Product Data Sheet

Classic I/O January 2008Page 1

TM

Classic I/O
I/O cards plugged into an 8-wide carrier

Redundant power supplies and controllers plugged into 2-wide carriers

Additional I/O The DeltaV I/O subsystem is easy to install and maintain.

Decreases capital equipment costs Decreases installation time and expense Increases productivity

The Classic I/O subsystem includes: I/O interface carrier (a DIN rail surface mounted) on which all I/O related components are installed. Bulk AC to 24 VDC power supply for field devices. An I/O interface consisting of an I/O card and an I/O terminal block. A variety of analog and discrete I/O cards enclosed in a common form factor that easily plugs into the I/O interface carrier. A variety of I/O terminal blocks mounted on the I/O interface carrier that can be prewired before I/O card installation.

Introduction
Classic I/O is a modular subsystem that offers flexibility during installation. Its designed to be installed in the field, near your devices. Classic I/O is equipped with function and field wiring protection keys to ensure that the correct I/O card is always plugged into the corresponding terminal block. Modularity, protection keys, and plug and play capabilities make DeltaV Classic I/O a smart choice for your process control system.

Product Data Sheet


Classic I/O January 2008Page 2

TM

Benefits
Decreases capital equipment costs.
Full system modularity. The Classic I/O subsystem was designed with your investment in mind. All components are fully modular and may be installable under power.1 You add I/O interface carriers and I/O interfaces in groups of 8 channels as you need them. The modular design enables you to purchase the exact amount of I/O cards, 8-wide carriers, power/controllers, and 2-wide carriers you need and add more DeltaV I/O as your system grows. Reduced system footprint. The DeltaV systems state-of-the-art form factor design of the I/O components enables you to mount the I/O interface carrier in a junction box in the field so you significantly reduce the footprint of your equipment and increase valuable control room space for other uses. Installation. Save on wiring expenses by installing Classic I/O in the field, near the actual field devices. Mounting the controller with the I/O further reduces your wiring expenditures by eliminating the need for long runs of multi-cores. The integrated design of the I/O subsystem can eliminate the need for marshaling panels. This saves you even more in your total capital costs. The provision of in-line fuses and bussed power saves on installation costs compared with external fuses and power distribution.

Decreases installation time and expense.


Plug-and-play installation saves money. All Classic I/O components plug into the I/O interface carrier. You can install the I/O interface carriers to manage anticipated growth and postpone the I/O interfaces until youre ready to install your additional field devices. Phased installation saves time. As soon as you mount the I/O interface carrier, youre ready to begin installing the field devices. I/O terminal blocks plug directly onto the I/O interface carrier. There is no need to have the I/O cards installed.

Classic I/O terminal block.

Keys. Classic I/O interfaces and terminal blocks have I/O function keys. These keys ensure that the correct I/O card is always plugged into the corresponding terminal block. Its incredibly easy to use and gives you time to do more. Refer to Zone 2 installation instructions (12P2046) and/or Class 1 Division 2 installation instructions (12P1293) for details.
1

This design enables you to initially install Classic I/O quickly and efficiently. When you need to replace an I/O card, the function key design ensures that you

Product Data Sheet


Classic I/O January 2008Page 3

TM

will always install it correctly. This keying system provides a safety measure by preventing the wrong I/O interfaces being installed.

Product Description and Specification I/O Cards


A variety of analog and discrete I/O cards is available to meet your specific requirements. All I/O cards are enclosed in a common form factor that plugs into the I/O interface carrier. The housing is clearly labeled with the enclosed I/O card type. Clearly visible LEDs on the top of the I/O card display the power, error, and status to the channels included in the I/O card. We have met ISA G3 corrosion specifications by the careful selection of superior electronic components and the use of conformal coating. For slow pulse applications (< 125 Hz) any discrete input card can be used. The most commonly used discrete input cards for pulse applications are the discrete input 24 VDC. If youre entering the world of smart plants, then you may be interested in the benefits associated with HART and FOUNDATION fieldbus I/O. For detailed information about these products, refer to the appropriate product data sheet.

Increases productivity.
Real-time, online equipment additions. Online addition of new I/O interfaces means your process does not get interrupted. As new equipment is added, the DeltaV Explorer acknowledges it and assigns it basic configuration.

A Classic I/O card easily plugs into an I/O carrier.

Product Data Sheet


Classic I/O January 2008Page 4

TM

The following tables list the specifications for the Classic I/O:
Common Environmental Specifications for all I/O Interfaces Category Storage temperature Operating temperature Relative humidity Specifications: -40 to 85 C (-40 to 185 F) 0 to 60 C (32 to 140 F) 5 to 95% , non-condensing Airborne contaminants Protection rating Hazardous area/location* Shock Vibration ISA-S71.04-1985 Airborne Contaminants Class G3 Conformal coating

IP 20, NEMA 12 Class 1, Div 2, Groups A, B, C, D, T4 hazardous locations, or ATEX 3 G IIC T4 10 g -sine wave for 11 ms 1 mm peak-to-peak from 5 to 16 Hz; 0.5 g from 16 to 150 Hz H 10.7 cm (4.2 in.) W 4.1 cm (1.6 in.) Depth 10.5 cm (4.1 in.)

