Sei sulla pagina 1di 6

Fluids/Solids Handling

Dont Get Burned


Courtesy Westech Industrial Ltd.

Picking Dry-Type Flame Arresters


Stanley S. Grossel, Process Safety & Design, Inc.

lame arresters prevent the propagation of a ame front from outside of a storage tank or process vessel to the inside, or of a ame between interconnected items of equipment. This article is based on a recent book by the author published by AIChEs Center for Chemical Process Safety (CCPS) that covers a wide range of topics on ame arresters (see sidebar). Here, we will look at the major dry types available and their general uses. These devices employ a medium, known as the matrix, inside a casing that extinguishes the ame and, when appropriate, stops a shock wave from a detonation. Typical media are crimped-metal-ribbon, expanded metal and parallel plates. There are also proprietary dry-type aressters, as well as other types of ame arresters that do not contain a matrix; these nd service where conventional dry types are not suitable or expensive. Among these are hydraulic (liquid-seal) and packed-bed arresters, velocity ame stoppers, high-velocity vent-valves, and conservation vent-valves. Space does not permit discussing these other types here, but the book covers them in detail.

These commonly used devices rely on an internal medium to extinguish flame fronts and take the punch out of shock waves, protecting piping and equipment, as well as personnel. Selecting such equipment involves considering the probable type of combustion, placement in the plant and other factors.
The number of directions that an arrester may encounter a ame. If it is from only one direction, then the device is unidirectional; if from either direction, a bidirectional arrester is needed. The latter is either symmetrically constructed or has been tested and certied for deagrations or detonations approaching from either direction. Back-to-back use of unidirectional ame arresters is generally not cost-effective. Flame arresters are also grouped according to certain characteristics and operational principles, by their process location, combustion conditions, or arrester matrix.

Classication schemes for dry types There are various ways to classify dry-type arresters: Deagration vs. detonation models Direction of ame approach for which the arrester is designed to operate in a pipe. The pipe that connects the arrester with an identied ignition source is known as the unprotected side of the arrester. The pipe connecting the arrester to at-risk equipment that must be protected from ame penetration is the protected side.

Process location When an arrester is located directly on a vessel or tank vent-nozzle, or on the end of a vent line from the ventnozzle, it is called an end-of-line arrester, and usually is

60

www.cepmagazine.org

October 2002

CEP

Deflagration and Detonation Flame Arresters


by Stanley S. Grossel Published by AIChES Center for Chemical Process Safety The book is written for chemical engineers and other technical personnel involved in the design, operation and maintenance of facilities and equipment where deflagration and detonation flame arresters (DDFAs) may be required. It covers a broad range of issues concerning the operation, selection, installation and maintenance of DDFAs, including an overview of deflagration and detonation prevention and protection practices; an overview of combustion and flame propagation and how DDFAs halt propagation; deflagration and detonation flame arrester technology; installation in process systems; regulations, codes and standards; illustrative examples, calculations and guidelines for DDFA selection; appendices, including a glossary, a flame-arrester specification sheet for vendor quotation, and a listing of flame arrester manufacturers. To order: Call (800) 242-4363; Fax: (301) 843-0159; outside the U.S.: (301) 374-2522; E-mail: xpress@aiche.org. For a complete listing of AIChEs publications, see www.aiche.org/pubcat/.

