Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Prisma Plus G
Wall-mounted and floor standing enclosures for Electrical Distribution up to 630 A
Catalogue 2012
Table of contents
Index
Alphabetical index
> page 2
Presentation
Overview
> page 10
Functional system
Functional units and distribution
> page 32 Circuit breakers > p. 32
Compact NSX 100/630 > p. 32 Easypact EZC 100/400 > p. 36
Switch-disconnect. > p. 38
Interpact INS-INV 250/630 > p. 38
Accessories
> page 56
Partitioning > p. 59
Distribution
> page 66
Electrical characteristics
> page 138
Practical Information
> page 145
Standards
> page 146
Prisma Plus G
Index
p. 2
Determining catalogue numbers
> page 25
Presentation
p. 10
Functional system
p. 29
Fusegear > p. 42
Fupact INF > p. 42 Fupact ISFT / ISFT-N > p. 44
Accessories
> page 56
Distribution
> page 66
Pack enclosures
p. 121
Enclosure characteristics
> page 151
Thermal characteristics
> page 159
Practical Information
> page 167
Additional information
p. 137
1
Index
Alphabetical index
Designation
400 A rear busbars 630 A multi-stage busbars in duct A Additional block Adhesive labels for mimic diagrams After-sales service B Barrel locks Blanking plates Brackets C C120 Cable trunking for doors Cable-tie supports Canopy Central uprights Clip-nuts Comb busbars Combination Combination uprights Compact NSX 100/250 Compact NSX 400/630 Connections Connectors Covers D Devices 144 x 144 Devices 72 x 72 Devices 96 x 96 Distribloc Doors E Earth blocks Earthing braid Easypact EZC100/400 F Fan Filters Fixed lighting Flush-mounting kit Flush-mounting kit Front cover support uprights Front-plate Front-plate, Multiclip distribution bloc accessories Fupact INF Fupact ISFT and ISFT-N G Gasket Gland plates Grill with filter Grommets for wiring through front H Handles Heating elements Hexagonal spacers Hook-on rail system Human-switchboard interface I iC120 INS100/160 INS40/160 Inserts Insulated flexible bars Interpact INS-INV250/630 IP30 enclosures IP30 wall-mounted and floor standing enclosures IP55 enclosures J Joinable distribution block K Kilowatt-hour meters
70 72
Pages
69 63 101, 102, 103, 117 100, 116 127 97 46 61 61, 132 95, 110, 126 102 58 82, 131 96 127 32, 40 34 129 71 69, 129 54 53, 54 53 77, 130 110 84, 132 100, 132 36 64 64 62 97, 127 97 103 56, 103 103, 117 42 44 95, 126 98, 102, 113, 126 64 61 100, 116 65 58 97 52 46 46 46 100, 116 74 38 94 94 110 79 50, 125
Index
Alphabetical index
Designation
L Lamps Lifting accessories Lifting cross-members Locks M Metal plate with cut-outs Modular devices Modular front-plate Modular incoming fusegear Modular rails Mounting plates Mounting supports Mounting uprights Multiclip Multiclip distribution block Multiple combination Multi-stage distribution block N Neutral bars NG125 NG160 P Padlocking Partial doors Partitioning Plinth cover panel Plinth gusset Plinths Pole Polybloc Power Meter Power supply block Powerclip busbars Prefabricated connections Pushbuttons R Rails Recessed slotted mounting plate Regulating Reinforcement cross-members Resistors S Self-tapping screws Side panels with cut-outs Source changeover system Spare-parts Straps Switchboard portable lamp Symbol sheets T Tap-off block Terminal block Terminal block layout TeSys, Altistart, Phaseo Thermostat Trunking Trunking spreader Trunking supports Universal angle bracket V Ventilated front-plate Vigi C120 Vigi iC120 Vigi NG125 Vigi NG160 Vigilohm Vigilohm system Vigirex W Wall mounting
Pages
55 97 97 116 98, 113 46, 103, 117 133 46 133 114 112 111, 112 80 131 111 78, 130 84 46 46 100, 116 99, 114 59 112 112 102 112 75, 76, 130 53 69 68, 128 69 55 57 57, 133 65 112 65 58 115 40 101, 102, 103, 117 60 62 63 69, 129 86 86 48 65 60 98, 126 60 58 64 46 46 46 46 55 54 53, 55 127
Index
Pages
63 63 63 63 63 102 101 102 117 102 102 102 101 95, 102 95, 102 95, 102 101 102 95, 102 95, 102 95, 102 95, 102 95, 102 95, 102 95, 102 102 102 102 102 56, 103, 117 103, 117 101 68, 103, 128 81, 103, 117 68, 103, 128 103 101 117 117 117 103 103 103 103 103 103 103 103 103 103 103, 117 103, 133 103, 133 46, 47, 48, 55, 57 46, 48, 55, 57, 75, 76, 86 49, 57, 133 48, 49, 57, 86, 133 57, 84, 86 133 46, 47, 48, 57 46, 48, 49, 57, 75, 76 32, 38
01000
03032
Diagram lines, 10 black mimic, W=900 mm Diagram outgoing arrows, 10 black mimic Diagram incoming arrows, 10 black mimic Diagram transformers, 5 black mimic Diagram earth symbols, 5 black mimic Plain IP30 gland plate System G IP30 accessory FL21 gland plate for Pack enclosures IP55 single struts (2), RAL 9001 Combination piece for IP30 33-module System G floor-standing enclosures Combination piece for IP30 30-module System G floor-standing enclosures Combination piece for IP30 27-module System G floor-standing enclosures Closing accessories for IP30 System G floorstanding enclosures Side for 33-module System G floor-standing enclo. Side for 30-module System G floor-standing enclo. Side for 27-module System G floor-standing enclo. IP30 System G struts (4) System G IP30 support plate for duct, W=300 mm Side for 6-module System G wall-mounted enclo. Side for 9-module System G wall-mounted enclo. Side for 12-module System G wall-mounted enclo. Side for 15-module System G wall-mounted enclo. Side for 18-module System G wall-mounted enclo. Side for 21-module System G wall-mounted enclo. Side for 24-module System G wall-mounted enclo. Accessories for plinth with holes Accessories for plinth Plinth front, 600 mm Plinth front, 300 mm Self adhesive front plate grips (20) Accessories quarter turn closing Washers for System G rear panel (4) IPxxB clipon covers for Powerclip (2) Terminal covers for 200 A Multiclip (4) Powerclip busbar accessories, 160 to 400 A Powerclip busbar accessories, 630 A System G retrofit handle Set of spare parts for IP55 wall-mounted enclo. Set of spare parts for IP55 wall-mounted enclo. IP55 closing system spare parts Plates uprights AFS G 6 m Plates uprights AFS G 9 m Plates uprights AFS G 12 m Plates uprights AFS G 15 m Plates uprights AFS G 18 m Plates uprights AFS G 21 m Plates uprights AFS G 24 m Plates uprights AFS G 27 m Plates uprights AFS G 30 m Plates uprights AFS G 33 m Pack modular device rail AFS Pack decentered plate 4 m AFS Pack decentered plate 4.5 m AFS Modular device rail Adjustable modular device rail Recessed modular device rail Rear modular device rail DIN rail support (45) Modular device rail for NG160 Pack Modular device rail, W=250 mm Adjustable modular device rail, W=250 mm
03033 03040 03041 03043 03050 03051 03070 03073 03074 03080 03081 03102 03104 03105 03113 03114 03120 03121 03122 03123 03124 03125 03126 03152 03154 03155 03156 03157 03158 03159 03160 03164 03165 03166 03170 03171 03172 03173 03175 03176 03177 03178 03180 03181 03182 03183 03185 03186 03187 03194 03195 03196 03197 03198 03199 03202 03203 03204 03205 03213 03214 03220 03221
03000
Mount. plate for horiz. NSX250 with motor mechanism/plug-in with toggle Mount. plate for horiz. fixed Vigi NSX250 with toggle Mount. plate for vert. fixed NSX250 with toggle Mount. plate for vert. fixed NSX250 with rotary handle Mount. plate for NSX-INS250 source changeover system with rotary handles Mount. plate for vert. fixed NSX-INS250 with toggle, W=250 mm Mount. plate for vert. fixed NSX-INS250 with rotary handle, W=250 mm Mount. plate for horiz fixed NSX630 with toggle Mount. plate for vert. fixed NSX-INS630 with toggle Mount. plate for vert. fixed NSX630 with rotary handle Mount. plate for vert. fixed NSX-INS630 with toggle, W=250 mm Mount. plate for vert. fixed NSX630 with rotary handle, W=250 mm Mounting plate for vertical EZC100, 1P Mounting plate for EZC250 /EZCV250 Mounting plate for EZC400 Mounting plate for INF32/40 Mounting plate for INF63-160 Mounting plate for vertical ISFT100 Mounting plate for ISFT160 Busbar assembly for mounting ISFT100N/160 Mount. plate for vertical ISFT160, W=250 mm Mounting plate for horizontal ISFT250 Mount. plate for vertical ISFT250, W=250 mm Mounting plate for ISFT100N Mounting plate for 2-meter service connection Front plate for 1 3-phase meter in duct Front plate for 3 1-phase meters Mounting plate for 1 3-phase meter in duct Mounting plate for 3 1-phase meters Front plate for 2 3-phase meters Front plate for Gould 3-phase fuses Mounting plate for 2 x 3PH meters 6 modules Clip-nuts for DIN rails, 20 M4 Clip-nuts for DIN rails, 20 M5 Clip-nuts for DIN rails, 20 M6 Slotted mounting plate, 4 modules, for wall-mounted or floor-standing enclosure Recessed slotted mounting plate, 4 modules, wall-mount. or fl.-standing encl. Recessed slotted mounting plate, 6 modules, wall-mount. or fl.-standing encl. Recessed slotted mounting plate, 9 modules, wall-mount. or fl.-standing encl. Slotted mounting plate, 4 modules, W=250 mm Recessed slotted mount. plate, 4 mod., W=250 mm Recessed slotted mount. plate, 6 mod., W=250 mm Recessed slotted mount. plate, 9 mod., W=250 mm Clip-nuts for slotted mounting plates, 20 M4 Clip-nuts for slotted mounting plates, 20 M5 Clip-nuts for slotted mounting plates, 20 M6 Self-tapping screws for functional unit mounting, 20 M5 Hexagonal spacers, H=9 mm, 4 M5 Hexagonal spacers, H=23 mm, 4 M5 Hexagonal spacers, H=55 mm, 4 M5 Captive nuts for M6 hexagonal spacers (20) Hexagonal spacers, H=9mm, 4 M6 Hexagonal spacers, H=23 mm, 4 M6 Hexagonal spacers, H=55 mm, 4 M6 Hexagonal spacers, H=25 mm, 4 M6 Hexagonal spacers, H=40+10mm, 4 M8 Modular front plate, 2 modules Modular front plate, 3 modules
32, 39
Pages
32 33, 39 33 40, 41 33, 39 33 34, 38 35, 39 35 35, 39 35 37 36, 37 36, 37 42, 43 42, 43 45 44, 45 45 45 44 45 45 50, 125 50, 125 50 51 50, 125 50 46 51 58 58 58 57 49, 57 49, 57, 125 57 49, 57 57 57 57 57, 58 57, 58 57, 58 58 58, 84 58, 84 58, 84 58 57, 58, 86 57, 58, 86 57, 58, 86 58 58 56 47, 48, 55, 56, 133 46, 47, 56 46, 48, 56, 133 47, 48, 56 46, 47, 56 46, 47, 48, 127 46, 47, 48, 127
Mount. plate for horizontal fixed NSX-INS250 with toggle Mount. plate for horizontal fixed NSX250 with rotary 32 handle
Modular front plate, 4 modules Modular front plate, 5 modules Modular front plate, 3 modules, W=250 mm Modular front plate, 4 modules, W=250 mm Blanking strip, W=1000 mm Divisible blanking plates (4), W=90 mm
Index
03223 03228 03229 03231 03232 03234 03235 03241 03243 03244 03245 03247 03248 03249 03251 03253 03271 03274 03275 03281 03283
03290 03292 03293 03296 03297 03298 03299 03303 03304 03305 03306 03307 03312 03313 03314 03315 03320 03321 03325 03326 03327 03328 03329 03342 03343 03344 03345 03352 03353 03354 03359 03581 03583 03801 03802
Modular front plate, 3 rows Vertical modular front plate 9 mod. Vertical modular front plate 12 mod. Front plate for horizontal INS250 Front plate for horizontal fixed NSX250 with toggles and rotary handle Front plate for horizontal fixed NSX250 with motor mechanism Front plate for INS250 source changeover system with rotary handles Front plate for 3-4 vertical Vigi NSX250 devices with toggles Front plate for 3-4 vertical NSX250 devices Front plate for 3-4 vertical Vigi NSX250 devices with rotary handles or motor mechanisms Front plate for vertical NSX250 source changeover system with rotary handles Front plate for INS250 complete source changeover assembly Front plate for vertical INS250 Blanking plate for vertical NSX-INS250 Front plate for vertical fixed INS250 with toggle, W=250 mm Front plate for vertical fixed NSX250 with rotary handle, W=250 mm Front plate for horizontal INS630 Front plate for vertical INS630 Front plate for vertical NSX630 with rotary handle or motor mechanism Front plate for vertical fixed INS630 with toggle, W=250 mm Front plate for vertical NSX630 with rotary handle or motor mechanism, W=250 mm Front plate for horizontal plug-in NSX250 with toggle Front plate for horiz.fixed manual Vigi NSX250 Front plate for vertical fixed manual Vigi NSX250, W=250 mm Front plate for horiz. fixed NSX630 with toggle Front plate for vertical Vigi NSX630 Front plate for vertical fixed manual NSX630, W=250 mm Front plate for vertical fixed manual Vigi NSX630, W=250 mm Front plate for vertical EZC100 Front plate for horizontal EZC250/EZCV250 Front plate for vertical EZC250/EZCV250 Front plate for horizontal EZC400 Front plate for vertical EZC400 Front plate for vertical INF32/40, 3P Front plate for INF32/40, 4P and horiz. 3P Front plate for INF63-160, 3P and vert. INV63, 3P Front plate for vert. INF63, 4P and vert. INF160 Front plate for vertical ISFT100 Front plate for vertical ISFT160 Front plate for vertical ISFT100N Front plate for horizontal ISFT160 Front plate for horizontal ISFT160, W=250 mm Front plate for horizontal ISFT250 Front plate for vertical ISFT250, W=250 mm Transparent front plate, 4 modules Transparent front plate, 6 modules Transparent front plate, 9 modules Transparent front plate, 12 modules Transparent front plate, 4 modules,W=250 mm Transparent front plate, 6 modules,W=250 mm Transparent front plate, 9 modules,W=250 mm Front plate for Gould 1-phase fuses Universal angle brackets (2) Universal angle brackets (6) Plain front plate, 1 module Plain front plate, 2 modules
47, 56 47 47 38 32 32 41 33 33 33 40 41 39 37 39 33 38 39 35 39 35 32 32 33 34 35 35 35
Pages
03803 03804 03805 03806 03807 03808 03811 03812 03813 03814 03815 03816 03817 03890 03891 03895 03900 03901 03902 03903 03904 03907 03908 03910 03911 03912 03913 03914 03928 03934
Plain front plate, 4 modules Plain front plate, 5 modules Plain front plate, 6 modules Plain front plate, 9 modules Plain front plate, 12 modules Plain front plate, 1 module, W=250 mm Plain front plate, 2 modules, W=250 mm Plain front plate, 3 modules, W=250 mm Plain front plate, 4 modules, W=250 mm Plain front plate, 5 modules, W=250 mm Plain front plate, 6 modules, W=250 mm Plain front plate, 9 modules, W=250 mm Front plate for fan or grill IP30 ventilated front plate, 1 module IP30 ventilated front plate, 3 modules Plain mounting plate for 72 x 72 mm meter Plain mounting plate for 96 x 96 mm meter Mounting plate with cut-out for 72 x 72 mm meter Mounting plate with cut-out for 96 x 96 mm meter Front plate with cut-outs for meter mount. plates Blanking plate, 72 x 72 Blanking plate, 96 x 96 for meters Front plate with cut-outs for 72 x 72 mm meters Front plate with cut-outs for 96 x 96 mm meters Front plate with cut-outs for 144 x 144 mm + 4 72 x 72 mm meters Front plate 96 x 96 for 1 device Front plate with holes for 22 mm dia. pushbuttons and lamps Visor for human/switchboard interface (HSI) Front plate for Vigilohm TR22A + 6 72 x 72 mm meters Multiclip distribution block, 4P, 80 A Multiclip distribution block, 4P, 63A, 1/2 row Multiclip distribution block, 2P, 200A, 1 row Multiclip distribution block, 3P, 200A, 1 row Multiclip distribution block, 4P, 200A, 1 row Multiclip distribution block, 4P, 160A, 1/2 row Powerclip busbar connection for 200 A Multiclip distribution block Duct busbar connection for 200 A Multiclip distribution block Rear busbar connection for 200 A Multiclip distribution block Multiclip/NG160 connection, 200 A Polybloc distribution block, 1P, 160 A Polybloc distribution block, 3P, 250 A Polybloc distribution block, 4P, 250 A Spacers Cu for Polybloc 250A distribution block (4) Distribloc 63 (top connection) Distribloc 63 (bottom connection) Distribloc 125 Distribloc 160 + connections Connections (4) between NG-INS125 and Distribloc distribution block Multi-stage distribution block, 4P, 160 A Multi-stage distribution block, 4P, 250 A Multi-stage distribution block, 4P, 400 A Multi-stage distribution block, 4P, 630 A Power supply block for horizontal NSX250 Universal power supply block, 250 A Connection between vertical NSX-INS250 and universal power supply block Connection between vertical NSX-INS250 in duct and universal power supply block Connection between vertical NSX-INS250 in duct and busbars Incoming connection block for NSX-INS250 supplied via the top
34, 35, 38, 40, 48, 56 35, 49, 56 49, 56 39, 49, 50, 51, 56 50, 56 56 35, 46, 48, 49, 56 35, 39, 56 48, 56 49, 56 56 56 51, 56 56, 64 56, 64 56, 64 53 53 53 53 53 53, 54 53 53 53 54 53 55 53 54 80, 131 80, 131 81 81 81 81 69, 81 73, 81 71, 81 81 75, 130 76 76 76 77, 130 77, 130 77, 130 77, 130 77, 130 78 78 78 78 69 69 69 69 73 38
Pages
37 36 37 36 37 43 42, 43 42, 43 43 45 45 45 44 45 44 45 48, 49, 55, 56 50, 51, 55, 56 50, 55, 56 55, 56 48, 49, 56 56 51, 56 46 58 58 32, 33, 35, 38, 39, 44, 45, 48, 49, 56 32, 33, 35, 39, 40, 41, 42, 43, 44, 45, 56
04000 04008 04012 04013 04014 04018 04021 04024 04029 04030 04031 04033 04034 04037 04040 04041 04045 04046 04047 04052 04053 04054 04055 04060 04061 04062 04064 04065 04066
04000
Index
04067 04070 04071 04073 04074 04075 04076 04103 04104 04107 04108 04111 04112 04113 04114 04116 04117 04118 04119 04121 04122 04123 04124 04126 04127 04128 04129 04145 04146 04147 04148 04149 04150 04151 04152 04155 04156 04158 04161 04162 04163 04171 04172 04173 04174 04190 04191 04192 04194 04195
04197 04198 04200 04201 04202 04205 04206 04207 04208 04210 04214 04215 04220 04223 04224 04226
Incoming connection block for NSX-INS250 supplied via the bottom Power supply block for horizontal NSX400 Power supply block for horizontal NSX630 Connection between vertical NSX-INS400-630 in duct and universal power supply block Universal power supply block, 400-630 A Connection between vertical NSX-INS630 in duct and busbars In-duct incoming connection block for NSX630 Powerclip busbars, 125 A, 3P, W=450 mm Powerclip busbars, 125 A, 4P, W=450 mm Powerclip busbars, 125 A, 3P, W=750 mm Powerclip busbars, 125 A, 4P, W=750 mm Powerclip busbars, 160 A, 3P, W=1000 mm Powerclip busbars, 250 A, 3P, W=1000 mm Powerclip busbars, 400 A, 3P, W=1000 mm Powerclip busbars, 630 A, 3P, W=1000 mm Powerclip busbars, 160 A, 3P, W=1400 mm Powerclip busbars, 250 A, 3P, W=1400 mm Powerclip busbars, 400 A, 3P, W=1400 mm Powerclip busbars, 630 A, 3P, W=1400 mm Powerclip busbars, 160 A, 4P, W=1000 mm Powerclip busbars, 250 A, 4P, W=1000 mm Powerclip busbars, 400 A, 4P, W=1000 mm Powerclip busbars, 630 A, 4P, W=1000 mm Powerclip busbars, 160 A, 4P, W=1400 mm Powerclip busbars, 250 A, 4P, W=1400 mm Powerclip busbars, 400 A, 4P, W=1400 mm Powerclip busbars, 630 A, 4P, W=1400 mm Connections, 125 A (4) Connections 160 A (4) Busbar/modular device connection, 160 A Busbar/Vigi modular device connection, 160 A Modular device/Polybloc connection, 160 A Covers for Powerclip busbars, 8 IPxxB Powerclip tap-off blocks with 6 mm + 10 mm terminals (12) Powerclip tap-off blocks with 16mm terminals (12) Additional 35mm block, 3P Additional 35mm block, 4P Screws for Powerclip busbars (20) Bars with threaded holes (4), 160 A, W=1000 mm Bars with threaded holes (4), 250 A, W=1000 mm Bars with threaded holes (4), 400 A, W=1000 mm Bars with threaded holes (4), 160 A, W=1000 mm Bars with threaded holes (4), 250 A, W=1000 mm Bars with threaded holes (4), 400 A , W=1000 mm Bars with threaded holes (4), 630 A, W=1000 mm Copper angle brackets (4), 250A Rear busbar support Multi-stage bar support for duct Bolts for 5 mm bars, 20 M6 x 20mm Screws for bars with threaded holes, less than 630 A, 40 M6 x 16 mm Busbar power supply barrier, 630 A Rear busbar barrier Earth bar, 24 modules Earth bar for direct earth blocks, 12 x 3 mm Earth bars (2), 12 modules Supports for earth bar on DIN rail (2) Fixing brackets for vert. earth bar in wall-mount. or fl.-standing encl. H 15 mm Fixing brackets for vert. earth bar in wall-mount. or fl.-standing encl. H 45 mm Fixing brackets for vert. earth bar in wall-mount. or fl.-standing encl. H 80 mm Kit for neutral bar Earth blocks with 12x4mm spring terminals (4) Earth blocks with 3x16mm spring terminals (4) Mount. plate for terminal block and earth bar in duct Mount. plate with 4 vertical DIN rails for terminal blocks Raisers, 5 Practic Modular device rail, W=1600 mm
38 69 69 69 69 73
Pages
34 128 128 128 128 68, 128 68 68 68 68 68 68 68 68, 126 68 68 68 68 68 68 68 69, 71, 129 69, 71, 129 69, 129 69, 129 75, 130 69, 129 69, 129 69, 129 69 69 69, 129 70, 72 70, 72 70, 72 70, 72 70, 72 70, 72 72 71 70 72 71, 73 71, 73 72 70 84, 132 84, 132 84 84 57, 84, 85, 86, 132 57, 84, 85, 86 57, 84, 85, 86 84 84, 132 84, 132 85, 87 85, 87 56 47, 57
04227 04233 04234 04235 04239 04243 04255 04256 04257 04263 04264 04265 04267 04330 04331 04332 04333 04742 04743 04746 04751 04752 04753
Rail and raisers modular Trunking for door, W=2000 mm Grommets for wiring through front (10) Flexible trunking for wiring to door Horizontal cable straps (12) Covers for horizontal cable straps (4) Horizontal trunking supports (12) Adaptable support for horizontal trunking (10) Horiz. trunking sections (4), W=450 mm, + supports Covers for vertical cable straps (2), W=1000 mm Vertical cable straps, System G (12) Vertical trunking supports (12) Vertical trunking, W=2000 mm Vertical partition Horizontal partition for wall-mounted or floor-standing enclosure Horizontal partition for duct Horizontal partition for Pack enclosure Insulated flexible bar 20 x 2 mm, W=1800 mm Insulated flexible bar 20 x 3 mm, W=1800 mm Insulated flexible bar 24 x 5 mm, W=1800 mm Insulated flexible bar 32 x 5 mm, W=1800 mm Insulated flexible bar 32 x 6 mm, W=1800 mm Insulated flexible bar 32 x 8 mm, W=1800 mm Cable connectors (4), 160 A, 70 mm Cable connectors (4), 250 A, 185 mm Cable connectors (4), 400 A, 300 mm Surface-mount Pack enclosure, W=550 mm, 2 rows Surface-mount Pack enclosure, W=550 mm, 3 rows Surface-mount Pack enclosure, W=550 mm, 4 rows Surface-mount Pack enclosure, W=550 mm, 5 rows Surface-mount Pack enclosure, W=550 mm, 6 rows Pack extension enclosure, 2 rows Pack extension enclosure, 3 rows Plain door for Pack enclosure, W=550 mm, 2 rows Plain door for Pack enclosure, W=550 mm, 3 rows Plain door for Pack enclosure, W=550 mm, 4 rows Plain door for Pack enclosure, W=550 mm, 5 rows Plain door for Pack enclosure, W=550 mm, 6 rows Transparent door for Pack enclos., W=550 mm, 2 rows Transparent door for Pack enclos., W=550 mm, 3 rows Transparent door for Pack enclos., W=550 mm, 4 rows Transparent door for Pack enclos., W=550 mm, 5 rows Transparent door for Pack enclos., W=550 mm, 6 rows Wall-mounted enclosure, W=600 mm, 6 modules Wall-mounted enclosure, W=600 mm, 9 modules Wall-mounted enclosure, W=600 mm, 12 modules Wall-mounted enclosure, W=600 mm, 15 modules Wall-mounted enclosure, W=600 mm, 18 modules Wall-mounted enclosure, W=600 mm, 21 modules Wall-mounted enclosure, W=600 mm, 24 modules Wall-mounted enclosure, W=600 mm, 27 modules Plain door for wall-mounted enclosure, 6 modules Plain door for wall-mounted enclosure, 9 modules Plain door for wall-mounted enclosure, 12 modules Plain door for wall-mounted enclosure, 15 modules Plain door for wall-mounted enclosure, 18 modules Plain door for wall-mounted enclosure, 21 modules Plain door for wall-mounted enclosure, 24 modules Transp. door for wall-mounted enclos., 6 modules Transp. door for wall-mounted enclos., 9 modules Transp. door for wall-mounted enclos., 12 modules Transp. door for wall-mounted enclos., 15 modules Transp. door for wall-mounted enclos., 18 modules Transp. door for wall-mounted enclos., 21 modules Transp. door for wall-mounted enclos., 24 modules Duct for wall-mounted enclos., W=300 mm, 6 mod. Duct for wall-mounted enclos., W=300 mm, 9 mod. Duct for wall-mounted enclos., W=300 mm, 12 mod. Duct for wall-mounted enclos., W=300 mm, 15 mod. Duct for wall-mounted enclos., W=300 mm, 18 mod.
