T 2.

4/2/EN/1

Active
Chilled Beams
Type DID300B

TROX GmbH
Heinrich-Trox-Platz
D-47504 Neukirchen-Vluyn

Telephone +49 / 28 45 / 2 02-0


Telefax
+49 / 28 45 / 2 02-2 65
e-mail trox@trox.de
www.troxtechnik.com

Contents Description
Contents Description
Construction
Casing arrangements
Dimensions
Assembly

2
3
4
5
6

DID300B-...-V
Top entry air connection spigot

Nomenclature
Performance overview cooling
with 2-pipe and 4-pipe systems
Performance overview heating
with 4-pipe systems
Aerodynamic data
Order details

8
9
10
11
12

DID300B-...-H
Side entry air connection spigot

Description
TROX Active Chilled Beams type DID300B use a combination of
air and water systems. They combine the air flow characteristics
of ceiling diffusers with the energy benefits of load dissipation
using water (heating/cooling).
The primary air volume flow required for fresh air supply enters
the upper plenum box through a connecting spigot and is then
discharged into the mixing zone via nozzles which are fitted into
a diaphragm plate.
The induced air is drawn from the room through a water coil. In
the mixing section of the DID300B the induced air is mixed with
the primary air and the total discharged into the room via slots.
The DID300B can be used for cooling and/or heating.
An additional spigot for extract of exhaust air can be fitted
adjacent to the primary air duct (supply and extract air
construction).
Caution !
The cold water supply temperature must be selected such
that it never falls below room dewpoint.
Max. pressure:
for 2-pipe and 4-pipe system
6 bar at 90C
7 bar at 20C
Other operating pressures available on request!

The type DID300B chilled beams are particularly suitable for use
in low ceiling void spaces because of their shallow construction.
Thus they are suitable not only for use in new buildings but are
also excellent for refurbishment projects.
When connected appropriately, they can be used for both
individual room control or form a grouped zone control.
The DID300B is available with either top or side entry air
connection spigot for supply and extract air.
Between the upper and lower casing there is a diaphragm plate
which contains two longitudinal rows of nozzles. These discharge nozzles are available in three different sizes, the selection
depending on the volume flow rates required.
The induction grille can easily be removed for cleaning purposes.
Materials
Casing, including the top plenum and perforated plate induction
grille are made of galvanised steel sheet.
The standard finish of the casing and the induction grille is
powder-coated white (RAL 9010), the top casing (plenum) and
coil remain untreated - optionally can be finished in black
(RAL 9005), nozzle plate only finished in black (RAL 9005).
The heat exchanger consists of copper tubes with formed
aluminium fins. The flexible hose, available as an accessory, is
made of special plastic with stainless steel sheathing.

Construction
IEE LN 900 to 1800 = 123
OE L 2100 to 3000 = 158
P N

L1 = Total length (diffuser face)


LN = Nominal length
(for dimensions of unit see page 5)

Construction with supply air spigot

Construction with supply and extract air spigot


L1

L1

 

LL

LR

LH

293

293

LH

L1
LR

LH

LL

LR

LH

293

293

LL

100

L1

100

View A - A
Construction with top entry supply air spigot

View B - B
Construction with side extract air spigot
10b

210
D

18

123

18

only with 4-pipe system

293

45

193

98
195

50

1a





264

38

293

View A - A
Construction with side entry supply air spigot

View B - B
Construction with top extract air spigot

210
98

18

143

123

only with 4-pipe system

10a

50

210

1b

36

10a
10b

Supply air top entry connecting spigot


Supply air side entry connecting spigot
Top of casing (plenum)
Discharge nozzles
Casing
Coil (pipe- 12 mm)
Perforated plate induction grille
Discharge slots
Label chilled water (blue)
Label warm water (red)
Extract air top connecting spigot
Extract air side connecting spigot

18


1a
1b










36
299

293

293

Casing arrangements

Top entry supply air spigot

Side entry supply air spigot

Chilled water connection

Top extract air spigot

Side extract air spigot

Warm water connection

Casing arrangement with top entry supply air spigot


V-S

V-L

V-M

V-R

Casing arrangement with side entry supply air spigot


H - SV

H - SH

H - LV

H - LH

H - MV

H - MH

H - RV

H - RH

Casing arrangement with top entry supply and extract air spigot
V - L - AR

V - R - AL

V - M - AR

V - M - AL

Casing arrangement with side entry supply and extract air spigot

H - LV - ARV

H - RV - ALV

H - MV - ARV

H - MV - ALV

H - LH - ARH

H - RH - ALH

H - MH - ARH

H - MH - ALH

H - LV - ARH

H - RV - ALH

H - MV - ARH

H - MV - ALH

H - LH - ARV

H - RH - ALV

H - MH - ARV

H - MH - ALV

Dimensions

V-S

H - SV

For construction and casing arrangements


see pages 3 and 4

H - SH

Arrangement of the top active plenum

Supply air

Extends over total length (standard)


