Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
TELE-DATA
www.TELE-DATA.de
NETWORK
PARAM
TK 400
Application
Working as a routing-device with control centres or with telecontrol devices, the TK 400 operates with all telecontrol protocols.
Serial interface 0 is able to work from 200 Bd. up to 230400 Bd. and serial interface 1 from 600 Bd. up to 230400 Bd. The last timer is used for the protocol software. For serial coupling in pulse-width-modulation (pulse-duration-m.) 100 Bd. up to bis 2400 Bd. are available. Both interfaces can be used either in PWM- or in PCM (pulse-codem.) -mode or as control lines for modems, so that up to 2 coupling partners can be served. Despite the functions running by different software branches on TK 400, there are general functions in order to protect the TK 400 module against malfunctions. These functions are realized by hardware supplements and by software parts.
Features
the TK 400 adjustable to any telecontrol protocol coordinates the telegram traffic between one or more substation units and AC- and/or modem-connections to central stations or substations checks automatically and continuously the memory of the device controls the watchdog parameters can be set online at any time boots itself after power-on multiple choices for connection such as fibre optics, RS 485, RS 232, 10-20mA current loop and 10mA single current
Interfaces
The TK 400 module offers the following interfaces for communication with parametrizing PC and for connection with serial communication partners: 1 serial interface to the parametrizing PC 1 serial interface to the control centre or central unit 1 serial interface to PCM or PWM coupling partners 1 serial interface RS485 1 Ethernet interface 10/100MBit 1 serial interface fibre optic ST- or SMAtype (optional) all transmitters and receivers are galvanically isolated by optocouplers all drivers are able to work at V.24 level, COM1 has got additional TTL level
Specification
The TK 400 board is equipped with an 8Bit CMOS - processor 80C400 and represents an independant computer, with an address-range of 8MByte. The CPU runs at a speed of 18 MHZ. The board has a maximum capacity of 1 RAM module with 8MBit in total memory as working memory. Depending on the kind of the module the storage capacity for saving of special system device data as well as for the specific telecontrol protocol structure are up to 16MBit flash memory. All four hardware-timers are required for the TELE-DATA realtime operating system TDXact. One timer is used for the system cycle. All of the prozessor-included UART modules turn the asynchronous V.24-interfaces. Each of these interfaces have their own baudrate timers.
Interfaces for serial communication are connected via rackmount connector. They include control lines, data lines and the requested power supply potentials. With the help of software parameters you can adjust the inversion of the specific signals. The status of each channel is shown on the 3 LEDs on the front panel.
TK 400
Technical Data
Processor Processor Technology Memory Operating system Serial Interfaces Input-resistance Output-resistance Input voltage Power supply REG-P 80400 CMOS 1-8MB RAM realtime, TDExact max. 4 1000 Ohm 120 Ohm +-3..24V + 5 V +/- 10% 0,9 A max.
General Functions
Beside the functions, running by different software applications , there are main functions protecting against malfunctions of the device. These functions are worked out by hardware-implementations and by software-routines:
Reset
There are four possibilities to trigger a reset on a TK 400. A proper restart of TK 400 is garanteed in each case: by pressing "RESET" on the front panel Watchdog runs up reconnection and return of power supply Reset by montoring software module
Reference conditions during operation in a 19" rack temperature: - 10..+55C relative humidity: max. 85% at 25C Storage: temperature: relative humidity: -25..+65C max. 80% at 25C
Parametrizing REG-P An edited file is transferred via serial interface from a standard PC into REG-P. Data is kept in flash memory.
Mechanical construction
Front Panel height, width weight Protection class plug in device terminal block Mounting connector block ALU, RAL 7035 3U, 6TE (129 mm, 30 mm) 0,4 kg IP 00 IP 00 according DIN 41494 Part 5 DIN 41612
TK 400
Electrical Connection
Terminal screws with selflocking protection; clip on connector block.
1 2 3 4 5 6 7 8 9
1 3 2 4
GND
5 6
RTS CTS
8 7 9
Electric security
Protection class I Grade of pollution 2 Overvoltage category, rated isulation voltage Name aux. voltage Serial interface Parallel interface Relais circuit Transient voltage strength Immunity Electrostatic discharge Electromagnetic fields Overvoltage max. Overvoltage II II II II 15 V 15 KV 15 V 60 V
CENTRAL STATION
TK 400
TELE-DATA
www.TELE-DATA.de
RTU 1 ... 8
NETWORK
IEC 101
PARAM
TK 400
LWL 1: SPA-BUS
NETWORK
PARAM
TK 400
Rapid transient disturbance quantities (Bursts) Power supply AC 230 V, 2 kV Contacted RF-disturbance factors 50 Hz-magnetic field Disturbance emission 0,15 MHz...80 MHz Ueff = 10 V 30 A / m Group 1 limit class A
REFERENCE LIST
PROTOCOL CONVERTER
TK 400
Protocol structure IEC 870-5-101 balanced IEC 870-5-101 unbalanced slave IEC 870-5-103 slave Other protocols specified separately Operation manual without German English G0 G1 G2 F1 F2 F3
C 1
N 2
N 3
C 4
O 5
R 6
T 7
O 8
E 9
T 10
A 11
L S T 12 13
A 14
I O 15
N 16
SINAUT IEC IEC SINAUT IEC IEC IEC IEC IEC IEC IEC IEC IEC DNP TG709 ETHERST 60870- 60870- FW537 60870- 60870- 60870- 60870- 60870- 60870- 60870- 60870- 60870- 3.0 NET 5-101 5-101 5-101 5-101 5-101 5-101 5-101 5-101 5-101 5-101 5-101
A B C D E F
SAT SK1703 MODBUS RTU SINAUT8FW IEC 60870-5-101 IEC 60870-5-101 IEC 60870-5-101
M SPABUS N ASCII
Phone: (+49) (0) 9101 / 99 78 10 Fax: (+49) (0) 9101 / 99 78 12 Mobile: (+49) (0) 171 236 75 66
info@tele-data.de www.tele-data.de