SABIANA
ENVIRONMENTAL COMFORT
HORIZONTAL UNIT
Air Conditioning
SABIANA
ENVIRONMENTAL COMFORT
The name Sabiana, for more than 70 years the symbol of a unit heater, is today, thanks to a wide range of products, the name of a company leader in the field of radiant heat, thermo-ventilation, air conditioning and heating, in commercial, industrial and sport buildings. The accuracy in each manufacturing detail, and the care in quality control places Sabiana products at the highest level in Europe. Founded in 1929, Sabiana is today a company of more than 200 people organized in an area of 30.000 m2 with modern machinery and processes that confirm the name Sabiana as a symbol of quality and reliability.
VERTICAL UNIT
FAN SECTION
BATTERY SECTION
Thanks to its expertise in the heating and airconditioning field Sabiana now presents you with the Ocean series of slim-line air conditioners. They are constructed in four basic versions in order to satisfy any installation request. By the use of the same modular components 6 vertical and 9 horizontal versions can be obtained. It is also possible to mount either 2, 3, 4 or 6 row heat exchangers for water, or a 4 row heat exchanger for the direct expansion of refrigerated gases in the treatment section. The fan section can be driven directly by choosing one of the three available speeds, by a recessed remote speed control switch, or by electronic proportional speed drive. The available air volume ranges from 600 to 1400 m3/Hr on model 1, from 1000 to 2100 m3/Hr on model 2, from 1500 to 3000 m3/Hr on model 3 and from 2400 to 5300 on model 4. Thanks to its modular construction the unit can be easily disassembled and re-assembled on site and the air flow direction can be changed according to the specific needs. Additional features like condensate collection trays, humidification etc. can also be easily added later. The special construction makes the inspection and the removal of the fan assembly and heat exchangers extremely easy.
Construction features
Casing Consists of self-supporting panels in hot dip galvanized, prepainted steel, which are completely insulated with a 20 mm. thick, thermoacustic, flame retardant lining. Fan section Consists of centrifugal fans in galvanized steel with two impellers and a directly coupled single phase, three speed motor, 230/240 Volt/50 Hz with permanently installed capacitor, insulation class F, power 185 W for sizes 1, 415 W for size 2, 375 W for size 3 and 2 x 350 W for size 4. Heat Exchanger Constructed in 3/8 dia expanded copper tubes with aluminium fins with a pitch of 2,1 mm. The steel headers have an extra tapping for an air vent and following male connectios: Sizes 1 and 2 = 3/4 Size 3 = 1 Size 4 = 1.1/4 except 6 rows with 1.1/2 The heat exchanger is mounted in a galvanized steel carrying frame. Diameters of connections of the direct expansion battery: - Inlet 16 mm - Outlet 24 mm
Noise level
SIZE 1
speed 1 2 3 dB (A) 45 51 55 m3/h 650 1000 1400 speed 1 2 3
The average noise level (sound pressure) is measured in the open air at a distance of one meter from the mouth of the unit.
SIZE 2
dB (A) 50 55 60 m3/h 1150 1550 2100 speed 1 2 3
SIZE 3
dB (A) 53 56 61 m3/h 1750 2300 3000 speed 1 2 3
SIZE 4
dB (A) 55 61 65 m3/h 2500 3800 5300
Sections dimensions
FAN SECTION SVE
a SIZE 1 SIZE 2 SIZE 3 SIZE 4 b c 65 40 40 40 d x z w
195 600 950 805 300 760 950 805 400 960 950 805 400 960 1500 1355
SECTION WEIGHTS WATER CONTENT kg litres SIZE FAN SECTION 2 ROWS 3 ROWS 1 23 2 28 3 32 4 52 1 2 3 4
16
20
24
42
BATTERY SECTIONS
18
22
26
45
22
28
34
55
The standard filter extraction is from the bottom, any different need must be specifically requested.
