Product naming
e.g. L M U 24 -SR
Torque General Damper Actuator 40Nm 20Nm 10Nm 5Nm 2Nm Mechanical Fail-Safe Damper Actuator 30Nm 20Nm 10Nm 4Nm 2Nm Electronic Fail-Safe Damper Actuator 40Nm General Damper Actuator Mechanical Fail-Safe Damper Actuator Electronic Fail-Safe Damper Actuator New Generation General Damper Actuator for Asia Pacific Power supply AC/DC 24V AC 100...240V (AC 230V for Mechanical Fail-Safe Damper Actuator) Function General Damper Actuator Open/Close, 3-point Open/Close (only for CMU230..) Modulating DC 2(0)...10V Auxiliary switch Form fit Terminal connection Mechanical Fail-Safe Damper Actuator Open/Close Modulating DC 2(0)...10V 3-point Auxiliary switch Electronic Fail-Safe Damper Actuator 3-point Blank -RES -SR -S -F -T Blank -SR -3 -S,-S2 -MF 24 230 G S N L C E S N L T G M F K
For customising types of damper actuators, please contact your nearest Belimo sales representative.
2Nm
5Nm
10Nm
20Nm
40Nm
CMU..
CMU24(-F8/-F10)(-T) CMU230(-F8/-F10) CMU230(-F8/-F10)-RES*
LMU..
LMU24(-F/-T) LMU24-S LMU230 LMU230-S
NMU..
NMU24(-F/-T) NMU24-S NMU230 NMU230-S
SMU..
SMU24(-F/-T) SMU24-S SMU230 SMU230-S
GMU..
GMU24* GMU230*
GMU24-SR
150s 14...25.2mm Max. 45dB(A) Gear disengaging by push button Cable 1m (-T: Terminal) Selected by switch Max. 95, can be limited at both ends with mechanical adjustable end stops Mechanical, plug-on IP54 (-T: IP20) CE according to 89/336/EEC CE according to 73/23/EEC -30...+50C -40...+80C 5...95% RH, non-condensing
* Only Open/Close, no 3-point. ** CMU24-SR-R: Control signal 2(0)V at the right side, and the left side is available on request. *** For 230V models.
4Nm
8Nm
16Nm
LMQU..
LMQU24
NMQU..
NMQU24
SMQU..
SMQU24
SMDU..
SMDU230
LMQU24-SR 2.5s
Disengaging the gearing latch by means of a push button, self-resetting Cable 1m Selected by switch Max. 95, can be limited at both ends with mechanical adjustable end stops Mechanical, plug-on IP54 CE according to 2004/108/EC CE according to 2006/95/EC -30+40C (without restrictions); +40+50C (with restrictions) -40+80C 5...95% RH, non-condensing
V5.01. 01.2013 Subject to modification
2Nm
4Nm
TF..
TF24 TF24-S TF230 TF230-S TF24-3
LF..
LF24 LF24-S LF230 LF230-S LF24-3
TF24-SR <75s* <25s 6...12mm Open/Close max. 50dB(A) Modulating and 3-point max. 35dB(A)
LF24-SR 40-75s* <20s 8...16mm Open/Close max. 50dB(A) Modulating and 3-point max. 30dB(A)
62dB(A) Cable 1m Selected by mounting L/R Max. 95 Yes Yes IP42 CE according to 89/336/EEC CE according to 73/23/EEC -30...+50C -40...+80C 5...95% RH, non-condensing IP54
* LF24-3 and all -SR types are 150s. ** TF24-3 nominal voltage is AC 24V, TF230 nominal voltage is AC 100...240V. *** For 230V models.
10Nm
20Nm
30Nm
NFU..
NFU NFU-S2 -
SFU..
SFU SFU-S2 -
EFU..
EFU24-S2 EFU230-S2
NFU24-SR
NFU24-SR
EFU24-SR Open/Close <75s; modulating 150s <20s...60s 12...26.7mm / 12...25.2mm Open/Close max. 55dB(A) / Modulating max. 45dB(A) Max. 71dB(A)
Open/Close 75s; modulating 150s <20s...60s 10...12mm / 14...25.4mm Open/Close max. 45dB(A) / Modulating max. 40dB(A) Max. 62dB(A)
Electrical connection Direction of rotation Angle of rotation Mechanical end stops Position indicator Degree of protection EMC LVD* Ambient temperature Non-operation temperature Humidity
* For 230V only.
Cable 1m Selected by mounting L/R Max. 95 Yes Yes IP54 CE according to 89/336/EEC CE according to 2006/95/EC -30...+50C -40...+80C 5...95% RH, non-condensing
40Nm
GKU..
GKU24 -
150s 35s
GKU24-MF 90...150s 35s 12...26.7mm / 12...25.2mm Max. 53dB(A) Max. 61dB(A) Cable 1m Selected by mounting L/R Max. 95 Yes Yes IP54 CE according to 2004/108/EC -30...+50C -40...+80C 5...95% RH, non-condensing
V5.01. 01.2013 Subject to modification
CMU24(-F8/-F10)(-T)
For operation of air control dampers in HVAC system Torque: Nominal voltage: Control: 2Nm AC/DC 24V Open/Close or 3-point
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connection -T Cable AC 24V 50/60Hz, DC 24V AC/DC 19.2...28.8V 0.5W @ nominal torque / 0.2W @ holding 1VA Terminals for 3x1.5mm2 CU wire or 3x1.5mm2 CU litz wires 1m, 3x0.75mm2 2Nm Dependent on electrical installation Gear disengagement by magnet Endless Fixed 315 or 0... 287.5 with mechanical end stops, can be adjusted in 2.5 increments 75s Max. 35dB(A) Mechanical, pluggable with integrated magnet for gear disengagement III (safety extra-low voltage) IP20 IP54 CE according to 89/336/EEC Type 1 (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free See Dimensions 6...12.7mm 8x8mm 10x10mm 0.13...0.22kg
Functional data
Torque Direction of rotation Manual override Angle of rotation no limiters With limiters Running time Sound power level Position indicator
Working conditions
Protection class Degree of protection (-T) Cable EMC Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
Dimensions / weight
Dimensions [mm]
CMU24
28
CMU24-T
28
CMU24-F8-T
20
16
158 28 130 28
14 9
16
149
12 1
28
121
56
56
56
16
CMU24-SR-R
For operation of air control dampers in HVAC system Torque: Nominal voltage: Control signal: Position feedback: 2Nm AC/DC 24V DC 2(0)...10V DC 2...10V
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connecting cable AC 24V 50/60Hz, DC 24V AC/DC 19.2...28.8V 1W @ nominal torque / 0.5W @ holding 2VA Cable 1m, 4x0.75mm2 2Nm DC2(0)10V @ input impedance 100k DC 210V @ max. 1mA 5% Y=0V at right end stop position Gear disengagement by magnet Max. 95, adjustable by mechanical stops 75s Max. 35dB(A) Mechanical, pluggable with integrated magnet for gear disengagement III (safety extra-low voltage) IP54 CE according to 89/336/EEC Type 1 (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free See Dimensions 6...12.7mm 0.22kg
Functional data
Torque Control signal Y Position feedback signal U Position accuracy Direction of rotation Manual override Angle of rotation Running time Sound power level Position indicator
Working conditions
Protection class Degree of protection EMC Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
Dimensions / weight
Dimensions [mm]
28
158 28 130
V5.01. 01.2013 Subject to modification
56
16
CMU230(-F8/-F10)
For operation of air control dampers in HVAC system Torque: Nominal voltage: Control: 2Nm AC 100...240V Open/Close or 3-point
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connecting cable AC 100...240V 50/60Hz AC 85...265V 1.5W @ nominal torque / 1W @ holding 3VA Cable 1m, 3x0.75mm2 2Nm Dependent on electrical installation Gear disengagement by magnet Endless Fixed 315 or 0... 287.5 with mechanical end stops, can be adjusted in 2.5 increments 75s Max. 35dB(A) Mechanical, pluggable with integrated magnet for gear disengagement II (Totally insulated) IP54 CE according to 2004/108/EC CE according to 2006/95/EC Type 1 (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free See Dimensions 6...12.7mm 8x8mm 10x10mm 0.22kg
Functional data
Torque Direction of rotation Manual override Angle of rotation no limiters with limiters Running time Sound power level Position indicator
Working conditions
Protection class Degree of protection EMC Low voltage directive Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
Dimensions / weight
Dimensions [mm]
CMU230 CMU230-F8
28
16
20
158 28 130 28
158 130
56
56
16
CMU230(-F8/-F10)-RES
For operation of air control dampers in HVAC system Torque: Nominal voltage: Control: 2Nm AC 230V Open/Close
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connecting cable AC 230V 50Hz AC 207...253V 1.5W @ nominal torque / 1.5W @ holding 8.5VA Cable 1m, 3x0.75mm2 2Nm Dependent on electrical installation Gear disengagement by magnet Endless Fixed 315 or 0... 287.5 with mechanical end stops, can be adjusted in 2.5 increments 75s Max. 35dB(A) Mechanical, pluggable with integrated magnet for gear disengagement II (Totally insulated) IP54 CE according to 2004/108/EC CE according to 2006/95/EC Type 1 (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free See Dimensions 6...12.7mm 8x8mm 10x10mm 0.22kg
Functional data
Torque Direction of rotation Manual override Angle of rotation no limiters with limiters Running time Sound power level Position indicator
Working conditions
Protection class Degree of protection EMC Low voltage directive Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance Dimensions (LxWxH) Shaft Form fit (-F8) (-F10) Weight
Dimensions / weight
Dimensions [mm]
CMU230-RES
28
CMU230-F8-RES
16
20
158 28 130 28
158 130
16
10
56
56
LMU24(-S/-F/-T)
For operation of air control dampers in HVAC system Torque: Nominal voltage: Control: 5Nm AC/DC 24V Open/Close or 3-point
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Auxiliary switch (-S) Connection -motor -auxiliary switch (-S) -terminals (-T) AC 24V 50/60Hz, DC 24V AC/DC 19.2...28.8V 1W @ nominal torque / 0.2W @ holding 1.5VA 1 SPDT, 1mA...3(0.5)A, AC 250V, adjustable Cable 1m, 3x0.75mm2 Cable 1m, 3x0.75mm2 Max. 3x1.5mm2 5Nm Selectable by switch Gearing latch disengaged by push button, self-resetting Max. 95, adjustable by mechanical stops 150s Max. 35dB(A) Mechanical, remote visible III (safety extra-low voltage) IP54 IP20 CE according to 89/336/EEC Type 1 (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free See Dimensions Min. 37mm LMU24(-S/-T) LMU24-F 6...20mm 8x8mm 0.5kg
Functional data
Torque Direction of rotation Manual override Angle of rotation Running time Sound power level Position indicator
Working conditions
Protection class Degree of protection LMU24(-S/-F) LMU24-T EMC Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
Dimensions / weight
Dimensions [mm]
33
5.2
33
5.2
33
11
LMU24-SR
For operation of air control dampers in HVAC system Torque: Nominal voltage: Control signal: Position feedback: 5Nm AC/DC 24V DC 2(0)...10V DC 2...10V