46, 57, 133 61 61 61 60, 132 60, 132 60, 132 60, 132 60, 132 60 60 60 60 59 46, 50, 51, 59 51, 59 125 71, 73, 74 71, 73, 74 71, 73, 74 71, 73, 74 71, 73, 74 71, 73, 74 71 71 71 124 124 124 124 124 124 124 124 124 124 124 124 124 124 124 124 124 94 94 94 94 94 94 94 94 94 94 94 94 94 94 94 94 94 94 94 94 94 94 94, 95 94, 95 94, 95 94, 95 94, 95
Pages
07000
08002 08003 08004 08005 08006 08012 08013 08082 08083 08084 08085 08086 08092 08093 08094 08095 08096 08102 08103 08104 08105 08106 08107 08108 08109 08122 08123 08124 08125 08126 08127 08128 08132 08133 08134 08135 08136 08137 08138 08172 08173 08174 08175 08176
08000
Index
08177 08178 08179 08182 08183 08184 08185 08186 08187 08188 08197 08198 08202 08203 08204 08212 08213 08214 08222 08223 08224 08232 08233 08234 08272 08273 08274 08282 08283 08284 08292 08293 08294 08302 08303 08304 08305 08306 08307 08309 08312 08313 08314 08315 08316 08317 08319 08322 08323 08324 08325 08326 08327 08329 08332 08333 08334 08335 08336 08337 08339 08342 08343 08344 08345 08346 08347 08349 08352 08353
Duct for wall-mounted enclos., W=300 mm, 21 mod. Duct for wall-mounted enclos., W=300 mm, 24 mod. Duct for wall-mounted enclos., W=300 mm, 27 mod. Door for wall-mounted enclosure duct, 6 modules Door for wall-mounted enclosure duct, 9 modules Door for wall-mounted enclosure duct, 12 modules Door for wall-mounted enclosure duct, 15 modules Door for wall-mounted enclosure duct, 18 modules Door for wall-mounted enclosure duct, 21 modules Door for wall-mounted enclosure duct, 24 modules Transp. door for wall-mounted enclos. duct, 21 mod. Transp. door for wall-mounted enclos. duct, 24 mod. Floor-standing enclosure, W=600 mm, 27 modules Floor-standing enclosure, W=600 mm, 30 modules Floor-standing enclosure, W=600 mm, 33 modules Floor-standing enclos. extension, W=600 mm, 27 mod. Floor-standing enclos. extension, W=600 mm, 30 mod. Floor-standing enclos. extension, W=600 mm, 33 mod. Plain door for wall-mounted and floor-standing enclosure, 27 modules Plain door for floor-standing enclosure, 30 modules Plain door for floor-standing enclosure, 33 modules Transparent door for wall-mounted and floorstanding enclosure, 27 modules Transp. door for floor-standing enclos., 30 modules Transp. door for floor-standing enclos., 33 modules Duct for floor-standing enclos., W=300 mm, 27 mod. Duct for floor-standing enclos., W=300 mm, 30 mod. Duct for floor-standing enclos., W=300 mm, 33 mod. Door for wall-mounted and floor-standing enclosure duct, 27 modules Door for floor-standing enclosure duct, 30 modules Door for floor-standing enclosure duct, 33 modules Transparent door for wall-mounted and floor-standing enclosure duct, 27 modules Transp. door for floor-standing enclos. duct, 30 mod. Transp. door for floor-standing enclos. duct, 33 mod. IP55 enclosure, 7 modules IP55 enclosure, 11 modules IP55 enclosure, 15 modules IP55 enclosure, 19 modules IP55 enclosure, 23 modules IP55 enclosure, 27 modules IP55 enclosure, W=850 mm, 33 modules IP55 enclosure extension, 7 modules IP55 enclosure extension, 11 modules IP55 enclosure extension, 15 modules IP55 enclosure extension, 19 modules IP55 enclosure extension, 23 modules IP55 enclosure extension, 27 modules IP55 enclosure extension, 33 modules IP55 plain door, 7 modules IP55 plain door, 11 modules IP55 plain door, 15 modules IP55 plain door, 19 modules IP55 plain door, 23 modules IP55 plain door, 27 modules IP55 plain door, 33 modules IP55 transparent door, 7 modules IP55 transparent door, 11 modules IP55 transparent door, 15 modules IP55 transparent door, 19 modules IP55 transparent door, 23 modules IP55 transparent door, 27 modules IP55 transparent door, 33 modules IP55 duct, W=300 mm, 7 modules IP55 duct, W=300 mm, 11 modules IP55 duct, W=300 mm, 15 modules IP55 duct, W=300 mm, 19 modules IP55 duct, W=300 mm, 23 modules IP55 duct, W=300 mm, 27 modules IP55 duct, W=300 mm, 33 modules IP55 side panels, 7 modules IP55 side panels, 11 modules
94, 95 94, 95 94, 95 94, 95 94, 95 94, 95 94, 95 94, 95 94, 95 94, 95 94, 95 94, 95 94 94 94 94 94 94 94 94 94 94
Pages
08354 08355 08356 08357 08359 08362 08363 08364 08365 08366 08367 08369 08371 08372 08374 08375 08376 08377 08381 08382 08383 08384 08386 08387 08391 08392 08393 08394 08395 08396 08585 08783 08801 08803 08804 08805 08807 08811 08812 08813 08814
94 94 94, 95 94, 95 94, 95 94, 95 94, 95 94, 95 94, 95 94, 95 94, 95 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110
08815 08816 08817 08818 08819 08820 08821 08822 08823 08824 08826 08827 08830 08831 08832 08833 08841 08850
IP55 side panels, 15 modules IP55 side panels, 19 modules IP55 side panels, 23 modules IP55 side panels, 27 modules IP55 side panels, 33 modules IP55 side panels with cut-outs, 7 modules IP55 side panels with cut-outs, 11 modules IP55 side panels with cut-outs, 15 modules IP55 side panels with cut-outs, 19 modules IP55 side panels with cut-outs, 23 modules IP55 side panels with cut-outs, 27 modules IP55 side panels with cut-outs, 33 modules Top and bottom plates, W=600 mm Top and bottom plates, W=300 mm IP55 4-module partial plain door for 11-27 module enclosures IP55 6-module partial plain door for 33-module enclosures IP55 4-module partial door with cut-outs for 11-27 module enclosures IP55 6-module partial door with cut-outs for 33-module enclosures IP55 horizontal/vertical combination kit IP55 L combination kit IP55 square combination kit IP55 vertical partition Canopy for IP55 wall-mounted or floor-standing enclosure, W = 600 mm Canopy for IP55 duct, W = 300 mm IP55 mounting upright IP55 plinth gusset IP55 plinth cover panels, W=600 mm IP55 plinth cover panels, W=300 mm Pole-mount kit for enclosures IP55 lifting rings 52 Front plate hinge kit (set of 2 hinges) Form C cable-tie support W=1600 Lifting rings (2) External wall-mounted brackets (4) for Pack enclos. External wall-mounted brackets (4) Plinth raiser for floor-standing enclosures, 100 mm Plinth raiser for ducts, 100 mm Lifting/reinforcement cross-members (2) for 2 wall-mounted or floor-standing enclosures Lifting/reinforcement cross-members (2) for single wall-mounted or floor-standing enclosure and duct Lifting-reinf. cross-members (2) for wall-mount. or fl.-standing encl. + ducts Lifting/reinforcement cross-members (2) for duct + enclos. + duct + enclos. or duct + enclos. + enclos. + duct IP30 combination kit for floor-standing enclosures Combination kit Combination uprights (2) Multiple combination kit Flush-mounting kit, 6 to 18 modules Flush-mounting kit, 21 to 27 modules Trunking spreader for Pack enclosure Pack flush-mount kit Pack IP31 canopy Trunking spreader for wall-mounted or floor-standing enclosure Lifting/reinforcement cross-members (2) for duct + enclosure + duct + enclosure + duct Canopy for duct + single wall-mounted or floor-standing enclosure + duct, IP31 IP31 canopy for 2 wall-mounted or 2 floor-standing enclosures Canopy for 2 wall-mounted or 2 floor-standing associated enclosures, IP31 Canopy for floor-standing enclosure, IP31 Canopy for enclosure + duct + enclosure, IP31 IP43 door gasket kit, 6-33 modules Partial door for wall-mounted or floor-standing enclosure, 6-module
110 110 110 110 110 115 115 115 115 115 115 115 110 110 114 114 114 114 111 111 111 59 110
Pages
110 111, 112 112 112 112 112 111 56 61 97 127 97 97 97 96, 97 96, 97 96, 97 96, 97 96 96 96, 127 96 97 97 126 127 126 98 96 95 95 95 95 95 95, 126 99
Index
08851 08861 08862 08863 08864 08866 08867 08868 08870 08871 08872 08874 08875 08876 08878 08879 08880
08881 08882 08884 08887 08888 08891 08892 08895 08896 08897 08898 08899 08900 08903 08904 08905 08906 08910 08911 08913 08914 08915 08916 08917 08918 08931 08932 08933 08934 08935 08936 08938 08939 08940 08941 08942 08943 08944 08945 08946 08947 08948 08949 08950 08951 08952 08953 08955 08956
Partial door with cut-out for human/switchboard interface (HSI) for wall-mounted or floorstanding enclosure, 6-module Plain mounting plate, 210 x 150 mm Mounting plate with eight 22 mm diameter holes Mounting plate with two 65 x 85 mm holes for industrial sockets IP55 mounting plate with 65 x 85 mm and 90 x 100 mm holes for industrial sockets Cable tie support adapter Cable tie supports for wall-mounted or floor-standing enclosure (2) Cable tie supports for ducts (4) Plain metal gland plate for wall-mounted or floor-standing enclosure Interface for gland plate for wall-mounted or floor-standing enclosure Membrane-type gland plate, 25 entries Plain metal gland plate for duct Interface for gland plate for duct IP55 gland plate interface Plastic gland plate and interface for Pack enclosures Plain metal gland plate for Pack enclosures Plastic gland plate and interface for wall-mounted or floor-standing enclosure Plain gland plate Plain plate for wall-mounted and floor-standing enclos. Plastic gland plate and interface for ducts Gland plate for floor-standing enclosure plinth Gland plate for duct plinth Knockout gland plate with 4xM12/20 + 4xM16/25 Knockout gland plate with 2xM20/32 + 2xM25/40 Gland plate with 13 knockouts Membrane-type gland plate, 35 entries Membrane-type gland plate, 2 entries Gland plate 39 incoming 7/26 IP55 Gland plate 2 incoming 33/72 IP55 Switchboard identification plate Adhesive label holders (12), H=24 mm, W=432 mm Adhesive label holders (12), H=36 mm, W=432 mm Adhesive label holders (12), H=24 mm, W=180 mm Adhesive label holders (12), H=36 mm, W=180 mm Earthing braid, 6 mm Earthing wire, 6 mm Clip-on labels (12), 18 x 35 mm Engraving plates (12), 18 x 35 mm Clip-on labels (12), 18 x 72 mm Engraving plates (12), 18 x 72 mm Clip-on labels (12), 25 x 85 mm Engraving plates (12), 25 x 85mm Standard handle, Ral 7016 EURO handle without insert Handle without insert, ASSA-ABLOY Handle for cylinder, EURO, IP55 Handle, IP55, L = 155 mm IP55 door latch with lock and 2 no. 405 keys Handle padlocking kit IP55 handle padlocking kit Barrel lock no. 405 Barrel lock no. 455 Barrel lock no. 1242E Barrel lock no. 3113A Barrel lock no. 2433A DIN double bar insert Screwdriver slot insert Triangle insert, 6.5 mm male Triangle insert, 7 mm male Triangle insert, 8 mm male Triangle insert, 9 mm male Square insert, 6 mm male Square insert, 7 mm male Square insert, 8 mm male Square insert, 6 mm female Barrel lock no. 2432E
99
Pages
114 114 114 114 61 32, 61, 132 61 98, 113 98 98, 113 98 98 113 126 126 98 98, 113 96 98 97, 98, 113 98 98, 113 113 98, 113 98, 113 98, 113 113 113 63 63 63 63 63 51, 100, 132 125 63 63 63 63 63 63 100 100 100 116 116 116 100 116 100, 116 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
08961 08963 08964 08965 08987 08988 08989 08990 08992 08993 08994 08998 09931 09932 09933 09934 09937 09939 09942 09943 09945 09946 09947 09948 09949 09981 09982 09983 09984 09985 09986 09987 09988 09989 13142 13143 13144
Touch-up paint brush Adhesive drawing holder Switchboard lighting Switchboard portable lamp Fan Grill with filter Filters, 5 standard Filters, 5 fine Resistor, 55 W Resistor, 90 W Resistor, 250 W Thermostat
63 63 62 62 64 64 64 64 65 65 65 65
Pages
09000
Slot handle insert IP55 for screwdriver Double bar handle insert IP55, 3 mm IP55 barrel + 2 no. 2433 A keys IP55 8 mm male triangle insert for handle (CNOMO) IP55 7 mm male triangle insert for handle IP55 9 mm male triangle insert for handle IP55 barrel + 2 no. 1242E keys IP55 barrel + 2 no. 3113A keys IP55 barrel + 2 no. 455 keys IP55 6 mm female square insert for handle IP55 7 mm male square insert for handle IP55 8 mm male square insert for handle IP55 6 mm male square insert for handle IP55 screwdriver slot insert for door IP55 3 mm double bar insert for door IP55 7 mm male triangle insert for door IP55 8 mm male triangle insert for door (CNOMO) IP55 9 mm male triangle insert for door IP55 6 mm male square insert for door IP55 7 mm male square insert for door IP55 8 mm male square insert for door IP55 6 mm female square insert for door Installation accessory for Kaedra enclosure: 103 x 225 mm plate - 2 openings Installation accessory for Kaedra enclosure: 103 x 225 mm plate - for 65 x 65 or 75 x 75 mm outlet Installation accessory for Kaedra enclosure: 103 x 225 mm plate - for 100 x 107 mm outlet Two-pole multi-stage distrib. block, 100 A (2 x 7 holes) Two-pole multi-stage distrib. block, 125 A (2 x 13 holes) Four-pole multi-stage distrib. block, 40 A (4 x 13 holes) Four-pole multi-stage distrib. block, 100 A (4 x 7 holes) Four-pole multi-stage distrib. block, 125 A (4 x 13 holes) Four-pole multi-stage distrib. block, 125 A (4 x 17 holes) Additional neutral bar for cat. no. 13508 Additional neutral bar for cat. no. 13510 Additional neutral bar for cat. no. 13512 Additional neutral bar for cat. no. 13514 Self-adhesive label sheets for common symbols (10) Self-adhesive label sheets for special symbols (10) Comb busbar (W=430 mm, 16 poles) 1P Comb busbar (W=430 mm, 16 poles) 2P Comb busbar (W=430 mm, 16 poles) 3P Comb busbar (W=430 mm, 16 poles) 4P Tooth caps (set of 20) Comb busbar, 24-module (9 mm modules) 1P Comb busbar, 24-module (9 mm modules) 2P Comb busbar, 24-module (9 mm modules) 3P Comb busbar, 24-module (9 mm modules) 4P Insulated connectors for 25 mm cables (4) End-caps 1P/2P/1P + N, for comb busbars (40) End-caps 3P/4P/3P + N, for comb busbars (40) Tooth-caps for comb busbar teeth (40) Comb busbars, 2 48-module (9 mm modules) 1P Comb busbars, 2 48-module (9 mm modules) 2P Comb busbars, 2 48-module (9 mm modules) 3P Comb busbars, 2 48-module (9 mm modules) 4P
116 116 116 116 116 116 116 116 116 116 116 116 116 116 116 116 116 116 116 116 116 116 115 115 115 79, 130 79, 130 79, 130 79, 130 79, 130 79, 130 79, 130 79, 130 79, 130 79, 130 63 63 82 82 82 82 82 82, 131 82, 131 82, 131 82, 131 82, 131 82, 131 82 82, 131 82, 131 82, 131 82, 131 82, 131
13000
13506 13507 13508 13510 13512 13514 13515 13516 13517 13518 13735 13736 14811 14812 14813 14814 14818 14881 14882 14883 14884 14885 14886 14887 14888 14891 14892 14893 14894
14000
Index
14936 14937 14938 14939 21086 21088 21089 21090 21092 21093 21094 21095 21096 21098 28947 28948
Cat. no.
80A joinable distribution block 1P - 25 and 16 mm 80A joinable distribution block 2P - 25 and 16 mm 80A joinable distribution block 1P - 35 and 25 mm 80A joinable distribution block 2P - 35 and 25 mm comb busbar for DPN - 2P - 24 mod (9mm) comb busbar for DPN - 2P - 48 mod (9mm) comb busbar for DPN - 2P - 96 mod (9mm) comb busbar for DPN - 3P - 24 mod (9mm) comb busbar for DPN - 3P - 48 mod (9mm) comb busbar for DPN - 3P - 96 mod (9mm) lateral tooth-caps - 2P lateral tooth-caps - 3P Tooth-caps (12) Insulated connectors (4) lateral tooth-caps - 2P lateral tooth-caps - 3P Tooth-caps (12) Long terminal shield INS-INV 250 Coupling accessory NSX 100/250-3P Coupling accessory NSX 100/250-4P Raiser Mechanical interlocking Source changeover assembly-100A-3P Source changeover assembly-100A-4P Source changeover assembly-200A-3P Source changeover assembly-200A-4P Source changeover assembly-160A-3P Source changeover assembly-160A-4P Source changeover assembly-250A-3P Source changeover assembly-250A-4P Long terminal shield INS-INV 320/630 Long terminal shield Fupact INF40/60 Long terminal shield Fupact INF100/160 Long terminal shield Fupact ISFT160-3P Long terminal shield Fupact ISFT250-3P Stop plate for markers 2-pole commoning link for 35 mm screw term.block 2-pole commoning link for 70 mm screw term.block 2-pole commoning link for 150 mm screw term.block Markers - 6 mm pitch Markers - 6 mm pitch Markers - 6 mm pitch Markers - 6 mm pitch Markers - 6 mm pitch Markers - 6 mm pitch Markers - 6 mm pitch Markers - 6 mm pitch Markers - 6 mm pitch Markers - 6 mm pitch Markers - 6 mm pitch Markers - 8 mm pitch Markers - 8 mm pitch Markers - 8 mm pitch Markers - 8 mm pitch Markers - 8 mm pitch Markers - 8 mm pitch Markers - 8 mm pitch Markers - 8 mm pitch Markers - 8 mm pitch Markers - 8 mm pitch Markers - 6 mm pitch Markers - 8 mm pitch Markers - 6 mm pitch
Designation
79 79 79 79
Pages
21000
82, 131 82, 131 82, 131 82, 131 82, 131 82, 131 82, 131 82, 131 82, 131 82, 131 69, 129 69, 129 38, 39, 41 40, 41 40, 41 41 41 41 41 41 41 41 41 41 41 38, 39 42, 43 42, 43 44, 45 44, 45 87 86 86 86 87 87 87 87 87 87 87 87 87 87 87 87 87 87 87 87 87 87 87 87 87 87 87 87
28000 29000
29324 29358 29359 31064 31073 31140 31141 31142 31143 31144 31145 31146 31147 32565 49658 49659 49869 49872
31000
32000 49000
AB1 AB8P35 AB1 ALN352 AB1 ALN702 AB1 ALN1502 AB1 B6L1 AB1 B6L2 AB1 B6L3 AB1 B610 AB1 B620 AB1 B630 AB1 B640 AB1 B650 AB1 B660 AB1 B680 AB1 B690 AB1 B810 AB1 B820 AB1 B830 AB1 B840 AB1 B850 AB1 B860 AB1 B870 AB1 B880 AB1 B890 AB1 B6100 AB1 B670 AB1 B8100 AB1 BV6
AB1
AB1 BV6BM AB1 BV6RP AB1 BV8 AB1 RRAL42 AB1 RRAL102 AB1 RRAL162 AB1 RRN435U2BL AB1 RRN435U2GR AB1 RRN435U3BL AB1 RRN435U3GR AB1 RRN635U2BL AB1 RRN635U2GR AB1 RRN1035U2BL AB1 RRN1035U2GR AB1 RRN1635U2BL AB1 RRN1635U2GR AB1 RRNAC442BL AB1 RRNAC442GR AB1 RRNAC443BL AB1 RRNAC443GR AB1 RRNAC643BL AB1 RRNAC643GR AB1 RRNAC1042BL AB1 RRNAC1042GR AB1 RRNAC1642BL AB1 RRNAC1642GR AB1 RRNAL62 AB1 RRNTP435U2 AB1 RRNTP435U3 AB1 RRNTP635U2 AB1 RRNTP1035U2 AB1 RRNTP1635U2 AB1 RRNTPAC442 AB1 RRNTPAC443 AB1 RRNTPAC642 AB1 RRNTPAC1042 AB1 RRNTPAC1642 AB1 S1 AB1 VVN3535U AB1 VVN3535UBL AB1 VVN7035U AB1 VVN7035UBL AB1 VVN15035U AB1 VVN15035UBL EZ4TSHD3P EZ4TSHD4P EZATSHD3P EZATSHD4P EZETSHD3P EZETSHD3PN EZETSHD4P EZETSHD4PN LV429285 LV429306 LV429307 LV429369 LV429515 LV429516 LV429517 LV429518 LV432593 LV432594 PRA90045 PRA90046 PRA90047 PRA90048 PRA90049 PRA90050 PRA90051
Cat. no.
