DEBER 2

Realice todos los ejercicios de caracterstica esttica del libro de Bentley, 4 ed.

1. The e.m.f. at a thermocouple junction is 645 V at the steam point, 3375 V at the zinc
point and 9149 V at the silver point. Given that the e.m.f.temperature relationship is
of the form E(T) = a
1
T + a
2
T
2
+ a
3
T
3
(T in C), find a
1
, a
2
and a
3
.

645 = a
1
(645) + a
2
(645)
2
+ a
3
(645)
3
3375 = a
1
(420) + a
2
(420)
2
+ a
3
(420)
3

9149 = a
1
(962) + a
2
(962)
2
+ a
3
(962)
3


a
1
= 5.845 VC
-1
a
2
= 6.303*10
-3
VC
-2
a
3
= -2.592*10
-6
VC
-3

2. The resistance R() of a thermistor at temperature K is given by R() =exp(/).
Given that the resistance at the ice point ( =273.15 K) is 9.00 k and the resistance at
the steam point is 0.50 k, find the resistance at 25 C.

Con R() = 9.00 k

273.15

273.15

e
9

e 9
=
=


Con R() =0.50 k

373.15

373.15

e
0.5

e 5 . 0
=
=



De lo que se tiene:

K 04 . 2946
18
1
ln
273.15

373.15

18
1
e
e
0.5
e
9
273.15

373.15

373.15

273.15

=
|
.
|

\
|
=
=
=


k 10 * 1.86
e
9

e
9

4
273.15
2946.04
273.15

=
=
=


A los 25C = 298.15

( )
( ) k 3.637 R
e * 10 * 1.86 R
298.15
2946.04
4 -
=
=


3. A displacement sensor has an input range of 0.0 to 3.0 cm and a standard supply voltage
Vs = 0.5 volts. Using the calibration results given in the table, estimate:
a) The maximum non-linearity as a percentage of f.s.d.
b) The constants K
I
, K
M
associated with supply voltage variations.
c) The slope K of the ideal straight line.

Displacement x cm 0.0 0.5 1.0 1.5 2.0 2.5 3.0
Output voltage millivolts (V
s
= 0.5) 0.0 16.5 32.0 44.0 51.5 55.5 58.0
Output voltage millivolts (V
s
= 0.6) 0.0 21.0 41.5 56.0 65.0 70.5 74.0

y = -6,5x
2
+ 38,89x - 0,428
y = -8,261x
2
+ 49,39x - 0,381
0
10
20
30
40
50
60
70
80
0 1 2 3 4
V
o
l
t
a
j
e

d
e

s
a
l
i
d
a

[
m
V
]
x [cm]
Caracterstica Esttica
V = 0.5 V
V = 0.6 V


c)

1 -
cm mV 33 . 19 K
0 - 3
0 58
K
Imin Imax
Omin Omax
K
=

=


a)

V(x) = -6.5x
2
+ 38.98x 0.428 Aproximando del grfico
V(x) = 19.33x Ideal
V(x) = 19.33x + N(x) Ajuste para curvas no lineales
N(x) = -6.5x
2
+ 38.98x 0.428 -19.33x = -6.5x
2
+ 19.65x 0.428 V(x) ideal y V(x) real

N(x) = -13x + 19.65 = 0 para que sea mxima

x = 1.51
n = Nmax = N(1.51) = -6.5(1.51)
2
+ 19.65(1.51) 0.428 = 14.42

87 . 24 nl%
100 *
0 58
14.42
nl%
100 *
Omin Omax
n
nl%
=

=

=


b)

K
I
= 0 No existe desplazamiento de la curva a lo largo de ningn eje.
I
M
= V
s1
-V
s2
= 0.1 mV

1 -
cm mV 67 . 24 K'
0 - 3
0 4 7
K'
Imin Imax
min O' max O'
K'
=

=


24.67 = 19.33 + K
M
(0.1)

K
M
= 53.37 mV cm
-1
V
-1

4. A liquid level sensor has an input range of 0 to 15 cm. Use the calibration results given
in the table to estimate the maximum hysteresis as a percentage of f.s.d.