Dimensions

*Refer to Zone 2 installation instructions (12P2046) and/or Class 1 Division 2 installation instructions (12P1293)

for information on installing in hazardous areas.

Product Data Sheet


Classic I/O January 2008Page 5

TM

Analog I/O Cards


Specifications for HART AI-Card, 8 channel, 4 to 20 mA Number of channels Isolation Nominal signal range (span) Full signal range LocalBus current (12 VDC nominal) per card Field circuit power per card Accuracy over temperature range Resolution Repeatability Rolloff frequency Calibration Optional fuse Hazardous area/location 8 Each channel is optically isolated from the system and factory tested to 1500 VDC. 4 to 20 mA 1 to 22.5 mA, with overrange checking 120 mA typical, 150 mA maximum 300 mA maximum at 24 VDC (+10%) 0.1% of span 16 bits 0.05% of span -3 dB at 2.7 Hz; -20.5 dB at the sampling frequency None required 2.0 A Class 1, Div 2, Groups A, B, C, D, T4 hazardous locations ATEX 3 G IIC T4

Field wiring

Class 1, Div 2, Groups A, B, C, D, T4 2-wirenon-incendive 4-wirenon-arcing 2-wire ATEX 3 G IIC T4 -nL 4-wire ATEX 3 G IIC T4 -nA
2

Non-incendive field circuits are designed such that under normal operating conditions energy is limited.

Product Data Sheet


Classic I/O January 2008Page 6

TM

Specifications for HART AO Card, 8 channel, 4 to 20 mA Number of channels Isolation Nominal signal range (span) Full signal range LocalBus current (12 VDC nominal) per card Field circuit power per card Accuracy over temperature range Resolution Output compliance Calibration Optional fuse Hazardous area/location 8 Each channel is optically isolated from the system and factory tested to 1500 VDC. 4 to 20 mA 1 to 23 mA 100 mA typical, 150 mA maximum 300 mA maximum @ 24 VDC (+/-10%) 0.25% of span 12 bits 20 mA at 21.6 VDC supply into 700 load Information stored on card. 2.0 A Class 1, Div 2, Groups A, B, C, D T4 hazardous locations ATEX 3 G IIC T4 Field wiring Class I, Div 2, Groups A, B, C, D T4 non-incendive ATEX 3 G IIC T4 -nL

Product Data Sheet


Classic I/O January 2008Page 7

TM

RTD I/O Card


Specifications for RTD Input Card, 8 channel
RTD channels per card Sensor types LocalBus power rating Repeatability Calibration Resolution (varies by sensor type) Wiring Sensor type 8 2 wire, 3 wire, or 4 wire: Resistance, Pt100, Pt200, Pt500, Ni120, Cu10, user defined 12 VDC, 160 mA 0.05% of span None required 16 bit. See RTD, ohms sensor type specifications (next page). 2, 3 and 4 wire sensors 100 ohm platinum 200 ohm platinum 500 ohm platinum 120 ohm nickel 10 ohm copper Custom RTD available Degrees C Degrees F -200 to 870 Degrees C Constant current source supplied by card 100 dB at 50/60 Hz > 10 megohms 100 dB at 50/60 Hz, -20dB at the sampling frequency 1 second 1 second (filtering is appropriate to realize a true 1 second detection

Units Temperature range Sensor excitation Common mode rejection Common mode impedance Normal mode rejection rolloff Frequency Open RTD response time Scan time Environmental conditions Temperature Operating Rate of Change Storage Relative humidity Operating Storage Hazardous area/location

0 to 60 Degrees C 1 degree C per minute without performance degradation -40 to 85 degrees C 5 to 95% (non-condensing) 5 to 95% (non-condensing) Class 1, Div 2, Groups A, B,C,D, T4 ATEX 3 G IIC T4 Class 1, Div 2, Groups A, B,C,D, T4 non-incendive ATEX 3 G IIC T4 -nL

Field wiring

Product Data Sheet


Classic I/O January 2008Page 8

TM

RTD, ohms Sensor Type Specifications Sensor Type


Resistance Pt100 Pt200 Pt500 Ni120 Cu10 User defined

Full Scale
0 to 2,000 ohms -200 to 850C -200 to 850C -200 to 850C -70 to 300C -30 to 140C 0 to 1000 ohms

