GFE-AD SERIES,

Addressable Photoelectric Smoke, ROR & Fixed Temperature Heat Detector and Combined Smoke + Heat Detector

Installation Wiring Diagram


LOOP +
COMPATIBLE
3.

The base of the smoke detector can be mounted directly onto most standard electrical junction boxes without using any type of mechanical adaptor. For surface wired installations the base adaptor P/N 882912 for two wire, P/N 884912 for four wire has cable entry points to accept standard electrical conduit.

CONTROL
PANEL

INSTALLING THE HEAD

TYPICAL WIRING DIAGRAM


THE GFE-AD SERIES DETECT CONTROL PANEL.

1. Set the desired address via DIP switch on the back of the detector, see ADDRESS SETTING section. 2. Align the components as shown in Figure 2. 3. Fit the detector head onto the base and twist clockwise to secure it. 4. After all detectors have been installed, apply power to the control unit and activate the detection Loop. 5. Test the detector(s) as described in the TESTING section of this manual. Note: Do not install the detector head until the area is thoroughly cleaned of construction debris, dusts, etc. Please refer to control panel technical information regarding the maximum number of detectors installed on the same loop.

When installed, terminals 4 and 6 are for connection of remote LED ORS MUST BE CONNECTED TO A COMPATIBLE ANALOGUE ADDRESSABLE FIRE ALARM THE INSTALLATION MUST BE IN COMPLIANCE WITH THE CONTROL PANEL SYSTEM INSTALLATION MANUAL.

WARNING
TO PREVENT DETECTOR CONTAMINATION AND SUBSEQUENT INVALIDATION OF WARRANTY, THE SMOKE DETECTOR MUST REMAIN COVERED UNTIL THE AREA IS CLEAN AND DUST FREE.

GENERAL DESCRITPTION GFE-AD series consists of: Photo electric smoke detectors, Rate of Rise and Fixed temperature detectors and combined smoke / heat detectors with advanced analogue addressable communications. DIP switches are provided for setting the detectors address. GFE-AD-S: Analogue addressable smoke detector GFE-AD-S-L: Analogue addressable smoke detector with remote LED output GFE-AD-SH: Analogue addressable smoke and rate-of-rise and fixed temperature heat detector GFE-AD-SH-L: Analogue addressable smoke and rate-of-rise and fixed temperature heat detector with remote LED output GFE-AD-H: Analogue addressable rate-of-rise and fixed temperature heat detector GFE-AD-H-L: Analogue addressable rate-of-rise and fixed temperature heat detector with remote LED output Note: The base model no. for GFE-AD-S, GFE-AD-SH and GFE-AD-H is P/N772912. The base model no. for GFE-AD-S-L, GFE-AD-SH-L and GFE-AD-H-L is P/N774912. INSTALLING THE BASE 1. To insure proper fit of the detector head to the base, all wires should be properly dressed at installation: (A) Position all the wires flat against terminals. (B) Fasten the wires away from connector terminals. 2. The detectors are intended for ceiling or wall mounting in accordance with local Fire authority recommendations.

Fig. 2 Fitting detector head onto base. Note Alignment marks TESTING All remote signaling systems, releasing devices and extinguishing systems should be disconnected during the test period and reconnected at the conclusion of testing. SMOKE SENSOR TESTING Allow smoke from a cotton wick or a test smoke aerosol to enter the detector-sensing chamber for at least 10 seconds. When sufficient smoke has entered the chamber, the detector will signal an alarm, this being indicated by illumination of the red LED. Make sure to clear smoke out of the chamber before resetting in order to keep the detector

at its current sensitivity setting. HEAT SENSOR TESTING The detector to be tested should be subject to a flow of warm air at a temperature of between 65C and 80C. (This requirement can be met by some domestic hair dryers). Proceed as follows: 1. Switch on the warm airflow and check that temperature is

correct and stable. 2. From a distance of several inches, direct the airflow at the guard protecting the thermistor. The detector should alarm within 60 seconds. 3. Upon alarm immediately remove the heat source and check that the red LED of the detector is illuminated. 4. If a detector fails to activate within 60 seconds, confirm connections and programming. If necessary replace and return to distributor for recalibration. NOTE: After testing, check that the system is returned to normal operation. Notify the appropriate authorities that the testing procedure has been completed and the system is active again. MAINTENANCE The recommended minimum requirement for detector maintenance consists of an annual cleaning of dust from the detector head by using a low power vacuum cleaner. CAUTION: DO NOT ATTEMPT TO DISASSEMBLE THE DETECTOR. THIS IS A SENSITIVE DEVICE AND IS NOT Address DIP switch settings

INTENDED TO BE OPENED FOR SERVICING BY USERS. OPENING THE DETECTOR HEAD WILL VOID THE WARRANTY. ADDRESS SETTING. Please consult the Address Dip switch setting chart for details of the Binary equivalent numbers. Note: Switch 8 is always off. (Unused) SPECIFICATIONS Operating Voltage Range: 17 to 28 VDC Standby Current: 500A @ 24 VDC Max. Alarm Current 5 mA @ 24 VDC (LED ON); Max. Remote LED output current: 2mA@1.5V Operating Humidity Range: 10% to 93% Relative Humidity, non condensing Operating Temperature Range: 0 to 49C (32 to 120F); Certification: EN 54 part 5 / 7(0845 CPD 232.1482, 0845 CPD 232.1483, 0845 CPD 232.1484) Height: 1.8 inches (46 mm) with base , Diameter: 3.93 inches (100 mm) with base.

DIP SWITCH for address setting

Dip switch

Global Fire Equipment Ltd. declares that this product is free from defects in material and workmanship. And it will repair or replace any product or part thereof which proves to be defective in workmanship or material for a period of 24 months from the date of purchase. Please visit the Global Fire Website for a full description of Global Fire Equipments LIMITED WARRANTY, which, among other things, limits the duration of warranties of merchantability and fitness for a particular purpose and excludes liability for consequential damages. Acceptance of order and/or original invoice which will become part of your sales agreement. Please contact Global Fire Equip directly for a return merchandise authorization (RMA) number before returning goods to the factory . Shipment must be prepaid and Global Fire repair or replace your returned detector.

LIMITED WARRANTY STATEMENT

Global Fire Equipment Ltda. Urb. Vale da Amoreira, Lt. 16 & 17, Porta A, Cave, 8005-334 FARO, PORTUGAL