DSR-12/20 DSRT-20 GENERAL INFORMATION EXPLODED VIEWS - PARTS LISTS

ENGLISH

Attention! 3 minutes delay on all units with Alfa-14 controller. When starting or restarting the unit, it will take 3 minutes before the compressor and the fan will start running. Achtung! Wenn Sie das Gert (wieder) in Betrieb setzen, wird bei allen Gerten, die mit einem Zeitschaltuhr Alfa-14 ausgestattet sind, der Anlauf des Kompressors und der des Ventilators um 3 Minuten verzgert. Attention! Quand vous mettez ou remettez votre appareil en fonctionnement, le compresseur et le ventilateur de tous les appareils equips dune horloge lectronique Alfa-14 commencent fonctionner aprs 3 minutes. Attentie! Wanneer u het apparaat wilt (her)starten en het apparaat is uitgevoerd met een Alfa-14 tijdschakelaar, dan duurt het 3 minuten voordat compressor en ventilator starten.

SAFETY
For safety reasons, read this information carefully before operating. Persons who are not familiar with this type of product must not use it. We strongly recommend keeping this information in a safe place for future reference.
>10

This appliance must be earthed. The unit is designated for indoor operation. Refer to the rating plate for voltage and power input. The installation must be in accordance with regulations of the country where the installation is performed. The minimum distance between air inlet(s) and/or air outlet(s) and any object must be 40 cm. * The unit is safe. It has been approved by many safety institutions around the world. However, as with other electrical appliance, use it with care. * Keep out of reach of children. * Do not clean the unit by spraying it or immersing it in water. * Do not insert any object into an opening of the unit. * Disconnect from the mains before cleaning the unit or any of its components. * Never connect to an electrical outlet using an extension cord. If an outlet is not available, one should be installed by a licenced electrician. * Any service other than regular cleaning or lter replacement should be performed by an authorized service representative. Failure to do so could result in a loss of warranty. * When the unit is placed in a (swimming) pool, connect to the mains via a transformer or a breaking switch, conform the regulations regarding electrical installations.

AMCOR DEHUMIDIFIERS
You cant control humidity and haze outdoors. But in an indoor swimming pool and other humid interior spaces where hot stu y air, steamy windows and walls are frequent phenomena, you can. Thats why you need Amcor. Amcors dehumidi ers clear the air in damp interior spaces. Condensation is removed from windows, walls and ceilings. Vaporous stu y air is drawn o , clean air is pumped back in. You simply set the dial and the air humidity remains at the required level. And, the Amcor dehumidi er is an energy saver. Water evaporating from a swimming pool, bathroom, archive, store or from wet objects and surfaces increases the humidity of the air and creates the hazy and stu y air often found in the hall. At the same time water condenses on the cooler parts in the hall: windows, walls, ceilings, etc. Water condensation is not only an aesthetic defect, it can, in the long run, cause structural damage. There are two methods for drying the air in humid spaces: - by ventilation, - by heat pumps. The Amcor dehumidi er is designed as a heat pump and has, through energy saving, a considerable advantage over a ventilation system.

HOW THE AMCOR DEHUMIDIFIER WORKS


The fan (1) sucks the humid air through the evaporator (2). There the air is cooled and the moisture in the air condenses into water. This water is collected in the tray (3) and drained away through the sump and piping. The compessor (5) pumps the heat, which has been extracted from the air, into the condensor (6). There, this heat is once again released, and absorbed by the dry air. The ready wired control box monitors and controls the operation.

2 4

ELECTRICAL WIRING
The unit can be supplied with a cord and an earthed plug. If it ever becomes necessary to replace this plug, be sure to use an earthed plug suitable for the power supply in your area and conform your national safety standard. The wires of the cable are coloured in accordance with the standard electrical code. Blue Brown Green/Yellow Neutral Live Earth

The blue (neutral) wire should be connected to the terminal in the plug marked N or coloured black. The brown (live) wire should be connected to the terminal in the plug marked L or coloured red. The green/yellow (earth) wire should be connected to the terminal in the plug marked E or coloured green or marked with this symbol: The unit must be connected to the power supply with the appropriate leads. The cord should pass through holes with rubber grommets. Properly fused disconnect switches must be installed between the unit and the power source. The unit must be wired with an isolation (mains) switch accessible from outside the wet area in which the unit is installed, to comply with IEE regulations.

MAINTENANCE
The appliance is actually maintenance free, exept in cases of soiling. In this case the lter has to be cleaned.

AMCOR INDOOR SWIMMING POOL ROOM DEHUMIDIFIERS


The Amcor pool dehumidi er is a ready to install, transportable, appliance. It can be mounted on a wall or ceiling console in the pool room or even over a shower booth. It may be mounted in adjoining rooms and connected by ducts to the pool room. Amcor has not adapted normal room air-conditioners for use in indoor swimming pools, but has developed pool dehumidi ers particulary for this purpose. The compressor therefore matches exactly the capacity of the evaporator, thus achieving the optimal balance between e ciency and power consumption. The pool dehumidi er is controlled by a humidistat which operates at a low (=safety) voltage of 24V.