Operating Range 25 Reference Accuracy


0 to 2,000 ohms -200 to 850C -200 to 850C -200 to 850C 70 to 300C -30 to 140C 0 to 1000 ohms 6.2 ohms 0.5 C 0.5 C 3.5 C 0.2 C 2.0 C 0.4 ohms

Temperature Drift
0.112 ohms/C 0.018 C/C 0.012 C/C 0.063 C/C 0.006 C/C 0.157 C/C 0.009 ohms/C

Resolution
~0.02 ohms ~0.05 C ~0.05 C ~0.18 C ~0.02 C ~0.23 C ~0.05 ohms

Product Data Sheet


Classic I/O January 2008Page 9

TM

Thermocouple/ Millivolt I/O Card


Specifications for Thermocouple Input Card, 8 channel Thermocouple or millivolt channels per card Resolution (varies by sensor type) Isolation 8 16 bit. See thermocouple/mV sensor type specifications (next page). Each channel is optically isolated from the system and factory tested to 1500 VDC. Channels 1, 2, 3, and 4 are isolated from channels 5, 6, 7, and 8 (verified by 1500 VDC factory test). Thermocouples attached to channels 1, 2, 3, and 4 are not electrically isolated and should be within + 0.7 VDC of each other. Thermocouples attached to channels 5, 6, 7, and 8 are not electrically isolated and should be within + 0.7 VDC of each other. Low level voltage source B, E, J, K, N, R, S, T, uncharacterized 12 VDC, 350 mA 0.05% of span

Sensor type mV Thermocouple LocalBus power rating Repeatability Rolloff frequency mV Thermocouple Calibration Units -25 dB at 50/60 Hz, -20 dB at the sample frequency 100 at 50/60 Hz, -200 dB at the sample frequency None required Degrees C Degrees F Millivolt range Cold junction compensation Common mode rejection Common mode impedance Normal mode rejection Open thermocouple response time Open circuit detection Scan time -100 to 100 mV Integral terminal block with cold junction compensation. Also, one input channel may be configured to use external cold junction compensation 100 dB at 60 Hz > 10 megohms 60 dB at 60 Hz 1 second Yes 1 second (filtering is appropriate to realize a true 1 second detection

Product Data Sheet


Classic I/O January 2008Page 10

TM

Specifications for Thermocouple Input Card, 8 channel Environmental conditions Temperature Operating Rate of change Storage Relative humidity Operating Storage Hazardous area/location 5 to 95% (non-condensing) 5 to 95% (non-condensing) Class 1, Div 2, Groups A, B, C , D, T4 hazardous location ATEX 3 G IIC T4 Field wiring Class 1, Div 2, Groups A, B, C, D, T4 non-incendive ATEX 3 G IIC T4 -nL 0 to 60 degrees C 1 Degree C per minute without performance degradation -40 to 85 degrees C

Thermocouple Sensor Type Specifications Sensor Type Uncharacterized (no linearization, no cold junction compensation.) B E J K N R S T Full Scale -100 to 100 mV Operating Range -100 to 100 mV 25 Temperature Drift Resolution Reference Accuracy 0.1 mV 0.002 mV/ C ~ 0.003mV

250 to 1810 C -200 to 1000 C -210 to 1200 C -270 to 1372 C -270 to 1300 C -50 to 1768 C -50 to 1768 C -270 to 400 C

500 to 1810 C -200 to 1000 C -190 to 1200 C -200 to 1372 C -190 to 1300 C -50 to 1768 C -40 to 1768 C -200 to 400 C

2.4 C 0.6 C 0.8 C 0.5 C 1.0 C 2.1 C 2.2 C 0.7 C

0.056 C/ C 0.008 C/ C 0.011 C/ C 0.016 C/ C 0.007 C/ C 0.013 C/ C 0.067 C/ C 0.001 C/ C

~ 0.18 C ~ 0.07 C ~ 0.05 C ~ 0.18 C ~ 0.10 C ~ 0.14 C ~ 0.24 C ~ 0.04 C

Product Data Sheet


Classic I/O January 2008Page 11

TM

mV Sensor Type Specifications Sensor Type


Low-level voltage source

Full Scale
-100 to 100 mV

Operating Range
-100 to 100 mV

25 Reference Accuracy
0.1 mV

Temperature Drift
0.002 mV/ C

Resolution
~ 0.003 mV

Isolated Input I/O Card


Specifications for Isolated Input Card,4 channel3

Number of channels Isolation CAN/CSA-C22.2 No.1010.1-924

4 Installation Cat II, Pollution degree 2 Channel to system - 600 VAC double insulation. Each channel is optically isolated from the system and factory tested to 5000 VDC. Channel to channel - 600 V basic insulation. Each channel is optically isolated from each other and factory tested to 3100 VDC.

