CO - Star Energy Recovery Unit > Technical Brochure

CFD Optimised Compact Design Plate Heat Exchanger Efficiency up to 70% Plug & Play Controls Indoor or Outdoor Installation Side-by-side Format Up to 1.0 m3/s (3600 m3/h) Full BMS Communication EC Motors = Low SFP Values: 0.17 w/l/s Very Low Noise Levels: 30 dBA Breakout*

Integrated Exchanger

Specification
Application
High performance self regulating ventilation and energy recovery for office and industrial applications Thermal efficiency up to 70 % (EN308), in compliance with ErP 2009/125/EC directive, using a Eurovent certified core. Air filtration and temperature control included. On demand ventilation is available via PIR or CO2 sensors Compact, plug n play units complete with integrated BMS communications (MODBUS) and touch screen HMI

Range
Available in 6 models, the e3co Star range covers flow rates from 300 to 3600 m3/h (0.08 to 1.00m3/s). e3co Star range is available in 3 variants: e3ssential ERU with plate heat exchanger and filters fitted e3nhanced ERU with plate heat exchanger, filters and post heater fitted (water or electric) e3lite ERU with plate heat exchanger, filters and post heater plus pre heater (electric)

Description
- Self-supporting casing made of galvanised steel; - Reduced height allows for easy installation into ceiling voids; - Side access for inspection and maintenance; - Differential pressure switches mounted on board (for plug-n-play solution); - Condensation drainage system, with side mounted drain point to minimise height Double Skin Sandwich Panels - Steel panels thickness is 0.9mm/0.7mm (inner/ outer skins) - Internal rockwool insulation thickness is 25mm. Density is 60Kg/m3 - giving a low noise solution, whilst optimising product weight

Available Configurations
Unit format: Side-by-side with internal by-pass no heater; Integral post heater option; water or electric Pre-heater option (fitted externally) 100% By-Pass via motorised Damper The plate heat exchanger is complete with a bypass damper which is fitted with an actuator, giving a 100% by-pass capability - control is via our integrated e3co Star control package.

Accessories available on request


Accessories for frost protection - Pre-Heater ESFP round electric heater with electronic regulation for duct mounting Accessories for post-heating: HWLG temperate water coil (45/35 C) available on request Accessories for air filtration: - F7 & F9 Optional filter (media) is available on request Protective accessories: ESWC Weather cowl c/w bird guard ESWR External weather protective roof

Exchanger
- Cross-flow aluminium heat exchanger with a thermal efficiency of up to 70%, has proven performance as it is Eurovent certified Filters - G4 class for exhaust air and fresh air, but higher filter grades are available on request Range - 6 models from 300m3/h (0.08 m3/s) up to 3600 m3/h (1.0 m3/s)

A shining example of excellence


1

Specification
Fans and Motors
Complete with direct driven centrifugal fans; single or double inlet with forward curved impeller blades Direct driven via EC (Electronically Commutated) motors with high-performance, thermal protection and built in speed control. EC technology is an ecological solution guaranteeing low energy consumption and better management and control of the operating point (air flows can be controlled from 30 to 100 %)

Controls
User friendly interface - colour touch screen Fast and easy commissioning - saving time on site Pre-configured controls. Variable Air Volume, Constant Air Volume and Constant Pressure options Plug and play solution Full BMS capability as standard, using an open table version of the MODBUS protocol - easy to integrate controls

Heat Exchanger
Cross-flow heat exchanger core with aluminium plates is EUROVENT certified Efficiency up to than 70 % (EN 308) under typical operating conditions as stated below: Fresh air : -5C/90 % RH Return air 20C/50 % RH Automatic defrost function is included to protect the heat exchanger core from the risk of freezing. An optional electric pre-heater (frost heater) is also available as part of frost protection strategy

Integrated Exchanger

Filters
Filters are included to provide protection to other components (ie, exchanger/fans) Media is mounted within runners for easy fitting/removal The e3co Star unit is equipped with G4 grade filter media fitted to the fresh air intake and return air intake. F7 & F9 grade filter media can be fitted if desired and are available as optional accessories