installed to stop deagrations. These devices are commonly installed on atmospheric-pressure storage tanks, process vessels and transport containers. If the vented vapors are ignited accidentally, say by lightning, then the arrester will prevent the ame from spreading to the inside of the vessel. Such ame arresters do not stop detonations. End-ofline ame arresters can be placed on vessels or tanks located inside buildings (Figure 1a) and outdoors as well (Figure 1b). If the arrester is not connected to the end of a line, then it can be placed in-line. Such arresters can be built to withstand deagrations or detonations (if properly designed for these more-extreme conditions), depending on the length of pipe and pipe conguration on the unprotected side of the arrester, and any restrictions on the protected side (e.g., the inclusion of valves or elbows). A detonation ame arrester is used where the run-up distance (that from the source to the arrester) is sufficient for a detonation to develop. Some in-line deagration ame arresters are called pipe-away or vent-line arresters. These are also installed on the vent-nozzles of atmospheric-pressure tanks and vessels, but have a short length of pipe attached to them to direct the vapors, and possibly ames, away from the tank or vessel roof (Figure 2). The maximum length of pipe from the discharge side to the atmosphere is usually 20 ft for Group D gases, and is a function of the pipe size and the manufacturers design. For other gases (Group B or Group C), the maximum distance must be established by proper testing with the gas mixture and pipe diameter. The groups are established by the National Electrical Code (NEC) of the National Fire Protection Association (NFPA) (1). Typical Group B gases include butadiene and ethylene oxide, as well as gases that contain

more than 30% of hydrogen by volume, among others. Those in Group C include ethylene, ethyl ether and other gases of equivalent hazard. Typical Group D gases include methane and other alkanes, alcohols, benzene and acetone. In establishing how arresters can be used safely with certain gases, if turbulence-promoting devices (bends, elbows, tees, valves, etc.) will be present in the actual plant, then they must be included in the test setup. During the test, the turbulence promoters must be placed using the exact geometry of a specic installation. It is essential to ensure that run-ups to detonations cannot occur in an actual system. For some fast-burning gases, such as hydrogen/air mixtures, the run-up distance can be appreciably less than the 20-ft limit
End-of-line Deflagration Arrester Weather Hood End-of-line Deflagration Arrester

Roof

a. Installation on vent line from indoor vessel

b. Installation on vent line from outdoor tank

s Figure 1. End-of-line arresters are used with indoor and outdoor tanks
and vessels.

CEP

October 2002

www.cepmagazine.org

61

Fluids/Solids Handling

Detonation ame arresters withstand and extinguish high-speed, high-pressure ame fronts. Therefore, these devices must be able to resist the mechanical effects of detonation shock waves while quenching the ames. Some designs have a shock absorber in front of the ame-arresting element to lessen the effect of the high-pressure wave and its dynamic energy, and to split the front before it In-line Deflagration reaches the arrester element. Flame Arrester Detonations in piping have velocities of about 6,000 ft/s or more, and, in closed process vessels and equipment, can generate pressures from 20100+ times the initial value. When installed in a vent-manifold, these arresters Storage Tank on the tanks can be uni- or bidirectional, depending upon the manufacturers recommendations. Detonation arresters preferably should be installed vertically, so if liquid is pres Figure 2. In-line deagration arrester has a short pipe to direct vapors or sent, the arrester will drain. If they must be installed horiames from the tank roof. zontally, drain connections are needed. Most detonation arresters Detonation Flame Emergency Vent Common Piping have crimped-metal-ribbon eleArrester to Atmosphere Header ments, although expanded-metal (Bidirectional) cartridges are also used. Detonation arrester elements are usually Central VaporProcessing longer than the elements used for Unit (Flare, deagration arresters. Scrubber, etc.) Some cases have been reported where a detonation arrester failed to stop a deagration (2). This occurs when there is a restriction (e.g., a valve) on the protected side of the Manifold device. Roussakis and Lapp (3) prePiping sent test data on three types of inline ame arresters that corroborate Detonation Flame this seemingly anomalous behavior. Arrester (Unidirectional The causes are complex and depend or Bidirectional) on such factors as the effect of runup length on the relative overpress Figure 3. Detonation arresters help to ensure safety of a vent-manifold system. sure (the ratio of the pressure rise caused by the ame front to the abfor Group D gases. In all cases, consult the manufacturer solute operating pressure at the time of ignition), ow refor the recommended maximum run-up length. striction on the protected side, and the absolute operating An in-line detonation ame arrester must be used wherpressure. The ame-quenching capability of a ame arrester ever a detonation may occur. This is always a strong possiis determined by the initial operating pressure. The new bility in vent-manifold (vapor-collection) systems, where CCPS book previously mentioned explains this seemingly long pipe-runs provide sufficient distances for a deagraanomalous behavior. tion-to-detonation (DTD) transition to occur. Figure 3 Regulations and requirements shows a typical installation of in-line detonation arresters in a vent-manifold system. There are no regulations or other legal requirements for installing ame arresters in vapor-collection (vent-maniCombustion conditions fold) systems in chemical and petrochemical plants. HowDeagration arresters on tanks normally cannot withever, many chemical companies follow the U.S. Coast stand signicant internal pressure and cannot stop detonaGuard regulations as a guide. tions. Typical ame speeds of a deagration in pipes range The installation of ame arresters should be considered from 10200 ft/s. Deagrations of fuel/air mixtures usually for vacuum pumps, activated-carbon adsorbers, and other generate pressures of 812 times the initial pressure in equipment that emits ammable vapors and/or can serve as closed process vessels and equipment. an ignition source.
Vent Piping