Dielectric strength ADC Resolution -3dB Filter Frequency DC/50/60 Hz Common Mode Rejection Input Impedance Thermocouple Sensor Types RTD Sensor Types mV and V ranges Input type mix Ambient temperature Calibration Mounting LocalBus power rating

Channel to system - 3700 V RMS Channel to channel - 2200 V RMS 16 bit 2.7 Hz 120 dB 10 Mohms B, E, J, K, N, R, S, T, Uncharacterized PT100, PT200, Ni120, Cu10, Resistance, user-defined Refer to following tables. Independently configurable -40 to 70C None required Assigned slot of I/O carrier 12 VDC, 350 mA, no field power required

3 4

Warning:

DeltaV version 7.3 is required for this card. When hazardous live voltages are present on a channel, adjacent channel wiring must be inaccessible.

Product Data Sheet


Classic I/O January 2008Page 12

TM

Isolated Input Card, Thermocouple and MilliVolt Input Specifications


Item Linearization error Cold Junction Compensation Accuracy Cold Junction Compensation types Cold Junction Compensation range Temperature scale Open circuit detection (Thermocouple only) Detection time
Specification

0.003% full scale 1.0C Off, local, remote -40 to 85C ITS90 0.4 A DC 1 second

Isolated Input Thermocouple Sensor Type Specifications Sensor Types


B E J K N R S T Uncharacterized no linearization or CJC

25C Reference Accuracy 1.2 C 0.5 C 0.6 C 0.5 C 1.0 C 1.7 C 1.8 C 0.7 C 0.05 mV

Temperature Drift 0.116 C/ C 0.004 C/ C 0.005 C/ C .013 C/ C .015 C/ C .083 C/ C .095 C/ C .025 C/ C .0003 mV/ C

Nominal Resolution
0.09 C 0.05 C 0.06 C 0.05 C 0.05 C 0.06 C 0.08 C 0.04 C .0031 mV

Full Scale
250 to 1810 C -200 to 1000 C -210 to 1200 C -270 to 1372 C -270 to 1300 C -50 to 1768 C -50 to 1768 C -270 to 400 C -100 to 100 mV

Operating Range
500 to 1810 C -200 to 1000 C -190 to 1200 C -140 to 1372 C -190 to 1300 C 0 to 1768 C 0 to 1768 C -200 to 400 C -100 to 100 mV

Isolated Input Millivolt Input Range Specifications Sensor Type 20 mV 50 mV 100 mV Input Ranges 20 mV 50 mV 100 mV 25 C Reference Accuracy 0.02 mV 0.03 mV 0.05 mV Temperature Drift 0.001 mV/C 0.0005 mV/C 0.0003 mV/C Maximum Resolution 0.0008 mV 0.0017 mV 0.0031 mV

Product Data Sheet


Classic I/O January 2008Page 13

TM

Isolated Input Card, RTD, ohms Input Specifications


Item Measurement configurations Excitation current Temperature scale Open sensor detection time Short circuit detection time Pt 100 and Pt 200 alpha Specification 2, 3, and 4 wire 100 A DC ITS90 1 second 1 second 0.00385

Isolated Input Card, RTD, ohms Input Range Specifications


Sensor Type Pt100 Pt200 Ni120 Cu10 Resistance User defined 25C Reference Accuracy 0.5 C 0.5 C 0.2 C 2.0 C 0.5 ohms 0.4 ohms

Temperature Drift 0.018 C/C 0.012 C/C 0.006 C/C 0.076 C/C 0.018 ohms/C 0.009 ohms/C

Resolution 0.05 C 0.05 C 0.02 C 0.23 C 0.02 ohms ~0.05 ohms

Sensor Input Range -200 to 850 C -200 to 850 C -70 to 300 C -30 to 140 C 1 to 1000 ohm 0 to 1000 ohms

Product Data Sheet


Classic I/O January 2008Page 14

TM

Isolated Input Card, Voltage Input Range Specifications


Sensor Type 0-5V 0 - 10 V 1-5V 1V 5V 10 V Sensor Range 0-5V 0 - 10 V 1-5V 1V 5V 10 V 25C Reference Accuracy 0.005 V 0.010 V 0.0005 V 0.0025 V 0.005 V 0.010 V Temperature Drift 0.0002 V C 0.0004 V C 0.0002 V C 0.0002 V C 0.0002 V C 0.0004 V C Maximum Resolution 0.00009 V 0.00016 V 0.00009 V 0.00015 V 0.00017 V 0.0003 V

Specifications for HART AI-Card 16 Channel, 4 to 20 mA Number of channels Isolation Nominal signal range (span) Full signal range LocalBus current (12 VDC nominal) per Card Field circuit power per Card Accuracy over temperature range Resolution Repeatability Rolloff frequency Calibration 16 Each channel is optically isolated from the system and factory tested to 1500 VDC. 4 to 20 mA 2 to 22 mA, with overrange checking 85 mA typical, 150 mA maximum 600 mA maximum at 24 VDC 0.2% of span 16 bits 0.05% of span -3 dB at 2.7 Hz; -20.5 dB at the sampling frequency None required HART pass-through request/response HART variable reporting Field device status reporting 600 800 mS (typical) per enabled channel