Benefits and Features


Integrated ventilation control can be accessed via our HMI (display panel), which uses touch screen technology, BMS communication uses a MODBUS protocol is via an RS485 port. Alternatively, the built-in Ethernet port can be used. 100 % bypass via integral damper is fitted with servomotors controlled automatically by our built-in controls, which can provide FREE-COOLING and NIGHT-COOLING functions Wide choice of airflow control scenarios are available to optimise energy consumption Temperature probes are included to monitor supply air, exhaust air and external temperature An integrated de-icing sensor is included to protect the hot water coil (where heater is fitted) Electric heaters are complete with a manual reset safety thermostat to protect the electric heater elements Programmable scheduler function is included to allow users to customise their own operating schedule Weekly, date period or single date schedule options are available. External timer control is also available Air pressure switches monitor filters and provide a dirty filter alarm function Pressure switches are used within the control of air flows for each fan, and provide fan fail alarms, both locally (on the HMI) and to the BMS

Installation
Side-by-Side format - designed to be compact Low profile - suitable for mounting in ceiling voids Indoor or outdoor (when weather roof and weather cowls accessories are fitted)

Applications
e3co Stare3co Star

EDUCATION High occupancy levels during teaching periods require energy-efficient and controllable demand-based management of air quality and temperature. The comfort, health and alertness of staff and pupils is ensured during the learning process, but operating costs can be minimised when these facilities are unoccupied.

OFFICES Flkt Woods offer a high performance product range covering all key elements of the overall ventilation system. Our products are designed to secure the best overall performance of the system as a whole, considering parameters such as health and air quality, energy efficiency, noise, fire safety and ease of installation.

GYMNASIUM/ INDOOR SPORTS Differing types of activity and occupancy mean a broad spectrum of functional requirements to ensure efficient removal of used air and the introduction of fresh supplies. Systems need to contain and control the periodic build up of high humidity levels and temperature.

RETAIL/ SHOPPING AREAS With high activity levels during the working week and weekends, its important to make sure that all areas of ventilation are maintained and Flkt Woods has the systems to achieve all requirements.

INDUSTRY Flkt Woods technology is used widely in industrial processing plants and factories for ventilation of work spaces, as vital components in high tech manufacturing facilities, and for maintaining delicate environments within high tolerance levels in petrochemical and pharmaceutical plants.

APARTMENTS The purpose of ventilation is to provide clean good quality air by removing the stale, polluted air from our homes. The main task is of course to ensure that the indoor air is healthy and safe to breathe. Ventilation today is also about energy and saving energy costs by adding heat recovery to the ventilation system.

HEALTHCARE For a hospital to operate at its maximum potential, it has to have all systems working at the optimum. This not only applies to staff, communications and life support systems, but also to pipework, cleaning and ventilation systems.

A shining example of excellence

Legislation
Being a global manufacturer and supplier makes meeting legislation easier for Flkt Woods. It means that Flkt Woods must produce solutions at standards that equal the most stringent legislation and guidelines around. Only by doing this can we ensure that we meet relevant standards within every market.

LEGISLATION In Europe, all countries now have to design their new buildings to meet energy targets that are set out in the Energy Performance in Buildings Directive (EPBD). All Flkt Woods Energy Performance of Buildings Directive solutions are designed to enable full compliance with this and other directives regarding ventilation and air conditioning.

Environmental Assessment Schemes


It is now very common for new build projects to be designed to achieve environmental standards such as those set out in LEED and BREEAM programs. Flkt Woods, with its market leading knowledge and products in energy recovery, has helped many projects achieve the very highest levels in both of these schemes.

Energy Performance of Buildings Directive (EPBD)


The Commission of the European Union has recently proposed a revision of the EPBD (Energy Performance in Buildings Directive, 2002/91/EC). The objective is to further strengthen the effectiveness and impact of the existing Directive. The background to this initiative is to optimise energy usage. It was noted that even in member states where the existing Directive has been successfully implemented, the Commission still identified an untapped potential for improvements that could further reduce the energy consumption and CO2 emissions from buildings.

Building Regulations - Part L for New (A) and Existing Buildings (B)
Building Regulations Part L and F outline the need for a healthier working/indoor environment, with the aim of decreasing CO2 emissions. The eco design of our e3co Star range will allow specifiers to create designs which incorporate the necessary energy usage reductions, whilst still providing precise control of mechanical ventilation.

