Product Data
Innovative Unit Base Design
On the inside a high--tech composite material will not rust and
incorporates a sloped drain pan which improves drainage and helps
inhibit mold, algae and bacterial growth. On the outside metal base
rails provide added stability as well as easier handling and rigging.
Dedicated Low NOx units designed for California installations.
These models meet the California maximum oxides of nitrogen
(NOx) emissions requirement of 40 nanograms/joule or less as
shipped from the factory and MUST be installed in California Air
Quality Management Districts or any other location where a Low
NOx rule exists.
Variable--speed blower motors provide better comfort and energy
efficiency. Economical constant airflow which provides improved
indoor air quality and more even temperatures from room to room;
and reduced indoor noise due to lower air velocity. In addition,
youll realize improved installation flexibility with 3 different
airflow choices for best overall comfort.
Easy installation
A09032
FEATURES/BENEFITS
One--piece heating and cooling unit with low installation cost,
dependable performance and easy maintenance.
Efficient operation
High--efficiency design with SEERs (Seasonal Energy Efficiency
Ratio) of up to 15.5, EER up to 12.0, HSPF of 8.0 and AFUE up
to 80.1%.
Puron environmentally--sound refrigerant is Bryants unique
refrigerant designed to help protect the environment. Puron is an
HFC refrigerant which does not contain chlorine that can harm the
ozone layer. Puron refrigerant is in service in millions of systems
proving highly reliable, environmentally sound performance.
Energy--saving, direct spark ignition saves gas by operating only
when the room thermostat calls for heating. Standard units are
furnished with natural gas controls. A low--cost field installed kit
for propane conversion is available for all units.
677D -- -- A
TABLE OF CONTENTS
FEATURES/BENEFITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1--2
MODEL NUMBER NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
AHRI CAPACITIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5--6
OPTIONS AND ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
BASE UNIT DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8--9
ACCESSORY DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
SELECTION PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
PERFORMANCE DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12--32
TYPICAL PIPING AND WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
APPLICATION DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
TYPICAL WIRING SCHEMATICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36--39
CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41--42
000
24
--- ---
Type of Unit
677D --- Single Packaged
HYBRID HEAT Dual
Fuel System
Variations
TP --- Base unit with tin plated indoor
coil hairpins
Electrical Supply
N --- 208/230--- 1--- 60
Variations
Minor Series
Major Series
Nominal Cooling Capacity
24 --- 2.0 Tons
30 --- 2.5 Tons
36 --- 3.0 Tons
42 --- 3.5 Tons
48 --- 4.0 Tons
60 --- 5.0 Tons
677D -- -- A
AHRI* CAPACITIES
Cooling Capacities and Efficiencies{
UNIT
677D-- - A
24
30
36
42
48
60
NOMINAL
TONS
2
2--1/2
3
3--1/2
4
5
EER @A{
SEER}
11.4
11.6
12
11.6
11
11
15.5
15.0
15.0
15.0
15.0
14.5
677D -- -- A
UNIT
677D-- - A
24
30
36
42
48
60
HSPF
8.0
8.0
8.0
8.0
8.0
8.0
Output Capacity
(Btuh)
High / Low
Temperature Rise
Range
High F (_C)
Temperature Rise
Range
Low F (_C)
AFUE
40,000 / 26,000
32,000 / 21,000
20--50 (11--28)
15--45 (8--25)
78
60,000 / 39,000
49,000 / 31,000
25--55 (14--31)
25--55 (14--31)
78.6
90,000 / 58,500
74,000 / 47,000
35--65 (19--36)
35--65 (19--36)
79.2
115,000 / 75,000
93,000 / 61,000
30--60 (17--33)
30--60 (17--33)
80.1
130,000 / 84,500
103,000 / 68,000
35--65 (19--36)
35--65 (19--36)
80.0
UNIT SIZE
NOMINAL COOLING CAPACITY (ton)
NOMINAL HEATING INPUT (Btu/hr)
SHIPPING WEIGHT (lb)
(kg)
COMPRESSORS
Quantity
REFRIGERANT: PURON (R --- 410A)
Quantity (lb)
(kg)
EXPANSION DEVICE --- HEATING
Orifice OD (in.) --- Left
Orifice OD (in.) --- Right
EXPANSION DEVICE --- COOLING
Size
OUTDOOR COIL
Rows...Fins/in.
Face Area (sq ft)
OUTDOOR FAN
Nominal Cfm
Diameter (in.)
(mm)
Motor Hp (Rpm)
INDOOR COIL
Rows...Fins/in.
Face Area (sq ft)
INDOOR FAN
Nominal Airflow (Cfm)
Comfort
Efficiency
Max
Furnace (gas ht.) airflow---Low Stage, Efficiency Mode
Furnace (gas ht.) airflow---High Stage, Efficiency Mode
Size (in.)
(mm)
Motor HP
FURNACE SECTION*
Burner Orifice No.
Natural Gas Qty...Drill Size (Factory Installed)
Propane Gas Qty...Drill Size
HIGH --- PRESSURE SWITCH (psig)
Reset (Auto)
A40040
2
40,000
468
212
A30040
2 ---1/2
40,000
498
226
A30060
2 ---1/2
60,000
498
226
A36060
A36090
3
3
60,000
90,000
540
540
245
245
Two ---Stage Scroll
1
A42060
3 ---1/2
60,000
551
250
A42090
3 ---1/2
90,000
551
250
10.3
4.7
11.5
5.2
11.5
5.2
0.042
N/A
0.038
0.038
0.038
0.038
2 Ton
3 Ton
3 Ton
9.7
4.4
AccuRater
0.035
0.035
TXV
3 Ton
9.7
4.4
14.0
6.4
14.0
6.4
0.035
0.035
0.040
0.042
0.040
0.042
3 Ton
4 Ton
4 Ton
2...21
13.6
2...21
15.3
2...21
15.3
2...21
17.5
2...21
17.5
2...21
19.4
2...21
19.4
2700
22
559
1/8 (825)
2700
22
559
1/8 (825)
2700
22
559
1/8 (825)
2800
22
559
1/8 (825)
2800
22
559
1/8 (825)
2800
22
559
1/8 (825)
2800
22
559
1/8 (825)
3...17
3.7
3...17
3.7
3...17
3.7
3...17
4.7
3...17
4.7
3...17
4.7
3...17
4.7
Variable based on Comfort Roll back (see User Interface instructions for more information).
700
875
875
1050
1050
1225
1225
800
1000
1000
1200
1200
1400
1400
475
475
727
745
875
745
875
844
844
1120
1120
1410
1120
1410
10x10
10x10
10x10
11x10
11x10
11x10
11x10
254x254
254x254
254x254
279x254
279x254
279x254
279x254
1/2
1/2
1/2
3/4
3/4
3/4
3/4
2...44
2...55
2...44
2...55
Cut---out
3...44
3...55
3...44
3...55
3...38
3...53
3...44
3...55
3...38
3...53
670 10
470 25
(Compressor Solenoid)
Cut---out
Reset (Auto)
565 15
455 15
23 5
55 5
20x24x1
508x610x25
24x30x1
610x762x25
24x36x1
610x914x25
677D -- -- A
PHYSICAL DATA
A48090
4
90,000
575
261
A48115
4
115,000
575
261
A48130
A60090
4
5
130,000
90,000
575
618
261
280
Two--Stage Scroll
1
A60115
5
115,000
618
280
A60130
5
130,000
618
280
15.5
7.0
15.5
7.0
16.0
7.3
16.0
7.3
0.038
0.046
0.038
0.046
0.046
0.046
0.046
0.046
4 Ton
4 Ton
15.5
16.0
7.0
7.3
AccuRater
0.038
0.046
0.046
0.046
TXV
4 Ton
5 Ton
5 Ton
5 Ton
3300
22
559
1/4 (1100)
3300
22
559
1/4 (1100)
3300
22
559
1/4 (1100)
3300
22
559
1/3 (1110)
3300
22
559
1/3 (1110)
3300
22
559
1/3 (1110)
2...21
19.4
2...21
19.4
2...21
19.4
2...21
23.3
2...21
23.3
2...21
23.3
3...17
5.7
3...17
5.7
3...17
5.7
4...17
5.7
4...17
5.7
4...17
5.7
677D -- -- A
COMPRESSORS
Quantity
REFRIGERANT: PURON (R-- 410A)
Quantity (lb)
(kg)
EXPANSION DEVICE-- HEATING
Orifice OD (in.) -- Left
Orifice OD (in.) -- Right
EXPANSION DEVICE-- COOLING
Size
OUTDOOR FAN
Nominal Cfm
Diameter (in.)
(mm)
Motor Hp (Rpm)
OUTDOOR COIL
Rows...Fins/in.
Face Area (sq ft)
INDOOR COIL
Rows...Fins/in.
Face Area (sq ft)
INDOOR FAN
Nominal Airflow (Cfm)
Comfort
Variable based on Comfort Roll back (see User Interface instructions for more
information).
1400
1400
1400
1750
1750
1750
1600
1600
1600
2000
2000
2000
815
1215
1255
845
1215
1255
1385
1885
1875
1300
1910
1920
11x10
11x10
11x10
11x10
11x10
11x10
279x254
279x254
279x254
279x254
279x254
279x254
3/4
3/4
3/4
1
1
1
Efficiency
Max
Furnace (gas ht.) airflow --- Low Stage, Efficiency Mode
Furnace (gas ht.) airflow --- High Stage, Efficiency Mode
Size in.
(mm)
Motor HP
FURNACE SECTION*
Burner Orifice No.
Natural Gas Qty...Drill Size (Factory Installed)
Propane Gas Qty...Drill Size
HIGH-- PRESSURE SWITCH (psig)
Cut--out
Reset (Auto)
HIGH-- PRESSURE SWITCH 2 (psig)
3...38
3...53
3...33
3...51
3...31
3...49
3...38
3...53
3...33
3...51
3...31
3...49
670 10
470 25
(Compressor Solenoid)
Cut--out
Reset (Auto)
LOSS-- OF-- CHARGE /
LOW-- PRESSURE SWITCH
(Liquid Line) (psig)
Cut--out
Reset (auto)
RETURN-- AIR FILTERS Throwaway (in.)
(mm)
565 15
455 15
23 5
55 5
24x36x1
610x914x25
Standard
Rating
(dBA)
125
250
500
1000
2000
4000
8000
24
30
36
42
48
60
75
75
75
75
78
78
58.8
58.8
60.7
56.7
62.4
63.5
63.5
63.5
63.3
62.8
69.9
67.6
67.2
67.2
66.8
67.8
71.3
71.8
66.9
66.9
66.5
67.4
73.4
75.5
63.7
63.7
64.2
63.7
70.0
71.0
58.3
58.3
60.3
57.7
66.3
68.1
50.0
50.0
53.0
50.8
60.1
59.9
NOTE: Tested in accordance with AHRI standard 270 (not listed in AHRI).
FACTORY
INSTALLED
OPTION
FIELD
INSTALLED
ACCESSORY
Coil Options
Corporate Thermostats
Filter Rack
Filter Rack features easy installation, serviceability, and high --filtering performance for vertical applications. Includes 1 ---in. (25
mm) filter.