LN

LH

LL

LR

V - L - AR
L1

H - LV - ARH

min

max

min

max

min

max

900

800

40

43

54

58

893

900

1200

1100

40

43

54

58

1193

1200

1500

1400

40

43

54

58

1493

1500

1800

1700

40

43

54

58

1793

1800

2100

2000

40

43

54

58

2093

2100

2400

2300

40

43

54

58

2393

2400

2700

2600

40

43

54

58

2693

2700

3000

2900

40

43

54

58

2993

3000

V-L

Supply air

H - LV

H - LH

900
1200

LH

LL

800
1100

LR

43
43

L1

min

max

min

max

58
58

658
658

901
1201

1500
1800

1500
1800

1400
1700

43
43

58
58

658
658

1501
1801

2100
2400

2100
2400
2700

2000
2300
2600

43
43
43

58
58
58

658
658
358

2101
2401
2701

2700
3000
3000

V-M

Supply air

H - LH - ARV

H - LH - ARH

Arrangement of the top active plenum (plenum shorter than L1)

Supply and
extract air

left

LN

LH

LL
min

max

min

max

900
1200

800
1100

43
43

253
253

658
658

1096
1396

1500
1800

1500
1800

1400
1700

43
43

253
253

658
658

1696
1996

2100
2400

2100
2400
2700

2000
2300
2600

43
43
43

253
253
253

658
658
358

2296
2596
2896

2700
3000
3000

LR

L1

Arrangement of the top active plenum (plenum shorter than L1)

left
LN

H - LV - ARV

H - MV

H - MH

V - M - AL

H - MV - ALV

H - MH - ALV

H - MH - ARV

V - M - AR

H - MV - ALH H - MV - ARH H - MH - ALH

H - MH - ARH

Arrangement of the top active plenum (plenum shorter than L1)

Supply and
extract air
LN

H - MV - ARV

middle

LH

L1
min

max

900
1200

800
1100

1290
1590

1800
1800

1500
1800

1400
1700

1890
2190

2100
2400

2100
2400

2000
2300

2490
2790

2700
3000

Arrangement of the top active plenum (plenum shorter than L1)

middle
V - R - AL
LN

900
1200

LH

L1

800
1100

H - RV - ALV

H - RV - ALH

min

max

901
1201

1500
1800

Supply and
extract air
LH

H - RH - ALV

H - RH - ALH

Arrangement of the top active plenum (plenum shorter than L1)

right
LL

LR

L1

1500
1800

1400
1700

1501
1801

2100
2400

LN

min

max

min

max

2100
2400
2700

2000
2300
2600

2101
2401
2701

2700
3000
3000

900
1200

800
1100

238
238

643
643

58
58

1095
1395

1500
1800

1500
1800

1400
1700

238
238

643
643

58
58

1695
1995

2100
2400

2100
2400
2700

2000
2300
2600

238
238
238

643
643
343

58
58
58

2295
2595
2895

2700
3000
3000

V-R

Supply air

H - RV

H - RH

Arrangement of the top active plenum (plenum shorter than L1)

right
LN

LH

LL

LR

min

max

L1
min

max

900
1200

800
1100

43
43

643
643

58
58

901
1201

1500
1800

1500
1800

1400
1700

43
43

643
643

58
58

1501
1801

2100
2400

2100
2400
2700

2000
2300
2600

43
43
43

643
643
343

58
58
58

2101
2401
2701

2700
3000
3000

All dimensions in mm with normal tolerances for sheet


construction!

Assembly
Assembly
The two long sides of the DID300B are each provided with
two suspension holes or for L1 = 1500 4 holes are provided on
each side. The assembly is installed on site using wire or metal
hangers which must have the Building Authority certificate of
approval. When the DID300B has been installed, 4 locking
devices can be loosened with a screw driver (detail X) and the
whole induction grille can be lowered down lengthways. The
induction grille is supported by two safety cables.

The coil is accessible when the induction grille is removed.