Markers - 6 mm pitch Markers - 6 mm pitch Markers - 8 mm pitch 2-pole insulated commoning link - 4 mm 2-pole insulated commoning link - 10 mm 2-pole insulated commoning link - 16 mm Terminal block 1in/1out-blue-4 mm Terminal block 1in/1out-grey-4 mm Terminal block 1in/2out-blue-4 mm Terminal block 1in/3out-grey-4 mm Terminal block 1in/1out-blue-6 mm Terminal block 1in/1out-grey-6 mm Terminal block 1in/1out-blue-10 mm Terminal block 1in/1out-grey-10 mm Terminal block 1in/1out-blue-16 mm Terminal block 1in/1out-grey-16 mm Blue end plate - 4 mm Grey end plate - 4 mm Blue end plate - 4 mm Grey end plate - 4 mm Blue end plate - 6 mm Grey end plate - 6 mm Blue end plate - 10 mm Grey end plate - 10 mm Blue end plate - 16 mm Grey end plate - 16 mm 2-pole insulated commoning link - 6 mm Terminal block 1in/1out-green/yellow-4 mm Terminal block 1in/2out-green/yellow-4 mm Terminal block 1in/1out-green/yellow-6 mm Terminal block 1in/1out-green/yellow-10 mm Terminal block 1in/1out-green/yellow-16 mm Separation partition - 4 mm Separation partition - 4 mm Separation partition - 6 mm Separation partition - 10 mm Separation partition - 16 mm Label for markers Screw terminal block grey 35 mm Screw terminal block blue 35 mm Screw terminal block grey 70 mm Screw terminal block blue 70 mm Screw terminal block grey 150 mm Screw terminal block blue 150 mm Long terminal shield EZC/EZCV250 3P Long terminal shield EZC/EZCV250 4P Long terminal shield EZC100-3P Long terminal shield EZC100-4P Long terminal shield EZC250-3P Long terminal shield EZC250-3P Long terminal shield EZC250-4P Long terminal shield EZC250-4P Sas Vigi NSX 100/250 400/630 Adaptator NSX 100/250 3P Adaptator NSX 100/250 4P Mechanical interlocking for NSX 100/250 changeover system Short terminal shield NSX400/630 3P Short terminal shield NSX400/630 4P Long terminal shield NSX100/250 3P Long terminal shield NSX100/250 4P Long terminal shield NSX400/630 3P Long terminal shield NSX400/630 4P 50 mm terminal block kit 25 mm terminal block kit 4 x 6 mm terminal block kit Splitter block kit Splitter block kit Splitter block kit Terminal block support kit
Designation
87 87 87 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86
Pages
EZ
36, 37 36, 37 37 37 36 37 36 37 32, 33, 35 32 32 40 32, 33, 35 32, 33, 35 32, 33, 40 32, 33, 40 35 35 83 83 83 83 83 83 83
LV
PRA
Presentation
Overview
10
Prisma Plus:
the optimised, tested and IEC compliant solution, for low voltage electrical distribution and control switchboards.
Prisma Plus,
11
Presentation
Overview
G System
160 A
> Residential > Laboratories > Healthcare centres > Shopping centres > Supermarkets > Malls, etc.
Pack
12
P System
3200 A
630 A
> Automobile factories > Food industry > Deary > Internet data centres > Logistics centres, etc.
Prisma Plus P
Prisma Plus G
13
Presentation
Overview
aesthetics
Prisma Plus G with its discreet design, blends harmoniously into all tertiary and industrial buildings, including in entrance halls and passageways.
Available power Safety of people and property Controlled costs and delivery times Upgradeability
14
upgradeable LV switchboards
optimised and upgradeable
With Prisma Plus G you can build just the right switchboard for your customer, sized precisely to fit costs and needs. With this complete, prefabricated and tested system, it's easy to upgrade your installation and still maintain the performance levels. > The wall-mounted and floor-standing enclosures combine easily with switchboards already in service. > Devices can be replaced or added at any time.
15
Presentation
16
Standard IEC 61439 clearly defines the type of verifications that must be conducted by both organisations involved in final conformity of the solution: the Original Manufacturer, guaranteeing assembly system design and the Assembly Manufacturer, responsible for the final conformity of the switchboard.
Specifier
> Specifies the needs and constraints for design, installation, operation and upgrading of the complete system. > Checks that its requirements have been fully integrated by the Assembly Manufacturer. Depending on the application, the specifier could be the end-user or a design office.
sse
ly mb
Sy
m ste
Tes t
ed
As
Proje
ct spe
sem
Original Manufacturer
The organisation that has carried out the original design and the associated verification of an assembly system.
He is responsible for the "Design verifications" listed by IEC 61439-2 including many electrical tests.
cifica
tion*
bly
End-User
Should ask for a certified LV switchboard. By systematically requesting routine verifications, he ensures that the assembly system used is compliant.
17
Presentation
For each of the following 10 functions, the standard IEC 61439 requires design verifications from the system manufacturer - mainly through type-tests - and routine verifications on each panel from the Panel Builder to achieve 3 basic goals: safety, continuity of service and compliance with end-user requirements. Safety
Voltage stresses withstand capability Current-carrying capability
To withstand long term voltages, and transient and temporary overvoltages according to the insulation coordination principles and requirements. To protect against burns and to withstand temperature rise: > when any circuit is continuously loaded, alone, to the specified current > when the assembly is loaded to the specified current according to the specified load pattern (between circuits and/or as a function of the time).
To withstand the stresses resulting from the prospective short-circuit current and from the associated data (High forces between conductors, temp. rise in a very short time, air ionization, overpressure). > Hazardous-live-parts not to be accessible (basic protection) > Accessible conductive parts not to become hazardous-live (fault protection).
> Resistance to internal glowing elements > Note: Protection of persons, and optional protection of the assembly, against arcing due to internal fault can be specified through a "special test" according to IEC 61641.
Continuity of service
Maintenance and modification capability
Capability to preserve continuity of supply without impairing safety during assembly maintenance or modification > Electrical condition of the assembly or various circuits > Speed of exchange of the functional units > Test facilities
Electro-Magnetic compatibility
To properly function (immunity) and not to generate EM disturbances (emission) in specified environmental conditions: > Industrial networks or locations (Environment A) > Domestic, commercial, and light industrial locations (Environment B).
> To withstand handling, transport, storage and installation constraints > Capability to be erected and connected (type of enclosure, type, material and cross sectional areas of external conductors).
Job No.: ................................................................................................. Switchboard No.: ................................................................................... Drawing No./Rev. No.: ............................................................................
Chapter
Degrees of protection provided by enclosures Insulation clearances and creepage distances Protection against electric shocks and integrity of protection circuits Integration of incorporated components Internal electric circuits and connections Terminals for external conductors Mechanical operation Dielectric properties Wiring, operating performance and function 11.2 11.3 11.4 11.5 11.6 11.7 11.8 11.9 11.10
Verified
Dielectric properties
The main circuits, and the auxiliary and control circuits connected to the main circuit, shall be subjected to the test voltage in accordance.
IEC 61 439-1 paragraph 11.10
19
Presentation
Incomer
Compact NSX250 4P Fixed, front connection Toggle Incoming cables via bottom to incoming connection block
Distribution
Polybloc distribution block
Outgoing devices
Multi 9 or Acti 9 devices Supply 80 A Multiclip Comb busbars Cable running Straps + cover Connection Terminal block at top of switchboard Motor circuit breakers Supply Comb busbars Cable running Straps + cover Connection Terminal block at top of switchboard
IP30 enclosure
Wall-mounted enclosure, W = 595 mm, H = 930 mm Plain door Partial plain door
20
Presentation
Incomer
Interpact INS160 4P Incoming cables via top
Distribution
160 A Powerclip busbars
Outgoing devices
Multi 9 or Acti 9 devices Supply 80 A Multiclip Comb busbars Cable running Straps + cover Connection Terminal block in duct, W = 300 mm Motor circuit breaker + contactor combinations Supply Cable wiring Cable running Straps + cover Connection Terminal block in duct, W = 300 mm
IP30 enclosure
Wall-mounted enclosure, W = 595 mm, H = 1230 mm Transparent door Duct, W = 305 mm, H = 1230 mm Plain door
21
Presentation
Incomer
Compact NSX250 Fixed, front connection Toggle Incoming cables via top to incoming connection block
Distribution
Powerclip busbars
Outgoing devices
Multi 9 or Acti 9 devices Supply 80/200 A Multiclip Comb busbars Cable running Straps + cover Trunking Connection Terminal block in duct, W = 300 mm Motor circuit breakers Supply Cable wiring Cable running Trunking Connection Terminal block in duct, W = 300 mm
IP30 enclosure
Wall-mounted enclosure, Transparent door W = 595 mm, H = 1230 mm Duct, W = 305 mm, Plain door H = 1230 mm
22
Presentation
Incomer
Interpact INS160 Lateral handle Incoming cables via bottom, directly to device
Distribution
Distribloc distribution block
Outgoing devices
Multi 9 or Acti 9 devices Supply Comb busbars Cable running Cable running Straps + cover Connection Terminal block at bottom of enclosure Motor control and protection devices Supply Comb busbars Cable running Trunking Connection Terminal block at bottom of enclosure
IP55 enclosure
Wall-mounted enclosure, Transparent door W = 595 mm, H = 1250 mm
23
Presentation
Incomer
Compact NSX400 Fixed, front connection Toggle Incoming cables via bottom in duct (W = 300 mm) to incoming connection block
Distribution
Powerclip busbars
Outgoing devices
Compact NSX250 Fixed, front connection Toggle Supply
Multi 9 or Acti 9 devices Supply Comb busbars 200 A Multiclip Cable running Trunking Connection Vertical terminal block at bottom of floor-standing enclosure Appareils protection et commande moteur Supply Multiclip 200 A Cable running Trunking Connection Vertical terminal block at bottom of floor-standing enclosure
Enveloppe IP30
Floor-standing enclosure, Transparent door W = 595 mm, H = 1830 mm Duct, W = 305 mm, Plain door H = 1830 mm
24
Presentation
Customise, and easily modify the single-line diagram. Move or duplicate devices. Generate current distribution and connection systems.
Choose the switchboard and let the software set up the enclosure. A list of mounting and connection accessories is proposed to make mounting work easier. Automatically export the information required to make a clear, comprehensive and professional quotation.
25
Presentation
DD384078
1
DD383850
Installation/connection
DD383960
NSX100/250
NSX
03232
2
DD381878
DD383961
NSX100/250
NSX
NSX
DD383521
Order the mounting plates and front plates taking into account: bb supply to the rows bb cable running.
1
DD383518
Multi 9 or Acti 9
> see page 47
DD383519
2
DD381880
TeSys "U"
bb Multiclip distribution block > see page 80 bb cable running > see page 60
19 modules 21 modules
Plain front plate
26
Presentation
Powerclip busbars
> see page 68
DD381882
DD383522
DD383520
DD381884
IP wall-mount enclosure
DD384356
DD384355
DD381885
Duct, W = 300 mm
3 4
Cable tie supports Accessories for lifting, handling, wall mounting, finishing parts, etc.
27
Functional system
28
Functional system
Contents
Presentation..................................................................................30
Fusegear ......................................................................................42
Fupact INF horizontal mounting........................................................................... 42 Fupact INF vertical mounting............................................................................... 43 Fupact ISFT and ISFT-N horizontal mounting...................................................... 44 Fupact ISFT and ISFT-N vertical mounting.......................................................... 45
Other devices................................................................................50
Kilowatt-hour meters Classe II............................................................................. 50 Kilowatt-hour meters............................................................................................ 51 Human-switchboard interface.............................................................................. 52
Accessories.................................................................. 56
Front plates, rails, slotted mounting plates........................................................... 56 Fixing accessories............................................................................................... 58 Partitioning........................................................................................................... 59 Cable running...................................................................................................... 60 Switchboard lighting............................................................................................. 62 Finishing parts..................................................................................................... 63 Management of the internal temperature............................................................. 64
Distribution.................................................................. 66
Panorama of the solution..................................................................................... 66
Non-Centralised distribution..........................................................68
630 A insulated busbar......................................................................................... 68 400 A rear busbars............................................................................................... 70 630 A multi-stage busbars in duct......................................................................... 72 Insulated flexible bars.......................................................................................... 74
Centralised distribution..................................................................75
Distribution block ................................................................................................. 75 Comb busbars..................................................................................................... 82 Earth block / neutral block.................................................................................... 83 Earth bars............................................................................................................ 84 Terminal blocks.................................................................................................... 86 Terminal blocks layout.......................................................................................... 87
29
Functional system
Presentation
Terminal block
Front plate
Example: "Incomer" functional unit.
The easy-to-read switchboard circuit diagram makes on-site cabling and connection operations simple.
30
Functional system
Presentation
Electrical characteristics
Prisma Plus components comply with standard IEC 61439-1 et 2 and have the following electrical characteristics: bb rated insulation level of main busbars at rear of enclosure: 1000 V bb rated operational current Ie (40 C): 630 A bb rated peak withstand current Ipk: 53 k bb rated short-time withstand current Icw: 25 kA rms / 1 second bb frequency: 50/60 Hz.
31
Functional system
Mounting
600 300
Devices
Toggle
Motor mechanism module 1 8 03031 03292 [4] + LV429285 (sas) 03802 [2] 03802 [2] 3P: LV429517 4P: LV429518
Number of devices per row No. of vertical modules Mounting plates Front plates with cut-out [No. of vertical upstream modules] downstream Incoming connection block Long terminal shields + cable tying
1 5 03030 03232 [4] 03801 [1] cables via top: 04066 cables via bottom: 04067 -
NSX100/250
Vigi NSX100/250
NSX100/250
Vigi NSX100/250
NSX100/250
(1) Maximum size of connection cables: 70 mm. For cable cross-sections greater than 70 mm, use of a cable duct is recommended.
Mounting
600 300
Horizontal fixed
DD383855 DD380589
Horizontal plug-in
DD383855
Devices
Toggle
Toggle
NSX100/250 NSX100/250
with ammeter module or Vigi
NSX100/250
1 4 03032 03290 [4] 3P: LV429517 4P: LV429518 3P: LV429306 4P: LV429307
Number of devices per row No. of vertical modules Mounting plates Front plates with cut-out [No. of vertical modules] downstream Long terminal shields + adaptator
Distribution
Powerclip busbars
DD380522
Rear busbars
DD380777
Busbars in duct
DD380761
Type of connected devices Busbars / distribution blocks Power supply block Short terminal shield
All type
All type
3P: 04033 > see page 75 > see page 68 4P: 04034 04060 (2) 04060 (2) 3P: LV429515 4P: LV429516
04061 (3) -
32
Functional system
Mounting
600 300
Vertical fixed
DD383871 DD380666
Devices Number of devices per row No. of vertical modules (1) Mounting plates Front plates with cut-out [No. of vertical modules] upstream downstream Incoming connection block Divisible 85 x 147 mm blanking plates 107 x 147 mm
NSX100/160 NSX250
Vigi NSX100/160
8 03040 03241 [7]
03802 [2] 03802 [2] 03802 [2] 03802 [2] 03801 [1] 03802 [2] 3P: LV429517 4P: LV429518 03249 (to add modular devices to a row with Compact NSX 3P or 4P without electronic trip unit) 03222 (to add modular devices to a row with Compact NSX 3P or 4P with electronic trip unit)
4 x 3P or 3 x 4P 7 9 8 03041 03041 03041 03243 [5] 03243 [5] 03244 [7] + LV429285 (sas) 03802 [2] 03802 [2] 03802 [2] 03801 [1]
Distribution
Rear busbars
DD380777
Busbars in duct
DD380761
Type of connected devices Distribution block / busbars Adjustable rail Power supply block Connection block Short terminal shield
NSX
VigiNSX
All type
All type
must be made
Mounting
300 600
Vertical fixed
DD383858
Devices
Toggle
Number of devices per row No. of vertical modules (2) Mounting plates Cut-out front plates Incoming connection block
NSX 100/250
11
Type of connected devices Distribution block / busbars Adjustable rail Power supply block Connection block Short terminal shield
NSX
DD382567
VigiNSX
All type
> see page72
All type
> see page70
03011 -
04065 -
(3) Space available at the top of the enclosure after mounting the universal power supply block: - NSX 100/250 = 7 modules - Vigi NSX 100/250 = 9 modules. Space required by power supply block on Powerclip busbars = 5 modules.
33
Functional system
Mounting
600 300
Horizontal fixed
DD383852 DD383851
Devices Number of devices per row No. of vertical modules Mounting plates Front plates cut-out [No. of vertical upstream modules] Incoming connection block
NSX400/630
Distribution
Powerclip busbars
DD380783
Rear busbars
DD380777
Busbars in duct
DD380761
NSX400 04070
NSX630 04071
All type -
All type -
34
Functional system
Mounting
600 300
Vertical fixed
DD383853 DD383854
Devices Number of devices per row No. of vertical modules (1) Mounting plates Front plates cut-out [No. of vertical modules] upstream downstream Long terminal shield (1) With or without spreaders.
NSX400
NSX630
Vigi NSX400
Vigi NSX630
NSX400/630
Vigi NSX400/630
Distribution
Powerclip busbars
DD383825
Rear busbars
DD380777
Busbars in duct
DD380761
Type of connected devices Busbars Power supply block Short terminal shield (2) Connection must be made
All type
All type
All type
Mounting
300 600
Vertical fixed
DD383857 DD383858
Busbars
Rear
DD380777
Devices
Toggle
Number of devices per row No. of vertical modules (3) Mounting plates Front cut-out plates [No. of upstream vertical downstream modules] Long terminal shield
Type of connected devices Busbars Power supply block Connection block Short terminal shield Barrier
All type
> see page 68
All type
> see page 70
All type
> see page 72
04074 04073
04075
04198
(4) Space available at the top of the enclosure after mounting the universal power supply block: - NSX 100/250 = 7 modules - Vigi NSX 100/250 = 9 modules Space required by power supply block on Powerclip busbars = 5 modules.
35
Functional system
Mounting
600 300
Horizontal fixed
DD383994
Devices
EZC250 / EZCV250
Number of devices per row No. of vertical modules Mounting plates Cut-out front plates Long terminal shield (set of 2)
EZC400
Distribution
Rear busbars
DD380777
Busbars in duct
DD380761
All type
All type
36
Functional system
Mounting
600 300
Vertical fixed
DD38110 DD383044 DD383993
Devices
EZC100
Number of devices per row No. of vertical modules Mounting plates Cut-out front plates Long terminal shield (set of 2) Divisible blanking plate H=85 mm, L=147 mm
EZC250 / EZCV250
EZC400
Distribution
Busbars in duct
DD380761
All type
All type
37
Functional system
Switch-disconnectors
Mounting
600 300
Devices Number of devices per row No. of vertical modules Mounting plates Front plates cut-out [No. of vertical upstream modules] Incoming cables via top connection cables via top block
Direct front handle 1 5 03030 03231 [4] 03801 [1] 04066 04067
INS-INV250
Mounting
600 300
Devices
INS-INV250
INS-INV320/630 INS-INV320/630
Number of devices per row No. of vertical modules Mounting plates Front plates cut-out [No. of vertical upstream modules] Long terminal shield (set of 2)
Distribution
Rear busbars
DD380777
Busbars in duct
DD380761
Type of connected devices Distribution block / busbars Power supply block (1) (1) Supplied with connection
All type
> see page 70
All type
> see page 72
38
Functional system
Switch-disconnectors
Mounting
600 300
Devices Number of devices per row No. of vertical modules Mounting plates Front plates cut-out [No. of vertical upstream modules] downstream Long terminal shield (set of 2)
Direct front handle 1 8 03040 03248 [5] 03801 [1] 03802 [2] 29324
INS/INV250
INS/INV320/400
INS/INV500/630
INS/INV250
Distribution
Powerclip busbars
Dd381348
Rear busbars
DD380777
Busbars in duct
DD380761
Distribution block / busbars Adjustable modular device rail Power supply block Connection block Short terminal shield (1) Copper spacer.
Lateral handle 3P 4P > see page 68 04033 04034 + 04037 (1) + 04037 (1) 03003 03003 04060 04062 29322
INS-INV 250
INS-INV 320/630
All type
All type
Mounting
Distribution
Rear busbars
300
600
Type of connected devices Distribution blocks / Busbars Adjustable modular device rail Power supply block Connection block Short terminal shield Barrier
INS-INV INS-INV INS-INV INS-INV All type 250 320/630 250 320/630
> see page 68 > see page 70 > see page 72
Devices
04198
No. of vertical modules Mounting plates Front plates cut-out [No. of downstream vertical modules] Long terminal shield (set of 2)
(2) Space available at the top of the enclosure after mounting the universal power supply block: 7modules. Encombrement du bloc dalimentation sur Powerclip: 5modules
DD380777
39
Functional system
Fixed
600
ON I
reset
O OFF
Devices
Front connection, direct rotary handle 3P 10 03043 03245 [5] 03802 [2] 03803 [3] LV429369 LV429517 29358
NSX100/250
No. of vertical modules Mounting plates Front plates cut-out [No. of vertical upstream modules] downstream Mechanical interlocking Long terminal shield Coupling accessory
4P 10 03043 03245 [5] 03802 [2] 03803 [3] LV429369 LV429518 29359
40
Functional system
Mounting
300
Fixed
600
I ON
I ON
OFF O
Devices
Front, direct rotary handle 3P 9 03043 + 2 x 31064 (raiser) 03235 [5] 03802 [2] 03802 [2] 31073 -
Front, direct rotary handle 4P 9 03043 + 2 x 31064 (raiser) 03235 [5] 03802 [2] 03802 [2] 31073 3P 9 03043 03247 [5] 03802 [2] 03802 [2] 100 A: 31140 160 A: 31144 200 A: 31142 250 A: 31146 29324 29358
INS-INV250
INS250
No. of vertical modules Mounting plates cut-out Front plates [No. of vertical upstream modules] downstream Mechanical interlocking Complete source changeover assembly Long terminal shield Coupling accessory
29324 29358
29324 29359
4P 9 03043 03247 [5] 03802 [2] 03802 [2] 100 A: 31141 160 A: 31145 200 A: 31143 250 A: 31147 29324 29359
41
Functional system
Mounting
600 300
Horizontal
DD382474 Dd382475
Devices
INF32
Number of devices per row No. of vertical modules Mounting plates Front plates cut-out [No. of vertical downstream modules] Long terminal shield
3P 1 5 03114 03314 -
INF40/60
INF100/160
49658
Distribution
Rear busbars
DD380777
Type of connected devices Distribution blocks / busbars Additional 35 mm2 block Connection block
All type
> see page 70
INF100/160 3P
4P 04156
All type
> see page 72
must be made
(2) T he mounting plate for INF Fupact does not leave a passage for the busbar; it can only be installed below the plate. The distribution system is installed under the functional unit.
42
Functional system
Mounting
600 300
Vertical
DD382477 DD382478
Devices
INF32/40
Number of devices per row No. of vertical modules Mounting plates Front plates cut-out [No. of vertical downstream modules] Long terminal shield
4P 3 3 03113 03313 -
3P 3 5 03114 03314 -
INF63
INF100/160
49658
Distribution
Rear busbars
DD380777
Busbars in duct
DD380761
Type of connected devices Distribution blocks / busbars Adjustable modular device rail Universal power supply block Connection block
INF100/160
> see page 70
All type
> see page 68
All type
> see page 72
(2) T he mounting plate for INF Fupact does not leave a passage for the busbar; it can only be installed below the plate. The distribution system is installed under the functional unit.
43
Functional system
Mounting
600 300
Horizontal
DD342480
Devices Number of devices per row No. of vertical modules Mounting plates Front plates cut-out [No. of vertical upstream modules] downstream Long terminal shield
On mounting plate 1 6 03121 03326 [3] 03801 [1] 03802 [2] (1) 49869 x 2
ISFT160
ISFT250
Busbars
Powerclip busbars
Dd382481
Rear busbars
Dd380777
Busbars in duct
Dd380761
Type of connected devi ces Distribution blocks / busbars Universal power supply block Connection block
All type
All type
All type
44
Functional system
Mounting
600 300
Vertical
Dd382482 Dd382483
Distribution
Devices Number of devices per row No. of vertical modules Mounting plates Front cut-out plates upstream [No. of downstream vertical modules] Long terminal shield On mounting plate 5 On busbars 4 6
Comb busbar
DD382484
ISFT100N
ISFT160
Connected devices Comb busbar Type Number
Distribution
Connectors (2)
Busbars in duct
DD380761
Type of connected devices Connectors / distribution block / busbars Adjustable modular device rail Universal power supply block Connection block
All type
All type
All type
Mounting
300 600
Vertical fixed
Dd382488
Devices Number of devices per row No. of vertical modules Mounting plates Cut-out front plates Long terminal shield
ISFT160
ISFT250
Distribution
Type of connected devices Distribution block / busbars Adjustable modular device rail Universal power supply block Connection block
All type
All type
All type
must be made
45
Functional system
Mounting
600 300
Circuit breaker
Dd383268
Switch-disconnector
Dd383995
Devices No. of vertical modules Rail (48 modules of 9 mm) Modular front plates Blanking plate strip > see page 127 divisible
NG125, Vigi NG125, C120, Vigi C120, iC120, Vigi iC120 5 03001 03205
(1) Can be completed by a rail + raiser (ctn.no 04227) to instal modular devices on.
Mounting
300 600
Circuit breaker
Dd383626
Switch-disconnector
Dd383496
Devices No. of vertical modules Rail (20 modules of 9 mm) Front plates modular [No. of vertical modules] downstream Blanking plate strip > see page 127 divisible
NG160 5 03011 (adjustable) (2) 03214 [4] 03811 [1] 03220 03221
INS100/160 with long terminal shields 5 03010 03214 [4] 03811 [1] 03220 03221
(2) Can be completed by a rail + raiser (ctn.no 04227) to instal modular devices on.