Flat Roof Curbs in both 11 ---in (279 mm) and 14 ---in. (356 mm)
sizes are available for roof mounted applications.
High Altitude Propane Conversion Kit is for use at 2001 to 6000 ft.
(611 ---1829 m) above sea level. Kit consists of propane gas
orifices that compensate for gas heat operation at high altitude.
Manual Outside Air Damper includes hood and filter rack with
adjustable damper blade for up to 25% outdoor air.
Square ---to ---Round Duct Transition Kit enable 24 ---48 size units to
be fitted to 14 in. (356 mm) round ductwork.
Curb Adapter
Adapter curb for new unit with base rail installed on existing curb
Gasket Kit
For field modified existing roof curb with new base rail unit.
FILTER RACK
677D -- -- A
ITEM
REPLACEMENT
PANEL
TOP FILTER RACK
EV APORATOR
COIL
MANUAL OUTSIDE
AIR HOOD
DAMPER
BLADE
A09235
BOTTOM FILTER
RACK
A09236
677D -- -- A
A09561
677D -- -- A
A09562
ACCESSORY DIMENSIONS
B
HVAC unit
basepan
HVAC unit
base rails
Sealing
Gasket
Roofcurb
Anchor screw
Wood nailer*
Flashing field
supplied
Roofcurb*
Insulation
(field supplied)
Roofing material
field supplied
677D -- -- A
H
F A
Cant strip
field supplied
SMALL CURB
A09418
A09090
H
F A
E
D
LARGE CURB
A09415
A09419
CATALOG
NUMBER
A
IN. (mm)
CPRFCURB010A00
CPRFCURB011A00
CPRFCURB012A00
CPRFCURB013A00
11 (279)
14 (356)
11 (279)
14 (356)
B
IN. (mm)
C
IN.
(mm)
D
IN.
(mm)
16 (406)
47.8
(1214)
10 (254)
14 (356)
E
IN.
(mm)
32.4
(822)
43.9
(1116)
F
IN.
(mm)
G
IN. (mm)
H
IN. (mm)
30.6 (778)
2.7 (69)
46.1 (1170)
42.2 (1072)
NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as required, to unit being installed.
3. Roof curb is made of 16--gauge steel.
4. Attach ductwork to curb (flanges of duct rest on curb).
5. Insulated panels: 1--in. (25 mm) thick fiberglass 1 lb. density.
10
SELECTION PROCEDURE
Determine cooling and heating requirements at design
conditions
Given:
REQUIRED COOLING CAPACITY (TC) . . . . . . 34,500 BTUH
SENSIBLE HEAT CAPACITY (SHC) . . . . . . . . . 22,000 BTUH
REQUIRED HEATING CAPACITY (SHC) . . . . . 42,000 BTUH
CONDENSER ENTERING AIR TEMPERATURE 95F (35_C)
INDOOR--AIR TEMPERATURE . . . 80F (26.6_C) EDB, 67F
(19.4_C) EWB
EVAPORATOR AIR QUANTITY . . . . . . . . . . . . . . . 1200 CFM
ELECTRICAL CHARACTERISTICS . . . . . . . . . . . . . 230--1--60
677D -- -- A
11
12
57
(13.9)
62
(16.7)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.9)
62
(16.7)
63*
(17.2)
67
(19.4)
72
(22.2)
20.16
22.97
13.43
22.76
22.76
27.77
12.75
27.16
16.81
15.72
24.66
25.22
15.18
22.85
16.20
18.69
22.40
23.39
21.77
21.77
57
(13.9)
62
(16.7)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.9)
62
(16.7)
63*
(17.2)
67
(19.4)
72
(22.2)
EWB
_F (_C)
1.11
11.75
12.26
10.05
17.52
15.66
12.58
13.14
10.61
17.61
19.23
21.48
17.52
17.71
18.10
19.75
22.06
1.09
14.47
17.20
1.08
1.08
1.08
1.09
1.08
1.06
1.06
16.65
16.65
1.05
75_F (23.8_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
600
525
CFM
EVAPORATOR
1.70
1.67
1.64
1.64
1.64
1.67
1.64
1.62
1.61
1.61
Total
System
KW
75_F (23.8_C)
Capacity
MBtuh
Total
Sens
800
700
CFM
EWB
_F (_C)
EVAPORATOR
AIR
12.96
16.32
15.71
21.76
21.81
12.28
15.24
14.70
18.21
20.88
1.88
1.85
1.83
1.82
1.82
1.86
1.83
1.80
1.80
1.79
Total
System
KW
20.93
18.71
17.12
16.78
16.77
20.41
18.23
16.69
16.29
15.95
10.21
12.74
12.18
16.75
16.77
9.66
11.87
11.36
14.07
15.95
1.26
1.24
1.23
1.23
1.23
1.24
1.22
1.21
1.21
1.20
85_F (29.4_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
26.37
23.94
22.19
21.84
21.81
25.83
23.44
21.71
21.29
20.88
Capacity
MBtuh
Total
Sens
85_F (29.4_C)
12.48
15.82
15.21
20.81
20.81
11.80
14.75
14.21
17.70
19.95
2.09
2.05
2.03
2.03
2.03
2.06
2.03
2.01
2.00
2.00
Total
System
KW
23.35
21.18
19.62
19.74
19.74
22.94
20.79
19.25
18.95
18.94
11.95
15.30
14.69
19.74
19.74
11.29
14.24
13.70
18.95
18.94
2.31
2.28
2.26
2.26
2.26
2.29
2.26
2.23
2.23
2.23
Total
System
KW
105_F (40.5_C)
Capacity
MBtuh
Total
Sens
19.72
17.60
16.09
15.96
15.96
19.26
17.18
15.70
15.34
15.21
9.80
12.32
11.76
15.96
15.96
9.26
11.47
10.96
13.65
15.21
1.43
1.41
1.39
1.39
1.39
1.41
1.39
1.38
1.37
1.37
18.41
16.41
14.98
15.10
15.10
18.02
16.05
14.64
14.40
14.40
9.36
11.88
11.32
15.10
15.10
8.84
11.03
10.53
14.40
14.40
1.62
1.60
1.59
1.59
1.59
1.60
1.58
1.57
1.57
1.57
24.90
22.60
20.94
20.81
20.81
24.42
22.15
20.52
20.13
19.95
Capacity
MBtuh
Total
Sens
95_F (35_C)
11.41
14.74
14.14
18.58
18.58
10.76
13.70
13.16
17.86
17.86
2.57
2.53
2.51
2.51
2.51
2.54
2.51
2.48
2.48
2.48
17.03
15.14
13.80
14.15
14.15
16.69
14.83
13.50
13.52
13.52
8.91
11.41
10.85
14.15
14.15
8.39
10.58
10.07
13.52
13.52
1.85
1.83
1.81
1.82
1.82
1.83
1.81
1.80
1.80
1.80
115_F (46.1_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
21.66
19.67
18.22
18.58
18.58
21.33
19.34
17.90
17.86
17.86
Total
System
KW
115_F (46.1_C)
Capacity
MBtuh
Total
Sens
677D -- -- A
11.05
14.14
13.54
17.29
17.29
10.18
13.12
12.58
16.66
16.66
2.57
2.82
2.79
2.80
2.80
2.83
2.79
2.77
2.77
2.77
15.51
13.76
12.51
13.12
13.11
15.24
13.50
12.27
12.55
12.55
8.41
10.91
10.35
13.12
13.11
7.90
10.09
9.58
12.55
12.55
2.11
2.09
2.08
2.09
2.09
2.09
2.07
2.06
2.07
2.07
125_F (51.6_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
20.60
18.01
16.69
17.29
17.29
19.57
17.74
16.42
16.66
16.66
Total
System
KW
125_F (51.6_C)
Capacity
MBtuh
Total
Sens
13
700
800
700
800
700
800
CFM
4.21
4.24
3.97
4.02
3.77
3.82
700
800
700
800
700
800
CFM
16.65
16.84
16.03
16.25
14.91
15.10
14.60
14.76
14.05
14.24
13.06
13.23
1.58
1.53
1.62
1.68
1.89
1.84
1.12
1.11
1.25
1.24
1.38
1.38
5.89
5.95
5.63
5.71
5.36
5.43
1.21
1.20
1.35
1.34
1.49
1.48
9.38
9.46
9.01
9.12
8.62
8.74
8.61
8.69
8.27
8.37
7.91
8.02
1.32
1.31
1.46
1.45
1.61
1.59
11.90
11.94
11.51
11.60
11.03
11.17
10.85
10.89
10.49
10.58
10.06
10.19
1.42
1.43
1.55
1.55
1.70
1.69
19.30
19.36
18.69
18.95
17.97
18.27
19.30
19.36
18.69
18.95
17.97
18.27
1.69
1.61
1.86
1.79
2.03
1.96
21.15
21.27
20.68
20.80
20.04
20.30
21.15
21.27
20.68
20.80
20.04
20.30
1.75
1.66
1.95
1.85
2.14
2.05
22.00
22.16
21.51
21.65
20.96
21.13
22.00
22.16
21.51
21.65
20.96
21.13
677D -- -- A
1.78
1.70
1.98
1.87
2.20
2.08
6.40
6.47
6.12
6.20
5.83
5.91
Heating Capacity
LEGEND
Cap. Heating Capacity (1000 Btuh) (Includes Indoor--Fan Motor Heat)
db Dry Bulb
kW Total Power Input (Includes Compressor Motor Power Input Outdoor--Fan Motor Input, and Indoor--Fan Motor Input)
rh Relative Humidity
NOTES:
Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it.
80
(26.7)
70
(21.1)
60
(15.6)
_F (_C)
EDB
INDOOR AIR
3.88
3.90
3.65
3.70
3.47
3.51
80
(26.7)
70
(21.1)
60
(15.6)
_F (_C)
EDB
INDOOR AIR
677D----A24 High
12.90
12.94
11.21
11.30
10.75
10.88
1.45
1.44
1.49
1.66
1.75
1.72
25.14
25.40
24.54
24.82
23.91
24.20
25.14
25.40
24.54
24.82
23.91
24.20
1.92
1.82
2.11
2.00
2.32
2.21
60_F (15.5_C)
Capacity
Total
MBtuh
System
KW
Total
Integ
14.22
14.27
12.36
12.46
11.85
12.00
14
525
600
525
600
525
600
CFM
2.95
2.99
2.81
2.87
2.61
2.66
525
600
525
600
525
600
CFM
12.17
12.37
11.60
11.80
11.00
11.21
10.66
10.84
10.17
10.34
9.64
9.83
1.30
1.27
1.46
1.43
1.64
1.61
1.05
1.04
1.22
1.21
1.37
1.36
4.50
4.58
4.34
4.41
4.09
4.16
1.11
1.09
1.29
1.28
1.46
1.44
7.22
7.31
6.73
6.87
6.26
6.38
6.63
6.71
6.18
6.30
5.75
5.86
1.18
1.17
1.35
1.34
1.52
1.51
8.74
8.89
8.26
8.40
7.78
7.92
7.97
8.11
7.53
7.66
7.10
7.22
1.22
1.20
1.38
1.37
1.56
1.54
15.20
15.22
14.55
14.80
13.91
14.16
15.20
15.22
14.55
14.80
13.91
14.16
1.37
1.33
1.54
1.50
1.72
1.68
17.28
16.79
16.84
16.80
16.15
16.40
17.28
16.79
16.84
16.80
16.15
16.40
1.41
1.37
1.61
1.54
1.79
1.74
18.16
16.85
17.86
17.64
17.17
17.36
18.16
16.85
17.86
17.64
17.17
17.36
1.44
1.36
1.64
1.57
1.83
1.77
4.89
4.97
4.72
4.80
4.45
4.53
Heating Capacity
LEGEND
Cap. Heating Capacity (1000 Btuh) (Includes Indoor--Fan Motor Heat)
db Dry Bulb
kW Total Power Input (Includes Compressor Motor Power Input Outdoor--Fan Motor Input, and Indoor--Fan Motor Input)
rh Relative Humidity
NOTES:
Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it.