Model DSR

The relative humidity in an indoor swimming pool can be adjusted between 50-80% when an external hygrostat is used.

INSTALLING THE AMCOR MODEL DSR/DSRT


The minimum distance between inlet(s) and/or outlet(s) and any object must be 40 cm. Installation of the dehumidi er is easy, as the unit is built on a base and slides out of the housing. The individual parts are logically arranged and can be inspected. First, remove the screws of the frame with louvers. Remove the screws on the base. Now the unit can be taken out the housing. Prepare a suitable console and mount it on the wall. Mount the housing on the console and attach it by fastening its base with screws to the legs (which should preferably be lagged with a vibration dampening material). Insert the unit into the housing, fasten the housing to the base and attach the louvered frame in front of the housing. Attach a 3/4 I.D. exible pipe to the drain nipple located at the back of the dehumidi er.

ATTACHMENT DIMENSIONS FOR INSTALLATION IN DUCT

MAINTENANCE DSR-12/20
The appliance is actually maintenance free, exept in cases of soiling. In this case the lter has to be cleaned. To take the lter out, unscrew 2 screws fastening the lter grid, located at the back. Swing the grid towards you and up in order to get access to the lter. Remove the lter. Hold it under a water tap and ush it clean with a stream of water. Let the trapped water drip o the lter fabric and replace the dried lter in reverse order.

AIR INLET

AIR OUTLET

AIR OUTLET
260 270 22 68 316

AIR INLET
530

OPERATING RANGE DSR-12/20


Max. working temperature 35 C Min. working temperature 5 C Relative humidity 40-100%

453

665

365 DRAIN 3/4" O.D.

EXPLODED VIEWS / DSR-12/20


6 22 8

14 7 2 13 3 4 1 5 15 36 31 30 39 33 40 11 29 12 32 35

17 23 18 10

19

20

21

24

25

26

27

28

38

16

TECHNICAL SPECIFICATIONS / DSR-12/20 AND DSRT-20


M O DEL E LE C TR I C A L S U PPLY FR E Q U E N C Y MOISTURE REMOVAL AT 30 65-75% R.H. PO W E R C O N S U M PTI O N C URRE N T R E FR IG E R A N T R E FR IG E R A N T C H A R G E A I R D E LI V E R Y M A X . FA N S PE E D S W I M M I N G PO O L S U R FA C E N E T W E IG H T LE N G TH W I D TH H E IG H T 5 1300 W 6.0 A R4 0 7 C 1300 g 1 3 0 0 m3 /h 2 3 5 m2 6 8 kg 6 8 0 mm 6 6 5 mm 4 5 3 mm
(or R22)

1 2 DSR 230 V 5 0 Hz C 2 . 7 - 3 . 6 l/ h

2 0 DSR 230 V 5 0 Hz 4 . 5 - 5 . 6 l/ h 2600 W 12.0 A R407C 1650 g 1500 m 3 /h 2 50 m 2 7 8 kg 6 8 0 mm 6 6 5 mm 4 5 3 mm


(or R22)

2 0 DSR T 3 8 0 V ( 3 p ha s e ) 5 0 Hz 4 . 5 - 5 . 6 l/ h 2600 W 3 X4 A R407C 1650 g 1500 m 3 /h 2 50 m 2 7 8 kg 6 8 0 mm 6 6 5 mm 4 5 3 mm


(or R22)

PARTSLIST / DSR-12/20
PA R T N O . A436844 468038 A436536 A436334 A434632 A434642 A414305 A342695 A528644 508002 68038 A436324 A434664 A492474 A342705 A434276 A434576 A326504 292026 A342725 X1 0 0 2 1 1 0 5 4 2 X1003140542 X1 0 0 3 1 9 0 5 6 2 X1004190562 274312 274314 271317 271283 271284 A328675 D E PE N D O F C O M P. D E PE N D O F C O M P. O 81071 O 81075 O O 4025 295060 294012 294010 D E PE N D O F C O M P. 2 7 5 0 3 1 -3 4 429171 482301 386117 346518 508027 326101 275016 2 1 1 1 1 1 6 4 1 1 1 1 1 1 1 1 1 Q TY. 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 PA R T N A M E C A S IN G G RID A I R - F I LTE R FR A M E E V A PO R A TO R D S R - 1 2 E V A PO R A TO R D S R - 2 0 TO P C O V E R W A LL R I G H T LO U V E R S ( I N ) C LA M P LO U V E R S ( O U T) FR O N T C O V E R - C O N TR O L B O A R D C O N TR O L B O A R D W A LL LE F T C A PI LA R Y D S R - 1 2 C A PI LA R Y D S R - 2 0 C H A S S IS S TR A I N E R - D I S TR I B U TO R LE F T B U LK H E A D E V A PO R A TO R D S R - 1 2 EVAPORATOR DSR-20 C O N DE N S E R DS R- 1 2 CONDENSER DSR-20 C O M PR E S S O R D S R - 1 2 C O M PR E S S O R D S R - 2 0 - 1 PH C O M PR E S S O R D S R - 2 0 - 3 PH FA N M O TO R + H O U S I N G D S R - 1 2 FA N M O TO R + H O U S I N G D S R - 2 0 D R A I N PA N RU BBE R G RO M M E T S LE E V E W A SHER S PR I N G W A S H E R N UT LE V E R S W I TC H G RO M M E T G RO M M E T C A PA C I TO R - C O M PR E S S O R TE R M I N A L C O N TA C TO R D S R - 3 PH TR A N S F O R M E R D E F R O S T C O N TR O L S E A L F O A M S TR I P LI N E C O R D C LI P FU S E 1 A TE R M I N A L F U S E 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 22 21 20 16 17 18 19 6 7 8 9 10 11 12 13 14 15 NO. 1 2 3 4 5

