Air Handling Units

IA
N
G

M ER

AN AIR T R

EA T
M

EN

PT

TC

EGY

CS - SERIES
For Air Conditioning Installations and Industrial Ventilation Plants

o.

GENERAL CHARACTERISTICS Summary of the CS Series range availability


Air Volume
From 0.39 m3/s (1400 m3/h) to 23 m3/sec (83000 m3/h), 21 unit sizes.

Total Air Pressure Development


Up to 800 Pa - Forward blade Fan Class I Up to 1000 Pa - Backward blade Fan Class II All fans are double inlet type and with belt drive.

CS series

Electric Motor
The electric motor is normally installed inside the fan section, in the air stream.

Air Treatment

Heating - Low pressure hot water - Medium/High pressure hot water - Saturated steam - Electric Cooling - Mains or well water - Recirculated brine - Recirculated chilled water - Direct expansion refrigeration

Humidification

Water spray type : with single or double bank water spray nozzles . Choice of once through to waste water or pump recirculated water.

Filtration

Medium Efficiency: Disposable flat or pleated

Air Intake
Fresh air
With inlet rain louvre or cowl, bird screen or damper with duct type, damper with counter flange

panel type Washable flat or pleated panel type Bag or rigid cartridge type Automatic roll filter filters of various lengths and dust holding capacity Standard or large air volume

High efficiency: Standard or rigid bag

Air mixing

With dampers for return air and fresh air

Air mixing and exhaust With dampers for exhaust,


return and fresh air

Absolute

Activated carbon: Cell or cartridge type

TECHNICAL DATA
Temperature
tw tw ts ts tu tu tvs te C C C C C C C C Inlet water temperature Outlet water temperature Inlet air temperature - dry bulb Outlet air temperature - dry bulb Inlet air temperature - wet bulb Outlet air temperature - wet bulb Saturated steam temperature Evaporating temperature

Air Handling Units

Pressure
ps pd pt pvs Pa Pa Pa bar Static pressure Dynamic pressure Total pressure Actual saturated steam pressure

Enthalpy
J J cal/kg cal/kg Total heat air inlet Total heat air outlet

Humidity
x x UR g/kg g/kg % Absolute humidity air inlet Absolute humidity air outlet Relative humidity

Vol./Q.ty
V Vw tw t pw p J x m3 /h m3 /s I/h

Air volume Air volume Water quantity Water temperature difference Air temperature difference Water pressure drop Air pressure drop Total heat difference Absolute humidity difference

Technical Manual presents basic information to select our standard range of CS Series Air Handling Units. Our manual is divided into two sections. Section 1 REFERENCE DATA provides basic information enabling the unit size to be selected, the modular components to be chosen and the technical characteristics and construction features to be summarised. Section 2 TECHNICAL DATA provides technical information in the form of data sheet to enable more detailed selection to be performed to meet the precise specification requirements.

C C mH2O Pa cal/kg g/kg

Velocity
cu cw Q Q

m/s m/s

Air velocity Water velocity

Capacity

Kcal/h Heating capacity KFrig/h Cooling capacity

Lpa N n kw Fbp PD2

Others

db kw rpm %

kg/m2

Sound level Power installed Revolutions speed Efficiency By-pass factor Dynamic moment

Note: The unit performances and all section diagrams are referred to following standard air conditions: - Air temperature + 15 C - Air specific weight 1,225 kg/m3 - Atmospheric pressure 760 mm Hg

SELECTION DIAGRAM

The unit size selection is made on the basis of two parameters: the Air volume the Coil Face air velocity Each model is identified by a very simple nomenclature: for example CS-200 corresponds to the air volume of 20000 m 3 /h at 2,5 m/s coil face velocity. The Selection Diagram shows the possibility of achieving smaller or greater air volumes for the same unit by varying the coil face velocity.

100

830 680 550 450

50 40 30 25 20

370 300 250 200 165 135 110 90

AIR VOLUME (x103) m3/h

10

73 60 49 40

5 32 4 3 26 21 17 2 14

1 2 2,5 3 AIR VELOCITY (m/s) 3,5

UNIT SIZE CS

This enables selection to be optimised in terms of cost, dimensions, noise criteria, power, etc.

15

UNIT SECTIONS General description of unit casing


The casing of the CS series Air Handling Units is composed of : Self supporting frame in extruded aluminium profiles anodised natural colour assembled by corners to give accurate alignment and easily cleaneable corrosion resistant structure. Sandwich type double skin panels 23 mm thickness with internal thermal insulation of special high density acoustic insulation. The external and internal sheet metal faces of the panel can be selected from: - Galvanized sheet steel 0.6 mm thick . - Plastic coated galvanized sheet steel 0.6 mm thick . - External and internal faces can be of different materials. - Galvanized screws inserted in nylon sleeves are used to fix the panel to the frame and air tightness is assured by an exclusive rubber seal under the panel. - Inspection and access doors constructed of sandwich panels as described above fixed to the casing frame by air tightening hinges and closed with nylon handles of design with a progressive threaded closing device. Mechanically secured exclusive rubber door seal ensures air tightness .

On request the CS series can be equipped with: - Bulkhead lights with or without external switch - Filter manometers . The unit support is provided by : - Strong steel profiles with holes for unit lifting. - Drain pan with sandwich panel insulation. All units can be easily supplied in separate divided sections or completely knocked down for transport, site, space or erection requirements.

Air mixing box


Complete with up to 3 dampers to provide mixing control of fresh, recirculated and exhaust air streams. The dampers are available in: - Extruded aluminium profile blade - Extruded aluminium with tight shut off edge seal Complete with : - Opposed blades - Shaft - Hand operation levers - Extension for connection of actuator motor or piston The damper blades are gear wheel driven .

UNIT SECTIONS

Filter section
See our separate Filter catalogue

Air treatment section


The heating and cooling coils for the treatment of the air are housed in section and are of finned block type, having the following standard characteristics: - Copper tube and aluminium fins . - Tube pitch 60 and 30 mm . - Rows pitch 30 mm . - Fins pitch 2.0, 2.5, and 3.0 mm. - (4 and 6 mm for special application). - Tube diameter 5/8. - Coil framework galvanised sheet steel. - Connections - threaded. - Electric heaters with multi-stage sheathed. elements with plain surface or extended fin surface dependent on duty.

Fan section
Forward blade and backward blade fans . The fans are always of belt drive, double inlet type, manufactured in galvanized steel sheet, with steel shaft and ball bearings.
The fan drive is effected through belts of trapezoidal shape. The motor pulley is made from aluminium or cast iron . Fixed and variable pulleys are available . The complete fan motor assembly will be mounted on a base constructed of extruded aluminium profiles and mounted on vibration isolators . Standard vibration isolators are of rubber, with spring type available on request. The anti-vibration connection mounted between the fan outlet and the casing is made of an aluminium profile frame with self-extinguishing cloth. The foregoing characteristics apply also to the return air and exhaust air fan sections. The units with twin fans operating in parallel are equipped with non-return dampers to prevent air re-circulation in the case of one fan not running.

UNIT SECTIONS Accessories


We provide as accessories the optional and complementary equipment described as follows:

Sound Attenuators

See our separate Sound Attenuators catalogue .

Germicidal Lamps Section

This section is specifically designed for specific application requirements. The internal walls are provided with reflecting surface, manufactured in aluminium, plain or white painted finish. The tube shape lamps are installed in the required number.

Internal Lighting System

Normally the internal lighting is required for the filter section, the Humidifier section and the fan section .

WATER COOLING COILS Selection of coils


With chilled water coils, the number of rows necessary to satisfy the requested cooling capacity can be immediately determined by the following diagrams, for water 5/10C and 7/12C respectively. The number of rows is found by following the tracing on the diagrams for the example selection as a function of air inlet conditions, selected unit size, air velocity through the coil, fins pitch and in relation to the required cooling capacity.

Selection diagram5/10C
4 5 6 8 10 10
J-

0,5
En tha lpy

0,3
Cal/k g

3R 4R

12

tu c

14

16

coil by-pass factor

18

15
5

20 u.r. % 100 90 80 70 60

5R

0,1

6R

0,05

7R
8 R

20

10

25

50
Air velocity

0,02 3 2,5 m/s 2

2m

m 2,5

3m

15

20

30

35

25

40 40 ts C

K Cal/h
900 1000 500 400
0 83 0 68 0 55 0 450 370 300 250 20 5 16 5 3 1 0 110 9 73 60 49 40 32 26 21 17 14

1000

1000

1000

1000

300 200

500 400 300 200

500 400 300 200

500 400 300 200

500 400 300 200

500 400 300 200

100 100 50 40 30 20 20 10 10 50 40 30 3 2,5 22 2,5 3 v. coil Fins pitch m/s mm 10 10 10 100 100 100

Unit size CS

100

50 40 30

50 40 30 20

50 40 30 20

50 40 30 20

50 40 30 20

10

50 40 30

50 40 30

50 40

50 40

50 40

3R 4R 5R 6R 7R 8R

WATER COOLING COILS

Selection diagram 7/12C


4 5 6 0,5 8 12
Cal/k g
J-

coil by-pass factor

10

10

En tha lpy

0,3 3 R
4R

tu c

14

16

18

15
5

20 u.r. % 100 90 80 70 60

5R

0,1

6R

20

0,05

7R
8 R

10

25

50
Air velocity

0,02 3 m/s 2,5 2

2m

m 2,5

3m

20

30

15

35

25

40 40 ts C

K Cal/h
1000 1000 500 400 300
0 83 0 8 6 0 5 5 0 5 4 0 370 30 0 250 20 5 16 5 13 0 11 0 9 73 60 49 40 32 26 21 17 14