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connecting cable AC 24V 50/60Hz, DC 24V AC/DC 19.2...28.8V 1W @ nominal torque / 0.4W @ holding 2VA Cable 1m, 4x0.75mm2 5Nm DC 2(0)...10V @ input impedance 100k DC 210V max. 1mA 5% Selectable by switch Gearing latch disengaged by push button, self-resetting Max. 95, adjustable by mechanical stops 150s Max. 35dB(A) Mechanical, remote visible III (safety extra-low voltage) IP54 CE according to 89/336/EEC Type 1 (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free See Dimensions 6...20mm 0.5kg
Functional data
Torque Control signal Y Position feedback signal U Position accuracy Direction of rotation Manual override Angle of rotation Running time Sound power level Position indicator Protection class Degree of protection EMC Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance Dimensions (LxWxH) Shaft Weight
Working conditions
Dimensions / weight
Dimensions [mm]
33
5.2
12
LMU230(-S/-F)
For operation of air control dampers in HVAC system Torque: Nominal voltage: Control: 5Nm AC 100...240V Open/Close or 3-point
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Auxiliary switch (-S) Connection -motor -auxiliary switch (-S) AC 100...240V 50/60Hz AC 85...265V 1.5W @ nominal torque / 0.5W @ holding 3.5VA 1 SPDT, 1mA...3(0.5)A, AC 250V, adjustable Cable 1m, 3x0.75mm2 Cable 1m, 3x0.75mm2 5Nm Selectable by switch Gearing latch disengaged by push button, self-resetting Max. 95, adjustable by mechanical stops 150s Max. 35dB(A) Mechanical, remote visible II (Totally insulated) IP54 CE according to 89/336/EEC CE according to 73/23/EEC Type 1 (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free See Dimensions Min. 37mm LMU230(-S) LMU230-F 6...20mm 8x8mm 0.55kg
Functional data
Torque Direction of rotation Manual override Angle of rotation Running time Sound power level Position indicator
Working conditions
Protection class Degree of protection EMC Low voltage directive Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance Dimensions (LxWxH) Shaft length Shaft Weight
Dimensions / weight
Dimensions [mm]
LMU230(-S) LMU230-F
61
47
47
116
100.5
20
66
66 30 5.2
22
94
41
22
94
41
33
61
13
LMU230SR
For operation of air control dampers in HVAC system Torque: Nominal voltage: Control signal: Position feedback: 5Nm AC 100...240V DC 2(0)...10V DC 2...10V
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connecting cable -power supply -signal AC 100...240V 50/60Hz AC 85...265V 2W @ nominal torque / 1W @ holding 4VA Cable 1m, 2x0.75mm2 Cable 1m, 4x0.75mm2 5Nm DC 2(0)...10V @ input impedance 100k DC 210V @ max. 1mA 5% Selectable by switch Gearing latch disengaged by push button, self-resetting Max. 95, adjustable by mechanical stops 150s Max. 35dB(A) Mechanical, remote visible II (Totally insulated) IP54 CE according to 89/336/EEC CE according to 73/23/EEC Type 1 (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free See Dimensions 6...20mm 0.7kg
Functional data
Torque Control signal Y Position feedback signal U Position accuracy Direction of rotation Manual override Angle of rotation Running time Sound power level Position indicator Protection class Degree of protection EMC Low Voltage Directive Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance Dimensions (LxWxH) Shaft Weight
Working conditions
Dimensions / weight
Dimensions [mm]
47
116
61
5.2
22
116
41
14
66
33
NMU24(-S/-F/-T)
For operation of air control dampers in HVAC system Torque: Nominal voltage: Control: 10Nm AC/DC 24V Open/Close or 3-point
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Auxiliary switch (-S) Connection -motor -auxiliary switch (-S) -terminals (-T) AC 24V 50/60Hz, DC 24V AC/DC 19.2...28.8V 1.5W @ nominal torque / 0.2W @ holding 3VA 1 SPDT, 1mA...3(0.5)A, AC 250V, adjustable Cable 1m, 3x0.75mm2 Cable 1m, 3x0.75mm2 Max. 3x1.5mm2 10Nm Selectable by switch Gearing latch disengaged by push button, self-resetting Max. 95, adjustable by mechanical stops 150s Max. 35dB(A) Mechanical, remote visible III (safety extra-low voltage) IP54 IP20 CE according to 89/336/EEC Type 1 (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free See Dimensions Min. 40mm (20mm with K-NA for reverse mounting-optional) NMU24(-S/-T) NMU24-F 8..26.7mm (8...20mm with K-NA) 8x8mm 0.75kg
Functional data
Torque Direction of rotation Manual override Angle of rotation Running time Sound power level Position indicator Protection class Degree of protection NMU24(-S/-F) NMU24-T EMC Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance Dimensions (LxWxH) Shaft length Shaft Weight
Working conditions
Dimensions / weight
Dimensions [mm]
NMU24(-S) NMU24-T NMU24-F
60
60
65.6
62
124
38
124
18
32
5.2
124 102
16
40
40
80
80 30 5.2
80
25
99
41
5.2
25
99
25
99
41
40
62
15
NMU24-SR
For operation of air control dampers in HVAC system Torque: Nominal voltage: Control signal: Position feedback: 10Nm AC/DC 24V DC 2(0)...10V DC 2...10V
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connecting cable AC 24V 50/60Hz, DC 24V AC/DC 19.2...28.8V 2W @ nominal torque / 0.4W @ holding 4VA Cable 1m, 4x0.75mm2 10Nm DC 2(0)...10V @ input impedance 100k DC 210V @ max. 1mA 5% Selectable by switch Gearing latch disengaged by push button, self-resetting Max. 95, adjustable by mechanical stops 150s Max. 35dB(A) Mechanical, remote visible III (safety extra-low voltage) IP54 CE according to 89/336/EEC Type 1 (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free See Dimensions 8...26.7mm (8...20mm with K-NA) 0.8kg
Functional data
Torque Control signal Y Position feedback signal U Position accuracy Direction of rotation Manual override Angle of rotation Running time Sound power level Position indicator
Working conditions
Protection class Degree of protection EMC Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
Dimensions / weight
Dimensions [mm]
60
124 5.2 80 40 9
62
25
99
41
16
NMU230(-S/-F)
For operation of air control dampers in HVAC system Torque: Nominal voltage: Control: 10Nm AC 100...240V Open/Close or 3-point
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Auxiliary switch (-S) Connection -motor -auxiliary switch (-S) AC 100...240V 50/60Hz AC 85...265V 2.5W @ nominal torque / 0.6W @ holding 5.5VA 1 SPDT, 1mA...3(0.5)A, AC 250V, adjustable Cable 1m, 3x0.75mm2 Cable 1m, 3x0.75mm2 10Nm Selectable by switch Gearing latch disengaged by push button, self-resetting Max. 95, adjustable by mechanical stops 150s Max. 35dB(A) Mechanical, remote visible II (Totally insulated) IP54 CE according to 89/336/EEC CE according to 73/23/EEC Type 1 (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free See Dimensions Min. 40mm (20mm with K-NA for reverse mounting-optional) NMU230(-S) NMU230-F 8..26.7mm (8...20mm with K-NA) 8x8mm 0.8kg
Functional data
Torque Direction of rotation Manual override Angle of rotation Running time Sound power level Position indicator
Working conditions
Protection class Degree of protection EMC Low voltage directive Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
Dimensions / weight
Dimensions [mm]
NMU230(-S) NMU230-F
60
62
38
124
18 32
124
102
16
5.2
40
80
80 30 5.2
25
99
41
25
99
41
40
62
17
NMU230SR
For operation of air control dampers in HVAC system Torque: Nominal voltage: Control signal: Position feedback: 10Nm AC 100...240V DC 2(0)...10V DC 2...10V
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connection -power supply -signal AC 100...240V 50/60Hz AC 85...265V 3.5W @ nominal torque / 1W @ holding 6.5VA Cable 1m, 2x0.75mm2 Cable 1m, 4x0.75mm2 10Nm DC 2(0)...10V @ input impedance 100k DC 210V @ max. 1mA 5% Selectable by switch Gearing latch disengaged by push button, self-resetting Max. 95, adjustable by mechanical stops 150s Max. 35dB(A) Mechanical, remote visible II (Totally insulated) IP54 CE according to 89/336/EEC CE according to 73/23/EEC Type 1 (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free 187x80x62mm Min. 40mm (20mm with K-NA for reverse mounting-optional) 6...20mm (8...20mm with K-NA) 0.95kg
Functional data
Torque Control signal Y Position feedback signal U Position accuracy Direction of rotation Manual override Angle of rotation Running time Sound power level Position indicator Protection class Degree of protection EMC Low voltage directive Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance Dimensions (LxWxH) Shaft length Shaft Weight
Working conditions
Dimensions / weight
Dimensions [mm]
60
40
62
80
25
121
41
18
5.2
SMU24(-S/-F/-T)
For operation of air control dampers in HVAC system Torque: Nominal voltage: Control: 20Nm AC/DC 24V Open/Close or 3-point
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Auxiliary switch (-S) Connection -motor -auxiliary switch (-S) -terminals (-T) AC 24V 50/60Hz, DC 24V AC/DC 19.2...28.8V 2W @ nominal torque / 0.2W @ holding 4VA 1 SPDT, 1mA...3(0.5)A, AC 250V, adjustable Cable 1m, 3x0.75mm2 Cable 1m, 3x0.75mm2 Max. 3x1.5mm2 20Nm Selectable by switch Gearing latch disengaged by push button, self-resetting Max. 95, adjustable by mechanical stops 150s Max. 45dB(A) Mechanical, remote visible III (safety extra-low voltage) IP54 IP20 CE according to 89/336/EEC Type 1 (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free See Dimensions Min. 42mm (20mm for reverse mounting) SMU24(-S/-T) SMU24-F 10..20mm (10...26.7mm with K-ENSA - optional) 12x12mm 1.05kg
Functional data
Torque Direction of rotation Manual override Angle of rotation Running time Sound power level Position indicator
Working conditions
Protection class Degree of protection SMU24(-S/-F) SMU24-T EMC Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance Dimensions (LxWxH) Shaft length Shaft Weight
Dimensions / weight
Dimensions [mm]
SMU24-F SM U24(- S) SM U24- T
