Sei sulla pagina 1di 12

Ball float steam traps

for pressures up to 32 bar

The only ball float steam trap with over 50 years of experience and constant development
The Spirax Sarco FT is the product of experience. First launched in the 1940's the FT has become the most advanced ball float steam trap available. Constant design improvements have made today's FT an extremely robust steam trap, ideally suited to the rigorous demands of any steam system. Unique amongst all ball float steam traps is the self-aligning main valve, waterhammer proof float assembly and corrosion resistant air vent. Such attention to detail ensures complete shut-off at all pressures and reliable operation for extended product life and minimal maintenance. Having an integral air vent and the options of a steam lock release (SLR) and drain cock tapping, the FT range is adaptable to all applications where ball float traps are recommended and instantaneous removal of condensate is required. With over three and a half million Spirax Sarco FT traps supplied to over 100 000 customers the Spirax Sarco FT has become the most widely used ball float steam trap in the world today.

Corrosion resistant stainless steel capsule type thermostatic element for near to steam temperature air venting.

Air vent increases cold condensate start-up capacity.

Waterhammer proof float and lever mechanism.

Asbestos free gasket.

Range and options


Connections Material Universal C Body design Size - DN Screwed Flanged Socket Cast SG Cast Stainless or vertical/ ENP version Drain rating 15 20 25 32 40 50 80 100 weld iron iron steel steel horizontal with with cock flow strainer SLR tapping FT14 PN16 q q q q q q q q q q q q q q FT14HC PN25 q q q q q FT43 PN16 q q q q q q q q q q q q FT47 PN40 q q q q q q q q q q FT450 ANSI 300 q q q q q q q q q q q q FT44 PN40 q q q q q q q q q q q q FT16 PN25 q q q q q q FT46 PN40 q q q q q q q q q Trap type Note: SLR is not available on FT43 and FT44 DN80 / DN100 and all vertical versions of FT43, FT44 and FT47. 32 bar versions of all float traps are only provided with a thermostatic air vent.

How it works
Cover can be rotated to suit pipework configuration (FT14 only). Others available in either horizontal or vertical orientation. On start-up a thermostatic air vent allows air to by-pass the main valve (1) which would otherwise be unable to escape (a condition known as 'air-binding') As soon as condensate reaches the trap, the float is raised and the lever mechanism opens the main valve (2). Hot condensate closes the air vent but continues to flow through the main valve. When steam arrives the float drops and closes off the main valve, which remains at all times below the water level, ensuring that live steam cannot be passed. In syphon drip pipes draining rotating cylinders or long drain lines, a steam pocket may form which can prevent condensate from reaching the trap (a condition known as 'steam locking'). If this is likely, a steam lock release (SLR) should be specified to bleed away the steam (3).

Steam lock release option.

Variety of seats optimises capacity at all pressures.

Self-aligning main valve.

FT14-C shown

Materials and pipe connections to suit every application.


q

User benefits
Compact and lightweight reducing installation costs. Immediate discharge with clean tight shut-off. No back-up of condensate ensures maximum plant efficiency. Robust construction to guarantee long life against waterhammer and vibration. Can be installed in both horizontal and vertical positions reducing installation problems. Large discharge capacity in relation to size. Stainless steel internals that can tolerate corrosive condensate. Spirax Sarco's guarantee of technical back-up knowledge and service. 3

q q

Typical applications
Ball float traps are the first choice for applications where the rate of heat transfer is high for the area of heating surface available: they are able to handle heavy or light condensate loads equally well and are not disturbed by wide and sudden fluctuations of pressures. Although compact in size, their discharge capacity is high and continuous ensuring maximum heat transfer: they are the best choice for draining both batch and continuous process plant with automatic temperature control. On all applications condensate is removed immediately it is formed.

Jacketed vessels
High productivity can only be achieved by fast and efficient removal of condensate and incondensible gases.

Separator drainage
Separator efficiency can only be maintained by removing condensate as it is formed which makes the float trap the ideal choice.

Unit heaters, heater batteries and driers


Since a large volume of condensate is produced from a small space, any accumulation of condensate or air causes uneven temperatures, poor control and corrosion. A float trap ensures efficient drainage when under positive differential pressure.

