Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
1/
10/15/2012
Demand References
Electric Power Basics For the Nonelectrical Professional, Steven W. Blume, IEEE Press, pp. 161-178, Chapter-7 An Introduction to Electric Power Distribution, second edition, Wayne Beaty; pp. 105-116 Basic Electric Power Distribution, third edition, Anthony J. Pansini; pp. 64-74 MYSTIQUES IN POWER SYSTEM PROTECTION
http://ceseeps.blogspot.com/2009/03/mystiques-in-system-protection.html
The Seven Types of Power Problems, White Paper 18, Revision 1, by Joseph Seymour, APC -Schneider Electric white paper library
10/15/2012
10/15/2012
10/15/2012
10/15/2012
Personal protection
rubber gloves, insulating blankets, grounding jumpers, switching platforms, tagging, and so on.
It is important system protection is for the protection of equipment and not intended for the protection of people
Community College of Rhode Island
10/15/2012
Protective relays
initiate alarms to system control notifying operators of changes that have occurred in the system
Control operators react to these incoming alarms from the system protection equipment Proper grounding provides equipment protection Effective or proper grounding can
minimize damage to equipment cause protective relays to operate faster provides additional safety for personnel
10/15/2012
10/15/2012
System-Protection Equipment
System protection - often called protective relaying Relay devices in substations monitor the power systems voltages and currents with CTs and PTs CTs and PTs and are programmed to trip circuit breakers if the thresholds are exceeded System control operators are then alarmed of the new conditions The relays, trip signals, circuit breaker control systems, and the system control equipment are all battery powered
Community College of Rhode Island
10/15/2012 7
Protective Relays
Protective relays are manufactured as two types Electromechanical relays are composed of
coils of wire, magnets, spinning disks and moving electrical switch contacts, and are very mechanical in nature
Advantages
Self-powered Simple, single function
Disadvantages
One relay per phase Difficult to set up Difficult to adjust Frequent testing Power required Complex software
Solid State
Multi function Small space Easy to set up Remote access and test
10/15/2012
10/15/2012
Substation relay would trip the breaker faster due to higher current Down stream slow due to less current (resistance of the wire) Some breakers trip in less than two cycles , other older breakers might take nine cycles to trip Relay coordination means downstream device clears fault first Upstream devices act as back up clearing devices Protection is an art as well as a science
Community College of Rhode Island
10/15/2012 9
One-Line Diagrams
Simplified three-line diagrams with redundancy removed of the system One-line diagrams are very useful for
planning maintenance activities rerouting power after a fault switching orders
A three line diagram shows the neutral and ground cables on an AC system.
10/15/2012
10
10/15/2012
10/15/2012
11
10/15/2012
12
10/15/2012
Distribution Protection
Distribution lines (i.e., feeders) are normally fed radially out of substations. The typical distribution line protection schemes used on radially fed lines Normally involve overcurrent protection with reclosing relays Also under frequency load-shed relays This approach to distribution protection is very common; however, variations do exist.
10/15/2012
13
This typical substation relay package must also coordinate with the downstream fuses that are located on the feeder itself The overcurrent relays are connected directly to current transformers (CTs) located on the circuit breaker bushings. This enables the monitoring of actual current magnitudes flowing through the breaker in real time Normally there are four CTs used for each feeder breaker (one for each phase and one for the grounded neutral). Each overcurrent relay has both an instantaneous and a time delay overcurrent relay connected to the CTs. These relays are looking for feeder faults that are phase to ground, phase to phase, two phases to ground, or three phases. The protection engineer analyzes the available fault current magnitudes for each feeder breaker Recommends relay settings that are later programmed into the relays. These relay settings are periodically tested to make sure they operate properly.
Community College of Rhode Island
10/15/2012 14
10/15/2012
Underfrequency Relays
To stop or prevent a cascading outage, underfrequency relays are used to shed load when the system frequency is dropping. Underfrequency relays are also referred to as load-shed relays. The system frequency will drop if there is more load than there is generation This automatic load-shedding scheme can trip up to 30% of total load in an effort to prevent the system from experiencing a wide-scale outage. The standard frequency in the United States is 60 hertz The typical underfrequency relay settings are chosen based on the following guidelines:
At 59.3 Hz, shed a minimum of 10% of load. At 59.0 Hz, shed a minimum of 10% of load. At 58.7 Hz, shed a minimum of 10% of load. At 58.5 Hz or lower, the system may take any action it deems necessary, including a domino effect disturbance.
Some systems start diesel engine generators and/or combustion turbines automatically upon underfrequency detection. All of these remedial action schemes are intended to balance generation and load and stop the possibility of a cascading outage disturbance.