European Energy Related Products Directive (ErP)


Directive 2009/125/EC was introduced by the European Parliament in 2009 with the aim to set requirements for energy-related products being placed on the European Market. The intention is to contribute to sustainable development by increasing the energy efficiency of those products having significant environmental impact. As a result, a series of implementing measures have been introduced and Regulation (EU) No 327/2011 applies to fans driven by electric motors with an electrical input power of between 125 W and 500 kW. The fans installed in the e3co Star product benefit from EC technology and exceed the requirements of this regulation. Further measures relating more generally to domestic ventilation and non-domestic ventilation are yet to be implemented. This will also have an impact on heat recovery units. The overall performance of the e3co Star product has been developed with this in mind. In addition, at the heart of the product, its heat exchanger is Eurovent certified, which provides reassurance that it will deliver performance that has been independently confirmed.

Performance - Composite Curves

Size 1 Fan Data


Max Installed Power: Watts input Nominal Running speed: rpm Fan Motor FLC: amps (note 1) Fan Motor IP rating Motor Insulation class 175 x2 2150 1.3 x 2 44 B

Size 2

Size 3

Size 4

Size 5

Size 6

171 x2 1740 1.3 x 2 44 B

465 x2 1640 3.0 x 2 54 B

450 x2 1085 2.8 x 2 54 B

750 x2 1030 3.4 x 2 54 B

1000 x2 880 1.7 x 2 54 B

Unit Data
Max Running temperature: C Min Running temperature: C (note 2) Electrical Supply: V/Ph/Hz (note 3) Electrical Supply: V/Ph/Hz (note 4) +40 -10 230/1/50 230/1/50 +40 -10 230/1/50 415/3/50 +40 -10 230/1/50 415/3/50 +40 -10 230/1/50 415/3/50 +40 -10 230/1/50 415/3/50 +40 -10 415/3/50 415/3/50

Thermal Recovery Performance


Recovered Thermal Power: kW (note 5) Air off temperature: C Condensate rate: l/h 2.5 9.9 0.5 3.6 10.0 0.8 6.1 8.2 0.9 7.1 8.3 1.1 11.0 9.3 2.1 16.0 9.4 3.1

Filters
Supply / Exhaust Air Filter class (note 6) G4 G4 G4 G4 G4 G4

Note 1: Note 2: Note 3: Note 4: Note 5: Note 6:

Starting currents are the same as full load currents as EC motors have a soft start function Based on Pre-Heater being fitted, the minimum inlet temperature is -5C Electrical supply when no electric heater is fitted ie, e3ssential variant Electrical supply when integral electric heater is fitted ie, e3nhanced and e3lite variants Data relates to nominal airflow rates, which are a mid-curve duty point. Thermal recovery data is based on the following conditions: External air: -5C @ 90%RH ; Return air: 20C @ 50%RH ; Nominal airflow as defined above F7 and F9 grade filter media is available as an optional extra. The extra pressure drop, when F7 grade filter media is fitted is approx 40 Pa

Technical Details
ESFP: Electric Pre-Heater Data (Frost Protection)
Size 1
Nominal Power: kW (note 7) Max Rated Power: kW Supply Voltage: V Supply Phase Ph Proportional Control Pre-Heater Absorbed Current: amps Max Absorbed Current: amps (note 8) Duct Connection Diameter Heater off temperature: C (note 9) 0.85 0.90 230 1 Yes 3.9 6.5 200 -5

Size 2
1.24 1.50 230 1 Yes 6.52 9.12 250 -5

Size 3
2.1 2.1 230 1 Yes 9.13 15.13 315 -5

Size 4
2.7 3.0 400 3 Yes 7.5 13.1 315 -5

Size 5
3.9 5.0 400 3 Yes 12.5 19.3 400 -5

Size 6
5.6 6.0 400 3 Yes 8.64 12.04 500 -5

Note 7: Note 8: Note 9:

Nominal Power based on nominal airflow per unit Stated Unit Max current rating includes Fans FLC and Electric Pre-Heater rating Heater off temperature is based on air entering the pre-heater at -10C at nominal airflow Air pressure loss for Pre-Heater is between 2 and 5 Pa

ESHE: Electric Post-Heater Data


Size 1
Nominal Power: kW Max Rated Power: kW Supply Voltage: V Supply Phase Ph Proportional Control Max Unit Absorbed Current: amps (note 10) Heater on temperature: C (note 11) Heater off temperature: C (note 12) 2.7 2.7 230 1 Yes 14.3 9.9 25