Distribution
Powerclip busbars
Dd383270
Rear busbars
Busbars in duct
Multi-stage distribution
DD382813
DD380777
All type
All type
All type
DD380761
All type
must be made
must be made
All type
All type
must be made
Mounting
600 300
Dd383530
Service connection
Modular incoming fusegear
Dd383531
Devices Number of devices per row No. of vertical modules Rail (48 modules of 9 mm) Cut-out front plates Horizontal partitioning (3)
(3) Order twice the catalogue number in case of other installation than at top enclosure
46
Functional system
Mounting
300
Vertical
Dd383121
600
Devices Rail length (modules of 9 mm) No. of vertical modules Rail (48 modules of 9 mm) Modular front plates Blanking plate strip > see page 127 divisible
Modular devices 40 A 48 3 03001 03203 03220 03221 48 8 03001 x 3 03223 03220 03221
(1) Note: For a modular row with a 160A (half row) and 200 A Multiclip distribution block positioned directly below a non-modular mounting-plate (Compact, Interpact, etc...), or at the top of a switchboard, add one additional module (i.e. 4+1) and a plain upstream front plate(03801)
Devices Rail length (modules of 9 mm) No. of vertical modules Rail (20 modules of 9 mm) Modular front plates Blanking plate strip > see page 127 divisible
Distribution
Comb busbar
Dd382484
According devices
> see page 82
All type
47
Functional system
For 600 mm wide wall-mounted For 300 mm wide duct and floor standing enclosures
DD381613 DD380708
600
Devices Useful length for rail No. of vertical modules Rail Plain front plates
For 600 mm wide wall-mounted For 300 mm wide duct and floor standing enclosures
DD383494 DD383492
600
Devices Useful length for rail No. of vertical modules Rail Front plates cut-out [No. of vertical upstream modules] downstream Blanking plate strip > see page 127 divisible
TeSys GV3 180 mm 5 03011 (adjustable) 03213 [3] 03811 [1] 03811 [1] 03220 03221
600
Devices Useful length for rail No. of vertical modules Rail Front plates transparent [No. of vertical plain modules] downstream
GV2 + LC1Dp or LC1Kp ( 40 A) 432 mm 5 03004 (in rear) 03342 [4] 03801 [1]
GV2 + LC1Dp or LC1Kp ( 40 A) 180 mm 5 03011 (adjustable) 03352 [4] 03811 [1]
48
Functional system
600
Devices Useful length for rail No. of vertical modules Rail Front plates transparent [No. of vertical plain modules]
TeSys U 432 mm 5 03004 (in rear) 03342 [4] (2) 03801 [1]
(1) TeSys U without communication module, neither auxiliary contact, neither inverter module. (2) If the communication module is installed, the transparent front plate is mandatory. If not, the 2 front plates can be replaced by one plain front plate (cat.no 03805 in wall-mounted or floor-standing enclosure, 03815 in duct). (3) Or plain front plate (cat.no 03804 in wall-mounted or floor-standing enclosure, 03814 in duct).
On recessed slotted On rail in duct mounting plate (L = 600 mm) (L = 300 mm)
DD382604 DD381191
600
Devices
Number of devices per row Useful length No. of vertical modules Rail Slotted plates Plain front plates
ATS01N103FT ATS01N109FT ATS01N222 ATS01N106FT ATS01N112FT to 232 ATS01N206 to212 19 9 9 432 mm 432 mm 432 mm 4 5 6 03004 03003 03003 (in rear) 03804 03805 03806
ATS01N230LY ATS01N272LY, ATS01N285LY ATS01N244LY ATS01N272Q, ATS01N285Q ATS01N244Q 2 432 mm 5 03003 03805 2 420 mm 6 03172 03806
600
Devices Useful length for mounting plate No. of vertical modules Slotted plates Plain front plates
49
Functional system
Mounting
600 300
Accessible (1)
DD382948 DD382949
Devices Number of devices per row No. of vertical modules Mounting plates Metering front plates Horizontal partitioning Insulating plate Accessories
Single-phase (Ph + N) 3 6 03157 03155 04331 03154 M5 spacers for mounting plate > see page 58
Mounting
600 300
Devices Number of devices per row No. of vertical modules Mounting plates Front plate at transparent your choice plain Horizontal partitioning Insulating plates Accessories
Single-phase (Ph + N) 3 6 03157 03343 03806 04331 03154 M5 spacers for mounting plate > see page 58
(1) Order one additional horizontal partition in case of installation other than at the top of enclosure. Note: Meters can be installed directly on mounting plate equipped with 6 mm earthing braid (cat.no 08910) and combined with partitioning or front plates.
50
Functional system
Kilowatt-hour meters
Mounting
600 300
Devices Number of devices per row No. of vertical modules Mounting plates Front plates at transparent your choice plain Horizontal partitioning Earthing braid (2) Accessories
3-phase kilowatt-hour meters Connection blocks (3 Ph + N) 2 2 6 6 03160 03160 03343 03343 03806 03806 04331 04331 08910 08910 M5 spacers for mounting plate > see page 58
3-phase kilowatt-hour meters (3 Ph + N) + connection block 1+1 6 03160 03343 03806 04331 08910
Mounting
300 600
Devices Number of devices per row No. of vertical modules Mounting plates Front plates at transparent your choice plain Horizontal partitioning Earthing braid (2) Accessories
3-phase (3 Ph + N) 1 9 03156 03354 03817 04332 08910 M5 spacers for mounting plate > see page 58
(1) O rder one additional horizontal partition in case of installation other than at the top of enclosure. (2) M eters can be installed directly on mounting plate equipped with 6 mm earthing braid (cat.no 08910) and combined with partitioning or front plates.
51
Functional system
Human-switchboard interface
1
Dd381685
1
> In the device zone of wall-mounted and floor-standing enclosures
> On an interface with plastic mounting plates clipped onto the metal front plate with cut-outs
Dd381705
40 10 0
60 10 0
40
60 10 0
40
60
A
60
40 10 0
bb The interface is made up of a metal front plate and plastic mounting plates that clip onto the front plate. bb The devices are attached in the cut-outs of the plastic mounting plates and insulated from the front plate.
Dd381687
2
> On a partial door with cut-outs in wallmounted and floor-standing enclosures
Dd382574 Dd381643
0 0 0
bb Each mounting plate can receive an adhesive label. bb Plain mounting plates are available to blank off any unused locations.
2
> Directly on a metal front plate with cut-outs
Dd381689 Dd382636
3
> On a partial door with cut-outs, on an inclined visor by 30
bb Devices are attached directly to the metal front plate. bb Blanking plates are available to blank off any unused locations.
bb With cut-out plastic mounting plate directly clipped on the visor. bb Supplied with a drilling diagram for mounting on a plain door.
Note: - to maintain the IP55 degree of protection, the measurement devices must be installed behind a transparent door. - if they are installed on a plain door, use the corresponding mounting plates. ( > see page 53).
52
Functional system
Human-switchboard interface
Mounting
300
Directly on a metal front plate On an inclined visor by 30 with cut-outs with plastic mounting plates
DD381689 DD382636
600
Devices Number of devices per row No. of vertical modules Visor Metal front plates with cut-outs Plastic mounting plates with cut-outs Blanking plate or device support
Vigirex (1) and other devices 72 x 72 5 3 03904 03902 03900 To blank-off or install: - from 1 to 4 buttons, 16 or 22 mm - 1 device 45 x 45
DD382575
Vigirex and other devices 72 x 72 5 03928 03902 03900 To blank-off or install: - from 1 to 4 buttons 16 or 22 mm - 1 device 45 x 45
DD382575
(1) RHU, RH10P, RH21P, RH99 relay, RM12T Multiplexer, for 72 x 72 mm version.
Mounting
600
300
Devices Number of devices per row No. of vertical modules Metal front plates with cut-outs Visor Plastic mounting plates with cut-outs Blanking plate or device support
Other devices 96x96 4 3 03904 03903 03901 To blank-off or install: - from 1 to 4 buttons 16 or 22mm - 1 device 45 x 45 - 1 device 72 x 72
DD382633
Power Meter (2) and other devices 96 x 96 4 1 3 3 03911 03913 03908 To blank-off or install: - 1 or 2 buttons 22 mm - 1 device 45 x 45 - 1 device 72 x 72
DD383634
Power Meter (2) and other devices 96 x 96 4 03928 03903 03901 To blank-off or install: - from 1 to 4 buttons 16 or 22 mm - 1 device 45 x 45 - 1 device 72 x 72
DD382633
53
Functional system
Human-switchboard interface
Mounting
600 300
Devices Number of devices per row No. of vertical modules Metal front plates with cut-outs Blanking plate or device support
Device 144 x 144 + devices 72 x 72 1+4 4 03912 03907 To blank-off the unused locations 72 x 72 or install: - 1 or 2 buttons 22mm - 1 device 45 x 45
Dd382637
Vigilohm system
Mounting
600 300
Devices Number of devices per row No. of vertical modules Metal front plates with cut-outs Blanking plate or device support
Vigilohm system (1) + devices 72 x 72 1+6 4 03934 03907 To blank-off the unused locations 72 x 72 or install: - 1 or 2 buttons 22mm - 1 device 45 x 45
Dd382637
54
Functional system
Human-switchboard interface
Devices Number of devices per row No. of vertical modules Metal front plates with cut-outs (1) Harmony Style 4, 5 and 7
600
300
DD383480
2 3 4 5
Devices No. of vertical modules Rail (48 modules of 9 mm) Cut-out front plates
(1) RH10, RH21, RH99, RMH relay and RM12T Multiplexer. (2) EM9, TR5A, SM21, IMD-IM9. (3) For installation at the top or bottom of the enclosure, use a 3-module modular front plate (03203).
4 mod. (H = 200 mm) 6 mod. (H = 300 mm) 9 mod. (H = 450 mm) 12 mod. (H = 600 mm)
55
Functional system
Accessories
Used for
Enclosure L600
DD381583 DD381582
Duct L300
DD381584 DD381585
Duct L300
DB124226
DD381576
04224 Set of 5 Heigth 10 mm, length 27 mm Colour: RAL 9001, insulating material
56
Functional system
Accessories
Used for
Enclosure L600
DD381351
Duct L300
DD381370
DD383497
DD381371
DD381353
DD381352
DD383497
Catalogue numbers Useful length 9mm modules number Useful depth behind front plate
Installation accessories
Used for 45 supports
DD383504
Brackets
DD383505
Hexagonal spacers
DD383506
03005 Set of 2
04206 H = 15 mm
04207 H = 45 mm
04208 H = 80 mm
03195 H = 9 mm
03196 H = 23 mm
DD381371
03197 H = 55 mm
Adjustable rails
Rail to be cut
DD381310 DD383292
04226
04227
Set of 2 rails, useful length: 1600 mm Rail and 4 modular raisers with 4 holes, dia. 6.4 mm, 450 mm Useful length: 432 mm between centres
Duct L300
DD381369 DD381375
Catalogue numbers Nb. of vertical modules Height Useful length Useful depth behind front plate
03172 6 300 mm
03173 9 450 mm
03177 6 300 mm
03178 9 450 mm
Clip-nuts
For slotted mounting plates
DD381312
M4 M5 M6 Characteristics
03180 03181 03182 Set of 20. Can also be mounted on cable-tie support cat. no. 08876. Offers installation of various devices
57
Functional system
Accessories
Fixing accessories
Clip-nuts
Clip-nuts
DD381312 DD381313 DD381612 DD381637 DD384035
M4 M5 M6 Mounting on Characteristics
03180 03181 03182 Slotted mounting plate and also on cable-tie support (08876) Set of 20 Mounting of various devices
Self-tapping screws
Self-tapping screws
M5 Characteristics
Hexagonal spacers
Hexagonal spacers
Dd380828 Dd380828 Dd380828 Dd380828 Dd380828
M5 M6 M8 Characteristics
03581 Set of 2
03583 Set of 6
58
Functional system
Accessories
Partitioning
Horizontal partitioning
The metal partitions are used to: bb separate the functional units from one to another bb create a physical separation between devices and a terminal block, for example.
Used for
04331 04332 Metal. It is mounted directly on the functional uprights. Lateral and rear cut-outs are available for cable running or the installation of busbars at the rear of the switchboard.
Vertical partitioning
The metal partition creates a physical separation between the device compartment and a wide duct. It is used to: bb separate the devices from busbars or a distribution block installed in the duct, bb set up a special zone for terminal blocks in the duct.
Used for
04330 Can be used for partitioning up to 33-modules. It can be cut to length every 150 mm.
08384 Metal. There are cut -outs for cable running. Quantity to order according to height. Nb. of vertical modules 7 11 of 50 mm Height (mm) 450 650 Quantity 1
15 850 2
19 1050
23 1250 3
27 1450
33 1750
59
Functional system
Accessories
Cable running
Dd381628
Dd381618
04264 Set of 12
Dd381633
04263 Set of 2 x1 m
Trunking supports
Type Vertical trunking supports
Dd383476
Dd381623
04265 Set of 12
Dd381626
04255 Set of 12
Trunkings
Type Vertical trunkings 80 x 60 mm
Dd381640
Dd382922
04256 Set of 10 Aligns the cover of a horizontal trunking section (H=60 or 80mm) with that of a vertical trunking section (H=80mm) Note: not designed for use with Pack enclosures.
60
Dd381621
Functional system
Accessories
Cable running
Cable trunkings
DD381641
Cable-tie supports
Used for Cable-tie supports for wall-mounted or floor-standing enclosures
DD381820
C-shaped cable-tie supports for wallmounted or floor standing enclosures and ducts
DD383424
08867 bb Set of 2 bb Supplied with hardware for mounting on the functional uprights of the enclosure.
08868 bb Set of 4 bb Supplied with hardware for mounting on the functional uprights of the duct.
DD383423
08783 bb L = 1600 mm, can be cut to length as needed. bb Cables secured by ties or cable clamps. bb Supplied with hardware for mounting on the functional uprights of the enclosure or duct.
08866 bb Set of 2 bb Makes it possible to tie down the cables next to the gland plate and gain one module in height.
DD381171
61
Functional system
Accessories
Switchboard lighting
Fixed lighting
Fixed lighting
600 300
DD381719
08964 This system is generally used to illuminate the front of a switchboard. bb The kit is made up of: vv a base, vv a neon tube, vv a front plate with cut-out (1 module), vv a door contact. bb Supply voltage: 220/240 V bb Power rating: 8 W bb Height: 1 vertical module (50 mm)
Characteristics
Characteristics
08965 bb Lamp with a magnetic base for installation behind a door or directly on the cubicle framework. bb Supplied without a power cord. bb It does not take up any useful space in the switchboard. bb Supply voltage: 220/240 V bb Power rating: 11 W
62
Functional system
Accessories
Finishing parts
Identification labels
Clip-on labels
DD381714
Engraving plates
DD381757
IERE LUM
IERE LUM
08913 08915 08917 18 x 35 18 x 72 25 x 85 bb Set of 12 bb The clip-on support is supplied with a paper label and a transparent cover. bb It clips onto the front plate horizontally or vertically and can be screwed to any support (plain door, plain front plate, etc.).
08914 08916 08918 18 x 35 18 x 72 25 x 85 bb Set of 12 bb These plates simply replace the paper labels.
Adhesive labels
DD381715
Symbol sheets
DD381751 DD381753 DD381752
08905 08906 08903 08904 24 x 180 36 x 180 24 x 432 36 x 432 bb Set of 12 bb The adhesive label holders are supplied with a paper label and a transparent cover.
13735 bb Set of 10 adhesive symbol sheets bb Standard symbols: vv loads: sockets, lights, heating units, etc. vv rooms: bedroom, bathroom, etc.
13736 bb Set of 10 adhesive symbol sheets bb Special symbols: vv loads: lightning arrestor, gate, swimming pool, etc. vv rooms: technical room, computer room, etc.
Earth symbols
01009
Accessories
Switchboard identification plate
DD381721
63
Functional system
Accessories
In most cases and notably for IP30 switchboards, convection takes place naturally and does not require fans. However, when the switchboard is installed in temperate environments or when the degree of protection is high (IP55), ventilation accessories are indispensable.
For more in-depth information on selecting air-conditioning accessories and the thermal management of switchboards. > see page 158 to page 167.
Fan
DD381703
08987 08988 Generally installed at the bottom of floor-standing enclosures: bb by cutting out a side panel; bb or by using the front plate with cut-out for fan, directly clipped on (03890). The set comprises the fan with a grill and a filter. bb Power rating: 70 W. bb Input voltage: 230 V. bb Noise level: 69 db. bb Degree of protection: IP54. bb Weight: 3 kg. bb Unimpeded throughput: 460 m3/h. bb Throughput with counterpressure (grill + standard filter, cat. no. 08988): 350 m3/h.
DD381723
Supplied with standard filter. bb Maximum throughput 350 m3/h. bb Degree of protection: IP54.
Filters
Catalogue numbers Characteristics 08989 Set of 5 (for replacement)
DD381724
Dimensions
Standard filters
Fine filters
03891 03895 1 vertical module, 3 vertical modules, H = 50 mm H = 150 mm 250 cm2 Surface area of the openings 80 cm2 Characteristics Degree of protection: IP30. Located at the top and bottom of the switchboard, IP30 ventilated front plates facilitate natural convection in the switchboard. Catalogue numbers Height
64
Functional system
Accessories
The resistors prevent condensation, corrosion and superficial leakage currents. They maintain a positive temperature in the enclosures when external temperatures drop very low.
Heating resistor
DD381574 DD381573
08992
08993
08994
55 W 90 W 250 W bb Horizontal or vertical mounting. bb Aluminium case with fins. bb Temperature: vv turns off at 60 C, vv turns on at 25-30 C (temperature of the resistor itself). bb Equipped with a symetrical rail for rapid mounting (clips on). bb Input voltage: 230 V.
Regulating
Thermostat
DD381575
Used to control the temperature inside electrical switchboards in conjunction with heating resistors and fans.
08998 bb Setting range: +5 C to +60 C. bb Input voltage: 230 V. bb Fixing: clips onto a modular rail.
65
Functional system
Distribution
Distribution blocks
> For incoming devices
160 to 250 A Polybloc
63/200 A Multiclip
- Reliable spring-terminal connections for outgoing circuits, requiring no maintenance - Horizontal or vertical installation in minimum space
- Reliable spring-terminal connections requiring no maintenance - Fast installation - Easy upgrades through replacement or addition of devices - Easy balancing of phases
- Fast and direct connections, adaptable to all needs - Fast, economical connections
- Innovative solution
66
Functional system
Distribution
Rear busbars.
Lateral busbars. The bars are staggered for easy access to connection points.
omb busbars are fully C insulated. Device can de connected in a single operation.
80 A Multiclip.
200 A Multiclip.
The Multiclip distribution block snaps easily onto the back of the rails. All types of modular devices can be mixed in the same row and phase balancing is simple. It's easy to change or add devices.
Snapped onto the back of rails, cable straps are a solution for clear and well-organised cabling.
They can be used for all configurations, whatever the number of cables and cable cross-sections. A cover protects the wiring and provides a neat finish. Horizontal and vertical, with different cross-sections, they are interconnected by adjustable trunking supports.
67
Functional system
Distribution
Non-Centralised distribution
Compact busbars, IPxxB, ready for installation in the switchboard (supplied with supports and extremity obturators) Tap-off blocks for 6 mm and 10 mm cable ETP H12 channelled copper bars with threaded M6 holes every 25 mm, can be cut every 200 mm Bars mounted on insulated bases that screw to the functional upwrights Wide choice of prefabricated and tested connections Clip-on covers to protect against direct contacts from the front (IPxxB). They can be easily cut for the connections to the devices The ends are protected by extremity obturators 200 A connection for Multiclip distribution block
PD390546
Powerclip busbars
Additional accessories*
W = 1000 mm W = 1400 mm 4P W= 1000 mm W = 1400 mm 2 Powerclip supports + 2 extremity obturators + mounting hardware 2 IPxxB clip-on covers, L= 200 mm
3P
160 A
250 A
PD390337
400 A
630 A
Electrical characteristics
Rated level
Insulation Ui 750 750 750 1000 Impulse withstand voltage Uimp 8 8 8 8
Rating
160 A 250 A 400 A 630 A
(kA rms / 1 s)
30 30 52,5 52,5
(k)
(V)
(kV)
Device to connect
NSX400 horizontal NSX630 horizontal NSX400/630 vertical with or without Vigi NSX100/250 horizontal with or without Vigi NSX100/250 vertical without Vigi
Interpact INS-INV
Fupact INS NG
NSX100/250 vertical with Vigi INS-INV250 horizontal INS-INV320/400 horizontal INS-INV500/630 horizontal INS-INV250 vertical INS-INV320/630 vertical INF100/160 horizontal INF100/160 vertical ISFT 100/250 vertical or horizontal INS40/125 3P 4P INS160 NG125 NG160 Vigi NG160
04070 04071 04074 + connection must be made (in enclosure) or 04074 + 04073 (in duct) 04060 04061 + 04062 (in enclosure) or 04061 + connection must be made (with rotary handle in enclosure) or 04061 +04064 (in duct) 04061 + connection must be made (in enclosure)04061 + 04064 (in duct) 04060 04070 04071 04061 + 04062 (in enclosure) or 04061 + 04064 (in duct) 04074 + connection must be made (in enclosure) or 04074 + 04073 (in duct) 04155 + connection must be made (3P) or 04156 + connection must be made (4P) 04061 + connection must be made 04061 + connection must be made 04145 +28947 04145 +28948 04147 or 04148 or 04146 04145 or 04147 or 04148 or 04146 04147 or 04148 or 04146 04148 04147 or 04148 or 04146 04147 or 04148 04151 or04152 04021 04151 or04152
68
Functional system
Distribution
Non-Centralised distribution
Busbar connection
DD380522
Description
Compact NSX100/250 horizontal with or without Vigi Interpact INS-INV250 horizontal Compact NSX400 horizontal Interpact INS-INV320/400 horizontal Compact NSX630 horizontal Interpact INS-INV500/630 horizontal Compact NSX100/250 toggle in enclosure Interpact INS-INV250 vertical in enclosure Compact NSX100/250 with or without Vigi in duct Interpact INS-INV250 vertical in duct Compact NSX400/630 with or without Vigi in duct Interpact INS-INV320/630 in duct Compact NSX100/250 rotary handle in enclosure Fupact INF100/160 vertical Fupact ISFT Compact NSX400/630 with or without Vigi in enclosure Interpact INS-INV320/630 in enclosure NSX, Multiclip 200 A, Fupact
Allows connection of
Cat. no.
DD380593
Universal power supply block +connections must be made (possibility to use insulated flexible bars)
> see page 74
DD381659
Universal power supply block +insulated flexible bars Set of 4 125 A connections, L= 230 mm 35 mm ferrule + 45 angle lug ( insulated covers IPxxB, cat. No 04150) Set of 4 160 A connections, L= 230 mm 45 mm ferrule + 45 angle lug ( insulated covers IPxxB, cat. No 04150) One-piece connection 3/4P - 160 A, L = 150mm bb Fast connection to busbars bb Equipped with male fittings one end for tunnel terminals bb Respects the degree of protection IPxxB bb Neutral is clearly indicated (blue)
DD383274
NG125, NSA equipped with tunnel terminals or comb, INS with tunnel terminals Catalogue numbers 28947 or 28948 NSA160, INS160, NG125, NG160 NSA160, NG160 (located on left-hand side), NG125, INS160, C120, iC120
DD381379
DD383294
One-piece connection 3/4P - 160 A, L = 440mm bb Fast connection to busbars bb Equipped with male fittings one end for tunnel terminals bb Respects the degree of protection IPxxB bb Neutral is clearly indicated (blue)
DD383276
NSA160, NG160 (located on left-hand side), Vigi NG160 (located in the middle), NG125, INS160, C120, iC120
DD383295
04148
DD381405
12 tap-off blocks for 6 mm and 10 mm cable Respects the degree of protection IPxxB 12 tap-off blocks for 16 mm Respects the degree of protection IPxxB Set of 4 200 A connections Supplied with mouting hardware + Insulating cover
DD383498
All type of device, equipped with tunnel terminals, 160/200 A Multiclip All type of device, equipped with tunnel terminals, 160/200 A Multiclip Multiclip 200A
DD383472
04021 + 04150
Accessories
Connection cover
DD381385
bb Clip-on covers that block off the connected 04150 cable lugs and can be cut as needed. bb They maintain IPxxB with 90 angle lugs and/ or cable sizes from 10 to 25 mm. bb 8 IPxxB covers for Powerclip busbars 04158
Cat. no.
Cat. no.
69
Functional system
Distribution
Non-Centralised distribution
Flat, copper bars with threaded M6 holes every 25 mm for connection along the entire length of the busbars. bb Connection by: vv 16 mm to 50 mm flexible cables, with crimped lugs vv insulated flexible bars
> see page 74
Dd381388
Dd381192
Presentation The rear busbars are mounted directly on the uprights of the framework. There are three and four-pole versions with ratings from 160 to 400 A. Available in two lengths, 1000 and 1400 mm, they can be cut as needed. The connection with a Compact or Interpact incoming device occupies two vertical modules (50 mm each).
Bars (Set of 4)
Rating
Cross-sectional areas of conductors Length 1000 mm 1400 mm Catalogue numbers Barrier, H = 100 mm, supplied with mounting hardware
160 A
250 A
Dd381389
400 A
(1) The insulating supports can receive a fifth bar, 15 x 5 mm or 20 x 5 mm to create an earth bar. (2) Rating (A) 160 250 400 Size of bars Distance between support centres (mm) (3) (mm) Icw (kA rms / 1 s) y 10 y 13 y 15 y 20 y 25 15 x 5 20 x 5 450 300 225 32 x 5
(3) Multiclip 200 A distribution blocks equipped with connections (04029) can be used as intermediate supports (200 mm max.distance between centres) in addition to the top and bottom supports (04191).