Heat exchangers
The float trap is ideal for handling a variable load normally associated with temperature controlled heat exchangers. Air and incondensible gases are also discharged efficiently to ensure rapid warm-up during start-up conditions. 4

FT14
Iron screwed
30 000 20 000 10 000 8 000 5 000 4 000 3 000 2 000
Condensate kg / h

Capacities
2
Differential pressure psi 20 30 50 3 4 5 10

100 200 60 000 50 000 40 000 30 000 20 000 10 000 5 000 4 000 3 000 2 000 1 000 500 400 300 200 100

F 2" F 2" T1 4-4 .5

T1

4-1

2" -14 14 FT
4

1 "HC 2"
(formally FT10)

"

1 FT T1

4-4

.5

T "F 1

1 14-

" 1"

1 000 500 400 300 200 100

F "

Sizes and pipe connections


", ", 1", 1", 1", 2" screwed BSP or NPT DN15, 20, 25 flanged BS 4504 PN16, ANSI 150 and JIS/KS 10 FT14 - ", ", 1" (DN15, 20, 25) horizontal / vertical connection FT14 - 1"HC, 1", 1" 2" horizontal only (formally FT10)

Materials
Body/cover
FT14 (",", 1", 1"HC, 1") SG iron (1", 2")

Bolting Gasket Internals

DIN 1693 GGG 40 / 40.3 Cast iron DIN 1691 GG25 Steel BS 3692 Gr. 8.8/ASTM A193 B7 Reinforced exfoliated graphite Stainless steel

50 40 30 0.1

HC -14 1" .5 T14 4-4 F 1 T " "F 1 &1 HC 1" .5 4-4 FT1 10 0 2 4 15, T1 DN 1" F " -10 ", T14 0F 2 4 , 5 4-1 N1 -14 FT1 ,D 4 " 0 1 2 FT 5, ", N1 1", ", D , "

4.5 14FT " &1

4-1

70 1014 2 3 45 0.2 0.3 0.5 1 Differential pressure bar (x 100 = kPa)

Note: Capacity shown above is based on discharge at saturation temperature. When discharge sub-cooled condensate the air vent provides extra capacity.

FT14X has an inbuilt strainer screen.

Operating range
Pressure psi g 87 116 145 174 203 232 250 482 200 1" - 2" (220C) 392 150 302 Steam saturation curve 212 100 122 50 32 0 0 6 8 2 4 10 12 14 16 Pressure bar g
0 29 58

Limiting conditions (ISO 6552)


Temperature C

Body design conditions PN16 PMA - Maximum allowable pressure 16 bar g TMA - Maximum allowable temperature: 250C (",", 1", 1"HC) 220C (1", 1", 2") Cold hydraulic test pressure 24 bar g Maximum differential pressure (DPMX) FT14 - 4.5 (4.5 bar) FT14 - 10 (10 bar) FT14 - 14 (14 bar)
A D E E F B B C FT14 ("-1") A FT14 (1"HC-2") D G

The product must not be used in red area.


FT14 (DN15 / DN20) E FT14 (DN25) E

C D D

Dimensions
Size " " 1" 1"HC 1" 1" 2" DN15 DN20 DN25 A 121 121 145 120 120 270 300 A A PN/ANSI JIS/KS 150 150 150 150 160 170 B 107 107 107 110 110 130 138 107 107 117

(approximate in millimetres) C 67 67 75 80 80 108 125 101 101 70 D 147 147 166 195 195 238 250 152 156 170 E 105 105 110 160 160 200 200 115 115 120 F 220 220 270 288 G 115 115 115 140 Weight kg 2.9 2.9 4.0 6.8 6.8 17.5 22.0 4.5 5.0 6.5

Temperature F

Condensate lb / h

" &1 HC 4-10 " 1 T1 F

FT43

Iron flanged
60 000 50 000 40 000 30 000 20 000 10 000 2

Capacities
3 45 Differential pressure psi 10 20 30 50 100 200 100 000
& 80 DN 100 4 N 3-1 D 0 4 1 DN FT 43FT 00 0 1 1 & 80 T43 50 -4.5 DN 0F DN 43-14 N5 T43 D F T 0 F 5 DN

80

00 &1

FT

43

-4.5

50 000 40 000 30 000 20 000 10 000 5 000 4 000 3 000 2 000 1 000 500 400 300 200 100 50

DN80 and DN100


Condensate kg / h

5 000 4 000 3 000 2 000 1 000 500 400 300 200 100 50 40 30 20 0.1

DN15 DN50

Sizes and pipe connections


DN15, 20, 25, 40, 50, 80 and 100 flanged BS 4504 PN16 ANSI flanges available on request DN15 - 50 horizontal / vertical connection DN80 - 100 horizontal