The coil connections are on the outside of the DID300B unit.
The connection options to the flow and return pipes are, solid
soldered, push fit or compression fittings (internal or external
threaded end fittings).
The air connection is either from the side or from the top,
depending on the construction.

Detail X

12

196
293

35

L1

side entry connection

top entry connection

Locking
device

Safety cable

Flexible hose (FS12),

Detail Y

for water connection 12 mm

with external thread 1/2,


compression fitting,
L = 500, 750, 1000 mm

48

26

min. bend radius

Available connectors

32

32

with union nut 1/2,


compression fitting,
L = 500, 750, 1000 mm

Suspension holes

with push-fit connector


12 mm,
L = 500, 750, 1000 mm

FS12-S

FS12-S/A
60

R8

FS12-S/U

49

both ends combination

Installation
The DID300B unit is fitted with a border extrusion which is
suitable for the usual range of ceiling constructions. This ensures
the best possible ceiling design.

Installation in T-bar ceilings or closed ceilings

Installation into grid ceilings

Weight relative to the stability of the construction must be taken


off the ceiling. Suspension holes are provided for this. The same
also applies to preventing the units themselves from sagging.

The DID300B can be installed on site at the ends using the


support angles which are available as an accessory.
The support angles are supplied loose and can be fitted as
appropriate for the grid on site. With this method it is no longer
necessary to level the DID300B units.

These options allow for installation in a visible T-bar ceiling


arrangement or in plasterboard or other closed ceiling systems.

Installation in grid ceilings


Ceiling panel/tile

B = Grid width
R = Grid pitch

Grid

18

30 or 40 mm

(AW)*
Support angle

Support angle (AW)


can be supplied loose

293

L1
R

18

Installation in T-bar ceilings

293

L1

Installation in plasterboard ceilings or closed ceilings

Depending on the quality of the


room air, there is the possibility of
dust deposits as with all room air
induction units.
If necessary the unit can be cleaned
with ordinary, non-aggressive
household cleaners. The coil can be
cleaned with an industrial vacuum
cleaner.

18

(See also VDI 6022, page 1


Hygiene requirements for room airconditioning systems)

293
L1

Nomenclature
WK
WH
WH
WK

tWRK
tWVH
tWRH
tVWK

LN + 300 mm
Top entry
connection

Side entry
connection
LN

1,7
1.7 m
m

Pr
Pr
tPr
L; tL

DID300B

H1; tH1
F
room
LLraum

tL

in K:

Temp. diff. between room air tR and core tL at distance L = X + H1

tH1

in K:

Temp. diff. between room air tR and core tH1 at distance L = A/2 + H1

tPr

in K:

Temp. diff. between room air and primary air

tZ

in K:

Temp. diff. between room air and supply air into space

tW

in K:

Water temperature difference

tRWV

in K:

pt

in Pa:

pW

in kPa:

Temp. diff. between room air and water flow temperature


Primary air pressure drop
Water pressure drop

tR

in C:

Room temperature

tWVK

in C:

Water flow temperature cooling

tWRK

in C:

Water return temperature cooling

tWVH

in C:

Water flow temperature heating

tWRH

in C:

Water return temperature heating

tPr

in C:

Primary air temperature

WK

in W:

Water cooling capacity

WH

in Watt:

Water heating capacity

ges

in Watt:

Total cooling capacity Pr + S

Pr

in Watt:

Primary air cooling capacity

S

in Watt:

Water side thermal capacity (for cooling S = WK, for heating S = WH)

Zul

in W/m2:

WK

in l/h:

Water volume flow rate cooling

WH

in l/h:

Water volume flow rate heating

Zul

in l/s:

Supply air volume flow rate to space

Pr

in l/s:

Primary air volume flow rate

Specific cooling capacity based on reference area F

in m/s:

Time average air velocity at distance L

H1

in m/s:

Time average air velocity at distance A/2 + H1

LWA

in dB(A):

ges
Zul

in m:

A-weighted sound power level


Spacing between 2 diffusers

in m:

Horizontal plus vertical distance from diffuser, discharge down the wall L = X + H1

Xkrit

in m:

Horizontal distance from diffuser at which the supply air begins to separate from ceiling

H1

in m:

Distance ceiling - occupied zone

in m:

Room height or height of installation

in m:

Distance from diffuser centre line to the wall

LN

in mm:

in m2:

