, this LED indicator is Green and Red if it is OFF. : If Fan Mode is Selected then only this LED indicator will glow blue. : If Fan Speed is Selected LO then only this LED indicator will glow ( LO / HI ) Yellow and if selected HI then LED indicator will glow Blue.

COOL MODE LED : If Cool Mode is Selected then only this LED indicator will glow blue. COMPR 1,2,3 LED : Compr 1,2,3 is ON, this LED indicator is Green and Red if it is OFF. ON/OFF LED UP/DN Key : This indicator is Green if the unit is in ON mode and Red if it is OFF. : These keys are used for increment / decrement value of the selected parameter.

16

TECHNICAL MANUAL

AC MODE Key ON/OFF Key FAN SPEED Key RESET Key

: This key is used for selecting either Fan or Cool Mode. : This key is used for switching ON or OFF the unit. : This key is used for switching Fan speed High/Low. : This key is used for resetting the Fault or for restarting the unit after removing the existing fault.

D) Setting of Temperature
The 2-digit seven-segment display will show the Actual Return Air Temperature. To view Set Temp. press UP/DN key once. At any time of the operation, if no key is pressed for next successive 10 seconds, the display will show Actual Return Air Temperature. Temperature can be set between 19 to 32 Degree Centigrade by pressing UP/DN keys. After you press UP or DN key Display will indicate the old setting. Press desired key to set new values. As soon as you reach the desired Temperature stop adjusting the keys. The digits will start blinking for 5 seconds. When the blinking stops the LED will show the Actual Return Air Temperature. Recommended Temperature for optimum comfort and power saving is 24 +/- 1 Deg. Cen.

E) Fault & Alarms Display


LED indicators displays the various faults occurring in the unit are as following. Nature of Fault SPPRFault Display on LED SP Pr (scrolling) LED indication on Keypad & correction of Fault. RESET LED indicator will flash after the fault s cleared, now press Reset Key to restart the unit. Co LED indicator will flash Red if the fault exists. This fault is Auto reset (Only for DSA 903 Model) COMPR 1 LED indicator will flash Red if the fault exists.RESET LED indicator will flash after the fault is cleared, now press Reset Key to restart the unit. (Not for DSA903) COMPR 2 LED indicator will flash Red if the fault exists.RESET LED indicator will flash after the fault is cleared, now press Reset Key to restart the unit. (Not for DSA903) IF Temp sensor is open or bad then only LED will display Fault. This fault is Auto reset.

Cond Fan MCB trip/off Fault Compr 1 Fault High/Lo Pressure

CF

HP LP (scrolling)

Compr 2 Fault High/Lo Pressure

HP LP (scrolling)

Temp sensor is open or bad.

tH

17

PACKAGED ACs & DUCTED SPLITS

F) Operating Instructions
Switch ON the unit by pressing ON/OFF key. ON/OFF key LED will glow Green.

On/Off Key

Fan Mode

Cool Mode Speed HI

Speed LO To Start Evaporator Blower (FAN Mode): Press AC MODE Key to select the FAN Mode, then FAN Mode LED will glow. The Blower Fan will come on immediately. To Start Compressor (COOL Mode): Press AC MODE Key once again to select the COOL Mode, then COOL Mode LED will glow & Fan Mode LED will be Off. The compressor will come on with pre-set delay of 1 minutes. In case of multi compressor system the 2nd & 3rd compr. will come on after additional 10 sec. delay per compressor. Simultaneously the compressor indication will start blinking in Green for time period stated & glow continuously thereafter. Controller will select number of compressors based on Actual Room Temp & Set Temp. as following If Actual Temp =/> Set Value + 3, all the Compressors will be ON. (Only for DSA 903) If actual Temp =/< Set Value + 2, only two Compressors will be ON. (for DSA 903 / 1322) If actual Temp =/< Set Value + 1, only one Compressor will be ON. If actual Temp =/< Set Value - 1, all the Compressors will be OFF.

18

TECHNICAL MANUAL

Inspection & Routine Maintenance


Regular inspection of the IDU and ODU reduces failures and assures continuous operation.