Heat exchanger The heat exchangers are tested to a pressure of 30 Bar. In normal operation the water temperature should not exceed 95C and the maximum working pressure 10 Bar. On request special heat exchangers can be supplied for H.T.H.W. Where a cooling battery is fitted the battery should always be fitted in a vertical position; if the unit is being used for heating only then the battery can be mounted either vertically or horizontally. The heat exchanger is not suitable for use in corrosive atmosphere or in environments where aluminium may be subject to corrosion.
26
30
52 SEE ABOVE
32
38
62
19
23
27
46
Operation limits
Electric motors The leaving air temperature must not exceed a temperature of 55C with 230V 50Hz supply and 50C with 240V 50Hz supply.
Air flow
Air flow
Combination possibilities
In addition to the 12 versions available using standard components a wide range of further combinations can be achieved and for each of them you can choose between the four different types of heat exchanger. The sizes 1, 2, 3 of the Ocean air conditioner can be supplied with the Crystall electrostatic filter (see page 17).
01
02
03
04
05
06
Heating only
07
08
09
10
11
12
Performance data
Fan section graphs
Fan section The fan section can be used for ventilation or as an air extraction box. The fan performance curve shows the air flow and the available static pressure for each speed at the mouth of the fan. Size 1 2 3 4 Maximum Absorbtion AMP High Medium 2 1,6 2,8 1,7 4,4 3,8 6 4 Low 1 1,2 3,3 3
SIZE 2
SIZE 1
250 25
3
150 15
3
200 20
2
150 15
2 1
AVAILABLE STATIC PRESSURE 100 10
1
AVAILABLE STATIC PRESSURE 100 10
50
50
m3/h
1000
1500
2000 m3/h
1500
2000
Pa mm H2O
SIZE 3
Pa mm H2O 350 35
SIZE 4
250
25 300 30
200
20
3
250 25
3
150 15
2 1
AVAILABLE STATIC PRESSURE
200
20
2
AVAILABLE STATIC PRESSURE 150 100 10 15
1
100 10
50
50
m3/h
2000
2500
3000
OCEAN 1
900
1000
1200
1400
1600
2000
OCEAN 2
1400
1600
1800
2000
2500
3000
OCEAN 3
2000
3000
4000
5000
OCEAN 4
ELECTROSTATIC FILTER
15 20 30 40 50 60
CARBON FILTER
10 15 20 30 40 50
INLET GRID
6 7 8 9 10 15 20 30
MIXING DAMPER
6 7 8 9 10 11 12
ELECTRIC BATTERY
10 11 12 13 14 15 16 17 18 19
HUMIDIFICATION SECTION
1000
3 4 2
1400
3 4
OCEAN Size
Battery rows 0 2 9.5 12.1 13.8 13.1 17.1 19.8 16.2 21.5 25.3
Water C 50/45 Air C + 10 + 20 7.3 9.2 10.4 10.0 13.0 15.1 12.3 16.4 19.3 5.1 6.5 7.4 7.0 9.2 10.7 8.6 11.5 13.7
Water C 70/60 Air C + 10 + 20 10.6 13.5 15.4 14.5 19.1 22.2 17.9 24.0 28.3 8.4 10.7 12.2 11.4 15.1 17.6 14.2 19.0 22.4
Water C 80/70 Air C + 10 + 20 12.6 16.1 18.3 17.3 22.7 26.3 21.5 28.6 33.7 10.3 13.2 15.0 14.2 18.6 21.6 17.6 23.4 27.6
1000
3 4 2
1550
3 4 2
2100
3 4
OCEAN Size
Battery rows 0 2 14.3 18.2 20.7 17.7 23.2 26.8 23.1 30.7 36.2