56
30 23
109 97
5.2
139
5.2
56
139
44
44
75
88
88
44
67.6 30 109
5.2 8
4.2 8.8
30
109
41
64
19
SMU24-SR
For operation of air control dampers in HVAC system Torque: Nominal voltage: Control signal: Position feedback: 20Nm AC/DC 24V DC 2(0)...10V DC 2...10V
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connecting cable AC 24V 50/60Hz, DC 24V AC/DC 19.2...28.8V 2W @ nominal torque / 0.4W @ holding 4VA Cable 1m, 4x0.75mm2 20Nm DC 2(0)...10V @ input impedance 100k DC 210V @ max. 1mA 5% Selectable by switch Gearing latch disengaged by push button, self-resetting Max. 95, adjustable by mechanical stops 150s Max. 45dB(A) Mechanical, remote visible III (safety extra-low voltage) IP54 CE according to 89/336/EEC Type 1 (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free 180x88x64mm Min. 42mm (20mm for reverse mounting) 10..20mm (10...26.7mm with K-ENSA - optional) 1.05kg
Functional data
Torque Control signal Y Position feedback signal U Position accuracy Direction of rotation Manual override Angle of rotation Running time Sound power level Position indicator
Working conditions
Protection class Degree of protection EMC Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
Dimensions / weight
Dimensions [mm]
56
139
5.2 44
64
88
30
109
41
20
SMU230(-S/-F)
For operation of air control dampers in HVAC system Torque: Nominal voltage: Control: 20Nm AC 100...240V Open/Close or 3-point
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Auxiliary switch (-S) Connection -motor -auxiliary switch (-S) AC 100...240V 50/60Hz AC 85...265V 2.5W @ nominal torque / 0.6W @ holding 6VA 1 SPDT, 1mA...3(0.5)A, AC 250V, adjustable Cable 1m, 3x0.75mm2 Cable 1m, 3x0.75mm2 20Nm Selectable by switch Gearing latch disengaged by push button, self-resetting Max. 95, adjustable by mechanical stops 150s Max. 45dB(A) Mechanical, remote visible II (Totally insulated) IP54 CE according to 89/336/EEC CE according to 73/23/EEC Type 1 (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free See Dimensions Min. 42mm (20mm for reverse mounting) SMU230(-S) SMU230-F 10..20mm (10...26.7mm with K-ENSA-optional) 12x12mm 1.05kg
Functional data
Torque Direction of rotation Manual override Angle of rotation Running time Sound power level Position indicator
Working conditions
Protection class Degree of protection EMC Low voltage directive Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
Dimensions / weight
Dimensions [mm]
SMU230-F SMU230(-S)
109 139 97
5.2 5.2 44 8
44
75
4.2 8.8
88
56
30
109
41
64
21
SMU230SR
For operation of air control dampers in HVAC system Torque: Nominal voltage: Control signal: Position feedback: 20Nm AC 100...240V DC 2(0)...10V DC 2...10V
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connection -power supply -signal AC 100...240V 50/60Hz AC 85...265V 3.5W @ nominal torque / 1W @ holding 6.5VA Cable 1m, 2x0.75mm2 Cable 1m, 4x0.75mm2 20Nm DC 2(0)...10V @ input impedance 100k DC 210V max. 1mA 5% Selectable by switch Gearing latch disengaged by push button, self-resetting Max. 95, adjustable by mechanical stops 150s Max. 45dB(A) Mechanical, remote visible II (Totally insulated) IP54 CE according to 89/336/EEC CE according to 73/23/EEC Type 1 (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free 202x88x64mm Min. 42mm (20mm for reverse mounting) 10..20mm (10...26.7mm with K-ENSA-optional) 1.2kg
Functional data
Torque Control signal Y Position feedback signal U Position accuracy Direction of rotation Manual override Angle of rotation Running time Sound power level Position indicator Protection class Degree of protection EMC Low voltage directive Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance Dimensions (LxWxH) Shaft length Shaft Weight
Working conditions
Dimensions / weight
Dimensions [mm]
56
139
64
30
131
41
22
88
44
5.2
GMU24
For operation of air control dampers in HVAC system Torque: Nominal voltage: Control: 40Nm AC/DC 24V Open/Close
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connecting cable Torque Direction of rotation Manual override Angle of rotation Running time Sound power level Position indicator AC 24V 50/60Hz, DC 24V AC/DC 19.2...28.8V 4W @ nominal torque / 2W @ holding 6VA Cable 1m, 3x0.75mm2 40Nm Selectable by switch Gearing latch disengaged by push button, self-resetting Max. 95, adjustable by mechanical stops 150s Max. 45dB(A) Mechanical, remote visible III (safety extra-low voltage) IP54 CE according to 89/336/EEC Type 1 (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free 220x116x70mm Min. 52mm (20mm for reverse mounting) 12...26.7mm / 12...25.2mm 1.7kg
Functional data
Working conditions
Protection class Degree of protection EMC Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
Dimensions / weight
Dimensions [mm]
Standard : Damper spindle Length >20 12...26.7 >12 <25
60
>52
12...26.7
>12
<25
179
70
12...22mm
12...18mm
116
58
22...26.7mm
12...18mm
36
143
41
5.2
23
GMU24-SR
For operation of air control dampers in HVAC system Torque: Nominal voltage: Control signal: Position feedback: 40Nm AC/DC 24V DC 2(0)...10V DC 2...10V
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connecting cable AC 24V 50/60Hz, DC 24V AC/DC 19.2...28.8V 4.5W @ nominal torque / 2W @ holding 6.5VA Cable 1m, 4x0.75mm2 40Nm DC 2(0)...10V @ input impedance 100k DC 210V @ max. 1mA 5% Selectable by switch Gearing latch disengaged by push button, self-resetting Max. 95, adjustable by mechanical stops 150s Max. 45dB(A) Mechanical, remote visible III (safety extra-low voltage) IP54 CE according to 89/336/EEC Type 1 (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free 220x116x70mm Min. 52mm (20mm for reverse mounting) 12...26.7mm / 12...25.2mm 1.7kg
Functional data
Torque Control signal Y Position feedback signal U Position accuracy Direction of rotation Manual override Angle of rotation Running time Sound power level Position indicator Protection class Degree of protection EMC Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
Working conditions
Dimensions / weight
Dimensions [mm]
Standard : Damper spindle
>52 >20
12...26.7 12...26.7
>12 >12
<25 <25
60
179
70
Length
58
5.2
12...22mm
12...18mm
9
116
22...26.7mm
12...18mm
36
143
41
24
GMU230
For operation of air control dampers in HVAC system Torque: Nominal voltage: Control: 40Nm AC 100...240V Open/Close
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connecting cable AC 100...240V 50/60Hz AC 85...265V 5W @ nominal torque / 2W @ holding 9VA Cable 1m, 3x0.75mm2 40Nm Selectable by switch Gearing latch disengaged by push button, self-resetting Max. 95, adjustable by mechanical stops 150s Max. 45dB(A) Mechanical, remote visible II (Totally insulated) IP54 CE according to 89/336/EEC CE according to 73/23/EEC Type 1 (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free 220x116x70mm Min. 52mm (20mm for reverse mounting) 12..26.7mm / 12...25.2mm 1.7kg
Functional data
Torque Direction of rotation Manual override Angle of rotation Running time Sound power level Position indicator
Working conditions
Protection class Degree of protection EMC Low voltage directive Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
Dimensions / weight
Dimensions [mm]
Standard :
>20
12...26.7
>12
<25
60
>52
12...26.7
>12
<25
179
70
Damper spindle
Length
12...22mm
12...18mm
58
22...26.7mm
12...18mm
116
36
143
41
5.2
25
LMQU24
For operation of air control dampers in HVAC system Torque: Nominal voltage: Control: 4Nm AC/DC 24V Open/Close (not made for 3-point applications)
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connecting cable AC 24V 50/60Hz, DC 24V AC 19.2...28.8V / DC 21.6...28.8V 13W @ nominal torque / 1.5W @ holding 23VA (Imax. 20A @ 5ms) Cable 1m, 3x0.75mm2 4Nm Reversible with switch 0 or 1 Gearing latch disengaged by push button, self-resetting Max. 95, adjustable by mechanical stops 2.5s Manual triggering of the adaption by pressing the Adaption button
Functional data
Torque Direction of rotation Manual override Angle of rotation Running time Automatic adjustment of operating range and measuring signal U to match the mechanical angle of rotation Sound power level Position indicator Negative torque
!
Max. 52dB(A) Mechanical, remote visible 50% from nominal torque (with restrictions) III (safety extra-low voltage) IP54 CE according to 2004/108/EC Type 1 (EN 60730-1)
!
Working conditions
Protection class Degree of protection EMC Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance Dimensions (LxWxH) Weight
-30...+40C (without restrictions) +40...+50C (with restrictions) -40...+80C 5...95% RH, non-condensing Maintenance-free 187x80x75mm 0.85kg
Dimensions / weight
Dimensions [mm]
52
124
5.2
75
Damper spindle *
25
121
41
26
40
LMQU24-SR
For operation of air control dampers in HVAC system Torque: Nominal voltage: Control signal: Position feedback: 4Nm AC/DC 24V DC 2(0)...10V DC 2...10V
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connecting cable AC 24V 50/60Hz, DC 24V AC 19.2...28.8V / DC 21.6...28.8V 13W @ nominal torque / 1.5W @ holding 23VA (Imax. 20A @ 5ms) Cable 1m, 4x0.75mm2 4Nm DC 2(0)...10V @ input impedance 100k DC 2...10V @ max. 0.5mA 5% Reversible with switch 0 or 1 At switch position 0 resp. 1 Gearing latch disengaged by push button, self-resetting Max. 95, adjustable by mechanical stops 2.5s Manual triggering of the adaption by pressing the Adaption button
Functional data
Torque Control signal Y Position feedback signal U Position accuracy Direction of rotation Direction of motion at Y=0V Manual override Angle of rotation Running time Automatic adjustment of operating range and measuring signal U to match the mechanical angle of rotation Sound power level Position indicator Negative torque
!