Size 2
3.9 4.3 415 3 Yes 8.8 10.0 24.1

Size 3
7.0 7.0 415 3 Yes 16.1 8.2 20.9

Size 4
8.7 9.5 415 3 Yes 19.3 8.3 23.2

Size 5
12.6 13.6 415 3 Yes 26.4 9.3 22.7

Size 6
17.9 19.0 415 3 Yes 30.8 9.4 23.3

Note 10: Stated Unit Max current rating includes Fans FLC and Electric Post-Heater rating, but excludes the Electric Pre-Heater rating Note 11: Heater on temperature is based air off temperature of Plate Heat Exchanger at nominal airflow Note 12: Heater off temperatures are stated at nominal airflow Air pressure loss for Pre-Heater is between 2 and 5 Pa

HWLP: Hot Water Coil (Post Heater) 82C / 71C


Size 1
Number of Rows Nominal Power: kW Heater off temperature: C Air Side Pressure loss : Pa Water Side Pressure loss : KPa Water Side Flow Rate : l/s Pipe Conn. sizes: DN / inches Proportional Control 1 2.8 23.7 21 1.0 0.06 15 / Yes

Size 2
1 4.7 26.2 19 5.0 0.10 15 / Yes

Size 3
1 8.1 24.5 29 15.0 0.18 15 / Yes

Size 4
1 9.6 24.9 25 4.0 0.21 25 / 1 Yes

Size 5
1 14.1 25.1 29 9.0 0.31 25 / 1 Yes

Size 6
1 22.8 27.4 41 5.0 0.50 25 / 1 Yes

Heater off temperature is based on following conditions: nominal air on value of 7C ; Nominal airflow Values refer to the following conditions: Water Flow and Return temperatures of 82/71C; Nominal Airflow Refer to our sales office (see back page for contact numbers) for other design options such as alternative flow and return temperatures or optional chilled water coil or heat pump system.

HWLG: Hot Water Coil (Post Heater) 45C / 35C


Size 1
Number of Rows Nominal Power: kW Heater off temperature: C Air Side Pressure loss : Pa Water Side Pressure loss : KPa Water Side Flow Rate : l/s Pipe Conn. sizes: DN / inches Proportional Control 2 2.7 22.8 41 3.0 0.06 15 / Yes

Size 2
2 4.3 24.8 37 10.0 0.10 15 / Yes

Size 3
2 8.1 24.6 64 5.0 0.19 25 / 1 Yes

Size 4
2 8.9 23.7 48 8.0 0.21 25 / 1 Yes

Size 5
2 14.3 25.3 65 9.0 0.34 25 / 1 Yes

Size 6
2 17.4 22.6 71 15.0 0.42 25 / 1 Yes

Heater off temperature is based on following conditions: nominal air on value of 7C ; Nominal airflow Values refer to the following conditions: Water Flow and Return temperatures of 45/35C; Nominal airflow

Electro Valve Kits


Size 1
Valve Model : 1 row (82C / 71C) Kvs Value (m3/h) Pipe Conn. sizes: DN Valve Model : 2 row (45C / 35C) Kvs Value (m3/h) Pipe Conn. sizes: DN ESMPVA-025 0.25 15 ESMPVA-025 0.25 15

Size 2
ESMPVA-040 0.4 15 ESMPVA-040 0.4 15

Size 3
ESMPVA-100 1 15 ESMPVA-100 1 25

Size 4
ESMPVA-100 1 25 ESMPVA-100 1 25

Size 5
ESMPVA-160 1.6 25 ESMPVA-160 1.6 25

Size 6
ESMPVA-250 2.5 25 ESMPVA-160 1.6 25

Actuator Motors used within all Electro Valve Kits are suitable for an electrical supply AC 24 V. Motors are designed to be controlled via a DC 010 V signal to provide proportional control. All actuator motors include an Actuator Return Spring