A healthy supply
CHECK IF INCOMING POWER IS AS PER THE RATED POWER SUPPLY: VOLTS PHASE CYCLES TYPE 380-420V THREE PHASE 50 Hz AC ONLY

Regular inspection
Regular inspection must be carried out as follows: Item Filter cleaning Period Once a week Inspection Procedure For Packaged AC
Filter Water hose

Pull out from top ends and lift to remove the front GRILLE from the UNIT. Then remove the internal filter and wash it with water. Dry the filter in the shade and re-install it. For Ducted Split AC Slide the filter from lifting upwards and wash it with water. Dry the filter in the shade and re install it.

19

PACKAGED ACs & DUCTED SPLITS

Item

Period

Inspection Procedure For Packaged AC Oil leaks... Verify that there are no oil leaks. Crank case heater...Touch the heater body to verify that it is warm. Vibration isolation rubber ... Inspect the vibration isolation rubber for wear. For Ducted Split AC Oil leaks... Verify that there are no oil leaks. Vibration isolation rubber ... Inspect the vibration isolation rubber for wear. Check for bolts tight at the mounting legs.

General compressor checks

Twice a year

Gas leak check

Twice a year

For Packaged AC

Remove the grille and front bottom cover and conduct test for gas leaks in all refrigerant pipe joints. Gas leak check Four times a year For Ducted Split AC Indoor Unit

Remove the cover from the bottom and conduct test for gas leaks inside portion of the coil and remove filter for outer portion. Outdoor Unit

Test for leaks in condenser coil tubes and also compressor joints.

20

TECHNICAL MANUAL

Item

Period

Inspection Procedure For Packaged AC

Condenser Coil and outdoor unit

Four times a year

Thorough cleaning of coil and the overall unit can reduce atmospheric dust pollution and improves performance. For Ducted Split AC Electrical circuits & terminals Four times a year Check all wires/cables and connector terminals are tight with screwed ends. If not, tighten and pull the wire for proper grip/ holding. Clean the condenser coils with portable blower to blow out dust. This improves the performance.

Condenser coils

Once in a month

21

PACKAGED ACs & DUCTED SPLITS

Troubleshooting
Faults and complaints in Packaged AC systems can be broadly classified under three areas. The first step in troubleshooting is to identify the area and diagnose the fault.

Diagnosing faults
Malfunctions can be classified under any of the following: A. The Electrical Circuit The malfuntioning of electrical circuit is due to LOW or HIGH voltage variations, frequent power failures, loose electrical contacts, defective electrical components, etc. Proper periodical maintenance of the unit will reduce such malfunctioning. Problems due to power supply quality must be sorted out with the concerned electricity board. B. The Refrigeration Circuit Improper cooling usually indicates poor performance of the refrigeration circuit. Reasons may be poor servicing, low/high gas in the system, noncondensible gases, and lower efficiency of the compressor. Periodical service helps avoid such problems. The troubleshooting chart that follows will help isolate the exact fault and suggest remedies. C. The Conditioned Air Circuit Less air flow, poor cooling, uneven temperature, excessive airleaks are complaints that come under this classification. Most of them can be eliminated by periodical servicing. The troubleshooting chart that follows will help isolate the exact fault and suggest remedies.

Quick-check Troubleshooting Chart


SYMPTOMS
1. COMPRESSOR HIGH DISCHARGE PRESSURE Non condensible gases Over charged refrigerant Choked condenser fins Less ODU airflow Low refrigerant charge Low compression efficiency HIGH SUCTION PRESSURE Excessive load Defective suction valves Purge the system Remove excess Clean the ODU coil Correct fan direction Check for leaks, repair and recharge Replace compressor. Reduce fresh air & load Replace compressor

CAUSE

REMEDY

LOW DISCHARGE PRESSURE

(continued)

22

TECHNICAL MANUAL

SYMPTOMS

CAUSE

REMEDY

LOW SUCTION PRESSURE

Clogged suction strainer No cooling load Choked air filter Thermostat erratic Air in the system Overcharged gas Condenser fan not working Liquid knock Defective valve reeds