Max. 52dB(A) Mechanical, remote visible 50% from nominal torque (with restrictions) III (safety extra-low voltage) IP54 CE according to 2004/108/EC Type 1 (EN 60730-1)
!
Working conditions
Protection class Degree of protection EMC Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
-30...+40C (without restrictions) +40...+50C (with restrictions) -40...+80C 5...95% RH, non-condensing Maintenance-free 187x80x75mm 0.85kg
Dimensions / weight
Dimensions [mm]
52
124
75
Damper spindle *
40
25
121
41
5.2
27
NMQU24
For operation of air control dampers in HVAC system Torque: Nominal voltage: Control: 8Nm AC/DC 24V Open/Close (not made for 3-point applications)
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connecting cable AC 24V 50/60Hz, DC 24V AC 19.2...28.8V / DC 21.6...28.8V 13W @ nominal torque / 1.5W @ holding 23VA (Imax. 20A @ 5ms) Cable 1m, 3x0.75mm2 8Nm Reversible with switch 0 or 1 Gearing latch disengaged by push button, selfresetting Max. 95, adjustable by mechanical stops 4s Manual triggering of the adaption by pressing the Adaption button
Functional data
Torque Direction of rotation Manual override Angle of rotation Running time Automatic adjustment of operating range and measuring signal U to match the mechanical angle of rotation Sound power level Position indicator Negative torque
!
Max. 52dB(A) Mechanical, remote visible 50% from nominal torque (with restrictions) III (safety extra-low voltage) IP54 CE according to 2004/108/EC Type 1 (EN 60730-1)
!
Working conditions
Protection class Degree of protection EMC Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
-30...+40C (without restrictions) +40...+50C (with restrictions) -40...+80C 5...95% RH, non-condensing Maintenance-free 202x88x77mm 0.97kg
Dimensions / weight
Dimensions [mm]
52
139
5.2
77
Damper spindle *
Length
88
30
131
41
28
44
NMQU24-SR
For operation of air control dampers in HVAC system Torque: Nominal voltage: Control signal: Position feedback: 8Nm AC/DC 24V DC 2(0)...10V DC 2...10V
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connecting cable Torque Control signal Y Position feedback signal U Position accuracy Direction of rotation Direction of motion at Y=0V Manual override Angle of rotation Running time Automatic adjustment of operating range and measuring signal U to match the mechanical angle of rotation Sound power level Position indicator Negative torque
!
AC 24V 50/60Hz, DC 24V AC 19.2...28.8V / DC 21.6...28.8V 13W @ nominal torque / 1.5W @ holding 23VA (Imax. 20A @ 5ms) Cable 1m, 4x0.75mm2 8 Nm DC 2(0)...10V @ input impedance 100k DC 2...10V @ max. 0.5mA 5% Reversible with switch 0 or 1 At switch position 0 resp. 1 Gearing latch disengaged by push button, self-resetting Max. 95, adjustable by mechanical stops 4s Manual triggering of the adaption by pressing the Adaption button
Functional data
Max. 52dB(A) Mechanical, remote visible 50% from nominal torque (with restrictions) III (safety extra-low voltage) IP54 CE according to 2004/108/EC Type 1 (EN 60730-1)
!
Working conditions
Protection class Degree of protection EMC Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
-30...+40C (without restrictions) +40...+50C (with restrictions) -40...+80C 5...95% RH, non-condensing Maintenance-free 202x88x77mm 0.95kg
Dimensions / weight
Dimensions [mm]
52
139
44
Damper spindle *
Length
88
5.2
77
29
SMQU24
For operation of air control dampers in HVAC system Torque: Nominal voltage: Control: 16m AC/DC 24V Open/Close (not made for 3-point applications)
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connecting cable AC 24V 50/60Hz, DC 24V AC 19.2...28.8V / DC 21.6...28.8V 15W @ nominal torque / 1.5W @ holding 26VA (Imax. 20A @ 5ms) Cable 1m, 3x0.75mm2 16Nm Reversible with switch 0 or 1 Gearing latch disengaged by push button, self-resetting Max. 95, adjustable by mechanical stops 7s Manual triggering of the adaption by pressing the Adaption button
Functional data
Torque Direction of rotation Manual override Angle of rotation Running time Automatic adjustment of operating range and measuring signal U to match the mechanical angle of rotation Sound power level Position indicator Negative torque
!
Max. 52dB(A) Mechanical, remote visible 50% from nominal torque (with restrictions) III (safety extra-low voltage) IP54 CE according to 2004/108/EC Type 1 (EN 60730-1)
!
Working conditions
Protection class Degree of protection EMC Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
-30...+40C (without restrictions) +40...+50C (with restrictions) -40...+80C 5...95% RH, non-condensing Maintenance-free 220x116x83mm 1.7kg
Dimensions / weight
Dimensions [mm]
Damper spindle
Length
62
179
83
5.2
12...22mm
12...18mm
116
30
22...26.7mm
12...18mm
36
143
41
58
SMQU24-SR
For operation of air control dampers in HVAC system Torque: Nominal voltage: Control signal: Position feedback: 16Nm AC/DC 24V DC 2(0)...10V DC 2...10V
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connecting cable AC 24V 50/60Hz, DC 24V AC 19.2...28.8V / DC 21.6...28.8V 15W @ nominal torque / 1.5W @ holding 26VA (Imax. 20A @ 5ms) Cable 1m, 4x0.75mm2 16 Nm DC 2(0)...10V @ input impedance 100k DC 2...10V @ max. 0.5mA 5% Reversible with switch 0 or 1 At switch position 0 resp. 1 Gearing latch disengaged by push button, self-resetting Max. 95, adjustable by mechanical stops 7s Manual triggering of the adaption by pressing the Adaption button
Functional data
Torque Control signal Y Position feedback signal U Position accuracy Direction of rotation Direction of motion at Y=0V Manual override Angle of rotation Running time Automatic adjustment of operating range and measuring signal U to match the mechanical angle of rotation Sound power level Position indicator Negative torque
!
Max. 52dB(A) Mechanical, remote visible 50% from nominal torque (with restrictions) III (safety extra-low voltage) IP54 CE according to 2004/108/EC Type 1 (EN 60730-1)
!
Working conditions
Protection class Degree of protection EMC Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
-30...+40C (without restrictions) +40...+50C (with restrictions) -40...+80C 5...95% RH, non-condensing Maintenance-free 220x116x83mm 1.7kg
Dimensions / weight
Dimensions [mm]
62
Damper spindle
Length
179
83
58
9
12...22mm 12...18mm
116
22...26.7mm
12...18mm
36
143
41
5.2
31
SMDU230
Damper actuator for adjusting air dampers in ventilation and air-conditioning systems for building services installations Torque: Running time Nominal voltage: Control: 16Nm 20s AC 100...240V Open/Close or 3-point
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connecting cable AC 100...240V 50/60Hz AC 85...265V 4.5W @ nominal torque / 1W @ holding 8VA Cable 1m, 3x0.75mm2 16Nm Reversible with switch 0 resp. 1 Gearing disengaged by pressing the push button, can be locked Max. 95, can be limited with adjustable mechanical end stops 20s Max. 55dB(A) Mechanical, remote visible II (Totally insulated) IP54 CE according to 2004/108/EC CE according to 2006/95/EC Type 1 (EN60730-1) 4kV 3 -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free See <Dimensions> 1kg
Functional data
Torque Direction of rotation Manual override Angle of rotation Running time Sound power level Position indicator
Working conditions
Protection class Degree of protection EMC Low voltage directive Mode of operation Rated impulse voltage Control pollution degree Ambient temp. Non-operation temp. Humidity Maintenance
Dimensions / weight
Dimensions [mm]
Damper spindle
56
139
44
30
131
41
32
8
88
5.2
64
For operation of air control dampers that perform safety function Torque: Nominal voltage: Control: 2Nm AC/DC 24V Open/Close
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Auxiliary switch (-S) AC 24V 50/60Hz, DC 24V AC 19.2...28.8V / DC 21.6...28.8V 2.5W @ nominal torque / 1.5W @ holding 5VA 1 SPDT, 1mA...3(0.5)A, AC 250V, adjustable
Connecting cable -motor Cable 1m, 2x0.75mm2 -auxiliary switch (-S) Cable 1m, 3x0.75mm2
Functional data
Torque Direction of rotation Angle of rotation Running time -motor -spring return
2Nm Selectable by mounting L/R Max. 95, 37...100% adjustable by mechanical stops 75s 25s @ -20...+50C / max. 60s @ -30C Max. 50dB(A) Max. 62dB(A) Mechanical III (safety extra-low voltage) IP42 CE according to 89/336/EEC Type 1.AA (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free 140x77x84mm Min. 84mm Min. 20mm 6...12mm 0.6kg Clamp up Clamp down
Working conditions
Protection class Degree of protection EMC Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
Dimensions / weight
Dimensions [mm]
17 84 6 61 6...12
104
38.5
77
10
20 84 36
5.3
33
For operation of air control dampers that perform safety function Torque: Nominal voltage: Control: 2Nm AC 24V 3-point
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connecting cable AC 24V 50/60Hz AC 19.2...28.8V 2.5W @ nominal torque / 1W @ holding 4VA Cable 1m, 4x0.75mm2 2Nm Selectable by mounting L/R Max. 95, 37...100% adjustable by mechanical stops -motor -spring return 150s 25s @ -20...+50C / max. 60s @ -30C Max. 35dB(A) Max. 62dB(A) Mechanical III (safety extra-low voltage) IP42 CE according to 89/336/EEC Type 1.AA (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free 140x77x84mm Min. 84mm Min. 20mm 6...12mm 0.6kg Clamp up Clamp down
