HCM534F - Technical Data Sheet

HCM534F
SPECIFICATIONS & OPTIONS
TERMINALS & TERMINAL BOX Standard generators are 3-phase reconnectable with 12 ends brought out to the terminals, which are mounted on a cover at the non-drive end of the generator. A sheet steel terminal box contains the AVR and provides ample space for the customers' wiring and gland arrangements. It has removable panels for easy access.

STANDARDS Marine generators may be certified to Lloyds, DnV, Bureau Veritas, ABS, Germanischer-Lloyd or RINA. Other standards and certifications can be considered on request.

VOLTAGE REGULATORS MX341 AVR - STANDARD This sophisticated Automatic Voltage Regulator (AVR) is incorporated into the Stamford Permanent Magnet Generator (PMG) control system, and is standard on marine generators of this type. The PMG provides power via the AVR to the main exciter, giving a source of constant excitation power independent of generator output. The main exciter output is then fed to the main rotor, through a full wave bridge, protected by a surge suppressor. The AVR has in-built protection against sustained overexcitation, caused by internal or external faults. This de-excites the machine after a minimum of 5 seconds. An engine relief load acceptance feature can enable full load to be applied to the generator in a single step. If three-phase sensing is required with the PMG system the MX321 AVR must be used. We recommend three-phase sensing for applications with greatly unbalanced or highly non-linear loads. MX321 AVR The most sophisticated of all our AVRs combines all the features of the MX341 with, additionally, threephase rms sensing, for improved regulation and performance. Over voltage protection is built-in and short circuit current level adjustments is an optional facility.

SHAFT & KEYS All generator rotors are dynamically balanced to better than BS6861:Part 1 Grade 2.5 for minimum vibration in operation. Two bearing generators are balanced with a half key.

INSULATION/IMPREGNATION The insulation system is class 'H'. All wound components are impregnated with materials and processes designed specifically to provide the high build required for static windings and the high mechanical strength required for rotating components.

QUALITY ASSURANCE Generators are manufactured using production procedures having a quality assurance level to BS EN ISO 9001. The stated voltage regulation may not be maintained in the presence of certain radio transmitted signals. Any change in performance will fall within the limits of Criteria 'B' of EN 61000-6-2:2001. At no time will the steady-state voltage regulation exceed 2%.

WINDINGS & ELECTRICAL PERFORMANCE All generator stators are wound to 2/3 pitch. This eliminates triplen (3rd, 9th, 15th ) harmonics on the voltage waveform and is found to be the optimum design for trouble-free supply of non-linear loads. The 2/3 pitch design avoids excessive neutral currents sometimes seen with higher winding pitches, when in parallel with the mains. A fully connected damper winding reduces oscillations during paralleling. This winding, with the 2/3 pitch and carefully selected pole and tooth designs, ensures very low waveform distortion.

NB Continuous development of our products entitles us to change specification details without notice, therefore they must not be regarded as binding. Front cover drawing typical of product range.

HCM534F
WINDING 311
CONTROL SYSTEM A.V.R. VOLTAGE REGULATION SUSTAINED SHORT CIRCUIT INSULATION SYSTEM PROTECTION RATED POWER FACTOR STATOR WINDING WINDING PITCH WINDING LEADS STATOR WDG. RESISTANCE ROTOR WDG. RESISTANCE EXCITER STATOR RESISTANCE EXCITER ROTOR RESISTANCE R.F.I. SUPPRESSION WAVEFORM DISTORTION MAXIMUM OVERSPEED BEARING DRIVE END BEARING NON-DRIVE END 1 BEARING WEIGHT COMP. GENERATOR WEIGHT WOUND STATOR WEIGHT WOUND ROTOR WR INERTIA SHIPPING WEIGHTS in a crate PACKING CRATE SIZE 1685 kg 805 kg 684 kg 10.033 kgm 1775 kg 166 x 87 x 124(cm) 50 Hz TELEPHONE INTERFERENCE COOLING AIR VOLTAGE SERIES STAR VOLTAGE PARALLEL STAR VOLTAGE SERIES DELTA 380/220 190/110 220/110 THF<2% 1.035 m/sec 2202 cfm 400/231 200/115 230/115 585 415/240 208/120 240/120 600 440/254 220/127 254/127 600 416/240 208/120 240/120 663
2

SEPARATELY EXCITED BY P.M.G. MX321 0.5 % MX341 1.0 % With 4% ENGINE GOVERNING

REFER TO SHORT CIRCUIT DECREMENT CURVES (page 7) CLASS H IP23 0.8 DOUBLE LAYER LAP TWO THIRDS 12 0.0037 Ohms PER PHASE AT 22C SERIES STAR CONNECTED 2.16 Ohms at 22C 17 Ohms at 22C 0.092 Ohms PER PHASE AT 22C BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0% 2250 Rev/Min BALL. 6220 (ISO) BALL. 6314 (ISO) 2 BEARING 1694 kg 805 kg 655 kg 9.7551 kgm2 1780 kg 166 x 87 x 124(cm) 60 Hz TIF<50 1.312 m/sec 2780 cfm 440/254 220/127 254/127 694 460/266 230/133 266/133 706 480/277 240/138 277/138 725

kVA BASE RATING FOR 565 REACTANCE VALUES Xd DIR. AXIS SYNCHRONOUS 2.45 X'd DIR. AXIS TRANSIENT 0.13 X''d DIR. AXIS SUBTRANSIENT 0.09 Xq QUAD. AXIS REACTANCE 2.04 X''q QUAD. AXIS SUBTRANSIENT 0.21 0.04 XL LEAKAGE REACTANCE 0.15 X2 NEGATIVE SEQUENCE 0.07 X0 ZERO SEQUENCE REACTANCES ARE SATURATED T'd TRANSIENT TIME CONST. T''d SUB-TRANSTIME CONST. T'do O.C. FIELD TIME CONST. Ta ARMATURE TIME CONST. SHORT CIRCUIT RATIO

