Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
E U R O P E
R-410A
Introduction
R-410A (an azeotropic mixture of HFC-32/HFC-125) has been developed by Honeywell to serve as a long-term, non-ozone depleting energy efcient replacement for R-22 (HCFC-22) in a variety of new-equipment applications.
Applications
Air-conditioning R-410A is an ideal non-ozone depleting, long-term replacement for R-22 in new residential and light commercial unitary air conditioning systems. In new unitary systems optimised for its use, with either scroll or reciprocating compressors, R-410A has shown in tests to have a 5-to-6 percent higher Energy Efciency Rating (EER) than R-22. R-410A also has a higher capacity and pressure than R-22, enabling the design of smaller, more compact air-conditioning equipment. Chillers R-410A may serve as an excellent replacement for R-22 in new designed chillers, particularly positive displacement chillers. Commercial refrigeration R-410A may be used as a replacement for R-22 in new medium and low temperature commercial refrigeration systems, including supermarket display cases and refrigerated transport. R-410A can serve as a replacement for refrigerants like R-13B1 in new low-temperature industrial refrigeration systems and can be used as a retrot gas of existing R-13B1 systems.
R-410A has a signicantly higher capacity and pressure than R-22 and an intrinsically low toxicity. Because it behaves like an azeotrope, R-410A is easy to service in the eld.
R-410A is patented and has been recognized by underwriters' laboratory as practically non-ammable.
Physical properties
Components: HFC-32 HFC-125 Chemical name: Diuoromethane Pentauoroethane Molecular formula: CH2F2 CHF2CF3 at 101.3 kPa Weight %: 50% 50% 72,6 -52,7 -155 72.5 49.50 0.0020 500.00 4.19 1063.38 1.67 0.84 256.68 16.49 0.0794(*) 0.0154(*) 121.23 13.85(*) 99.99 0.28 None 0.00 A1/A1
Pressure/Temperature table
Temperature (C) -50.0 -45.0 -40.0 -35.0 -30.0 -25.0 -20.0 -15.0 -10.0 -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 45.0 50.0 55.0 60.0 Pressure (kPa) 110 140 176 220 271 331 401 482 574 680 799 934 1085 1254 1443 1652 1883 2137 2417 2724 3061 3429 3833
Molecular weight Boiling point (C) Freezing point (C) Critical temperature (C) Critical pressure (bar) Critical volume (m3/kg) Critical density (kg/m3) Vapour density at boiling point (kg/m3) Liquid density (kg/m3) Liquid heat capacity (kJ/kgK) Vapour heat capacity (kJ/kgK) Heat of vaporization at boiling point (kJ/kg) Vapour pressure (bar) Liquid thermal conductivity (W/mK) Vapour thermal conductivity (W/mK) Liquid viscosity (Pasec) Vapour viscosity (Pasec) % Volatiles by volume Solubility of water in R-410A (wt.%) Flammability limits in air (vol.%)(**) Ozone Depletion Potential (ODP R11=1) ASHRAE Safety Group Classication (*) Information based on estimated properties. (**) ASTM E681-85 match ignition, ambient conditions. All measurements are at 25C unless otherwise noted.
REFRIGERANTS
E U R O P E
-10
10 20 Temperature (C)
30
40
50
Materials compatibility
Compatibility: plastic/elastomers Material Ethylene-Propylene Diene Terpolymer Ethylene-Propylene Copolymer Chlorosulfonated Polyethylene Chlorinated Polyethylene Neoprene (Chloroprene) Epichlorohydrin Fluorinated Rubbers Silicone Polyurethane Nitriles H-NBR Butyl Rubber Polysulde Nylon Polytetrauoroethylene PEEK ABS Polypropylene Polyphenyl Sulde Polyethylene Terephthalate Polysulfone Polyimide Polyetherimide Polyphthalamide Polyamideimide Acetal Phenolic S: Suitable Su: Suitable with some exceptions U: Unsuitable R-410A S S S Su S Su U Su Su Su Su Su S S S S U Su U Su Su S S Su S Su S
REFRIGERANTS
E U R O P E
Safety
Honeywell recommends reading the Material Safety Data sheet (MSDS) before using R-410A. Toxicity R-410A can be safely used in all of its intended applications, based on data developed by the Program for Alternative Fluorocarbon Toxicity Testing (PAFT 1). Leaks If a large release of R-410A a vapour occurs, the area should be evacuated immediately. Vapours may concentrate near the oor, displacing available oxygen. Once the area is evacuated, it must be ventilated using blowers or fans to circulate the air at oor-level. Flammability According to ASHRAE Standard 34, R-410A is classied in safety group A1/A1, i.e., it is non-ammable at 1 atm. pressure (101.3 kPa) and 18C.
Leak detection
Use leak detectors for pinpointing leaks or for monitoring an entire room on a continual basis. Leak detectors are important for refrigerant conservation, equipment protection and performance, reduction of emissions and protection of those coming in contact with the system. Leak testing should not be performed with mixtures of air and R-410A under pressure. Since R-410A is an HFC mixture, use a leak detector capable of detecting an HFC gas.
Environmental considerations
R-410A is a halogenated hydrocarbon. Treatment or disposal of wastes generated by use of this product may require special consideration, depending on the nature of the wastes and the means of discharge, treatment or disposal. For more information, refer to the MSDS.
REFRIGERANTS
E U R O P E
Available literature
Honeywell has a wide range of literature available on topics including: retrotting procedures, product specications and product descriptions. Please ask for the CD-rom containing Refrigerant Properties, Cycle Analysis and Pipe Sizing.
For further information and/or technical assistance on refrigerants, please contact us at our sales & technical ofces: Honeywell - Northern & Central Europe Haasrode Research Park, Grauwmeer 1 B-3001 Heverlee (Leuven) Belgium Tel: +32 16-391 278 Fax: +32 16-391 277 Honeywell - Southern Europe, Middle East & Africa Via A. De Gasperi 19, I-20020 Lainate MI Italia Tel: +39 02-9379 6777 Fax: +39 02-9379 6761
Disclaimer All statements, information and data given herein are believed to be accurate and reliable but are presented without guaranty, warranty or responsibility of any kind, expressed or implied. Statements or suggestions concerning possible use of our products are made without representation or warranty that any such use is free of patent infringement and are not recommendations to infringe any patent. The user should not assume that all safety measures are indicated, or that other measures may not be required.
www.honeywellrefrigerants.com