Water C 50/45 Air C + 10 + 20 11.0 13.8 15.6 13.6 17.6 20.5 17.6 23.4 27.6 7.7 9.8 11.1 9.5 12.5 14.5 12.3 16.4 19.6
Water C 70/60 Air C + 10 + 20 15.9 20.3 23.1 19.6 25.9 30.1 25.6 34.3 40.4 12.6 16.1 18.3 15.4 20.5 23.8 20.3 27.2 32.0
Water C 80/70 Air C + 10 + 20 18.9 24.2 27.5 23.4 30.8 35.6 30.7 40.9 48.2 15.5 19.8 22.5 19.2 25.2 29.3 25.2 33.4 39.4
1500
3 4 2
2100
3 4 2
3000
3 4
OCEAN Size
Battery rows 0 2 22.8 28.9 33.3 31.1 40.5 47.6 38.4 51.0 60.8
Water C 50/45 Air C + 10 + 20 17.4 22.3 25.6 23.8 31.2 36.6 29.4 39.3 46.8 12.3 15.9 18.3 16.8 22.3 26.1 20.7 28.0 33.4
Water C 70/60 Air C + 10 + 20 25.6 32.9 37.9 34.8 46.0 54.1 43.0 57.8 69.0 20.3 26.2 30.2 27.6 36.7 43.2 34.1 46.1 55.1
Water C 80/70 Air C + 10 + 20 30.7 39.1 44.9 41.9 54.7 64.3 51.7 68.9 82.1 25.3 32.3 37.1 34.5 45.3 53.1 42.6 57.0 67.9
2400
3 4 2
3800
3 4 2
5300
3 4
90 80 70
60
50
SIZE 1
2 ROW BATTERY 4 3 ROW BATTERY 6 4 ROW BATTERY 7 8 9 10 15 20 25 30 7 8 9 10 15 20 25 5 6 7 8 9 10 15 20
SIZE 2
2 ROW BATTERY 7 3 ROW BATTERY 9 4 ROW BATTERY 10 15 20 25 30 35 40 45 50 10 15 20 25 30 35 40 8 9 10 15 20 25 30
SIZE 3
2 ROW BATTERY 9 3 ROW BATTERY 15 4 ROW BATTERY 15 20 25 30 35 40 45 50 60 70 20 25 30 35 40 45 50 60 10 15 20 25 30 35 40 45
SIZE 4
2 ROW BATTERY 16 3 ROW BATTERY 20 4 ROW BATTERY 30 40 50 60 70 80 90 100 30 40 50 60 70 80 20 30 40 50 60
NOTE: Emission at high speed. For emission figures at medium speed multiply by 0.75. For emission figures at low speed multiply by 0.55.
9
SENSIBLE
Water temperature 12/17 C Entering Air temperature, dry bulb C +26 1.4 1.7 2.0 2.3 2.7 3.1 2.8 3.4 4.5 2.8 3.2 3.4 3.5 4.0 4.9 4.4 5.1 6.4 3.9 4.4 5.4 5.4 6.2 6.6 6.8 8.1 10.0 5.9 7.2 7.6 8.1 10.2 11.0 10.1 12.9 15.3 2.9 3.4 4.6 3.9 4.7 6.6 4.6 5.7 8.3 5.1 6.0 6.7 6.0 7.0 9.5 7.0 8.5 11.8 7.0 8.2 11.2 9.3 11.2 14.3 11.2 13.7 18.1 10.7 13.9 16.6 13.9 17.3 22.9 16.5 21.1 28.2 +30 1.9 2.2 2.8 3.0 3.5 4.3 3.8 4.4 5.6 3.5 4.0 4.4 4.8 5.4 6.4 6.0 6.9 8.3 5.2 5.8 7.0 6.9 7.8 9.2 8.9 10.3 12.3 7.7 9.2 10.4 10.6 12.5 14.9 13.4 16.1 19.1 3.8 4.5 5.8 5.1 6.2 8.4 6.1 7.6 10.6 6.6 7.8 8.7 8.0 9.4 12.3 9.5 11.4 15.4 9.2 11.6 14.5 12.0 14.5 18.3 14.6 17.9 23.3 14.0 17.8 20.9 18.3 22.4 28.9 21.7 27.5 35.8 +32 2.2 2.6 3.2 3.4 3.9 4.8 4.3 5.0 6.3 4.0 4.5 5.0 5.4 6.1 7.3 6.8 7.8 9.4 5.8 6.8 7.9 7.7 8.9 10.4 9.9 11.5 13.8 8.6 10.4 11.7 11.9 14.1 16.7 14.9 18.0 21.4
1000
4 6 3
1400
4 6 3
1000
4 6 3
1550
4 6 3
2100
4 6 3
1500
4 6 3
2100
4 6 3
3000
4 6 3
2400
4 6 3
3800
4 6 3
5300
4 6
10
12
18
24
19 20
21
23
22
34 32 30 28
26
24
11
10
3 4 5 Water t (C)
2 ATTENTION: A sensible heat figure higher than a total heat figure shows that the cooling is obtained without dehumidification, therefore the emission to refer to is the sensible one.