Materials
Body/cover Bolting Gasket Internals DN15 - 50 DN80 - 100 DN15 - 50 DN80 - 100 DIN 1691 GG25 DIN 1691 GG20 BS 3692 Gr. 8.8 BS 3692 Gr. 8.8 and BS 4439 Gr. 8.8 Reinforced exfoliated graphite Stainless steel Cast iron Cast iron Steel Steel

-10 T43 0F 4 DN 4.5 43FT 5 2 DN 0 3-1 FT4 5 2 4 DN 3-1 FT4 .5 5 2 3-4 DN FT4 0 2 15, DN 0 3-1 FT4 0 2 15, DN 4 3-1 FT4 0 2 15, DN

10 14 0.2 0.3 0.5 1 2 3 45 Differential pressure bar (x 100 = kPa)

Note: Capacity shown above is based on discharge at saturation temperature. When discharge sub-cooled condensate the air vent provides extra capacity.

Operating range
Pressure psi g 87 116 145 174 203 232 428 220 392 200 A, B 150 302 Steam saturation curve 100 212 122 50 B A 32 0 8 0 6 2 10 12 14 16 4 Pressure bar g
0 29 58

Temperature C

Limiting conditions (ISO 6552)


Body design conditions PN16 PMA - Maximum allowable pressure 16 bar g TMA - Maximum allowable temperature 220C Cold hydraulic test pressure 24 bar g Maximum differential pressure (D PMX) FT43 - 4.5 (4.5 bar) FT43 - 10 (10 bar) FT43 - 14 (14 bar)

The product must not be used in red area A - A Flanged BS 4504 PN16 B - B Flanged ANSI 150 flat face (DN15, 20, 80 and 100), ANSI 125 (DN25 - 50)
E E

B C A D F F D FT43 (DN80 / DN100)

C A FT43 (DN15 - DN50) E F D

Dimensions
Size DN15 DN20 DN25 DN40 DN50 DN80 DN100 6 A 150 150 160 230 230 350 350 B 54 54 110 128 140 140 140 C 54 54 80 110 126 123 123

(approximate in millimetres)

D 188 195 245 330 340 387 387

E 110 110 160 200 200 200 200

F Weight (kg) 155 5.5 165 5.5 215 8.3 200 21.5 225 21.5 310 72.0 310 74.0

Temperature F

Condensate lb / h

DN

40

FT

4.5 43-

DN

40

3 FT4

-14

FT47

DIN specification SG iron flanged


30 000 20 000 10 000 2 3 45

Capacities
Differential pressure psi 10 20 30 50 100 200 400

DN

F 50
F

T4

7-4

.5

60 000 50 000 40 000 50 2 DN -21-3 30 000 47 FT 20 000


F 7T4 2132

5 000 4 000 3 000 2 000


Condensate kg / h

DN

50 40

7T4

10 .5

DN

FT

4 477

10 000 5 000 4 000 3 000


Condensate lb / h Temperature F

1 000 500 400 300 200 100 50 40 30

Sizes and pipe connections


DN15, 20, 25, 40 and 50 flanged BS 4504 PN40 ANSI flanges available on request

Materials
Body/cover Bolting Gasket Internals SG iron DIN 1693 GGG 40.3 Steel DIN 17240 21 Cr Mo V57 Reinforced exfoliated graphite Stainless steel

20

.5 7-4 T4 F 0 25 DN T47-1 F 5 2 4.5 -14 DN FT47 T47F 5 0 2 N2 DN 10 &D 4715 FT N 0 D N2 4 &D 15 7-1 N T4 D 0F 2 N &D 21 15 47DN FT 0 N2 &D -32 15 T47 N D 0F 2 N &D 15 DN

4 DN

0F

T4

-10
1 7-2 T4 5F 2 -32 DN T47 5F 2 DN

2 000 1 000 500 400 300 200 100 50 40 30

10 2 3 4 5 10 20 32 0.1 0.2 0.3 0.5 1 Differential pressure bar (x 100 = kPa)

Body and cover from TV approved foundry.

Note: Capacity shown above is based on discharge at saturation temperature. When discharge sub-cooled condensate the air vent provides extra capacity.