Nominal length
Reference area (LN + 0.3) x 5

5000 mm

H1

Performance overview cooling


with 2-pipe and 4-pipe system

LN

900
1200
1500
1800
2100
2400
2700
3000

50

70

90

110

140

180

200

250

0.71
0.69
0.68
0.67
0.55
0.53
0.52
0.51

0.85
0.83
0.82
0.81
0.67
0.66
0.64
0.63

0.94
0.93
0.93
0.92
0.76
0.75
0.74
0.73

1.00
1.00
1.00
1.00
0.83
0.82
0.81
0.80

1.07
1.07
1.08
1.09
0.90
0.90
0.89
0.89

1.12
1.14
1.15
1.16
0.97
0.97
0.97
0.97

1.14
1.15
1.18
1.19
1.00
1.00
1.00
1.00

1.18
1.20
1.23
1.25
1.05
1.05
1.05
1.05

tW in K

WK in l/h

Reference values
tWVK = tPr = 16C
WK = 110 l/h (LN 900 up to 1800)
WK = 200 l/h (LN 2100 up to 3000)
tPr = tPr tR = 10 K
tRWV = tWVK tR = 10 K
LN

Type of
nozzles

K
900

M
G
K

1200

M
G
K

1500

M
G
K

1800

M
G
K

2100

M
G
K

2400

M
G
K

2700

M
G
K

3000

M
G

.
V Pr

50 l/h 60

70

80

90 100

110

7.5
7.0
6.5
6.0
150
5.5
5.0
4.5
200
4.0
3.5
250
3.0
2.5
WK
2.0
1.5
1.0
0.5
0.0
200 300 400 500 600 700 800 900 1000 1100

pW in kPa

8.5
8.0

Correction factors

16
15
14
12
12
11
10
9
8
7

II

3000
2800
2400
2100
1800
1500
1200
900
LN

6
5
4
3
2
1
0
40

60 80 100 120 140 160 180 200 220 240 260

WK in l/h

WK in W

l/s

m3/h

.
Q Pr
(air)
watts

3
7
11
6
13
19
11
19
27
3
8
13
8
15
23
15
23
30
4
9
15
10
18
26
19
25
32
5
11
17
12
21
29
22
29
36
6
12
18
14
23
32
26
32
38
7
13
19
16
25
34
30
35
40
8
14
21
18
27
37
34
37
41
9
16
23
20
30
39
38
40
43

11
25
40
22
47
68
40
68
97
11
29
47
29
54
83
54
83
108
14
32
54
36
65
94
68
90
115
18
40
61
43
76
104
79
104
130
22
43
65
50
83
115
94
115
137
25
47
68
58
90
122
108
126
144
29
50
76
65
97
133
122
133
148
32
58
83
72
108
140
137
144
155

36
84
133
72
157
229
133
229
326
36
96
157
96
181
277
181
277
362
48
109
181
121
217
314
229
301
386
60
133
205
145
253
350
265
350
434
72
145
217
169
277
386
314
386
458
84
157
229
193
301
410
362
422
482
96
169
253
217
326
446
410
446
494
109
193
277
241
362
470
458
482
518

.
QS
(water)
watts

.
Q ges

tW

.
q Zul

.
VPr /m2

watts

W/m2

l/(s m2)

m3/(h m2)

116
256
324
156
291
352
201
295
351
79
303
399
202
347
437
267
363
418
113
342
466
245
412
504
329
404
468
146
406
527
287
472
565
374
462
526
199
515
681
377
609
750
503
598
673
235
555
729
425
659
807
571
650
715
270
592
797
471
707
873
637
684
741
304
664
863
517
773
922
701
732
775

152
340
457
229
448
581
334
524
676
115
399
556
298
528
714
448
640
780
161
451
647
366
629
818
559
706
854
206
539
732
432
725
915
639
811
960
271
660
898
546
886
1136
817
984
1131
319
711
958
618
961
1217
933
1072
1198
366
761
1050
688
1033
1319
1047
1131
1235
413
857
1140
758
1135
1393
1159
1214
1294

0.9
2.0
2.5
1.2
2.3
2.7
1.6
2.3
2.7
0.6
2.4
3.1
1.6
2.7
3.4
2.1
2.8
3.3
0.9
2.7
3.6
1.9
3.2
3.9
2.6
3.2
3.7
1.1
3.2
4.1
2.2
3.7
4.4
2.9
3.6
4.1
0.9
2.2
2.9
1.6
2.6
3.2
2.2
2.6
2.9
1.0
2.4
3.1
1.8
2.8
3.5
2.5
2.8
3.1
1.2
2.5
3.4
2.0
3.0
3.8
2.7
2.9
3.2
1.3
2.9
3.7
2.2
3.3
4.0
3.0
3.1
3.3