Sound Levels & Configurations


Duty Speed Options, Noise Levels and SFP / Power Saving Data
Model Speeds Size 1
Boost 75% 60% 45% Trickle Max 75% 60% 45% Min Max 75% 60% 45% Min Max 75% 60% 45% Min Max 75% 60% 45% Min Max 75% 60% 45% Min Max 75% 60% 45% Min 42 42 36 32 28 39 35 29 28 27 42 43 37 31 25 44 41 39 31 29 45 41 38 28 31 55 52 48 40 32 54 53 46 37 33 48 43 38 31 24 47 43 38 29 33 45 40 35 27 25 47 42 43 30 28 52 46 41 32 25 50 48 42 33 29 50 44 38 30 22 40 36 30 27 28 40 35 30 23 22 40 34 34 25 23 42 36 31 25 <20 46 43 38 34 29 43 37 31 24 <20 36 34 29 26 <20 43 39 36 32 20 42 39 36 32 23 48 43 39 33 25 42 41 37 31 24 41 36 31 23 <20 42 41 35 29 <20 46 42 37 31 <20 49 44 40 33 22 48 43 38 33 21 43 40 33 28 <20 43 37 31 23 <20 40 38 31 24 <20 43 38 34 25 <20 43 36 31 24 <20 45 39 34 <20 <20 37 34 28 <20 <20 37 30 23 <20 <20 34 32 24 <20 <20 34 28 23 <20 <20 32 25 <20 <20 <20 34 27 21 <20 <20 20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 57 55 49 41 37 54 48 43 35 30 50 48 42 36 35 52 47 44 37 31 53 48 46 38 34 58 54 50 42 34 29 27 21 <20 <20 31 25 <20 <20 <20 30 28 22 <20 <20 25 21 <20 <20 <20 29 25 25 <20 <20 33 28 23 21 <20 0.88 0.79 0.55 0.37 0.27 0.88 0.58 0.40 0.25 0.17 0.70 0.62 0.43 0.28 0.20 0.72 0.50 0.34 0.22 0.18 0.68 0.50 0.35 0.25 0.18 0.75 0.52 0.36 0.25 0.18 58% 78% 91% 97% 58% 78% 91% 97% 58% 78% 91% 97% 58% 78% 91% 97% 58% 78% 91% 97% 58% 78% 91% 97% 199 270 313 335 198 268 311 333 538 729 845 905 520 706 818 876 867 1176 1363 1460 1156 1568 1818 1946

% of Duty

Inlet Sound Power Levels (LwA) 63 Hz 125 Hz 250 Hz 500 Hz 1 KHz 2 KHz 4 KHz 8 KHz Total LwA

*Breakout dB(A) @ 3m

SFP

Power Saving %

Power Saving (Watts)

Size 2
Boost 75% 60% 45% Trickle

Size 3
Boost 75% 60% 45% Trickle

Size 4
Boost 75% 60% 45% Trickle

Size 5
Boost 75% 60% 45% Trickle

Size 6
Boost 75% 60% 45% Trickle

SFP values stated are per fan * 30 dBA is the max sound level for units running at 75% of full running speed

Configurations
Right Hand (SS-R) (Access Side) Left Hand (SS-L)

RA

FA

SA

EA

SA

EA

RA (Access Side)

FA

FA = Fresh Air
7

EA = Exhaust Air

RA = Return Air

SA = Supply Air

Drawing & Dimensions


J 12

21 DN 15

E D M N

33

58

32 50 S

20

SIZE 1 2

A 170 238

B 310 425

C 180 215

D 677 728

E 140 200

F 32 42

H 380 400

J 1128 928

K 550 800

L 1100 1200

M 684 734

N 855 905

P 68 68

Q 69 103

S 200 250

W 650 900

Weight Kg 67 92

12

G L

G F

DN 25

21

45

58

E D M N

50 138 S

20

SIZE 3 4 5 6

A 295 289 313 358

B 540 522 574 659

C 230 285 450 425

D 807 960 1250 1250

E 227 215 244 244

F 62 62 62 62

G 463 562 711 711

H 430 570 750 750

J 1428 1682 2122 2122

K 1030 993 1093 1263

L 1400 1650 2090 2090

M 834 980 1270 1270

N 887 1069 1359 1359

P 83 114 124 124

Q 120 120 200 200

S 315 400 400 500

W 1130 1100 1200 1375

Weight Kg 121 172 262 300

All dimensions shown in mm

Individual Performance Curves


e 3co Star - Size 1
350

300

Boost Mode

250 Static Pressure (Pa)

75%

200

150

60%

100 45% 50 Trickle Mode 0 0 0.02 0.04 0.06 0.08 Volume Flow (m3 /s) 0.1 0.12 0.14 0.16

e 3co Star - Size 2


400

350

Boost Mode

300 Static Pressure (Pa)

250

200

75%

150 60% 100 45% Trickle Mode 0 0 0.05 0.1 0.15 Volume Flow (m3 /s) 0.2 0.25 0.3

50

Individual Performance Curves


e 3co Star - Size 3
400

350 Boost Mode

300 Static Pressure (Pa) 75%

250

200 60%

150

100 45% 50 Trickle Mode 0 0 0.05 0.1 0.15 0.2 0.25 0.3 Volume Flow (m3 /s) 0.35 0.4 0.45 0.5

e 3co Star - Size 4


350

300

Boost Mode

250 Static Pressure (Pa)

200

75%

150 60% 100 45% 50 Trickle Mode 0 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 Volume Flow (m3 /s)