1000

1000

1000

1000

500 400 300 200

500 400 300 200

500 400 300 200

500 400 300 200

500 400 300 200

200

100

100

Unit size CS

100

100

100

100

50 40 30 20

50 40 30 20

50 40 30 20

50 40 30 20

50 40 30 20

50 40 30 20

10

10 10 10 10 10

50 40 30 3 3,5 22 2,5 3 v. coil Fins pitch m/s mm

50 40 30

50 40

50 40

50 40

50 40

3R 4R 5R 6R 7R 8R

FANS
Determination of CS pressure drops
To determine fan characteristics it is absolutely necessary to calculate the pressure drops, expressed in Pa, of the different sections forming the unit and to add them to the required external pressure drop . It will result :
Air intake louvres Mixing box with air dampers Filter cells Roll filters Bag filters Spray humidifier Evaporating package humidifier Preheating coil Reheating coil Precooling coil After cooling coil Electric coil Other coil Plenum Absolute filters Other Required external pressure drop

Arrangements for fans


Position of fan outlet for air distribution ducts

Dynamic Pressure
Dynamic Pressure and outlet air velocity are calculated on the full air discharge area including that of the cut- off area, and therefore ducted outlet conditions. In the case of free outlet the velocity pressure is higher and the new value is obtained by multiplying the velocity pressure of the ducted outlet from the curves, by the correction factor K shown in the table Nr. 2 below.

TOTAL

Pa

ADN = 1.38 RDN = 1.6

Tab. 2

Noise
The noise level shown on each diagram refers to the sound power (A filter) and the data on the inlet side has been measured in accordance with AMCA STANDARD 300 pict. 2 - configuration A. The noise levels of the fans are determined as follows: - Sound power level-(A scale):

Lw (A) as catalogue - octive band spectrum Lw = Lw (A) + Lw rel. dB (tab. 3- 4) - Sound pressure level a) free field Lp (A) = Lw (A) - (20log10 d) -11 b) room conditions Lp (A) = Lw (A) - (20log10 d) - 7 where d = is a distance of fan

ADN Lw (rel)

Correction factor for frequence analysis


Ventilatore / Fans 180/200/225 250/280/315/355 400/450/500/560 630/710/800/900/1000 HZ 63 -0.6 -3.7 +2 +5.4 125 -0.2 -3.6 +2.2 +6 250 0 0 +1.3 -0.7 500 -2.7 -1.3 -4.3 -4.4 1000 -5.3 -5.7 -5.6 -4.6 2000 -8.8 -9.6 -7.8 -11.5 4000 -13.5 -13.2 -14.3 -15.4

Tab. 3
8000 -17.6 -19.5 -19.1 -22.5

RDN Lw (rel)

Correction factor for frequence analysis


Ventilatore / Fans 160/180/200/225 250/280 315/355 400/450/500 560/630/710 800/900/1000 HZ 63 -9 -7.1 -3.2 +2.8 +3.2 +5.5 125 -3.9 -2.2 -1.5 +2.7 +1.7 +1.9 250 -1.2 -1.5 -3 +0.3 +1.3 +1.9 500 -4.7 -8.7 -5.7 -2.1 -3.8 -3.4 1000 -5.6 -4.7 -5.7 -7.1 -6.8 -6.2 2000 -6.6 -8.8 -7.7 7.8 -9.1 -11.3 4000 -9 -9.2 -8.4 -11.3 -13.4 -16.8

Tab. 4
8000 -12.8 -13 -13.5 -16.7 -19.9 23.5

Forward Blade Fan

NICOTRA

ADN 160
160 mm LR
WHEEL DIAMETER

= 1.2 Kg/ m3 TOTAL EFF. %

TOTAL PRESSURE

Pa N/m2

2500 2 2000
KW

24

31

39

45 3

49

43

27

1.5 1 .8 1000 .4 .3 3000 500 400 .2 .15 .1 85 2200 90 2600 .6 95 3500 4700 4200

300

200 .05

80

1800 1600

75
L w(A) in dB (A)

1400

100 1200 80 .05 x1000 .2 .3 2 .1 .4 .5 3 4 5 .2 1 .3 .4 .5 2 3 1 volume 4 5 m3/h m/s 2 m3/ s

10 20 30 40 air outlet velocity 50 100 500 1000 velocity pressure

10

Pa N/m2

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

RPM

Forward Blade Fan

NICOTRA

ADN 180
180 mm LR
WHEEL DIAMETER

= 1.2 Kg/ m3 TOTAL EFF. %

TOTAL PRESSURE

Pa N/m2

2500 2000
KW

22

28

36 3

44

52

47

32

2 1.5 1 4000 3500 95

1000

.8 .6 .4 .3 90 3000 2700 2400 2100 85 1800 .1 80 1600 1400 .05 75


Lw(A) in dB (A)

500 400 .2 .15


PRESSIONE TOTAL E

300

200

1200

100 1000 80 .05 x1000 1 .2 .3 .1 .4 .5 2 3 4 .2 .3 1 5 .4 .5 2 3 1 4 2 3 volume 5 10 m3/ s m3/h m/s

10 20 30 40 50 air outlet velocity 50 100 500 1000 velocity pressure

10

Pa N/m2

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

RPM

Forward Blade Fan

NICOTRA

ADN 200
200 mm LR
WHEEL DIAMETER

= 1.2 Kg/ m3 TOTAL EFF. %

TOTAL PRESSURE

Pa N/m2

29 3500 3000
KW

35

42

47

52

52

39

3 2000 1.5 1 .8 1000 .6 2

3800

3200 2900 2600 95 2300 2000 90 1800 1600

.4 .3 500 .2 400 .15 85 300 .1 1200 200 .05 1000 75


Lw(A) in dB (A)

1400

80

100 80 .05 x1000 .2 1 .3 .1 .4 .5 2 3 .2 1 4 5 .3 . 4 .5 2 3 1 4 5 2 volume 10 4

800 m3/ s m3/h m/s

10 20 30 40 50 air outlet velocity 50 100 500 1000 velocity pressure

10

Pa N/m2

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

RPM

Forward Blade Fan

NICOTRA

ADN 225
225 mm LR
WHEEL DIAMETER

= 1.2 Kg/ m3 TOTAL EFF. %

TOTAL PRESSURE

Pa N/m2

3500 3000
KW

26

32

38

44

52

55

34

3 4 2 1.5 3000 1 .8 2600 2300 2000 95 1800 1600 90 1400

2000

3400

1000

.6 .4 .3

500 .2 400 300 .15 .1 85 200 .05 80 900


Lw(A) in dB (A)

1200

1000

800

100 80 .05 x1000 .1 .3 1 .5 2 3 .2 .3 1 4 5 . 4 .5 2 3 1 4 5 2 3 4 volume 10 5 m3/ s m3/h m/s

10 20 30 40 50 air outlet velocity 50 100 500 1000 velocity pressure

10

Pa N/m2

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

RPM

Forward Blade Fan

NICOTRA

ADN 250
250 mm LR
WHEEL DIAMETER

= 1.2 Kg/ m3 TOTAL EFF. %

Pa N/m2

K 22 30 39 48

TOTAL PRESSURE

3500 3000
KW

56

54

39

5 4 2000 3 2 1.5 1000 1 .8

7.5 3000 2800 2400 2200 2000 1800 95 1600 1400 90 1200

.6 500 400 300 .2 85 .15 200 .1 80 .4 .3

1000 900 800 700


Lw(A) in dB (A)

100 80 .08 x1000 .3 1 .5 2 .2 .3 1 3 4 .4 .5 2 5 3 1 4 5 2 3 4 6 volume 10 20 m3/ s m3/h m/s

10 20 30 40 50 air outlet velocity 50 100 500 1000 velocity pressure

10

Pa N/m2

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

RPM

Forward Blade Fan

NICOTRA

ADN 280
280 mm LR
WHEEL DIAMETER

= 1.2 Kg/ m3 TOTAL EFF. %

Pa N/m2

K 29
KW

TOTAL PRESSURE

3500 3000

37

44

51 11

58

59

42

5.5 4

7.5

2700 2500

2000 2 1.5

3 2100

1800 1000 .8 .6 500 400 300 .2 .15 200 .1 80 700 600 85 800 .4 .3 90 1000 95 1400 1200 1 1600

Lw(A)

in dB (A)

100 80 .1 x1000 1 .5 .2 .3 1 2 3 .4 .5 2 4 5 3 1 4 5 2 3 10 4 5 volume 20 8 m3/ s m3/h m/s

10 20 30 40 50 air outlet velocity 50 100 500 1000 velocity pressure

10

Pa N/m2

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

RPM

Forward Blade Fan

NICOTRA

ADN 315
315 mm LR
Pa N/m2
WHEEL DIAMETER

= 1.2 Kg/ m3 TOTAL EFF. %


RPM

K 29 36 43 50

TOTAL PRESSURE

3500 3000
KW

57

60

47 2400 2100 1900 1700 1500 1300

8
5.5

11

2000 4 3 2 1000 1.5 1 .8 500 400 300 .2 200 80 .1 .4 .3 85 .6 90 95

1100 1000 900 800 700

600

500
Lw (A) in dB (A)

100 80 .15 x1000 1 .3 1 2 3 .4 .5 2 4 3 5 1 4 5 10 2 3 10 4 5 volume 20 30 10 m3/ s m3/h m/s