25
57
76
38
75
97
56
87
113
15
53
74
40
70
95
60
85
104
18
50
72
41
70
91
62
78
95
20
51
70
41
69
87
61
77
91
23
55
75
45
74
95
68
82
94
24
53
71
46
71
90
69
79
89
24
51
70
46
69
88
70
75
82
25
52
69
46
69
84
70
74
78

0.5
1.2
1.8
1.0
2.2
3.2
1.8
3.2
4.5
0.4
1.1
1.7
1.1
2.0
3.1
2.0
3.1
4.0
0.4
1.0
1.7
1.1
2.0
2.9
2.1
2.8
3.6
0.5
1.0
1.6
1.1
2.0
2.8
2.1
2.8
3.4
0.5
1.0
1.5
1.2
1.9
2.7
2.2
2.7
3.2
0.5
1.0
1.4
1.2
1.9
2.5
2.2
2.6
3.0
0.5
0.9
1.4
1.2
1.8
2.5
2.3
2.5
2.7
0.5
1.0
1.4
1.2
1.8
2.4
2.3
2.4
2.6

1.8
4.2
6.6
3.6
7.8
11.4
6.6
11.4
16.2
1.4
3.8
6.2
3.8
7.2
11.0
7.2
11.0
14.4
1.6
3.6
6.0
4.0
7.2
10.4
7.6
10.0
12.8
1.7
3.8
5.8
4.1
7.2
9.9
7.5
9.9
12.3
1.8
3.6
5.4
4.2
6.9
9.6
7.8
9.6
11.4
1.9
3.5
5.1
4.3
6.7
9.1
8.0
9.3
10.7
1.9
3.4
5.0
4.3
6.5
8.9
8.2
8.9
9.8
2.0
3.5
5.0
4.4
6.5
8.5
8.3
8.7
9.4

LWA, entry from


top
side
dB(A)
dB(A)

Pt
(air)
Pa

< 20
32.5
45.1
< 20
34.0
44.6
< 20
32.0
41.7
< 20
31.4
44.9
< 20
33.1
45.0
22.5
34.4
41.8
< 20
30.9
45.1
< 20
34.4
44.6
26.9
34.5
41.4
< 20
34.3
46.5
< 20
34.5
43.5
26.1
33.8
39.8
< 20
34.1
45.4
20.6
34.4
43.6
29.2
35.0
39.8
< 20
34.1
44.7
22.0
34.5
43.0
31.9
36.2
39.9
< 20
34.2
45.5
23.3
34.6
43.4
34.2
36.6
39.4
20.1
36.1
46.2
24.4
35.7
43.0
36.3
37.7
39.7

29
156
386
24
112
239
25
75
151
17
124
326
24
85
201
28
65
110
21
106
294
25
80
167
30
51
84
24
115
275
25
76
146
28
49
76
26
105
236
25
68
132
30
46
64
28
98
208
25
62
115
31
43
56
30
92
207
26
58
108
33
39
47
32
100
207
26
58
98
34
37
43

< 20
32.5
45.1
< 20
35.0
45.6
20.8
36.0
45.7
< 20
31.4
44.9
< 20
34.1
46.0
26.5
38.4
45.8
< 20
30.9
45.1
< 20
35.4
45.6
30.9
38.5
45.4
< 20
33.3
45.5
21.0
36.5
45.5
32.1
39.8
45.8
< 20
33.1
44.4
22.6
36.4
45.6
35.2
41.0
45.8
< 20
33.1
43.7
24.0
36.5
45.0
37.9
42.2
45.9
< 20
33.2
44.5
25.3
36.6
45.4
40.2
42.6
45.4
< 20
35.1
45.2
26.4
37.7
45.0
42.3
43.7
45.7