80
(26.7)
70
(21.1)
60
(15.6)
_F (_C)
EDB
INDOOR AIR
2.72
2.75
2.59
2.64
2.41
2.46
80
(26.7)
70
(21.1)
60
(15.6)
_F (_C)
EDB
INDOOR AIR
677D----A24 Low
677D -- -- A
8.60
8.74
8.14
8.28
7.68
7.80
1.24
1.22
1.40
1.38
1.57
1.56
19.43
16.78
20.96
18.39
20.53
20.33
19.43
16.78
20.96
18.39
20.53
20.33
1.44
1.29
1.71
1.53
1.91
1.85
60_F (15.5_C)
Capacity
Total
MBtuh
System
KW
Total
Integ
9.48
9.64
8.97
9.13
8.46
8.60
15
57
(13.9)
62
(16.7)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.9)
62
(16.7)
63*
(17.2)
67
(19.4)
72
(22.2)
23.85
19.34
19.99
16.13
29.10
25.68
20.61
21.34
16.96
28.72
29.28
31.48
34.49
29.10
29.40
29.91
32.13
35.18
57
(13.9)
62
(16.7)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.9)
62
(16.7)
63*
(17.2)
67
(19.4)
72
(22.2)
EWB
_F (_C)
1.36
14.40
14.96
12.26
21.32
19.04
15.36
15.98
12.91
21.55
23.40
25.95
21.32
21.67
22.13
24.00
26.61
1.34
17.65
21.08
1.32
1.31
1.31
1.35
1.32
1.30
1.30
20.32
1.29
Total
System
KW
2.18
2.14
2.10
2.10
2.09
2.14
2.10
2.07
2.06
2.05
20.32
Capacity
MBtuh
Total
Sens
700
615
CFM
EVAPORATOR
AIR
75_F (23.8_C)
27.90
27.90
75_F (23.8_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
1000
875
CFM
EWB
_F (_C)
EVAPORATOR
AIR
25.22
22.76
20.98
20.56
20.44
24.65
22.22
20.47
20.01
19.50
12.42
15.50
14.89
18.54
20.44
11.79
14.49
13.94
17.18
19.50
2.40
2.36
2.32
2.32
2.32
2.36
2.32
2.29
2.28
2.27
1.55
1.53
1.51
1.50
1.50
1.53
1.51
1.49
1.49
1.48
Total
System
KW
85_F (29.4_C)
16.32
20.69
19.98
27.75
27.84
15.50
19.36
18.72
23.21
26.73
Capacity
MBtuh
Total
Sens
33.29
30.42
28.33
27.90
27.84
32.69
29.85
27.78
27.25
26.73
85_F (29.4_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
23.71
21.40
19.74
19.46
19.46
23.20
20.93
19.28
18.86
18.60
2.65
2.60
2.57
2.56
2.56
2.61
2.56
2.53
2.52
2.52
29.11
26.64
24.86
25.00
25.00
28.70
26.23
24.46
24.09
24.09
14.94
19.30
18.60
25.00
25.00
14.15
18.00
17.38
24.09
24.09
95_F (35_C)
11.90
14.98
14.38
19.46
19.46
11.28
13.99
13.44
16.67
18.60
1.76
1.74
1.72
1.72
1.72
1.75
1.72
1.70
1.70
1.70
Total
System
KW
22.06
19.91
18.38
18.38
18.38
21.63
19.51
17.99
17.62
17.60
11.34
14.42
13.83
18.38
18.38
10.73
13.44
12.90
17.58
17.60
Capacity
MBtuh
Total
Sens
2.92
2.87
2.83
2.84
2.84
2.88
2.83
2.80
2.79
2.79
2.01
1.99
1.97
1.97
1.97
2.00
1.97
1.95
1.95
1.95
20.25
18.29
16.90
17.17
17.17
19.91
17.97
16.58
16.49
16.20
10.74
13.82
13.24
17.17
17.17
10.14
12.85
12.33
16.49
16.20
3.22
3.17
3.13
3.15
3.15
3.18
3.13
3.10
3.10
3.10
2.30
2.28
2.26
2.26
2.26
2.28
2.26
2.24
2.24
2.21
Total
System
KW
115_F (46.1_C)
14.18
18.53
17.84
23.34
23.34
13.40
17.25
16.64
22.56
22.56
Capacity
MBtuh
Total
Sens
26.76
24.51
22.90
23.34
23.34
26.43
24.19
22.58
22.56
22.56
115_F (46.1_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
677D -- -- A
Total
System
KW
105_F (40.5_C)
15.65
20.02
19.31
26.48
26.48
14.85
18.70
18.07
22.53
25.47
Capacity
MBtuh
Total
Sens
31.27
28.60
26.66
26.48
26.48
30.77
28.11
26.18
25.70
25.47
18.28
16.52
15.28
15.82
15.82
18.01
16.26
15.02
15.23
15.23
10.09
13.17
12.60
15.82
15.82
9.51
12.24
11.71
15.23
15.23
3.55
3.51
3.47
3.49
3.49
3.19
3.47
3.43
3.44
3.44
2.63
2.61
2.60
2.60
2.60
2.62
2.60
2.58
2.58
2.58
Total
System
KW
125_F (51.6_C)
13.36
16.98
17.00
21.47
21.47
13.36
16.42
15.82
20.81
20.81
Capacity
MBtuh
Total
Sens
24.19
22.47
20.75
21.47
21.47
26.31
21.92
20.50
20.81
20.81
125_F (51.6_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
16
875
1000
875
1000
875
1000
CFM
7.07
7.16
6.74
6.84
6.31
6.42
875
1000
875
1000
875
1000
CFM
19.48
19.75
18.76
19.03
18.00
18.32
17.07
17.31
16.44
16.67
15.77
16.05
1.91
1.89
2.11
2.08
2.31
2.28
1.56
1.56
1.73
1.73
1.90
1.90
8.60
8.70
8.28
8.39
7.88
8.00
1.64
1.64
1.82
1.82
2.00
2.00
12.08
12.23
11.66
11.80
11.20
11.35
11.09
11.23
10.70
10.83
10.28
10.42
1.72
1.71
1.91
1.90
2.10
2.09
14.34
14.51
13.82
14.00
13.30
13.48
13.07
13.23
12.60
12.76
12.13
12.29
1.78
1.77
1.97
1.95
2.17
2.15
24.32
24.63
23.39
23.75
22.48
22.83
24.32
24.63
23.39
23.75
22.48
22.83
2.04
2.02
2.23
2.20
2.44
2.40
28.09
28.28
27.23
27.60
26.17
26.59
28.09
28.28
27.23
27.60
26.17
26.59
2.08
2.15
2.34
2.31
2.56
2.51
29.61
30.05
29.07
29.24
27.94
28.38
29.61
30.05
29.07
29.24
27.94
28.38
2.12
2.19
2.40
2.34
2.62
2.57
9.35
9.46
9.00
9.12
8.56
8.69
Heating Capacity
LEGEND
Cap. Heating Capacity (1000 Btuh) (Includes Indoor--Fan Motor Heat)
db Dry Bulb
kW Total Power Input (Includes Compressor Motor Power Input Outdoor--Fan Motor Input, and Indoor--Fan Motor Input)
rh Relative Humidity
NOTES:
Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it.
(26.7)
80
(21.1)
70
60
(15.6)
_F (_C)
EDB
INDOOR AIR
6.51
6.59
6.20
6.29
5.81
5.91
(26.7)
80
(21.1)
70
60
(15.6)
_F (_C)
EDB
INDOOR AIR
677D----A30 High
677D -- -- A
13.99
14.16
13.46
13.64
12.95
13.11
1.81
1.79
2.00
1.98
2.20
2.18
35.99
36.32
35.34
35.85
34.42
34.50
35.99
36.32
35.34
35.85
34.42
34.50
2.18
2.32
2.46
2.54
2.70
2.82
60_F (15.5_C)
Capacity
Total
MBtuh
System
KW
Total
Integ
15.42
15.61
14.85
15.04
14.28
14.46
17
615
700
615
700
615
700
CFM
3.77
3.81
3.34
3.42
2.85
2.91
615
700
615
700
615
700
CFM
13.95
14.14
13.39
13.58
12.86
13.03
12.23
12.39
11.73
11.90
11.27
11.42
1.41
1.37
1.61
1.57
1.82
1.78
1.12
1.12
1.29
1.29
1.47
1.47
5.29
5.36
5.00
5.10
4.45
4.54
1.20
1.19
1.38
1.37
1.57
1.56
8.06
8.16
7.66
7.75
7.16
7.27
7.40
7.49
7.03
7.11
6.57
6.67
1.27
1.25
1.46
1.44
1.65
1.63
9.90
10.01
9.47
9.60
8.97
9.10
9.03
9.13
8.64
8.75
8.18
8.30
1.32
1.29
1.51
1.48
1.71
1.68
17.78
18.04
17.11
17.39
16.41
16.66
17.78
18.04
17.11
17.39
16.41
16.66
1.50
1.45
1.70
1.65
1.92
1.86
20.83
21.17
20.08
20.40
19.37
19.66
20.83
21.17
20.08
20.40
19.37
19.66
1.57
1.51
1.78
1.71
2.01
1.93
22.25
22.64
21.45
21.80
20.70
21.02
22.25
22.64
21.45
21.80
20.70
21.02
677D -- -- A
1.61
1.54
1.81
1.74
2.05
1.96
5.75
5.82
5.44
5.55
4.84
4.93
Heating Capacity
LEGEND
Cap. Heating Capacity (1000 Btuh) (Includes Indoor--Fan Motor Heat)
db Dry Bulb
kW Total Power Input (Includes Compressor Motor Power Input Outdoor--Fan Motor Input, and Indoor--Fan Motor Input)
rh Relative Humidity
NOTES:
Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it.