Operating range
0
Temperature C

150
A, B

Pressure psi g 300

450

Limiting conditions (ISO 6552)


Body design conditions PN40 PMA - Maximum allowable pressure 40 bar g TMA - Maximum allowable temperature 300C Cold hydraulic test pressure 60 bar g Maximum differential pressure (D PMX) DN FT47-4.5 FT47-10 FT47-14 FT47-21 FT47-32 15,20,25 4.5 bar 10 bar 14 bar 21 bar 32 bar 40,50 4.5 bar 10 bar 21 bar 32 bar

300 200 100 0 0

500 572 292 212


A

Steam saturation curve B

32

10

20 Pressure bar g

30

40

The product must not be used in red area A - A Flanged BS 4504 PN40 B - B Flanged ANSI 150

C A E D F

Dimensions
Size DN15 DN20 DN25 DN40 DN50 A 150 150 160 230 230 B C 80 80 80 80 115 85 130 115 141 123

(approximate in millimetres)

D 215 225 276 326 332

E 120 120 170 200 200

F 155 165 215 200 225

Weight (kg) 10.8 10.8 15.0 33.0 43.0 7

ASTM specification Steel screwed Socket weld Flanged


DN20 DN50

FT450

Capacities
2 345 150 000 100 000 50 000 40 000 30 000 20 000 10 000 5 000 4 000 3 000 2 000 1 000 500 400 300 200 100 50 40 30 20
.5 0-4 T45 F 50 DN
DN80 & 100 0 FT45

Differential pressure psi 10 20 30 50 100 200 400 200 000 150 000 100 000

-10 450 FT

450 FT -32 -21 -14

50 000 40 000 30 000 20 000 10 000


Condensate lb / h Temperature F

Condensate kg / h

DN80 and DN100

Sizes and pipe connections


DN20, 25, 40, 50, 80 and 100 screwed NPT, socket weld, flanged BS 1560 class 150, 300 or 600

Materials
Body/cover Bolting Gasket Internals ASTM A216 WCB ASTM A193 B7 and Steel A194 2H Reinforced exfoliated graphite Stainless steel Steel

4.5 5032 FT4 210 4 140 DN 5 FT4 40 50 FT4-21 DN 0 0-1 5 5 . 4 4 32 FT 505040 FT4 0-10 DN FT4 25 5 2 DN FT45 14 DN 25 DN FT450 5 . 5 4 2 5 DN FT4 20 10 DN 50FT4 0 2 DN 14 50FT4 0 2 DN 32 50F T4 0 2 DN

5 000 4 000 3 000 2 000 1 000

500 400 300 200 100 50 30

10 10 20 32 2 3 45 0.1 0.2 0.3 0.5 1 Differential pressure bar (x 100 = kPa)

Note: Capacity shown above is based on discharge at saturation temperature. When discharge sub-cooled condensate the air vent provides extra capacity.

Operating range
Pressure psi g
0 150 300 450 550

Limiting conditions (ISO 6552)


Body design conditions ANSI 300 PMA - Maximum allowable pressure 50 bar g TMA - Maximum allowable temperature 400C Cold hydraulic test pressure 75 bar g Maximum differential pressure (D PMX) FT450-4.5 (4.5 bar) FT450-10 (10 bar) FT450-14 (14 bar) FT450-21 (21 bar) FT450-32 (32 bar)
D

Temperature C

400 300 200 100 0 0 10

725 752 572 392 212 A 32 50

A, B Steam saturation curve B 30 20 Pressure bar g


40

The product must not be used in red area. A - A Screwed, socket weld, flanged ANSI 300 and 600 B - B Flanged ANSI 150

B B C F D

C A A1 FT450 (DN20 - DN50) E F A A1

FT450 (DN80 / DN100)

Dimensions
Size DN20 DN25 DN40 DN50 DN80 DN100 8 A 155 165 250 300 705 A1 255 257 356 406 988 988

(approximate in millimetres)

B C 65 65 115 84 130 80 141 90 431 171 431 171

D 163 208 250 255 203 203

E 120 160 195 195 813 813

F Weight (kg) 189 10.8 234 15.0 282 29.0 295 32.0 444 220.0 444 220.0

FT44

DIN specification Steel flanged


50 000 40 000 30 000 20 000 10 000 5 000 4 000 3 000 2 345

Capacities
Differential pressure psi 10 20 30 50 100 200 400

100 000
4 4.5 80 T4 44DN 100 F FT 0 0 N &1 0 &D 44 80 4-1 FT -32 DN T4 F 1 2 0 0 1 0 &1 T44 F 0 8 50 4.5 DN DN 44FT 0 5 DN 10 .5 44FT 4-4 0 T4 40 F N 4-1 D 40 FT4 DN 25 N D -21