10

Individual Performance Curves


e 3co Star - Size 5
350 Boost Mode 300

250 Static Pressure (Pa) 75% 200

150

60%

100 45% 50 Trickle Mode 0 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 Volume Flow (m3 /s)

e 3co Star - Size 6


400 Boost Mode 350

300 Static Pressure (Pa)

250

75%

200 60%

150

100 45% 50 Trickle Mode

0 0 0.2 0.4 0.6 Volume Flow (m3 /s) 0.8 1 1.2

11

Control Solutions
The e3co Star unit has a factory-pre-set controller as standard, which can be used to configure how air flows can be modulated:

Pa HS air flow LS air flow

LS constant air flow Pa HS constant air flow

Air flow

Air flow

VAV

Variable Air Volume - Trickle & Boost Strategy 2 Air flow rates - Low Speed/High Speed

CAV

Constant Air Volume 2 Constant Air flow Options

Pa

HS air flow

Pa Constant pressure

LS air flow

VAV AQ

Air flow

Variable Air Volume plus CO2 sensor Proportional air flow control via CO2 sensor

COP

Air flow

Constant Pressure Control

HMI Screen Overview


Alarm indication, building parameters, operation mode, temperature, on demand set points and alarm status can all be viewed and set via our touch screen HMI

12

Accessories
Filter media upgrade

The Filter Media grade fitted to the supply air side, can be upgraded from G4 to F7, for enhanced protection.

Alternatively, The Filter Media grade for the supply air side can be upgraded from G4 to F9, for ultimate protection.

e3co-Star units can have a number of accessories fitted:

ESDC Connectors

ESMPVA 3-Port Valve + Actuator

BDER Cylindrical Duct Silencers

ESMF (set of 4) Mounting feet

HMI extension cables 10m ESC10 25m ESC25

ESFP Optional Pre-Heater

ESPIR PIR Occupancy Sensor

BDEP-46-024 Inlet damper and actuator

e3co-Star units can be installed outside when a weather proof kit is fitted. ESWR: Weather Roof

ESWC Weather Cowl / Bird Guard


Fit to inlet and discharge spigots

13

Accessories and Product Codes


BDER Silencer Information
Dia A (mm) 200 200 200 250 250 250 315 315 315 400 400 500 500 Length (mm) 600 900 1200 600 900 1200 600 900 1200 900 1200 900 1200 Dia B mm 300 300 300 355 355 355 415 415 415 500 500 630 630 Code BDER-30-020-060 BDER-30-020-090 BDER-30-020-120 BDER-30-025-060 BDER-30-025-090 BDER-30-025-120 BDER-30-031-060 BDER-30-031-090 BDER-30-031-120 BDER-30-040-090 BDER-30-040-120 BDER-30-050-090 BDER-30-050-120 Attenuation, dB 63Hz -1 -2 -3 0 -2 -2 0 -1 -2 -1 -2 -1 -1 125Hz -3 -3 -5 -2 -2 -4 -2 -2 -4 -2 -4 -1 -3 250Hz -7 -9 -14 -7 -8 -11 -7 -7 -10 -6 -8 -5 -7 500Hz -14 -24 -30 -12 -19 -25 -10 -16 -22 -13 -18 -11 -16 1KHz -20 -30 -37 -18 -25 -30 -15 -22 -28 -19 -25 -14 -20 2KHz -26 -36 -46 -23 -32 -39 -20 -24 -30 -16 -20 -12 -15 4KHz -15 -20 -25 -10 -12 -14 -7 -10 -12 -8 -10 -9 -10 8KHz -7 -9 -12 -5 -6 -10 -4 -6 -9 -6 -8 -6 -7

Dia B Dia A

Length

Product Coding Guide 1


e co-Star
3

2
1

3
SS-R
3

4
e ssential e3nhanced HW/HE e3lite HW/HE

5
Control option

1 - Thermal Efficiency unit (up to 70%) - complete with automatic control and Cross Flow Plate Heat Exchanger 2 - Unit Model Code Examples: 1 6 Unit size = 1 (0.12 m3/s) Unit size = 6 (0.90 m3/s) e3co-Star 1 e3co-Star 6