(26.7)
80
(21.1)
70
60
(15.6)
_F (_C)
EDB
INDOOR AIR
3.47
3.51
3.07
3.15
2.62
2.68
(26.7)
80
(21.1)
70
60
(15.6)
_F (_C)
EDB
INDOOR AIR
677D----A30 Low
9.75
9.86
9.35
9.47
8.89
9.02
1.34
1.31
1.53
1.50
1.73
1.70
27.83
28.00
26.70
27.26
25.66
26.16
27.83
28.00
26.70
27.26
25.66
26.16
1.75
1.62
1.96
1.87
2.20
2.09
60_F (15.5_C)
Capacity
Total
MBtuh
System
KW
Total
Integ
10.75
10.87
10.31
10.45
9.80
9.94
18
57
(13.9)
62
(16.7)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.9)
62
(16.7)
63*
(17.2)
67
(19.4)
72
(22.2)
33.64
28.72
23.25
24.04
18.41
35.06
30.91
24.79
25.68
19.31
33.64
34.47
35.12
37.76
42.16
35.06
35.29
35.86
38.52
42.99
57
(13.9)
62
(16.7)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.9)
62
(16.7)
63*
(17.2)
67
(19.4)
72
(22.2)
EWB
_F (_C)
1.53
16.28
16.96
13.86
24.45
21.68
17.42
18.17
14.64
24.46
26.63
29.67
24.45
24.61
25.11
27.33
30.44
1.50
20.06
23.91
1.49
1.48
1.48
1.51
1.48
1.47
1.46
23.27
23.27
1.46
75_F (23.8_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
850
745
CFM
EVAPORATOR
AIR
2.41
2.36
2.33
2.33
2.32
2.37
2.32
2.29
2.29
2.28
75_F (23.8_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
1200
1050
CFM
EWB
_F (_C)
EVAPORATOR
AIR
18.61
24.97
24.08
33.64
33.64
17.73
23.34
22.56
28.00
32.32
2.66
2.61
2.58
2.58
2.58
2.62
2.57
2.54
2.54
2.53
28.89
25.92
23.80
23.43
23.43
28.20
25.29
23.21
22.70
22.34
14.12
17.64
16.89
23.43
23.43
13.35
16.45
15.77
19.54
22.34
1.71
1.69
1.68
1.67
1.67
1.70
1.67
1.66
1.65
1.65
85_F (29.4_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
40.85
36.62
34.09
33.64
33.64
40.12
35.94
33.44
32.83
32.32
85_F (29.4_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
17.87
24.22
23.34
32.12
32.12
17.01
22.61
21.83
27.24
30.90
2.93
2.88
2.85
2.85
2.85
2.90
2.84
2.81
2.81
2.81
36.13
32.43
30.23
30.46
30.46
35.58
31.91
29.73
29.36
29.36
17.09
23.43
22.56
30.46
30.46
16.24
21.83
21.07
29.36
29.36
3.24
3.19
3.15
3.16
3.16
3.20
3.15
3.12
3.11
3.11
27.21
24.40
22.39
22.33
22.33
26.61
23.85
21.87
21.41
21.31
13.55
17.08
16.34
22.33
22.33
12.81
15.90
15.23
18.97
21.31
1.93
1.91
1.89
1.89
1.89
1.91
1.89
1.87
1.87
1.87
25.40
22.76
20.88
21.12
21.11
24.89
22.28
20.42
20.19
20.19
12.96
16.48
15.74
21.12
21.11
12.23
15.32
14.65
20.19
20.19
2.17
2.15
2.14
2.14
2.14
2.16
2.14
2.12
2.12
2.12
38.57
34.60
32.22
32.12
32.12
37.93
34.00
31.65
31.11
30.90
16.25
22.57
21.71
28.63
28.63
15.43
21.00
20.25
27.65
27.65
3.58
3.53
3.49
3.50
3.50
3.54
3.49
3.45
3.46
3.46
23.45
20.99
19.24
19.80
19.80
23.01
20.58
18.85
18.95
18.95
12.33
15.84
15.10
19.80
19.80
11.60
14.69
14.03
18.95
18.95
2.46
2.44
2.43
2.44
2.44
2.45
2.43
2.41
2.41
2.41
115_F (46.1_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
33.48
30.06
28.05
28.63
28.63
33.02
29.65
27.64
27.65
27.65
115_F (46.1_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
677D -- -- A
15.35
21.64
20.78
26.56
26.56
14.53
20.10
19.35
25.71
25.71
3.96
3.90
3.87
3.89
3.89
3.92
3.87
3.83
3.84
3.84
21.30
19.06
17.46
18.32
18.32
20.96
18.72
17.14
17.58
17.58
11.65
15.15
14.42
18.32
18.32
10.93
14.02
13.36
17.58
17.58
2.80
2.78
2.77
2.78
2.78
2.79
2.77
2.75
2.76
2.76
125_F (51.6_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
30.56
27.47
25.66
26.56
26.56
30.21
27.14
25.33
25.71
25.71
125_F (51.6_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
19
1050
1200
1050
1200
1050
1200
CFM
8.62
8.70
8.34
8.44
7.96
8.07
(26.7)
80
(21.1)
70
60
(15.6)
_F (_C)
EDB
1050
1200
1050
1200
1050
1200
CFM
INDOOR AIR
1.43
1.43
1.59
1.59
1.74
1.74
23.95
24.20
23.16
23.44
22.38
22.66
20.99
21.21
20.29
20.54
19.61
19.86
2.22
2.20
2.44
2.41
2.67
2.64
7.93
8.01
7.68
7.77
7.32
7.43
(26.7)
80
(21.1)
70
60
(15.6)
_F (_C)
EDB
INDOOR AIR
677D----A36 High
10.43
10.53
10.14
10.25
9.76
9.88
1.60
1.59
1.77
1.77
1.95
1.94
14.73
14.88
14.26
14.42
13.78
13.93
13.52
13.66
13.09
13.24
12.65
12.79
1.78
1.77
1.97
1.96
2.17
2.15
17.57
17.76
16.99
17.20
16.38
16.59
16.02
16.19
15.49
15.68
14.93
15.12
1.92
1.90
2.12
2.10
2.33
2.31
29.99
30.20
28.99
29.28
28.03
28.36
29.99
30.20
28.99
29.28
28.03
28.36
2.51
2.45
2.73
2.71
2.99
2.94
34.51
34.82
33.82
33.60
32.65
33.00
34.51
34.82
33.82
33.60
32.65
33.00
2.69
2.67
2.98
2.90
3.24
3.21
36.57
36.95
35.98
35.59
34.87
34.97
677D -- -- A
36.57
36.95
35.98
35.59
34.87
34.97
2.79
2.74
3.08
3.00
3.37
3.29
11.33
11.45
11.02
11.14
10.60
10.74
Heating Capacity
17.15
17.33
16.61
16.81
15.99
16.19
1.99
1.97
2.19
2.17
2.40
2.38
43.09
43.39
42.90
43.10
42.66
42.80
43.09
43.39
42.90
43.10
42.66
42.80
3.12
2.88
3.44
3.30
3.75
3.69
60_F (15.5_C)
Capacity
Total
MBtuh
System
KW
Total
Integ
18.91
19.11
18.32
18.53
17.63
17.86
20
745
850
745
850
745
850
CFM
3.84
3.91
3.10
3.23
2.22
2.34
745
850
745
850
745
850
CFM
16.25
16.46
15.55
15.78
14.74
14.98
14.24
14.42
13.62
13.82
12.91
13.13
1.78
1.74
1.99
1.95
2.22
2.18
1.62
1.62
1.82
1.82
2.03
2.04
6.10
6.17
5.41
5.53
4.60
4.71
1.68
1.67
1.89
1.89
2.10
2.11
9.48
9.61
8.83
8.98
8.01
8.17
8.70
8.82
8.10
8.24
7.35
7.49
1.72
1.70
1.93
1.92
2.15
2.14
11.69
11.84
11.03
11.20
10.24
10.42
10.66
10.80
10.06
10.21
9.33
9.50
1.74
1.71
1.95
1.93
2.18
2.16
20.33
20.70
19.45
19.78
18.60
18.90
20.33
20.70
19.45
19.78
18.60
18.90
1.81
1.76
2.02
1.97
2.26
2.20
23.56
23.96
22.61
23.00
21.56
21.95
23.56
23.96
22.61
23.00
21.56
21.95
1.84
1.78
2.05
1.98
2.28
2.21
25.01
25.46
24.02
24.44
22.94
23.44
25.01
25.46
24.02
24.44
22.94
23.44
1.85
1.78
2.06
1.99
2.29
2.22
6.63
6.71
5.88
6.01
5.00
5.12
Heating Capacity
LEGEND
Cap. Heating Capacity (1000 Btuh) (Includes Indoor--Fan Motor Heat)
db Dry Bulb
kW Total Power Input (Includes Compressor Motor Power Input Outdoor--Fan Motor Input, and Indoor--Fan Motor Input)
rh Relative Humidity
NOTES:
Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it.