60 000 50 000 40 000 30 000 20 000 10 000 5 000 4 000 3 000

DN80 and DN100


Condensate kg / h

2 000 1 000 500 400 300 200 100 50 40 30 20

DN15 DN50

Sizes and pipe connections


DN15, 20, 25, 40, 50, 80 and 100 flanged BS 4504 PN40, BS 1560 class 150 or 300 DN15 - 50 horizontal / vertical connection DN80 - 100 horizontal

Materials
Body/cover DN15 - 50 Bolting DN80 - 100 Gasket Internals DIN 17245 GS-C25N DIN 17240 21 Cr MoV57 and Steel 24 Cr Mo5 BS 4439 B7 and Steel BS 3692 2H Reinforced exfoliated graphite Stainless steel Steel

2 1-3 4.5 4-2 44T4 F FT 0 5 4 2 DN DN -14 T44 5F 2 DN -4.5 T44 0F 2 & 15 DN 14 -10 44T44 20 FT 21 F 0 445& &2 15 DN1 20 FT DN & -32 15 T44 DN 0F 2 & 15 DN

21 2 000 4425 FT 5 DN 44-32 2 N D FT

1 000 500 400 300 200 100 50 40 30

10 0.1 0.2 0.3 0.5 1 10 20 32 2 345 Differential pressure bar (x 100 = kPa)

Note: Capacity shown above is based on discharge at saturation temperature. When discharge sub-cooled condensate the air vent provides extra capacity.

Body and cover from TV approved foundry.


0

Operating range
Pressure psi g
150 300 450

Temperature C

Limiting conditions (ISO 6552)


Body design conditions PN40 PMA - Maximum allowable pressure 40 bar g TMA - Maximum allowable temperature 400C Cold hydraulic test pressure 60 bar g Maximum differential pressure (D PMX) FT44-4.5 (4.5 bar) FT44-10 (10 bar) FT44-14 (14 bar) FT44-21 (21 bar) FT44-32 (32 bar)
B

300 200 100 0 0

A, B Steam saturation curve


30 32

572 392 212

B
10

A
40

32

20 Pressure bar g

The product must not be used in red area A - A Flanged ANSI 300, PN40 B - B Flanged ANSI 150

B C A E F D F D E

C A FT44 (DN15 - DN50) E F

FT44 (DN80 and DN100)

Dimensions
Size DN15 DN20 DN25 DN40 DN50 DN80 DN100 A A CI.300 CI.150 209 203 209 205 212 208 327 321 320 313 373 373 366 350 A PN40 150 150 160 230 230 373 350 B 80 80 115 130 141 140 140

(approximate in millimetres)

C 80 80 85 115 123 123 123

D 215 225 282 337 347 340 390

E 120 120 170 200 200 200 200

F Weight (kg) 155 165 215 200 225 310 310 10.8 10.8 15.0 33.0 43.0 95.0 97.0 9

Temperature F

400

580 752

Condensate lb / h

Austenitic stainless steel Screwed


2 3 000 2 000

FT16

Capacities
Differential pressure psi 3 4 5 10 20 30 50

100

200 6 000 5 000 4 000 3 000

1 000

.5 -4 16 T F 1"

2 000

500
Condensate kg / h

300 200

Sizes and pipe connections


", " and 1" screwed BSP or NPT FT16 - horizontal connection

"

F "
"F

T1

6-4

.5

500 400 300 200

T1

0 6-1

100

, "

, "

T "F

16

-14

50 40

100 70

Materials
Body/cover Bolting Gasket Internals Stainless steel AISI 316L Stainless steel A2 Gr. 80 Austenitic stainless steel Stainless steel

30 10 14 0.1 0.2 0.3 0.5 1 2 3 4 5 Differential pressure bar (x 100 = kPa)

Note: Capacity shown above is based on discharge at saturation temperature. When discharge sub-cooled condensate the air vent provides extra capacity.

Operating range
0 50

Pressure psi g 150 250

350

Temperature C

Limiting conditions (ISO 6552)


Body design conditions PN25 PMA - Maximum allowable 25 bar g TMA - Maximum allowable temperature 300C Cold hydraulic test pressure 38 bar g Maximum differential pressure (D PMX) FT16-4.5 (4.5 bar) FT16-10 (10 bar) FT16-14 (14 bar)

200 100 0 0 5 15 16.5 20 10 Pressure bar g 25

292

Steam saturation curve

212 32

The product must not be used in red area.