10/15/2012
15
10/15/2012
16
10/15/2012
Transmission Protection
Transmission protection is much different than distribution protection simply because transmission is usually not radially fed. Normally transmission systems have multiple feeds to a substation and transmission lines must have special protective relaying schemes to identify the actual faulted transmission line. Some transmission lines might have generation at the other end that contributes to the fault current Others can be transporting generation from different lines and substations Zone relaying (sometimes called distance or impedance relaying) with directional overcurrent capability is used to identify and trip the faulted transmission lines. The direction of the fault current verifies that a particular breaker needs to trip For example, excessive current must be leaving the substation as opposed to just excessive current magnitude. Both fault current magnitude and direction are required for transmission breakers to trip.
Community College of Rhode Island
10/15/2012 17
10/15/2012
18
10/15/2012
10/15/2012
19
10/15/2012
20
10
10/15/2012
Substation Protection
Substation protection is generally uses differential relays Differential relays are used to protect major transformers and buses from faults Substation differential relays are very similar in concept to GFCI breakers With a GFCI receptacle breaker, the current leaving the hot leg (black wire) must equal or be within 5 milliamps of the current returned in the neutral (white wire) or the GFCI breaker will trip. Differential relays used in substation transformers and buswork monitor the current entering versus the current exiting the protection zone.
10/15/2012
21
Differential Relays
Differential relays are generally used to protect buses, transformers, and generators. Differential relays operate on the principle that the current going into the protected device must be equal to the current leaving the device. Should a differential condition be detected, then all source breakers that can feed fault current on either side of the device are tripped. Current transformers (CTs) on both the high side and low side of the transformer are connected to a transformer differential relay. Matching CTs are used to compensate for the transformer windings turns ratio. Should a differential be detected between the current entering the transformer and exiting the transformer after adjusting for small differences due to losses and magnetization, the relay trips the source breaker(s) and the transformer is deenergized immediately.
10/15/2012
22
11
10/15/2012
10/15/2012
23
10/15/2012
24
12
10/15/2012
Generator Protection
The chances of failure of rotating machines are small due to improved design, technology, and materials. Failures can occur, and the consequences can be severe. Generators are expensive It is very important that proper generation protection is provided. When a generator trips offline for any reason, it is extremely important to determine exactly what caused the generator to trip.
10/15/2012
25
Unbalanced fault produce very strong magnetic forces that cannot be sustained for a long period of time. This condition quickly causes rotor overheating and serious damage. To protect against this condition, a reverse rotation overcurrent relay is used to detect these conditions. Reverse rotation (i.e., negative sequence) relays look for currents that want to reverse the direction of the rotor
10/15/2012
26
13
10/15/2012
10/15/2012
27
10/15/2012
28
14
10/15/2012
Generator Synchronization
The purpose of a synchronizing relay is to safely connect two three-phase lines together or to place a spinning generator online. There are four conditions that must be met first in order to safely connect two three-phase systems together. Failure to meet these four conditions can result in catastrophic failure of the equipment (i.e., generator). Permissive relays are used in circuits like this to block the closing of circuit breakers until all conditions are met.
An analogy to permissive relays would be to require that your seat belt be buckled before your car will start
10/15/2012
29
Condition 2. Voltage
Condition 4. Rotation
10/15/2012
30
15
10/15/2012
10/15/2012
31
16
10/15/2012
Lightening Arrestors
Lightning arresters are designed to limit the line-to-ground voltage in the event of lightning or other excessive transient voltage conditions. Some of the older gap-type lightning arresters actually short-circuited the line or equipment, causing the circuit breaker to trip. The breaker would then re close when the transient overvoltage condition was gone. The lightning arrester protects the equipment near the lightning arrester from experiencing highvoltage transient conditions The newer lightning arresters use gapless metal oxide semiconductor materials to clamp or limit the voltage. These newer designs offer better voltage control and have higher energy dissipation characteristics. They can be found near distribution transformers, overhead of underground transition structures, and along long distribution lines.
10/15/2012
33
Arrestor Classes
Voltage rating is associated with an arrestor They fall into different energy dissipation classes. An arrester might have to dissipate energy up until the circuit breaker clears the line. Station class arresters are the largest types and can dissipate the greatest amount of energy. Class arresters are normally used in substations that do not have excessive shortcircuit current. Residential and small commercial customers may use secondary class arresters to protect large motors, sensitive electronic equipment, and other voltage-surgesensitive devices connected to their service panel.
10/15/2012
34
17
10/15/2012
Grounding Grid
Ground beds provide safety grounding of electrical equipment. The lower the resistance of the ground bed, the better protection it provides. While ground beds may have a low resistance when first installed, corrosion of ground rods, breaks in interconnecting wires, and water table changes can all increase the resistance of the safety ground bed. For this reason it is important that the resistance of the ground bed be measured not only when first installed, but also periodically to ensure that it remains low in value.
10/15/2012
35
18