Level h cm 0.0 1.5 3.0 4.5 6.0 7.5 9.0 10.5 12.0 13.5 15.0
Output volts h increasing 0.00 0.35 1.42 2.40 3.43 4.35 5.61 6.50 7.77 8.85 10.2
Output volts h decreasing 0.14 1.25 2.32 3.55 4.43 5.70 6.78 7.80 8.87 9.65 10.2

y = 0,010x
2
+ 0,532x - 0,213
y = -0,008x
2
+ 0,822x + 0,025
0
2
4
6
8
10
12
0 5 10 15 20
V
o
l
t
a
j
e
I [cm]
Caracterstica esttica
Voltaje de salida
incrementando
Voltaje de salida
decreciendo


H(I) = O
b
(I) O
s
(I)
H(I) = -0,008x
2
+ 0,822x + 0,025 - 0,01x
2
- 0,532x + 0,213 = -0,018x
2
+ 0.29x + 0.238
H(I) = -0.036x+0.29 = 0 para que sea mxima
x = 8.055
h = maxH(I) = H(8.055) = 1.406
78 . 13 h%
100 *
0 - 10.2
1.406
h%
100 *
Omin Omax
h
h%
=
=

=


5. A repeatability test on a vortex flowmeter yielded the following 35 values of frequency
corresponding to a constant flow rate of 1.4x10-2 m3 s-1: 208.6; 208.3; 208.7; 208.5;
208.8; 207.6; 208.9; 209.1; 208.2; 208.4; 208.1; 209.2; 209.6; 208.6; 208.5; 207.4;
210.2; 209.2; 208.7; 208.4; 207.7; 208.9; 208.7; 208.0; 209.0; 208.1; 209.3; 208.2;
208.6; 209.4; 207.6; 208.1; 208.8; 209.2; 209.7 Hz.
a) Using equal intervals of width 0.5 Hz, plot a histogram of probability density values.
b) Calculate the mean and standard deviation of the data.
c) Sketch a normal probability density function with the mean and standard deviation
calculated in (b) on the histogram drawn in (a).

b)

6 . 208 637 . 208 O
O
35
1
O
N
1
O
35
1 k
k
N
1 k
k
~ =
= =

= =


6 . 0 6302 . 0
) 208.637 (O
35
1
) O (O
N
1

O
2
35
1 k
k
2
N
1 k
k O
~ =
= =

= =


c)
(
(


=
2
o
2
o
2
) O (O
exp
2
1
p(O)
(


=
2
2
2(0.6302)
208.637) (O
exp
2 6302 . 0
1
p(O)
a)
Ejemplo para O = 208.8
6122 . 0 p(208.8)
2(0.6302)
208.637) (208.8
exp
2 6302 . 0
1
p(208.8)
2
2
=
(


=



0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
1 2 3 4 5 6 7
p
(
O
)
Oi
Histograma


6. A platinum resistance sensor is used to interpolate between the triple point of water (0
C), the boiling point of water (100 C) and the freezing point of zinc (419.6 C). The
corresponding resistance values are 100.0 , 138.5 and 253.7 . The algebraic form
of the interpolation equation is:
R
T
= R
0
(1 + T + T
2
)
where R
T
= resistance at T C
R
0
=resistance at 0 C
, =constants.
Find the numerical form of the interpolation equation.

100

= R
0
(1 + (0) + (0)
2
) R
0
= 100
138.5

= R
0
(1 + (100) + (100)
2
) 0.385 = 100 + 10000
253.7

= R
0
(1 + (419.6) + (419.6)
2
) 1.537 = 419.6 + 176064.16
= 3.908*10
-3

= -5.821*10
-7


Entonces, la ecuacin es:
R
T
= 100(1 + 3.908*10
-3
T + -5.821*10
-7
T
2
)

7. The following results were obtained when a pressure transducer was tested in a
laboratory under the following conditions:
I. Ambient temperature 20 C, supply voltage 10 V (standard)
II. Ambient temperature 20 C, supply voltage 12 V
III. Ambient temperature 25 C, supply voltage 10 V

Input (barg) 0 2 4 6 8 10
Output (mA)
I 4 7.2 10.4 13.6 16.8 20
II 4 8.4 12.8 17.2 21.6 28
III 6 9.2 12.4 15.6 18.8 22

(a) Determine the values of K
M
, K
I
, a and K associated with the generalised model
equation O = (K + K
M
I
M
)I + a + K
I
I
I
.
(b) Predict an output value when the input is 5 barg, V
s
=12 V and ambient temperature
is 25 C.

a) Se tiene dos efectos, el del voltaje y el de la temperatura ambiental.
- El del voltaje es entre I e II, y nos proporciona I
M
, as: I
M
= 12 10 = 2
- El de la temperatura es entre I e III, y nos proporciona I
I
, as: I
I
= 25 20 = 5

Para I, K = 1.6; a = 4
Para II, K = 2.4, y como K = K + K
M
I
M
2.4 = 1.6 + 2K
M
K
M
= 0.4
Para III, a = 6, y como a = a + K
I
I
I
6 = 4 + 5K
I
K
I
= 0.4

b) P = 5 barg, V
s
=12 V, y T = 25 C.

