REL316*4
Technology and Solutions
Protection and Substation Automation
ABB
REL316*4 Objectives
Problem Description Solution Basic Tripping Schemes PUTT - Permissive Underreaching Transferred Tripping POTT - Permissive Overreaching Transferred Tripping BLOCK OR - BLOCKing OverReaching
RE.316_TeleComm / 2003-10-01 / RW
ABB
REL316*4
Problem Description
Starter
Starter Zone 1
Zone 2
Zone 2
Starter
Zone 1
RE.316_TeleComm / 2003-10-01 / RW
Faults near the ends of the line section will be cleared at zone 2 time, with additional time delay
(this is often acceptable at the distribution level, if fast reclosure is not required)
Reverse Zone
ABB
REL316*4
Station A
Solution
Station B
10 8 .. 10 9 VA
(1 GVA)
Watt
(- 50dBm)
RE.316_TeleComm / 2003-10-01 / RW
High speed tripping for all kind of faults occurring on 100% of the protected line Strict selectivity between two stations
ABB
Basic Tripping Schemes Permissive Underreaching Transferred Tripping Permissive Overreaching Transferred Tripping
ABB
REL316*4
PUTT (basic)
Starter Z underreaching
Starter
Starter Z- underreaching Starter *) T2 RX
RE.316_TeleComm / 2003-10-01 / RW
Z underreaching
Starter Z-underreaching Starter *) T2 RX
& 1 & 1
&
TRIP
TRIP
&
Z- underreaching
Z- underreaching
ABB
REL316*4
PUTT (basic)
Starter Z underreaching
Starter
Starter Z- underreaching Starter *) T2 RX
RE.316_TeleComm / 2003-10-01 / RW
Z underreaching
&
Starter Z- underreaching Starter *) T2 RX *) Alternatively: Starting + U-Weak
& 1 &
TRIP
TRIP
1 &
Z underreaching
Z underreaching
ABB
REL316*4
POTT (basic)
Starter Z overreaching
Z overreaching Starter
Z overeaching RX
&
TRIP
TRIP
&
Z overeaching RX
RE.316_TeleComm / 2003-10-01 / RW
Z overeaching
Z overeaching
ABB
REL316*4
POTT (basic)
Starter Z overreaching
Z overreaching Starter
Z overeaching RX
&
TRIP
TRIP
&
Z overeaching RX
RE.316_TeleComm / 2003-10-01 / RW
Z overeaching
Z overeaching
ABB
REL316*4
BLOCK OR (basic)
Z1 Z overreaching
Z reverse
Z overreaching Z2 Z3 Starter
Z1
Z reverse
Z1, t1; Z2, t2; Z3, t3; Starter, tEnd Z overeaching Loos of signal
RE.316_TeleComm / 2003-10-01 / RW
t wait (t1Block)
TRIP
&
TRIP TRIP
&
t wait (t1Block) 20 ms
Z overeaching
&
20 ms RX
TRIP
&
Loos of signal
&
&
Z overeaching
ABB
REL316*4
BLOCK OR (basic)
Z1 Z overreaching
Z reverse
Z overreaching Z2 Z3 Starter
Z1
Z reverse
Z1, t1; Z2, t2; Z3, t3; Starter, tEnd Z overeaching Loos of signal
RE.316_TeleComm / 2003-10-01 / RW
t wait (t1Block)
TRIP
&
TRIP TRIP
&
t wait (t1Block) 20 ms
Z overeaching
&
20 ms RX
TRIP
&
Loos of signal
&
&
Z overeaching
ABB
REL316*4
DTT (basic)
Starter Z underreaching
Starter
Starter Z- underreaching
Z underreaching
Starter Z-underreaching
& 1 1
&
TRIP
RX
RE.316_TeleComm / 2003-10-01 / RW
TRIP
RX
ABB
ABB