Output figures of 4 row battery are obtained multiplying the 3 row battery figures of the graph by 1.19
NOTE: Do not supply the unit with water at a temperature lower than +5C.
Output figures of 6 row battery are obtained multiplying the 3 row battery figures of the graph by 1.45
11
12
12
18
24
19 20
21
23
22
34 32 30 28
26
24
11
10
3 4 5 Water t (C)
3 4 ATTENTION: A sensible heat figure higher than a total heat figure shows that the cooling is obtained without dehumidification, therefore the emission to refer to is the sensible one.
Output figures of 4 row battery are obtained multiplying the 3 row battery figures of the graph by 1.19
NOTE: Do not supply the unit with water at a temperature lower than +5C.
Output figures of 6 row battery are obtained multiplying the 3 row battery figures of the graph by 1.45
12
18
21
24
19 20
23
34 32 30
28
26
22
24
11
10
3 4 5 Water t (C)
5 6 ATTENTION: A sensible heat figure higher than a total heat figure shows that the cooling is obtained without dehumidification, therefore the emission to refer to is the sensible one.
Output figures of 4 row battery are obtained multiplying the 3 row battery figures of the graph by 1.19
NOTE: Do not supply the unit with water at a temperature lower than +5C.
Output figures of 6 row battery are obtained multiplying the 3 row battery figures of the graph by 1.45
13
14
12
18
21
24
19 20
23
34 32 30
28
26
22
24
11
10
3 4 5 Water t (C)
10 ATTENTION: A sensible heat figure higher than a total heat figure shows that the cooling is obtained without dehumidification, therefore the emission to refer is the sensible one.
Output figures of 4 row battery are obtained multiplying the 3 row battery figures of the graph by x 1.19
NOTE: Do not supply the unit with water at a temperature lower than +5C.
Output figures of 6 row battery are obtained multiplying the 3 row battery figures of the graph by x 1.45
SIZE 1
Air flow m3/h Total heat kW Sensible heat kW 600 4.1 3.1 1000 6.4 4.8 1400 8.3 6.2
SIZE 2
Air flow m3/h Total heat kW Sensible heat kW 1000 6.7 5.0 1550 9.8 7.3 2100 12.5 9.4
SIZE 3
Air flow m3/h Total heat kW Sensible heat kW 1500 10.3 7.7 2100 12.9 9.7 3000 16.3 12.2
SIZE 4
Air flow m3/h Total heat kW Sensible heat kW 2400 15.5 10.0 3800 22.0 14.6 5300 26.1 18.0
NOTE: For correct working of the unit it must be installed a thermostatic valve (not supplied)
15
100 90 80 70 60 50 45 40 35 30
25
25
20
20
15
15
10 9 8 7 6 5
10 9 8 7 6 5
500
600
2000
3000
4000
5000
The table shows the water pressure drop in kPa (10 kPa = about 1 m of W.G.) of each unit with either 2, 3, 4, or 6 row battery against the water flow in l/hr at a mean water temperature of 75C. For different M.W.T. the correction factor (K) must be applied. 16
C K
10
20
30
40
50
60
70
80
90
CARBON FILTER
On request, the carbon filter can also be fitted in the electrostatic filter section. It is highly efficent for the purification of the air from gaseous pollutants and odours.