O = (K + K
M
I
M
)I + a + K
I
I
I
.
O = (1.6 + (0.4)(2))(5) + 4 + (0.4)(5)
O = 18 mA

8. A force sensor has an output range of 1 to 5 V corresponding to an input range of 0 to
2x10
5
N. Find the equation of the ideal straight line.

Si para Imin = 0, Omin = 1, entonces a = 1.
3
3
10 * 2 K
0 - 10 * 2
1 5
K
Imin Imax
Omin Omax
K

=

O(I) = 2*10
-3
I + 1

9. A differential pressure transmitter has an input range of 0 to 2x10
4
Pa and an output
range of 4 to 20 mA. Find the equation to the ideal straight line.

Si para Imin = 0, Omin = 4, entonces a = 4.
4
4
10 * 8 K
0 - 10 * 2
4 0 2
K
Imin Imax
Omin Omax
K

=

O(I) = 8*10
-4
I + 4

10. A non-linear pressure sensor has an input range of 0 to 10 bar and an output range of 0
to 5 V. The output voltage at 4 bar is 2.20 V. Calculate the non-linearity in volts and as
a percentage of span.

Si para Imin = 0, Omin = 0, entonces a = 0.
5 . 0 K
0 - 10
0 5
K
Imin Imax
Omin Omax
K
=

=


Oi(I) = 0.5I
Si I = 4 bar Oi(4) = 0.5*4 = 2 V
Si I = 4 bar O(4) = 2.2 V

N(I) = O(I) Oi(I)
N(4) = 2.2 2
N(4) = 0.2 V

4 nl%
100 *
0 - 5
0.2
nl%
100 *
Omin Omax
N
nl%
=
=

=


11. A non-linear temperature sensor has an input range of 0 to 400 C and an output range
of 0 to 20 mV. The output signal at 100 C is 4.5 mV. Find the non-linearity at 100 C
in millivolts and as a percentage of span.

Si para Imin = 0, Omin = 0, entonces a = 0.
05 . 0 K
0 - 400
0 20
K
Imin Imax
Omin Omax
K
=

=


Oi(I) = 0.05I

Si I = 100C Oi(100) = 0.05*100 = 5 mV
Si I = 100C O(100) = 4.5 mV

N(I) = O(I) Oi(I)
N(4) = 4.5 5
N(4) = -0.5 mV

5 . 2 nl%
100 *
0 - 20
0.5 -
nl%
100 *
Omin Omax
N
nl%
=
=

=


12. A thermocouple used between 0 and 500 C has the following inputoutput
characteristics:

Input TC 0 100 200 300 500
Output E V 0 5268 10777 16325 27388

a) Find the equation of the ideal straight line.
b) Find the non-linearity at 100 C and 300 C in V and as a percentage of f.s.d.

a) Si para Imin = 0, Omin = 0, entonces a = 0.

776 . 54 K
0 - 500
0 27388
K
Imin Imax
Omin Omax
K
=

=


Ei(T) = 54.776T

b)

Ei(T) = 54.776T

T = 100C T = 300C
Ei(100) = 54.776*100 = 5477.6 V
E(100) = 5268 V

N(T) = E(T) Ei(T)
N(100) = 5268 5477.6
N(100) = -209.6 V

765 . 0 nl%
100 *
27388
209.6 -
nl%
100 *
Omin Omax
N
nl%
=
=

=

Ei(300) = 54.776*300 = 16432.8 V
E(300) = 16325 V

N(T) = E(T) Ei(T)
N(300) = 16325 16432.8
N(300) = -107.8 V

394 . 0 nl%
100 *
27388
107.8 -
nl%
100 *
Omin Omax
N
nl%
=
=

=


13. A force sensor has an input range of 0 to 10 kN and an output range of 0 to 5 V at a
standard temperature of 20 C. At 30 C the output range is 0 to 5.5 V. Quantify this
environmental effect.