PW
(water)
kPa

1.3

1.7

2.0

2.3

7.6

8.5

9.3

10.2

Performance overview heating


with 4-pipe system

Correction factors
50

70

90

110

130

150

0.70
0.70
0.69
0.69
0.47
0.46
0.45
0.44

1.00
1.00
1.00
1.00
0.68
0.67
0.67
0.66

1.18
1.19
1.20
1.21
0.83
0.82
0.81
0.81

1.30
1.32
1.34
1.35
0.93
0.93
0.92
0.92

1.38
1.41
1.43
1.45
1.00
1.00
1.00
1.00

1.44
1.47
1.50
1.53
1.06
1.06
1.06
1.06

1.49
1.52
1.56
1.59
1.10
1.10
1.11
1.11

Reference values

Type of
nozzles

K
900

M
G
K

1200

M
G
K

1500

M
G
K

1800

M
G
K

2100

M
G
K

2400

M
G
K

2700

M
G
K

3000

M
G

10

50 l/h 60

III

70 80

90

100
110

4.0

IV

3000
2800

3.5
12

2400
150

10
8

200
250

WH

3.0

2100

2.5

1800
1500

2.0

1200
900

1.5

LN

1.0

tR
= tPr = 22C (isothermal)
WH = 50 l/h (LN 900 up to 1800)
WH = 110 l/h (LN 2100 up to 3000)
tRWV = tWVH tR = 28 K

LN

14

pW in kPa

LN

900
1200
1500
1800
2100
2400
2700
3000

4.5

16

30

tW in K

WH in l/h

.
V Pr

l/s

m3/h

.
.
Q S = Q ges
(water)
watts

3
7
11
6
13
19
11
19
27
3
8
13
8
15
23
15
23
30
4
9
15
10
18
26
19
25
32
5
11
17
12
21
29
22
29
36
6
12
18
14
23
32
26
32
38
7
13
19
16
25
34
30
35
40
8
14
21
18
27
37
34
37
41
9
16
23
20
30
39
38
40
43

11
25
40
22
47
68
40
68
97
11
29
47
29
54
83
54
83
108
14
32
54
36
65
94
68
90
115
18
40
61
43
76
104
79
104
130
22
43
65
50
83
115
94
115
137
25
47
68
58
90
122
108
126
144
29
50
76
65
97
133
122
133
148
32
58
83
72
108
140
137
144
155

184
399
502
246
452
543
316
457
542
125
469
613
316
536
668
416
559
642
178
529
711
383
632
767
509
621
714
229
624
800
446
720
854
575
705
798
379
965
1264
711
1135
1388
943
1114
1249
446
1037
1350
799
1226
1488
1066
1208
1326
512
1104
1471
884
1311
1605
1185
1271
1371
576
1235
1587
967
1428
1692
1299
1355
1432

0.5

0
200 400 600 800 1000 1200 1400 1600 1800 2000

0
50 60 70 80 90 100 110 120 130 140 150 160 170

WH in W

WH in l/h
.
VPr /m2

tW

.
q Zul

W/m2

l/(s m2)

m3/(h m2)

3.2
6.9
8.6
4.2
7.8
9.3
5.4
7.9
9.3
2.2
8.1
10.5
5.4
9.2
11.5
7.2
9.6
11.0
3.1
9.1
12.2
6.6
10.9
13.2
8.8
10.7
12.3
3.9
10.7
13.8
7.7
12.4
14.7
9.9
12.1
13.7
3.0
7.5
9.9
5.6
8.9
10.8
7.4
8.7
9.8
3.5
8.1
10.6
6.2
9.6
11.6
8.3
9.4
10.4
4.0
8.6
11.5
6.9
10.3
12.5
9.3
9.9
10.7
4.5
9.7
12.4
7.6
11.2
13.2
10.2
10.6
11.2

31
66
84
41
75
90
53
76
90
17
63
82
42
72
89
55
75
86
20
59
79
43
70
85
57
69
79
22
59
76
43
69
81
55
67
76
32
80
105
59
95
116
79
93
104
33
77
100
59
91
110
79
89
98
34
74
98
59
87
107
79
85
91
35
75
96
59
87
103
79
82
87

0.5
1.2
1.8
1.0
2.2
3.2
1.8
3.2
4.5
0.4
1.1
1.7
1.1
2.0
3.1
2.0
3.1
4.0
0.4
1.0
1.7
1.1
2.0
2.9
2.1
2.8
3.6
0.5
1.0
1.6
1.1
2.0
2.8
2.1
2.8
3.4
0.5
1.0
1.5
1.2
1.9
2.7
2.2
2.7
3.2
0.5
1.0
1.4
1.2
1.9
2.5
2.2
2.6
3.0
0.5
0.9
1.4
1.2
1.8
2.5
2.3
2.5
2.7
0.5
1.0
1.4
1.2
1.8
2.4
2.3
2.4
2.6

