Sei sulla pagina 1di 3

HVAC DESIGN ROOM BOOK COVER SHEET

CLIENT : TEVA API INDIA LTD.

PROJECT

GWALIOR PROJECT

LOCATION

MALANPUR,GWALIOR M.P.

TITLE

HVAC DESIGN ROOM BOOK (MINI API PLANT)

DOC. NO.

44-LK4800/H.01/0001/A4

A REV

Issued for Approval ISSUE

11.04.2008

PT PREP

TPS CHKD

S.Stt. APPRD Remarks

DATE

44LK4800 : GWALIOR PROJECT

HVAC DESIGN ROOM BOOK - MINI PLANT

Type of Filters Return Air Bag in Bag out Pre Filter Microvee (F-7) in AHU Equipment Load (kW) / Heat Dissipation (kW) Relative humidity (%) NMT Dust extraction Y / N Prefilter (G-4) in AHU Air changes (AC/ hr.) minimum HEPA Filter (H-13) at Terminal Class of Cleanliness Make up air change (Ac/hr.) [min.] Recirculation (RC) / Once Through (OT) Lighting Lux Level Supply Air Location Return Air Location Preliminary data

Occupancy (Nos.)

Machine Exhaust 3 (m /hr.)

Temperature (C)

Clear Height (mt)

1 2 3 4 6 10 5 7 8 9 11 12

AHU - 1 AHU - 1 AHU - 1 AHU - 1 AHU - 1 AHU - 1 AHU - 1 AHU - 1 AHU - 1 AHU - 1 AHU - 1 AHU - 1

GF GF GF GF GF GF GF GF GF GF GF GF

008 009 010 011 013 018 012 021 016 017 015 022

Gowning Degowning Air Lock Main Corridor Quarantine Wash clean FG Packing Blender Room RVD Room FBD Room Milling Room Micronizer room

5.2 4.8 7.5 31.6 9.8 7.5 9.3 13.2 16.3 14.7 11.0 11.0

3 3 3 3 3 3 3 3 3 3 3 3

D D D D D D D D D D D D

232 232 232 232 232 232 232 232 232 232 232 232

60 60 60 60 60 60 60 60 60 60 60 60

25 25 25 25 25 25 25 25 25 25 25 25

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

2 2 2 4 2 2 4 2 2 2 2 2

1 5 3.73 7.45 1.5 5

300 300 300 300 300 300 300 300 300 300 300 300

200 300 300 300 300 300

OT OT OT OT OT OT OT OT OT OT OT OT

Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes

Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes

Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes

Return Air Pre Filter(EU-4)

Size (Sq mt)

Room Description

Room No.

System

Sr. No.

Floors

Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes

No No No No No No

Ceiling Ceiling Ceiling Ceiling Ceiling Ceiling Ceiling

Bottom Bottom Bottom Bottom Bottom Bottom Bottom Bottom Bottom Bottom Bottom Bottom

P P P P P P P P P P P P

In common return duct

Ceiling Ceiling Ceiling Ceiling Ceiling

13 14 15

AHU - 2 AHU - 2 AHU - 2

GF GF FF

019 023 109

Centrifuge Room ANFD Room Crystalizer Room

45.2 14.6 50.4

3 3 3

D D D

232 232 232

60 60 60

25 25 25

1.5 1.5 1.5

2 2 2

5.5 8 3.7

300 300 300

OT OT OT

Yes Yes Yes

Yes Yes Yes

Yes Yes Yes

Yes Yes Yes

No No No

Ceiling Ceiling Ceiling

Bottom Bottom Bottom

P P P

16 17 18 19 20 21

VU & EU -1 VU & EU -1 VU & EU -1 VU & EU -1 VU & EU -1 VU & EU -1

GF GF GF GF GF GF

001 002 003 006 007 024

ENT Lobby Change/ Locker Room Corridor Reactor Area Washing Room Lobby

24.04 18.1 25.1 139.7 7.8 19.0

3 3 3 4.9 4.9 3

UC UC UC UC UC UC

20 20 20 20 20 20

4 2 4 3 2 3

200 300 200 300 300 200

OT OT OT OT OT OT

Yes Yes Yes Yes Yes Yes

Yes Yes Yes Yes Yes Yes

No No No No No No

No No No No No No

No No No No No No

Ceiling Ceiling Ceiling Ceiling Ceiling Ceiling

Ceiling Ceiling Ceiling Ceiling Ceiling Ceiling

P P P P P P

\\vboxsrv\conversion_tmp\scratch_5\153931965.xls.ms_office

2 of 3

44LK4800 : GWALIOR PROJECT

HVAC DESIGN ROOM BOOK - MINI PLANT

Type of Filters Return Air Bag in Bag out Pre Filter Microvee (F-7) in AHU Equipment Load (kW) / Heat Dissipation (kW) Relative humidity (%) NMT Dust extraction Y / N Prefilter (G-4) in AHU Air changes (AC/ hr.) minimum HEPA Filter (H-13) at Terminal Class of Cleanliness Make up air change (Ac/hr.) [min.] Recirculation (RC) / Once Through (OT) Lighting Lux Level Supply Air Location Return Air Location Preliminary data

Occupancy (Nos.)

Machine Exhaust 3 (m /hr.)

Temperature (C)

Clear Height (mt)

22 23 24 25 26 27

VU & EU -1 VU & EU -1 VU & EU -1 VU & EU -1 VU & EU -1 VU & EU -1

FF FF FF FF FF FF

111 106 104 101 103 110

Lobby Carbon Slurry Prep. Reactor Area Corridore IPQC RM Pay Storage

15.02

3 4.9 4.9 3 3 4.9

UC UC UC UC UC UC

20 20 20 20 20 20

3 1 4 3 2 2

0.75

200 300

OT OT OT OT OT OT

Yes Yes Yes Yes Yes Yes

Yes Yes Yes Yes Yes Yes

No No No No No No

Return Air Pre Filter(EU-4)

Size (Sq mt)

Room Description

Room No.

System

Sr. No.

Floors

No No No No No No

No No No No No No

Ceiling Ceiling Ceiling Ceiling Ceiling Ceiling

Ceiling Ceiling Ceiling Ceiling Ceiling Ceiling

P P P P P P

10.9 151.6 24.8 13.0 14.2

29.52 300 200 300 200

28

Exhaust Fan

GF

005

MCC Room

35.0

4.9

0.5

200

No

No

No

No

No

Wall mounted

29 30

Split AC Split AC

FF FF

102

Office

16.7 6.7

3 3

0.5 0.5

4 2

1 3.5

300 200

No No

No No

No No

No No

No No

Wall mounted Wall mounted

P P

102A UPS Room

NOTE :1.GF - Ground Floor, FF - First Floor 2. AHU - Air Handline Unit ,VU & EU - Ventilation & Exhaust Unit 3. UC - Uncontrolled Area, 4. P=Preliminary , F=Fixed 5. We have consider occupany & Dust exhaust CFM as on our experience basis.

\\vboxsrv\conversion_tmp\scratch_5\153931965.xls.ms_office

3 of 3

Potrebbero piacerti anche