El efecto medioambiental es la temperatura, que se puede cuantificar as:
I
M
= 30C 20C = 10C

T
ambiental
= 20C T
ambiental
= 30C
5 . 0 K
0 - 10
0 5
K
Imin Imax
Omin Omax
K
=

=

55 . 0 K'
0 - 10
0 5 . 5
K'
Imin Imax
Omin Omax
K'
=

=


1 - 1 - 3
M
M
M M
C kN V 10 * 5 K
10K 0.5 0.55
I K K K'

=
+ =
+ =


Como no existe desplazamiento de la curva respecto al eje I u O, entonces:

K
I
= 0

14. A pressure transducer has an output range of 1.0 to 5.0 V at a standard temperature of
20 C, and an output range of 1.2 to 5.2 V at 30 C. Quantify this environmental effect.

El efecto interferente es la temperatura, que se puede cuantificar as:

I
I
= 30C 20C = 10C


T
ambiental
= 20C T
ambiental
= 30C
a = 1 a' = 1.2

1 -
I
I
I I
C V 0.02 K
10K 1 1.2
I K a a'
=
+ =
+ =


Como no existe cambio en el rango de salida, entonces:

K
M
= 0

15. A pressure transducer has an input range of 0 to 104 Pa and an output range of 4 to 20
mA at a standard ambient temperature of 20 C. If the ambient temperature is increased
to 30 C, the range changes to 4.2 to 20.8 mA. Find the values of the environmental
sensitivities K
I
and K
M
.

T
ambiental
= 20C T
ambiental
= 30C I
I
= 30-20 =10C I
M
= 30-20 =10C
1538 . 0 K
0 - 104
4 20
K
Imin Imax
Omin Omax
K
=

=

a = 4
1596 . 0 K'
0 - 104
4.2 8 . 20
K'
Imin Imax
Omin Omax
K'
=

=

a' = 4.2
1 -
I
I
I I
C mA 0.02 K
10K 4 2 . 4
I K a a'
=
+ =
+ =

1 - 1 - 4
M
M
M M
C Pa mA 10 * 6 K
10K 0.1538 1596 . 0
I K K K'

=
+ =
+ =


16. An analogue-to-digital converter has an input range of 0 to 5 V. Calculate the resolution
error both as a voltage and as a percentage of f.s.d. if the output digital signal is:
a) 8-bit binary
b) 16 -bit binary

8 bits 16 bits
mV 19.61 V 0196 . 0 I
1 2
5
I
1 2
5
I
R
8
R
n
R
= =

=

=

392 . 0 % Resolucion
100 *
5
0.0196
% Resolucion
100 *
Imin Imax
I
% Resolucion
R
=
=

A
=


V 76.3 V 10 * 63 . 7 I
1 2
5
I
1 2
5
I
5
R
16
R
n
R
= =

=

=


3
5
R
10 * 526 . 1 % Resolucion
100 *
5
10 * 63 . 7
% Resolucion
100 *
Imin Imax
I
% Resolucion

=
=

A
=


17. A level transducer has an output range of 0 to 10 V. For a 3 metre level, the output
voltage for a falling level is 3.05 V and for a rising level 2.95 V. Find the hysteresis as a
percentage of span.

H(I) = O(I)
bajada
O(I)
subida

H(3) = 3.05 2.95
H(3) = 0.1 V

1 H%
100 *
0 - 10
0.1
H%
100 *
Omin Omax
H
H%
=
=

=

Realice tres ejercicios de Caracterstica esttica del compendio de ejercicios.

1. Para un sensor bimetlico de hierro y nquel, cuyo rango de medicin es de 10 a 150 C,
Determine:
a. Rango de salida.
b. Alcance.
c. Sensibilidad

Las placas del sensor son de 100x10x1 mm y los valores de E y para el Fe y el Ni son
211.4 GPa, 12.1x106 K
-1
, 99.5 Gpa, y 13.3x106 K
-1
.



a) Para T = 20C (temperatura ambiente)
T * l * ) - ( l l
T * l * ) - ( l - l
T * l * ) - ( l
o Fe Ni o
o Fe Ni o
o Fe Ni
+ =
=
=

m 1000117 . 0 lmax
20) - (150 * 0.1 * ) 10 * 12.1 - 10 * 3 . 3 1 ( 1 . 0 lmax
-6 6
=
+ =



m 0999991 . 0 lmin
20) - (10 * 0.1 * ) 10 * 12.1 - 10 * 3 . 3 1 ( 1 . 0 lmin
-6 6
=
+ =



b) Asalida = Omax Omin
Asalida = 0.1000117 0.0999991
Asalida = 1.26*10
-5
m
Aentrada = Imax Imin
Aentrada = 150 10
Aentrada = 140C

c) Sensor lineal sens = K = (Omax Omin)/(Imax Imin) = (1.26*10
-5
)/140
sens = 9*10
-8