Functional data
Working conditions
Protection class Degree of protection EMC Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
Dimensions / weight
Dimensions [mm]
6...12 84 61 6
17
38.5
77
10
20
84
36
34
5.3
For operation of air control dampers that perform safety function Torque: Nominal voltage: Control signal: Position feedback: 2Nm AC/DC 24V DC 2(0)...10V DC 2...10V
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connecting cable AC 24V 50/60Hz, DC 24V AC 19.2...28.8V / DC 21.6...28.8V 2.5W @ nominal torque / 1W @ holding 4VA Cable 1m, 4x0.75mm2 2Nm DC 2(0)...10V @ input impedance 100k DC 210V @ max. 0.5mA Selectable by mounting L/R Max. 95, 37...100% adjustable by mechanical stops -motor -spring return 150s 25s @ -20...+50C / max. 60s @ -30C Max. 35dB(A) Max. 62dB(A) Mechanical III (safety extra-low voltage) IP42 CE according to 89/336/EEC Type 1.AA (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free 140x77x84mm Min. 84mm Min. 20mm 6...12mm 0.6kg Clamp up Clamp down
Functional data
Torque Control signal Y Position feedback signal U Direction of rotation Angle of rotation Running time
Working conditions
Protection class Degree of protection EMC Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
Dimensions / weight
Dimensions [mm]
6...12 84 61 6
17
104
38.5
77
10
20
84
36
5.3
35
For operation of air control dampers that perform safety function Torque: Nominal voltage: Control: 2Nm AC 100...240V Open/Close
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Auxiliary switch (-S) AC 100...240V 50/60Hz AC 85...265V 2.5W @ nominal torque / 1.5W @ holding 5VA 1 SPDT, 1mA...3(0.5)A, AC 250V, adjustable
Connecting cable -motor Cable 1m, 2x0.75mm2 -auxiliary switch (-S) Cable 1m, 3x0.75mm2
Functional data
Torque Direction of rotation Angle of rotation Running time -motor -spring return
2Nm Selectable by mounting L/R Max. 95, 37...100% adjustable by mechanical stops 75s 25s @ -20...+50C / max. 60s @ -30C Max. 50dB(A) Max. 62dB(A) Mechanical I (Totally insulated) IP42 CE according to 89/336/EEC CE according to 73/23/EEC Type 1.AA (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free 140x77x84mm Min. 84mm Min. 20mm 6...12mm 0.6kg Clamp up Clamp down
Working conditions
Protection class Degree of protection EMC Low voltage directive Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
Dimensions / weight
Dimensions [mm]
17 6...12 84 61 6
10
20 84 36
36
104
38.5
5.3
77
For operation of air control dampers that perform safety function Torque: Nominal voltage: Control signal: Position feedback: 2Nm AC 100...240V DC 2(0)...10V DC 2...10V
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connecting cable AC 100...240V 50/60Hz AC 85...265V 2.5W @ nominal torque / 2W @ holding 5.5VA Cable 1m, 2x0.75mm2 Cable 1m, 3x0.75mm2 2Nm DC 2(0)...10V @ input impedance 100k DC 210V @ max. 0.5mA Selectable by mounting L/R Max. 95, 37...100% adjustable by mechanical stops -motor -spring return 150s 25s @ -20...+50C / max. 60s @ -30C Max. 35dB(A) Max. 62dB(A) Mechanical II (Totally insulated) IP42 CE according to 2004/108/EC CE according to 2006/95/EC Type 1.AA (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free 140x77x84mm Min. 84mm Min. 20mm 6...12mm 0.63kg Clamp up Clamp down
Functional data
Torque Control signal Y Position feedback signal U Direction of rotation Angle of rotation Running time
Working conditions
Protection class Degree of protection EMC Low voltage directive Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
Dimensions / weight
Dimensions [mm]
17
6...12
84 61
104
38.5
77
10
20 84 36
5.3
37
For operation of air control dampers that perform safety function Torque: Nominal voltage: Control: 4Nm AC/DC 24V Open/Close
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Auxiliary switch (-S) Connecting cable -motor -auxiliary switch (-S) AC 24V 50/60Hz, DC 24V AC 19.2...28.8V / DC 21.6...28.8V 5W @ nominal torque / 2.5W @ holding 7VA 1 SPDT, 1mA...3(0.5)A, AC 250V, adjustable Cable 1m, 2x0.75mm2 Cable 1m, 3x0.75mm2 4Nm Selectable by mounting L/R Max. 95, 37...100% adjustable by mechanical stops -motor -spring return 40...75s 20s @ -20...+50C / max. 60s @ -30C Max. 50dB(A) Max. 62dB(A) Mechanical III (safety extra-low voltage) IP54 CE according to 2004/108/EC -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free 181x98x82mm Min. 84mm Min. 20mm 8...16mm 1.4kg Clamp up Clamp down
Functional data
Working conditions
Protection class Degree of protection EMC Ambient temp. Non-operation temp. Humidity Maintenance Dimensions (LxWxH) Shaft length Shaft Weight
Dimensions / weight
Dimensions [mm]
6.5
57
8...16
82
18.5
181 155
25
16.8 18 93 125
38
6.5
12.6
1 .8 .6 .4 .2
49
80
49
98
10
For operation of air control dampers that perform safety function Torque: Nominal voltage: Control: 4Nm AC/DC 24V 3-point
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connecting cable AC 24V 50/60Hz, DC 24V AC 19.2...28.8V / DC 21.6...28.8V 2.5W @ nominal torque / 1W @ holding 5VA Cable 1m, 4x0.75mm2 4Nm Selectable by mounting L/R Max. 95, 37...100% adjustable by mechanical stops -motor -spring return 150s 20s @ -20...+50C / max. 60s @ -30C Max. 30dB(A) Max. 62dB(A) Mechanical III (safety extra-low voltage) IP54 CE according to 2004/108/EC -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free 181x98x82mm Min. 84mm Min. 20mm 8...16mm 1.4kg Clamp up Clamp down
Functional data
Working conditions
Protection class Degree of protection EMC Ambient temp. Non-operation temp. Humidity Maintenance Dimensions (LxWxH) Shaft length Shaft Weight
Dimensions / weight
Dimensions [mm]
49
16.8
10
39
For operation of air control dampers that perform safety function Torque: Nominal voltage: Control signal: Position feedback: 4Nm AC/DC 24V DC 2(0)...10V DC 2...10V
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connecting cable AC 24V 50/60Hz, DC 24V AC 19.2...28.8V / DC 21.6...28.8V 2.5W @ nominal torque / 1W @ holding 5VA Cable 1m, 4x0.75mm2 4Nm DC 2(0)...10V @ input impedance 100k DC 210V @ max. 0.7mA Selectable by L/R switch Selectable by L/R mounting Max. 95, 37...100% adjustable by mechanical stops -motor -spring return 150s 20s @ -20...+50C / max. 60s @ -30C Max. 30dB(A) Max. 62dB(A) Mechanical III (safety extra-low voltage) IP54 CE according to 2004/108/EC Type 1.AA (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free 181x98x82mm Min. 84mm Min. 20mm 8...16mm 1.4kg Clamp up Clamp down
Functional data
Torque Control signal Y Position feedback signal U Direction of rotation Angle of rotation Running time
Working conditions
Protection class Degree of protection EMC Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
Dimensions / weight
Dimensions [mm]
16.8
40
49
10
For operation of air control dampers that perform safety function Torque: Nominal voltage: Control: 4Nm AC 230V Open/Close
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Auxiliary switch (-S) Connecting cable -motor -auxiliary switch (-S) AC 230V 50/60Hz AC 198...264V 5W @ nominal torque / 3W @ holding 7VA 1 SPDT, 1mA...3(0.5)A, AC 250V, adjustable Cable 1m, 2x0.75mm2 Cable 1m, 3x0.75mm2 4Nm Selectable by mounting L/R Max. 95, 37...100% adjustable by mechanical stops -motor -spring return 40...75s 20s @ -20...+50C / max. 60s @ -30C Max. 50dB(A) Max. 62dB(A) Mechanical II (Totally insulated) IP54 CE according to 2004/108/EC CE according to 2006/95/EC -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free 181x98x82mm Min. 84mm Min. 20mm 8...16mm 1.55kg Clamp up Clamp down
Functional data
Sound power level -motor -spring return Position indicator Protection class Degree of protection EMC Low voltage directive Ambient temp. Non-operation temp. Humidity Maintenance Dimensions (LxWxH) Shaft length Shaft Weight
Working conditions
Dimensions / weight
Dimensions [mm]
18.5 6.5 57 8...16 82
181 155
25
6.5
.8 .6 .4
12.6
.2
49
80
49
98
16.8 18 93 125
10
41
Damper actuator for operating air control dampers in ventilation and air-conditioning systems for building services installations Torque: Nominal voltage: Control: 10Nm AC 24...240V / DC 24...125V Open/Close
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connecting cable AC 24...240V 50/60Hz, DC 24...125V AC 19.2...264V / DC 20.4...126.5V 6W @ nominal torque / 2.5W @ holding 6VA @ AC 24V; 6.5VA @ AC 120V; 9.5VA @ AC 240V Cable 1m, 2x0.75mm2 10Nm Selectable by mounting L/R By manual override key Max. 95, adjustable by mechanical stops -motor -spring return <75s 20s @ -20...+50C / max. 60s @ -30C Max. 45dB(A) Max. 62dB(A) Mechanical II (Totally insulated) IP54 CE according to 2004/108/EC CE according to 2006/95/EC Type 1.AA (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free 236x98x85mm 2kg
Functional data
Working conditions
Protection class Degree of protection EMC Low voltage directive Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