Communications support Hart Scan Time

Product Data Sheet


Classic I/O January 2008Page 15

TM

High-Density Discrete I/O Cards


Specifications for DI Card, 32 channel, 24 VDC, Dry Contact Number of channels Isolation Detection level for On Detection level for Off Input impedance LocalBus current (12 VDC nominal) per card Field circuit power per card Return Terminal block Hazardous areas/location 32 Each channel is optically isolated from the system and factory tested to 1500 VDC. > 2 mA < 0.25 mA 5K ohm (approximate) 50 mA typical, 75 mA maximum 150 mA at 24 VDC Uses common return 32-screw termination block Class 1 Div 2, Groups A, B, C, D, T4 hazardous location ATEX 3 G IIC T4 Field wiring Class 1, Div 2, Groups A, B, C, D, T4 non-arcing5 ATEX 3 G IIC T4 -nA6

Non-arcing field circuits are designed so that ignition does not occur during normal operation. Non-sparking circuits (-nA) are designed to minimize the risk of occurrence of arcs, sparks, or hot spots capable of creating ignition hazards during normal operation. Normal operation excludes the removal or insertion of field wiring with circuits energized.
6

Product Data Sheet


Classic I/O January 2008Page 16

TM

Specifications for DO Card, 32 channel, 24 VDC, High Side Number of channels Isolation Output range Output rating Off-state leakage LocalBus current (12 VDC nominal) per card Field circuit power per card Return Terminal block Hazardous area/location 32 Each channel is optically isolated from the system and factory tested to 1500 VDC. 24 VDC 10% 100 mA per channel 0.1 mA maximum 100 mA typical, 150 mA maximum 3.2 A at 24 VDC per I/O interface Uses common return 32-screw termination block Class 1, Div 2, Groups A, B, C, D, T4 hazardous location ATEX 3 G IIC T4 Field wiring Class 1, Div 2, Groups A, B, C, D, T4 non-arcing ATEX 3 G IIC T4 -nA

Product Data Sheet


Classic I/O January 2008Page 17

TM

Discrete I/O Cards


Specifications for DI Card, 8 channel, 24 VDC, Dry Contact Number of channels Isolation Detection level for On Detection level for Off Output Impedance LocalBus current (12 VDC nominal) per card Field circuit power per card Optional fuse Hazardous area/location 8 Each channel is optically isolated from the system and factory tested to 1500 VDC. > 2.2 mA < 1 mA 5 K (approximate) 75 mA typical, 100 mA maximum 40 mA at 24 VDC 2.0 A Class 1, Div 2, Groups A, B, C, D, T4 hazardous location ATEX 3 G IIC T4 Class 1, Div 2, Groups A, B, C, D, T4 non-incendive ATEX 3 G IIC T4 -nL

Field wiring

Specifications for DI Card, 8 channel, 24 VDC, Isolated Number of channels Isolation Detection level for On Detection level for Off Input impedance LocalBus current (12 VDC nominal) per card Field circuit power per card Optional fuse Hazardous area/location 8 Each channel is optically isolated from the system and from each other and factory tested to 1500 VDC. > 10 VDC < 5 VDC 5 mA at 24 V 75 mA typical, 100 mA maximum None 2.0 A Class 1, Div 2, Groups A, B, C, D, T4 hazardous location ATEX 3 G IIC T4 Class 1, Div 2, Groups A, B, C, D, T4 non-arcing ATEX 3 G IIC T4 -nA

Field wiring

Product Data Sheet


Classic I/O January 2008Page 18

TM

Specifications for DI Card, 8 channel, 120 VAC, Isolated Number of channels Isolation Detection level for On Detection level for Off Input load (contact cleaning) Input Impedance LocalBus current (12 VDC nominal) per card Field circuit power per card Optional fuse Hazardous area/location Field wiring 8 Each channel is optically isolated from the system at 250 VAC and from other channels at 250 VAC. 84 to 130 VAC 0 to 34 VAC 2 mA at 120 VAC 60 K 75 mA typical, 100 mA maximum None 2.0 A Class 1, Div 2, Groups A, B, C, D T4 hazardous location Class 1, Div 2, IIC T4 non-arcing

Specifications for DI Card, 8 channel, 120 VAC, Dry Contact Number of channels Isolation Detection level for On Detection level for Off Output Impedance LocalBus current (12 VDC nominal) per card Field circuit power per card Optional fuse Hazardous area/location Field wiring 8 Each channel is optically isolated from the system at 250 VAC > 1.4 mA < 0.56 mA 60 K 75 mA typical, 100 mA maximum 15 mA at 120 VAC 2.0 A Class 1, Div 2, Groups A, B, C, D T4 hazardous location Class 1, Div 2 IIC T4 non-arcing

