HV/MV CABLE DATA SHEET Part 1 (Data by Purchaser) 1. Site Conditions Ambient temp (Design) 50 C 2. A. System Parameters Voltage Nominal System Voltage 415 V 3.3 kV(E) 3.3 kV(UE) 6.6 kV(E) 6.6 kV(UE) 11 kV(E) 11 kV(UE) 22 kV 33 kV E - Earthed System B. C. 3. Frequency : Highest System Voltage 500 V 3.6 kV 3.6 kV 7.2 kV 7.2 kV 12 kV 12 kV 24 kV 36 kV Voltage grade 650 V/ 1100 V 1.9 kV/ 3.3 kV 3.3 kV/ 3.3 kV 3.8 kV/ 6.6 kV 6.6 kV/ 6.6 kV or 6.35 kV / 11 kV 6.35 kV/ 11 kV 11 kV/ 11 kV 12.7 kV/ 22 kV 19 kV/ 33 kV UE - Un-Earthed System 50 Hz 3% 25 kA/ 0.2 sec Min 3 C

Single line to ground fault current / duration: (Applicable to high voltage cables) Conductor material i) ii) iii) HV Power Cables MV Power Cables Control Cables Aluminum

Copper

Aluminum (25 mm & above) and Copper (upto 16 mm) Copper

A Rev. No

13.8.04 Date

Issued with MR Purpose

NMS Prepared by

RM Checked by

RPG Approved by

Format No. EIL 1641-1924 Rev. 1

Copyright EIL All rights reserved

Cable datasheet (Calcination package)

DOCUMENT No. 0287-10-XZ-DS-6519 Rev. A


Page 2 of 3

4.

Specific Requirements

4.1
4.2

Cables to be flame retardant

Yes

No

Type of sheath and armour bonding system adopted for single core cables Solidly bonded (earthed at both ends) Single point bonded

4.3

Whether installation falls under the jurisdiction of Directorate General of Mines Safety Yes No : :Heat Shrinkable/Push On*/ Tapex* : 500M

4.4 4.5 4.6

Make of accessories (if applicable) Type of cable accessories (if applicable) Drum length required (Indicate whether standard drum lengths as per specification or specific drum lengths are required)

Note: NA Not Applicable

Place a tick mark ( ) against box.

Notes 1. In case the installation as per cl. 4.3 above falls under the jurisdiction of Directorate General of Mines Safety, only those cable manufacturers may quote, who have a valid DGMS approval. Copy of DGMS approval certificates to be furnished along with the offer.

Format No. EIL 1641-1924 Rev. 1

Copyright EIL All rights reserved

Cable datasheet (Calcination package)

DOCUMENT No. 0287-10-XZ-DS-6519 Rev. A


Page 3 of 3

CABLE DATA SHEET

Part 2 (Data by Vendor)


1. 1.1 1.2 2. 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 2.12 2.13 GENERAL Name of manufacturer Cable type / code : :

Technical particulars (To be furnished separately for each size) Conductor material :

Material/ thickness of semi-conducting conductor screen (for HV cables) : Thickness of insulation :

Material/ thickness of semi-conducting insulation screen (for HV cables) : Thickness of inner sheath Calculated diameter of cable under armour (as per IS:10462) Material/ Type and size of armour Nominal diameter of cable under outer sheath Calculated diameter of cable under outer sheath Thickness of outer sheath Nominal outer diameter of cable Tolerance on outer diameter Type of compound for conductor insulation, inner sheath and outer sheath Max. Drum length of cable : : : : : : : :

: :