Electrical characteristics
Rating Icw (kA)
Short-time withstand current Icw 160 A 250 A 400 A 10 13 15, 20, 25
Ui (V)
Rated peak withstand current Rated insulation level
(kA rms / 1 s)
30 40 55
(k)
(V)
70
Functional system
Distribution
Non-Centralised distribution
Designation
bb A comb busbar bb NG125, NSA and INS equipped with tunnel terminals
DD383510
04145
Catalogue numbers
NSA160
04146
Set of 4 rear busbar connection - 200 A Note: Multiclip 200 A distribution blocks equipped with connections (04029) can be used as intermediate supports (200 mm max. distance between centres) in addition to the top and bottom supports.
Multiclip 200 A
04029
DD381458
04190
DD381659
NSX100 NSX160/250 NSX400 NSX630 INS125/160 INS250 INS400 INS630 200 A multiclip Fupact 250 Fupact 400 Fupact 630
04742 04743 04751 04753 04742 04743 04751 04752 04743 04746 04751 04753
Accessories
8.8 class mounting hardware
20 bolts M6x20 + 20 nuts + 40 contact washers 40 screws M6x16 + 40 contact washers
DD381398
Catalogue numbers
04194 04195
07051
07052
07053
71
Functional system
Distribution
Non-Centralised distribution
Presentation The multi-stage busbars are installed in a 300 mm wide duct. They are particularly useful for distribution to two enclosures on each side of the duct. All connection points are easily accessible from the front. The inclination of the bars facilitates connections and improves cable running. There are three and four-pole versions with ratings from 160 to 630 A. Available in two lengths, 1000 and 1400 mm, they can be cut as needed.
Front barrier protect against direct contact with connections (in option).
Dd381388
Flat, copper bars with threaded M6 holes every 25 mm for connection along the entire length of the busbars. bb Connection: vv 16 mm to 50 mm flexible cables, with crimped lugs vv insulated flexible bars
> see page 74
Bars (Set of 4)
Rating
Insulating support (1) (2) Accessories (1) Rating (A) 160 250 400 630 Size of bars (mm) 15 x 5 20 x 5 32 x 5 32 x 8
Cross-sectional areas of conductors Length 1000 mm 1400 mm Catalogue numbers Barrier, H = 1500 mm
160 A
250 A
400 A
Dd381395
Bars supports in insulating material direct installation on the functional uprights of the duct.
630 A
Distance between support centres (mm) Icw (kA rms / 1 s) y 10 y 13 y 15 y 20 y 25 450 300 300 (3)
(2) Supplied with mounting hardware for barrier, cat.no. 04197. (3) With Icw 25 kA rms / 0,6 s.: distance between supports 300 mm (Rating 400 A with bars 32 x 5 mm only).
Electrical characteristics
Rating Icw (kA)
Short-time withstand current Icw 160 A 250 A 400 A 630 A 10 13 15, 20 25
Ui (V)
Rated peak withstand current Rated insulation level
(kA rms / 1 s)
30 40 55 55
(k)
(V)
72
Functional system
Distribution
Non-Centralised distribution
Dd382305
Description
bb Compact NSX 100/250 vertical in duct bb Interpact INS-INV 250 vertical in duct
04065
Catalogue numbers
bb Compact NSX 400/630 vertical in duct bb Interpact INS-INV 320/630 vertical in duct
04075
Dd383499
Multiclip 200A
04024
DD381659
NSX100 NSX160/250 NSX400 NSX630 INS125/160 INS250 INS400 INS630 200 A multiclip Fupact 250 Fupact 400 Fupact 630
04742 04743 04751 04753 04742 04743 04751 04752 04743 04746 04751 04753
Accessories
Dd381398
Catalogue numbers
04194 04195
73
Functional system
Distribution
Non-Centralised distribution
The insulated flexible bars are tested in a type-tested switchboard environment. Their design takes into account the switchboard architecture where they are often in close proximity to a protection device (circuit breaker or fuse) with significant heat losses. The sizes for the flexible bars indicated below take into account the heat losses of Schneider Electric devices in a Prisma Plus switchboard.
Dd381659
Dd382008
Characteristics
Length Rated insulation level (Ui) 1800 mm 1000V
The flexible bars are determined taking into account the connected device, whatever the internal temperature of the switchboard. The bar sizes indicated below take into account the derating curves of devices.
NSX100 NSX160/250 NSX400 NSX630 INS125/160 INS250 INS400 INS630 200 A multiclip Fupact 250 Fupact 400 Fupact 630
Device
20 x 2 20 x 3 (1) 32 x 5 32 x 8 20 x 2 20 x 3 32 x 5 32 x 6 20 x 3 24 x 5 32 x 5 32 x 8
Size (mm)
04742 04743 04751 04753 04742 04743 04751 04752 04743 04746 04751 04753
Catalogue numbers
(1) To connect a Compact NSX250 to Powerclip busbars, use a 24 x 5 mm flexible bar (04746).
Flexible bars are designed for connections between busbars taking into account the following characteristics: bb a maximum temperature of 60 C inside the switchboard. This corresponds to the average temperature inside a switchboard for an ambient temperature of 35 C bb the maximum withstand temperature for the insulating material is 125 C.
200 A 250 A 400 A 520 A 580 A 660 A
Ie* Max.
20 x 2 20 x 3 24 x 5 32 x 5 32 x 6 32 x 8
Size (mm)
Catalogue numbers
74
Functional system
Distribution
Distribution block
Centralised distribution
DD381399
The 160 A Polybloc is made up of individual elements that can be used alone or with others to make two-pole, three-pole or four-pole distribution blocks. Mounting is very fast. It clips onto a modular rail and is supplied by cables via a tunnel terminal. The connection spring terminals are slanted to facilitate cable entry and bending of the flexible and rigid cables. It is supplied with a cover that also guides the cables.
160 A Polybloc
160 A Polybloc
Dd382981 Dd383300 Dd383658
Dd381392
04031 bb Supply direct to a tunnel terminal, for cables up to 70 mm. bb Distribution via cables, up to 6x16 mm cables. Clip onto a modular rail.
Dd384321
70
95
36
Rated insulation level (Ui) Impulse withstand voltage (Uimp) Short-circuit withstand current
750 V 8 kV The reinforced breaking capacity due to cascading in circuit breaker combinations is maintained. The worst-case situations were tested.The electrical characteristics are perfectly compatible with the connected devices. Neither the temperature derating curves nor the performance levels of the circuit breakers and switch-disconnectors are altered.
Device to connect
Connection must be made + rail 03002 Connection must be made + rail 03002 or 03011 04149 04149 04149
Catalogue numbers
Description
04149
Cat. no.
Accessories
Adjustable modular rails
Dd381371
03002 03011
Cat. no.
75
Functional system
Distribution
Distribution block
Centralised distribution
DD381399
250 A Polybloc
Applications The Polybloc distribution block is designed for installation directly downstream of Compact circuit breakers and Interpact switch-disconnectors devices up to 250 A. It can be rapidly mounted in the horizontal position. Electrical connections are made directly to the device terminals. It has the same width as the devices and does not take up any additional space in the switchboard. The connection terminals are slanted to facilitate cable entry and not exceed the bending radius of the flexible and rigid cables.
3P
PD390549R DD380780 Dd381346
4P
DD380745
Rated insulation level (Ui) Impulse withstand voltage (Uimp) Short-circuit withstand current
DD381406
Space required
H L P
04033 04034 Supply directly to the terminals of the Compact NSX and Interpact INS devices up to 250 A. Directly on the mounting plates of horizontally mounted Compact NSX100/250 and Interpact INS250 devices in the enclosures. It can also be mounted downstream of vertically mounted Compact NSX100/250 and Interpact INS250 devices in the enclosures. In this case, the Polybloc is mounted on a depth-adjustable modular rail 105 140 138 138 63 63
750 V 8 kV The reinforced breaking capacity due to cascading in circuit-breaker combinations is maintained. The worst-case situations have been tested.
Device to connect
NSX100/250 with or without Vigi horizontal NSX100/250 with or without Vigi vertical INS-INV250 horizontal INS-INV250 vertical INS-INV250 Lateral handle vertical
04033 (3P) 04034 (4P) 04033 (3P) 04034 (4P) + rail 03002 or 03011 04033 (3P) 04034 (4P) 04033 (3P) 04034 (4P) + rail 03002 or 03011 04033 (3P) 04034 (4P) + rail 03002 or 03011 + spacer 04037
Catalogue numbers
Accessories
Adjustable modular rails
Dd381371
03002 03011
Catalogue numbers
Copper spacer
04037
Catalogue number
35 mm additional blocks
Designation
DD381403
These blocks with screw terminals can be mounted on the 250 A Polybloc for connection of two 35 mm cables per phase.
35 mm, 3P additional blocks (3 blocks) 35 mm, 4P additional blocks (4 blocks) 04155 04156
Catalogue numbers
76
Functional system
Distribution
Distribution block
Centralised distribution
125 A
PG123021 054947
160 A
PD390657
From the top or from bottom From the top or from bottom 04045 04046 04047 Supplied bb Incoming connection in a terminal for 10 to 35 mm cable per phase bb Distribution spring terminals: vv 7 outgoers from 1.5 to 4 mm2 vv 3 outgoers from 2.5 to 6 mm2 vv 2 outgoers from 4 to 10 mm2 bb Distribution in tunnel terminal: vv 1 outgoer from 4 to 16 mm2 For INS100/160 or NSA160, For NG125 andINS125 Installed on the right or left. Set of four flexible Set of 4 flexible connections 35mm2, L= 210mm connections supplied with the distribution block bb Clipped onto a modular rail: 12 modules (9 mm each) bb Screwed to plain or slotted backplate. Distances between centres = 100 x 75 mm.
Dd381608 Dd381609
Rated insulation level (Ui) Impulse withstand voltage (Uimp) Short-circuit withstand current Degree of protection Accessories supplied
750 V 8 kV The reinforced breaking capacity due to cascading in circuit breaker combinations is maintained. The worst-case situations have been tested. IPxxB An identification label Adhesive labels for phase identification
Distribloc 63 A
Rated operational current (Ie) 40 C 63 A
PB104500 PB104499
Incoming Catalogue numbers Total connection capacity ( for flexible cables) Installation Dimensions
Distribution block 4P
From the top From bottom 04040 04041 bb Incoming connection in a tunnel terminal for 25 mm cable per phase bb Distribution spring terminals: vv 4 outgoers from 6 mm2 for each phase vv 12 outgoers from 6 mm2 for the neutral bb Clipped onto a modular rail: 8 modules (9 mm each)
Dd122616
Rated insulation level (Ui) Rated operational voltage (Ue) Impulse withstand voltage (Uimp) Short-circuit withstand current Degree of protection
500 V CA 440 V CA 6 kV Up to the breaking capacity of Schneider Electric circuit breakers, even in cascading configuration IP20
77
Functional system
Distribution
Distribution block
Centralised distribution
160 A
DD381342
250 A
Dd381343
400 A
630 A
Composition
Rated insulation level (Ui) Impulse withstand voltage (Uimp) Rated short-time withstand current (Icw) Rated peak withstand current (Ipk)
750 V 8 kV 10 kA rms /1 s 30 k
DD381344
04052 04053 04054 04055 bb 13 threaded M6 holes for outgoers bb Four 12.2 mm diameter holes to supply the distribution block. bb Screwed horizontally onto the functional uprights of wall-mounted and floor standing enclosures. bb Screwed vertically onto the functional uprights of the 300 mm wide duct. bb Screwed to plain or slotted backplate. bb Two staggered supports made of an insulating material bb Four slanted copper bars with holes every 25 mm bb M6 hardware bb One IPxxB insulating barrier for the front. 15 x 5 mm 20 x 5 mm 32 x 5 mm 32 x 8 mm
13 kA rms /1 s 30 k
20 kA rms /1 s 40 k
25 kA rms /1 s 40 k
78
Functional system
Distribution
Distribution block
Centralised distribution
4P
058930d
Catalogue numbers Additional neutral bar Rated operational current (Ie) Pole number Supply (screw terminal) per phasis Distribution (screw terminal) per phasis Dimensions (H x W x P) Electrical characteristics
13514 13518 4P 1 term 25mm2 7 term 6 mm2 7 term 10 mm2 2 term 16 mm2 15 modules (9 mm) 81 x 134 x 50 mm
Installation
5 term 6mm2 11 term 6mm2 3 term 6 mm2 5 term 6 mm2 5 term 10 mm2 3 term 10 mm2 5 term 10 mm2 2 term 16 mm2 2 term 16 mm2 7 modules (9 mm) 12 modules (9 mm) 10 modules (9 mm) 7 modules (9 mm) 12 modules (9 mm) 40 x 62 x 50 mm 40 x 107 x 50 mm 81 x 89 x 50 mm 81 x 62 x 50 mm 81 x 107 x 50 mm bb Rated insulation level (Ui): 500 V CA bb Short-circuit withstand current: compatible with all Schneider Electric circuit-breakers. bb With other device, it is advised to check the energy limiting curve of the upstream device bb Rated short-time withstand current (Icw): 3.5 kA rms /1 s bb Rated peak withstand current Ipk = 20 k Designed to be clipped onto rail
2P
030925d
Catalogue numbers Pole number Supply per phasis Distribution per phasis Electrical characteristics Installation Dimensions
14936 14938 1P 1P 2 1 screw terminal 35 mm2 1 screw terminal 25 mm 4 screw terminal 16 mm2 4 screw terminal 25 mm2 bb Rated operational current (Ie): 80 A bb Rated insulation level (Ui): 500 V CA Designed to be clipped onto rail 2.5 modules 18 mm
5 modules 18 mm
79
Functional system
Distribution
Distribution block
Centralised distribution
Multiclip 63 / 80 A
Multiclip 63 / 80 A 63 A
DD383403
80 A
PD104505
PD381661
Supply Distribution
Installation
04008 b Rating: 63 A b 4P b 24 modules (9 mm), 12 modules (18 mm) Tunnel terminals up to 25 mm2 b Spring terminals: v 4 for each phase (2 x 4 mm2 + 2 x 6 mm2) v 8 for the neutral (4 x 4 mm2 + 4 x 6 mm2) By clipping at the rear of a modular rail, or by screwing.
DB404608
04000 b Rating: 80 A b 4P b 48 modules (9 mm) 24 modules (18 mm) Tunnel terminals up to 25 mm2 b Spring terminals: v 6 for each phase (6 mm2) v 18 for the neutral (6 mm2) By clipping at the rear of a modular rail, or by screwing.
DB124195
Accessories supplied
80
DB124196
PD384088
Functional system
Distribution
Distribution block
Centralised distribution
160 A
DD381673
Supply
Distribution
04012 04013 04014 04018 bb 3P bb 4P bb 4P bb 2P bb Rating: 200 A bb Rating: 200 A bb Rating: 200 A bb Rating: 160 A bb 48 modules (9 mm), bb 48 modules (9 mm), bb 48 modules (9 mm), bb 24 modules (9 mm), 24 modules (18 mm) 24 modules (18 mm) 24 modules (18 mm) 12 modules (18 mm) 1/2 row bb Rated insulation level (Ui): 750 V bb Impulse withstand voltage (Uimp): 8 kV bb Short-circuit withstand current: the reinforced breaking capacity due to cascading in circuit breaker combinations is maintained. The worst-case situations have been tested. vv 10 mm cable outgoer: Imax = 50 A vv two 10 mm cables: Imax = 63 A. bb From Powerclip insulated busbars in a wall-mounted or floor-standing enclosure (04021) bb From lateral, channelled busbars in a cubicle (connection must be made) bb From busbars in the duct of a wall-mounted or floor-standing enclosure (04024) bb From busbars in the rear of a wall-mounted or floor-standing enclosure (04029) bb 12 connection points for bb 12 connection points for each phase bb 6 connection points phase and neutral bb 18 connection points for the neutral for each phase bb 9 connection points for the neutral bb Clipped onto the rear of modular rail bb Screwed to plain or slotted backplate. bb 100 mm long, bared 10 mm copper connections bb 2 sets of 12 connections bb Protection covers for the supply terminals (IPxxB) 100 mm long, bared 10 mm bb The hardware required for the supply terminals copper connections bb Protection covers for the supply terminals (IPxxB) bb The hardware required for the supply terminals
Powerclip busbars
Supplied with
04021
Catalogue numbers
Dd383617
Busbars in duct
04024
Connection 4P 200 A (supplied with mounting hardware) Connection 4P 160 A for Multiclip 1/2 row
04029 04030
Spare parts
Description
DD384505
01202
Catalogue number
81
Functional system
Distribution
Comb busbars
Centralised distribution
Lateral tooth-caps
Tooth-caps
Insulated connectors
2-pole 3-pole
21086
21088
21089
21094
Supplied accessories
21090 21092 24 modules (9 mm) 48 modules (9 mm) 12 modules (18 mm) 24 modules (18 mm) Rating: 80 A Quantity per catalogue numbers: 1 4 lateral tooth-caps 1 tooth-caps 2 tooth-caps
Lateral tooth-caps
Tooth-caps
Insulated connectors
Catalogue numbers
Characteristics
Supplied accessories
14881 14891 14882 14892 14883 14893 14884 14894 bb 24 modules (9 mm) bb 48 modules (9 mm) bb 12 modules (18 mm) bb 24 modules (18 mm) bb 1 piece bb Set of 2 Rating: 80 A with 1 supply point 100 A with 2 supply points 2 lateral tooth-caps
Catalogue numbers
Characteristics
Supplied accessories
14814 bb 45 modules (9 mm) bb 48 modules (9 mm) bb 22.5 modules (18 mm) bb 24 modules (18 mm) bb 1 piece bb Set of 1 Rating: 125 A 63 A maxi by outgoers Tooth-caps (8 for 1 and 2-pole, 4 for 1 and 2-pole) 2 lateral tooth-caps
14813
14811 14812
82
Functional system
Distribution
Centralised distribution
DB107883
DB107884
DB107885
DB107888
DB107891
DB107887
PRA90047
PRA90051
PRA90048
PRA90050
PRA90049
bb Set of 10 bb Set of 1 bb W = 1 blocks bb W = 34 blocks max. bb Mounting on the functional uprights 63 A to 40C -
Permissible current
160 A to 40C
90 A to 40C
bb Set of 4 bb Set of 1 bb Set of 10 bb W = 1 blocks bb W = 8blocks bb W = 2blocks bb Designed to be clipped onto modular rail bb Ui: 400 V - Uimp: 6 kV 90 A with 1 jonction 160 A with 2 jonctions in parallel
Examples of composition
Single-phase terminal block
E101369d E101370d
DB107886
83
Functional system
Distribution
Earth bars
Centralised distribution
Earth bars
They are installed: bb In a duct, which may be a dedicated zone, totally separate from the devices bb In the device compartment, at the top or bottom.
Dd383501
Dd381560
04201 bb Size: 12 x 3 mm bb W = 330 mm bb Equipped with a 35 mm tunnel terminal (for earth blocks with spring terminals)
Dd383513
Neutral bars
Kit for neutral bar
DD382529
On 45 supports
DD383514
On fixing brackets
DD383515
On hexagonal spacers
DD383516
04206
04207
04208 H= 80 mm
03185
03186
03187
In enclosure: earth bars W = 450 mm with clamps or spring terminals In duct: earth bar with clamps W = 200 mm
H= H= 15 mm 45 mm Set of 2 brackets
84
Functional system
Distribution
Earth bars
Centralised distribution
This solution saves considerable space in the device zone and avoids the need for the 300 mm wide duct.
04206 04207 04208 H = 15 mm H = 45 mm H = 80 mm Set of 2 brackets Earth bar with clamps or spring terminals.
04220 bb A mounting plate (04220), made up of two supports, is equipped with: vv a 1600 mm modular rail (04226) for terminal blocks vv an earth bar The supports have cut-outs that can be used to easily tie down the connection wires. Earth bar with clamps or spring terminals.
04223 The mounting plate for terminal blocks (04223) can be equipped with two earth bars with clamps 200 mm earth bar with clamps.
85
Functional system
Distribution
Terminal blocks
Centralised distribution
They can be installed: bb In a duct, which may be a dedicated zone, totally separate from the devices bb In the device compartment, at the top or bottom.
Size of the conductor 4 mm
DD383818
4 mm2
DD383819
6 mm2
DD383820
10 mm2
DD383821
16 mm2
DD383821
Number of points Catalogue 1 Terminal Grey numbers blocks and Blue quantity Green / Yellow 2 Separation partition 3 End Grey plate Blue 4 2-pole insulated commoning link
1 incomer, 1 outgoer AB1 RRN435U2GR 100 AB1 RRN435U2BL 100 AB1 RRNTP435U2 100 AB1 RRNTPAC442 10 AB1 RRNAC442GR 10 AB1 RRNAC442BL 10 AB1 RRAL42 10
1 incomer, 2 outgoers AB1 RRN435U3GR 100 AB1 RRN435U3BL 100 AB1 RRNTP435U3 100 AB1 RRNTPAC443 10 AB1 RRNAC443GR 10 AB1 RRNAC443BL 10 AB1 RRAL42 10
1 incomer, 1 outgoer AB1 RRN635U2GR 50 AB1 RRN635U2BL 50 AB1 RRNTP635U2 50 AB1 RRNTPAC642 10 AB1 RRNAC643GR 10 AB1 RRNAC643BL 10 AB1 RRNAL62 10
1 incomer, 1 outgoer AB1 RRN1035U2GR 50 AB1 RRN1035U2BL 50 AB1 RRNTP1035U2 50 AB1 RRNTPAC1042 10 AB1 RRNAC1042GR 10 AB1 RRNAC1042BL 10 AB1 RRAL102 10
1 incomer, 1 outgoer AB1 RRN1635U2GR 50 AB1 RRN1635U2BL 50 AB1 RRNTP1635U2 50 AB1 RRNTPAC1642 10 AB1 RRNAC1642GR 10 AB1 RRNAC1642BL 10 AB1 RRAL162 10
Width
6 mm
6 mm
8 mm
10 mm
12 mm
Size of the conductor 35 mm2
501685_1R
150 mm2
501687_1R
Number of points Catalogue 1 Terminal Grey numbers blocks and Blue quantity 2 2-pole insulated commoning link
Width
16 mm
24 mm
28 mm
Fixing mode Directly on the functional uprights
DD383503 DD383504
On hexagonal spacers
DD383506
03004
03005
04206
04207
04208
03195 H = 9mm
03196
03197
bb Rear modular bb Set of 2 supports rail bb Rail catalogue numbers 03004 bb W = 432 mm ordered separately
H= H= H= 15mm 45mm 80mm bb Set of 2 brackets bb Rail catalogue numbers 03004 ordered separately
H= H= 23mm 55mm bb Set of four M6 hexagonal spacers bb Rail catalogue numbers 03004 ordered separately
86
Functional system
Distribution
Centralised distribution
Dd383500
04220 bb A mounting plate, made up of two supports can be equipped with: vv a modular rail for the terminal blocks, that is 1600 mm long, can be cut to length and has 6.4 mm holes every 450 mm vv an earth bar. bb The supports have cut-outs that can be used to easily tie down the connection wires.
This mounting assembly is used to easily install and connect a large number of terminal blocks in a minimum amount of space. It is particularly useful when a duct is not warranted or cannot be installed.
Mounting
In device compartment
DD383507
04223 bb Mounting brackets, fixed to the functional uprights at the top or bottom of the enclosure, is equipped with four 200 mm symetrical rails. They are installed vertically to facilitate cable running. bb To facilitate mixing of different size terminal blocks and ensure convenient connections from the front or the side, the distance between rails and the depth of each rail can be adjusted. bb The assembly has cut-outs that can be used to easily tie down the connection wires. bb Earth bars, supplied separately, can be installed between the rows of terminal blocks to form different configurations, e.g.: vv four sets of terminal blocks vv 3 sets of terminal blocks + one or two earth bars (W = 290mm). bb The mounting assembly occupies a height of 250 mm, i.e. five 50mm vertical modules.
Accessories
Markers
Catalogue numbers
DG113069
Label
AB1 S1
Stop plate
AB1 AB8P35
Characteristics
6 mm pitch AB1 BV6 AB1 B610 AB1 B620 AB1 B630 AB1 B640 AB1 B650 AB1 B660 AB1 B670 AB1 B680 AB1 B690 AB1 B6100 AB1 B6L1 AB1 B6L2 AB1 B6L3 AB1 BV6RP AB1 BV6BM
8 mm pitch AB1 BV8 AB1 B810 AB1 B820 AB1 B830 AB1 B840 AB1 B850 AB1 B860 AB1 B870 AB1 B880 AB1 B890 AB1 B8100 -
87
Contents
89
Presentation
> Safety of people and property > Continuity of service > Optimization and upgradeability > Ergonomics and complete accessibility > Controlled costs (installation, maintenance) and delivery times
100% reliable and in compliance with existing standards All the components (switchgear, splitter blocks, prefabricated connections, etc.) have been designed to work together. All switchboard configurations have been tested. Optimized, upgradeable installation With Prisma Plus G, you can build the right switchboard for your customer, sized precisely to fit costs and needs. Thanks to the organization around functional units, the installation evolves simply while preserving its original performance. Ease of setup The complete accessibility of all mounting and connection points facilitates assembly and cabling in the workshop. The functional units are clearly identified: operations are intuitive and reliable, and connection and checking are performed naturally.
