Sei sulla pagina 1di 6

2/16.

4/EN/1

Universal
Plenum Boxes
Type AK
for ceiling mounted diffusers
Types RFD, FD, VDW, TDF, TDV, DLQ, ADLQ, ADD, ADLR

TROX GmbH
Heinrich-Trox-Platz
D-47504 Neukirchen-Vluyn

Telephone +49 / 28 45 / 2 02-0


Telefax
+49 / 28 45 / 2 02-2 65
e-mail trox@trox.de
www.troxtechnik.com

Contents Description Construction Materials


Description Construction Materials
Dimensions
Technical data Supply air
Technical data Extract air
Order details

2
3
4
5
6

Universal Plenum box with standard connection diameter ( D)


relating to individual leaflets in KLIMA-catalogue 1
Type

Leaflet no.

RFD

2/

ADD

2/ 4.2/EN/...

4/EN/...

FD

2/

TDF-SilentAIR

2/ 6.2/EN/...

VDW

2/

7/EN/...

TDV-SilentAIR

2/

7.1/EN/...

DLQ/ADLQ

2/

11/EN/...

ADLR

2/

16/EN/...

6/EN/...

Description

Construction

Universal Plenum Boxes Type AK can be supplied for


diffusers Type RFD, FD, VDW, TDF, TDV, DLQ, ADLQ, ADD
and ADLR.
Subject to performance requirements they can be used with
various ceiling diffusers. The plenum boxes with standard
spigot diameters (D) are marked in the table on Page 3.
Only by using these diameters can the maximum volume
flows be achieved and the sound power values maintained
as stated in the individual leaflets.
The plenum boxes not marked have different spigot
diameters. The volume flow here should be considered in
relation to the acoustic requirements.

The Universal Plenum Box type AK comprises a casing with


horizontal circular spigot for duct connection, with or without
volume flow measurement and/or lip seal.
At the bottom of the plenum there is a built in spigot for
connecting diffusers Type FD, VDW, TDF, TDV and ADLR.
Plenum boxes Type RFD and ADD are supplied as standard
with a bottom spigot for connection to square and circular
face diffusers.

Materials
Galvanized sheet steel plenum box with rubber lip seal.

Determining the volume flow by pw









pw








Test nipple
Plastic tube
Plenum box
Diffuser face
Inclined manometer
Green sheathed cable
to close butterfly damper
 White sheathed cable
to open butterfly damper
 Plenum box code

With the option MN (volume flow setting with control cable


and test nipple) see order code the setting of required
flow rates simplified.
The reference pressure pw is measured using a plastic tube
to a standard manometer.
The relevant volume flow is determined from the
characteristic = f(pw) enclosed with every plenum box.
The diffuser constant C can be read on Page 4 (supply) and
Page 5 (extract) of this leaflet.
The volume flow can be calculated using the reference
pressure and the constant C (for formula see Page 4).
If necessary cables  and  can be used to adjust the
butterfly damper in order to obtain the required volume flow.
When the measurement and the adjustment have been
completed the tube and the cables are pushed behind the
diffuser face.

Dimensions

For square face diffusers


Type DLQ/ADLQ, VDW, FD, TDV/TDF-SilentAIR

32

FD

PB
Code

* 250
* 300

* 400

* 500

* 300 x 8
* 400 x 16
* 500 x 24
500 x 24

* 300
* 400
* 500
500

* 300
* 400
* 500

158
158
158
198
198
248

250
250
250
295
295
345

216
266
290
372
476
476

AK 008
AK 009
AK 001
AK 002
AK 003
AK 010

600
625

* 600 x 24
* 625 x 24

* 600
* 625

* 600
* 625

248

345

567

AK 004

600
625

600 x 24
625 x 24
* 600 x 48

600
625

248

345

590

AK 005

625

625 x 24
* 625 x 54

248

345

615

AK 006

625

* 600
* 625

600 x 24
625 x 24

600
625

313

410

567

AK 011

600
625

600 x 24
625 x 24
600 x 48

600
625

313

410

590

AK 012

625

625 x 24
625 x 54

625

* 825 x 72

313

410

615

AK 027

313

410

806

AK 007

TDV/TDF  D
SilentAIR

VDW

D

Size
DLQ/
ADLQ

Square
diffuser face

 FD/VDW
= 8 mm
DLQ/ADLQ = 12.5 mm

For circular face diffusers


Type ADLR, VDW, FD, TDV/TDF-SilentAIR, ADD

123
158
158
198
198
198
248
248
248

220
250
250
295
295
295
345
345
345

266
290
290
372
372
476
476
476
567

202
258
278
314
362
460
362
426
557

AK 019
AK 020
AK 013
AK 021
AK 014
AK 015
AK 022
AK 023
AK 016

248

345

590

578

AK 017

248
313

345
410

615
567

590
482

AK 018
AK 024

* 600
* 625 2)