62

www.cepmagazine.org

October 2002

CEP

Matrix constructions for dry arresters Dry-type deagration and detonation arresters have an internal arrester element that quenches the ame and cools the products of combustion. There are many types of arrester elements. The most common are crimped-metal-ribbon, parallel-plate, expanded-metal-cartridge, perforatedplate, wire-gauze (and wire-gauze in packs), sinteredmetal, metal-shot in small housings, and ceramic balls. Some of these arresting elements are often used in both deagration and detonation arresters. Compressed wire-wool ame arresters are available in the U.K., but are not sold commercially in the U.S. Crimped-metal-ribbon (CMR) This element is one of the most widely used types, especially for detonation ame arresters (Figure 4). CMR arresters are made of alternating layers of thin, corrugated metal ribbons and at metal ribbons of the same width, which are wound together on a mandrel to form a manylayered cylinder of the desired diameter. The thickness of the cylindrical element is equal to the ribbon width. The spaces between the corrugations and the at ribbon provide multiple small gas passages of approximately triangular shape. Elements can be made in a variety of crimp heights, ribbon and element thicknesses, and diameters. Some major advantages are: (1) they can be manufactured to within close tolerances; (2) they are sufficiently robust to withstand mechanical and thermal shocks; and (3) they have a fairly low resistance to ow (pressure drop) because usually only about 20% of the face (cross-sectional area) of the arrester is obstructed by the ribbon. The layers of ribbon must not spring apart because this would increase the crimp height and render the device ineffective. Since effectiveness in quenching a ame diminishes rapidly with thin arresters, the elements should be at least 0.5 in. thick. One manufacturer produces a composite design consisting of multiple CMR elements with diverter shields (turbulence-inducing devices) between the elements. CMR elements can be made circular, rectangular or square, depending upon the shape of the pipe or housing. The elements are often reinforced by inserting metal rods radially through the assembly. CMR arresters may use single or multiple elements with the crimp perpendicular to the ribbon. Newer designs include deectors between element sections to redistribute ow. A drawback of CMR arrester elements is their sensitivity to damage during handling. This must be considered during maintenance. Damage may lead to either enlarged channels that allow ame penetration, or to channel collapse that increases the pressure drop. Therefore, the manufacturers instructions should be strictly followed during maintenance and cleaning. Another possible problem is that the small channel size may make the elements more susceptible to fouling due to solids deposition, and regularly scheduled or predictive maintenance is essential when this is possible.

Element Diameter

Crimped Ribbon Flat Ribbon Element Thickness (Ribbon Width)

s Figure 4. Crimped-metal ribbon ame arresters are widely used to


stop detonations.

CMR elements are installed in housings in two ways. In one method, the element can be removable, in which case it can be cleaned and reinstalled or replaced without taking the housing from the piping. In the other method, the element is fused to the housing. Thus, the entire unit must be removed from the pipe to clean the element. If the element is damaged, the unit must be replaced. Many test protocols (e.g., those of the U.S. Coast Guard and Factory Mutual) will not approve this type of element. CMR arresters are used to stop deagrations and detonations. They are especially useful for detonations, since the apertures can be made small, which is necessary to stop the ame and pressure front.