20 30 40 50 air outlet velocity 100 500 1000 velocity pressure

10

50

Pa N/m2

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

Forward Blade Fan

NICOTRA

ADN 355
355 mm LR
WHEEL DIAMETER

= 1.2 Kg/ m3 TOTAL EFF. % 46 53 58 62 61 46

Pa N/m2

K 39
KW

TOTAL PRESSURE

3500 3000

7.5
5 2000 3 2 1000 1.5 1 .8 500 400 300 .2 .4 .3 .6 4

10

15

2000 1800 1600 1400 1200

1000 95 900 800 90 700 600

200

85 500

Lw (A)

in dB (A)

100 80 .2 x1000 1 .3 1 2 .4 .5 2 3 3 4 5 1 4 5 10 2 3 10 4 5 20 10 volume 30 14 m3/ s

40 50 m3/h m/s

20 30 40 50 air outlet velocity 100 500 1000 velocity pressure

10

50

Pa N/m2

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

RPM

Forward Blade Fan

NICOTRA

ADN 400
400 mm LR
Pa N/m2
WHEEL DIAMETER

= 1.2 Kg/ m3 TOTAL EFF. %


RPM

K 34
KW

TOTAL PRESSURE

3500 3000

43

52

61

67

62

46

7. 5 2000 6 4 3 1000 1.5 1 500 400 300 .3 .4 .8 2

10

15
1800 1600 1500 1300

1100 1000 95 900 800

.6 90 700 600 85

200

.2 500 80 .1
Lw (A) in dB (A)

400

100 80 .2 x1000 1 1 .5 2 2 3 3 1 4 4 5 5 2 3 10 4 5 20 10 volume 30 16 m3/ s m3/h m/s

40 50

10 20 30 40 50 air outlet velocity 50 100 500 1000 velocity pressure

10

Pa N/m2

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

Forward Blade Fan

NICOTRA

ADN 450
450 mm LR
Pa N/m2
WHEEL DIAMETER

= 1.2 Kg/ m3 TOTAL EFF. % 38 45 53 60 66 61 47


RPM

TOTAL PRESSURE

2500 2000
KW

8 6 4

11

15

1500 1400

1200

1000 2

3 1000 900 1.5 95 800 700 90 600 .4 .3 85 500

500 400 .8 .6 300

200 .2 80 400
Lw (A) in dB (A)

100 80 .25 x1000 1 1 .4 .5 2 2 3 3 1 4 5 4 5 2 3 10 4 5

350

10 volume 30 40 50

18

m3/ s m3/h m/s

20

10 20 30 40 50 air outlet velocity 50 100 500 1000 velocity pressure

10

Pa N/m2

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

Forward Blade Fan

NICOTRA

ADN 500
500 mm LR
WHEEL DIAMETER

= 1.2 Kg/ m3 TOTAL EFF. %

Pa N/m2

K 40
KW

TOTAL PRESSURE

2500 2000

49

57

64

66

56

39

8 6 4 3 2 1.5 500 400 .8 300 .6 .4 200 .3 .2 1

11

15

1300 1200

1000

1100 1000 900 800 700 90

95

600

85

500

80
Lw (A) in dB (A)

400 350

100 80 .4 x1000 1 2 3 2 1 4 3 5 4 5 2 3 10 10 4 5 20 30 10

20 25 m3/ s volume m3/h m/s

40 50

20 30 40 50 air outlet velocity 100 500 1000 velocity pressure

10

50

Pa N/m2

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

RPM

Forward Blade Fan

NICOTRA

ADN 560
560 mm LR
Pa N/m2
WHEEL DIAMETER

K2

= 1.2 Kg/ m3 TOTAL EFF. %


RPM

K 38
KW

TOTAL PRESSURE

3500 3000

46

55

64

68

60

44

25
15 10 8

37
1300 1200 1100 1000 900 100 800 700

18.5

2000

6 1000 4 3 2 500 1.5 400 1 300 .8 .6 200 85 .4 .3 80


Lw (A) in dB (A)

95

600 90 500 450 400 350 300

100 80 .5 x1000 1 2 3 2 1 4 5 3 4 2 3 10 5 4 5 20 10 30 10 40 50 20 volume 32 100

m3/ s m3/h m/s

20 30 40 50 air outlet velocity 100 500 1000 velocity pressure

10

50

Pa N/m2

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

Forward Blade Fan

NICOTRA

ADN 630
630 mm LR
Pa N/m2
WHEEL DIAMETER

K2

= 1.2 Kg/ m3 TOTAL EFF. %


RPM

K 36
KW

TOTAL PRESSURE

3500 3000

46

56

64

68

59

42

45 30
18. 5 15 1100 1000

2000

10 8 1000 4 3 500 400 300 .8 200 .4 .6 85 1.5 1 2 6

900 800 700 100 600 95 500 450 90 400 350 300 80
Lw (A) in dB (A)

100 80 .6 x1000 1 3 1 4 5 2 3 2 3 10 4 5 4 5 20 10 30 10 40 50 20 30 volume 100 45

250 m3/ s m3/h m/s

20 30 40 50 air outlet velocity 100 500 1000 velocity pressure

10

50

Pa N/m2

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

Forward Blade Fan

NICOTRA

ADN 710
710 mm LR
Pa N/m2
WHEEL DIAMETER

K2

= 1.2 Kg/ m3 TOTAL EFF. %


RPM

K 35
KW

TOTAL PRESSURE

2500 2000

44

54

64

69

60

43

45
15 10

18.5

30
900 850 750 700

1000 6 4

600 100

3 500 400 1.5 300 1 .8 200 .6 300 85 250


Lw (A) in dB (A)

500 2 95 450 400 90 350

100 80 .8 x1000 1 5 2 3 2 3 10 4 5 4 5 20 30 10 40 50 20 30 volume 100 45 m3/ s m3/h m/s

10 20 30 40 50 air outlet velocity 50 100 500 1000 velocity pressure

10

Pa N/m2

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

Forward Blade Fan

NICOTRA

ADN 800
800 mm K
Pa N/m2
WHEEL DIAMETER

= 1.2 Kg/ m3 TOTAL EFF. % 46 54 63 70 62 44


RPM

K2 38
KW

TOTAL PRESSURE

2500 2000

45
22 15

30

800 750

1000

10 8 6 4 100

650 600 550 500

500 3 400 2 300 95

450 400 350

1.5 1

90 300 85 250

200

.8

.5 80 100 80 1 x1000 1 4 5 2 2 3 10 3 4 4 5 20 5 30 10 40 50 20 30 40 volume 100 m3/ s 55 m3/h m/s


Lw (A) in dB (A)

200

10 20 30 40 50 air outlet velocity 50 100 500 1000 velocity pressure

10

Pa N/m2

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

Forward Blade Fan

NICOTRA

ADN 900
900 mm K
Pa N/m2
WHEEL DIAMETER

= 1.2 Kg/ m3 TOTAL EFF. % 35 44 53 63 70 66 48

K2

TOTAL PRESSURE

2500 2000
KW

30 20 15

40

50

75 700 650

1000 10 8 100 6 500 400 2 1.5 200 3

4 95 350

300

90

1 85 .6 80
Lw (A) in dB (A)

100 80 1 x1000 1 5 2 3 10 2 3 4 5 20 4 5 30 10 40 50 20 30 40 70 volume 100 200

10 20 30 40 50 air outlet velocity 50 100 500 1000 velocity pressure

10

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

GIRI / m RPM

550 500 450 400

300

250

200

170 m3/ s m3/h m/s

Pa N/m2

Forward Blade Fan

NICOTRA

ADN 1000
1000 mm K
WHEEL DIAMETER

= 1.2 Kg/ m3 TOTAL EFF. % 38 49 61 70 67 51

Pa N/m2

K2 29
KW

TOTAL PRESSURE

2500 2000

75 50 37 30 550 650 600

1000

20 15 10 8

100

500 400 4 300 2 200 1.5 3

6 95

90

85 1
Lw (A) in dB (A)

100 80 1.4 x1000 1 3 10 2 3 4 5 20 4 30 5 10 40 50 20 30 100 40 50 80 volume 200

10 20 30 40 air outlet velocity 50 100 500 1000 velocity pressure

10

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

GIRI / m RPM
500 450 400 350 300 250 200 160 m3/ s m3/h m/s Pa N/m2

Backward Blade Fan

NICOTRA

RDN 180
180 mm LR
WHEEL DIAMETER

= 1.2 Kg/ m3 TOTAL EFF. %

TOTAL PRESSURE

Pa N/m2

3500 3000
KW

33

46

57

60

54

41

27

1.5 1 .8 .6

2000

1000

.4 .3 .2

500 400 300

.15 .1 85

90

7500 6800 6000 5500 5000

200

80

4500 4000

75 100 70

3500 3000 2500

50

65
Lw(A) in dB (A)

2000 30 .05 x1000 1 .2 .3 .1 .4 .5 2 3 4 .2 1 5 .3 . 4 .5 2 3 1 4 2 volume 5 2 . 6 m3/ s m3/h m/s