Clean/replace strainer Check thermostat Clean air filter Check thermostat Purge the system Remove excess charge Check ODU performance Check return air filter/ Check for coil chokeup Replace compressor

COMPRESSOR SHORT CYCLES ON LOW PRESSURE COMPRESSOR TRIPS ON HIGH PRESSURE

COMPRESSOR NOISY

SCROLL COMPRESSOR COMPRESSOR PRESSURE DOES NOT BUILD UP TO HIGH PRESSURE COMPRESSOR PRESSURE DOES NOT GO DOWN ON LOW PRESSURE COMPRESSOR NOISY Compressor motor working in reverse rotation Do Interchange any two phases of polarity for changing direction Do

Do

Do

2. BLOWER FAN MOTOR NOT STARTING TRIPPING ON OVER LOAD

Check power supply/fuses Check over load relay Fuse blown

Restore power supply Reset relay Check electrical circuit and replace

3. OVERALL UNIT NOISY OPERATION Blower touching scroll Bearing noise Belt loose Realign blower Lubricate bearings Tighten the belt

(continued)

23

PACKAGED ACs & DUCTED SPLITS

SYMPTOMS

CAUSE
Loose panels

REMEDY
Check & tighten screws Charge gas Replace thermostat Recheck heatload

UNIT OPERATES CONTINOUSLY

Shortage of refrigerant Defective thermostat Unit undersized

4. CONDITIONED AREA DISCOMFORT IN THE CONDITIONED AREA Less air flow High humidity Poor cooling Excess heat load Inadequate cooling Less airflow Compressor trips soon after start TOO COLD IN CONDITIONED SPACE Check air filter / belt Regulate fresh air Check refrigeration circuit Check & regulate heat load Check compressor ON/ Check filter choke up Check reversal of blower fan Change incoming supply phase polarity on any two phases (for scroll compressor) Replace thermostat Replace contactor

TOO WARM IN CONDITIONED SPACE

Defective thermostat Contactor stuck up

24

TECHNICAL MANUAL

Condenser Water Piping Schematic

25

PACKAGED ACs & DUCTED SPLITS

Troubleshooting the Water Circuit


SYMPTOMS
EXCESSIVE WATER DRIFT

CAUSE
Faulty drift elimination

REMEDY
Check to be sure all Louvres, Eliminator Sections or slats and splash retainers are in place. Top deck assemblies and wood fill splash bars must be intact and level. There must be no tendency to channel water. Fill packs must be intact and in place with no sagging or gaps between packs.

Over-pumping

Reduce water flow to tower to design conditions or use larger metering orifices. Tighten all bolts and cap screws on all mechanical equipment and supports. Be sure blades are properly positioned in correct sockets. Check match numbers. Make certain all blades are as far from centre of fan as safety devices permit. All blades must be pitched the same. Clean-off deposit build up on blades. Disconnect load and operate motor. If motor still vibrates, check for bent shaft or unbalanced rotor. Replace shaft or rebalance rotor. Tighten fan hub cover fasteners. Check water quality Install Water Treatment System

UNUSUAL FAN DRIVE VIBRATION

Loose bolts & cap screws

Fan

Motor

FAN NOISE SCALE OR FOREIGN SUBSTANCE IN WATER SYSTEM

Loose fan hub cover Insufficient blow down Poor water quality

26

TECHNICAL MANUAL

Technical Specifications
MODELS
Floor-Mounted Packaged ACs
HiPer Plus + Packaged Airconditioner HiSen Packaged Airconditioner Tandem Packaged Airconditioner Air Cooled Packaged Airconditioner DPAP 661S, 1052S, 1322S, 1983S DPAN 661S, 1052S, 1322S, 1983S DPAY 1321S, 1982S DPA 661BS, 1052BS, 1322BS, 1983BS, 2642S DPW 661AS, 1322AS, 1983AS

Water Cooled Packaged Aircondionter

Ducted Splits
Aircooled Ductable Splits with Recip. Compressor Air Cooled Ductable Splits with Scroll Compressor Water Cooled Ductable Splits with Scroll Compressor and Recip DSA 361D, 601D, 903B