1.8
4.2
6.6
3.6
7.8
11.4
6.6
11.4
16.2
1.4
3.8
6.2
3.8
7.2
11.0
7.2
11.0
14.4
1.6
3.6
6.0
4.0
7.2
10.4
7.6
10.0
12.8
1.7
3.8
5.8
4.1
7.2
9.9
7.5
9.9
12.3
1.8
3.6
5.4
4.2
6.9
9.6
7.8
9.6
11.4
1.9
3.5
5.1
4.3
6.7
9.1
8.0
9.3
10.7
1.9
3.4
5.0
4.3
6.5
8.9
8.2
8.9
9.8
2.0
3.5
5.0
4.4
6.5
8.5
8.3
8.7
9.4

LWA, entry from


top
side
dB(A)
dB(A)

Pt
(air)
Pa

< 20
32.5
45.1
< 20
34.0
44.6
< 20
32.0
41.7
< 20
31.4
44.9
< 20
33.1
45.0
22.5
34.4
41.8
< 20
30.9
45.1
< 20
34.4
44.6
26.9
34.5
41.4
< 20
34.3
46.5
< 20
34.5
43.5
26.1
33.8
39.8
< 20
34.1
45.4
20.6
34.4
43.6
29.2
35.0
39.8
< 20
34.1
44.7
22.0
34.5
43.0
31.9
36.2
39.9
< 20
34.2
45.5
23.3
34.6
43.4
34.2
36.6
39.4
20.1
36.1
46.2
24.4
35.7
43.0
36.3
37.7
39.7

29
156
386
24
112
239
25
75
151
17
124
326
24
85
201
28
65
110
21
106
294
25
80
167
30
51
84
24
115
275
25
76
146
28
49
76
26
105
236
25
68
132
30
46
64
28
98
208
25
62
115
31
43
56
30
92
207
26
58
108
33
39
47
32
100
207
26
58
98
34
37
43

< 20
32.5
45.1
< 20
35.0
45.6
20.8
36.0
45.7
< 20
31.4
44.9
< 20
34.1
46.0
26.5
38.4
45.8
< 20
30.9
45.1
< 20
35.4
45.6
30.9
38.5
45.4
< 20
33.3
45.5
21.0
36.5
45.5
32.1
39.8
45.8
< 20
33.1
44.4
22.6
36.4
45.6
35.2
41.0
45.8
< 20
33.1
43.7
24.0
36.5
45.0
37.9
42.2
45.9
< 20
33.2
44.5
25.3
36.6
45.4
40.2
42.6
45.4
< 20
35.1
45.2
26.4
37.7
45.0
42.3
43.7
45.7

PW
(water)
kPa

0.12

0.14

0.16

0.18

0.85

0.93

1.02

1.11

Aerodynamic data

Correction factors for diagram values


depending on length of unit L N
LN
in mm

900

1200

1500

1800

2100

2400

2700

3000

v-L, v-H1, Xkrit.


from diagram

0.92

0.96

1.0

1.04

1.07

1.11

1.14

1.17

tL, tZ, tH1 /tZ


from diagram

0.87

0.94

1.0

1.05

1.09

1.13

1.17

1.20

Nozzle type K

Nozzle type K
H1 0.8

0.60

6
4 -

0.07

0.30

-4

0.06

0.25

0.05

2.0

3.0

0.018
0.016
0.014

VI

0.04
6.0

4.0

0.012
1.0

Distance L or Xkrit in m

0.09

-8

0.07

K
-6

0.30

K
-4

0.06

0.05

0.25

1.0

3.0

0.016

VIII

0.04
6.0

4.0

1.0

Distance L or Xkrit in m

1.5

2.0

0.040

0.55

0.22

tL/tZ

0.50

0.20

0.18

0K
K
-8

0.14
-

0.30

6K

r=

K
-4

16

tL/tZ

1.5

2.0

0.10

12

0.20
1.0

l/s

0.

IX

0.12

15

14

0.25

18

3.0

H1 in m/s

-1

0.35

4.0

Distance L or Xkrit in m

0.08
6.0

18

l/s

0.030

0.
0 0
0
20 .25 .30 .40

0.16

tL / tZ

at
t
Z

0.035
r=

16
14
12

kr
it

0.012
6.0

1.2 1.6 2m

0.24

0.40

4.0

Nozzle type G
H1 0.8

0.60

0.45

3.0

Spacing A or A/2 + H1 in m

Nozzle type G

L in m/s

0.020
0.018

10
2.0

0.022

0.
1.5

0.024

0.014

VII
0.20

0.026
l/s

0 0
20 .25 .30

0.08
K

12

10

0.