Dimensions / weight
Dimensions [mm]
Standard : - clamp (with insert) Damper shaft Length 10 10...22 Optional 1: 1- clamp (without insert) 19...25.4 12...18 19...25.4 12...18 Optional 2: - clamp (optional via configuration) Damper shaft Length 10...19 10...19 14...20 14...20 10 14...25.4
85
59
20
T N O R -F 2
49
80
98
Damper shaft
Length
32
42
Damper actuator for operating air control dampers in ventilation and air-conditioning systems for building services installations Torque: Nominal voltage: Control: 10Nm AC 24...240V / DC 24...125V Open/Close
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Auxiliary switch (-S2) Connecting cable -motor -auxiliary switch (-S2) AC 24...240V 50/60Hz, DC 24...125V AC 19.2...264V / DC 20.4...126.5V 6W @ nominal torque / 2.5W @ holding 6VA @ AC 24V; 6.5VA @ AC 120V; 9.5VA @ AC 240V 2 SPDT, 1mA...3(0.5)A, AC 250V one fixed at 10%, one adjustable 10...90% Cable 1m, 2x0.75mm2 Cable 1m, 6x0.75mm2 10Nm Selectable by mounting L/R By manual override key Max. 95, adjustable by mechanical stops -motor -spring return 75s 20s @ -20...+50C / max. 60s @ -30C Max. 45dB(A) Max. 62dB(A) Mechanical II (Totally insulated) IP54 CE according to 2004/108/EC CE according to 2006/95/EC Type 1.AA (EN 60730-A-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free 236x98x85mm 2.2kg
Functional data
Working conditions
Protection class Degree of protection EMC Low voltage directive Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
Dimensions / weight
Dimensions [mm]
Standard : - clamp (with insert) Damper shaft Length 10 10...22 Optional 1: 1- clamp (without insert) 10 14...25.4
85
59
20
T N O R -F 2
49
19...25.4 12...18 19...25.4 12...18 Optional 2: - clamp (optional via configuration) Damper shaft Length 10...19 10...19 14...20 14...20
80
98
Damper shaft
Length
32
43
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connecting cable AC 24V 50/60Hz, DC 24V AC 19.2...28.8V / DC 21.6...28.8V 3.5W @ nominal torque / 2.5W @ holding 6VA Cable 1m, 4x0.75mm2 10Nm DC 2(0)...10V @ input impedance 100k DC 210V @ max. 0.5mA 5% Reversible with switch / Selectable by mounting L/R By manual override key Max. 95, adjustable by mechanical stops -motor -spring return 150s 20s @ -20...+50C / max. 60s @ -30C Max. 40dB(A) Max. 62dB(A) Mechanical III (safety extra-low voltage) IP54 CE according to 2004/108/EC Type 1.AA (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free 236x98x85mm 2kg
Functional data
Torque Control signal Y Position feedback signal U Position accuracy Direction of rotation Manual override Angle of rotation Running time
Sound power level -motor -spring return Position indicator Protection class Degree of protection EMC Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
Working conditions
Dimensions / weight
Dimensions [mm]
Standard : - clamp (with insert) Damper shaft Length 10 10...22 Optional 1: 1- clamp (without insert) 19...25.4 12...18 19...25.4 12...18 Optional 2: - clamp (optional via configuration) Damper shaft Length 10...19 10...19 14...20 14...20 10 14...25.4
85
59
20
T N O R -F 2
49
80
98
Damper shaft
Length
32
44
Damper actuator for operating air control dampers in ventilation and air-conditioning systems for building services installations Torque: Nominal voltage: Control: 20Nm AC 24...240V / DC 24...125V Open/Close
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connecting cable AC 24...240V 50/60Hz, DC 24...125V AC 19.2...264V / DC 20.4...126.5V 7W @ nominal torque / 3.5W @ holding 7VA @ AC 24V; 8.5VA @ AC 120V; 18VA @ AC 240V Cable 1m, 2x0.75mm2 20Nm Selectable by mounting L/R By manual override key Max. 95, adjustable by mechanical stops -motor -spring return 75s 20s @ -20...+50C / max. 60s @ -30C Max. 45dB(A) Max. 62dB(A) Mechanical II (Totally insulated) IP54 CE according to 2004/108/EC CE according to 2006/95/EC Type 1.AA (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free 236x98x85mm 2.2kg
Functional data
Working conditions
Protection class Degree of protection EMC Low voltage directive Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
Dimensions / weight
Dimensions [mm]
Standard : - clamp (with insert) Damper shaft Length 10 10...22 Optional 1: 1- clamp (without insert) 19...25.4 12...18 19...25.4 12...18 Optional 2: - clamp (optional via configuration) 10 14...25.4
85
59
20
T N O R -F 2
49
80
98
Damper shaft
Length
32
27 162 172
Damper shaft
182 236
45
Damper actuator for operating air control dampers in ventilation and air-conditioning systems for building services installations Torque: Nominal voltage: Control: 20Nm AC 24...240V / DC 24...125V Open/Close
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Auxiliary switch (-S2) Connecting cable-motor -auxiliary switch (-S2) AC 24...240V 50/60Hz, DC 24...125V AC 19.2...264V / DC 21.6...143V 7W @ nominal torque / 3.5W @ holding 7VA @ AC 24V; 8.5VA @ AC 120V; 18VA @ AC 240V 2 SPDT, 1mA...3(0.5)A, AC 250V one fixed at 10%, one adjustable 10...90% Cable 1m, 2x0.75mm2 Cable 1m, 6x0.75mm2 20Nm Selectable by mounting L/R By manual override key Max. 95, adjustable by mechanical stops -motor -spring return 75s 20s @ -20...+50C / max. 60s @ -30C Max. 45dB(A) Max. 62dB(A) Mechanical II (Totally insulated) IP54 CE according to 2004/108/EC CE according to 2006/95/EC Type 1.AA (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free 236x98x85mm 2.4kg
Functional data
Working conditions
Protection class Degree of protection EMC Low voltage directive Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
Dimensions / weight
Dimensions [mm]
Standard : - clamp (with insert) Damper shaft Length 10 10...22 Optional 1: 1- clamp (without insert) 19...25.4 12...18 19...25.4 12...18 Optional 2: - clamp (optional via configuration) Damper shaft Length 10...19 10...19 14...20 14...20 10 14...25.4
85
59
20
T N O R -F 2
49
80
98
Damper shaft
Length
32
46
Damper actuator for operating air control dampers in ventilation and air-conditioning systems for building services installations Torque: Nominal voltage: Control signal: Position feedback 20Nm AC/DC 24V DC 2(0)...10V DC 2...10V
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connecting cable Torque Control signal Y Position feedback signal U Position accuracy Direction of rotation Manual override Angle of rotation Running time -motor -spring return AC 24V 50/60Hz, DC 24V AC 19.2...28.8V / DC 21.6...28.8V 5W @ nominal torque / 3.5W @ holding 7VA Cable 1m, 4x0.75mm2 20Nm DC 2(0)...10V @ input impedance 100k DC 2...10V @ max. 0.5mA 5% Reversible with switch / Selectable by mounting L/R By manual override key Max. 95, adjustable by mechanical stops 75s 20s @ -20...+50C / max. 60s @ -30C Max. 40dB(A) Max. 62dB(A) Mechanical III (safety extra-low voltage) IP54 CE according to 2004/108/EC Type 1.AA (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free 236x98x85mm 2.2kg
Functional data
Working conditions
Protection class Degree of protection EMC Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
Dimensions / weight
Dimensions [mm]
20
Standard : - clamp (with insert) Damper shaft Length 10 10...22 Optional 1: 1- clamp (without insert) 10 14...25.4
85
59
T N O R -F 2
49
19...25.4 12...18 19...25.4 12...18 Optional 2: - clamp (optional via configuration) Damper shaft Length 10...19 10...19 14...20 14...20
80
98
Damper shaft
Length
32
47
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Auxiliary switch (-S2) Connecting cable-motor -auxiliary switch AC 24V 50/60Hz, DC 24V AC 19.2...28.8V / DC 21.6...28.8V 9.5W @ nominal torque / 4.5W @ holding 16VA 2xSPDT, 1mA...3(0.5)A, AC 250V one fixed at 10%, one adjustable 10...90% Cable 1m, 2x0.75mm2 Cable 1m, 6x0.75mm2 30Nm 5% Selectable by mounting L/R With hand crank and interlocking switch Max. 95, can be limited with adjustable mechanical end stops -motor -spring return <75s 20s @ 20 ... 50C / 60s @ 30C Max. 55dB(A) Max. 71dB(A) Mechanical III (safety extra-low voltage) IP54 CE according to 2004/108/EC Type 1.AA.B (EN60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free 322x138x120.5mm 4.5kg
Functional data
Torque Position accuracy Direction of rotation Manual override Angle of rotation Running time
Working conditions
Protection class Degree of protection EMC Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
Dimensions / weight
Dimensions [mm]
27
12 ... 26.7 >12 < 25.2 12 ... 26.7 >12 < 25.2
120.5
Damper spindle
Length
13.5
80
12 ... 22 mm
12 ... 18 mm
112 138
35
35
22 ... 26.7 mm
12 ... 18 mm
50
48
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connecting cable AC 24V 50/60Hz, DC 24V AC 19.2...28.8V / DC 21.6...28.8V 7W @ nominal torque / 4.5W @ holding 12VA Cable 1m, 4x0.75mm2 30Nm DC 2(0)...10V @ input impedance 100k DC 2...10V @ max. 0.5mA 5% Reversible with switch / selectable by mounting L / R With hand crank and interlocking switch Max. 95, can be limited with adjustable mechanical end stops -motor -spring return 150s 20s @ 20 ... 50C / 60s @ 30C Max. 45dB(A) @ 150s running time Max. 71dB(A) Mechanical III (safety extra-low voltage) IP54 CE according to 2004/108/EC Type 1.AA (EN60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free 322x138x120.5mm 4.3kg