10 20 30 40 air outlet velocity 50 100 500 1000 velocity pressure

10

Pa N/m2

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

RPM

Backward Blade Fan

NICOTRA

RDN 200
200 mm LR
WHEEL DIAMETER

= 1.2 Kg/ m3 TOTAL EFF. %

TOTAL PRESSURE

Pa N/m2

3500 3000
KW

42 3 2

51

58

62

61

54

43

2000

1.5 1 .8 .6

1000 .4 .3 500 400 300 .2 .15 80 85 90

7000 6000 5500 5000 4500 4000 3500

200

75 3000

70
Lw(A) in dB (A)

2500 2200

100 80 .1 x1000 .4 .5 2 3 .2 1 4 5 .3 .4 .5 2 3 1 4 5 2 volume

2 . 6 m3/ s m3/h m/s

10 20 30 air outlet velocity 50 100 500 velocity pressure

10

Pa N/m2

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

RPM

Backward Blade Fan

NICOTRA

RDN 225
225 mm LR
WHEEL DIAMETER

= 1.2 Kg/ m3 TOTAL EFF. %

TOTAL PRESSURE

Pa N/m2

3500 3000
KW

41 4 3 2 1.5 1 .8

51

59

65

64

54

40

2000

1000 95

6300 5800 .4 .3 5000

500 .2 400 300 85

90

4500 4000 3500 3000

200

80 2600 2300 75
Lw(A) in dB (A)

100 80 .14 x1000 .6 2 3 .2 1 4 5 .3 .4 .5 2 3 10 1 4 5 2 3 volume 10 4

2000

m3/ s m3/h m/s

20 30 40 air outlet velocity 100 500 1000 velocity pressure

10

50

Pa N/m2

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

RPM

Backward Blade Fan

NICOTRA

RDN 250
250 mm LR
WHEEL DIAMETER

= 1.2 Kg/ m3 TOTAL EFF. % 48 60 68 67 56 42

Pa N/m2

K 36
KW

TOTAL PRESSURE

3500 3000 4 3 2000 2 1.5 1 .8 .6 .4 500 400 .3

1000

5400

4600 90 4000 85 3600 3200 80 2800

300

200 2400 75
Lw(A) in dB (A)

2000

100 80 .16 .2 x1000 .6 2 1 3 4 5 .3 .4 .5 2 3 1 4 10 5 2 3 4 volume 10 5 m3/ s m3/h m/s

20 30 40 air outlet velocity 100 500 1000 velocity pressure

10

50

Pa N/m2

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

RPM

Backward Blade Fan

NICOTRA

RDN 280
280 mm LR
WHEEL DIAMETER

= 1.2 Kg/ m3 TOTAL EFF. %

Pa N/m2

K 45 5.5
KW

TOTAL PRESSURE

3500 3000

56

65

70

68

59

47

4 3

2000 2 1.5 1 .8 .6 .4 500 400 .2 300 80 200 75


Lw(A) in dB (A)

4700 95 4300 4000 90 3600 3200 85 2800

1000

.3

2400

2000 1800 1600 1400 1 2 3 4 5 3 4 5 2 3 4 volume 10 5 m3/ s m3/h m/s

100 80 .2 x1000 2 .3 1 .4 .5

70

10 20 30 air outlet velocity 50 100 500 velocity pressure

10

Pa N/m2

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

RPM

Backward Blade Fan

NICOTRA

RDN 315
315 mm LR
WHEEL DIAMETER

= 1.2 Kg/ m3 TOTAL EFF. % 58 67 72 69 58 43

Pa N/m2

K 47
KW

TOTAL PRESSURE

3500 3000 5.5 4 2000 2 1.5 1000 .8 .6 500 400 300 .3 .4 1 3

7.5

4300 100 4000 3500 95 3200 2800 90 2400

200

85

2000 1800

80
Lw (A) in dB (A)

1600 1400

100 80 .25 x1000 1 2 3 .4 .5 2 4 3 5 1 4 5 10 2 3 10 4 5 6 volume 20 8

m3/ s m3/h m/s

20 30 40 air outlet velocity 100 500 1000 velocity pressure

10

50

Pa N/m2

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

RPM

Backward Blade Fan

NICOTRA

RDN 355
355 mm LR
WHEEL DIAMETER

= 1.2 Kg/ m3 TOTAL EFF. % 61 70 74 70 59 44

Pa N/m2

K 50
KW

TOTAL PRESSURE

3500 3000 5.5 4 2000 3 2 1.5 1000 1 .8 .6 500 400 300 .4 .3

10 7.5

4000 3800 100 3300

95

2800

2400 90 2000

200

1800 85 1600 1400


Lw (A) in dB (A)

80 100 80 .25 x1000 1 2 .4 .5 2 3 3 4 5 1 4 5 10 2 3 10

1200 4 5 volume 20 30 m3/h m/s 10 m3/ s

20 30 40 air outlet velocity 100 500 1000 velocity pressure

10

50

Pa N/m2

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

RPM

Backward Blade Fan

NICOTRA

RDN 400
400 mm LR
WHEEL DIAMETER

= 1.2 Kg/ m3 TOTAL EFF. % 61 72 76 71 58 42

Pa N/m2

K 49
KW

TOTAL PRESSURE

3500 3000 7. 5 5 4 3 2 1000 1.5 1 .8 500 400 .4 .6

11

2000

3400 3100 100 2800 2600 95 2300 2000

300

90

1800 1600

200 85

1400 1200

80 100 80 .4 x1000 2 2 3 3 4 1 4 5 5 2 3 10 10 4

Lw (A)

in dB (A)

5 20

10 volume 30

1000 14 m3/ s

40 50 m3/ h m/ s

20 30 40 50 air outlet velocity 100 500 1000 velocity pressure

10

50

Pa N/m2

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

RPM

Backward Blade Fan

NICOTRA

RDN 450
450 mm LR
WHEEL DIAMETER

= 1.2 Kg/ m3 TOTAL EFF. % 65 73 77 74 62 44

Pa N/m2

K 56 10
KW

TOTAL PRESSURE

3500 3000 7. 5 5 4 3 2 1000 1. 5 1 .8 500 400 300 .4 .6

15

2000

3100 2800 100 2500 2200 2000 1800 90 1600

95

200 85

1400 1200

80 100 80 .4 x1000 2 2 3 3 1 4 5 4 5 2 3 10 10 4 5

1100
Lw (A) in dB (A)

1000 900 16 m3/ s m3/ h m/ s

10 volume 20 30 40 50

20 30 40 air outlet velocity 100 500 1000 velocity pressure

10

50

Pa N/m2

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

RPM

Backward Blade Fan

NICOTRA

RDN 500
500 mm LR
WHEEL DIAMETER

= 1.2 Kg/ m3 TOTAL EFF. %

Pa N/m2

K 58 15
KW

TOTAL PRESSURE

3500 3000

67

74

77

73

64

52

11 8 6

2000

4 3 1000 2 1.5 1 .8 .6 95 100

2800 2500 2300 2100

500 400 300

1800 1600

90 1400 1200

85 200

1000 80
Lw (A) in dB (A)

900 800

100 80 .7 x1000 3 2 1 4 3 5 4 5 2 3 10 10 4 5 20 30 10 volume 40 50 40

18 m3/ s m3/h m/s

20 30 air outlet velocity

10

50

100 500 1000 Pa N/m2 velocity pressure


Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

RPM

Backward Blade Fan

NICOTRA

RDN 560
560 mm LR K2
WHEEL DIAMETER

= 1.2 Kg/ m3 TOTAL EFF. %

Pa N/m2

K 62 18.5
KW

TOTAL PRESSURE

3500 3000 15 10 8 6 4 1000 3 2 1.5 500 1 400 300 .6 .8

70

76

77

73

62

47

25

30

2000

2600 2300 100 2000 1800 95 1600 1400 90 1200

200 85 1000

850 100 80 1 x1000 2 5 3 4 2 3 10 5 4 5 20 10 30 10 40 20 volume 50 80


Lw (A) in dB (A)

700 25 m3/ s m3/h m/s

20 30 40 air outlet velocity 100 500 1000 velocity pressure

10

50

Pa N/m2

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

RPM

Backward Blade Fan

NICOTRA

RDN 630
630 mm LR K2
WHEEL DIAMETER

= 1.2 Kg/ m3 TOTAL EFF. %

Pa N/m2

K 58 25
KW

TOTAL PRESSURE

3500 3000

67

75

79

78

69

54

18.5 15

30

40

2000 10 8 6 2000 1000 3 2 500 400 .8 300 .6 200 85 1000 900 800 80
Lw (A) in dB (A)

2300

4 100 1800 1600 95 1400

1.5 1 90

1200

700 600

100 80 1 x1000 2 5 3 4 2 3 10 5 4 5 20 10 30 10 40 50 20 volume 30 100

m3/ s m3/h m/s

20 30 40 air outlet velocity 100 500 1000 velocity pressure

10

50

Pa N/m2

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

RPM

Backward Blade Fan

NICOTRA

RDN 710
710 mm LR K2
WHEEL DIAMETER

= 1.2 Kg/ m3 TOTAL EFF. %

Pa N/m2

K 69
KW

TOTAL PRESSURE

3500 3000 25 22

74

78

79

75

65

51

45 35

15 2000 10 8 6 1000 4 3 2 500 400 1 300 90 900 200 85 700 600 800 1.5 95 100 2000 105 1700 1500 1300 1200 1100 1000