661DS, 1001BS, 1052BS, 1322DS 2642S DSW361, 661S, 1052S, 1322S

27

PACKAGED ACs & DUCTED SPLITS

HiPer Plus
(Hi Sensible Air-cooled Packaged Airconditioners with Scroll Compressors & High EER Condensers)
Model Nominal Cooling Capacity Units KCAL/HR TR Indoor Unit Dimensions Cooling Coil Blower Fan Nominal Airflow Fan Motor Compressor Conrol Panel External Static Outdoor Unit (high ambient) Dimensions Condenser Coil Quantity Condenser Fan Type Nominal Airflow Fan Motor Quantity Indoor Unit Weight Outdoor Unit Weight Safety Devices for Compressor Protection Kg Kg CMH Watts 7500 188 2 195 75 W x D x H (mm) 1020 x 406 x 1270 1 1020 x 406 x 1270 2 Propeller 7500 188 2 295 75 7500 188 2 470 75 7500 188 2 600 75 1020 x 406 x 1270 2 1020 x 406 x 1270 3 Inner Grooved with Slit Fins-Anti Corrosion Coating 6 CMH Watts Type Quality 1 4675 560 W x D x H (mm) 900 x 660 x 1700 1160 x 660 x 1700 Centrifugal 7450 1500 Scroll 2 Inbuilt 7.5 8 10 2 9350 2250 14025 3000 1500 x 750 x 1800 1500 x 930 x 2000 Internally Grooved Copper Tubing with Slit Fins DPAP-661S 16500 5.5 DPAP-1052S 26250 8.75 DPAP-1322S 33000 11 DPAP-1983S 49500 16.5

4 Wire System-415V -3PH-50Hz

Inbuilt Internal Thermal Protector Internal Pressure Relief Valve High Pressure Cutout Low Pressure Cutout

Refrigerant Piping/Elecrical Hot Gas Line Liquid Line Condensate Drain GI / PVC MCB Rating Power Cable Incoming Earthing Double Loop Copper Od Inches X Gauge 7/8 X 16G 5/8 X 19G 32mm 32A 4Cx6mm Sq Cu 2 X 8 G GI Wires

Hard Drawn Grade - L Copper Tubes Only 7/8 X 16G 5/8 X 19G 32mm 40A 4Cx10mm Sq Cu 2 X 8 G GI Wires 7/8 X 16G 5/8 X 19G 32mm 40A 4Cx10mm Sq Cu 2 X 8 G GI Wires 7/8 X 16G 5/8 X 19G 32mm 63A80A 4Cx16mm SQ CU 2 X 8 G GI Wires

28

TECHNICAL MANUAL

HiSen
(Hi Sensible Air-cooled Packaged Airconditioners with Scroll Compressors & Standard Condensers)
Model Nominal Cooling Capacity Units KCAL/HR TR DPAN-661S 16500 5.5 DPAN-1052S 26250 8.75 4 Wire System-415V -3PH-50Hz Indoor Unit Dimensions Cooling Coil Blower Fan Nominal Airflow Fan Motor Power Compressor CMH Watts Type Quality Conrol Panel External Static Outdoor Unit (Normal ambient) Dimensions Condenser Coil Quantity Condenser Fan Type Nominal Airflow Fan Motor Power Quantity Indoor Unit Weight Outdoor Unit Weight Safety Devices for Compressor Protection Kg Kg CMH Watts 7500 240 1 195 86 W x D x H (mm) 1020 x 406 x 954 1020 x 406 x 954 1020 x 406 x 954 1020 x 406 x 954 MM 6 1 4675 560 W x D x H (mm) 900 x 660 x 1700 1160 x 660 x 1700 1500 x 750 x 1800 1500 x 930 x 2000 DPAN-1322S 33000 11 DPAN-1983S 49500 16.5

Internally Grooved Copper Tubing with Slit Fins Centrifugal 7450 1500 Scroll 2 Digital-Micro Controller Type Inbuilt 7.5 8 10 2 3 9350 2250 14025 3000