Product Data Sheet


Classic I/O January 2008Page 19

TM

Specifications for DO Card, 8 channel, 120/230 VAC, Isolated Number of channels Isolation Output range Output rating 8 Each channel is optically isolated from system at 250 VAC and from other channels at 250 VAC 20 to 250 VAC 1.0 A continuous per channel; 2.0 A maximum per card up to 60 C (140 F) 3.0 A maximum per card up to 50 C (122 F) 2 mA maximum at 120 VAC 4 mA maximum at 230 VAC 100 mA typical, 150 mA maximum None Output Output stays in last state submitted by the controller. Output is active for a pre-configured time period (100 ms to 100 s). Output is active as a percentage of a pre-configured base time period (100 ms to 100 s). Resolution = 5 ms 2.0 A Class 1, Div 2, Groups A, B, C, D T4 hazardous location Class 1, Div 2 IIC T4 non-arcing

Off state leakage LocalBus current (12 VDC nominal) per card Field circuit power per card Configurable channel types: Discrete output Momentary output Continuous pulse output Optional fuse Hazardous area/location Field wiring

Product Data Sheet


Classic I/O January 2008Page 20

TM

Specifications for DO Card, 8 channel, 120/230 VAC, High Side7 Number of channels Isolation Output range Output rating 8 Each channel is optically isolated from the system at 250 VAC 20 to 250 VAC 1.0 A continuous per channel; 2.0 A maximum per card up to 60 C (140 F) 3.0 A maximum per card up to 50 C (122 F) 2 mA maximum at 120 VAC 4 mA maximum at 230 VAC 100 mA typical, 150 mA maximum 3.0 A at 120 VAC or 230 VAC Output Output stays in last state submitted by the controller Output is active for a pre-configured time period (100 ms to 100 s). Output is active as a percentage of a pre-configured base time period (100 ms to 100 s). Resolution = 5 ms 2.0 A Class 1, Div 2, Groups A, B, C, D T4 hazardous location Class 1, Div 2 IIC T4 non-arcing

Off state leakage LocalBus current (12 VDC nominal) per card Field circuit power per card Configurable channel types: Discrete output Momentary output Continuous pulse output Optional fuse Hazardous area/location Field wiring

High-side means the output signal is switched on the positive leg. Switching on the positive leg avoids current in field wiring when there is no output signal.

Product Data Sheet


Classic I/O January 2008Page 21

TM

Specifications for DO Card, 8 channel, 24 VDC, Isolated Number of channels Isolation Output range Output rating Off state leakage LocalBus current (12 VDC nominal) per card Field circuit power per card Configurable Channel Types: Discrete output Momentary output Continuous pulse output Hazardous area/location 8 Each channel is optically isolated from the system and from each other and factory tested to 1500 VDC. 2 VDC to 60 VDC 1.0 A 1.2 mA maximum 100 mA typical, 150 mA maximum None Output Output stays in last state submitted by the controller. Output is active for a pre-configured time period (100 ms to 100 s). Output is active as a percentage of a pre-configured base time period (100 ms to 100 s). Resolution = 5 ms Class 1, Div 2, Groups A, B, C, D, T4 hazardous locations ATEX 3 G IIC T4 Field wiring Class I, Div 2 Groups A, B, C, D, T4 non-arcing ATEX 3 G IIC T4 -nA

Product Data Sheet


Classic I/O January 2008Page 22

TM

Specifications for DO Card, 8 channel, 24 VDC, High Side Number of channels Isolation Output range Output rating Off state leakage LocalBus current (12 VDC nominal) per card Field circuit power per card Configurable channel types: Discrete output Momentary output Continuous pulse output Optional fuse Hazardous area/location 8 Each channel is optically isolated from the system and factory tested to 1500 VDC. 2 VDC to 60 VDC 1.0 A continuous per channel; 3.0 A maximum per I/O Interface 1.2 mA maximum 100 mA typical, 150 mA maximum 3.0 A at 24 VDC per I/O Interface Output Output stays in last state submitted by the controller. Output is active for a pre-configured time period (100 ms to 100 s). Output is active as a percentage of a pre-configured base time period (100 ms to 100 s). Resolution = 5 ms 2.0 A Class 1, Div 2, Groups A, B, C, D, T4 hazardous locations ATEX 3 G IIC T4 Field wiring Class I, Div 2 Groups A, B, C, D, T4 non-arcing ATEX 3 G IIC T4 -nA

Product Data Sheet


Classic I/O January 2008Page 23

TM

I/O Terminal Blocks


A variety of I/O terminal blocks is available to meet specific functionality and environmental requirements. I/O terminal blocks and I/O cards used together are equipped with function and field wiring protection keys to ensure that only the I/O card and I/O terminal block that match functionally can be plugged into each other. The terminal block keys can be preset to speed installation. For field devices that are located in an intrinsically safe zone, or discrete field devices that require more than the maximum specified current, standard mass terminated interfaces are provided with 10-, 16-, 24-, or 40- pin connections to allow mass termination cable connection to intermediary panels. The systems integrator usually installs these panels. The low-level signals are conducted over 0.093 mm (28 AWG) ribbon cable or round instrument cable. For field devices requiring external power, the 4-wire I/O terminal block is available. This particular I/O terminal block is used in conjunction with the AI, 420 mA card.