3 - Unit Configuration Options: SS-R SS-L 4 - Unit Version Options:

Side-by-Side format (access and controls on right side) Side-by-Side format (access and controls on left side)

Unit with NO coils fitted e3ssential e3nhanced HW Hot water coil (POST Heater) plus appropriate controls fitted e3nhanced HE E lectric heater (POST Heater) plus appropriate controls fitted e3lite HW Unit with Electric PRE-Heater and hot water POST Heater plus controls e3lite HE Unit with Electric PRE-Heater and Electric POST heater plus controls 5 - Controls: VAV VAV AQ CAV COP Variable Air Volume - Trickle and Boost Variable Air Volume - + Air Quality (CO2) Sensor Constant Air Volume Constant Pressure

All motors are EC type


14

The Flkt Woods Group is divided into three businesses: Global Infrastructure and Industry (GII) A leader for Air Movement using fans to improve performance of equipment and industrial processes Air Climate Solutions (ACS) A worldwide HVAC leader recognized by our customers as a provider of superior Air Climate Solutions combining Indoor Air Quality and Energy Efficiency applied to specified buildings Ventilation Solutions (VS) A European Ventilation Specialist Servicing our customers with a complete range of ventilation products focused on Non residential buildings. For more specific product information for Ventilation Solutions, please visit:

www.vsecatalogue.flaktwoods.com
Flkt Woods Group - Ventilation Solutions
Flkt Woods Limited Axial Way, Colchester Essex, C04 5ZD UNITED KINGDOM Tel: +44 (0)1206 222 555 Fax: +44 (0)1206 222 777 E-mail: info.uk@flaktwoods.com Flkt Woods Oy Kalevantie 39 FI-20520 Turku FINLAND Tel: +358 20 442 3000 Fax: +358 20 442 3018 E-mail: info.fi@flaktwoods.com Flkt Woods Oy Hmeentie 23 FI-37800 Toijala FINLAND Tel: +358 20 442 3500 Fax: +358 20 442 3502 E-mail: info.fi@flaktwoods.com Flkt Woods AB Gesllgatan 17 745 39 Enkping SWEDEN Tel: +46 36 19 30 00 Fax: +46 171-240 97 E-mail: info.se@flaktwoods.com Flkt Woods AB Kung Hans vg 12 192 68, Sollentuna Sweden Tel: +46 (0)771 26 26 26 Fax: +46 (0)8 626 73 10 E-mail: info.se@flaktwoods.com Flkt Woods AB Flktvgen 2, Box 84 153 22 Jrna SWEDEN Tel: +46 8-551795 00 Fax: +46 8-551744 80 E-mail: info.se@flaktwoods.com Flkt Woods 4 Avenue Laurent CELY-Batiment C - Etage 3 Asnieres Sur Seine 92600 FRANCE Tel: +33 1 80 21 07 00 Fax: +33 1 80 21 07 00 E-mail: info.fr@flaktwoods.com Flkt Woods Ventilatoren GmbH Am Sportplatz 4 DE-40882 Ratingen GERMANY Tel: +49 2012 61038 11 Fax: +49 2102 61038 18 E-mail: info.de@flaktwoods.com Flkt Woods SpA Via Pacinotti, 28 IT-20092, Cinisello Balsamo ITALY Tel: +39 02 6186 6091 Fax: +39 02 6186 0947 E-mail: info.it@flaktwoods.com Flkt Bovent Sp. z o.o. Panattoni Park Pruszkw II ul. Poudniowa 2, Otarzew 05-850 Oarw Mazowiecki POLAND Tel: +48 22 392 43 43 Fax: +48 22 392 43 44 E-mail: info.pl@flaktwoods.com LLC Flkt Industrial & Building Systems 23, ul. Profsojuznaya RU-117418 Moscow RUSSIA Tel: +7 (495) 589-31-08 Fax: +7 (495) 589-31-74 E-mail: info.ru@flaktwoods.com

Flkt Woods Limited


Axial Way, Colchester, Essex, C04 5ZD Tel 01206 222 555 Fax 01206 222 777 email info.uk@flaktwoods.com www.flaktwoods.co.uk

Flkt Woods operates a policy of continuous improvement and reserves the right to supply products that may differ from those illustrated and described in this publication. Certified dimensions can be supplied on request on receipt of order.

VS/ESTB-ENG-02/0912

Potrebbero piacerti anche