MOISTURE REMOVAL / DSR-12

AMCOR DSR 12 - MOISTURE REMOVAL AT DIFFERENT ROOM TEMP. EN R.H.% (kg water/24h) RELATIVE HUMIDITY % 85 80 75 70 65 60 ROOM TEMP. C 15 20 24 25 26 27 28 29 30 32 35 41 57 73 77 80 84 88 92 96 100 104 37 52 66 70 73 77 80 84 87 91 94 34 48 60 63 67 70 73 76 79 82 86 31 43 55 58 60 63 66 69 72 75 78 28 38 49 51 54 56 59 62 64 67 69 25 34 43 46 48 50 52 55 57 59 62

55

50

23 30 39 41 43 45 47 49 51 53 55

17 27 34 36 38 40 42 43 45 47 49

MOISTURE REMOVAL / DSR-20, DSRT-20

AMCOR DSR 20 - MOISTURE REMOVAL AT DIFFERENT ROOM TEMP. EN R.H.% (kg water/24h) RELATIVE HUMIDITY % 85 80 75 70 65 60 ROOM TEMP. C 15 20 24 25 26 27 28 29 30 32 35 69 96 121 128 134 141 147 153 160 166 173 62 87 110 116 122 128 134 139 145 151 157 57 79 100 106 111 116 121 127 132 137 143 52 72 91 96 101 106 110 115 120 125 130 46 64 81 85 90 94 98 103 107 111 116 41 57 72 76 80 84 87 91 95 99 103

55

50

23 51 64 68 71 74 78 81 85 88 92

17 45 57 60 63 66 69 72 75 78 82

WIRING DIAGRAM / DSR-12

3 1

GREEN/YELLOW

BLACK

COMP.
WHITE R RED S

FAN MOTOR

RED WHITE WHITE BLACK BROWN

GREEN/YELLOW

GREEN/YELLOW

CAPACITOR

CAPACITOR WHITE

230V/50HZ

GREEN/YELLOW

GREEN/YELLOW

SWITCH

BLUE

BLUE BLUE

LINE

BROWN

BLACK BLACK

0 GND

DEFROST TIMER ALFA - 14/1


SNS1 SNS2 HYG

TO CONDENSOR

TO EVAPORATOR

TO HYGROSTAT

WIRING DIAGRAM / DSR-20

GREEN/YELLOW BLACK

COMP.
R

FAN MOTOR
S RED BLACK

GREEN/YELLOW GREEN/YELLOW

WHITE

RED CAPACITOR

WHITE

BROWN

CAPACITOR

BLUE SWITCH 230V/50HZ GREEN/YELLOW GREEN/YELLOW

BLUE

BLUE BLUE

LINE

BROWN

BLACK BLACK

0 GND

DEFROST TIMER ALFA - 14/1


SNS1 SNS2 HYG

TO CONDENSOR

TO EVAPORATOR

TO HYGROSTAT

WIRING DIAGRAM / DSRT-20

GREEN/YELLOW GREEN/YELLOW GREEN/YELLOW GREEN/YELLOW

CONTACTOR
380V/50HZ L3 L2 L1 VIOLET BROWN BLACK RED BROWN BLACK BLACK LINE N BLUE BLUE BLUE BLACK A2 A1 BLUE WHITE BLUE GREEN/YELLOW BLUE BLACK BLACK BLACK BLACK RED 2 4 6 14 1 3 5 13 RED BLACK BROWN RED BROWN BLACK

COMP.

FAN MOTOR

CAPACITOR

SWITCH
P F M 0 GND

DEFROST TIMER ALFA - 14/1


SNS1 SNS2 HYG

TO CONDENSOR

TO EVAPORATOR TO HYGROSTAT