OPERATING PRINCIPLE OF THE ELECTROSTATIC FILTER CRYSTALL SABIANA The air is sucked in and first passes a mechanical prefilter, which keeps away particles of more than 50 m (dust, insects, etc.) (Phase 1)
CARBON FILTER
PHASE 4
Then the smallest particles (50 0.01 m) are exposed to an intensive ionic field and are polarized. (Phase 2)
PHASE 3
The charged particles passing through the second filter section, are pushed back by the anode and attracted to the collection surfaces by a strong, inducted magnetic field. (Phase 3)
POLARIZED ELECTRODE
ELECTROSTATIC FILTER
PHASE 2
IONIC FIELD
The air which leaves the unit is free from polluting particles. The carbon filter (supplied on request) purifies the air from gaseous pollutants and from odours. (Phase 4)
PRE-FILTER
PHASE 1
17
example
pollen
particle m
10 100
origin
Outdoor Indoor
dangers
May cause harmful allergic reactions May cause allergic reactions
annotations
Derived from plants in certain periods of the year Present during the whole year with max. concentrations during wet periods and in humid environments They can be transported on other particles, on the body and the clothes
moulds
3 10
Indoor Outdoor
bacteria
0.3 30
virus carbon powder synthetic and mineral fibre lead powder tobacco smoke
Indoor Outdoor pipes filters humidifiers Outdoor (Indoor) Outdoor Indoor Outdoor Indoor
Eventual diseases
Irritation of the skin, the lungs and the eyes Neurological problems in children A high risk of lung cancer, respiratory diseases, irritations of the eyes, the nose and the throat, allergic and olfactory problem Olfactory problem May cause allergic reactions Carcinogenic
0.3 10
2 30
0.005 1
18
Crystall electrostatic filter Recommended fresh air inlet levels for environmental ventilation according to the regulations of ASHRAE STD 62-1989
Type of environments meeting rooms cocktail bars/lounges restaurants hotel rooms offices coffe-housefast food schoolrooms smoking rooms residences big department stores 7 100 50 70 max. fresh air occupation inlet levels with persons m3/h per person /100m2 50 100 70 36.5 54 (1) 36 (1) 54 (2) 36 36 29 108 (3) (4) L/s per person 10 15 (1) 10 (1) 15 (2) 10 10 8 30 (3) (4)
ASHRAE 62-1989 standard: 1) The use of an high-efficiency filter is recommended 2) L/s m2/h per room 3) Spotted air extractions are recommended 4) 0.35 volume/hour, but not less than 8 L/s (29 m2/h) per person 5) L/s m2/h per square metre of surface
ground floor and basement upper floors dressing rooms stores theatres ticket offices theatres miscellaneous theatres audience-room shops
30 20 5 60 150 150
CS = = = = = =
ppm
= = = = = =
Example of the CO2 concentration with a phisycal activity of 1.2 MET. (1 MET = 18.4 BTU/h x Ft )
2
= Mean quantity of pollutant for each cigarette (Leaderer und Cain 1983) ** = K empirical constant (setting and plating factor A.E. Wheeler 1988)
19
OCEAN
AIR FLOW m3/h 650 1000 1400 1150 1550 2100 1750 2300 3000 2500 3800 5300
MAX ROOM VOLUME m3 160 250 350 280 380 520 430 570 750 620 950 1320
20
Crystall electrostatic filter + carbon filter SFE electrostatic filter section and FCA carbon filter
Pre-filter Electrostatic filter Carbon filter (optional extra)
DIMENSIONS 1 2 3 4 335 415 515 515 300 380 480 480 950 950 950 1500 840x112 840x112 840x112 1390x112 2 3 4 4 7.8 8.5 10 17
CIF
Remote control 3 speed switch and electrostatic filter switch
Wiring diagram
21
Accessories
Filter section
SFS
GAS
Synthetic, re-usable pleated filter, efficiency according to ASHRAE 84%, Eurovent EU3 class. Dimension: model 1 = 290x870x48 model 2 = 370x870x48 model 3 = 470x870x48 model 4 = 470x1420x48 The standard filter extraction is from the bottom, any different need must be specifically requested. Filter section with inlet grid
Mod. A B
1 225 820
2 325 820
3 425 820
4 425 1380
FGR
PAG
Mod. A B
1 318 950
2 398 950
3 498 950
4 498 1500
Mod. A B
1 318 950
2 398 950
3 498 950
4 498 1500
FSR
Panel with inlet grid to be installed on the fan section or on the air box
PGA
Mod. A B
1 318 950
2 398 950
3 498 950
4 498 1500
Mod. A B
1 300 950
2 380 950
3 480 950
4 480 1500
22
Accessories
Inlet damper
SRA
PMB
Model A B
1 300 950
2 380 950
3 480 950
4 480 1500
Model A B
1 318 950
2 398 950
3 498 950
4 498 1500
PAS
PMC
Model A B
1 318 950
2 398 950
3 498 950
4 498 1500
Model A B C
PDS
PMS
Model A B C
Model A B C
Accessories
Outlet grid with double louvres
BMA
Humidification section
SUD
Deck fill humidification with 2-way valve controlled by a room humidification sensor (not supplied). The maximum water pressure feeding is 2 Bar.
