Sei sulla pagina 1di 5

Raw Water Quality Analysis

Existing Condition There are 7 Water Treatment Plant for Zone 1 : a. 5 WTPs located in Kec. Neglasari (IPA Mekarsari), raw water taken from Cisadane River, distributed to Kec. Batu Ceper and Cipondoh b. 1 WTP located in Kec. Benda (IPA Benda), raw water taken from Saluran Irigasi Cisadane Timur, distributed to Kec. Benda c. 1 WTP located in Kec. Banjar Wijaya (IPA Banjar Wijaya) , raw water taken from Situ Cipondoh, distributed to Banjar Wijaya residence In order to be used as drinking water, those raw water should meet the requirement from PP 82/2001, specifically for Class I. Here are the water quality analysis in each point and its compliance to the referred regulation. Cisadane River Water Quality Analysis Analysis for Raw Water is carried out both internally and externally. Internal sampling is conducted every week and external sampling (by Sucofindo) is conducted every month. In PP 82/2001, there were physical, inorganic chemical substance, microbiological, and radioactive paremeters. For physical paremeters, there was no issue, since all parameters comply to PP 82/2001, both internal and external measurement . But for inorganic substances, some parameters didn't meet the requirement such as Iron Dissolved, Manganese, nitrite, zinc, and total phospate. And also we also need to give more attention to microbiological aspect that significantly exceeds the threshold limit value.

Tabel 1.1 The average value of all parameters at Cisadane River during 3 years, 2010-2012 Treshold Limit Value PP 82/2001 Class I
6-9 1000 0.3 0.1 0.5 0.06 0.05 400 0.03 6 0.2 100 1000 50 2 10

Parameters
Turbidity Color pH Total Dissolved Solid Iron Dissolved Manganese Ammonia Nitrite Zinc Sulfate Free Chlorine Dissolved Oxygen Total Phosphat Total Coliform Faecal Coliform Suspended solid BOD COD *N/M = Not Measured

Unit
NTU Pt-Co mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L per 100 mL per 100 mL mg/L mg/L mg/L

Average Value (PDAM)


77.20 303.50 6.74 77.66 1.08 0.29 0.44 0.05 0.01 19.47 0.91 3.77 N/M N/M N/M N/M N/M N/M

Average Value (Sucofindo)


N/M N/M Comply Comply 0.37 0.10 0.27 0.11 0.11 76.57 Comply 10.54 0.91 9369.58 4753.04 86.29 4.46 12.57

Detail information for measurement results (maximum, minimum, and average) in each month were summarize in Attachment A. This table describes percentage of samples that comply to PP 82/2001 for Class I (which can be used for drinking water) The calculation to get the percentage value is : number of sample that meet the regulation x 100% number of sample Tabel 1.2 Performance Cisadane River Performance (based Parameter Faecal Coliform Nitrite Total Phosphat Total Coliform BOD Suspended solid Zinc Fe COD Manganese DO Ammonia Florida Cooper
*N/M = Not Measured
on Sucofindo Measurement)

Performance
(based on PDAM Measurement)

11% 19% 22% 26% 33% 44% 67% 70% 78% 81% 85% 89% 89% 93%

N/M

89%
N/M N/M N/M N/M

96% 6%
N/M

1% 2% 78%
N/M N/M

As we can see, the table show the performance starting from the poorest quality which are faecal coliform, followed by nitrit and total phosphat Therfore, it is urgently required to provide treatment for biological aspect. We can also see that inorganic chemical usually didnt meet the treshold limit We can conclude that Cisadane didn't River meet PP 82/2001. As consequences, it couldn't be classified as Class I, and confirmed as Class IV Saluran Irigasi Cisadane Timur Water (IPA Benda) Quality Analysis Tabel 1.3 The average value of all parameters at Saluran Irigasi Cisadane Timur during 3 years, 2010-2012 Parameters Turbidity Color pH Iron Dissolve Ammonia Nitrite Manganese Total Dissolved Solid
Zinc

Treshold Limit Value PP 82/2001 Class I


6-9 0.3 0.5 0.06 0.1 1000 0.05

Unit
NTU Pt-Co mg/L mg/L mg/L mg/L mg/L mg/L

Average Value (PDAM) 44.87 238.43 6.68 0.86 1.31 0.09 0.34 104.36
0.10

For Saluran Irigasi Cisadane Timur, the value of iron dissolved, ammonia, nitrite, manganese, and zinc are exceeding the threshold limit value. As consequences, it couldn't be classified as Class I, and confirmed as Class IV Situ Cipondoh (IPA Banjar Wijaya) Quality Analysis Tabel 1.4 The average value of all parameters at Situ Cipondoh during 3 years, 20102012 Treshold Limit Average Value Parameters Unit Value PP 82/2001 (PDAM) Class I Turbidity NTU 18.37 Color Pt-Co 148.17 pH 6-9 6.95 Iron Dissolve 0.3 mg/L 0.55 Ammonia 0.5 mg/L 0.79 Nitrite 0.06 mg/L 0.09 Manganese 0.1 mg/L 0.50 Total Dissolved Solid 1000 mg/L 123.01
Zinc 0.05 mg/L 0.01

For Situ Cipondoh, the value of iron dissolved, ammonia, nitrite, and manganese are exceeding the threshold limit value. As consequences, it couldn't be classified as Class I, and confirmed as Class IV

Reservoar Analysis Existing Condition Before Februari 2011, the measurement were carried out in reservoar Gabungan (there was 3 reservoars in IPA Mekarsari) and reservoar II (distributed to Benda before IPA Benda installed)

Table 1.5 The average value of all parameters during 3 years, 2010-2012, that taken by PDAM Tirta Benteng in Reservoar Gabungan Treshold Limit Average Value Value No : (PDAM) Parameters Unit 492/MENKES/SK/I V/2010 Turbidity Color pH Total Dissolved Solid Iron Dissolved Manganese Ammonia Nitrite Nitrate 5.00 15.00 6,5-8,5 500.00 0.30 0.40 1.50 3.00 50
NTU Pt-Co mg/L mg/L mg/L mg/L mg/L mg/L

1.04 6.23 6.62 82.26 0.04 0.05 0.04 0.01 0.89

Detail information for measurement results (maximum, minimum, and average) in each month were summarize in Attachment D.

Table 1.4 The average value of all parameters during 3 years, 2010-2012, that taken by PDAM Tirta Benteng in Reservoar II Treshold Limit Value No : 492/MENKES/SK/I V/2010 5.00 15.00 6,5-8,5 500.00 0.30 0.40 1.50 3.00 50 Average Value (PDAM)

Parameters Turbidity Color pH Total Dissolved Solid Iron Dissolved Manganese Ammonia Nitrite Nitrate

Unit
NTU Pt-Co mg/L mg/L mg/L mg/L mg/L mg/L

1.02 6.48 6.67 88.46 0.04 0.04 0.03 0.00 0.95

We can conclude that all parameters from IPA Mekarsari meet the requirement of Health Minister Decree 492/MENKES/SK/IV/2010 Detail information for measurement results (maximum, minimum, and average) in each month were summarize in Attachment C.