2. La placa rectangular, mostrada en seccin vertical AB, es de 4m de alto y 6m de ancho
(normal al plano del dibujo) y bloquea la salida de un tanque de agua de vaciado rpido.
La puerta est sujeta en su parte superior por un pasador en A y en la inferior por una
pieza, en B, que puede descender para permitir su apertura. Si sobre la pieza en B se
coloca un sensor piezoelctrico para medir el nivel del lquido, determine cul es la
variacin de su voltaje de salida suponiendo que el mnimo nivel de agua en el tanque
es de 25 cm y el mximo de 3.5 m. Suponga que la caracterstica esttica del cristal
piezoelctrico es el indicado en la grfica.



A = 25 cm A = 3,5 m
P = *h
P = (1000 kg/m
3
)*(9.8 m/s
2
)*(0.025 m/2)
P = 1.225 kPa = 1225 Pa

P = F/A F = P*A
F = (1225 Pa)*(0.25 m)*(6 m)
F = 1.8375 kN
y
c
= 0.25/3 = 8.33*10
-2
m

= 0 M
A

Bx*4 1.8375*(4 8.33*10
-2
) = 0
Bx = 1.8 kN
P = *h
P = (1000 kg/m
3
)*(9.8 m/s
2
)*(3.5 m/2)
P = 17.15 kPa = 17150 Pa

P = F/A F = P*A
F = (17150 Pa)*(3.5 m)*(6 m)
F = 360.15 kN
y
c
= 3.5/3 = 1.166 m

= 0 M
A

Bx*4 360.15*(4 1.166) = 0
Bx = 255.16 kN

Para Bx = 1.8 kN, el voltaje de salida es aproximadamente 0 V.
Para Bx = 255.16 kN, el voltaje de salida es aproximadamente 13.5 V.

3. En el tanque de almacenamiento de agua de la figura, calcule el valor de la presin
sobre el manmetro cuando se le imprime una aceleracin de 10 m/s2, y determine cul
debe ser el rango de entrada del sensor de presin para esta aplicacin. Suponga que el
aire sobre el lquido se encuentra a una presin de 60 kPa. El tanque tiene 1 m de altura,
1.20 m de longitud y 0.6 m de profundidad.



Pman = Paire + Pagua
Pman = 60 kPa + ah
Pman = 60000 Pa + (1000 kg/m
3
)*(10 m/s
2
)h
Pman = 60000 + 10000h

0.8 h 0 s s

Pman
min
= 60000 + 10000 (0) = 60000 Pa
Pman
max
= 60000 +10000 (0.8) = 68000 Pa

Las otras dimensiones no se toman en cuenta porque la presin del agua slo depende de la
columna de fluido.

Consulte los siguientes trminos:

- Sensores activos y pasivos
- Precisin, repetibilidad y reproducibilidad.
- Tolerancia
- Incertidumbre en la medicin.
- Deriva de cero y deriva de sensibilidad
- Respuesta frecuencial o respuesta en frecuencia
- Estabilidad.

Sensores activos y pasivos

Son aquellos que emiten energa sobre el objeto y reciben la seal reflejada por el mismo.
Los sensores activos ms comunes son los sensores de RADAR (Radio Detection And
Ranging), estos sensores trabajan en el rango de las microondas, razn por la cual es
posible trabajar sobre cualquier condicin atmosfrica. Otro tipo de sensor activo es el
LIDAR (Light Detection and Ranging), este sensor permite conocer informacin de alturas
y variaciones de altura en superficie calculando el tiempo de retorno de una seal.

Sensores Pasivos

Son aquellos que utilizan fuentes externas de energa para obtener informacin de los
objetos. La mayora de los sensores utilizados para la observacin de la tierra son pasivos;
estos sensores generalmente trabajan sobre el rango del visible dentro del espectro
electromagntico. Dentro de ellos se encuentran algunos sistemas fotogrficos, sensores
multiespectrales e hiperespectrales.

Precisin

La precisin representa la capacidad de un instrumento de dar el mismo resultado en
mediciones diferentes realizadas en las mismas condiciones. Se obtiene el error de
precisin de una serie de medidas al restar la mxima medida de la mnima medida. Es
decir, precisin es lo mismo que rango.