Lw (A)

in dB (A)

100 80 1. 4 x1000 6 2 3 2 3 10 4 5 4 5 20 30 10 10 40 50 20 30 volume 100 40 m3/ s m3/h m/s

20 30 40 air outlet velocity 100 500 1000 velocity pressure

10

50

Pa N/m2

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

RPM

Backward Blade Fan

NICOTRA

RDN 800
800 mm K
WHEEL DIAMETER

= 1.2 Kg/ m3 TOTAL EFF. % 70 76 79 74 63 46

Pa N/m2

K2 62

TOTAL PRESSURE

3500 3000
KW

25 22 15

35

45

2000

10 8 1000 4 3 500 400 300 1.5 1 95 2 100 6 105 1600 1400 1300 1200 1100 1000 900 800 200 90 700

600 85
Lw (A) in dB (A)

100 80 1.6 x1000 6 2 3 10 3 4 5 4 5 20 30 10 40 50 10 20

500 30 40 50 m3/ s volume 100 m3/h m/s

20 30 40 air outlet velocity 100 500 1000 velocity pressure

10

50

Pa N/m2

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

RPM

Backward Blade Fan

NICOTRA

RDN 900
900 mm K
WHEEL DIAMETER

= 1.2 Kg/ m3 TOTAL EFF. % 69 76 79 75 78 70 57

Pa N/m2

K2 62 40
KW

TOTAL PRESSURE

3500 3000

30 2000 20 15 10 1000 6 4 3 500 400 1.5 300 1 200 85 2 8

50

60 1600 1500 105 1300 1200 100 1100 1000 95 900 800 90 700 600

80 100 80 2 x1000 2 3 10 3 4 4 5 20 5 30 10 40 50 10 20

Lw (A)

in dB (A)

30 100

40 volume

60 m3/ s 200 m3/h m/s

20 30 40 air outlet velocity 100 500 1000 velocity pressure

10

50

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

GIRI / m RPM
500 400 Pa N/m2

Backward Blade Fan

NICOTRA

RDN 1000
1000 mm K
Pa N/m2
WHEEL DIAMETER

= 1.2 Kg/ m3 TOTAL EFF. % 69 60 75 77 79 74 59 42

K2 58 50
KW

TOTAL PRESSURE

3500 3000

37 2000 25 20 15 10 8 6 4 500 400 2 300 95 3

1000

105 1050 100

200 90

85 100 80 2.4 x1000 10 2 3 4 5 20 4 30 5 10 40 50 10 20

Lw (A)

in dB (A)

30 100

40 50 volume 200

80 m3/ s m3/h m/s

20 30 40 air outlet velocity 100 500 1000 velocity pressure

10

50

Installation type: free inlet , ducted outlet Effects of appurtenances in airstream not included Power rating kw does not include drive Losses

GIRI / m RPM

1350 1200

900 800 700

600

500 450 400

Pa N/m2

DESCRIPTION
APPLICATIONS
The double inlet TA series centrifugal fans, forward curvedblade fanwheels, are naturally suited for ventilating and air conditioning systems, both civil and industrial applications , for heating and cooling units and warm air generators. This centrifugal fan series is projected for handling clean air. Discharge volumes up to 100.000 cu m/h. Static pressures up to 150 mm H2 O Temperatures up to 70 3TA/R: available up to size 18/18, single shaft with two lateral bearings. The performance of these fans, if compared to single fans, is approximately the following: Delivery : x3 Pressure : x1 RPM : x 1,08 Power : x 3,25 Max allowable fan RPM : x 0,7

CONSTRUCTION DETAILS
The fans of this series are produced with particular care and structurally very rugged. The SCROLLS are made of stamped steel plates. Casing sides, cut from a single plate, are electrically welded to the scroll. A deflector plate is fixed with self tapping screws to the diffuser. The DOUBLE SECTION FANWHEELS aer sheet construction with forward curved plates. Disks and rims are well oversized. Blades are beaded or riveted to disks and rims. Each fanwheel is carefully balanced, both statically and dinamically. SHAFT and BEARINGS are produced with particular care, as far as dimensions and quality are concerned. The supports of all ball bearings are prelubrified,as to guarantee, under normal working and environmental conditions, a troubleless and longlasting operation. The FRAMES of the TA/R series are constructed with steel bars, so as to form a frame cube and are electrically welded.

ACCESSORIES
a) BASE SUPPORTS in pre-drilled heavy duty steel plate, ready for mounting in any position around the ventilator scroll in the TA/S version. Supplied with fasteners and assembly hardware. b) MOTOR SUPPORT, to be mounted in a number of positions around the fan scroll in the TA/S version, with axial and tangential motor adjustments, and regulation of transmission tension. Supplied with necessary fasteners. c) FIXED PULLEYS IN ALUMINIUM for ventilator fan shaft mounting, one groove for section A,trapezoidal belts, in aluminium for 100 - 130 - 150 - 180 pitch diameters. d) VARIABLE PITCH PULLEYS IN ALUMINIUM for motor shaft mounting,one grove for section A and B, trapezoidal belts, as to allow for an about 30% fan RPM regulation, when motor is stopped. In aluminium for the following pitch diameters: from 60 to 75 mm, from 70 to 85 mm and from 92 to 113 for section "A" belts from 63 to 79 mm, from 73 to 95 mm and from 100 to 130 for section "B " belts N.B.: section " A " = 13x8 mm section " B " = 17x11 mm e) MOTOR MOUNTS for fan case mounted motors in the TA/R and 2 TA/R versions,with motor axial and tangential adjustments. Supplied with necessary fasteners. f) VIBRATION DAMPER, produced from a glass- neoprene material fastened two galvanized steel strips. Maximum operating temperature allowed is 95C. To be mounted when the fan has to be thouroughly insulated from ducts, as to avoid all interferences and subsequent noises and vibrations. g) DRIVE SAFETY GUARD CARTERS - The employment of safety carter guards to be mounted as beltdrive protection is recommended as to eliminate whatever risk of injuries to personnel. h) COMMON MOTOR AND FAN MOUNTING BASE. i) BASE VIBRATION DAMPERS to cut down transmission of vibrations between the fan and the supporting frame. Thus, the fan is completely insulated from its foundations.

FINISHES
Zinc plated finish: for high corrosion resistance. Special finish: series TA/R with aluminium scroll.

TYPES AVAILABLE
The following types of series TA centrifugal fans are produced and available: TA/S: includes 11 types, from 7/7 to 18/18, with discharge capacities of up to 18.000 cu m/h and static heads of up to 80 mm H2 O These models have been designed to meet maximum simplicity and economy requirements, without giving up precision or strength. TA/R: available in 20 sizes from 7/7 to 30/28 with discharge capacities of up to 60.000 cu m/ h, and static heads of up to 80 mm H2 O for 1stclass fans and 150 mm H2 O for 2nd class fans (see characteristic diagrams). The fans of this series are mounted in a frame,allowing for orientation in 4 directions. 2TA/R: available up to size 30/28, single shaft with two lateral bearings. Performance of these fans, in comparison to single fans is approximately the following: Delivery :x2 Pressure :x1 RPM : x 1,05 Power : x 2,15 Max allowable fan RPM : x 0,7

EXAMPLE
HOW TO USE THE DIAGRAMS a) Performance curves refer to double intake fans.
The following information is reported on the performance charts:

discharge volume in cu m/h - logarithmic scale discharge volume in cv m/sec - logarithmic scale static pressure in mm H2 O logarithmic scale velocity pressure in mm H2 O - logarithmic scale outlet velocity in m/sec. - logarithmic scale 1st and 2nd class boundary delivery -pressure curves delivery-pressure curves revolutions per minute RPM logarithmic scale brake horsepower curves noise level curves fan wheel diameter number of blades peripheral speed blade surface RPM speed limits for the two classes maximum installed power fan weight
Revolutions per minute

b) Sample of calculation. Assuming a double intake centrifugal fan has to be selected to meet the following requirements: volume (Q) : 3.400 cu m/h static head (p. st.) 35 mm H2O

Starting from point A, corresponding to the 3.400 cu m/h required, continue upwards vertically and cross at point X the horizontal line draw to B, in correspondence to a static head pressure of 35 mm H2O On the TA 10/10 diagram the following fan characteristics can be directly read off: revolutions per minute n = 1170 R.P.M. brake hors power P inst = 0,75 metric H.P. total efficency T = 0,65 discharge velocity VU = 10 m/s velocity pressure P din = 6 mm H2O noise level LA = 72 dBA

Brake horsepower-metric H.P. t = 0,64

Noise level dBA t = 0,67 t = 0,58

Hst [mm H2O] x 9,81 = [Pa]

150

Hst mm H2O

2a

Cl as se
2000 1800 1700 1600 1500 1400

2400

2200 100 90 80 70 60 50 90 40 30

1a

60 50 40 B

Cl as

100 90 80 70

se

Hd 7,5 5,5 X 3 2 4 85

1300 1200 1100

l1 Gi ri a

30

1000 900 1,5

w]

0,10 1.000
0,2 0,3 3 0,3 0,4 0,5

PO

4 3

65

TE

60

NZ

0,25

AS

70

SO

500

0,33

RB

ITA

600

0,5

5 4 3
Q m3/h

1.500 2.000
0,4 4 1 0,5 5 1,5 2 6 7 3

3.000A 4.000 5.000 6.000 8.000 10.000


15 15 10 15 20 2 20 30 8 4 9 10 5

0,6 0,7 0,8 0,9 1

3 Q m3/sec. 30 Vu. m/sec. 40 50


2

100

Hd [mm H O] x 9,81 = [Pa]

H [mm H2O] x 9,81 = [Pa]

10 9 8 7

[C

75

.V.