Function keys

24 pin

10 pin

16 pin

Standard mass terminated interfaces.

Product Data Sheet


Classic I/O January 2008Page 24

TM

The following tables list specifications for I/O and mass termination blocks:

Item Voltage rating I/O and fused I/O 4-wire I/O Maximum current Hazardous area/location

Specification

250 VAC between non-connected signals 30 VDC 1 A per I/O channel Class 1, Div 2, Groups A, B, C, D T4 hazardous locations ATEX 3 G IIC T4

Specifications for Mass Terminal Blocks Models 10-pin mass termination block 16-pin mass termination block 24-pin mass termination block 40-pin mass termination block Maximum current 1 A per I/O Channel (16-pin, 40-pin) 1 A per cable (10-pin, 24-pin) Voltage rating Maximum cable length Key position 30 VDC between non-connected signals 4 m. (13.1 ft.) Set the key position based on I/O card type. Factory settings: 10-pin: B6 16-pin: A1 24-pin: A3 40-pin: B3 Hazardous area/location Class 1, Div 2, Groups A, B, C, D T4 hazardous locations ATEX 3 G IIC T4

Product Data Sheet


Classic I/O January 2008Page 25

TM

Options
The table below lists Classic I/O and terminal block compatibility:
I/O Card Terminal Block Compatibility I/O Card AI, 8-channel, 420 mA, HART I/O Card Keying A1 Recommended I/O Terminal Block I/O terminal block Optional I/O Terminal Block Fused I/O terminal block 4-wire I/O terminal block 16-pin mass termination block (2-wire connection) 24-pin mass termination block (4-wire connection) AI, 16-channel, 4-20 mA HART (Simplex mode) AO, 8-channel,420 mA, HART Isolated Input Card DI, 8-channel, 24 VDC, Isolated DI, 8-channel, 24 VDC, dry contact DI, 8-channel, 120 VAC, isolated DI, 8-channel, 120 VAC, dry contact DI, 32-channel, 24 VDC dry cntact DO, 8-channel, 120 VAC/230 VAC, isolated DO, 8-channel, 120 VAC/230 VAC, high side DO, 8-channel, 24 VDC, isolated DO, 8-Channel, 24 VDC, High Side DO, 32-channel, 24 VDC high-side Thermocouple, mV A2 A4 C2 B2 B1 E4 E1 B3 F4 F1 B5 B6 16-channel analog input terminal block I/O terminal block Isolated Input Terminal Block I/O terminal block Fused I/O terminal block I/O terminal block Fused I/O terminal block 32-channel terminal block I/O terminal block Fused I/O terminal block I/O terminal block Fused I/O terminal block Fused I/O terminal block 16-pin mass termination block NA Fused I/O terminal block 16-pin mass termination block I/O terminal block 16-pin mass termination block Fused I/O terminal block I/O terminal block 40-pin mass termination block Fused I/O terminal block I/O terminal block Fused I/O terminal block 16-pin mass termination block I/O terminal block 10-pin mass termination block 16-pin mass termination block 40-pin mass termination block I/O terminal block Note: When the thermocouple, mV card is plugged into an I/O terminal block, it functions as an mV card.

B4 C1

32-channel terminal block Thermocouple, mV terminal block Note: When the thermocouple, mV card is plugged into a thermocouple terminal block, it functions as a thermocouple card.