-1

r=

0.
15

0.35

at Xkrit
t
Z

0.10

H1 in m/s

0.40

6.0

0.030

tL/tZ
P

tL / tZ

l/s

10

4.0

1.2 1.6 2m

0.11

tL/tZ
12

3.0

tH1 / tZ

0.45

L in m/s

H1 0.8

0.12

0.50

2.0

Nozzle type M

0.60
r=

1.5

Spacing A or A/2 + H1 in m

Nozzle type M
0.55

0.020

0.026
0.024
0.022

tH1 / tZ

1.5

0.022

0.

0.20
1.0

0.024
m

tL/tZ

10

0 0
20 .25 .30

-8

0.08

0.

0.35

l/s

0.09

-1

15

at Xkr
t it
Z

0.45

0.026

r=

0.

l/s

0.40

0.10

tH1 / tZ

r=

tL/tZ

H1 in m/s

0.50

0.030

0.11

tL / tZ

0.55

L in m/s

1.2 1.6 2m

0.12

0.020
0.018

0.016
1.0

1.5

2.0

3.0

4.0

6.0

Spacing A or A/2 + H1 in m

11

Order details

Specification text
Support angles and flexible hoses are available as accessories for the
DID300B unit.

The active chilled beam type DID300B is suitable for dealing with
high internal heat loads using a combination of air and water.
It consists of the top plenum which serves as primary air duct and
a diaphragm plate with nozzles in two longitudinal rows (different
nozzle sizes are available). A coil is fitted underneath the primary air
plenum and diaphragm plate. The induction grille below the coil is a
perforated plate. The coil can be used either for heating or cooling
(2-pipe system) as well as heating and cooling (4-pipe system).
The external diameter of the bare coil tube ends is 12 mm. Primary
and conditioned induced air are mixed in the unit and discharged
horizontally with coanda effect into the room via the two slots formed
by the external frame and the internal extrusions. There are holes in
the casing to enable the unit to be hung by the customer.
A construction incorporating an extract air spigot can be provided.
Spigots for supply and extract air can be either side or top mounted.

Materials
Casing, including the top plenum and perforated plate induction grille
are made of galvanised steel sheet.
The standard finish of the casing and the induction grille is powdercoated white (RAL 9010), the top casing (plenum) and coil remain
untreated optionally can be finished in black (RAL 9005), nozzle
plate only finished in black (RAL 9005).
The heat exchanger consists of copper tubes with formed aluminium
fins. The flexible hose, available as an accessory, is made of special
plastic with stainless steel sheathing.

Order code
These codes do not need to be completed for standard products

DID300B - 2 - K - H - SV - ALV

1800 x 1500

P1

RAL 9016

/ G3

EI
EE
OEE
EE
EE
PE

Coil:
Two-pipe
Four-pipe

2
4

Nozzle options:
small
K
medium
M
large
G

900 x 900
1200
1500
1800 1)
1200 x 1200
1500
1800
1500 x 1500
1800
2100
1800 x 1800
2100
2400
2100 x 2100
2400
2700
2400 x 2400
2700
3000
2700 x 2700
3000
3000 x 3000
L1 x LN
(mm)

IEE
OE
P
IE
EEO
EE
EP

Spigot and casing


arrangements
(see page 4)

IE
EEO
EE
EP

Design changes reserved All rights reserved TROX GmbH (6/2006)

1) For casing arrangement M, MV and MH


2) GE = Gloss level

Accessory:
FS12-... (see table)
AW = Support angle

Not used

TE
EE
EE
EZE
EE
EE
EU

TE Coil finish:
EE
EE
EZE 0 Standard untreated
EE
EE G3 Finished
UE to RAL 9005

Standard finish
Powder-coated to RAL 9010
(GE 50%) 2)

P1 Powder-coated to RAL . . .
(GE 70%) 2)

Note:
L1 = 893 ... 3000 mm
LN only available in standard length
L1 maximum 7 mm shorter than LN

L1 = Total length (diffuser face)


LN = Nominal length

Accessory: Flexible hose (FS12) (see page 6)


Available connectors
both ends

combination

FS12-S

FS12-S/U

length in mm

Order example
500, 750, 1000

FS12-S/A

12

Make: TROX
Type: DID300B-2-K -H-SV-ALV / 1800 x 1500 / P1 / RAL 9016 / G3