700

0,75

0,7

15

35

800

80

[K

20

20 15

10 9 8 7 Hd 6

TA 7-7
CHARACTERISTIC CURVES
Ptot = Pst + Pdin Data refer to standerd air at 15C, 760 mm Hg ( = 1.22 kg/cu m) Max. circulating air temperature: 70C

Hst [mm H2O] x 9,81 = [Pa]

t = 0,60

t = 0,65

150

Hst mm H2O
t = 0,58

100 90 80 70 60 50 40 30 2000 1900 1800 1700 1600 1500 1400 1300

2400 2200

40 30 Hd 0,75 0,5 0,33 0,25 75


SO [K

ri a l1

85
35

Gi

w]

20 15

1200 1100

20 15

800 700 0,1

6
NZ A

6 5 4 3

5 4 3
0,09 0,1 2 0,2

70
TE

400
0,15 3 0,3 0,4 0,5

600
0,2 4 1

800
5 1,5

60 55 0,05 1.000 1.500 2.000


0,3 6 2 7 3 8 4 0,4 9 10 5 10 0,5 0,6

3.000
0,7 0,8 0,9 1 15 15 20 20 30

4.000

Q m3/h Q m3/sec. Vu. m/sec.

40

Hd [mm H2O] x 9,81 = [Pa]


Fanwheel diameter Number of blades PD (kgxm )
2 2

200 mm 40 0.08 n x 0.0105 m/s 0.046 m2 I class 2.400 TA-S: TA-R: 1.5 1.5 II class

Ht

= Total pressure

Peripheral velocity Blade surface Max. allowable fan RPM Max. installed power (metric H.P.)

Hst = Statics pressure

Hd =Dynamics pressure

Ht
TA-S: TA-R: 5 kg 6 kg

= Hst + Hd = Total efficiency Revolutions per minute Brake horsepower - metric H.P. Noise level dBA

Fan net weight

H [mm H2O] x 9,81 = [Pa]

PO

AS

RB

10 9 8 7

ITA

[C

.V.

900

0,7

1000

80

10 9 8 7

TA 9-9
CHARACTERISTIC CURVES
Ptot = Pst + Pdin Data refer to standerd air at 15C, 760 mm Hg ( = 1.22 kg/cu m) Max. circulating air temperature: 70C

Hst [mm H2O] x 9,81 = [Pa]

t = 0,65 t = 0,68

Cla

150

sse
2600 2400 2200 2.000 1900 1800 1700 1600 1500 1400 1300

Hst mm H2O

Cla sse

100 90 80 70 60 50 40 30

2a

t = 0,58

70 60 Hd 4 90 3 30 2 1,5 1 0,75 0,5 0,33 0,25 70 75 80 85 50 40

1200

ri a l1

1100 1.000

1a

Gi

800 10 9 8 7 6 5 4 3 0,10 60 600


0,15 2 0,2 0,3 0,2 3 0,4 0,5

0,7

35

15

900

[K
15 10 9 8 7 6 5 4 3
Q m3/h 2 Q m3/sec. Vu. m/sec.

20

.V.

w]

20

1.000
0,3 4 1

1.500
0,4 5 1,5 2 6

2.000
0,5 7 3 0,6 8 4

3.000

4.000 5.000 6.000


1,5 15 10 15 20 20 30 40

0,7 0,8 0,9 1 9 10 5

PO

TE

65

NZ

500

Fanwheel diameter Number of blades PD (kgxm )


2 2

250 mm 33 0.12 n x 0.0131 m/s 0.078 m2 I class 2.000 I class TA-S: TA-R: 2TA-R: 3TA-R: 3 3 4 4 II class 2.400 II class 5.6 5.5 TA-R: 9kg 3TA-R: 48kg

Ht

= Total pressure

Peripheral velocity Blade surface Max. allowable fan RPM Max. installed power (metric H.P.)

Hst = Statics pressure

Hd =Dynamics pressure

Ht t

= Hst + Hd = Total efficiency Revolutions per minute Brake horsepower - metric H.P. Noise level dBA

Fan net weight

TA-S: 8kg 2TA-R: 30kg

AS

SO

Hd [mm H2O] x 9,81 = [Pa]

RB

600

ITA

[C

700

H [mm H2O] x 9,81 = [Pa]

TA 10-10
CHARACTERISTIC CURVES
Ptot = Pst + Pdin Data refer to standerd air at 15C, 760 mm Hg ( = 1.22 kg/cu m) Max. circulating air temperature: 70C

t = 0,64

t = 0,67 t = 0,58

Hst [mm H2O] x 9,81 = [Pa]

150

2a

Cl as

Hst mm H2O

se
2000 1800 1700 1600 1500 1400

2400

2200 100 90 80 70 60 50 90 40 30

60 50 40 30

1a

Cl as

100 90 80 70

se

Hd 7,5 5,5 4 3 85 2 1,5 80 1 0,75 0,5 0,33 0,25


X

1300 1200 1100

ri a l1 Gi

1000

w]

35

700 10 9 8 7 6 5 4 3
0,2

AS

70

SO

500

RB

ITA

600

6 5 4 3

0,10 1.000
0,3 3 0,3 0,4 0,5

1.500 2.000
0,4 4 1 0,5 5 1,5 2 0,6 6 7 3

3.000 4.000 5.000 6.000 8.000 10.000


0,7 0,8 0,9 1 8 4 9 10 5 10 15 15 15 20 20 30 2 3 30 40 50

PO

65

TE

60

Q m3/h Q m3/sec.

Vu. m/sec. 100

Hd [mm H2O] x 9,81 = [Pa]


Fanwheel diameter Number of blades PD (kgxm )
2 2

280 mm 39 0.16 n x 0.0146 m/s 0.0955 m2 I class 1.800 I class TA-S: TA-R: 2TA-R: 3TA-R: 3 3 4 4 II class 2.200 II class 5.5 5.5 TA-R: 11kg 3TA-R: 55kg

Ht

= Total pressure

Peripheral velocity Blade surface Max. allowable fan RPM Max. installed power (metric H.P.)

Hst = Statics pressure

Hd =Dynamics pressure

Ht t

= Hst + Hd = Total efficiency Revolutions per minute Brake horsepower - metric H.P. Noise level dBA

Fan net weight

TA-S: 9kg 2TA-R: 36kg

H [mm H2O] x 9,81 = [Pa]

NZ

[C

75

.V.

0,7

15

800

[K

20

900

20 15

10 9 8 7

TA 12-12
CHARACTERISTIC CURVES
Ptot = Pst + Pdin Data refer to standerd air at 15C, 760 mm Hg ( = 1.22 kg/cu m) Max. circulating air temperature: 70C

t = 0,62 Hst [mm H2O] x 9,81 = [Pa]

t = 0,68 t= 0,63

150

cl a ss e

100 90 80 70 60 50 40

1500 1400

2a

cl a ss e

Hst mm H2O

1900 1800 1700 1600

1300 1200 Hd 75 5,5 4 3 2 1,5 65 0,35 0,5 1 0,75 80 85

70 60 50 40 30

1a Gi ri a l1 ,
900 800

1100 1000

30

15 600 10 9 8 7 6 5 4 3

[K ]X 0, 7 35 =

700

w]

20

20 15

70

AS SO RB ITA

[C

75

5 4 3
Q m3/h

1.000
0,3 2 0,2 0,3

1.500
0,4 3 0,4 0,5

2.000
0,5 4 1 0,6 5 1,5

3.000
6 2 7 3

4.000 5.000 6.000 8.000 10.000


1,5 8 4 9 10 5 10 2 15 15 20 2,5 20 30 3

0,7 0,8 0,9 1

Q m3/sec. Vu. m/sec.

Hd [mm H2O] x 9.81 = [Pa]

Fanwheel diameter Number of blades PD (kgxm )


2 2

330 mm 45 0.4 n x 0.0173 m/s 0.135 m2 I class 1.500 I class TA-S: TA-R: 2TA-R: 3TA-R: TA-S: 2TA-R: 4 5.5 7.5 10 II class 1.800 II class 7.5 10

Ht

= Total pressure

Peripheral velocity Blade surface Max. allowable fan RPM Max. installed power (metric H.P.)

Hst = Statics pressure

Hd =Dynamics pressure

Ht t

= Hst + Hd = Total efficiency Revolutions per minute Brake horsepower - metric H.P. Noise level dBA

Fan net weight

16kg TA-R: 22kg 56kg 3TA-R: 96kg

H [mm H2O] x 9,81 = [Pa]

10 9 8 7 6

PO TE N

ZA

.V.