Functional data
Torque Control signal Y Position feedback signal U Position accuracy Direction of rotation Manual override Angle of rotation Running time
Working conditions
Protection class Degree of protection EMC Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
Dimensions / weight
Dimensions [mm]
27
12 ... 26.7 >12 < 25.2 12 ... 26.7 >12 < 25.2
120.5
Damper spindle
Length
12 ... 22 mm
12 ... 18 mm
112 138
35 35 143 188 238 272 322 50
22 ... 26.7 mm
12 ... 18 mm
13.5
80
49
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Auxiliary switch (-S2) Connecting cable -motor -auxiliary switch AC 230V 50/60Hz AC 198...264V 9.5W @ nominal torque / 4.5W @ holding 22VA 2xSPDT, 1mA...3(0.5)A, AC 250V one fixed at 10%, one adjustable 10...90% Cable 1m, 2x0.75mm2 Cable 1m, 6x0.75mm2 30Nm 5% Selectable by mounting L/R With hand crank and interlocking switch Max. 95, can be limited with adjustable mechanical end stops -motor -spring return <75s 20s @ 20 ... 50C / 60s @ 30C Max. 55dB(A) Max. 71dB(A) Mechanical II (Totally insulated) IP54 CE according to 2004/108/EC CE according to 2006/95/EC Type 1.AA.B (EN60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free 322x138x120.5mm 4.5kg
Functional data
Torque Position accuracy Direction of rotation Manual override Angle of rotation Running time
Working conditions
Protection class Degree of protection EMC Low voltage directive Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance
Dimensions / weight
Dimensions [mm]
27
Damper spindle
Length 12 ... 26.7 >12 < 25.2 12 ... 26.7 >12 < 25.2
120.5 80 13.5
12 ... 22 mm
12 ... 18 mm
112 138
35
35
22 ... 26.7 mm
12 ... 18 mm
50
50
Parameterisable damper actuator with capacitor technology for adjusting air dampers with emergency control function and extended functionalities in ventilation and air-conditioning systems for building services installations and in laboratories. Torque: Nominal voltage: Control: 40 Nm AC/DC 24V Open/Close
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connecting cable AC 24V 50/60Hz, DC 24V AC 19.2...28.8V / DC 21.6...28.8V 12W @ nominal torque / 3W @ holding 21VA Cable 1m, 2x0.75mm2 40Nm 0...100% adjustable 2s 5% As an option with / Reversible with switch 0 ... 100% Gearing latch disengaged by push button Max. 95, adjustable by mechanical stops -standard -POP -standard -POP 150s 35s @ 0...50C Max. 52dB(A) @ 150s running time Max. 61dB(A) Mechanical III (safety extra-low voltage) IP54 CE according to 2004/108/EC Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14 Type 1.AA (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free 210x116x87mm 1.8kg
Functional data
Torque Emergency setting position (POP) Bridging time (PF) Position accuarcy Direction of rotation -motor -POP Manual override Angle of rotation Running time Sound power level Position indicator
Working conditions
Protection class Degree of protection EMC Certification Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance Dimensions (LxWxH) Weight
Dimensions / weight
Dimensions [mm]
Damper spindle
*
Length 12 ... 26.7 >12 < 25.5 12 ... 26.7 >12 < 25.5
60
210
179
12 ... 22 mm
12 ... 18 mm
116
22 ... 26.7 mm
12 ... 18 mm
36 174
99
87
51
Technical data
Electrical data
Nominal voltage Nominal voltage range Power consumption For transformer sizing Connecting cable AC 24V 50/60Hz, DC 24V AC 19.2...28.8V / DC 21.6...28.8V 12W @ nominal torque / 3W @ holding 21VA (Imax 20A @ 5ms) Cable 1m, 5x0.75mm2 40Nm DC 2(0)...10V @ input impedance 100k DC 2(0)...10V @ max. 0.5mA 0...100% adjustable 1...10s adjustable (factory setting 2s) 5% As an option with / Reversible with switch 0 ... 100% At switch position 1 or 0 , respectively Gearing latch disengaged by push button Max. 95, adjustable by mechanical stops -standard -POP 90...150s adjustable (factory setting 150s/90) 35s @ 0...50C Manual triggering of the adaption by pressing the Adaption button
Functional data
Torque Control signal Y Position feedback signal U Emergency setting position (POP) Bridging time (PF) Position accuarcy Direction of rotation -motor -POP -Y=0V Manual override Angle of rotation Running time
Automatic adjustment of running time, operating range and measuring signal U to match the mechanical angle of rotation Override control
MAX (maximum position) = 100% MIN (minimum position) = 0% ZS (intermediate position, only AC) = 50% -standard -POP Max. 53dB(A) @ 90s running time Max. 52dB(A) @ 150s running time Max. 61dB(A) Mechanical III (safety extra-low voltage) IP54 CE according to 2004/108/EC
Position indicator
Working conditions
Protection class Degree of protection EMC Certification Mode of operation Ambient temp. Non-operation temp. Humidity Maintenance Dimensions (LxWxH) Weight
Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14 Type 1.AA (EN 60730-1) -30...+50C -40...+80C 5...95% RH, non-condensing Maintenance-free 1.8kg
V5.01. 01.2013 Subject to modification
Dimensions / weight
52
1
>32 m m
6 ... 12.7 mm
2
2.5
5 10
12 0
3
90
45
30
15
90
75
60
0 12
2.5
15
70 20 mm
75
90
10 5
60 45 30
12
4
8
75
60 45 30
90
10 5
12
0 12
12 0
0 12
12 0
12 0
12
10 5
CMU24-SR..
5 10 12 0
90
ma
75 60
45
x
5 .9
30 15
0 12
A
V5.01. 01.2013 Subject to modification
24 V
230 V
90 10 5
12 0
60 45
30
60 45
75 9 0
12
90
30
75 9 0
10 5
75
10 5
60 45 30
0 12
10 5
30
60 45
75 9 0
10 5
30
90 10 5
45
12 0
6 Nm
90 1 05
12 0
75
60 45 30
90
10 5
120 60
5 10
90
75
60
45
30 15
5 10
15
90
75
5 10
90
75
60
45
30
15
5 10
90
75
60
45
30 15
90 10 5
12 0
12 0
90 10 5
12 0
10 5
90 1 05
12 0
12 0
10 5
30
45
60
75 9 0
10 5
60 75 90
10 5
2
90
1
75
60 45 30
75
90
60 45 30
12 0
15
75
90
60 45 30
15 15
53
>37
6 ... 20
>6
< 20
1
8
10
1
2
6 Nm
1mm
Z-PI
65
V5.01. 01.2013 Subject to modification
54
40
8 ... 26.7
>8
< 26.7
1
10
10
1
2
9 Nm
1mm
Z-PI
65
V5.01. 01.2013 Subject to modification
55
48
10 10
20 20
1
10
10
1
2
1 mm
9 Nm CrNi(INOX)15 Nm
5
2
1
Z-PI
65
V5.01. 01.2013 Subject to modification
56
2
1
>52
12 ... 22 mm
12 ... 18 mm
4
22 ... 26.7 mm 12 ... 18 mm
3
1m m
1 1
15 Nm CrNi (INOX) 25 Nm
2
2
2
Z-PI
V5.01. 01.2013 Subject to modification
>20
1 2
5
65
13
57
A
LMQU.. NMQU.. > 40 > 42 8 ... 26.7 8 ... 26.7 >8 >8 < 26.7 < 26.7
2
10 1
10
1
9Nm
1mm
1
2
1 2 Z-PI 65
58
2
1
>52
12...22mm
12...18mm
4
22...26.7mm 12...18mm
3
1m m
1
1
15 Nm
CrNi(INOX) 25 Nm
2
2
2
Z-PI
V5.01. 01.2013 Subject to modification
>20
1 2
5
65
13
59
L
min . 84
6...12.7mm
37...100%
R
ZG-TF1
!
max. 1 Nm
60
ZDB-TF
L
min . 20
6...12.7mm
37...100%
R
ZDB-TF
8...16
R
min . 84
R .2 0
L
1 .8 .6 .4 .8 .6 .4 .2 0 L
Mad d erlan in Switz e in erlan Switz d
1 .8
% .100 37..
.6 .4 .2 0 L
Made in Sw and itzerl
Made
8...16
min
R
. 20
0 R .2
L
.8
1 .8 .6 .4 .8 .6 .4 .2 0 L
Made d erlan in Switz d erlan in Switz
% .100 37..
ZDB-LF
.6 .4 .2 0 L
in Made d erlan Switz
ZDB-LF
Made
ZDB-LF
61
10...22
min
. 85
10...21
min
. 15
19...25.4
21...26
10 10 Nm
33...100%
.2
.9 .8 .7 .6 .5 .4 .3 .2 .1
.4 .6
.8
62
117 m m
12 ... 22 mm
12 ... 18 mm
12 ... 22 mm
12 ... 18 mm
20 m
22 ... 26.7 mm
12 ... 18 mm
22 ... 26.7 mm
12 ... 18 mm
0 .1 .2 .3 .4 .5 .6 .7 .8 .9 1
0 .1 .2 .3 .4 .5 .6 .7 .8 .9 1
0=Y
0=Y
0=Y
63
40 ... 100%
.9
.8
.7
.6
13 15 Nm
Y= 0
IN
12 m m
Y= 0
25 Nm
Y=0
Y=0
64
52 m m
12 ... 22 mm
12 ... 18 mm
22 ... 26.7 mm
12 ... 18 mm
3 2
1 1
4
2
13
5
1 2 Z-Pl 65
1
15Nm
1 mm
65
66
20 m m
Open/Close control ~ 2 2 2 T 1 N 1 N
V5.01. 01.2013 Subject to modification
Open/Close control
AC 24V + DC 24V
CMU24(-T) CMU24-F8(-F10)
!
Y U
DC 2(0)...10V DC 2...10V
1 T
2 ~
CMU24-SR-R
CMU230 CMU230-F8(-F10)
CMU230-RES CMU230-F8(-F10)-RES
~
0 0
AC 24V + DC 24V
CMU24(-T) CMU24-F8(-F10)
CMU230(-T) CMU230-F8(-F10)
67
Wiring diagrams: Open/Close actuatorsparallel connection possible, please note the performance data.
1-wire control + AC 24V DC 24V 2-wire control
Direction of rotation
0
(while
1 0
S1 S2 S3
S1 S2 S3
0...100%
AC 100...240V
S1 S2 S3
1 0
S1 S2 S3
S1 S2 S3
0...100%
Wiring diagram: Modulating actuatorsparallel connection possible, please note the performance data.
Position - signal voltage ~ T + AC 24V DC 24V
!
Y U
% of 95 100
DC 2(0)...10V DC 2...10V
50
0 0 2 5
AC 100...240V
Direction of rotation
68
~
0 0
AC 24V DC 24V
T T
Direction of rotation
0
(while
1 0
S1 S2 S3
S1 S2 S3
0...100%
S1 S2 S3
1 0
S1 S2 S3
S1 S2 S3
0...100%
Closed
Closed
Y 10 [ V ]
clockwiseclosing damper
0 1
L ~ 2
M M
S1 S2 S3
<x >x
x = 0...100%
TF230-S, TF24-S
TF230, TF24
N T 1 T 1 T 1
L ~ 2
M M
S1 S2 S3
<x >x
x = 0...100%
LF230-S, LF24-S
LF230, LF24
L ~ 2
M M
AC 24...240V DC 24...125V
S1 S2 S3 S4 S5 S6
10%
10%...90% adjustable
NFU-S2, SFU-S2
NFU, SFU
L ~ 2
M
S1 S2 S3 S4 S5 S6
10%
69
AC 24V
70
~ ~ ~ ~
T T T T
Reversing switch
a (Y 1 )
b (Y 2 )
stop
stop
stop
stop
Y1
Y2
TF24-3
Mounting side
1 1 .8 .6 .4 .2 .2 0 0 .4
AC 24V + DC 24V
.8 .6
Reversing switch
a (Y 1 )
b (Y 2 )
stop
stop
stop
stop
Y1
Y2
LF24-3
Mounting side
AC 24V + DC 24V
AC 24V + DC 24V
1
V5.01. 01.2013 Subject to modification
~ ~ ~ ~ ~ ~
T T T T T T
AC 24V + DC 24V
!