Inner Grooved with Slit Fins-Anti Corrosion Coating 1 2 Propeller 7500 240 1 295 86 Inbuilt Internal Thermal Protector Internal Pressure Relief Valve High Pressure Cutout Low Pressure Cutout Hard Drawn Grade - L Copper Tubes Only 7/8 X 16g 7/8 X 16g 7/8 X 16g 5/8 X 19g 32mm 32A Copper 4Cx6mm Sq Cu 2 X 8 G GI Wires 5/8 X 19g 32mm 40A 4Cx10mm Sq Cu 2 X 8 G GI Wires 5/8 X 19g 32mm 63A 4Cx10mm Sq Cu 2 X 8 G GI Wires 7/8 X 16g 5/8 X 19g 32mm 63A 4Cx16mm Sq Cu 2 X 8 G GI Wires 7500 240 1 470 86 7500 240 1 600 86 2 3

Refrigerant Piping/Electrical Hot Gas Line Od Inches X Gauge Liquid Line Condensate Drain GI/PVC MCB Rating Power Cable Incoming Earthing Double Loop

29

PACKAGED ACs & DUCTED SPLITS

Air-cooled Packaged Airconditioners


(With Scroll Tandem Compressors)
Model Nominal Cooling Capacity Indoor Unit Dimensions Cooling Coil Blower Fan Nominal Airflow Fan Motor External Static Compressor Safety Devices For Compressor Protection CMH Watts mm Type Quantity Units Kcal /Hr TR W X D X H (mm) DPAY-1321S 33000 11 1160 X 660 X 1700 Centrifugal 7480 1500 8 Scroll 1tandem Inbuilt Internal Thermal Protector Internal Pressure Relief Valve High Pressure Cutout Low Pressure Cutout Digital -micro Cotroller Type W X D X H (mm) 1020 X 406 X 954 2 Propeller CMH Watts Kg Kg Od Inches X Gauge 7500 240 1 305 86 1 1/8 X 16g 5/8 X 19g 32mm 40A Copper 4cx10mm Sq Cu 2 X 8 G Gi Wires 1020 X 406 X 954 3 Propeller 7500 240 1 503 86 1 1/8 Tandem & 7/8 Solo 16 g 5/8 X 19g Both 32mm 63A 4cx16mm Sq Cu 2 X 8 G Gi Wires 11220 2250 9 Scroll 1 Tandem + 1 Single DPAY-1982S 49500 16.5 1500 X 750 X 1800

Control Panel Outdoor Unit Dimensions Quantity Condenser Fan Type Nominal Airflow Fan Motor Quanity Indoor Unit Weight Outdoor Unit Weight Refrigerant Piping/Elecrical Hot Gas Line Liquid Line Condensate Drain GI / Pvc MCB Rating Power Cable Incoming Earthing Double Loop

30

TECHNICAL MANUAL

Air-cooled Packaged Airconditioners


(With Scroll Compressors)
Model Nominal Cooling Capacity Units KCAL/HR TR Indoor Unit Dimensions Cooling Coil Blower Fan Nominal Airflow Fan Motor Power Compressor DPA-661BS 16500 5.5 DPA-1052BS 26250 DPA-1322BS 33000 DPA-1983BS 49500 16.5 New DPA2642S 66000 22

8.75 11 4 Wire System-415V -3PH-50Hz

W x D x H (mm)

900 x 660 x 1700

CMH Watts Type Quality

3740 560 1 6

Conrol Panel External Static MM Outdoor Unit (Normal ambient) Dimensions W x D x H (mm) Condenser Coil Quantity Condenser Fan Type Nominal Airflow CMH Fan Motor Power Watts Quantity Indoor Unit Weight Kg Outdoor Unit Weight Kg Safety Devices for Compressor Protection Refrigerant Piping/Elecrical Hot Gas Line Liquid Line Condensate Drain Gi / PVC Mcb Rating Power Cable Incoming Earthing Double Loop Od Inches X Gauge