Product Data Sheet


Classic I/O January 2008Page 26

TM

Ordering Information
Model Number VE4001S2T1B1 VE4001S2T1B2 VE4001S2T1B3 VE4001S2T2B1 VE4001S2T2B2 VE4001S2T2B3 VE4001S2T2B4 VE4001S2T2B5 VE4001S3T1B1 VE4001S3T1B2 VE4001S3T2B1 VE4001S3T2B2 VE4002S1T1B1 VE4002S1T1B2 VE4002S1T1B3 VE4002S1T2B1 VE4002S1T2B2 VE4002S1T2B3 Description Discrete Input Card: 8 Channels, 24Vdc, Isolated, Standard I/O Termination Block Discrete Input Card: 8 Channels, 24Vdc, Isolated, Fused I/O Termination Block Discrete Input Card: 8 Channels, 24Vdc, Isolated, 16-Pin Mass I/O Termination Block Discrete Input Card: 8 Channels, 24Vdc, Dry Contact, I/O Termination Block Discrete Input Card: 8 Channels, 24Vdc, Dry Contact, Fused I/O Termination Block Discrete Input Card: 8 Channels, 24Vdc, Dry Contact, 16-Pin Mass I/O Termination Block Discrete Input Card: 32 Channels, 24 Vdc, Dry Contact, Termination Block Discrete Input Card: 32 Channels, 24 Vdc, Dry Contact, 40-pin Mass Termination Block Discrete Input Card: 8 Channels, 120Vac, Isolated, I/O Termination Block Discrete Input Card: 8 Channels, 120Vac, Isolated, Fused I/O Termination Block Discrete Input Card: 8 Channels, 120Vac, Dry Contact, I/O Termination Block Discrete Input Card: 8 Channels, 120Vac, Dry Contact, Fused I/O Termination Block Discrete Output Card: 8 Channels 24Vdc, Isolated, I/O Termination Block Discrete Output Card: 8 Channels 24Vdc, Isolated, Fused I/O Termination Block Discrete Output Card: 8 Channels 24Vdc, Isolated, 16-Pin Mass I/O Termination Block Discrete Output Card: 8 Channels 24Vdc, High Side, I/O Termination Block Discrete Output Card: 8 Channels 24Vdc, High Side, Fused I/O Termination Block Discrete Output Card: 8 Channels 24Vdc, High Side, 16-Pin Mass I/O Termination Block

Product Data Sheet


Classic I/O January 2008Page 27

TM

Ordering Information (continued)


VE4002S1T2B4 VE4002S1T2B5 VE4002S1T2B6 VE4002S2T1B1 VE4002S2T1B2 VE4002S2T2B1 VE4002S2T2B2 VE4003S2B1 VE4003S2B2 VE4003S2B3 VE4003S2B4 VE4003S2B5 VE4003S2B6 VE4003S4B1 VE4003S5B1 Discrete Output Card: 8 Channels 24Vdc, High Side, 10-Pin Mass I/O Termination Block Discrete Output Card, 32 Channels, 24Vdc, High Side, I/O Termination Block Discrete Output Card, 32 Channels, 24Vdc, High Side, 40-Pin Mass I/O Termination Block Discrete Output Card: 8 Channels 115/230Vac, Isolated, I/O Termination Block Discrete Output Card: 8 Channels 115/230Vac, Isolated, Fused I/O Termination Block Discrete Output Card: 8 Channels 115/230Vac, High Side, I/O Termination Block Discrete Output Card: 8 Channels 115/230Vac, High Side, Fused I/O Termination Block Analog Input Card: 8 Channels 4-20 mA, HART, I/O Termination Block Analog Input Card: 8 Channels 4-20 mA, HART, Fused I/O Termination Block Analog Input Card: 8 Channels 4-20 mA, HART, 4-wire I/O Termination Block Analog Input Card: 8 Channels 4-20 mA, HART, 16-Pin Mass I/O Termination Block Analog Input Card: 8 Channels 4-20 mA, HART, 24-Pin Mass I/O Termination Block Analog Input Card: 16 Channels 4-20 mA, HART, I/O Termination Block Analog Input Card: 8 Channels, mV Ranges, I/O Termination Block Analog Input Card: 8 Channels Thermocouple, CJC Termination Block

Product Data Sheet


Classic I/O January 2008Page 28

TM

Ordering Information (continued)


VE4003S6B1 VE4003S7B1 VE4005S2B1 VE4005S2B2 VE4005S2B3 Analog Input Card: 8 Channels RTD, RTD Termination Block Isolated Input Card , 4 Isolated Channels for T/C, RTD, mv, or volts; Isolated Input terminal Block Analog Output Card: 8 Channels 4-20 mA, HART, I/O Termination Block Analog Output Card: 8 Channels 4-20 mA, HART, Fused I/O Termination Block Analog Output Card: 8 Channels 4-20 mA, HART, 16-Pin Mass I/O Termination Block

Prerequisites
DeltaV version 7.3 is required for 4-channel isolated card and 16-channel AI card.

To locate a sales office near you, visit our website at: or call us at:

www.EasyDeltaV.com/reach 65.777.8211 41.41.768.6111 +1 800.833.8314 or +1 512.832.3774

Asia Pacific: Europe, Middle East: North America, Latin America:

For large power, water, and wastewater applications contact Power and Water Solutions at: www.emersonprocess-powerwater.com or call us at: Asia Pacific: Europe, Middle East, Africa: North America, Latin America:
Emerson Process Management 19962008 All rights reserved. For Emerson Process Management trademarks and service marks, go to:Trademarks

65.777.8211 48.22.630.2443 +1 412.963.4000