Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Test and research facilities of High Voltage Laboratories for Electrical Energy Systems at Darmstadt University of Technology
(Stand: December 2009) Address: Prof. Dr.-Ing. Volker Hinrichsen High Voltage Laboratories Darmstadt University of Technology Landgraf-Georg-Strae 4 64283 Darmstadt Telephone: +49-6151-162529 Telefax: +49-6151-162329 Email: hinrichsen@hst.tu-darmstadt.de http://www.hst.tu-darmstadt.de
High Voltage Laboratories -Offices: building S3/10 -Big high voltage hall: building S3/08 -Workshop and small high voltage hall: building S3/09 (Parking possibilities between S3/08 und S3/09, access from LandgrafGeorg-Strae)
Front page photograph: Sight of the high voltage hall and the office building from the Institutes of Energy Technology at the Darmstadt University of Technology.
Table of Content
1. Testing facilities
1.1 Big high voltage hall (accredited Test laboratory) 1.2 High power facilities 1.2.1 Synthetic test facility 1.2.2 1.35 MJ capacitor bank 1.2.3 1.5-MW-DC current facility 1.3 Aging facilities 1.4 Diagnostic test facilities 1.5 Impulse current laboratory 1.5.1 Exponential impulse current circuit 1.5.2 Long duration impulse circuit 1.5.3 AC current testing system 1.5.4 Impulse generator for testing of low voltage arresters (SPDs)
1.2 High power facilities 1.2.1 Synthetic medium voltage test circuit for high power tests
Technical data:
Available test currents .................................................................... up to 35 kA (rms) Transient voltages ...................................................... up to 200 kV Maximum energy ..........................................................................................1.35 MJ Charging voltage High current circuit ...................................................... up to 15 kV High voltage circuit .................................................... up to 120 kV
L-C-oscillating circuit as an energy source, functions according to the principal of current superposition
Configuration:
Nominal power at continuous operation:1.5 MW Current voltage combinations at nominal power: Current / A Voltage / V 3000 500 1500 1000 1000 1500 750 2000 500 3000 250 6000
The current can in each case be change up to the maximum value for that voltage range. A voltage control is also possible. Short time operation: The current level can be doubled up to a duration of 8 s. Current ripple: 1 % (with reference to the chosen current value) Statistical accuracy Of the current control: + 0.1 %
Configuration:
The picture shows the rectifying and current smoothing of the facility.
Fogging room 1
Execution of long term tests e.g. test as per IEC 61109 or weather aging test as per IEC 60099-4
The department has three fogging rooms with the following options: Fogging room I (in the basement):
-Intended for 5000 h test as well as 1000 h test -Two voltage supplies with the same earthing reference - 0...40 kV AC and 0... 8 kV DC -Monitoring of maximally 6 channels - UV light with 2x2 kW gas discharge lamps - Volume 14.8 m Fogging room II (on the Bhne):
-Intended for 5000 h test as well as 1000 h test -Two voltage supplies with the same earthing reference - 0...60 kV AC and 0... 8 kV DC -Monitoring of maximally 6 channels - UV light with 2x2 kW gas discharge lamps - Volume 16.5 m (reducible by a partition wall) Fogging room III (on the Bhne):
b)
Measuring system 1: Data: - Measuring range: ........................................................................................ 0-180 - max. sample size LxBxH: ........................................................ 150 x 150 x 50 mm - Measurement accuracy: ................................................................................... 0,5 Measuring system 2: Data: - Measuring range: ........................................................................................ 0-180 - max. sample size LxBxH: ...........................................................510 x x 50 mm
Measurements of AC voltage are possible, with constant rate of increase of voltage (2 V/s, 5 V/s, 10 V/s, 20 V/s, 50 V/s, 5 kV/s). The measurement of the electrical quantities is made by means of high precision instrument or by an oscilloscope (values may be stored). Technical data of the equipment: AC voltage: 0 200 kV (50 mA) Rate of increase of voltage: (2 V/s, 5 V/s, 10 V/s, 20 V/s, 50 V/s, 100 V/s, 200 V/s, 500 V/s, 1 kV, 2 kV/s, 5 kV/s) Various electrode arrangements depending on the type of insulating material.