TA 15-15
CHARACTERISTIC CURVES
Ptot = Pst + Pdin Data refer to standerd air at 15C, 760 mm Hg ( = 1.22 kg/cu m) Max. circulating air temperature: 70C

Hst [mm H2O] x 9,81 = [Pa]

t = 0,64

t = 0,69 t = 0,64

150

Cl as

100 90 80 70 60 50

se

1700 1600 1500 1400 1300 Hd 15 10 7,5 5,5 4 3 2 1,5 1 60 0,35 0,5 65 0,75 70 80 85 90

2a

Cl as

Hst mm H2O

se

1200 1100

90 80 70 60 50 40 30

1a
ri a l1
900 800

1000

40 30

Gi
700

[K

w]

20 15 500 10 9 8 7 6 5 4 3

]X 0,7 35

600

20 15

ITA

75

[C

.V.

NZ

6 5 4 3
Q m3/h Q m3/sec. Vu. m/sec.

1.500
0,5

2.000
0,6 3

3.000
0,7 0,8 0,9 1 4 1 5 1,5

4.000 5.000 6.000 8.000 10.000


1,5 6 2 7 2,5 3 8 4 9 10 5 10 2 2,5 15 15 20 3

15.000 20.000
4 20 30 5 2,5 40 30 6

0,3 0,4 0,5

Hd [mm H2O] x 9,81 = [Pa]


Fanwheel diameter Number of blades PD (kgxm )
2 2

395 mm 51 0.9 n x 0.0206 m/s 0.190 m2 I class 1.300 I class TA-S: TA-R: 2TA-R: 3TA-R: TA-S: 2TA-R: 5.5 7.5 10 15 II class 1.700 II class 10 15

Ht

= Total pressure

Peripheral velocity Blade surface Max. allowable fan RPM Max. installed power (metric H.P.)

Hst = Statics pressure

Hd =Dynamics pressure

Ht t

= Hst + Hd = Total efficiency Revolutions per minute Brake horsepower - metric H.P. Noise level dBA

Fan net weight

22kg TA-R: 30kg 80kg 3TA-R: 139kg

H [mm H2O] x 9,81 = [Pa]

PO

TE

AS

10 9 8 7

SO

RB

TA 18-18
CHARACTERISTIC CURVES
Ptot = Pst + Pdin Data refer to standerd air at 15C, 760 mm Hg ( = 1.22 kg/cu m) Max. circulating air temperature: 70C

Hst [mm H2O] x 9,81 = [Pa]

t = 0,64

t = 0,69

t = 0,65

Cl as 2a

150

se
1300 1200

Hst mm H2O

Cl as

100 90 80 70 60 50

1100

se

1000 900

1a

Hd 25 20 15 10 7,5 5,5 4 3 80 0,75 1,5 75 1 90

100 90 80 70 60 50 40

800 700

Gi

600

20 15

]X 0,7 35

85

[K

w]

30

ri a l1

40

30

500

20 15

PO

TE

NZ

AS

70

5 4 3

5 4 3
Q m3/h

3.000
0,9 1

4.000 5.000 6.000 8.000 10.000


1,5 4 1 5 1,5 2 6 7 3 2 8 4 2,5 3 9 10 5 6 7 8 9 10

15.000
4 15 15 20 5

20.000
6 20 30 7 25

30.000 40.000
8 30 9 10 40 100

Q m3/sec. Vu. m/sec.

40 50

Hd [mm H2O] x 9,81 = [Pa]


Fanwheel diameter Number of blades PD (kgxm )
2 2

470 mm 53 2.3 n x 0.0246 m/s 0.267 m2 I class 1.000 I class TA-S: TA-R: 2TA-R: 3TA-R: 5.5 7.5 15 20 II class 1.300 II class 10 25

Ht

= Total pressure

Peripheral velocity Blade surface Max. allowable fan RPM Max. installed power (metric H.P.)

Hst = Statics pressure

Hd =Dynamics pressure

Ht t

= Hst + Hd = Total efficiency Revolutions per minute Brake horsepower - metric H.P. Noise level dBA

Fan net weight

TA-S: 38kg TA-R: 53kg 2TA-R: 126kg 3TA-R: 200kg

H [mm H2O] x 9,81 = [Pa]

10 9 8 7 6

RB

65

ITA

400

[C

.V.

10 9 8 7 6

SO

TA 20-20
CHARACTERISTIC CURVES
Ptot = Pst + Pdin Data refer to standerd air at 15C, 760 mm Hg ( = 1.22 kg/cu m) Max. circulating air temperature: 70C

Hst [mm H2O] x 9,81 = [Pa]

Cl as

2a

150

Hst mm H2O

se

200

t = 0,68 t = 0,69 t = 0,64

1300

1200 1100

100 90 80 70 60 50 40

se

1000 900 Hd

80 70 60 50

1a
700 600

Cl as

800 25 20 15 10 7,5

40 95 30

ri a l1 Gi

30

500

[K w]

20 15 400 4 10 9 8 7 6 5 4 3 300 65 2 1,5 70 1 0,75 75 3

90

20 15

AS SO RB ITA [C .V. ]

85

0,7 35

5,5

80

5 4 3
Q m3/h Q m3/sec. 30 Vu. m/sec.

3.000 4.000
0,9 1 2 0,3 0,4 0,5 3

6.000
1,5 4 1

8.000 10.000
2 5 2,5 6 7 3 8 4 9 5

15.000 20.000
4 10 10 5 6 15 15 7

30.000 40.000
8 20 20 25 30 9 10 25

1,5 2 2,5 3

40 50 60

Hd [mm H2O] x 9,81= [Pa]


Fanwheel diameter Number of blades PD (kgxm )
2 2

512 mm 42 4.3 n x 0.0268 m/s 0.397 m2 I class 1.000 I class TA-R: 2TA-R: 15 20 II class 1.200 II class 20 25

Ht

= Total pressure

Peripheral velocity Blade surface Max. allowable fan RPM Max. installed power (metric H.P.)

Hst = Statics pressure

Hd =Dynamics pressure

Ht t

= Hst + Hd = Total efficiency Revolutions per minute Brake horsepower - metric H.P. Noise level dBA

Fan net weight

TA-R: 98kg 2TA-R: 200kg

H [mm H2O] x 9,81 = [Pa]

10 9 8 7 6

PO TE NZ A

TA 22-22
CHARACTERISTIC CURVES
Ptot = Pst + Pdin Data refer to standerd air at 15C, 760 mm Hg ( = 1.22 kg/cu m) Max. circulating air temperature: 70C

t = 0,68

t = 0,68

t = 0,63

Hst [mm H2O] x 9,81 = [Pa]

Cl as 2a se
900 800 700

150

Hst mm H2O

1a

100 90 80 70 60 50 40

1000

se
1200 1100

Cl as

70 Hd 40 30 25 20 95 15 60 50 40 30

600

30

Gi ri a

l1
500 10 400 7,5 5,5 300 3 2 200 1 65 6.000 8.000 10.000
1,5 3 0,4 0,5 4 1 2 2,5 5 1,5 2 6 3 7 3 8 4

20 15

[K w] =
X

90

20 15

AS SO RB ITA [C .V. ]

4 80

85

0,7 35

1,5

PO TE NZ A

75

5 4

5 4 3

0,75

70

3 4.000

15.000 20.000
4 5 9 10 5 10 6 7

30.000 40.000
8 9 10 20 20 30 25 15 15

60.000
15 30

Q m3/h

Q m3/sec. Vu. m/sec.

40 50 Hd [mm H2O] x 9,81= [Pa]

Fanwheel diameter Number of blades PD (kgxm )


2 2

575 mm 48 5.8 n x 0.03 m/s 0.480 m2 I class 900 I class TA-R: 2TA-R: 15 20 II class 1.100 II class 20 30

Ht

= Total pressure

Peripheral velocity Blade surface Max. allowable fan RPM Max. installed power (metric H.P.)

Hst = Statics pressure

Hd =Dynamics pressure

Ht t

= Hst + Hd = Total efficiency Revolutions per minute Brake horsepower - metric H.P. Noise level dBA

Fan net weight

TA-R: 2TA-R:

104kg 225kg

H [mm H2O] x 9,81 = [Pa]

10 9 8 7 6

10 9 8 7 6

TA 25-25
CHARACTERISTIC CURVES
Ptot = Pst + Pdin Data refer to standerd air at 15C, 760 mm Hg ( = 1.22 kg/cu m) Max. circulating air temperature: 70C

t = 0,67 t = 0,69

Hst [mm H2O] x 9,81 = [Pa]

Cl as

se

150

Hst mm H2O 1000 900

t = 0,62

Cl as

100 90 80 70 60 50 40 30

2a

800

se

700 600 30 25 20 15 90 10 7,5 5,5 4 3 80 85 Hd 40 95

80 70 60 50 40 30

1a
500

Gi ri a

l1
20 15 300 10 9 8 7 6 5 4 3 4.000
2 0,2 0,3 0,4 0,5

400

0,7 35 =

[K w]
X

20 15

AS SO RB ITA [C .V. ]

200 65 1

2 75

6 5 4 3
Q m3/h Q m3/sec. Vu. m/sec.