Y U
1 .8 .6
1 .8 .6
DC 2(0)...10V
L
.4 .2 0 0 .2
.4
DC 2...10V
Reversing switch
with Y=0
with Y=0
with Y=0
with Y=0
LF24-SR
Mounting side
!
Y U
1 .8 .6
1 .8 .6
DC 2(0)...10V
L
.4 .2 0 0 .2
.4
DC 2...10V
Reversing switch
5
with Y=0 with Y=0 with Y=0 with Y=0
TF24-SR
Mounting side
1 .8 .6 1 .8 .6 .4 .2 .2 0 0 .4
Y U
DC 2(0)...10V DC 2...10V
L
Reversing switch
5
with Y=0 with Y=0 with Y=0 with Y=0
TF230-SR
!
Y U 5
Mounting side
1 .8 .6 .4 .4 .2 .2 0 0
DC 2(0)...10V DC 2...10V
.6
Reversing switch
with Y=0
with Y=0
with Y=0
with Y=0
71
O p e n / C l o s e c o nt ro l
T AC 24V + DC 24V
U 1 3 4 5
DC 2...10V 1 2 3 4 5
Y1
GKU24-MF
72
T 1 T T
GKU24
Y U 3 4 5
DC 2(0)...10V DC 2...10V
Y1
GKU24-MF
3 -p o i n t c o n tr o l
Connection via safety isolated transformer
AC 24V + DC 24V
b U DC 2...10V
a (Y 1 ) b (Y 2 )
Reversing switch
0 1 0 1
stop
stop
Y1
Y2
GKU24-MF
1
S1 S1
2 1
1 .8
.6 .8 .4 .2 1
.6 .4
0
S2 S1 S3 S1
S2
73
Electrical Accessories
Actuators CMU S..A.. Auxiliary switch, add on S1A 1xSPDT 3A(0.5A), AC 250V S2A 2xSPDT 3A(0.5A), AC 250V S2A -F 1xSPDT 3A(0.5A), AC 250V Feedback potentiometer, add on P140A.. 140 P500A.. 500 P1000A.. 1000 P2800A.. 2800 P5000A.. 5000 P10000A.. 10000 P200A-F 200 Positioner for surface mounting 0...100% Reversible operating range DC 0...10V or DC 2...10V Positioner for rack mounting 0...100% Reversible operating range DC 0...10V or DC 2...10V Positioner for front-panel mounting 0...100% Reversible operating range DC 0...10V or DC 2...10V Digital position indicator for front-panel mounting 0...99% Front size 72x72mm Operating range DC 2...10V 1) LMU . . NMU . . SMU . . GMU . . . . . TF LF NFU SFU EFU GKU . .
P..A..
. . . . . .
. . . . . .
. . . . . .
. . . . . . . . 1) . 1) 1)
. . . . . .
SGA24
1)
1)
1)
1)
1)
1)
2)
SGE24
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
2)
SGF24
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
2)
ZDA24
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
2)
74
Mechanical Accessories
Actuators LMU AN-20 Actuator arm NMU LMQU NMQU . SMU SMDU . GMU SMQU TF LF NFU SFU
AH-25
Actuator arm
AH-GMA
Actuator arm
AV6-20
Shaft extension Length approximately 170mm For damper spindles 6...20mm Extension 10mm Shaft extension Length approximately 250mm For damper spindles 8...25mm Extension 20mm NFU/SFU.. position indicator
AV8-25
IND-AFB
K6-1
Spindle clamp for LF.. For damper spindles 16...20mm NFU/SFU.. standard clamp 1/2, 3/4, 1.05
K7-2
K-ENSA
K-NA
K-SA
KG8
Ball joint Suitable for damper crank arm KH8 For round steel rod with 8mm Zinc-plated steel Ball joint Suitable for damper crank arm KH8 For round steel rod with 10mm Zinc-plated steel
KG10A
75
Mechanical Accessories
Actuators LMU ZG-118 NFU/SFU.. mounting bracket NMU LMQU NMQU SMU SMDU GMU SMQU TF LF NFU . SFU .
ZG-AFB
ZG-AFB118
ZG-GMA
ZG-LF1
Damper linkage kit For side mounting (with 2 ball joint KG8)
ZG-LF3
Damper linkage kit For side mounting (with 2 ball joint KG8)
ZG-NMA
ZG-SMA
ZG-TF1
Z-AF
ZF10-NSA-F
10x10 formfit adapter multpack 20 pieces 12x12 formfit adapter mutipack 20 pieces 16x16 formfit adapter mutipack 20 pieces
ZF12-NSA-F
ZF16-NSA-F
76
Series NFU..
Old models
NF24 NF230 NF24-S NF230-S NF24-SR
New Generation
NFU
Description
Open/Close 10Nm Open/Close 10Nm
NFU-S2
Open/Close 10Nm, 2xSPDT auxiliary switch Open/Close 10Nm, 2xSPDT auxiliary switch
NFU24-SR SFU
Modulating 10Nm Open/Close 20Nm Open/Close 20Nm Open/Close 20Nm Open/Close 20Nm
SFU..
AF24 AFR24 AF230 AFR230 AF24-S AFR24-S AF230-S AFR230-S AF24-SR AFR24-SR
SFU-S2
Open/Close 20Nm, 2xSPDT auxiliary switch Open/Close 20Nm, 2xSPDT auxiliary switch Open/Close 20Nm, 2xSPDT auxiliary switch Open/Close 20Nm, 2xSPDT auxiliary switch
SFU24-SR
77
Japan Office: Belimo Actuators Ltd. 7th Floor, Honjo-Azumabashi DJ Building 4-19-3, Honjo, Sumida-ku Tokyo 130-0004, Japan Tel: +81 3 6823 6961 Fax: +81 3 3626 3911 E-mail: info.japan@belimo.ch Malaysia Office: Belimo Actuators Ltd. 12-1, Jalan PJS 10/2, Subang Indah 46000 Petaling Jaya Selangor, Malaysia Tel: +603 5631 2188 Fax: +603 5638 2189 E-mail: info.malaysia@belimo.ch Singapore Office: Belimo Actuators Ltd. 1 Tannery Road #08-04, One Tannery Singapore 347719 Tel: +65 6842 1626 Fax: +65 6842 1630 E-mail: info.singapore@belimo.ch Taiwan Office: Belimo Actuators Ltd. 7F-2, No. 343, Jhonghe Road, Yonghe City Taipei County 234, Taiwan Tel: +886 2 2922 8805 Fax: +886 2 2922 8806 E-mail: info.taiwan@belimo.ch Thailand Office: Belimo Actuators Ltd. 90/2 Pensiri Place Soi Phaholyothin 32, Phaholyothin Road Chandrakasem, Jatujak Bangkok 10900, Thailand Tel: +662 9415582-3 Fax: +662 9415584 E-mail: info.thailand@belimo.ch
Belimo AUSTRALIA
Melbourne Office: Belimo Actuators Pty. Ltd. 12 Enterprise Court Mulgrave Business Park Mulgrave, VIC 3170, Australia Tel: +61 (0)3 9545 0844 Fax: +61 (0)3 9545 0855 E-mail: info.australia@belimo.ch Sydney Office: Belimo Actuators Pty. Ltd. Suite 2.20, 32 Delhi Road North Ryde, NSW 2113 Australia Tel: +61 (0)2 9805 1777 Fax: +61 (0)2 9805 1722 E-mail: info.australia@belimo.ch
Belimo CHINA
Shanghai Office: Belimo Actuators (Shanghai) Trading Ltd. 479 Chun Dong Road, Building C-2 Xin Zhuang Industry Park Shanghai 201108, P.R. China Tel: +86 21 5483 2929 Fax: +86 21 5483 2930 E-mail: info.shanghai@belimo.ch Beijing Office: Belimo Actuators Ltd. Room 605, Hai Chang Edifice 44 Liang Ma Qiao Road Beijing 100016, P.R. China Tel: +86 10 6462 1382 Fax: +86 10 6462 1383 E-mail: info.beijing@belimo.ch Chongqing Office: Belimo Actuators Ltd. Room 4, 9th floor, Unit 7, Luoma Jiari Garden No. 36, QingLong Road, Nanan District Chongqing 400060, P.R. China Tel: +86 23 6275 3155 Fax: +86 23 6280 3380 *519 E-mail: info.chongqing@belimo.ch Guangzhou Office: Belimo Actuators Ltd. Room 1202, Skyline Plaza 644 Tong Fu East Road, Haizhu Area Guangzhou 510240, P.R. China Tel: +86 20 3435 1860 Fax: +86 20 3435 1870 E-mail: info.guangzhou@belimo.ch
Belimo INDIA
Mumbai Office: Belimo Actuators India Pvt. Ltd. 23/ ABCD, Govt. Industrial Estate, Charkop, Kandivali West, Mumbai 400067, India Tel: +91 22 4025 4800 Fax: +91 22 4025 4899 E-mail: info.india@belimo.ch Bangalore Office: Belimo Actuators India Pvt. Ltd. Sreerama Complex, No. 13, 2nd Floor, 5th Cross Road, 6th Block, Koramangala, Bangalore 560097, India Tel: +91 80 4090 6311 Fax: +91 80 4090 6288 E-mail: info.india@belimo.ch New Delhi Office: Belimo Actuators India Pvt. Ltd. Flat No. 516, DLF Tower B, Jasola Distt. Centre, Jasola, New Delhi 110025, India Phone: +91 11 41078501 to 41078507 Fax: +91 11 41078508 E-mail: info.india@belimo.ch Chennai Office: Belimo Actuators India Pvt. Ltd. #25, Bagavadam Street, T-Nagar Chennai 600017, India Tel: +91 44 4299 9450 Fax: +91 44 4299 9451 E-mail: info.india@belimo.ch
www.belimo.com
Belimo Regional Head Offices EU BELIMO Automation AG Brunnenbachstrasse 1 8340 Hinwil, Switzerland Tel: +41 43 843 61 11 Fax: +41 43 843 62 68 E-mail: info@belimo.ch AP BELIMO Actuators (Shanghai) Trading Ltd. 479 Chun Dong Road, Building C-2 Xin Zhuang Industry Park Shanghai 201108, P.R. China Tel: +86 21 5483 2929 Fax: +86 21 5483 2930 E-mail: info.asiapacific@belimo.ch US BELIMO Aircontrol (USA), Inc. 43 Old Ridgebury Road Danbury, CT 06813-2928, USA Tel: +800 543-9038 / 203 791-9915 Fax: +800 228-8283 / 203 791-9919