1160 x 660 x 1700 1160 x 660 x 1700 1500 x 750 x 1800 Internally Grooved Copper Tubing with Slit Fins Centrifugal 5900 7480 11220 1100 1500 2250 Hermetically Sealed Scroll 2 2 3 Digital-Micro Controller Type (Inbuilt) 7.5 8 9

1500 x 930 x 2000

14960 3000 2 10

1020 x 406 x 954 1020 x 406 x 954 1020 x 406 x 954 1020 x 406 x 954 Inner Grooved with Slit Fins-Anti Corrosion Blue fin coated 1 2 2 3 Propeller 7500 7500 240 240 1 1 295 302 86 86 Inbuilt Internal Thermal Protector Internal Pressure Relief Valve High Pressure Cutout Low Pressure Cutout 7/8 X 16g 5/8 X 19g 32mm 40A 4cx10mm Sq Cu 2 X 8 G GI Wires 7/8 X 16g 5/8 X 19g 32mm 40A 4cx10mm Sq Cu 2 X 8 G GI Wires

1435 x 620 x 947 2

7500 240 1 195 86

7500 240 1 438 86

17000 260 2 580 120

Hard Drawn Grade - L Copper Tubes Only 7/8 X 16g 5/8 X 19g 32mm 32A 4cx6mm Sq Cu 2 X 8 G GI Wires 7/8 X 16g 5/8 X 19g 32mm 63A 4cx16mm Sq Cu 2 X 8 G GI Wires 1 1 / 8 X 16g 7 / 8 X 19g 32mm 80A 4cx25mm Sq Cu 2 X 8 G GI Wires

Copper

31

PACKAGED ACs & DUCTED SPLITS

Water-cooled Packaged Airconditioners


(With Scroll Compressors)
Model Nominal Cooling Capacity Dimensions Weight Compressor Type External Static Compressor Protection Units KCAL /HR TR WxDxH (mm) Kg Type Quantity mm DPW-661AS DPW-1322AS DPW1983AS 49500 16.5 1500x750x1800 556 Scroll 3 9 16500 33000 5.5 11 900x660x1700 1160x660x1700 253 390 Scroll Scroll 1 2 6 8 Inbuilt Internal Thermal Protector Internal Pressure Relief Valve High Pressure Cutout Low Pressure Cutout 1.77 1.77 380 / 420 V, 3 Phase, 50 Hz AC 342 / 462 4 Nos Rubber Mounts With Sleeves 38.1 38.1 Aluminium 0.16mm Thick Copper 9.5 / 3/8" Centrifugal Forward Curved Double Inlet CMH Watts mm Qtty 3740 7480 560 1500 305 X 229 305 X 305 1 1 1440 Thermostatic Expansion Valve With External Eqaliser 517x828x10 517x828x10 1 2 11220 2250 381x 381 1

Oil Charge (Ltrs) Power Supply Operating Voltage Mounting Arrangement Compressor Wt. Evaporator Coil Fin Material Tube Material Tube Dia Mm / Inches Evaporator Blower Blower Fan Nominal Airflow Fan Motor Blower Size (Od Xlg) No Of Blowers Motor Rpm Expansion Device Air Filter Size No Of Filters Condenser Water Cooled Type Tube Material/ Od Quantity Water Connections In & Out Refrigerant Conn. -Hs Inlet/ Liquid Fusible Plug Size / Melting Temp. Drain Plug And Vent Water Quantity Pressure Drop Fouling Factor Sq. Ft. Hr. Deg. F/Btu Drain Piping/Elecrical Condensate Drain GI / PVC MCB Rating Power Cable Incoming Earthing Double Loop

Ltrs

1.77

Kgs

38.1

mm Nos

457x933x10 3

Cu / 3/4"Od 1 Bsp Mm Od Cu Inches mm / Deg C mm Fpt Usgpm Psig 1/2" / 3/8"

Cu / 3/4"Od 1 32 Mm 1/2" / 3/8" 9.5mm/91 C 6.3 Mm / 1/4" 40 9 0.0005 GI/ Class B Pipes 32mm 40A 4cx10mm Sq Cu 2 X 8 G GI Wires