Parallel-plate Parallel-plate elements are used in both end-of-line and in-line (vent-line) deagration arresters (Figure 5). They are not used as detonation arresters, however. These devices contain solid metal plates or rings arranged edgewise to the gas ow and separated from each other by a small spacing.
s Figure 5. Parallel
plate arresters are relatively robust, inexpensive and easy to dismantle.

CEP

October 2002 www.cepmagazine.org

63

Fluids/Solids Handling

s Figure 6. Expanded-metal cartridge ame arresters are suited for use with
reactive monomers.

The spacing is maintained by gaskets or nubs on the plates. Parallel-plate devices are relatively inexpensive, robust and readily dismantled for cleaning. Their main disadvantage is their weight, especially in large sizes with housings made of steel or stainless steel. Heavy units may require independent support when mounted on a tank nozzle.

Expanded-metal cartridge (EMC) EMC elements are comprised of a sheet of expanded metal that is wrapped similarly to a cartridge lter element (Figure 6). Diamond-shaped openings in the sheet are not aligned during wrapping, so that there is no direct path from one layer to the next. Such a design tends to reduce the incidence of plugging by suspended solids, since they will not be heavily deposited on the inlet face. The elements are normally offset, rather than inline, to the gas ow so that the ame passes radially toward the cartridge axis. This creates a relatively large inlet surface area that further reduces plugging problems. Another advantage is that liquids and solids drop out into an external container that surrounds the inlet. This may make these units suitable for use with reactive monomers. Disadvantages include support problems for larger pipe diameters due to their size and weight, so, often, EMCs must be located at or near grade to facilitate maintenance. These arresters are suited for deagration and detonation, and are designed for bidirectional ow. EMC elements are manufactured in different congurations. One is a cylinder that ts into a housing with offset inlet and outlet connections. Another is a thimble shape that is welded to a ange for insertion in an in-line, straight-through housing. Perforated-plate These elements are used primarily for deagration arresters (Figure 7a). The perforated plates are usually metal (stainless steel), but some also incorporate perforated refractory disks and gauze pads in combination with the metal plates. They are available with a range of hole diameters and plate thicknesses, but the most-common devices have hole diameters and plate thicknesses analogous to the corresponding dimensions of coarse-gauze arresters. Perforated-metal arresters have greater mechanical strength and are less likely to overheat than gauze arresting elements, but the percentage of the plate area available for gas ow is even less than that for the corresponding gauzes (4).

Wire gauze These arresters use either single gauzes, or a series or pack of gauzes (Figure 7b). They are manufactured such that the aperture size is carefully controlled. Single layers offer limited performance. Gauzes coarser than 28 mesh to the linear inch are ineffective at quenching a ame, and those ner than 60 mesh to the linear inch are liable to become blocked. The main advantages of gauzes are their low cost, ready availability and ease of tting. Their disadvantages include limited effectiveness at quenching highvelocity ames, the ease with which they are damaged, and the high pressure drop of gases through ne gauzes. Gauzes can be combined into multiple-layer packs, and if the gauzes are all of the same mesh width, they are more effective than single constructions. However, the increase in effectiveness is limited. Combined packs of a coarse and ne mesh are less effective than the ne gauze alone. A disadvantage of gauze packs is that the good contact required between gauze layers may be difficult to guarantee in practice without fusing and calendering (4). Since gauzes have limited effectiveness in quenching high-velocity ames, they are only used as end-of-line deagration ame arresters. Sintered metal Sintered metal (Figure 7c) is effective as an arresting element, but it offers a high resistance to gas ow, and is suitable only when the gas ow is low or high pressure is available (e.g., on a compressor discharge line). Banks of sintered-metal ame arresters can be installed in parallel to offset the pressure-drop problem. Their small apertures tend to block easily, so these ame arresters should only be used with clean gases. One advantage is that they can be produced in a variety of shapes to suit various applications. How they are mounted is critical because the clearance between the arresting element and the housing must be less than the arrester passage dimensions (2). If a ame stabilizes on the surface of these elements, there is a risk that it will eventually burn its way through the sintered-metal disk. For this reason, these arresters may incorporate a pressure- or temperature-activated ow cutoff-device. The apertures can be made so small that these arresters are able to quench detonations, provided that they have sufficient mechanical strength. Care is required to ensure a secure anchorage of the sintered element to prevent leakage around it caused by the impact of a shock wave (4). The main uses of these arresters are in the sensing heads of ammable-gas detectors and in ame arresters for gas welding (oxy-acetylene) equipment. Ceramic balls In these devices, ceramic (alumina) balls are housed between stainless-steel grids (Figure 7d). These arresters have been tested for NEC Groups C and D gases, as well as for hydrogen. They have also been accepted by the U.S. Coast Guard. The ceramic balls are claimed to be cleaned