F B

C A G D

Dimensions
Size " " 1" 10 A B 120 54 120 54 120 110

(approximate in millimetres)

C D E F G Weight (kg) 54 148 110 169 45 4.0 54 148 110 169 45 4.0 80 195 160 220 115 6.8

Temperature F

300

362 572

Condensate lb / h

400

-10 16 T F 1" -14 16 FT " 1

1 000

DIN specification Austenitic stainless steel Flanged

FT46

Capacities
30 000 20 000 10 000
50 DN

2 345

Differential pressure psi 10 20 30 50 100 200 300 60 000 50 000 40 000


30 000
5 -4. 46 FT
21 46FT 0 5 DN 21 46FT

20 000 10 000

5 000 4 000 3 000 2 000

1 000 500 400 300

Sizes and pipe connections


DN15, 20, 25, 40 and 50 flanged BS 4504 PN40 ANSI flanges available on request FT46 horizontal connection

200

100 50 40 30

Materials
Body/cover Bolting Gasket Internals Stainless steel AISI 316 Stainless steel A2 Gr. 80 Austenitic stainless steel Stainless steel

-10 46 FT 0 5 5 DN -4. 46 FT 0 4 DN 0 6-1 T4 0F 4 DN 4.5 46FT 5 2 0 DN 6-1 T4 5 F -14 2 DN FT46 4.5 4625 FT DN 0 &2 15 10 DN 46FT 0 &2 15 4 DN 6-1 T4 0F 2 & 15 21 DN 46FT 0 &2 15 DN

40 DN

Condensate kg / h

4 FT 25 DN

1 6-2

2 000 1 000

500 400 300 200

100 50 20

20 10 0.1 0.2 0.3 0.5 1 2 345 Differential pressure bar (x 100 = kPa)

Note: Capacity shown above is based on discharge at saturation temperature. When discharge sub-cooled condensate the air vent provides extra capacity.

Body and cover from TV approved foundry.

Operating range
0
Temperature C

150
A

Pressure psi g 300

450

Limiting conditions (ISO 6552)


Body design conditions PN40 PMA - Maximum allowable pressure 40 bar g TMA - Maximum allowable temperature 400C Cold hydraulic test pressure 60 bar g Maximum differential pressure (D PMX) FT46-4.5 (4.5 bar) FT46-10 (10 bar) FT46-14 (14 bar) FT46-21 (21 bar)

300 Steam saturation curve 200 B 100 B 0 0 10 13.6 20 25.5 30 Pressure bar g

572 392 212 A 32 40

The product must not be used in red area A - A Flanged ANSI 300, PN40 B - B Flanged ANSI 150

C A E D F

Dimensions
Size DN15 DN20 DN25 DN40 DN50 A 150 150 160 230 230 B 80 80 115 130 141 C 80 80 85 115 123

(approx. in millimetres)

D 215 225 276 326 332

E 120 120 170 200 200

F Weight (kg) 155 10.8 165 10.8 215 15.0 200 33.0 225 43.0 11

Temperature F

400

580 752

Condensate lb / h

5 000 4 000 3 000

Installation
Float traps should be installed as close to the drain outlet as possible, with the float arm horizontal and with the direction of flow as indicated on the body. A strainer should be fitted in front of the trap. If exposed to freezing conditions, they should always be lagged or drained.

Options
SLR (Steam lock release):- a manually adjustable needle valve for applications where traps are subject to steam locking. Drain cock tapping:- the cover can be drilled and screwed 3/8" for the purpose of fitting a drain cock (" on FT14). Steam trap leakage detection:- for automatically monitoring steam trap performance consider the use of Spiratec. Separate literature is available on request.

Typical specification
The steam traps shall be Spirax Sarco FT14 float and lever design having an in-built stainless steel capsule type air vent. The trap shall be manufactured in SG iron to grade GGG 40 and have connections screwed " BSP. The trap shall be capable of operating with a maximum differential pressure of 14 bar.

Some of the products may not be available in certain markets.


Spirax-Sarco Limited, Charlton House, Cheltenham, Gloucestershire, GL53 8ER UK. Tel: +44 (0)1242 521361 Fax: +44 (0)1242 573342 E-mail: Enquiries@SpiraxSarco.com Internet: www.SpiraxSarco.com
Copyright 2001 Spirax Sarco is a registered trademark of Spirax-Sarco Limited

SB-S02-01

ST Issue 5

FT

Potrebbero piacerti anche