(26.7)
80
(21.1)
70
60
(15.6)
_F (_C)
EDB
INDOOR AIR
3.53
3.60
2.86
2.98
2.05
2.16
(26.7)
80
(21.1)
70
60
(15.6)
_F (_C)
EDB
INDOOR AIR
677D----A36 Low
677D -- -- A
11.51
11.66
10.90
11.07
10.18
10.36
1.75
1.72
1.96
1.94
2.19
2.16
30.27
30.88
29.09
29.68
27.95
28.50
30.27
30.88
29.09
29.68
27.95
28.50
1.90
1.82
2.11
2.02
2.35
2.25
60_F (15.5_C)
Capacity
Total
MBtuh
System
KW
Total
Integ
12.69
12.85
12.02
12.20
11.23
11.42
21
57
(13.9)
62
(16.7)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.9)
62
(16.7)
63*
(17.2)
67
(19.4)
72
(22.2)
40.34
37.05
29.94
30.93
24.77
41.96
39.80
31.90
33.01
26.04
40.34
41.24
42.00
45.04
49.21
41.96
42.17
42.81
45.87
50.09
57
(13.9)
62
(16.7)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.9)
62
(16.7)
63*
(17.2)
67
(19.4)
72
(22.2)
EWB
_F (_C)
1.91
19.56
20.31
16.51
29.53
25.99
20.89
21.71
17.40
29.61
32.05
35.41
29.53
29.77
30.34
32.81
36.21
1.91
24.09
28.99
1.90
1.90
1.90
1.89
1.89
1.89
1.89
28.20
28.20
1.89
75_F (23.8_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
975
855
CFM
EVAPORATOR
AIR
2.96
2.89
2.84
2.83
2.82
2.91
2.84
2.78
2.77
2.76
75_F (23.8_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
1400
1225
CFM
EWB
_F (_C)
EVAPORATOR
AIR
25.02
31.98
30.89
40.04
40.04
23.77
29.93
28.96
36.02
38.56
3.23
3.15
3.10
3.10
3.10
3.17
3.10
3.05
3.04
3.03
34.17
31.00
28.69
28.23
28.23
33.47
30.33
28.04
27.46
27.00
16.72
21.04
20.23
28.23
28.23
15.84
19.65
18.92
23.43
27.00
2.12
2.12
2.12
2.12
2.12
2.10
2.11
2.11
2.11
2.11
85_F (29.4_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
47.23
43.30
40.45
40.04
40.04
46.48
42.59
39.74
39.06
38.56
85_F (29.4_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
23.92
30.88
29.81
37.92
37.92
22.69
28.85
27.90
36.39
36.60
3.51
3.44
3.39
3.39
3.39
3.46
3.39
3.34
3.33
3.32
45.09
38.65
36.05
36.46
36.46
44.33
38.03
35.56
35.21
35.21
24.26
30.16
29.03
36.46
36.46
22.99
28.11
27.16
35.21
35.21
3.58
3.69
3.63
3.64
3.64
3.52
3.63
3.58
3.57
3.58
31.95
29.00
26.88
26.78
26.78
31.36
28.43
26.32
26.46
25.67
16.00
20.30
19.52
26.78
26.78
15.12
18.94
18.23
22.99
25.67
2.35
2.36
2.37
2.36
2.36
2.34
2.35
2.35
2.31
2.35
31.03
28.00
24.87
25.14
25.14
31.76
26.33
24.41
24.16
24.16
15.68
19.93
18.73
25.14
25.14
15.26
18.16
17.47
24.16
24.16
2.58
2.59
2.64
2.64
2.64
2.28
2.62
2.63
2.63
2.63
23.12
28.88
27.35
33.86
33.86
21.88
26.85
25.89
32.79
32.79
3.93
4.03
4.03
4.00
4.00
3.87
3.98
3.92
3.93
3.93
30.23
24.36
22.66
23.27
23.27
26.40
23.99
22.29
22.43
22.43
15.42
18.62
17.88
23.27
23.27
13.49
17.30
16.64
22.43
22.43
2.60
2.93
2.96
2.95
2.95
2.90
2.92
2.95
2.94
2.94
115_F (46.1_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
41.83
35.36
31.99
33.86
33.86
41.24
34.81
32.52
32.79
32.79
115_F (46.1_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
677D -- -- A
44.13
40.50
37.88
37.92
37.92
43.50
39.90
37.29
36.71
36.60
20.13
26.96
25.92
29.82
29.82
18.96
25.04
24.13
29.04
29.04
4.51
4.45
4.40
4.43
4.43
4.47
4.40
4.35
4.37
4.37
24.42
21.97
20.20
21.29
21.29
24.07
21.52
19.93
20.48
20.50
13.57
17.76
16.93
21.29
21.29
12.74
16.42
15.73
20.48
20.50
3.26
3.29
3.31
3.29
3.29
3.25
3.28
3.30
3.29
3.29
125_F (51.6_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
32.98
30.38
28.59
29.82
29.82
32.75
30.12
28.29
29.04
29.04
125_F (51.6_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
22
1225
1400
1225
1400
1225
1400
CFM
10.65
10.79
10.16
10.32
9.53
9.69
1225
1400
1225
1400
1225
1400
CFM
28.26
28.60
27.38
27.71
26.37
26.72
24.77
25.06
23.99
24.28
23.10
23.41
2.62
2.60
2.87
2.85
3.13
3.11
2.06
2.08
2.28
2.29
2.49
2.51
12.87
13.02
12.42
12.57
11.86
12.03
2.19
2.20
2.42
2.42
2.64
2.65
17.85
18.04
17.32
17.52
16.69
16.90
16.39
16.56
15.89
16.08
15.32
15.51
2.32
2.32
2.55
2.55
2.80
2.80
21.02
21.26
20.37
20.60
19.70
19.94
19.17
19.39
18.58
18.78
17.96
18.18
2.41
2.41
2.66
2.65
2.91
2.90
35.01
35.38
33.83
34.27
32.67
33.12
35.01
35.38
33.83
34.27
32.67
33.12
2.81
2.79
3.06
3.03
3.34
3.30
40.36
40.37
39.05
39.50
37.72
38.23
40.36
40.37
39.05
39.50
37.72
38.23
2.97
2.91
3.22
3.20
3.50
3.46
42.96
43.00
41.60
41.96
40.19
40.71
42.96
43.00
41.60
41.96
40.19
40.71
3.05
2.96
3.31
3.27
3.59
3.55
13.99
14.15
13.49
13.66
12.89
13.07
Heating Capacity
LEGEND
Cap. Heating Capacity (1000 Btuh) (Includes Indoor--Fan Motor Heat)
db Dry Bulb
kW Total Power Input (Includes Compressor Motor Power Input Outdoor--Fan Motor Input, and Indoor--Fan Motor Input)
rh Relative Humidity
NOTES:
Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it.
(26.7)
80
(21.1)
70
60
(15.6)
_F (_C)
EDB
INDOOR AIR
9.80
9.92
9.34
9.49
8.77
8.92
(26.7)
80
(21.1)
70
60
(15.6)
_F (_C)
EDB
INDOOR AIR
677D----A42 High
677D -- -- A
20.43
20.67
19.77
20.01
19.14
19.37
2.46
2.45
2.70
2.69
2.96
2.94
51.37
51.50
50.54
50.80
49.42
49.70
51.37
51.50
50.54
50.80
49.42
49.70
3.25
3.19
3.54
3.48
3.92
3.78
60_F (15.5_C)
Capacity
Total
MBtuh
System
KW
Total
Integ
22.53
22.79
21.80
22.06
21.10
21.36
23
855
975
855
975
855
975
CFM
5.94
6.03
5.11
5.22
4.12
4.22
855
975
855
975
855
975
CFM
19.99
20.23
19.18
19.44
18.27
18.54
17.51
17.72
16.81
17.03
16.01
16.24
1.99
1.95
2.21
2.17
2.46
2.41
1.70
1.69
1.90
1.90
2.11
2.11
8.24
8.36
7.48
7.61
6.57
6.69
1.77
1.76
1.97
1.97
2.18
2.18
12.26
12.41
11.48
11.65
10.55
10.72
11.25
11.39
10.54
10.69
9.68
9.84
1.84
1.82
2.05
2.03
2.27
2.26
14.78
14.95
14.01
14.20
13.09
13.29
13.47
13.63
12.77
12.95
11.94
12.12
1.89
1.86
2.11
2.08
2.33
2.31
24.57
24.89
23.66
23.98
22.72
23.04
24.57
24.89
23.66
23.98
22.72
23.04
2.07
2.02
2.31
2.25
2.56
2.50
28.27
28.72
27.19
27.60
26.12
26.53
28.27
28.72
27.19
27.60
26.12
26.53
2.15
2.08
2.38
2.31
2.64
2.57
30.02
30.53
28.83
29.31
27.72
28.17
30.02
30.53
28.83
29.31
27.72
28.17
677D -- -- A
2.18
2.11
2.42
2.34
2.68
2.60
8.96
9.08
8.13
8.27
7.14
7.27
Heating Capacity
LEGEND
Cap. Heating Capacity (1000 Btuh) (Includes Indoor--Fan Motor Heat)
db Dry Bulb
kW Total Power Input (Includes Compressor Motor Power Input Outdoor--Fan Motor Input, and Indoor--Fan Motor Input)
rh Relative Humidity
NOTES:
Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it.
(26.7)
80
(21.1)
70
60
(15.6)
_F (_C)
EDB
INDOOR AIR
5.46
5.55
4.70
4.80
3.79
3.88
(26.7)
80
(21.1)
70
60
(15.6)
_F (_C)
EDB
INDOOR AIR
677D----A42 Low
14.43
14.60
13.73
13.92
12.91
13.11
1.91
1.88
2.13
2.10
2.36
2.33
36.61
37.32
35.19
35.86
33.63
34.44
36.61
37.32
35.19
35.86
33.63
34.44
2.32
2.23
2.56
2.47
2.83
2.73
60_F (15.5_C)
Capacity
Total
MBtuh
System
KW
Total
Integ
15.91
16.10
15.14
15.35
14.24
14.46
24
57
(13.9)
62
(16.7)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.9)
62
(16.7)
63*
(17.2)
67
(19.4)
72
(22.2)
44.39
38.20
30.85
32.01
25.88
46.32
41.09
32.81
34.10
27.17
44.39
45.43
46.29
50.04
55.24
46.32
46.57
47.25
51.07
56.36
57
(13.9)
62
(16.7)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.9)
62
(16.7)
63*
(17.2)
67
(19.4)
72
(22.2)
EWB
_F (_C)
2.23
22.28
23.21
19.02
33.04
29.57
23.76
24.78
20.03
33.19
36.14
40.19
33.04
33.42
34.05
37.06
41.21
2.23
27.41
32.49
2.23
2.23
2.24
2.21
2.21
2.21
2.21
31.49
31.49
2.22
75_F (23.8_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
1100
965
CFM
EVAPORATOR
AIR
3.60
3.53
3.49
3.48
3.48
3.53
3.46
3.42
3.41
3.40
75_F (23.8_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
1600
1400
CFM
EWB
_F (_C)
EVAPORATOR
AIR
26.25
33.18
31.89
44.43
44.10
24.98
31.11
29.95
37.29
42.70
3.91
3.84
3.80
3.79
3.79
3.84
3.77
3.73
3.72
3.71
39.26
35.29
32.40
31.85
31.76
38.34
34.45
31.62
30.96
30.30
19.35
24.10
23.08
28.86
31.76
18.36
22.54
21.62
26.74
30.30
2.48
2.49
2.50
2.50
2.50
2.46
2.47
2.48
2.48
2.49
85_F (29.4_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
53.67
48.62
44.97
44.43
44.10
52.68
47.71
44.11
43.33
42.70
85_F (29.4_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
25.29
32.20
30.92
42.54
42.54
24.04
30.16
29.00
36.31
40.87
4.25
4.18
4.13
4.13
4.13
4.18
4.11
4.06
4.05
4.05
47.69
43.19
39.95
41.40
40.41
46.96
42.50
39.28
38.87
38.88
24.26
31.17
29.90
41.40
40.41
23.04
29.14
28.00
38.87
38.88
4.62
4.55
4.50
4.51
4.51
4.55
4.48
4.43
4.43
4.43
37.19
33.40
30.64
30.39
30.39
36.37
32.65
29.95
29.34
29.02
18.64
23.38
22.37
30.39
30.39
17.67
21.84
20.92
26.03
29.02
2.77
2.78
2.80
2.80
2.80
2.75
2.77
2.78
2.78
2.78
34.96
31.39
28.77
28.90
28.90
34.25
30.72
28.14
27.64
27.63
17.88
22.62
21.61
28.90
28.90
16.93
21.10
20.18
27.57
27.63
3.10
3.12
3.14
3.13
3.13
3.08
3.10
3.12
3.12
3.12
50.80
46.00
42.55
42.54
42.54
49.93
45.21
41.79
41.11
40.87
23.15
30.06
28.80
38.04
38.04
22.53
28.60
26.91
36.67
36.67
5.03
4.96
4.91
4.92
4.92
4.52
4.43
4.84
4.84
4.84
32.54
29.20
26.73
27.27
27.27
31.95
28.62
26.19
26.10
26.10
17.07
21.81
20.81
27.27
27.27
16.14
20.30
19.39
26.10
26.10
3.48
3.51
3.53
3.52
3.52
3.46
3.49
3.52
3.51
3.51
115_F (46.1_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
44.30
40.12
37.11
38.04
38.04
45.43
41.00
36.54
36.67
36.67
115_F (46.1_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
677D -- -- A
22.59
29.43
27.59
36.61
36.62
20.75
26.85
25.73
35.30
34.16
5.06
4.97
5.36
4.93
4.93
5.41
5.34
5.29
4.84
5.30
29.89
26.79
24.50
25.45
25.45
29.40
26.31
24.04
24.40
24.40
16.19
20.93
19.92
25.45
25.45
15.29
19.44
18.53
24.40
24.40
3.92
3.95
3.99
3.97
3.97
3.90
3.94
3.97
3.97
3.96
125_F (51.6_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
42.55
38.36
33.97
36.61
36.62
40.04
36.24
33.51
35.30
34.16
125_F (51.6_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
25
1400
1600
1400
1600
1400
1600
CFM
13.33
13.53
12.72
12.94
11.86
12.09
1400
1600
1400
1600
1400
1600
CFM
33.39
33.83
32.29
32.73
31.08
31.53
29.26
29.64
28.29
28.68
27.23
27.62
3.16
3.15
3.43
3.41
3.71
3.69
2.19
2.21
2.39
2.41
2.58
2.61
15.98
16.18
15.40
15.62
14.63
14.88
2.40
2.42
2.62
2.64
2.84
2.86
21.89
22.14
21.24
21.52
20.40
20.70
20.10
20.32
19.50
19.75
18.73
19.00
2.63
2.64
2.87
2.88
3.11
3.12
25.47
25.78
24.70
25.00
23.85
24.18
23.23
23.51
22.52
22.79
21.74
22.05
2.80
2.80
3.05
3.05
3.31
3.31
40.69
41.16
39.25
39.82
37.81
38.39
40.69
41.16
39.25
39.82
37.81
38.39
3.49
3.48
3.77
3.74
4.07
4.04
46.59
46.62
44.95
45.50
43.28
43.94
46.59
46.62
44.95
45.50
43.28
43.94
3.77
3.72
4.05
4.04
4.37
4.33
49.36
49.42
47.65
48.12
45.87
46.54
49.36
49.42
47.65
48.12
45.87
46.54
677D -- -- A
3.91
3.83
4.19
4.17
4.51
4.48
17.37
17.59
16.74
16.98
15.90
16.17
Heating Capacity
LEGEND
Cap. Heating Capacity (1000 Btuh) (Includes Indoor--Fan Motor Heat)
db Dry Bulb
kW Total Power Input (Includes Compressor Motor Power Input Outdoor--Fan Motor Input, and Indoor--Fan Motor Input)
rh Relative Humidity
NOTES:
Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it.