Tener un error de precisin alto significa variabilidad e incertidumbre en un instrumento, y
eso es lo ms indeseable en la ingeniera.

Repetibilidad

La repetibilidad se define como la proximidad de concordancia entre los resultados de
mediciones sucesivas del mismo mensurando bajo las mismas condiciones de medicin.

Las condiciones de repetibilidad incluyen: el mismo procedimiento de medicin, el mismo
observador, el mismo instrumento de medicin, utilizado bajo las mismas condiciones, el
mismo lugar, repeticin en un periodo corto de tiempo.
La repetibilidad puede ser expresada cuantitativamente en trminos de la dispersin
caracterstica de los resultados (precisin).

Reproducibilidad

La reproducibilidad determina la proximidad de concordancia entre los resultados de
mediciones sucesivas del mismo mensurando bajo condiciones de medicin que cambian.

Una declaracin vlida de reproducibilidad requiere que se especifique la condicin que
cambia. Las condiciones que cambian pueden incluir: principio de medicin, mtodo de
medicin, observador, instrumento de medicin, patrn de referencia, lugar, condiciones de
uso, tiempo.

Tolerancia

La tolerancia es una definicin propia de la metrologa industrial, que se aplica a
la fabricacin de piezas en serie. Dada una magnitud significativa y cuantificable propia de
un producto industrial (sea alguna de sus dimensiones, resistencia, peso o cualquier otra), el
margen de tolerancia es el intervalo de valores en el que debe encontrarse dicha
magnitud para que se acepte como vlida, lo que determina la aceptacin o el rechazo de
los componentes fabricados, segn sus valores queden dentro o fuera de ese intervalo.

Incertidumbre en la medicin

Es un parmetro asociado a los resultados de una medicin que caracteriza la dispersin de
los valores que podran ser atribuidos razonablemente al mensurando o magnitud sujeta a
una medicin. La incertidumbre est presente en todos los aspectos de la metrologa. Al
medir temperatura con un termmetro, al medir longitud con una regla, o al pesar una carga
en una balanza. Esto, por las circunstancias o condiciones que rodean a la medicin.




Deriva de cero

Se suelen considerar la deriva de cero a la variacin en la seal de salida para el valor cero
de la medida atribuible a cualquier causa interna. Es el cambio en la lectura del cero de un
instrumento que pueda suceder con el tiempo (figura 1).

Figura 1: Efecto de la deriva de cero.

Deriva de sensibilidad

La deriva de sensibilidad es la cantidad que vara la sensibilidad como resultado de cambios
en las condiciones ambientales (figura 2).

Figura 2: Deriva de la sensibilidad.

Respuesta frecuencial o respuesta en frecuencia

Es un parmetro que describe las frecuencias que puede recibir o emitir un dispositivo. Es
decir, la respuesta de un sistema en estado de rgimen permanente ante una entrada
sinusoidal. Cuando aplicamos a un sistema una entrada senoidal, la salida tambin ser
senoidal y de la misma frecuencia. La salida puede diferir de la entrada en amplitud y fase.

Estabilidad

Aptitud de un instrumento de medicin para mantener constante en el tiempo, sus
caractersticas metrolgicas. En el caso de que la estabilidad se considere en funcin de otra
magnitud diferente del tiempo, esta debe ser mencionada claramente.

La estabilidad puede ser cuantificada en varias formas, por ejemplo:
- Por el tiempo en el cual cambia una caracterstica metrolgica por una cantidad dada.
- El cambio de una caracterstica en un tiempo determinado.

Bibliografa

- http://www.upaep.cesat.com.mx/index.php?option=com_content&view=article&id=28:
exactitud-y-precision&catid=11:metrologia&Itemid=14
- http://www.astm.org/SNEWS/SPANISH/SPMJ09/datapoints_spmj09.html
- http://www.disfrutalasmatematicas.com/datos/exactitud-precision.html
- http://books.google.com.ec/books?id=Gj9Wyr7keDsC&pg=PR3&lpg=PR3&dq=medici
ones+y+pruebas+el%C3%A9ctricas+y+electr%C3%B3nicas&source=bl&ots=3deJBkz
2vE&sig=_u0kCekJCAqDqWDyOAVMiaA62mg&hl=es&ei=AdSKTsrMHceCtgeck-
WvAw&sa=X&oi=book_result&ct=result&resnum=4&ved=0CDQQ6AEwAw#v=onep
age&q&f=false