Cu / 3/4"Od 1 1/2" / 3/8"

20 3.5

60 10

32mm 32A 4cx6mm Sq Cu 2 X 8 G GI Wires

32mm 63A 4cx16mm Sq Cu 2 X 8 G GI Wires

Copper

32

TECHNICAL MANUAL

Air-cooled Ductable Split Airconditioners


(With Scroll Compressors)
Model Indoor Unit Nominal Cooling Capacity Dimensions Indoor Unit Weight Evaporator Coil Fin Material Tube Material Tube Dia Mm / Inches Evaporator Blower Blower Fan Nominal Airflow Fan Motor Blower Size (Od Xlg) No Of Blowers Air Outlet Size Expansion Device Air Filter Size No Of Filters Speed Rpm Outdoor Unit Dimensions Compressor Type Power Input Each Compressor Compressor Protection Units Kcal /Hr Tr WxDx H (Mm) Kg DSA-661DS 16500 5.5 1220x675x450 68 DSA-1001BS 24900 8.3 1525x675x450 96 DSA-1052BS 26250 8.75 1525x675x450 96 DSA-1322DS 33000 11 1850x675x450 127 DSA-2642S 66000 22 2160x1225x690 230

Aluminium 0.16mm Thick Copper 9.5 / 3/8" Centrifugal Forward Curved Double InletCentrifugal Forward Curved Double Inlet Cmh Watts Mm Qtty Mm Mm Nos Rpm WxDx H (mm) Type Quantity Kw 3740 375 270x270 1 280x345 563 X 403 2 920/870 1020x406x954 Scroll 1 5.25 5650 5900 7480 375 Each 375 Each 375 Each 270x270 270x270 270x270 2 2 2 280x920 280x920 280x1095 Thermostatic Expansion Valve With External Eqaliser 468x403 468x403 593x403 3 3 3 920/870 920/870 920/870 1380x856x557 Scroll 1 7.86 1020x406x954 Scroll 2 4.14 1020x406x954 Scroll 2 5.25 14960 375 Each 305x229 3 342x1650 645x595 3 920/870 1435x620x947 Scroll 2 10.5

Oil Charge (Ltrs) Power Supply Operating Voltage Mounting Arrangement Compressor Wt. Condenser Coil Quantity Condenser Fan Type Nominal Airflow Fan Motor Quanity Weight Refrigerant Piping/ Elecrical Suction Line Liquid Line Condensate Drain GI / PVC Mcb Rating Power Cable Incoming Earthing Double Loop

Ltrs

Inbuilt Internal Thermal Protector Internal Pressure Relief Valve High Pressure Cutout Low Pressure Cutout 1.77 3.25

1.77

1.77

3.25

Kgs

Cmh Watts Kg

380 / 420 V , 3 Phase, 50 Hz Ac 342 / 462 4 Nos Rubber Mounts With Sleeves 38.1 69.4 35.4 3/8" (9.5mm) Cu Tubes And 0.16 Mm Thick Al Fins 1 2 2 Four Blade Propeller Fan 7500 10200 7500 240 586 240 1 1 1 107 188 107 Hard Drawn Grade - L Copper Tubes Only 7/8 X 19g 5/8 X 19g 25mm 32A 4cx6mm Sq Cu 2 X 8 G Gi Wires 1 1/8 X 19g 5/8 X 19g 25mm 40A 4cx10mm Sq Cu 2 X 8 G Gi Wires 3/4 X 19g 1/2 X 19g 25mm 40A 4cx10mm Sq Cu 2 X 8 G Gi Wires