(26.7)
80
70
(21.1)
60
(15.6)
_F (_C)
EDB
INDOOR AIR
12.27
12.45
11.71
11.91
10.91
11.12
(26.7)
80
(21.1)
70
60
(15.6)
_F (_C)
EDB
INDOOR AIR
677D----A48 High
24.61
24.92
23.83
24.14
23.04
23.36
2.88
2.88
3.13
3.13
3.40
3.40
58.12
58.16
57.17
57.23
55.65
55.70
58.12
58.16
57.17
57.23
55.65
55.70
4.29
4.22
4.65
4.57
5.07
4.92
60_F (15.5_C)
Capacity
Total
MBtuh
System
KW
Total
Integ
27.14
27.47
26.27
26.61
25.40
25.75
26
965
1100
965
1100
965
1100
CFM
5.86
5.95
5.21
5.32
4.44
4.55
965
1100
965
1100
965
1100
CFM
21.99
22.24
21.27
21.53
20.45
20.73
19.27
19.48
18.64
18.87
17.92
18.16
2.26
2.22
2.53
2.48
2.81
2.76
1.86
1.86
2.08
2.08
2.32
2.33
8.32
8.42
7.76
7.88
7.05
7.17
1.96
1.95
2.19
2.18
2.43
2.43
12.71
12.85
12.11
12.27
11.36
11.53
11.67
11.79
11.12
11.27
10.42
10.58
2.05
2.03
2.30
2.28
2.55
2.54
15.64
15.80
15.01
15.20
14.25
14.45
14.26
14.41
13.69
13.86
12.99
13.17
2.12
2.09
2.37
2.34
2.64
2.61
27.98
28.40
26.97
27.36
26.04
26.39
27.98
28.40
26.97
27.36
26.04
26.39
2.40
2.33
2.66
2.59
2.96
2.89
32.83
33.33
31.72
32.20
30.48
30.97
32.83
33.33
31.72
32.20
30.48
30.97
2.51
2.43
2.78
2.70
3.08
2.99
35.07
35.65
33.87
34.41
32.72
33.22
35.07
35.65
33.87
34.41
32.72
33.22
2.56
2.47
2.84
2.74
3.15
3.04
9.04
9.16
8.43
8.56
7.66
7.79
Heating Capacity
LEGEND
Cap. Heating Capacity (1000 Btuh) (Includes Indoor--Fan Motor Heat)
db Dry Bulb
kW Total Power Input (Includes Compressor Motor Power Input Outdoor--Fan Motor Input, and Indoor--Fan Motor Input)
rh Relative Humidity
NOTES:
Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it.
(26.7)
80
(21.1)
70
60
(15.6)
_F (_C)
EDB
INDOOR AIR
5.39
5.47
4.80
4.89
4.09
4.18
(26.7)
80
(21.1)
70
60
(15.6)
_F (_C)
EDB
INDOOR AIR
677D----A48 Low
677D -- -- A
15.42
15.58
14.83
15.01
14.13
14.33
2.15
2.12
2.41
2.37
2.68
2.64
43.68
44.63
41.97
42.84
40.41
41.15
43.68
44.63
41.97
42.84
40.41
41.15
2.76
2.66
3.05
2.93
3.37
3.24
60_F (15.5_C)
Capacity
Total
MBtuh
System
KW
Total
Integ
17.00
17.18
16.35
16.55
15.58
15.80
27
57
(13.9)
62
(16.7)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.9)
62
(16.7)
63*
(17.2)
67
(19.4)
72
(22.2)
EWB
_F (_C)
58.24
54.46
43.33
44.86
35.33
56.01
50.62
40.75
42.11
33.69
58.24
58.46
59.23
63.56
69.55
56.01
57.19
58.18
62.48
68.41
57
(13.9)
62
(16.7)
63*
(17.2)
67
(19.4)
72
(22.2)
57
(13.9)
62
(16.7)
63*
(17.2)
67
(19.4)
72
(22.2)
EWB
_F (_C)
2.71
29.14
30.17
24.40
41.69
38.83
31.09
32.23
25.68
41.76
45.04
49.59
41.69
41.98
42.72
46.03
50.62
2.72
35.96
40.94
2.72
2.72
2.72
2.68
2.68
2.69
2.69
39.88
39.88
2.70
75_F (23.8_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
1370
1200
CFM
EVAPORATOR
AIR
4.48
4.39
4.32
4.31
4.29
4.59
4.50
4.42
4.42
4.41
75_F (23.8_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
1750
2000
CFM
EVAPORATOR
AIR
32.46
40.86
39.51
49.37
53.76
34.07
43.59
42.07
55.79
55.10
4.91
4.81
4.74
4.73
4.72
5.02
4.92
4.85
4.84
4.84
48.09
43.75
40.63
40.02
40.00
47.18
42.87
39.78
39.01
38.34
24.78
31.34
30.20
40.02
40.00
23.52
29.29
28.27
35.09
38.34
3.04
3.05
3.07
3.07
3.07
3.01
3.02
3.04
3.04
3.04
85_F (29.4_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
65.01
59.41
55.35
54.45
53.76
66.01
60.35
56.27
55.79
55.10
85_F (29.4_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
31.14
39.90
38.20
48.01
51.30
32.73
42.24
41.83
55.36
54.80
5.37
5.18
5.20
5.19
5.19
5.48
5.38
4.69
4.69
4.69
57.37
55.71
51.66
50.93
50.80
58.07
56.62
52.48
52.73
52.40
29.72
39.39
37.95
47.74
50.80
31.30
42.14
40.49
52.73
52.40
5.88
5.21
5.10
5.08
5.08
5.99
5.33
5.22
5.23
5.23
45.37
41.27
38.35
38.18
37.90
44.52
40.50
37.61
36.90
36.64
23.83
30.36
29.24
38.18
37.90
22.56
28.35
27.34
34.14
36.64
3.41
3.43
3.45
3.45
3.45
3.38
3.40
3.42
3.43
3.43
42.32
38.55
35.86
36.13
35.45
41.68
37.91
35.23
34.90
34.74
22.77
29.32
28.21
36.13
35.45
21.55
27.31
26.33
34.90
34.74
3.83
3.86
3.89
3.89
3.89
3.80
3.84
3.87
3.87
3.87
28.19
36.58
35.27
45.50
45.20
29.74
39.21
37.74
46.94
46.70
6.44
6.34
6.26
6.27
6.27
6.54
6.44
6.37
6.40
6.40
39.01
35.56
33.13
33.82
33.62
38.47
35.04
32.61
32.60
31.90
21.64
28.18
27.09
33.82
33.62
20.43
26.21
25.22
32.60
31.90
4.31
4.36
4.40
4.38
4.38
4.28
4.33
4.37
4.37
4.37
115_F (46.1_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
52.97
48.47
45.27
45.50
45.20
53.51
48.97
45.80
46.94
46.70
115_F (46.1_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
677D -- -- A
61.35
57.00
52.28
51.51
51.30
62.20
56.88
55.68
55.36
54.80
26.53
34.88
33.59
41.99
41.70
28.03
37.49
36.02
43.20
42.90
7.04
6.94
6.87
6.89
6.89
7.15
7.05
6.97
7.02
7.02
35.34
32.25
30.10
31.19
30.90
34.93
31.84
29.69
30.16
29.70
20.40
26.93
25.87
31.19
30.90
19.21
25.00
24.04
30.16
29.70
4.86
4.92
4.98
4.95
4.95
4.84
4.90
4.96
4.94
4.94
125_F (51.6_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
48.09
44.00
41.16
41.99
41.70
48.46
44.37
41.56
43.20
42.90
125_F (51.6_C)
Capacity
Total
MBtuh
System
KW
Total
Sens
28
1750
2000
1750
2000
1750
2000
CFM
17.01
17.24
16.62
16.88
16.04
16.31
1750
2000
1750
2000
1750
2000
CFM
41.80
41.90
40.71
41.19
39.61
40.12
36.62
36.71
35.67
36.09
34.70
35.15
4.14
4.12
4.52
4.53
4.93
4.92
3.08
3.12
3.40
3.44
3.72
3.77
19.89
20.13
19.53
19.78
18.99
19.27
3.31
3.34
3.65
3.69
4.01
4.04
27.05
27.37
26.51
26.82
25.93
26.26
24.83
25.12
24.33
24.62
23.80
24.11
3.55
3.57
3.91
3.93
4.29
4.31
31.57
31.93
30.80
31.18
30.06
30.42
28.78
29.11
28.08
28.43
27.41
27.74
3.73
3.74
4.10
4.11
4.49
4.50
50.24
50.80
49.81
50.10
48.50
48.79
50.24
50.80
49.81
50.10
48.50
48.79
4.44
4.36
4.91
4.84
5.35
5.29
56.80
56.90
56.00
56.40
55.46
55.90
56.80
56.90
56.00
56.40
55.46
55.90
4.63
4.40
5.13
4.99
5.63
5.56
59.20
59.50
58.75
59.10
58.45
58.90
59.20
59.50
58.75
59.10
58.45
58.90
4.67
4.42
5.26
5.02
5.74
5.66
21.62
21.87
21.22
21.50
20.64
20.95
Heating Capacity
LEGEND
Cap. Heating Capacity (1000 Btuh) (Includes Indoor--Fan Motor Heat)
db Dry Bulb
kW Total Power Input (Includes Compressor Motor Power Input Outdoor--Fan Motor Input, and Indoor--Fan Motor Input)
rh Relative Humidity
NOTES:
Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it.