91
Presentation
Commercial buildings: hotels, offices, shops, etc. Industry: technical room, etc.
Gland plate
PD390300
Safety
Continuity of service
bb Direct accessibility of functional unit thanks to the front plate hinges kit bb Total accessibility of switchgear thanks to the installation of hinges on all front plate (allows the front panel to be made swivelling)
PD390240
Main characteristics
Steel sheet metal with electrophoresis treatment + hot-polymerised polyester epoxy powder. Enclosure: bb width: 600 mm, with duct: 300 mm bb height: 330 to 1380 mm, bb depth: 205 mm without door / 250 mm with door.
Designation
G IP30 - IP31 - IP43 enclosure
Rated operational current Color Standards conformity Degree of protection Degree of protection against mechanical impacts Isolation Doors 630 A - Icc = 50 kA White colour RAL 9001 EN 62208, IEC 61439-2 IP30 with or without door, IP31 with canopy + door, IP43 with canopy + door + gasket IK08 with door, IK07 without door Class 1 bb Plain or transparent, opening to right or left bb By design, electrical continuity of moving parts (hinges) bb Supplied with a handle and keylock (key 405) Distance behind door = 58mm (possibility of push-buttons, lamps installation). Surface mounting, floor standing, flush mounting via a kit
Rapsody software
> see page 25
Mounting
93
Reversible doors (opening to left or right), equipped with a handle and keylock (key 405).
DD380622
DD380623
DD380624
DD382928
DD380626
Height inmm 330 480 630 780 930 1080 1230 1380
Enclosure
Plain door
Transparent door
No. of vertical Height modules of inmm 50mm 6 9 12 15 18 21 24 27 330 480 630 780 930 1080 1230 1380
Rear + top and bottom plates (1) 08172 08173 08174 08175 08176 08177 08178 08179
Plain door
Reversible doors (opening to left or right), equipped with a handle and keylock (key 405). bb two basic floor standing enclosures cannot be combined; bb to create a switchboard comprising a number of enclosures, use a basic floor standing enclosure and one or more floor-standing enclosure extensions; bb floor standing enclosure extensions are supplied with a combination kit for the basic floor standing enclosure; bb cables can be run on the sides of the plinth (diameter y 140 mm).
Dd380634
Dd380636
Dd380636
Dd380635
Dd380636
Dd380637
Dd380638
Dd380639
DD380627
Height Basic Plain inmm enclosure door 1530 1680 1830 08202 08203 08204 08222 08223 08224
Rear
Plain door
Plain door
Partitionning
94
Dd380640
Transparent door
Gasket for the door to increase the IP value from IP31 to IP43
Dd381268
Used with
1 wallmounted enclosure
2 wallmounted enclosures
08830
08832
08831
08833
08827
08841
The addition of a canopy over a wall-mounted or floor standing enclosure equipped with When the switchboard is equipped with a canopy, a door ensures compliance with the degree of protection IP31. a gasket for the doors ensures compliance with the degree of protection IP43. L = 5.3 m
Dd382928
Dd383030
Dd380626
Height inmm
Rear + top and bottom plates 08172 08173 08174 08175 08176 08177 08178 08179
Side panels
Plain door
Dd380631
Dd383030
Dd380639
Side panels
Plain door
Spare parts (rear accessories, door accessories, sides, uprights, plinths, etc.)
> see page 101
Dd380640
Dd380627
95
Combinations
Multiple combinations
Combination kits Horizontal
To make the combination more rigid, particularly during transport, it is mandatory to use a set of cross-members secured to the rear of the switchboard.
Vertical
1 wall-mounted enclosure + 1 duct Set of two lifting/reinforcement 08812 cross-members or vertical uprights + combination kit (2) DD384000
DD384000
Set of two lifting/reinforcement 08812 cross-members or vertical uprights + combination kit (2) -
+ plain plate
08882
Combination kits
Multiple
DD384000
2 wall-mounted enclosures + 2 ducts Set of two lifting/reinforcement 08812 cross-members Set of two vertical uprights (1) 08817 + combination kit (2) 08816
2 additional wall-mounted enclosures must be made 2 supplied with the enclosure extensions
08818
08818
2 x 08818
3 x 08818
4 x 08818
08818
08818
1 floor standing enclosure + 1 enclosure extension + 2 wall-mounted enclosures 08811 08817 08815
Set of two lifting/reinforcement 08812 cross-members Set of two vertical uprights 08817 + combination kit (2) 08815
DD384000
1 floor standing enclosure + 1 enclosure extension + 2 ducts + 2 wall-mounted enclosures 08813 08817 -
1 floor standing enclosure + 1 enclosure extension +4 ducts + 2 wall-mounted enclosures 08814 08817 -
1 floor standing 2 more ducts enclosure + 1 enclosure extension +6 ducts + 2 wall-mounted enclosures 08826 must be made 08817 -
08818 08882
08818 2 x 08882
2 x 08818 2 x 08882
3 x 08818 2 x 08882
4 x 08818 2 x 08882
08818 -
08818 08882
(1) Note: for more than 33 combined modules, these vertical uprights are mandatory. (2) A combination kit is supplied with each duct or enclosure extension. It can be necessary to use one kit more than those already supplied.
96
The lifting rings are used to move a single wall-mounted or floor standing enclosure. For combined enclosures, use the lifting/reinforcement cross-members (see below).
08801
08812
08811
08811
08813
08814
08826
Installation possibilities
Switchboards can be mounted on a wall in three manners: with the hook-on rail system, via the inside of the enclosure or using external wall-mounted brackets. Combined enclosures can be mounted using the lifting/reinforcement crossmembers set of two lifting/reinforcement cross-members.
Delivered with the enclosure The enclosure comes with 2 cross-members secured to the back of the enclosure (top and bottom) and a support rail (with levelling adjustment) for screwmounting on the wall. The enclosure is easily mounted on the hook-on rail system.
08804 The enclosure can be mounted through 4 external wall-mounted brackets. the spacers in the 4 holes provided on the enclosure using using 8 mm diameter screws (2 knockouts can be removed if necessary to provide 2 other holes).
Plinth raiser
For floor standing enclosure
Dd380633
Flush-mounting kit
For wall-mounted enclosure
Dd381256
08819 6 to 18 modules
08820 21 to 27 modules
97
Gland plates
G gland plates
Enclosures (wall-mounted, floor standing, ducts) are supplied with a plastic gland plate installed on the top or bottom for wall-mounted enclosures and the top for floor standing enclosures. For some connections needs, the existing plastic gland plate can be replaced by this metal gland plate.
At the top or bottom of a wall-mounted enclos. or duct, at the top of a floor standing enclos. Wall-mounted or floor standing enclos. Duct 08870 08874
Using at the top or bottom of a wall-mounted enclosure (+ duct) at he top of a floor standing enclosure (+ duct) Wall-mounted or floor standing enclosure. Duct 08880 08884
Trunking spreader
Trunking spreader
Dd381636
This plastic gland plate can be replaced by an interface plate with cut-outs for special cable entry systems made of an insulating material (plain, with knockouts or membrane-type).
Cat. no. 08824 Characteristics For a professional-looking connection between the trunking and the enclosure. Can be installed at the top or bottom. The spreader is marked for cut-outs for standard trunking sizes. The maximum capacity is two 250 x 80 mm trunking sections.
Duct 08875
Between the plinth and the bottom of a floor standing enclosure or duct, for ensuring IP20 Floor standing enclosure Duct 08887 08888
The gland plates are easy to install using the mounting kit (supplied with each gland plate) that positions and holds the nuts during installation. This makes it possible to mount the gland plates using a single tool.
Gland plates
Plain
Dd382934
With knockouts
Dd382935 Dd382935 Dd382935
Membrane-type
Dd382936 Dd382936 Dd382936
Catalogue numbers M12 M12 or M20 M16 or M25 M20 M20 or M32 M25 or M40
08881 -
08891 4 4 4 -
08892 2 2
08895 5 8 -
Number of entries
12
13
From 5 to 7 mm dia. From 6 to 10 mm dia. From 7 to 12 mm dia. From 8 to 12 mm dia. From 10 to 14 mm dia. From 12 to 18 mm dia. From 14 to 20 mm dia. From 17 to 32 mm dia. From 20 to 26 mm dia. From 28 to 60 mm dia.
08872 4 4 12 4 1 25
08896 2 6 8 16 2 1 35
08897 2 2
98
Accessories
Partial doors
Type Plain door Partial door with cut-outs
Dd381636
(for 72 x 72 or 96 x 96 mm devices)
Dd381636
08850 08851 Height: 6 modules. Useful height behind a partial door: 5modules. Installation on a wall-mounted enclosure at least 12 modules high (H u 630 mm). Reversible (opening to left or right), equipped with a handle and keylock (key 405). Note: each wall-mounted enclosure and basic floor standing enclosure or extension can be equipped with only one partial door. The front must be completed with another door.
99
Door accessories
ASSA/ABLOY handle
DD383882
Standard handle
DD383883
Padlocking
DD383885
08931 Supplied with barrel lock (key no. 405) RAL 7016
08938 The kit can be installed on the door handles equipped with any of the barrel locks and inserts above
The barrel locks and inserts below can be mounted on handle 08931 and on all the door handles of the Prisma Plus G IP30.
Inserts
DD383884 DD383884 DD383884 DD383884
08950 9 mm
Earthing braid
Earthing braid, 6 mm
DD384005
The earthing braid is used to earth a door or partial door with devices.
2
08910 Equipped with a 4 mm diameter lug at one end and a 6 mm diameter lug on the other
DD381338
08911 Equipped with a 5 mm diameter lug at one end and a 6 mm diameter lug on the other
DD384052
100
DD383884
Spare-parts
Accessories (IP30)
Duct accessories
DD384483
01036
4 kit pillars + pillar heads 1 earthing braid plug 4 washers 2 combination uprights 2 short combination crossbars 2 base blanking plugs 2 association fasteners 4 spacers 2 screws with flange 1 self threading screw 2 A-angle parts 2 B-angle parts 7 nuts HX grooved Wall-mounted and floor standing enclosure accessories 01018
DD384484
4 kit pillars + pillar head 2 A-angle parts 2 B-angle parts 8 self threading screws 1 earthing braid plug 4 base blanking plugs 4 spacers 4 nuts HX grooved
DD384485
4 spacers
01098
01032
1 earthing braid plug 2 door stops 3 self threading screws M5 x 10 1 handle staple 1 handle 1 square rod 3 fixed hinges 3 hinge pins 3 stop bolt 4 self threading screws M5 x 17 Retrofit handle 01220
DD384487
1 handle 1 key no.405 1 handle staple 1 Pack kit pin 1 assembled rod angle 1 peg and angle assembly for G cubicle 1 pozidriv screw for handle staple 1 self threading screw for Pack enclosure 1 pozidriv screw for wall-mounted and floor standinbg enclosures
101
Spare-parts
01017
DD384490
01039
Side (IP30)
DD384491
Wall-mounted enclosures Side for 6-module wall-mounted enclosures Side for 9-module wall-mounted enclosures Side for 12-module wall-mounted enclosures Side for 15-module wall-mounted enclosures Side for 18-module wall-mounted enclosures Side for 21-module wall-mounted enclosures Side for 24-module wall-mounted enclosures Floor standing enclosures Side for 27-module floor standing enclosures Side for 30-module floor standing enclosures Side for 33-module floor standing enclosures
Floor standing enclosures Side for 27-module floor standing enclosures Side for 30-module floor standing enclosures Side for 33-module floor standing enclosures
Plinths (IP30)
DD384493
Floor standing enclosures Left drilled base bracket + Right drilled base bracket 4 self threading screws Accessories for plinth Left base bracket + Right base bracket 4 self threading screws Plinth front, 600 mm Base cover + plinth 2 self threading screws
01050
DD384494
01051
DD384495
01052
01053
102
Spare-parts
2 front cover support uprights - 6 modules 2 front cover support uprights - 9 modules 2 front cover support uprights - 12 modules 2 front cover support uprights - 15 modules 2 front cover support uprights - 18 modules 2 front cover support uprights - 21 modules 2 front cover support uprights - 24 modules 2 front cover support uprights - 27 modules 2 front cover support uprights - 30 modules 2 front cover support uprights - 33 modules
01250 01251 01252 01253 01254 01255 01256 01257 01258 01259 01093
Front-plate accessories
DD384501
DD384502
01094
Accessories Powerclip 160/400 A 2 extremity obturators 2 brackets 2 screws Accessories Powerclip 630 A 2 extremity obturators 2 metallic supports 2 brackets for support 2 hexagonal spacers 8 self threading screws
01210
01211
DD384504
01201
103
Dimensions
Wall-mounted enclosures
DD384039 Dd381897 DD384044
H
330 480 630 780 930 1080 1230 1380 1530 1680 1830
H1
1380 1530 1680
Ducts
DD384041 DD384045
DD383052
DD383049
DD383050
147
104
Dimensions
Cable entry
DD383841
Trunking spreader
157
DD383841
496
206
Wall-mounted installation
Wall-mounted and floor standing enclosures
DD384318 DD384317
Ducts
545 483
DD384043
255 193
H1
246 396 546 696 846 996 1146 1296 1488 1638 1788
H2
430 580 730 880 1030 1180 1330 1480 1580 1730 1880
Functional uprights
Modular rail
Recessed mounting plate Cat. no. 03171, 03172, 03173, 03176, 03177 or 03178
Dd383058
Dd383059
105
IP55 enclosures
IP55 enclosures
Presentation
> Safety of people and property > Continuity of service > Robustness > Ergonomics and complete accessibility > Optimization and upgradeability
100% reliable and in compliance with existing standards All the components (switchgear, splitter blocks, prefabricated connections, etc.) have been designed to work together. All switchboard configurations have been tested. Even the most demanding. ptimized, upgradeable installation O Prisma Plus G IP55 is the only switchboard in this category designed as a "kit". All configurations and combinations are possible, with full access. Thanks to the organization around functional units, the installation evolves simply while preserving its original performance. Ease of setup The complete accessibility of all mounting and connection points facilitates assembly and cabling in the workshop. The functional units are clearly identified: operations are intuitive and reliable, and connection and checking are performed naturally.
107
IP55 enclosures
Presentation
Weatherproof enclosures
Metallic indoor enclosures to compose Severe environments: industrial and agricultural buildings, basements, kitchens, etc.
Practical
bb Functionalized installation of push buttons, power sockets, etc. bb Installation of power sockets on the side
PE60330
Continuity of service
bb Direct accessibility of functional unit if front plates are equiped with hinges
Weaterproofing
PE60331
Main characteristics
Steel sheet metal with electrophoresis treatment + hot-polymerised polyester epoxy powder. Enclosure: bb width: 575 mm, with duct: 325 mm bb height: 450 to 1750 mm, bb depth: 260 mm with door. Delivered with earthing braid (with door).
Description
Rated operational current Color Standards conformity Degree of protection Degree of protection against mechanical impacts Isolation Doors
IP55 enclosure
630 A - Icc = 50 kA White colour RAL 9001 EN 62208, IEC 61439-2 IP55 with door IK10 Class 1 bb Plain or transparent, opening to right or left bb By design, electrical continuity of moving parts (hinges) bb Supplied with a handle and keylock (key 405) Distance behind plain door = 78 mm, Distance behind transparent door = 73 mm Earthing braid delivered with enclosure
> see page 111
Rapsody software
> see page 25
Earthing Combination
109
IP55 enclosures
IP55 enclosures
Reversible doors (opening to left or right), equipped with a handle and keylock (key 405).
Height inmm
Basic enclosure
Frame + plain Frame Rear door + transparent door 08322 08323 08324 08325 08326 08327 08329 08332 08333 08334 08335 08336 08337 08339 08312 08313 08314 08315 08316 08317 08319
7 11 15 19 23 27 33
Top and bottom plates for side-by-side combination 08371 08371 08371 08371 08371 08371 08371
Side panels for vertical combination 08352 08353 08354 08355 08356 08357 08359
Frame + transparent door 08332 08333 08334 08335 08336 08337 08339
Type
Rear + plain door 08342 08343 08344 08345 08346 08347 08349
Top and bottom plates 08372 08372 08372 08372 08372 08372 08372
Rear + plain door 08342 08343 08344 08345 08346 08347 08349
Top and bottom plates 08372 08372 08372 08372 08372 08372 08372
Spare parts > see page 117 Dimensions > see page 118
Canopy
Using For enclosure
DB404577
For duct
08386 08387 bb Installed on the mounting uprights or directly on the wall, canopies improve switchboard protection against vertically falling water and objects. bb Colour: RAL 7016. bb Supplied with: vv the hardware required for mounting on the uprights vv the components required for combination with another canopy.
110
IP55 enclosures
Multiple combinations
Combination kits
Catalogue numbers
Horizontal/vertical combination kit 08381 2 double pillars "L" combination kit 08382 1 triple pillar + 1 single pillar Square combination kit 08383 1 quadruple pillar Single pillar Supplied with basic enclosures Mounting upright 08391 L = 1950 mm
Mounting example
Simple In L In square
Dd381434
DB404572
Wall-mounted enclosures
1 Basic enclosure 2 Rear plate for enclosure extension 3 Rear plate for enclosure extension
1 1 basic enclosure 2 1 rear + door for duct 3 1 set of two top and bottom plates for duct 4 1 rear plate for enclosure extension 5 1 set of two side panels
Combination kits
Mounting uprights
Note: for combinations of more than two enclosures, the switchboard must be reinforced using mounting uprights (08391).
Lifting
Lifting rings
Dd381455
08396 Set of two. Supplied with mounting hardware. The lifting rings are secured directly to the switchboard or to the mounting uprights.
Dd381436
1 1 basic enclosure 2 3 rear plates for enclosure extensions 3 1 set of two top and bottom plates for enclosure extensions 4 1 set of two side panels 5 1 square combination kit 08383 6 2 horizontal/vertical combination kits 2 x 08381 7 3 mounting uprights W = 1950 mm (to reinforce the switchboard) 3 x 08391
111
IP55 enclosures
Installation accessories
Mounting supports
Catalogue numbers
Mounting uprights Catalogue numbers Characteristics 08391 bb W = 1950 mm bb Colour: RAL 7016 bb Supplied with: vv two adjustable fixing brackets, vv one joint for combination with a plinth or another upright. Leave space behind the switchboard for cable running and to improve ventilation. For one enclosure, order two uprights. For each enclosure extension or duct, order one additional upright. Plinth gusset 08392 bb H=150mm bb Colour: RAL 7016 Plinth cover panel (for enclosure) 08393 bb L = 600 mm bb Colour: RAL 7016 Plinth cover panel (forduct) 08394 bb L = 300 mm bb Colour: RAL 7016
Quantity to order
For the basic enclosure, order two gussets and one 600 mm wide plinth cover panel. For each enclosure extension or duct, order one additional gusset and the corresponding cover panel.
Mounting example
On uprights
DB404573
On plinth
DB404574
On wall structure
DB404575
Free-standing structure
DB404576
Remarks
4 x 08391 + 4 x 08392 + 2 x 08393 3 mounting uprights 4 uprights + 4 gussets + 2 plinth cover panels for enclosure The uprights are used to The plinth, installed in the factory The switchboard can be mounted The free-standing structure is mount on a wall one or or on-site, raises the switchboard on the structure in the factory or on simply two wall structures more enclosures combined to protect it and facilitate spreading site. combined back-to-back. horizontally or vertically. of cables arriving from a trough. Two wall-fixing brackets supplied The switchboard can be The wall-fixing brackets supplied with the basic enclosure ensure positioned anywhere. with the plinth ensure that the that the switchboard cannot topple It can be fixed to the floor and switchboard cannot topple over. over. moved easily using the lifting rings (08396). It can be equipped with one or more enclosures with Schneider sockets.
08391
3 x 08391 + 3 x 08392 + 08393 + 08394 3 gussets 3 uprights + 3 gussets + 1 plinth cover panel for enclosure + 1 plinth cover panel for enclosure + 1 plinth cover panel for duct + 1 plinth cover panel for duct
Mounting on a pole
2 reinforcement cross-members to support the enclosure
DD381450
08395 The kit is used to mount an enclosure or an enclosure + duct combination, without drilling, to an I-beam or concrete pole that can be rectangular or cylindrical. The maximum circumference of the pole is 580 mm. Supplied with mounting hardware.
112
IP55 enclosures
Enclosures are supplied with metal gland plates installed on the top or bottom panel of the enclosures (2 plates) or 300 mm wide ducts (1 plate). These plates can be replaced by metal plates with cut-outs for special cable entry systems made of an insulating material (plain, with knockouts or membrane-type). They are designed for entry of cables of different cross-sectional areas via the bottom of a switchboard while maintaining the IP55 degree of protection. The gland plates are easy to install using the mounting kit (supplied with each gland plate) that positions and holds the nuts during installation. This makes it possible to mount the gland plates using a single tool.
Catalogue number
08876
Catalogue numbers M12 M12 or M20 M16 or M25 M20 M20 or M32 M25 or M40 Number of entries
08881 -
08891 4 4 4 12
08892 2 2 4
08895 5 8 13
39
Catalogue numbers From 5 to 7 mm cable diameters From 6 to 10 mm cable diameters From 7 to 12 mm cable diameters From 8 to 12 mm cable diameters From 10 to 14 mm cable diameters From 12 to 18 mm cable diameters From 14 to 20 mm cable diameters From 17 to 32 mm cable diameters From 20 to 26 mm cable diameters From 28 to 60 mm cable diameters Number of entries
08872 4 4 12 4 1 25
08896 2 6 8 16 2 1 35
08897 2 2
Spare parts (FL21 gland plate for Pack enclosures) > see page 117 Dimensions > see page 119
113
IP55 enclosures
Type
Plain
DD382674
With cut-outs
DD381438
4 modules (H = 200 mm) for enclosure from 11 to 27 modules 6 modules (H = 300 mm) for enclosure at least 33 modules high Installation Characteristics
08374 08375
08376 08377
bb On a wall-mounted enclosure at least 11 modules high (H = 650 mm). bb The front must be completed with another door (plain or transparent). bb Each enclosure or extension can be equipped with only one partial door. bb Designed for two mounting plates with 22 mm diameter devices or Schneider Electric industrial sockets. bb They are supplied with an insulating plain mounting plate that can be used to: vv blank off a reserve hole, vv install all types of devices (sockets, EPO devices, measurement devices). bb The dimensions of the two holes are 200 mm x 112 mm. bb Hinges that open 170 bb Equipped with a 8 mm male triangle insert (key not supplied).
They can be installed: bb horizontally on the partial doors with cut-outs bb horizontally vertically at any point on a door or side panel.
Type
Plain
DB404552
08861 bb Can be used to: vv blank off partial doors with cut-outs vv mount any type of device (EPO devices, measurement devices, sockets)
08862 bb For installation of eight 22 mm diameter devices (lights, switches, pushbuttons, etc.) bb Supplied with 4 blanking plug
08863 bb With two 65 x 85 mm holes bb Intended for the installation of: vv 10/16 A residential sockets vv flush-mount 16 A LV sockets, inclined or straight, IP44/IP67
08864 bb Intended for the installation of: vv residential sockets (< 10 /16 A) in the 65 x 85 mm hole (1a) vv flush-mount inclined or straight 16 A LV sockets, IP44/ IP67, IK08, in the 65 x 85 mm hole (1b) vv inclined 16 and 32 A IP44 and IP67 sockets in the 90 x 100 mm hole (1)
DD381444
114
DD381443
IP55 enclosures
These panels are designed to replace the standard side panel. They can be mounted on the left or right-hand side.
The cut-outs are designed for the installation of Pratika PK industrial sockets up to 63 A either directly or on 103 x 225 mm adaptation plates of the Kaedra enclosure range. Installation is direct (in 103 x 225 mm cut-outs) for: bb 16/32 A interlocked LV sockets, IP44/IP65, IK08 bb 16 A VLV sockets with safety transformers, IP44/IP65, IK08.
Industrial sockets and functional units Size for industrial sockets Functional units catalogue numbers
bb 16/32 A interlocked LV sockets bb 16 A VLV sockets with safety transformers 103 x 225 mm Direct installation
115
IP55 enclosures
Door accessories
Locks
bb The small plain and transparent doors (7 to 23 modules) are supplied with a small handle comprising a barrel lock no. 405. bb The large plain and transparent doors (27 to 33 modules) are supplied with a large handle comprising a barrel lock no. 405. bb The partial doors are supplied with an 8 mm male triangle insert. bb All doors can receive as optional equipment: vv a large or small handle with a barrel lock no. 405. The latter can be replaced by other barrel locks or special inserts vv a large EURO handle, supplied without a barrel lock vv door inserts (squares, triangles, double bars, screwdriver slots).