2.29 2.18 1.94 2.99 2.80 2.60 2.46 0.12 0.12 0.10 0.14 0.13 0.12 0.11 0.09 0.08 0.07 0.10 0.09 0.09 0.08 1.91 1.82 1.62 2.39 2.24 2.08 1.96 0.20 0.19 0.17 0.28 0.26 0.24 0.23 0.03 0.04 0.03 0.04 0.04 0.04 0.04 0.14 0.13 0.12 0.19 0.18 0.17 0.16 0.07 0.06 0.06 0.08 0.07 0.07 0.07 VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED 0.08s 0.012s 2.5s 0.019s 1/Xd

50 Hz

HCM534F
Winding 311 THREE PHASE EFFICIENCY CURVES

60 Hz

HCM534F
Winding 311 THREE PHASE EFFICIENCY CURVES

HCM534F
Winding 311 Locked Rotor Motor Starting Curve

50
Hz
30
346V 380V 400V 415V 440V

25

PER CENT TRANSIENT VOLTAGE DIP .

20

15

10

0 0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400
LOCKED ROTOR kVA

60
Hz
30
380V 416V 440V 460V 480V

25

PER CENT TRANSIENT VOLTAGE DIP .

20

15

10

0 0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400
LOCKED ROTOR kVA

HCM534F
Three-phase Short Circuit Decrement Curve. No-load Excitation at Rated Speed Based on star (wye) connection.

50 Hz
CURRENT (Amps)

100000

SYMMETRICAL ASYMMETRICAL

10000

1000

100 0.001

0.01

0.1 TIME (secs)

10

Sustained Short Circuit = 2,900 Amps

60 Hz

100000

SYMMETRICAL ASYMMETRICAL

CURRENT (Amps)

10000

1000

100 0.001

0.01

0.1 TIME (secs)

10

Sustained Short Circuit = 3,300 Amps


Note 1 The following multiplication factors should be used to adjust the values from curve between time 0.001 seconds and the minimum current point in respect of nominal operating voltage : 50Hz
Voltage 380v 400v 415v 440v Factor X 1.00 X 1.06 X 1.09 X 1.12

Note 2 The following multiplication factor should be used to convert the values calculated in accordance with NOTE 1 to those applicable to the various types of short circuit :
3-phase 2-phase L-L 1-phase L-N

60Hz
Voltage 416v 440v 460v 480v Factor X 1.00 X 1.06 X 1.12 X 1.20

The sustained current value is constant irrespective of voltage level

Instantaneous x 1.00 x 0.87 x 1.30 Minimum x 1.00 x 1.80 x 3.20 Sustained x 1.00 x 1.50 x 2.50 Max. sustained duration 10 sec. 5 sec. 2 sec. All other times are unchanged Note 3 Curves are drawn for Star (Wye) connected machines. For other connection the following multipliers should be applied to current values as shown : Parallel Star = Curve current value X 2 Series Delta = Curve current value X 1.732 Note 3

HCM534F
Winding 311 / 0.8 Power Factor RATINGS
Class - Temp Rise Cont. E - 65/50C 380 190 220 420 336 400 200 230 440 352 95.6 368 415 208 240 450 360 95.6 377 440 220 254 450 360 95.5 377 380 190 220 440 352 95.6 368 Cont. B - 70/50C 400 200 230 460 368 95.6 385 415 208 240 475 380 95.6 397 440 220 254 475 380 95.6 397 380 190 220 505 404 95.4 423 Cont. F - 90/50C 400 200 230 525 420 95.5 440 415 208 240 540 432 95.5 452 440 220 254 540 432 95.5 452 Cont. H - 110/50C 380 190 220 565 452 95.3 474 400 200 230 585 468 95.3 491 415 208 240 600 480 95.3 504 440 220 254 600 480 95.4 503 Series Star (V) Parallel Star (V) Series Delta (V) kVA kW

50
Hz

Efficiency (%) 95.6 kW Input 351

60
Hz

Series Star (V) Parallel Star (V) Delta (V) kVA kW

416 208 240 515 412

440 220 254 540 432 95.5 452

460 230 266 550 440 95.5 461

480 240 277 555 444 95.5 465

416 208 240 544 435 95.4 456

440 220 254 565 452 95.5 473

460 230 266 578 462 95.5 484

480 240 277 582 466 95.5 488

416 208 240 619 495 95.3 520

440 220 254 644 515 95.4 540

460 230 266 656 525 95.4 550

480 240 277 663 530 95.5 555

416 208 240 663 530 95.2 557

440 220 254 694 555 95.3 583

460 230 266 706 565 95.3 593

480 240 277 725 580 95.4 608

Efficiency (%) 95.5 kW Input 431

DIMENSIONS

Barnack Road Stamford Lincolnshire PE9 2NB Tel: 00 44 (0)1780 484000 Fax: 00 44 (0)1780 484100

2006

TD_HCM534F.GB_10.06_04_GB