70
(21.1)
80
(26.7)
60
(15.6)
_F (_C)
EDB
INDOOR AIR
15.65
15.86
15.29
15.53
14.75
15.01
70
(21.1)
80
(26.7)
60
(15.6)
_F (_C)
EDB
INDOOR AIR
677D----A60 High
677D -- -- A
30.55
30.90
29.86
30.22
29.01
29.39
3.82
3.83
4.19
4.20
4.59
4.59
64.80
65.10
63.56
64.30
62.90
63.50
64.80
65.10
63.56
64.30
62.90
63.50
4.75
4.50
5.44
5.11
6.23
5.78
60_F (15.5_C)
Capacity
Total
MBtuh
System
KW
Total
Integ
33.69
34.08
32.92
33.32
31.99
32.41
29
1200
1370
1200
1370
1200
1370
CFM
9.91
10.02
9.46
9.59
8.82
8.96
1200
1370
1200
1370
1200
1370
CFM
28.14
28.41
27.54
27.81
26.82
27.11
24.66
24.90
24.13
24.37
23.50
23.76
2.91
2.84
3.28
3.21
3.69
3.61
2.55
2.55
2.89
2.89
3.25
3.25
12.36
12.48
11.94
12.08
11.36
11.52
2.64
2.62
2.99
2.97
3.36
3.34
17.58
17.73
17.10
17.29
16.47
16.67
16.14
16.28
15.69
15.87
15.12
15.30
2.72
2.69
3.08
3.05
3.46
3.43
20.92
21.10
20.40
20.61
19.75
19.98
19.07
19.23
18.60
18.79
18.01
18.22
2.78
2.74
3.15
3.10
3.54
3.49
35.04
35.43
34.06
34.46
33.24
33.60
35.04
35.43
34.06
34.46
33.24
33.60
3.03
2.94
3.40
3.31
3.82
3.71
40.62
41.18
39.50
40.01
38.34
38.85
40.62
41.18
39.50
40.01
38.34
38.85
3.13
3.03
3.51
3.40
3.92
3.80
43.31
43.95
42.04
42.63
40.91
41.41
43.31
43.95
42.04
42.63
40.91
41.41
677D -- -- A
3.18
3.07
3.56
3.44
3.99
3.85
13.43
13.56
12.98
13.13
12.35
12.52
Heating Capacity
LEGEND
Cap. Heating Capacity (1000 Btuh) (Includes Indoor--Fan Motor Heat)
db Dry Bulb
kW Total Power Input (Includes Compressor Motor Power Input Outdoor--Fan Motor Input, and Indoor--Fan Motor Input)
rh Relative Humidity
NOTES:
Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it.
80
(26.7)
70
(21.1)
60
(15.6)
_F (_C)
EDB
INDOOR AIR
9.11
9.22
8.70
8.82
8.11
8.24
80
(26.7)
70
(21.1)
60
(15.6)
_F (_C)
EDB
INDOOR AIR
677D----A60 Low
20.36
20.54
19.88
20.08
19.29
19.51
2.81
2.76
3.18
3.13
3.57
3.52
53.58
54.06
51.83
52.74
50.19
51.04
53.58
54.06
51.83
52.74
50.19
51.04
3.38
3.19
3.77
3.62
4.21
4.04
60_F (15.5_C)
Capacity
Total
MBtuh
System
KW
Total
Integ
22.45
22.64
21.92
22.14
21.27
21.51
= tedb --
tlwb
hlwb
*At 75_F (23.8_C) entering dry bulb (Tennessee Valley Authority [TVA] rating
conditions); all other at 80_F (26.6_C) entering dry bulb.
COOLING NOTES:
1. Ratings are net; they account for the effects of the evaporator ---fan motor
power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. The following formulas may be used:
677D -- -- A
1.10 x cfm
tldb
Multiplication Factors
HEATER kW
RATING
240
MULTIPLICATION FACTOR
200
208
.69
.75
230
.92
240
1.00
Nameplate
Input,
High Stage
(Btu/hr)
40000
60000
90000
115000
130000
2001 to
3000*
[610 to 914]
0 to 2000
[0 to 610]
Orifice No. (Qty)
Manifold Press. High / Low
Orifice No. (Qty)
Manifold Press. High / Low
Orifice No. (Qty)
Manifold Press. High / Low
Orifice No. (Qty)
Manifold Press. High / Low
Orifice No. (Qty)
Manifold Press. High / Low
3001 to 4000
[915 to 1219]
4001 to 5000
[1220 to 1524]
5001 to 6000
[1524 to 1829]
44 (2)
45 (2)
48 (2)
48 (2)
48 (2)
3.2 /1.4
3.2 /1.4
3.8 /1.6
3.5 /1.5
3.2 /1.4
44 (3)
45 (3)
48 (3)
48 (3)
48 (3)
3.2 /1.4
3.2 /1.4
3.8 /1.6
3.5 /1.5
3.2 /1.4
38 (3)
41 (3)
41 (3)
42 (3)
42 (3)
3.6 /1.6
3.8 /1.6
3.4 /1.5
3.4 /1.5
3.2 /1.4
33 (3)
36 (3)
36 (3)
36 (3)
38 (3)
3.8 /1.7
3.8 /1.7
3.6 /1.6
3.3 /1.4
3.6 /1.5
31 (3)
31 (3)
33 (3)
33 (3)
34 (3)
3.8 /1.7
3.2 /1.4
3.7 /1.6
3.4 /1.4
3.3 /1.4
*In the U.S.A., the input rating for altitudes above 2000 ft (610m) must be reduced by 4% for each 1000 ft (305 m) above Sea level.
In Canada, the input rating for altitudes from 2001 to 4500 ft (610 to 1372 m) above sea level must be derated by 10% by an authorized gas conversion station or
dealer.
For Canadian Installations from 2000 to 4500 ft (610-1372 m), use U.S.A. column 2001 to 3000 ft (610 to 914 m).
Orifices available through your distributor.
NOTE: Orifice sizes and manifold pressure settings are based on natural gas with a heating value of 1025 Btu/ft3 and a specific gravity of .6.
0 to 2000
[0 to 610]
2001 to 3000*
[610 to 914]
3001 to 4000
[915 to 1219]
4001 to 5000
[1220 to 1524]
5001 to 6000
[1524 to 1829]
55 (2)
56 (2)
56 (2)
56 (2)
56 (2)
10.0/5.0
11.0/6.0
11.0/5.5
11.0/5.0
10.7/4.8
55 (2)
56 (2)
56 (2)
56 (2)
56 (2)
10.0/5.0
11.0/6.0
11.0/5.5
11.0/5.0
10.7/4.8
53 (3)
54 (3)
54 (3)
54 (3)
54 (3)
10.0/5.4
11.0/6.4
11.0/5.9
11.0/5.4
11.0/5.0
51 (3)
52 (3)
52 (3)
53 (3)
53 (3)
10.0/5.4
11.0/5.0
10.6/4.8
11.0/6.1
11.0/5.5
49 (3)
50 (3)
51 (3)
52 (3)
52 (3)
10.0/5.4
11.0/4.8
11.0/4.9
11.0/5.2
11.0/5.0
*In the U.S.A., the input rating for altitudes above 2000 ft (610m) must be reduced by 4% for each 1000 ft (305 m) above Sea level.
In Canada, the input rating for altitudes from 2001 to 4500 ft (610 to 1372 m) above sea level must be derated by 10% by an authorized gas conversion station or
dealer.
For Canadian Installations from 2000 to 4500 ft (610 to 1372 m), use U.S.A. column 2001 to 3000 ft (610 to 914 m).
Use Kit No. CPLPCONV013A00 (0--- 2000 ft [0--- 610 m] above sea level. Use Kit No. CPLPCONV014A00 (2001--- 6000 ft [611--- 1829 m] above sea level.
30
3001 to 4000 ft
915 to 1219 m
4001 to 5000 ft
1220 to 1524 m
5001 to 6000 ft
1524 to 1829 m
High
Stage
Low
Stage
High
Stage
Low
Stage
High
Stage
Low
Stage
High
Stage
Low
Stage
High
Stage
Low
Stage
40000
40000
26000
36000
23400
34400
22300
32800
21300
31200
20300
60000
60000
39000
54000
35100
51600
33500
49200
32000
46800
30400
90000
90000
58500
81000
52700
77400
50300
73800
48000
70200
45600
115000
115000
75000
103500
67500
98900
64500
94300
61500
89700
58500
130000
130000
84500
117000
76100
111800
72700
106600
69300
101400
65900
*In the U.S.A., the input rating for altitudes above 2000 ft (610 m) must be reduced by 4% for each 1000 ft (305 m) above sea level.
In Canada, the input rating for altitudes from 2001 to 4500 (611 to 1372 m) above sea level must be derated by 10% by an authorized gas conversion station or
dealer.
For Canadian Installations from 2000 to 4500 ft (610 to 1372 m), use U.S.A. column 2001 to 3000 ft (610 to 914 m).
Rated Heating Input (Btu/hr), Propane Gas at Installation Altitude Above Sea Level, U.S.A.*
0 to 2000 ft
0 to 610 m
3001 to 4000 ft
915 to 1219 m
4001 to 5000 ft
1220 to 1524 m
5001 to 6000 ft
1524 to 1829 m
High
Stage
Low
Stage
High
Stage
Low
Stage
High
Stage
Low
Stage
High
Stage
Low
Stage
High
Stage
Low
Stage
40000
38000
26000
31700
23400
31700
22300
31700
21300
31200
20300
60000
57000
39000
47500
35100
47500
33500
47500
32000
46800
30400
90000
79000
58500
68900
52700
68900
50300
68600
48000
68600
45600
115000
103000
75000
100400
67500
98900
64500
83000
61500
83000
58500
130000
116000
84500
115500
76100
111800
72700
101300
69300
100400
65900
*In the U.S.A., the input rating for altitudes above 2000 ft (610 m) must be reduced by 4% for each 1000 ft (305 m) above sea level.
In Canada, the input rating for altitudes from 2001 to 4500 (611 to 1372 m) above sea level must be derated by 10% by an authorized gas conversion station or
dealer.
For Canadian Installations from 2000 to 4500 ft (610 to 1372 m), use U.S.A. column 2001 to 3000 ft (610 to 914 m).