313

410

590

578

AK 025

313

410

615

590

AK 026

* 300 x 8

* 400 x 16
* 500 x 24
400 x 16

* 600 x 24
* 625 x 24

* 300

* 400
* 500
400

* 600
* 625

600 x 24
625 x 24
* 600 x 48

600
625

8
*6

625 x 24
500 x 24

625
500

*7

600 x 24
625 x 24
600 x 48

600
625

625 x 24

625

*8

* 300

* 400
* 500

* 600
* 625

* 250
* 300

* 400

* 450
* 500

P


Spigot
Circular diffuser face

Without nozzle

For square and circular face diffusers


Type RFD
R

PB
Code

* 125
* 160
* 200
* 250
* 315
* 400

98
123
158
198
248
313

195
220
250
295
345
410

216
266
290
476
567
615

123.5
158.5
198.5
248.5
313.5
398.5

25
25
25
25
35
35

AK 028
AK 029
AK 030
AK 031
AK 032
AK 033

= Plenum box with standard spigot diameter  D


= Standard plenum box
1) = for circular and square diffusers
2) = Types ADD/size 625 not for circular face diffusers

With nozzle

P

60

P

/

60

D

Size

32

D

*1
*2
2
*3
4

*4
*5
7

32

PB
Code

D

P

VDW

35

ADLR

Size
D
FD TDV/TDF ADD1)
SilentAIR

Spigot

/

Circular or square
diffuser face

Technical data
Supply air

Nomenclature

Example

Data given:
Diffuser:

in m3/h: Volume flow

 p W in Pa: Reference pressure


C

: Constant

Plenum box:
Volume flow required:
Constant C from table:

C-value for reference pressure


Plenum box for square face diffusers
Type

DLQ/
ADLQ

VDW

FD

TDVSilentAir

TDFSilentAir

Calculation of reference pressure to be set:

Size

AK
Code

C Value

250
300
400

AK 008
AK 009
AK 002

36.21
53.41
108.22

500
600/625
600/625

AK 010
AK 004. AK 005. AK 006
AK 011. AK 012. AK 027

173.70
182.35
260.00

300 x 8
400 x 16
500 x 24

AK 001
AK 002
AK 003

36.92
70.71
87.07

500 x 24
600/625 x 24
600/625 x 24

AK 010
AK 004. AK 005. AK 006
AK 011. AK 012. AK 027

104.09
125.80
141.91

600 x 48
600 x 48
625 x 54

AK 005
AK 012
AK 006

154.81
181.95
158.94

625 x 54
872 x 72

AK 027
AK 007

191.44
262.15

300
400
500

AK 001
AK 002
AK 003

36.45
70.71
92.72

500
600/625
600/625

AK 010
AK 004. AK 005. AK 006
AK 011. AK 012. AK 027

103.45
125.80
141.91

300
400

AK 001
AK 002

47.66
82.08

500
600/625

AK 003
AK 004

100.54
145.54

300
400

AK 001
AK 002

47.66
82.08

500
600/625

AK 003
AK 004

100.54
145.54

 pW =

700
 C  =  154.81


= C

RFD

Type

ADD

Size
125
160
200

AK 028
AK 029
AK 030

12.42
18.70
25.45

17.85
26.29
43.87

250
315
400

AK 031
AK 032
AK 033

46.38
82.00
124.34

68.44
103.00
134.39

Size

AK
Code

C Value

250
300

AK 019
AK 020

27.44
52.20

400
450

AK 021
AK 022

79.88
128.66

500
600
6251)

AK 023
AK 025
AK 025

143.39
245.68
245.68


 pW

 pW =

 C 

C-value for reference pressure


Plenum box for circular face diffusers
Type

ADLR

VDW

C-value for reference pressure


AK
Code

 p W = 20.45 Pa

Plenum box for square and circular face diffusers


Type

VDW 600 x 48
square construction
AK 005
V = 700 m3/h
C = 154.81

C Value
C Value
without nozzle with nozzle

FD

TDVSilentAIR

TDFSilentAIR

Size

AK
Code

1
2
3

AK 019
AK 013, AK 020
AK 021

29.77
53.34
86.22

4
4
5

AK 014
AK 022
AK 015

112.62
128.67
114.93

5
6
7

AK 023
AK 024
AK 016, AK 017

150.58
206.76
184.05

7
8
8

AK 025
AK 018
AK 026

231.93
183.91
254.66

300 x 8
400 x 16
400 x 16

AK 013
AK 014
AK 022

33.81
70.71
67.08

500 x 24
500 x 24
600/625 x 24

AK 015
AK 024
AK 016, AK 017

82.97
101.31
124.27

600/625 x 24
600 x 48
600 x 48

AK 025
AK 017
AK 025

131.39
158.25
186.03

625 x 24
625 x 24

AK 018
AK 026

122.49
129.87

300
400
400

AK 013
AK 014
AK 022

36.45
70.71
67.08

500
500
600/625

AK 015
AK 024
AK 016, AK 017

94.35
111.80
124.27

600/625
625
625

AK 025
AK 018
AK 026

131.39
122.49
129.87

300
400

AK 013
AK 014

47.66
82.08

500
600/625

AK 015
AK 016

100.54
145.54

300
400

AK 013
AK 014

47.66
82.08

500
600/625

AK 015
AK 016

100.54
145.54

C Value

1) = Type ADD/size 625 not for circular face diffusers.

