The AC SMARTstart® is a multifunctional AC power A circuit breaker at the AC input provides overall protec-
distribution unit designed to control eight AC loads tion. To prevent the circuit breaker from tripping during
and monitor vital parameters. This product is avail- power up, the PDU features a power-on current limit. The
able in 15 Amp, 16 Amp, 20 Amp, and 30 Amp total AC SMARTstart® is also capable of monitoring input line
load capacity models. In addition, we offer output voltage and total load current, as well as line frequency.
configurations that use screw clamp terminal blocks,
in lieu of IEC or NEMA connectors, for industrial ap- Operation/control is accomplished either manually, us-
plications. ing controls on the front panel of the unit, or remotely,
using a computing device that utilizes EIA RS-232 and
All models have the ability to power-on or power-off RS-485/422 communications such as a laptop computer,
any or all loads in any sequence over a wide range desktop computer, or other personal electronic device.
of time intervals. The PDU automatically sequences
each output. This significantly reduces the total in- Two user programmable external contacts can be config-
rush current and limits the possibility of equipment ured to alert the user of under-voltage, over-current, or
damage due to the combined turn-on transient of over-temperature conditions using the dry contact clo-
several loads. The sequence order and delay is user sure. These contacts allow remote operation and control
defined at setup. from Web browser or Telnet interface.
Features
• Power control capability to groups of outlets
• Remote operation and control capabilities via Telnet
or Web interface
• Local operation and control capabilities by means of
front panel push-button switch and backlit LED status
indicator
• Monitors input line voltage, total load current, line
frequency, and remote external temperature (with
optional temperature sensor
• Two isolated contact inputs can be used with alarm
sensors, security sensors, limit switches, and/or
remote stop. Emergency Power Off (EPO) configura-
tion also possible.
• May be used as a master PDU with several slaves
linked via RS-485/422 or RS-232
• Includes optional front or center mounting brackets
• Complies to FCC, CE, UL, and TÜV requirements
Main Screen
Alert Threshold
Screen
Input Current 16A max. per breaker 32A max. split between (2) 20A max. per breaker 30A max. split between (2)
16A circuits 15A circuits
Power Entry IEC C20 Inlet IEC 60309, 30A, on 10’ Cord IEC C20 Inlet IEC C20 Inlet or
Connector or NEMA (L5-30P or L6-30P)
NEMA 5-20P on 10’ cord on 10’ cord
Outlet 8 x IEC C13 8 x IEC C13 8 x NEMA 5-20R 8 x NEMA 5-15R
Connectors
Output Power 1.92 or 3.26 KVA 3.84 or 6.38 KVA 4.30 KVA 6.45 KVA
(Basic Power) (Basic Power) (Basic Power) (Intermediate Power)
Input Protection 95 - 137 VAC - 16A 1 95 - 137 VAC - 16A 1 Pole 20A 2 Pole Circuit 2 x 15A 2 Pole Circuit
Pole Circuit Breaker Circuit Breaker per input Breaker per input Breaker
per input
200 - 208 VAC - 16A 2 Pole
200 - 208 VAC - 16A Circuit Breaker per input
2 Pole Circuit Breaker
per input
Panel Indicators LED LED LED LED
Communications:
• RS-232: Front panel DB-9F or DB-9M connector
• RS-485/422 rear panel RJ-11
• Telnet with web interface (when ordered with LAN module)
• SNMP
• Other options available upon request
Accessory (Optional):
• Temperature Sensor 72-1021-189 (Hookup wire not supplied)
7608 A D 20 12 S N T E
Amperage
AC SMARTstart 20, or 30 for NEMA Emergency Power Off
16 or 30 (32*) for Global (EPO) option - add E
to the end of the part
Voltage Design Communications number
A = AC Voltage Options
* To configure a 32A Global PDU, you must enter “30” in the 7th and 8th digit of the part number.
Ordering Information
(20.32)
8.00
17.188
(43.66)
Front View:
Web/Telnet
Remote & Local RJ-45
Ready Light
Output Indicator LEDs Lights
Back View:
2x8-pin
‘Quick Disconnect’ RJ-11/EIA RS-485
Connection AC Power Entry
(4.44)
1.745