31
677D -- -- A
Nameplate
Input, High
Stage
(Btu/hr)
SYSTEM SETTING
0.2
0.3
COMFORT (Default)
24
677D -- -- A
0.9
1.0
525
525
525
525
525
525
525
525
525
600
600
600
600
600
600
600
600
600
EFFICIENCY
613
613
613
613
613
613
613
613
613
613
MAX
700
700
700
700
700
700
700
700
700
700
EFFICIENCY
743
743
743
743
743
743
743
743
743
743
MAX
850
850
850
850
850
850
850
850
850
850
EFFICIENCY
853
853
853
853
853
853
853
853
853
853
MAX
975
975
975
975
975
975
975
975
975
975
EFFICIENCY
963
963
963
963
963
963
963
963
963
963
MAX
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
COMFORT (Default)
60
0.8
600
COMFORT (Default)
48
0.7
525
COMFORT (Default)
42
0.6
MAX
COMFORT (Default)
36
0.5
EFFICIENCY
COMFORT (Default)
30
0.4
EFFICIENCY
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
MAX
1372
1372
1372
1372
1372
1372
1372
1372
1372
1372
0.8
0.9
1.0
SYSTEM SETTING
0.2
0.3
COMFORT (Default)
24
700
700
700
700
700
700
700
700
700
800
800
800
800
800
800
800
800
800
800
EFFICIENCY
875
875
875
MAX
1000
1000
1000
875
875
875
875
875
875
1000
1000
1000
1000
1000
1000
1000
EFFICIENCY
1050
1050
1050
1050
1050
1050
1050
1050
1050
1050
MAX
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
EFFICIENCY
1225
1225
1225
1225
1225
1225
1225
1225
1225
1225
MAX
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
EFFICIENCY
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
MAX
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
COMFORT (Default)
60
875
COMFORT (Default)
48
0.7
700
COMFORT (Default)
42
0.6
MAX
COMFORT (Default)
36
0.5
EFFICIENCY
COMFORT (Default)
30
0.4
EFFICIENCY
1750
1750
1750
1750
1750
1750
1750
1750
1750
1750
MAX
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
Air delivery values are based on operating voltage of 230v, and wet coil. Filter and electric heater will not change air delivery values.
NOTES:
1. See User Interface instructions for more information on Max, Efficiency, and Comfort Settings
2. Efficiency Setting operates at 350 cfm/ton (nominal) and Max Setting operates at 400 cfm/ton (nominal)
32
ROOF-MOUNTING
CURB
ROOF
RETURN-AIR
FLEXIBLE DUCT
677D -- -- A
SUPPLY-AIR
FLEXIBLE DUCT
CEILING
CONCENTRIC DIFFUSER BOX
(FIELD-SUPPLIED)
A09226
A09237
33
APPLICATION DATA
Condensate trap A 2--in. (50 mm) condensate trap must be field
supplied.
Ductwork Secure downflow discharge ductwork to roof curb. For
horizontal discharge applications, attach ductwork to unit with
flanges.
To convert a unit to downflow discharge Units are equipped
with factory--installed inserts in the downflow openings. Remove the
inserts similar to removing an electrical knock--out. Leave on duct
covers to seal the horizontal discharge openings in the unit. Units
70
Based on Entering Indoor Air of 70 Deg. F and Rated CFM
677D -- -- A
60
50
60
48
40
42
36
30
30
24
20
10
0
-20
(-28.9)
-10
0
(-23.3) (-17.8)
10
(-12.2)
20
(-6.7)
30
(-1.1)
40
(4.4)
50
(10)
60
(15.6)
34
ELECTRICAL DATA
V-- PH-- HZ
VOLTAGE
RANGE
INDOOR
FAN MOTOR
IDM
POWER SUPPLY
RLA
LRA
FLA
FLA
FLA
MCA
MOCP
15.3
52.0
0.9
4.3
.21
24.3
35
30040
16.8
70.0
0.9
4.3
.21
26.2
40
30060
16.8
70.0
0.9
4.3
.21
26.2
40
36060
16.7
82.0
0.9
6.8
.21
28.6
40
36090
16.7
82.0
0.9
6.8
.21
28.6
40
42060
21.8
96.0
0.9
6.8
.21
34.9
50
21.8
96.0
0.9
6.8
.21
34.9
50
48090
27.8
96.0
1.5
6.8
.21
43.1
60
48115
27.8
96.0
1.5
6.8
.50
43.1
60
48130
27.8
96.0
1.5
6.8
.50
43.1
60
60090
27.3
118.0
1.9
9.1
.21
45.2
60
60115
27.3
118.0
1.9
9.1
.50
45.2
60
60130
27.3
118.0
1.9
9.1
.50
45.2
60
208/230160
187
Max
OUTDOOR
FAN MOTOR
24040
42090
Min
COMPRESSOR
253
LEGEND
FLA --- Full Load Amps
LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps
MOCP --- Maximum Overcurrent Protection
RLA --- Rated Load Amps
NOTES:
1. In compliance with NEC (National Electrical Code) requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be Power Supply fuse or circuit breaker.
2. Minimum wire size is based on 60_C copper wire. If other than 60_C wire is used, or if length exceeds wire length in table, determine size from NEC
*Heater capacity (kW) based on heater voltage of 208v & 240v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly.
35
677D -- -- A
UNIT
SIZE
677D -- -- A
CONNECTION WIRING SCHEMATIC 230--1--60 GAS INPUTS 040, 060, 090 kBtu/hr
A10217C
36
677D -- -- A
LADDER WIRING SCHEMATIC 230--1--60 GAS INPUTS 040, 060, 090 kBtu/hr
A10217L
37
677D -- -- A
A10219C
38
677D -- -- A
A10219L
39
CONTROLS
Sequence of Operation
When the UI calls for gas heat, the Evolution furnace board performs
a self--check, verifies the pressure switch is open, and starts the
inducer on high speed.
677D -- -- A
Second stage heat pump will run until call for heat is satisfied or for
fifteen minutes. If after 15 minutes the call for heat still exists, the unit
will stage to first stage gas.
For first stage gas the heat pump will be off unless the unit is in
defrost. There is a ten--minute staging timer on first stage gas. If call
for heat still exists after 10 minutes, the system will stage to second
stage gas and run until the call for heat is satisfied.
NOTE: Heat stages are not shortened due to a 5 degree or higher
demand. All stages are utilized for the full allotted time described
above. If the UI determines it is making sufficient progress toward set
point, it may not stage up after the staging timer has elapsed. Pressing
the FAN and TEMPERATURE UP buttons simultaneously defeats
cycle timers. See UI installation instructions for more detail.
If the burner flame is not proved within 2 seconds, the control will
close the gas valve and repeat the ignition sequence up to 3 more
Trials--For--Ignition before going to Ignition--Lockout. Lockout will
reset automatically after 3 hours, by momentarily interrupting 230
VAC power, or by interrupting 24 VAC power at SEC1 or SEC2 to
the furnace board.
40
GUIDE SPECIFICATIONS
PART I -- GENERAL
SYSTEM DESCRIPTION
Outdoor rooftop or ground mounted heat pump unit utilizing a
hermetic, 2--stage scroll compressor for heating and cooling duty
and optional electric heating. Unit shall discharge supply air vertically or horizontally as shown on contract drawings. Outdoor
fan/coil section shall have a draw--thru design with vertical discharge for minimum sound levels.
QUALITY ASSURANCE
A. Unit shall be rated in accordance with AHRI Standards
210/240 and 270.
B. Unit shall be designed in accordance with UL Standard
1995 and ANSI Z21.47.
C. Unit shall be manufactured in a facility registered to ISO
9001 manufacturing quality standard
D. Unit shall be UL listed and c--UL certified as a total
package for safety requirements.
E. Roof curb shall be designed to conform to NRCA
Standards.
F. Insulation and adhesives shall meet NFPA 90A
requirements for flame spread and smoke generation.
G. Cabinet insulation shall meet ASHRAE Standard 62P.
DELIVERY, STORAGE, AND HANDLING
Unit shall be stored and handled per manufacturers recommendations.
PART 2-- PRODUCTS
EQUIPMENT
A. General:
Factory--assembled, single--piece, heat pump. Contained within
the unit enclosure shall be all factory wiring, piping, controls, refrigerant charge (R--410A), and special features required prior to
field start--up.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of phosphated, zinc--coated,
prepainted steel capable of withstanding 500 hrs of salt spray.
2. Normal service shall be through a single removable cabinet
panel.
3. The unit shall be constructed on a rust proof unit base that has
an externally trapped, integrated sloped drain pan.
4. Indoor fan compartment top surface shall be insulated with a
minimum 1/2--in. (13 mm) thick, flexible fiberglass
insulation, coated on the air side and retained by adhesive and
mechanical means. The indoor wall sections will be insulated
with a foil--faced insulation capable of being wiped clean.
Aluminum foil--faced fiberglass insulation shall be used in the
entire indoor air cavity section.
5. Unit shall have a field--supplied condensate trap.
C. Fans:
D. Compressor:
1. Fully hermetic, 2--stage scroll compressors with
factory--installed vibration isolation.
2. Scroll compressors shall be standard on all units.
3. Compressor Protection:
Defrost control shall protect compressor by preventing
short cycling.
E. Coils:
1. Indoor and outdoor coils shall have aluminum plate fins
mechanically bonded to seamless copper tubes with all joints
brazed.
2. Tube sheet openings shall be bellied to prevent tube wear.
F. Refrigerant Metering Device:
Refrigerant metering device shall be of the single body,
fixed orifice feed type (outdoor) and TXV (indoor).
G. Filters:
Filter section shall consist of field--installed, throw--away,
1--in. (25 mm) thick fiberglass filters of commercially
available sizes.
H. Heating Section:
1. Induced--draft combustion type with energy saving direct
spark ignition system and redundant main gas valve.
2. Pressure switch ensures adequate airflow for combustion
from induced draft motor.
3. The heat exchangers shall be constructed of 409 stainless
steel for corrosion resistance.
4. Burners shall be of the in--shot type constructed of
aluminum coated steel.
5. All gas piping and electric power shall enter the unit cabinet
at a single location.
I. Controls and Safeties:
1. Unit controls shall be complete with self--contained low
voltage control circuit.
2. Units shall incorporate an internal compressor protector that
provides reset capability.
3. Unit shall provide high-- and low--/loss--of--charge pressure
safety protection.
J. Operating Characteristics:
1. Unit shall be capable of starting and running at 125F
(51.6_C) ambient outdoor temperature, exceeding maximum
load criteria of AHRI Standard 240.
2. Compressor shall be capable of operation down to 55F
(12.7_C) ambient outdoor temperature in cooling and --10F
(--23F) in heating.
3. Unit shall be capable of low--ambient cooling from 55_F
(12.7_C) down to 0_F (--17.7_C) ambient outdoor
temperature with low--ambient cooling enabled on the UI.
K. Electrical Requirements:
All unit power wiring shall enter unit cabinet at a single location.
L. Motors:
1. Compressor motors shall be of the refrigerant--cooled type
with line--break thermal and current overload protection.
2. All fan motors shall have permanently lubricated bearings and
inherent automatic--reset thermal overload protection.
677D -- -- A
677D -- -- A
O. Special Features:
1. Coil Options:
Shall include factory--installed optional tin--plated indoor
coil hairpins.
2. Evolution User Interface:
To provide for two--stage heat pump heating, two--stage cooling, and electric (auxiliary) heat, in addition to manual or automatic changeover and indoor fan control.
E2012 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231
Printed in U.S.A.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.