Technical data
Extract air

Type

DLQ/
ADLQ

VDW

FD

TDVSilentAIR

TDFSilentAIR

C-value for reference pressure

C-value for reference pressure

Plenum box for square face diffusers

Plenum box for circular face diffusers

Size

AK
Code

C Value

Size

AK
Code

C Value

250
300
400

AK 008
AK 009
AK 002

35.33
66.90
130.84

1
2
2

AK 019
AK 020
AK 013

27.75
53.16
52.08

500
600/625
600/625

AK 010
AK 004
AK 005

247.22
500.60
400.26

3
4
4

AK 021
AK 014
AK 022

74.40
109.86
108.19

625
600/625
600/625
625

AK 006
AK 011
AK 012
AK 027

496.41
412.60
411.60
428.03

5
6
7

AK 023
AK 024
AK 016

162.44
202.99
276.18

300 x 8

AK 001

400 x 16

AK 002

32.08
56.00 1)
63.51
123.91 1)

7
7
8
8

AK 017
AK 025
AK 018
AK 026

255.65
262.14
363.98
351.07

300 x 8

AK 013

500 x 24

AK 003

92.57
189.56 1)

33.57
58.14 1)

400 x 16

AK 014

600/625 x 24
600/625 x 24
600/625 x 24

AK 004
AK 005
AK 006

150.56
151.67
145.16

64.33
127.37 1)

400 x 16

AK 022

64.88
113.29 1)

600/625 x 24
600/625 x 24
600/625 x 24

AK 011
AK 012
AK 027

162.31
154.12
154.35

500 x 24

AK 015

90.93
183.19 1)

500 x 24

AK 024

600 x 48
600 x 48
625 x 54

AK 005
AK 012
AK 006

197.01
210.18
214.73

103.03
161.91 1)

625 x 54
872 x 72

AK 027
AK 007

230.26
348.68

600/625 x 24
600/625 x 24
600/625 x 24

AK 016
AK 017
AK 025

151.94
144.96
158.22

300
400

AK 001
AK 002

41.67
85.51

600 x 48
600 x 48
625 x 54

AK 017
AK 025
AK 026

209.14
212.25
159.73

500
500
600/625

AK 003
AK 010
AK 004

137.86
143.25
200.50

300
400
400

AK 013
AK 014
AK 022

46.71
90.85
89.99

600/625
600/625
600/625

AK 005
AK 006
AK 011

196.67
182.11
217.08

500
500
600/625

AK 015
AK 024
AK 016

138.08
144.63
207.72

600/625
625

AK 012
AK 027

216.11
211.84

300
400

AK 001
AK 002

58.97
104.20

600/625
600/625
625
625

AK 017
AK 025
AK 018
AK 026

208.98
213.61
182.11
219.44

500
600/625

AK 003
AK 004

138.73
188.23

300
400

AK 013
AK 014

58.97
104.20

300
400

AK 001
AK 002

58.97
104.20

500
600/625

AK 015
AK 016

138.73
188.23

500
600/625

AK 003
AK 004

138.73
188.23

300
400

AK 013
AK 014

58.97
104.20

500
600/625

AK 015
AK 016

138.73
188.23

Type

ADLR

VDW

FD

TDVSilentAIR

TDFSilentAIR

C-value for reference pressure


Plenum box for square and circular face diffusers
Type

ADD

Size

AK
Code

C Value

250
300

AK 019
AK 020

31.41
74.01

400
450

AK 021
AK 022

96.96
141.48

500
600
6252)

AK 023
AK 025
AK 025

194.88
256.00
256.00

1) = Face diffusers without air control blades !


2) = Type ADD/size 625 not for circular face diffusers.

Order Details

Order code

AK 002 - ZL - M - L

For AK code see table Page 3

Supply air
ZL
Extract air 1) AL

L Spigot with lip seal

IEE
OE
P

TE
EZ
EE
U

M Volume control damper


MN Volume control damper with
control cable and test nipple

1) Does not apply to Type RFD


For extract application supply construction
RFD diffuser must be used

Specification text
Design changes reserved All rights reserved TROX GmbH (8/2008)

The Universal Plenum box comprises a casing with a circular,


horizontal spigot for duct connection, with or without volume flow
measurement and/or lip seal.
To measure the reference pressure the Universal Plenum box is
equipped on request with a cable and test nipple to measure and
set the required volume flow.
The plenum box can be suspended using wires or slotted strips
using the fixing holes provided. Subject to performance requirements the Universal Plenum box can be used with various ceiling
diffusers.

Materials:
Galvanized sheet steel Universal Plenum box with rubber lip seal.

Order Example:
Make: TROX
Type: AK 002 - ZL - M - L

Potrebbero piacerti anche