38.1 2 7500 240 1 107

62.6 2 17000 260 2 220

Od InchesxGauge

7/8 X 19g 5/8 X 19g 25mm 40A 4cx10mm Sq Cu 2 X 8 G Gi Wires

1 3/8 X 19g 7/8 X 19g 25mm 80A 4cx25mm Sq Cu 2 X 8 G Gi Wires

Copper

33

PACKAGED ACs & DUCTED SPLITS

Air-cooled Ductable Split Airconditioners


(With Recip Compressors)
Model Nominal Cooling Capacity Indoor Unit Dimensions Cooling Coil Blower Fan Nominal Airflow Fan Motor Quantity Speed - Rpm Power To Fan Motor External Static Outdoor Unit Dimensions Quantity Power Supply Source Compressor Quantity Condenser Fan Type Nominal Airflow Fan Motor Quanity Controller Indoor Unit Weight Outdoor Unit Weight Refrigerant Piping/ Elecrical Suction Line Liquid Line Condensate Drain GI / PVC MCB Rating Power Cable Incoming Earthing Double Loop Copper Kg Kg CMH Watts 4000 105 1 1 WxDxH (Mm) 1020x406x686 1 1020x406x954 1 415 V -3 Ph - 50HZ Hermetically Sealed Recip Compressor 1 Propeller 6800 188 1
-188 2 Di. Pendant Controller 96 kg 220 3 1360x550x856

Units KCAL /HR Tr WxDxH (mm)

DSA -361D 9000 3 915x660x375

DSA-601D 15000 5 1219x660x457 Centrifugal

DSA -903B
7.5

1525x660x457

Inner Grooved Copper Tubing With Slit Fins

CMH Watts

2040 188 1 2-1200/1150

3400 375 1 2-920/870 230 V - 1 Ph - 50 Hz 5

5100 750 1 2 - 1200 /1150

mm

7.5

Elec. Micro Processor Pendant Controller 60 80 Hard Drawn Grade - L Copper Tubes Only Od Inches X Gauge 3/4 X 19g 3/8 X 19g 25mm 32A 4cx6mm Sq Cu 2X8 G GI Wires 7/8 X 19g 5/8 X 19g 25mm 32A 4cx6mm Sq Cu 2X8 G GI Wires 86 112

5/8 X 19g 3/8 X 19g 25mm 40A 4cx6mm Sq Cu 2x8 G GI Wires

34

TECHNICAL MANUAL

Water-cooled Ductable Split Airconditioners


(With Recip & Scroll Compressors)
Model Nominal Cooling Capacity Indoor Unit Dimensions Blower Fan Nominal Airflow Fan Motor Quantity Speed - Rpm Power To Fan Motor External Static Outdoor Unit Dimensions Quantity Power Supply Source Compressor Quantity Condenser Water Inlet/Out Let Size Cooling Water Quantity Controller Indoor Unit Weight Outdoor Unit Weight Cds Water Piping/ Electrical Condenser Water In Condenser Water Out Condensate Drain GI / PVC Mcb Rating Power Cable Incoming Earthing Double Loop Copper 32mm 32mm 25mm 32A 4cx4mm Sq Cu 2 X 8 G GI Wires Kg Kg 60 130 mm Usgpm 11 Recip 1 1 Shell And Tube 31.7BSP 20 15.5 20
W X D X H (mm) 983x713x546 W X D X H (mm) 953 X 585 X 381 1220 X 675 X 457 1525 X 675 X 457 1830 X 675 X 457

Units Kcal /Hr Tr

DSW 361 9000 3

DSW 661S 16500 5.5

DSW 1052S 26250 8.75

DSW 1322S 33000 11

Centrifugal CMH /CFM Watts 2050/1200 180 1 1200/1100 3740/2200 375 1 2 - 920/870 230 V - 1 Ph - 50 Hz mm 4 5 6 7 5900/3440 375 2 2 - 920/870 7480/4400 375 2 2 - 920/870

1 415 V -3 Ph - 50Hz

Scroll 1 1

Electronic Micro Processor Pendant Controller 68 149 GI/ Ms Class B Pipes 40mm 40mm 25mm 32A 4cx6mm Sq Cu 2 X 8 G GI Wires 32mm 32mm 25mm 40A 4cx10mm Sq Cu 2 X 8 G GI Wires 40mm 40mm 25mm 63A 4cx10mm Sq Cu 2 X 8 G GI Wires 96 144 127 149

35

PACKAGED ACs & DUCTED SPLITS

36