Catalogue numbers 08936 Designation Door latch with lock and 2 no.405 keys
08935 08934 Handle (W = 155mm) EURO handle without with lock and a barrel lock (1) 2 no.405 keys
(1) Do not suit to barrels with an automatic return stroke of the key.
Padlocking
Padlocking
Dd380706
08939 The kit can be installed on all IP55 doors, except those equipped with an EURO lock. Kit designed for three padlocks.
These components may equip handles after removing the standard barrel lock no.405.
Dd380706 Dd380706
2 keys 2 keys 2 keys 2 keys Screwdriver Double Male triangle insert Male square insert no.2433A no.455 no.1242E no.3113A slot insert bar insert 7 mm 8 mm 9 mm 6 mm 7 mm 8 mm 3mm (CNOMO) 09933 09945 09942 09943 09931 09932 09937 09934 09939 09949 09947 09948
(1) Others A and E combinations are available from Ronis, please contact us.
Door insert
Type
Dd380705
Dd380705
Dd380705
Dd380705
Catalogue numbers
3 mm double Male triangle insert bar insert 7 mm 8 mm (CNOMO) 09982 09983 09984
9 mm 09985
8 mm 09988
116
Dd380705
These inserts simply replace the standard male triangle insert (8 mm).
IP55 enclosures
Spare-parts
Accessories (IP55)
Dd384507
2 pillars
01025
01247
24 screws M6 x 12 + stubs contact 4 simple fixing brackets 4 screws pillar/seating 12 nylon washers 12 self threading screws 4 conical washers 4 screws M8 x 16 Set of spare parts for door 01248
Dd384508
1 screw M6 x 12 + stub washers 2 keys no.405 1 spring nut 4 screws frame/pillar 3 hinge pins 8 o-ring joints 3 stop rings Spare parts for closing system 01249
Dd384510
1 stop washer 1 screw body 1 screw cap 1 o-ring 1 screw nut 1 composite seal 1 captive screw 1 special washer 1 cam 1 washer
Front-plate accessories
DD384501
01093
DD384502
01094
117
IP55 enclosures
Dimensions
Wall-mounted enclosures
Dd381726 Dd381729
Ducts
No. of vertical modules H1
425 625 825 1025 1225 1425 1725
Doors
A
375 575 775 975 1175 1375 1675
B
525 725 925 1125 1325 1525 1825
7 11 15 19 23 27 33
Dd381727 Dd381730
Dd381728
Dd381735
Dd381734
Surface utile
Dd381731
(1) Multifix rail. (2) Recessed slotted mounting plate. (3) Transparent door. (4) Plain door. (5) Front plate. (6) Door.
7 11 15 19 23 27 33
C
420 620 820 1020 1220 1420 1720
E
284 484 684 884 1084 1284 1584
H
450 650 850 1050 1250 1450 1750
Dd381732
Enclosure combinations
Dd381738 Dd381742
Canopy
118
Dd381742
Dd381737
IP55 enclosures
Dimensions
Gland plates
Dd381733
7 modules
(1) Cat. no. 08376 for wall-mounted enclosures from 11 to 27 modules (2) Cat. no. 08377 for wall-mounted enclosures at least 33 modules
From 11 to 33 modules
Cat. no 08863
Cat. no 08864
Cat. no 08862
Cat. no 08861
Wall structure
Dd381741 Dd381740 Dd381739
119
Pack enclosures
Pack enclosures
Contents
Presentation................................................................................123 Pack wall-mounted and flush-mounted enclosures......................124 Kilowatt hour meters....................................................................125 Accessories.................................................................................126 Distribution Insulated busbars........................................................................128
Power supply of rows from the incoming device Power supply of rows from the incoming device Power supply of a modular devices row
121
Pack enclosures
Pack enclosures
Presentation
Metallic indoor enclosures, supplied mounted, can be ordered with a single catalogue number. An enclosure + modular rails + front plates + blanking plates + a plastic gland plate + an earth bar + a template for drilling wall-mounted holes.
PD391279
Gland plate
Accessibility
bb Double rail supplied premounted in the 4-, 5- and 6-row enclosures allowing mixing of devices of different depths
PD390161
Main characteristics
Steel sheet metal with electrophoresis treatment + hot-polymerised polyester epoxy powder. Enclosure: bb width: 555 mm, bb height: 480 to 1080 mm, bb depth: 157 mm without door / 186 mm with door.
Description
Pack enclosures
Rated operational current Colour Standards conformity Degree of protection Degree of protection against mechanical impacts Isolation Doors 160 A - Icc = 50 kA White colour RAL 9001 EN 62208, IEC 61439-2, NFC 61-910 IP30 with or without door IK08 with door IK07 without door Class 1 bb Plain or transparent, opening to right or left bb By design, electrical continuity of moving parts (hinges) bb Supplied with a handle and keylock (key 405) bb No possibility to install push buttons (distance behind door = 42 mm) The Pack enclosures can be built-in easily using its flush mounting kit
Mounting
The design of Pack enclosures ensures easy device access and mounting. Optimised depth and an extra-thin door ensure perfect integration in all environments. Models with 4, 5 and 6 rows are particularly well-suited for the incomer function: bb more space available for wiring of the incoming device bb optimised number of front plates. 123
Pack enclosures
DD383298
DD383985
2 3 4 5 6
9 12 15 18 21
Height Width Depth 480 555 157 without door 630 175 with 780 door + 11 930 for handle 1080
DD383982
Enclosure extension
Meters can be installed at different levels on the functional uprights of enclosures. Class 1: Depending on preferences and needs, meters can be installed directly on mounting plates equipped with earthing braids and combined with partitioning or front plates. The mounting plates can be raised using M5 spacers. Doors are: bb reversible, opening to left or right, bb supplied with a handle and barrel with keylock (key 405), bb barrel locks and inserts > see page 100
Dimensions (mm)
Enclosure
DD382404
Door
DD382405 DD382406
9 12
Width 555
08012 08013
124
Pack enclosures
Kilowatt-hour meters
Class 1: Depending on preferences and needs, meters can be installed directly on mounting plates (without insulating plate) equipped with earthing braids of 6mm2 (08910) and combined with partitioning or front plates. The mounting plates can be raised using M5 spacers > see page 58
Installation
In an enclosure extension
DD383982 DD383981
Device Nb. of devices per row Nb. of vertical modules Mounting plate Insulating plate Horizontal partitioning (1) Front plate transparent plain Enclosure Door Earthing wire 6 mm2 Combination uprights (set of 2)
Single-phase meters 3 6 03157 03154 04333 03343 or 03806 Pack enclosure Depending on enclosure 08911 -
3-phase meters 2 9 03152 03154 04333 03344 or 03807 Pack enclosure Depending on enclosure 08911 -
Single-phase meters 3 6 03157 03154 03343 or 03806 08012 08092 (transparent) or 08082 (plain) 08911 08817 (2)
3-phase meters 2 9 03152 03154 03344 or 03807 08013 08093 (transparent) or 08083 (plain) 08911 08817 (2)
(1) If not installed at the top of a Pack enclosure, order an addition horizontal partition (04333). (2) To make the combination more rigid, particularly during transport, it is mandatory to use a set of combination uprights secured to the rear of the switchboard.
125
Pack enclosures
Accessories
Gland plates
Gland plates
DD383989 DD383990
Trunking spreader
Trunking spreader
DD383991
Catalogue number
08821
Canopy
Canopy for IP31
DD383933
08823 The canopy cannot be mounted on the existing top plate. It therefore comes with a special top plate that must be mounted in place of the existing top plate. The existing top plate is remounted at the bottom of the enclosure to allow cable entry and exit via the bottom. The addition of a canopy over a wall-mounted or floor-standing enclosure equipped with a door ensures compliance with the degree of protection IP31.
Gasket
Gasket for IP43
DD381268
08841 When the switchboard is equipped with a canopy, a gasket for the doors ensures compliance with the degree of protection IP43. L = 5.3 m
126
Pack enclosures
Accessories
Combination uprights
Combination uprights
DD383984
08817 Set of 2 uprights. Particularly during transport, it is mandatory to use a set of combination uprights secured to the rear of the switchboard, to make the combination more rigid.
Wall mounting
Wall mounting
DD384071
Flush-mounting kit
Flush-mount kit
DD381256
Catalogue number
08822
Blanking plates
Blanking plates
DD384029
127
Pack enclosures
Distribution
Insulated busbars
PD390545_SE
bb Compact busbars, fully insulated(IPxxB), ready for installation (supplied with supports and clip-on covers) bb Copper bars: vv channelled ETPH12, vv threaded M6 holes every 25 mm, vv can be cut every 150 mm (125 A) or 200 mm (160 A). bb Mounted on insulated bases. bb Delivered with supports that screw to the functional upwrights of enclosures. bb Large choice of prefabricated and tested connections. bb Clip-on covers protect against direct contact. Can be easily cut for the connections to the devices. bb Ends are protected by shutters.
125 A
DD382673
160 A
DD381380
Powerclip busbars
3P
4P
Spare parts*
Electrical characteristics
Rating
125 A 160 A
8,5 10
160 A 200 A
128
Pack enclosures
Distribution
Insulated busbars
Catalogue numbers
04145
DD381379
04146 04147
DD383294
One piece connection, 3/4P, 160 A, W = 150 mm Fast connection to busbars Equipped with male fittings one end for tunnel terminals Respects the degree of protection IPxxB Neutral is clearly indicated (blue)
DD383276
NSA160, INS160, 04148 NG160 (located on left-hand side), Vigi NG160 (located in the middle), NG125, C120, iC120
DD383295
12 tap-off blocks with 6 mm and 10 mm terminals Respects the degree of protection IPxxB 12 tap-off blocks with 16 mm terminals Respects the degree of protection IPxxB
All device equipped with tunnel terminals Multiclip 160 A All device equipped with tunnel terminals Multiclip 160 A
DD383498
04151 04152
Accessories
Description
8 IPxxB covers Set of 8 clip-on covers that can be cut as needed Maintain IPxxB with 90 angle lugs and/or cable sizes from 10 to 25 mm Set of 20 CHC M6 x 12 mm
DD381385
Catalogue numbers
04150
04158
129
Pack enclosures
Distribution
Distribution blocks
DD381200
DD382981
04031 Installation on a raised modular rail Other characteristics > see page 75
04149 Two 45 mm end fittings for tunnel terminals For the connection of: INS40/160, NG125, NG160, C120, iC120 with or without Vigi
DD383301
04040
04041
04045 04047 bb Installation on a modular rail bb Width: 6 modules of 18 mm bb Connections L = 210 mm for NG125, INS40/125, C120, iC120
04046 Supplied bb Installation on a modular rail bb Width: 6 modules of 18 mm bb Connection for NG160, INS100/160 with or without Vigi
Supplied Supplied bb Installation on a raised modular rail bb Width: 4 modules de 18 mm Other characteristics > see page 77
100 A 125 A 40 A 13506 13507 13508 13516 2 x 7 holes 2 x 13 holes 4 x 13 holes Other characteristics > see page 78
130
Pack enclosures
Distribution
Comb busbars
DD382981
Lateral bracket
Tooth-caps
Insulated connectors
Two-pole Four-pole
Supplied accessories
2 tooth-caps
Lateral bracket
Tooth-caps
Insulated connectors
Catalogue numbers
Characteristics
Supplied accessories
14881 14882 14883 14884 b Set of 1 b 24 modules of 9 mm b 12 modules of 18 mm Rating: 80 A with 1 feeding point 100 A with 2 feeding points 2 lateral bracket
Supplied accessories
63 A 04008 b 4P b 24 x 9 mm modules, 12 x 18 mm modules b Upstream connection: tunnel terminals for cables up to 25 mm b Downstream connection spring terminals: v 4 for each phase (2 x 4 mm2 + 2 x 6 mm2) v 8 for the neutral (4 x 4 mm2 + 4 x 6 mm2) Clipped onto the rear of modular rail or screwed. Bared copper connections (L=100 mm) 10 of 4 mm2 + 6 of 6 mm2
80 A 04000 b 4P b 48 x 9 mm modules, 24 x 18 mm modules b Upstream connection: tunnel terminals for cables up to 25 mm b Downstream connection spring terminals: v 6 for each phase (6 mm2) v 18 for the neutral (6 mm2)
131
Pack enclosures
Accessories
Cable running
DD381819
Cable-tie supports
Cable-tie supports
DD381820
12 horizontal cable straps 4 covers for horizontal cable straps, W = 430 mm 4 horizontal sections, 60 x 30 mm, W = 450 mm + supports 12 horizontal trunking supports 2 fixing brackets, H = 15 mm (for vertical trunking)
Cable straps
04239 04243
Cat. no.
Catalogue number Characteristics 08867 Set of 2 Supplied with hardware for mounting on the functional uprights of the enclosure
Trunking
Cat. no.
Bare earth bar Catalogue numbers Characteristics 04201 bb Size: 12 x 3 mm bb Connection space: 330 mm Equipped with a 35 mm tunnel terminal bb Can receive earth blocks with spring terminals
Earth blocks with spring terminals to clip 04214 04215 bb 12 x 4 mm2 bb Set of 4 bb Length: 75 mm bb 3 x 16 mm2 bb Set of 4 bb Length: 37 mm
04206 H = 15 mm Set of 2 brackets Vertically on two fixing brackets secured to a functional upright. Earth bar with clamps or spring terminals
Earthing braid
Earthing braid, 6 mm
DD384005
The earthing braid is used to earth a door or wicket door with devices.
2
08910 The braid is equipped with a 4 mm diameter lug at one end and a 6 mm diameter lug on the other
DD381338
08911 Equipped with a 5 mm diameter lug at one end and a 6 mm diameter lug on the other
DD384052
132
Pack enclosures
Spare-parts
Front-plate (IP30)
DD384498
01264
DD384499
01265
Modular rail
DD384506
Pack modular device rail 1 DIN rail 432 mm lenght 2 fixing brackets 2 self threading screws M5 x 10
01260
01020
Front-plate accessories
DD384501
01093
DD384502
01094
133
Pack enclosures
Dimensions
2 3
Nb. of rows
480 630
4 5 6
Nb. of rows
Door
DD383988 DD381953 DD381956
134
Pack enclosures
Dimensions
Gland plates
DD381954
Trunking spreader
DD382916
Wall-mounted
DD381955 DD380509
2 3 4 5 6
Nb. of rows
H1
H2
135
Additional information
Additional information
Contents
Electrical characteristics.........................................138
Designing Prisma Plus power circuits..........................................138
Presentation and approach................................................................................ 138
Practical information................................................145
Connection of power cables.........................................................145
Thermal characteristics..........................................159
Thermal management of switchboards........................................159
General.............................................................................................................. 159 Comparative method......................................................................................... 161 Example............................................................................................................. 163 Charts................................................................................................................ 164 Ventilation.......................................................................................................... 165 Heating.............................................................................................................. 166
Practical information................................................167
Tools required for mounting and connection................................167
137
Additional information
Electrical characteristics
The Prisma Plus system takes into account the installation and connection conditions of Schneider Electric devices. The entire installation complies with standard IEC61439-1 and 2. The result is a type tested switchboard.
PD390311
Busbar sizing
The factors that must be taken into account in determining the size of busbars include: bb the diversity factor. Not all the loads supplied by a set of busbars are used at full rated load or at the same time. The diversity factor is the means to determine the maximum load current used to size the busbars. Standard IEC 61439-1 and 2 4.7 specifies the table below: Number of circuits
2 and 3 4 and 5 6 and 9 10 and more
bb the degree of protection IP. bb the ambient temperature around the switchboard.
Flexible copper bars with an insulating cover. To determine the required sizes for flexible bars, see the tables starting on > see page139 which indicate the correct size for each type of connected device. bb an insulated flexible bar (not connected) must meet standards IEC 60243-1, (dielectric, > see page139), NFC 32201 (insulation) and IEC 60332-1 (fire) bb a flexible bar connected to a device in an enclosure must comply with standard IEC61439-1 and 2. Cables To determine the cables required, see the tables. on > see page142. They can be used to determine: bb the size of cables as a function of: vv the circuit breaker rating vv the current vv the ambient temperature around the switchboard bb the permissible current for individually tied cables or touching cables as a function of: vv the size of the cables vv the degree of protection for the switchboard.
Rapsody software
> see page 25
138
Additional information
Electrical characteristics
bb better insulation temperature withstand (125 C for bars, 105 C for cables) and a larger exchange surface for an equivalent size, i.e. a smaller size for a given current bb greater rigidity offering better electrodynamic characteristics for short-circuit currents bb no intermediate parts (lugs) for a direct connection between the device and the busbars therefore less temperature rise and less risk of error bb fast implementation of prefabricated connections already cut to length, formed and drilled.
Technical characteristics bb thickness of the insulation: variable depending on the bar size, 2 mm on average bb rated insulation level Ui = 1000 V bb impulse withstand voltage Uimp = 12 kV bb maximum withstand temperature of insulating material = 125 C.
Connection
In all enclosures with IP y 55 bb the switchboard internal temperature is 60 C bb the withstand temperature of the insulating material is 125 C. If the withstand temperature of the insulation is only 105 C, use the next largest flexible bar. The bar sizes (S) indicated below take into account the derating curves of devices.
(1) The values for circuit breakers apply to contactors with the same ratings.
Note: the values indicated above have been validated for Prisma Plus switchboards.
139
Additional information
Electrical characteristics
Devices IP y 55
NSX100 TMD-TMG NSX125 TMD-TMG NSX160 (1) TMD-TMG NSX250 (1) TMD-TMG NSX100 STR NSX160 STR NSX250 (2) STR Size per phase Inc (A) Size per phase Inc (A) Size per phase Inc (A) Size per phase Inc (A) Size per phase Inc (A) Size per phase Inc (A) Size per phase Inc (A)
Rated current of a circuit Inc (A) Ambient temperature around the switchboard
25 C 30 C 35 C
(1) For a withdrawable NSX160 or NSX250 equipped with a Vigi or an insulation-monitoring module, multiply the In values by 0.9. (2) For a withdrawable NS250 equipped with a Vigi or an insulation-monitoring module, multiply the In values by 0.86.
40 C
45 C
50 C
Note: the values indicated above have been validated for Prisma Plus switchboards.
140
Additional information
Electrical characteristics
Determining the permissible current of NSX100 to NSX630 connection and power supply blocks as a function of the ambient temperature around the switchboard and their IP degree of protection. Device Rated current of a circuit Inc (A)
Ambient temperature around the switchboard 25 C 30 C 35 C 40 C 45 C 50 C IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 95 100 92 100 90 97 87 95 85 92 bb
Incoming connection block Power supply block Incoming connection block Power supply block Incoming connection block Power supply block Incoming connection block Power supply block Incoming connection block Power supply block Incoming connection block Power supply block Incoming connection block Power supply block Incoming connection block Power supply block
via the top via the bottom via the top via the bottom via the top via the bottom via the top via the bottom via the top via the bottom via the top via the bottom
04066 100 04067 04060 04066 100 04067 04060 04066 160 04067 04060 04066 160 04067 04060 04066 238 04067 04060 04066 250 04067 04060 04076 400 04070 04076 570 04071
100
100
97
100
95
100
92
100
90
97
bb
152
160
147
160
144
156
140
152
136
147
bb
160
160
156
160
152
160
147
160
144
156
bb
213
231
207
225
200
219
193
213
185
207
bb
219
245
213
238
207
225
200
219
193
213
bb
360
390
350
380
340
370
330
360
320
350
bb
520
555
505
540
490
525
470
510
450
495
bb
The indicated performance characteristics are valid for: bb Compact NSX100/160/250/400 circuit breakers used as incoming or outgoing devices bb Compact NSX630 circuit breakers used as incoming device.
Note: the values indicated above have been validated for Prisma Plus switchboards.
141
Additional information
Electrical characteristics
NSX100
25
NSX160
50
NSX250
95
Note: Schneider Electric recommends connecting NSX400/630 circuit breakers with insulated flexible bars or rigid bars.
Note: the values indicated above have been validated for Prisma Plus switchboards.
142
Additional information
Electrical characteristics
Maximum size of lugs for connection to the different incoming connection blocks.
Narrow bimetal lugs
Incoming connection block for NSX-INS250 supplied via the top or bottom, cat. no. 04066 and 04067 In-duct incoming connection block for NSX630, cat. no. 04076
150 mm 240 mm
240 mm 300 mm
185 mm 300 mm
143
Additional information
Electrical characteristics
144
Additional information
Practical information
bb To ensure protection of persons, first connect the switchboard protective conductor to the earth electrode. bb Tie the cables as close as possible to the connections to avoid any mechanical stresses on the device terminals. When not using cable glands, also attach the cables near to the cubicle entry point. bb Cables must never be in contact with or passed between live conductors. bb Sharp edges of the framework must be protected where cables pass to avoid damaging the conductors. bb Comply with a minimum radius of curvature of 6 to 8 times the cable outside diameter. bb All power connections must be made with class 8.8 mounting hardware and elastic contact washers, tightened to the torque indicated in the table below. bb When connecting aluminium cables to copper terminals, use bimetal lugs or interfaces. bb Separate the different types of circuits into separate cable bundles (power, control, 48 V, 24 V, DC, AC, etc).
Cable bundles
Cable cross-sectional area (mm ) CSA y 10 16 < CSA y 50 CSA u 50 Max. number of cables per bundle 8 4 Tie individually
For cable sizes of 50 mm or more, use 9 mm wide fixing ties. Recommended tightening torque for mechanical and electrical connections with 8.8 class screws.
Diameter of screw M3 M4 M5 M6 M8 M10 M12 Tightening torque (Nm) (with nut + contact washer) 1.5 3.5 7 13 28 50 75
145
Additional information
Standards
Standards
What is a standard?
A common reference
"A standard helps to define a common language between economic stakeholders (producers, users and consumers), to clarify and harmonize practices and to define the levels of quality, safety, compatibility, and least environmental impact of products, services and practices. Standards facilitate trade, both national and international, and help to better structure the economy and facilitate the everyday life of everyone."
Afnor definition
The IEC (International Electrotechnical Commission) is a worldwide organisation for standardisation comprising all national electrotechnical committees (IEC National Committees). The object of the IEC is to promote international cooperation on all questions concerning standardisation in the electrical and electronic fields. To that end, the IEC publishes International Standards. Their preparation is entrusted to technical committees and any IEC National Committee interested in the subject dealt with may participate in the preparatory work.
National standards
In Europe The IEC documents are first studied by CENELEC, which establishes: bb either a European standard (EN), often identical to the IEC standard, which then becomes the applicable national standard in all the member countries bb or, in the event of differences, a harmonisation document (HD). Other IEC member countries Each country is autonomous and can accept the IEC standard as the national standard, with or without modifications. Even though they are IEC members, countries such as Japan and the United States continue to develop their own standardisation systems. Countries without a standardisation system It is possible to refer to an IEC standard in the framework of a project.
DD383972
Worldwide
Countries
CEI / IEC Commission Electrotechnique Internationale CENELEC Comit Europen de Normalisation ELECtrotechnique UTE Union Technique de llectricit VDE Verband der Elektrotechnik, Elektronik und Informationstechnik e.v. (German electrotechnical, electronics and computer technology standardisation organisation) BSI British Standards Institution
146
Additional information
Standards
Standards
Management standards
ISO 9004: Quality-management systems - guidelines for performance improvements. Used in setting up a quality-management system. ISO 9001: Quality management systems - requirements. Used for certification audits.
ISO 14004: Environmental-management systems. General guidelines on the principles, systems and supporting techniques. ISO 14001: Environmental-management systems. Specification with guidance for use. The majority of Schneider Electric development centres and factories are certified ISO 9001 and ISO 14001.
DD381777
The set of IEC 60364 standards defines the main principles and rules for the design and the mounting of the electrical installation: bb determining general characteristics of installations bb protection bb selection and installation of equipment bb verification and maintenance of installations.
Switchgears standards
They apply to devices or assemblies and are aimed at ensuring correct operation and safety of the concerned products: bb standards on low-voltage switchgear and controlgear: vv IEC 60947-1: general rules vv IEC 60947-2: circuit breakers vv IEC 60947-3: switches and disconnectors vv IEC 60947-4: contactors vv IEC 62208: empty enclosures. bb The IEC 61439 switchboard standard The IEC 61439 standard: vv characterizes the electrical switchboard and specifies the design, construction and verification rules vv describes in detail all low-voltage switchgear and controlgear: definitions, technical characteristics, conditions of use, and construction and verification requirements vv applies to power switchgear and controlgear assemblies (PSC assemblies) whose rated voltage does not exceed 1000 V in alternating current or 1500 V in direct current. Regulations in a given country may make certain standards legally binding and may also create additional safety requirements. In addition to providing proof of the conformity of its quality-management system, a product manufacturer can demonstrate the quality of products by providing proof that the design and manufacture comply with the requirements in the applicable standard. Proof of conformity may be a declaration by the manufacturer or a certificate supplied by an independent organisation.