Test specimen setup with ball-ball electrode arrangement for testing disc shaped insulating materials
Measurement of DC and AC voltages is possible. The measurement of the electrical quantities is made by means of a high precision pointer instrument or by an oscilloscope (values may be stored). Technical data: DC voltage: 0 15 kV (max. 100 mA) AC voltage: 0 20 kV (max. 20 mA) Frequency domain: 10 Hz 100 Hz (distortion free curve shapes) Current measurement: 10 nA 100 mA
Test specimen setup with protection ring electrode as per IEC 60093 for testing disc shaped insulating materials.
1.5
Exponential impulse current circuit (Highvolt) (Lightning impulse, switching impulse, high impulse, steep impulse)
FS L R PO
UL
1,2 kA
CGesamt = 20 10 F = 200 F
Hybrid generator CWG 4-404 (current and voltage impulse by system voltage) Peak value of the open circuit voltage 1,2/50 s: 0,1 ... 4 kV Peak value of the short circuit current 8/20 s: 0,05 ... 2 kA Impulse in positive / negative half wave or alternating Impulse generator HVPG 6-363 Charging voltage: 0 ... 6,3 kV Curve type: 1,2/50 s, 10/700 s High voltage impulse generator HVPG 4-640 Charging voltage: 0 ... 4 kV Curve type: 10/700 s
2. Testing equipments for special research projects 2.1 Test setup for the accelerated aging test of MO resistance as per IEC 60099-4
For a surge arrester, input electrical power must always remain smaller than the thermal power which it can dissipate to the surroundings in the form of heat. Only then, thermally stable operation can be ensured.
As per definition of IEC 60099-4, accelerated aging test determines whether an arrester remains thermally stable for a time of over 100 years during load with its continuous operation voltage. A resistance is heated in a furnace at 115 C (heating serves as accelerated aging) and stressed for a duration of 1000 h with 105% of its continuous operation voltage. Thereby, the measured energy dissipation should become constantly smaller or at least not rise significantly.
UN
PVerlust =
U I dt
2.2 Temperature measurement with passive remote surface acoustic wave (SAW) sensors
Temperature range -20 - +150C Measuring accuracy of the SAW-sensor chips -+0.5C Dimensions of the SAW-sensor chips ca. 1x1.5 cm Wireless high frequency measuring signal transmission over distances up to approximately 15 meters, also through (non-metallic bodies) SAW Technique Receiver unit (power system 12 24 V DC) 2,45 GHz receiver antenna passive SAW-Temperature sensor (SAW-Sensor chip, Sensor antenna, housing)
2.3 Optical monitoring with high speed camera and photo sensing instruments
High speed camera
High speed camera Redlake Imaging Motion Scope PCI 2000 SC Model: 1108-0012 2000 fps Maximum recording time: 2 sec
Photomultiplier A photomultiplier is a special vacuum tube, in order to strengthen and convert weak light signals into individual photons and hence into an electrical signal. A photomultiplier consists of an entrance window, a photocathode and a secondary downstream multiplier. The output signal of the photomultiplier can be used electrically, like a constant current source.
Type: H 8249 Series Spectral response: 185 680 nm Frequency bandwidth: DC till 200 kHz
POWER SUPPLY
SAMPLE
PMT
O SCILOSCO PE
Booster pump:
Two stage rotary pump: DUO 030 A Pumping rate for nitrogen N2 Final pressure Nominal connection diameter 500 m3/h 10-3 mbar DN 40 ISO KF
3 Other Laboratory Equipment 3.1 Molding facility for the fabrication of EP-, PUR-resin and plastic molded materials Fabrication of insulating components from epoxy resin or polyurethane resin molded materials with a vacuum molding system (Hbers make, type Epsilon).
Technical data - Volume of vacuum mixer: .....................................................................................3 l - Internal volume of the vacuum tank: .......................................500 x 700 x 850 mm - Vacuum pump volume: ................................................................................ 27 m3/h - Mixer heating temperature:....................................................................max. 130 C