What is boiler ?
What is boiler ?
What is a boiler ? When water is heated in a boiler, it begins to absorb energy. Depending on the pressure in the boiler, the water will evaporate at a certain temperature to form steam. The steam contains a large quantity of stored energy which will eventually be transferred to the process or the space to be heated
Steam turbine
Drum level measurement
Heat exchanger
3
Types of boilers
Boiler drum
Application overview
Steam Drum Level is both a critical and difficult measurement to make. Control of the water level in the drum must be precise. A water level that is too high can result in water carryover into the steam piping. A level that is too low can expose the generating tubes (down comers), preventing the water in the drum from cooling the furnace tubes, possibly damaging them. Several factors make this measurement difficult to obtain. The steam drum itself may not be perfectly level, and even at steady state conditions, considerable turbulence in the drum can cause the level to fluctuate. In addition, a changing rate of water inflow and steam outflow adds to the potential for measurement error.
Drum level measurement 7
Application overview
Measurement of boiler steam drum level using a differential pressure transmitter must take into account certain physical properties of the fluid.
The Steam drum contains a two-phase mixture of water and steam at saturation conditions. The densities of water and steam vary with saturation temperature or pressure. The density of saturated steam above water must be considered, as well as the density of saturated water in the drum.
This technical note offers a method for calibrating transmitters that takes into account these factors.
Water Property
320F
0.01602 ft3
= 62.42 lbm/ft3
Drum level measurement 9
Water Property
= 61.73 lbm/ft3
Drum level measurement 10
Water Property
= 59.81 lbm/ft3
Drum level measurement 11
Saturated Water
Boiling point
2120F
0.01672 ft3
12
Saturated Water
Water and Steam bubble swell Boiling Boiling With Bubble 1 lbm Pressure is increased 2120F 2120F 0.01672 ft3
13
Saturated Water
Water and Steam bubble more swell 2120F 0.01672 ft3
14
Saturated Water
Water and Steam bubble shrink 2120F 0.01672 ft3
1 lbm
15
PH
PL
16
18
20
Calibration range
% 100 0 Level (m) 0.6 0 D/P (Pa) -191.40 -5825.33 Signal (mA) 20 4
Finally, check the zero elevation and span against the transmitter specifications to ensure the selected transmitter can be calibrated to the required values.
21
Calibration range
Level % 100 75 50 25 0 DBR (m) 0.60 0.45 0.30 0.15 0.00 Range (m) 0.30 0.15 0.00 -0.15 -0.30 PH (Pa) 5633.93 4225.44 2816.96 1408.48 0.00 PL (Pa) 5825.33 5825.33 5825.33 5825.33 5825.33 DP (Pa) O/P (mA) Controller (m) 0.600 0.450 0.300 0.150 0.000 -191.40 20.000 -1599.88 -3008.36 -4416.85 -5825.33 16.000 12.000 8.000 4.000
22
Normalization Unit
Percent (0 - 100%) to level(0 0.6 m) At 50 %, what is Level ? Solution sensitivity = span output / span input = 0.6/100 = 0.006 m / % At 50 % level = 0.006 50 = 0.3 m
23
Normalization Unit
Level 0 0.6 m to DP (- 5825.33 (-191.40)) At 0.3 m, What is differential pressure ? Solution sensitivity = span output / span input = (-191.40 (- 5825.33)) / (0.6 0) = 9389.88 Pa/m At 0.3 m P = 9389.88 (0.3-0) + (- 5825.33) = - 3008.36 Pa
24
Normalization Unit
DP (-191.40 (- 5825.33)) to Signal (4-20 mA) At (- 3008.36 Pa), What is Signal ? Solution sensitivity = span output / span input = (20-4) / (-191.40 (- 5825.33)) = 2.84 10-3 mA/Pa At (- 3008.36 Pa) signal = 2.84 10-3 (- 3008.36 - (- 5825.33)) + (4) = 12 mA
25
Level Transmitter
Transmitter Signal 12 mA ,What is water in drum level ? Solution sensitivity = span output / span input = (20-4) / (0.6 0) = 26.67 mA/m At 12 mA controller = [(12-4)/26.67] + (0) = 0.3 m
26
Level & DP
P
-5825.33 -4416.85 -3008.36 -1599.88 -191.40 0% 0 25% 0.15 50% 0.30 75% 0.45 100 %
Level
0.6 m
27
DP Transmitter signal
Level (m) mA
0.60 0.45 0.30 0.15 0.0
%
75% 50% 25% 0% 0% 25% 50% 75% 100 % -191.40 -5825.33 -3008.36 -1599.88 -4416.85
20 100% 16 12 8 4
P (Pa)
28
29
PH
PL
PH
PL
Operating condition Temp = 353 C Pressure = 2498.1 Psia P = - 3819.83 Pa Signal = ???? mA
30
Normalization Unit
DP (-191.40 (- 5825.33)) to Signal (4-20 mA) At (- 3819.83 Pa), What is Signal ? Solution sensitivity = span output / span input = (20-4) / (-191.40 (- 5825.33)) = 2.84 10-3 mA/Pa At (- 3819.83 Pa) Signal = 2.84 10-3 (- 3819.83 - (- 5825.33)) + (4) = 9.69 mA
31
Level Transmitter
At Transmitter Signal 9.69 mA ,What is water in drum level ? Solution Sensitivity = span output / span input = (20-4) / (0.6 0) = 26.67 mA/m At 12 mA Controller = (9.69-4)/26.67 + (0) = 0.214 m
32
Error = 0.214 - 0.3 = - 0.086 m Water Level at 35% from 50 % or reduce 15%
33
DP Transmitter signal
Level (m) mA
0.60 0.45
%
75% 50% 25% 0% 0% 25% 50% 75% -5825.33 -3008.36 -3819.83
Drum level measurement 34
20 100% 16
100 % -191.40
P (Pa)
36
Calibration range
Level % 100 75 50 25 0 DBR (m) 0.60 0.45 0.30 0.15 0.00 range (m) 0.30 0.15 0.00 -0.15 -0.30 PH (Pa) 2577.65 1933.23 1288.82 644.41 0.00 PL (Pa) 5108.65 5108.65 5108.65 DP (Pa) -2531.00 -3175.41 -3819.82 Output Controller (mA) (m) 13.356 11.526 9.696 7.865 6.035 0.351 0.282 0.214 0.145 0.076
37
Density compensate
From differential pressure formula P = g.h(WD- S) - g.H(W - S) Liquid level in boiler drum
h=
P + gH(w-s) g(WD-s)
38
Density compensate
signal Controller or DCS Card 4-20mA to steam table (WD,S) 4-20mA to P
S WD
39
Exercise
Condensing pot Pd Saturated Steam S 0 Saturated water WD h W
What is calibration range of D/P transmitter at operating condition 200 C and wet leg temperature 43.333 C Where H = 1000 mm h = 700mm V = 150 mm
PH
PL
40
41
42
43
44
45
46
47
48