147
Additional information
Standards
Standards
Enclosure standards
Standard IEC 62208 lay down definitions, classifications, characteristics and test requirements for enclosures used for switchgear and controlgear assemblies. They apply to empty enclosures before installation of the devices by the panelbuilder, as supplied by the manufacturer. They apply to one-piece enclosures and to enclosures supplied in kit form.
e marking
e marking is a regulatory symbol attributed under the sole responsibility of the manufacturer and intended for the verification authorities of the European countries that enforce the European regulations. It allows free circulation of a product in the European Union and certifies that it complies with the basic requirements in all the applicable European directives. e marking is not a quality symbol and does not indicate conformity with a standard The e declaration is intended exclusively for the authorities in charge of verifying compliance with the applicable regulations and it is drafted, signed and held for presentation to the authorities by the manufacturer. For the Prisma Plus range, the declaration is the responsibility of the Schneider Electric unit that has designed and developed the product. For LV switchboards, the declaration is the responsibility of the panelbuilder. The following products receive e marking: bb all products that are liable to endanger the safety of persons, animals and property (LV directive) bb all products likely to emit electromagnetic disturbances above a standardised threshold or to be disturbed during operation (EMC directive). Consequences: bb the Prisma Plus range falls under the LV directive only bb LV switchboards are covered by the LV directive and may also fall under the EMC directive, depending on the type of devices incorporated. For the Prisma Plus range, e marking is applied: bb on the packing of "mechanical" components bb on the product itself for "electrical" components. For the LV assemblies created by the panelbuilder, e marking is applied: bb on the packing bb on the rating plate (if applicable) bb on one of the documents accompanying the switchboard when it is shipped.
e
148
Additional information
Standards
Standards
Degree of protection
Standard IEC 60364-5-51 lists and codifies a large number of external influences to which electrical installations can be subjected, including the presence of water, solid objects, shocks, vibrations, corrosive substances, etc.
IP code
Standard IEC 60529 (IP code, February 2001) indicates the degrees of protection provided by an enclosure for electrical devices against access to hazardous parts, against penetration of solid foreign objects and against penetration of water. These standards do not apply for the protection against the risks of explosion or conditions such a humidity, corrosive vapour, fungus or vermin. The IP code is made up of two characteristic numerals and can include an additional letter when the actual protection for persons against access to the hazardous parts is better than that indicated by the first numeral. The first numeral characterises the protection provided against the ingress of solid foreign objects and the protection of persons. The second numeral characterises the protection provided against the ingress of water with harmful effects.
DD381959
DD381960
DD381963
DD381961
DD381961
DD381962
DD381962
DD381962
DD381964
DD381962
DD381965
DD381973
DD381972
DD381971
Dust tight
DD381970
DD381969
DD381968
DD381967
DD381966
149
Additional information
Standards
Standards
Additional letter
The additional letter is used only if the actual protection of persons is higher than that indicated by the first characteristic numeral of the IP code. Additional letter
A B C D
Protection
A Protected against access with back of hand B Protected against access with a 12 mm diameter finger C Protected against access with a 2.5 mm diameter tool D Protected against access with a 1 mm diameter wire
If only the protection of persons is of interest, the two characteristic numerals are replaced by the letter "X", e.g. IPXXB.
IP30D
Remarks bb The degree of protection IP must always be read and understood numeral by numeral and not as a whole. For example, an IP31 wall-mount enclosure is suitable for an environment that requires a minimum degree of protection IP21. However an IP30 wall-mount enclosure is not suitable. bb the degrees of protection indicated in this catalogue are valid for the enclosures as presented. However, the indicated degree of protection is guaranteed only when installation and device mounting are carried out in accordance with professional standards that conserve the initial degree of protection.
IK code
IK code
01 02 03 04 05 06 07 08 09 10
Standard IEC 62262 defines an IK code characterising the capacity of products to resist mechanical impacts from all sides. Impact energy (joules)
0.14 0.2 0.35 0.5 0.7 1 2 5 10 20
IK codes can be selected according to the risks of impacts on a given site. Site
No risk of major impact Significant risk of impact that can damage devices Maximum risk of impact that can damage the switchboard Technical premises Hallways Workshops
Recommended IK
07 08 (switchboard with door) 10
150
Additional information
Enclosure characteristics
1 Opposite the relevant premises, read the recommended IP and IK values. 2 The b symbol indicates the enclosure or cubicle satisfying the criteria of the UTE guide. Any enclosure or cubicle with a higher degree of protection can also be used. 3 If several degrees of protection are possible (refer to the standard for more details) and the v and b symbols are indicated (e.g. 24v/25b), enclosures that correspond to the higher degree of protection (b) are suitable for the lower degree of protection (v). Example: Selection of an enclosure for a laundry room. Minimum degree of protection: IP21/IK02 A wall-mounted enclosure with a door (plain or transparent), a canopy and a gasket offer IP43/IK08 degrees of protection and are therefore suitable for this application. Type of premises Enclosures
Wall-mounted enclosure Floor-standing enclosure Min. IP/IK required IP IK Domestic or comparable premises or locations 24 07 Porch Bathrooms (see washrooms) Bicycles, motorcycles, tricycles, etc. (premises for) Water, sewer and heating connections Laundries Cellars, garages, furnace rooms Bedrooms Trash rooms Halls in cellars Courtyards Kitchens Shower rooms (see washrooms) Indoor stairways and alleys Outdoor stairways and outdoor alleys without roofs Outdoor alleys with roofs Attics (roof space) Garden shelters Latrines Dustbin rooms Ironing room Access ramps to garages N/A 20 24 21 20 24/25 20 25 20 25 02/07 07 02 02 02/07 02 02/07 02 07 bb bb bb bb bb bb bb bb 20 23 21 20 20 25 20 24/25 20 07 02 02 02/07 02 07 07 02/07 02 bb bb bb bb bb bb bb bb without door with door with door + canopy with door + canopy + gasket with door + canopy+ gasket IP43/IK08 IP55
IP55/IK10
bb
151
Additional information
Enclosure characteristics
Type of premises
Enclosures
Wall-mounted enclosure Floor-standing enclosure Min. IP/IK required IP IK 27 02 24 23 21 20 21 21 20 20 23 02 02 02 02 02 02 02 02 07 08 07 07 07 07 02 08 07 02 02 02 07 07 02/07 07 07 07 07 02 08 08 07 07 07 02 02 02 08 07 02 07 bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb b bb bb bb bb bb bb bb bb bb bb bb bb bb bb without door with door with door + canopy with door + canopy + gasket with door + canopy + gasket IP43/IK08 IP55
IP55/IK10
bb
Lounges, living rooms, etc Drying rooms Covered terraces WCs Verandas Crawl spaces
Commercial premises and adjoining areas Gunsmiths (storage area, workshop) 30 Laundries (wash room) Butchers shop cold room: y -10 C Bakers, cake shops (kitchens) Coffee roasters Coal, wood, oil Delicatessen (production) Sweets (production) Shoe repair shops Dairies Hardware stores (storage areas for chemicals and paint) Wood workers Art galleries Florists Furriers Fruit and vegetable merchants Grain shops Bookshops, stationers Motorcycle and bicycle repairs and accessories Messenger services Furniture shops (antiques, secondhand) Glass and mirror merchants (workshop) Wallpaper shop (storage area) Cosmetics shop (storage area) Chemists (storage area) Photographers (dark room) Plumbers (storage area) Fishmongers Dry cleaners Hardware stores (without paint, chemicals, etc.) Locksmiths Vintners, spirits Interior decorator (carding) Tailors, clothing retailers (storage area) Pet care N/A 24 24 23 50 21 20 24 20 20 24 33 50 20 24 20 24 50 20 20 20 20 20 20 20 20 23 20 25 23 20 20 20 50 20 35
07v/08b vv 07 07 02 07 bb
152
Additional information
Enclosure characteristics
Type of premises
Enclosures
Wall-mounted enclosure without door with door with door + canopy with door + canopy + IP55 gasket with door + canopy + gasket IP43/IK08 IP55/IK10
Floor-standing enclosure without door Min. IP/IK required IP IK Buildings open to the general public Shared premises of storage rooms buildings open to the packing rooms general public archive rooms film and magnetic media storage linen rooms laundry rooms misc. shops kitchens (large) J L Reception old and handicapped people Lecture halls, halls meeting rooms, stage areas auditoriums, scenery storage halls used for several purposes rooms costume rooms Retail premises, sales premises shopping malls areas for storage and handling of packing Restaurants and cafes Hotels and boarding houses Dance halls and gaming parlours Teaching classrooms establishments, dormitories holiday camps Libraries and documentation centres Exhibitions halls and rooms areas for reception of equipment and merchandise U Healthcare establishments bedrooms incineration operating rooms centralised sterilisation 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 21 20 24 02 02/07 08 08 07 08 08 08 02 07 02 08 02 02 07 02 07/08 07 02/07 bb bb bb bb bb bb bb bb bb bb bb 20 20 20 20 20 24 21 08 08 02 02 02 07 07/08 bb bb bb IP30/IK07
bb bb
bb bb
bb bb
bb bb bb
N O P R S T
bb
bb bb vv bb bb bb bb bb vv bb bb bb vv bb bb
pharmacies and labs 21v/23b 02v/07b with more than 10 l of inflammable liquids V W X Places of worship Administrative premises, banks Indoor sports facilities Museums Covered open air facilities halls 20 20 20 02 02 08 02 08 08 08v/10b
07v/08b vv
Y PA
23v/25b 08v/10b
153
Additional information
Enclosure characteristics
Type of premises
Enclosures
Wall-mounted enclosure Floor-standing enclosure Min. IP/IK required IP IK without door with door with door + canopy with door + canopy + gasket with door + canopy + gasket IP43/IK08 IP55
IP55/IK10
Technical premises Battery rooms Lifts (machine rooms and pulley rooms) Electrical rooms Control rooms Workshops Laboratories Air conditioning washers Garages (used exclusively for parking vehicles) of an area not exceeding 100 m2 Machine rooms Water pressurisers Boiler rooms coal fuel other fuel electrical Fuel storage areas Cinder tips Pump rooms Pressure reduction rooms (gas) Steam or hot water facilities Expansion vessel rooms Parking lots Carwash areas (inside premises) Petrol stations Lubrication areas Battery recharging areas Workshops Offices Libraries Archives Computer rooms Design offices Rooms containing reprographic machines Sorting rooms Refectories in restaurants or canteens Large kitchens Sports rooms Barracks Meeting rooms Waiting rooms, lounges, halls Medical consulting rooms, not fitted with specific equipment inside outside coal oil liquefied gas
23 20 20 20
02/07 07v/08b vv 07 02 bb bb vv vv bb bb bb
bb
bb bb bb
bb vv bb bb vv bb bb bb vv bb vv bb vv bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb
Boiler houses and adjoining premises (power in excess of 70 kW) 51v/61b 07v/08b 21 21 20 20 50 20 21 21 25 21 23 23 21 20 20 20 20 20 20 20 21 07/08 07/08 07v/08b vv 07v/08b vv 08 07v/08b vv 02 07v/10b 07 07 08 07 08 02 02 02 02 02 02 07 07
50v/60b 08
20 20 20 20 20
07v/08b vv 07 02 02 02 02/07 bb bb bb bb bb
bb
154
Additional information
Enclosure characteristics
Type of premises
Enclosures
Wall-mounted enclosure Floor-standing enclosure Min. IP/IK required IP IK without door with door with door + canopy with door + canopy + IP55 gasket with door + canopy + gasket IP43/IK08 IP55/IK10
Farm premises or locations Alcohol (storage) Closed cattle sheds Laundries Wood storage rooms Threshing floors Distilling cellars Vat rooms (wine) Courtyards Poultry barns Stables Fertiliser (storage) Stables Manure heaps Haylofts Haystacks, forage (storage) Granaries, barns Straw (storage) Greenhouses Grain silos Milking rooms Pig sties Chicken houses Miscellaneous installations Fair facilities Water treatment facilities
23 35 24 30 50 23 23 35 35 35 50 35 24 50 50 50 50 23 50 35 35 35 33 24/25
07 07 07 10 07 07 07 07 07 07 07 07 07 07 07 07 07 07 07 07 07 07 08 07/08
bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb
Thermodynamic installations, air-conditioned rooms and cold rooms 25 07 Height above from 0 to 1.10 m ground 24 07 from 1.10 to 2 m above 2 m under evaporator or water drain pipe ceiling and up to 10cm underneath Temperature y -10 C Compressor room 21 23 23 21 07 07 07 08 08
N/A
155
Additional information
Enclosure characteristics
Type of premises
Enclosures
Wall-mounted enclosure Floor-standing enclosure Min. IP/IK required IP IK without door with door with door + canopy with door + canopy + gasket with door + canopy + gasket IP43/IK08 IP55
IP55/IK10
Industrial facilities Slaughter houses Batteries (manufacture) Acid (manufacture and storage) Alcohol (manufacture and storage) Aluminium (manufacture and storage) Livestock (raising, fattening and sale) Asphalt and bitumen storage Wool beating and carding Industrial laundry Wood (processing) Meat packers Bakeries Breweries Brickworks Rubber (production and processing) Carbide (manufacture and storage) Ammunition factories Carton board (production) Quarries Celluloid (manufacture of objects) Cellulose (manufacture) Coal (depots) Pork products Boiler-making works Lime kilns Rag (storage) Chlorine (manufacture and storage) Chrome-plating Cement works Coking plant Adhesives (production) Bottling lines Liquid fuels (storage) Fats (processing) Leather (tanning and storage) Copper (ore processing) Paint stripping Detergents (manufacture) Distilleries Electrolysis Ink manufacturing Fertilisers (manufacture and storage) Explosives (manufacture and storage) Iron (production and processing) Spinning mills Furriers (beating process) Cheese factories Gas (production and storage) Tar (processing) Seed production Metal engraving Oils (extraction) Petroleum products (manufacture) Printworks
08 07 07 07 08 07 07 08 07 08 07 07 07 08 07 07 08 07 08 08 08 08 07 08 08 07 07 07 08 08 07 08 08 07 08 08 08 07 07 08 07 07 08 08 07 07 07 08 05 07 07 07 08 08
bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb vv bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb vv bb
156
Additional information
Enclosure characteristics
Type of premises
Enclosures
Wall-mounted enclosure Floor-standing enclosure without door with door with door + canopy with door + canopy + gasket with door + canopy + gasket IP43/IK08 IP55
Min. IP/IK required IP IK Industrial establishments (continued) Dairies 25 07 Public wash-houses Liqueurs (production) Halogenated liquids (use) Inflammable products (storage and workshops where they are used) 25 21 21 21 07 07 08 08 08 08 08 08
IP55/IK10
bb bb bb bb bb bb bb bb bb vv bb bb bb bb vv bb bb bb bb bb bb vv bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb bb
Magnesium (production, storage and 31 use) Machine rooms Plastics (production) Cabinet makers Metals (processing) Combustion engines (testing of) Ammunition storage Nickel (ore processing) Household waste (processing) Paper (production) Paper (storage) Perfume (production and storage) Pulp mill Paint (production and storage) Plaster (processing and storage) Gunpowder factory Chemicals (production) Oil refineries Salt preserve factories Soap (production) Saw mills Metalwork shops Grain or sugar silos Silk and artificial hair factories Sodium carbonate (processing and storage) Sulphur (processing) Spirits (storage) Sugar mills Tanners Dye works Textile and fabric (production) Varnish (production and application) Glass works Zinc works 20 51 50 30 33 33 54 31 31 34/35 33 50 55 34/35 33 31 50 30 50 50 33 51 33 55 35 35 51 33 33 31
31v/33b 08 08 08 08 07 07 07 07 08 07 08 07 07 07 08 08 07 08 07 07 07 07 07 07 08 08 08 08
33v/34b 07
30v/50b 08
157
Additional information
Enclosure characteristics
Schneider Electric enclosures comply with standard IEC 62208 for empty enclosures. The sheet metal used for Schneider Electric enclosures receives an anti-corrosion epoxy electrophoresis treatment and a coating of a thermosetting, polyester-resinmodified epoxy powder for colour and appearance. This two-coat system provides excellent finish and corrosion protection. The characteristics of this coating are much better than those of traditional epoxy powders: bb improved colour stability bb wider operating temperature range.
Adhesion (cross-hatch and pull-off) Impact strength (1) Mandrel bending test (2) Persoz hardness
(1) No cracking of the paint film after dropping a weight of one kilogram on the test piece from a height of 50 centimetres. (2) Film cracks over a length of 10 millimetres maximum.
Test conditions: two tests carried out on the same 1 mm thick steel sheet test piece. bb cyclical damp-heat test: vv as per standard IEC 68-2-30 -- six 24-hour cycles at temperatures higher than 40 C bb continuous resistance to neutral salt mist: vv the tests were carried out over a period of 400 hours, far more than the 48 hours required by the standard for indoor installations vv as per standard IEC 68-2-11 and ISO 7253 -- 400 hours without blistering for normal surface on test piece -- 250 hours for a scratched surface. Evaluation of corrosion as per ISO 4628: bb adhesion: class y 1 bb blistering: degree 1 dim.1 bb rusting: Ri 1 bb cracking: class 1 bb flaking imp. 1 dim. 1 bb propagation of corrosion under scratch with respect to the scratch axis: 3 mm max.
Bases Water
Concentration 20 % 30 % 30 % 30 % 30 % 10 % 10 % 10 % 10 %
10
12
Solvents
158
Additional information
Thermal characteristics
Forced-air ventilation
?
IP > 31 On special request. IP > 31
bb For these extreme cases, many installers prefer to set up the switchboards with other electrotechnical and electronic devices in air-conditioned electrical rooms. Heating The means employed to raise the internal temperature in a switchboard is a resistorbased heater, used to: bb avoid condensation by limiting variations in temperature bb ensure that the switchboard does not freeze.
159
Additional information
Thermal characteristics
DD381401
Calculation of the temperature is the means to check that the enclosure can evacuate the dissipated power of the installed devices. Important note Correct thermal management of the switchboard depends on compliance with the installation requirements for the distribution system (power circuits). Incorrect installation will have major consequences on the connected device, but almost none on the internal temperature of the enclosure. Once the circuit has been correctly sized, it is necessary to check whether the assembly (devices + distribution system + cables) have a level of dissipated power P(W) y the P(W) that the enclosure can handle. Method defined by IEC 890 technical report This IEC guide for switchboards proposes a calculation method to determine three levels of internal temperature, depending on the dissipated power of the devices and distribution blocks installed in the switchboard. Users can consult this document when it is necessary to determine precisely the internal temperature in view of optimising the switchboard. On request, Schneider Electric can carry out a thermal study to check that the installed assembly and the thermal capacity of the enclosure are compatible. Comparative method A number of qualified and tested configurations serve as the basis for indicating the thermal capacity of Prisma Plus enclosures. This is en empirical means to check whether the dissipated power of the desired configuration is close to that of a tested configuration. Method using charts taking into account enclosure characteristics To speed up calculations, Schneider Electric produces charts based on the companys experience and a number of assumptions on the installation. They can be used sufficiently precisely to determine the variations in temperature and the dissipated-power levels for the different types of wall-mount enclosures, floor-standing enclosures and cubicles.
DD382422
DD383636
160
Additional information
Thermal characteristics
You will have no problems with your switchboard if: bb the volume of the enclosure is greater than that of the tested enclosure with a similar assembly bb the P(W) of the installed assembly is less than the P(W) of the tested configuration in the same size enclosure. Pack enclosure, 3 rows, IP30 Diversity factor: 0.7 Ambient temperature around the switchboard: 35C P(W) = 95 W
DD384080
C60N or IC60N 40 A
C60N or IC60N 32 A
C60N or IC60N 20 A
C60N or IC60N 25 A
C60N or IC60N 40 A
C60N or IC60N 25 A
Wall-mounted enclosure, 23 modules, IP30 Diversity factor: 0.7 Ambient temperature around the switchboard: 35C P(W) = 170 W
DD384081
NSX250N
C60N or IC60N 63 A
C60N or IC60N 50 A
C60N or IC60N 20 A
C60N or IC60N 50 A
C60N or IC60N 40 A
C60N or IC60N 32 A
C60N or IC60N 20 A
C60N or IC60N 20 A
C60N or IC60N 40 A
C60N or IC60N 32 A
C60N or IC60N 20 A
C60N or IC60N 25 A
161
Additional information
Thermal characteristics
You will have no problems with your switchboard if: bb the volume of the enclosure is greater than that of the tested enclosure with a similar assembly bb the P(W) of the installed assembly is less than the P(W) of the tested configuration in the same size enclosure. Wall-mounted enclosure, 23 modules, plain door, IP30 Diversity factor: 0.7 Ambient temperature around the switchboard: 35C P(W) = 200 W
DD383955
NSX400
NSX125N
NSX100N
Floor-standing enclosure, 33 modules, IP30 Diversity factor: 0.7 Ambient temperature around the switchboard: 35C P(W) = 270 W
DD384082
NSX630N
NSX250N NSX250N
C60a or IC60a 10 A
C60a or IC60a 10 A
C60a or IC60a 10 A
C60a or IC60a 10 A
C60a or IC60a 10 A
162
Additional information
Thermal characteristics
Draw a line parallel to the others on the chart and read the corresponding difference in temperature. For the given example, the heat rise is 22 C at mid-height in the enclosure. The internal temperature = external temperature + heat rise = 35 C + 22 C = 57 C 57 C < 60 C stipulated by the standard, i.e. the result is acceptable for an IP3 cubicle. This gives roughly: Internal temperature = 60 C at mid-height in the enclosure for a low IP value. = 70 C at mid-height in the enclosure for a high IP value.
163
Additional information
Thermal characteristics
Test conditions: 600 mm wide enclosure mounted directly on wall without fixing lugs. IP3X floor-standing enclosure
DD382434 DD382435
Test conditions: 600 mm wide enclosure mounted directly on wall without fixing lugs. IP43 floor-standing enclosure
Test conditions: Mounted on wall with fixing lugs or on mounting uprights. IP55 wall-mounted and floor-standing enclosures
DD382436
Test conditions: 600 mm wide enclosure mounted directly on wall without fixing lugs or mounting uprights.
164
Additional information
Thermal characteristics
The air enters the lower section via the fans and exits the upper section: bb through a ventilated roof bb or through a ventilation opening. The air throughput of the fans is determined by the equation:
P D = 31 -- KS DT
The chart below can be used to determine the necessary throughput, based on the dissipated power, the difference in temperature (internal - external) and the exposed surface area of the enclosure. Example Consider an IP3X cubicle, 650 mm wide and 400 mm deep, containing components (devices, connections, busbars, etc.) dissipating 1000 W. The ambient temperature around the cubicle is 50 C. Given that the average temperature at mid-height should not exceed 60 C, the difference in temperature DT is equal to 60 - 50 = 10 C. The exposed surface of the cubicle (non adjacent to a wall or other cubicle) is 4.46m. (back = 1.3 m, front = 1.3 m, roof = 0.26 m, side panels = 1.6 m). What is the necessary throughput of the ventilation system? The throughput can be calculated as:
1000 D = 31 ----- 5 5 10 46
D=234m3/h. In the range of Prisma Plus accessories, select a system with a throughput of 300m3/h.
DD381391
Calculation data P : power dissipated by the devices, connections and busbars (in Watts) Pr : power of the heating resistor (in Watts) Tm : maximum internal temperature in the device zone (in C) Ti : average internal temperature (in C) Te : average external temperature (in C) DTm =Tm Te DT=Ti Te S : total free surface area of the enclosure (expressed in m2) K : thermal-conduction coefficient of the material (W/m2 C) K = 5.5 W/m2 C for painted sheet metal D : ventilation throughput (in m3/h)
Note: The dissipated power of each device is provided by the manufacturer. Add approximately 30% to account for the connections and the busbars.
165
Additional information
Thermal characteristics
The heating resistor, placed in the bottom of the switchboard, maintains the internal temperature 10 C higher than the external temperature. When the switchboard is not in operation, the heater compensates the dissipated power normally emitted by the switchboard. The power of the heating resistor is calculated: bb using the equation: Pr = (DT x S x K) - P bb or using the charts below, based on the exposed surface area of the enclosure and the desired difference in temperature. Chart to determine the heating resistor for small wall-mounted enclosures (exposed surfaces y 1 m2)
DD381788
Calculation data P : power dissipated by the devices, connections and busbars (in Watts) Pr : power of the heating resistor (in Watts) Tm : maximum internal temperature in the device zone (in C) Ti : average internal temperature (in C) Te : average external temperature (in C) DTm =Tm Te DT=Ti Te S : total free surface area of the enclosure (expressed in m2) K : thermal-conduction coefficient of the material (W/m2 C) K = 5.5 W/m2 C for painted sheet metal D: ventilation throughput (in m3/h)
Note: The dissipated power of each device is provided by the manufacturer. Add approximately 30 % to account for the connections and the busbars.
166
Additional information
Practical information
DD383904
167
Notes
168
As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.
This document has been printed on ecological paper.
Publication: Schneider Electric Industries SAS Design/Layout: Emmanuel Froger / SEDOC Printed: Altavia Connexion - Made in France 10-2011