64

www.cepmagazine.org

October 2002

CEP

Cell Housing

Heat Absorption into Alumina Ceramic Media

a. Perforated Plate

b. Wire Gauze and Gauze Packs

s Figure 7. Four other


types of matrixes used in dry-type arresters.

Protected Side c. Sintered Metal d. Ceramic Balls

Flame Front

easily and totally resistant to oxidation and corrosion. Also, the balls will withstand severe ame stabilizations without suffering any deterioration.

Metal shot Metal-shot arresters consist of a tower or housing lled with various sizes of metal shot (balls) in about nine zones. The size varies from 47 mesh for the largest balls and from 4060 mesh for the smallest ones. The larger balls are arranged in the outer layers of a zone with the smaller shot in the inner layers. A typical unit is 6 in. O.D. 15 in. long, with 3/4-in. connections. The size of the apertures depends on the diameter of the shot, which is packed tight-

ly together within the container to prevent movement. One advantage of this ame arrester is its ease of assembly and disassembly for cleaning. Another is that it can be made sufficiently robust to withstand detonations. One design using nickel shot contained in a thick-walled housing successfully stops acetylene detonations at initial pressures from 15 to 400 psig. The disadvantages include their weight and relatively high resistance to gas ow. In addition, the size of the apertures is not controlled directly. Movement of the balls during a deagration or detonation can lead to failure of the CEP device (4).
STANLEY S. GROSSEL is president of Process Safety & Design, Inc. (41 Sussex Road, Clifton, NJ 07012-2016; Phone and Fax: (973) 779-8579; E-mail: psadi28@aol.com). He consults in process safety, loss prevention, solids handling and processing, air-pollution control and batch-process design. Grossel has 52 years of experience in process design and application of safety and loss prevention for pharmaceutical, organic, inorganic and petrochemical plants. Previous employers include Hoffmann-LaRoche, The Lummus Co., and Chemical Construction Corp. He has been a Fellow of AIChE since 1980 and received the Safety and Health Div. Norton Walton/Russell Miller Award for outstanding contributions to loss prevention. He is a past chair of that division, is currently active in AIChE committee work, and lectures and writes publications for the Institute. Grossel holds bachelors and masters degrees in chemical engineering from the City College of New York and the Polytechnic Institute of Brooklyn, respectively. He is also a member of ACS, NFPA, CMA (now the American Chemistry Council), the National Association of Manufacturers and the Combustion Institute.

Literature Cited
1. National Electrical Code, NFPA 70, National Fire Protection Association, Batterymarch Park, Quincy, MA (www.nfpa.ord/catalog/ product.asp?category%5Fname=&pid=7099sb) (1999). 2. Howard, W. B., Flame Arresters and Flashback Preventers, Plant/Operations Progress, 1 (4), pp. 203208 (Oct. 1982). 3. Roussakis, N., and L. Lapp, A Comprehensive Test Method for Inline Flame Arresters, Plant/Operations Progress, 10 (2), pp. 8592 (Apr. 1991). 4. Health and Safety Executive, Flame Arresters and Explosion Vents, Health and Safety Series Booklet HS(G)11, HSE, London, U.K. (1980).

CEP

October 2002 www.cepmagazine.org

65