Model A B
1 225 820
2 325 820
3 425 820
4 425 1380
BEL
Mod. 1 (for rows)
ROWS 2/3/4/6 4+2 / 6+2 335 335 300 600 480 480 950 950 200 200
A B C D E
MODEL A B C D E
BRC
Suspencion brackets Galvanized steel angle brackets for either ceiling mounting or wall mounting.
SQS
Made in galvanized and painted steel, complete with brackets and securing screws. It is mounted on the bottom of the battery section and has a 15 mm diameter connection. A tube should be connected and taken to a suitable drain.
Model Weight kg
1 2.9
2 3.9
3 4.9
4 7.3
24
Code
9060160
- For Ocean size 1 and size 2 only. - ON-OFF switch and 3 speed switch. - Without thermostatic control.
LEGEND
MO-3V TMO-T E CH TME TMM G B M A R W = = = = = = = = = = = = MO-3V terminal board TMO-T terminal board Water valve Remote Summer/Winter switch TME low temperature cut-out thermostat TMM low temperature cut-out thermostat Yellow/Green Light Blue Brown Orange Red White
Identification
TMO-T
Code
9060161 For Ocean size 1 and size 2 use TMO-T only. For Ocean size 3 and size 4 use TMO-T + SEL-S (Code 9070110). ON-OFF switch. 3 speed switch. Summer/Winter switch. Electronic room thermostat for fan or valves control (ON-OFF). It allows to control the low temperature cut-out thermostat (TME). It allows to control the summer or winter cycle with centralized and remote switch, or an automatic change-over fitted on the water pipe (for 2-tube installations only).
25
Code
9053022
Identification
VAR
Code
3021051
Identification
SEL-S
Code
9079110
RECEIVING BOARD FOR CENTRALIZED CONTROL It allows to control up to 8 units with one TMO-T centralized thermostat using one SEL-S speed selector for each unit.
Identification
TME
Code
3021091 It stops the fan when the water temperature is lower than 38C and it starts the fan when is higher than 42C.
To be fitted between the coil fins; when connecting the control, the TME probe cable must be separated from the power supply wires. To eliminate cold air blow. To be used with TMO-T control.
Identification
TMM
Code
9053048
TMM low temperature cut-out thermostat To be installed in contact with the hot water circuit. To eliminate cold air blow. Installed by the installing engineer. To be used with MO-3V control. For units working on heating only.
26
It stops the fan when the water temperature is lower than 30C and it starts the fan when is higher than 38C.
RED BROWN
The descriptions and illustrations provided in this publication are not binding: Sabiana reserves the right, whilst maintaining the essential characteristics of the types described and illustrated, to make, at any time, without the requirement to promptly update this piece of literature, any changes that it considers useful for the purpose of improvement or for any other manufacturing or commercial requirements.
Air Conditioning
OCEAN - EX - 05/10
SABIANA
ENVIRONMENTAL COMFORT
Sabiana s.p.a.
via Piave, 53 20011 Corbetta Milano Italy phone +39.02.97203.1 r.a. / +39.02.97270429 / +39.02.97270576 fax +39.02.9777282 / +39.02.9772820 www.sabiana.it info@sabiana.it
COD. A4350100
I/05/10