MAJOR FINDINGS
p2 1/2/12
CONDITION
Safety Issue: No catwalk provision for Cooling Tower Personnel in accessing/ inspecting the motor, belt, pillow block bearing, etc Provide Catwalk
p3 1/2/12
p4 1/2/12
CONDITION RECOMMENDATION
No signage for FE, provide easy access. Provide a signage which can easily be seen and remove obstruction to FE Inspect all PFE for possible similar scenario
p5 1/2/12
p6 1/2/12
p8 1/2/12
p9 1/2/12
p10 1/2/12
p12 1/2/12
p13 1/2/12
CONDITION
p14 1/2/12
p15 1/2/12
p16 1/2/12
MINOR FINDINGS
FIRE PROTECTION
CONDITION RECOMMENDATION RESPONSIBLE TARGET DATE Broken Glass of FHC at 2nd floor south left wing entrance Replace the broken glass for safety
p19 1/2/12
ROOFING
CONDITION Presence of Plastic at gutter: Extension bridge from mall to cyberpad Remove or execute housekeeping of gutters
p20 1/2/12
ROOFING
CONDITION
Roof flashing to wall termination: possible source of leaks Rectify Consult waterproofing contractor for correct solution.
RECOMMENDATION
p22 1/2/12
VACS
CONDITION Sign of corrosion of AHU support and valves at Tenant Store 1 Remove the rust and install proper insulation.
p24 1/2/12
VACS
CONDITION RECOMMENDATION RESPONSIBLE TARGET DATE Corrosion starting to build up at Chilled water pipe Paint the pipes with anticorrosive paint
p26 1/2/12
ELECTRICAL SYSTEM
p27 1/2/12
ELECTRICAL SYSTEM
CONDITION RECOMMENDATION Corroded and Open Junction boxes at AHU rooms Remove rust then repaint/ Cover all open junction boxes Inspect all areas for possible open junction box
p28 1/2/12
ELECTRICAL SYSTEM
CONDITION RECOMMENDATION RESPONSIBLE TARGET DATE Improper tagging of panel board at Tenant Store 1 Provide proper tagging and panel directory
p30 1/2/12
ELECTRICAL SYSTEM
CONDITION RECOMMENDATION RESPONSIBLE TARGET DATE Presence of dangling telephone wire at the roof. Remove / relocate the telephone wire Telco
p31 1/2/12
ELECTRICAL SYSTEM
CONDITION Presence of litters, tools and unwanted stocks at EE room of Tenant Store 1 Remove all unwanted materials inside EE room
p32 1/2/12
ELECTRICAL SYSTEM
CONDITION Improper installation of MDF lines at MDF room with presence of stocks Remove stocks/Rewiring
p33 1/2/12
EXTERIOR
CONDITION RECOMMENDATION RESPONSIBLE TARGET DATE Sign of corrosion of Drop down banner frame Remove the rust then Repaint
p36 1/2/12
EXTERIOR
CONDITION 1.No floodlight at the top of Drop Down Banner 2. All electrical lines are exposed Install floodlight if still needed(see effect during night time) All electrical lines should be place inside a conduit for weather protection, short circuit and safety
RECOMMENDATION
p37 1/2/12
EXTERIOR
CONDITION Gutter waterponding, presence of garbage and accumulation of algae Execute housekeeping of the canopy
p38 1/2/12
EXTERIOR
CONDITION RECOMMENDATION RESPONSIBLE TARGET DATE Building cracks near pump room (scattered along exterior wall) Rectify/Apply sealant or epoxy injection
p39 1/2/12
EXTERIOR
CONDITION RECOMMENDATION RESPONSIBLE TARGET DATE Damage EIFS at Cinema and near Cooling Tower Repair
p41 1/2/12
EXTERIOR
CONDITION Presence of leak at canopy area at Store Entrance and Tenant Store 1 Rectify
p42 1/2/12
INTERIOR
CONDITION RECOMMENDATION RESPONSIBLE TARGET DATE Damage walls near EE room going to Cyberzone Repair
p45 1/2/12
CPS - Nonpotable
CONDITION CPS pump #3: starting to accumulate dirt and corrosion Pressure gauge: Glass cover not fixed Repair/Rectify
p48 1/2/12
EXHAUST SYSTEM
CONDITION RECOMMENDATION RESPONSIBLE TARGET DATE Corroded base, vibration isolator, bolts and nuts Remove rust then repaint
p49 1/2/12
EXHAUST SYSTEM
CONDITION RECOMMENDATION
Damage Kitchen Air Supply Fan wire mesh Rectify, design a wiremesh frame which can be easily detached.
p50 1/2/12
OTHERS
CONDITION 1. Open canal @ Tenant Store 1 2. Leak coming TS 1 area 3. Open Floor Drain Remove dirt from canal and rectify condition 2 and 3
p54 1/2/12
OTHERS
CONDITION Presence of garbage, litters, molds, and dried algae at Roof Deck Housekeeping
p56 1/2/12
OTHERS
CONDITION RECOMMENDATION RESPONSIBLE TARGET DATE Damage tiles at Garbage House Rectify/Replace damage tiles
p58 1/2/12
OTHER SYSTEMS
STP With live mosquito larvae Determined the consumption rate of chlorine per day Proper dozing of chlorine FREIGHT ELEVATOR 1 (T1 Store) With abnormal sound of door when open and close (Door Limit switch on going observation) Slow down limit defective for quotation. FREIGHT ELEVATOR (Main) Operational
p60 1/2/12
PASSENGER ELEVATOR (Main) Operational no concern ESCALATOR (Main) Escalator #2( going Down) Handrail Canvas (Partial Damage) Escalator #5 (going Up) Newel guide roller (Partial Damage Right Side) Escalator #3 (going Up) Temporary motor (service unit) Original Motor for rewiring since August 2011 ESCALATOR (TS 1) Escalator #1 (going Up) Oil Leak at motor assembly for Quotation
p62 1/2/12