70

6.000
1,5 3

8.000 10.000
2 2,5 4 1 3 5 1,5 2

15.000 20.000
4 6 7 3 5 8 4 6 9 10 5 7

30.000 40.000 50.000


8 9 10 15 10 15 20 20 25 30 15 25 40

Hd[mm H2O] x 9,81= [Pa]


Fanwheel diameter Number of blades PD (kgxm )
2 2

665 mm 54 9.8 n x 0.0347 m/s 0.630 m2 I class 800 I class TA-R: 2TA-R: 15 25 II class 1.000 II class 25 40

Ht

= Total pressure

Peripheral velocity Blade surface Max. allowable fan RPM Max. installed power (metric H.P.)

Hst = Statics pressure

Hd =Dynamics pressure

Ht t

= Hst + Hd = Total efficiency Revolutions per minute Brake horsepower - metric H.P. Noise level dBA

Fan net weight

TA-R: 2TA-R:

145kg 295kg

H [mm H2O] x 9,81 = [Pa]

10 9 8 7

PO TE NZ A

TA 28-28
CHARACTERISTIC CURVES
Ptot = Pst + Pdin Data refer to standerd air at 15C, 760 mm Hg ( = 1.22 kg/cu m) Max. circulating air temperature: 70C

t = 0,69 t = 0,67

Hst [mm H2O] x 9,81 = [Pa]

150

2a
100 90 80 70 60 50 40 30

Cl as
800

Hst mm H2O

se

700 600

se

1a

Cl as

t = 0,62

550 500 450

60 Hd 50 40 30 90 25 30 20 15 85 10 20 15

Gi ri a

l1
350 300

400

20 15 250 10 9 8 7 6 5 5
1,5 2 0,3

5,5 4

PO [C TEN .V. ] ZA A X 0,7 SS 35 OR = BIT [K w] A

7,5

80

200

65 2 70

75

10 9 8 7 6 5

7
2 2,5

8
3

9 10
2,5 3 4 1 5 1,5

15
4 6 2 5

20
6 7 3 8 4 9 5 7 10

30
8 9 10

40
15 15

50
15 20 20

60

Q m3/h x 1000 20 Q m3/sec. 25 Vu. m/sec.

0,4 0,5

6 7 8 9 10

30

40

Hd[mm H2O] x 9,81= [Pa]


Fanwheel diameter Number of blades PD (kgxm )
2 2

720 mm 60 13 n x 0.0375 m/s 0.757 m2 I class 700 I class TA-R: 2TA-R: 20 30 II class 800 II class 30 40

Ht

= Total pressure

Peripheral velocity Blade surface Max. allowable fan RPM Max. installed power (metric H.P.)

Hst = Statics pressure

Hd =Dynamics pressure

Ht t

= Hst + Hd = Total efficiency Revolutions per minute Brake horsepower - metric H.P. Noise level dBA

Fan net weight

TA-R: 2TA-R:

175kg 340kg

H [mm H2O] x 9,81 = [Pa]

TA 30-28
CHARACTERISTIC CURVES
Ptot = Pst + Pdin Data refer to standerd air at 15C, 760 mm Hg ( = 1.22 kg/cu m) Max. circulating air temperature: 70C

t =0,67
Hst [mm H2O] x 9.81 = [Pa] 150
la ss e

t =0,69

t =0,61

Hst mm H2O
2aC

1aC

100 90 80 70 60 50 40 30

800 750 700

650 600 550

la ss

Hd

500 40 30 25 20 15 90 95

100 90 80 70 60 50 40 30

450 400 350

ri a l1

[K

w]

Gi

300 10 7,5 5,5 4 3 75 80 85

,73

5=

20 15

20 15

[C .

V.]

250

x0

TE NZ A

5 4 3

4 3 8.000 10.000
2 2,5 3 0,4 0,5 3 4 1

1 65 15.000 20.000
4 5 1,5 2 6 5 7 3 6 8 4 7 9 5

70

30.000 40.000
8 10 6 7 8 9 10 9 10 15 15

60.000 80.000 100.000


15 20 20 30 20 25 25 30

Q m3/h

30 Q m3/sec. Vu. m/sec.

40 50 Hd [mm H2O] x 9.81 = [Pa]

Fanwheel diameter Number of blades PD (kgxm )


2 2

780 mm 66 18 n x 0.0407 m/s 0.813 m2 I class 600 I class TA-R: 2TA-R: 20 30 II class 800 II class 30 40

Ht

= Total pressure

Peripheral velocity Blade surface Max. allowable fan RPM Max. installed power (metric H.P.)

Hst = Statics pressure

Hd =Dynamics pressure

Ht t

= Hst + Hd = Total efficiency Revolutions per minute Brake horsepower - metric H.P. Noise level dBA

Fan net weight

TA-R: 2TA-R:

215kg 395kg

H [mm H2O] x 9.81 = [Pa]

10 9 200 8 7 6 150 5

10 9 8 7 6

PO

AS

SO RB

ITA

AIR HANDLING UNIT - Sections dimensions and Weight

Fresh air intake with louver Mixing and damper box

Mixing and exhaust box

Panel filter

Bag filter

Coil

Electric heater

Droplet eliminator and humidifier

L1

L2

L3

L4

L5

L6

L7

L8

L9

Width Hight Unit Size CS - 14 CS - 17 CS - 21 CS - 26 CS - 32 CS - 40 CS - 49 CS - 60 CS - 73 CS - 90 CS - 110 CS - 135 CS - 165 CS - 200 CS - 250 CS - 300 CS - 370 CS - 450 CS - 550 CS - 680 CS - 830
B C

L1
Length Weight

L2
Length Weight

L3
Length

L4
Weight

L5
1:4R
Length Weight Length

L6
5:6R 7:8R
Weight Length

L7
28 31 38 44 53 64 75 85 550 550 550 550 550 550 550 34 39 46 54 64 80 90 300 300 300 300 300 300 300

Weight Length

Weight Length Weight Length Weight

720 720 800 800 900 1000 1120 1280 1280 1400 1520 1600 1700 1960 2240 2400 2600 3340 3550 4020 4380

x x x x x x x x x x x x x x x x x x x x x

550 610 800 800 850 850 850 1060 1120 1240 1420 1480 1480 1600 1660 1840 2020 1940 2180 2300 2540

100 100 100 100 100 100 100 100 150 150 150 150 150 150 500 500 500 700 700 700 700

24 27 30 33 40 44 48 58 62 70 78 92 110 150 190 230 270 310 360 420 500

350 350 350 350 350 350 350 350 350 350 350 350 350 350 450 550 650 650 650 650 650

28 31 38 40 50 55 61 70 75 90

750 750 750 950 950 950 1050

50 54 62 67 80 89 98

240 240 240 240 240 240 240 240 250 250 250 250 250 250 250 250 250 270 270 270

7 9 10 12 13 15 17 20 22 25 28 32 36 42 49 58 70 82 95 110 130

650 650 650 650 650 650 650 650 650 650 650 650 650 650 650 650 650 650 650 650 650

22 29 33 39 43 49 55 65 71 80 89 100 112 135 160 180 220 260 300 345 410

350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350

23 26 31 37 46 53 61 70 81 88 98 110 132 153 200 215 250 274 332 423 520

450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450

1050 110 1050 120 1250 150

550 105 300 550 125 300 550 140 300 550 155 300 550 177 300 550 200 300 550 240 300 550 270 300 550 320 300 550 400 300 550 450 300 550 560 300 550 675 300 550 800 300

100 110 125 137 165 192 230 265 320 350 425 540 670

105 1250 180 125 1450 210 145 1450 240 160 1650 270 185 1650 400 275 1850 435 350 2000 525 410 2300 640 500 2300 750 630 2300 900

780 2900 1080 270

2 kw = kg

Absolute filter Fan

Multizone

Sound Supply attenuator air plenum

L101

L102

L11

L12

B1

L13

L14

L8
50 %
Length Weight Length Weight

75 %
Length Weight

L9

92 %
Length Weight

L 10 1
Length Weight

L 10 2
Length Weight

L 11
Length Weight

L 12
Length

B1
Hight Weight

L 13
170 200 225 250 300 330 365 400 445 485 530 595 680 790 935 1075
Length as required

L 14
Length Weight

200 200 200 200 200 200 200 200 200 200 200 200 200 200

18 20 22 25 28 32 37 44 51 57 62 70 78 95

800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800

51 58 63 70 80 92

1250 110 1650 135 1250 122 1650 150 1250 135 1650 162 1250 150 1650 177 1250 170 1650 200 1250 185 1650 220

800 900 900 900 1000 1100 1100 1100 1250 1250 1400 1400 1600 1750 1900 2050 2150 2200 1850 2050 2150

47 52 56 60 70 80 97 110 122 160 205 237 318 395 440 540 660 800 910 1100 1300

800 900 900 900 1000 1150 1150 1150 1300 1300 1500 1500 1700 1850 2150 2350 2400 2400 2000 2150 2400

47 52 56 60 70 80 97 110 122 160 205 237 318 395 440 540 660 800 910 1100 1300

1050 1050 1050 1050 1050 1150 1150 1150 1150 1200 1200 1200 1300 1300 1300 1500 1500 1600 1600 1600 1600

75 80 85 100 110 130 135 180 180 200 240 250 270 310 320 400 450 510 550 625 760

1000 1000 1100 1100 1200 1200 1350 1350 1500 1500 1650 1650 1900 1900 2200 2350 2500 2700 2900 3100 3300

800 900 900 1100 1100 1200 1200 1200 1400 1500 1600 1800 1900 2000 2000 2200 2600 2400 2600 2700 3000

700 700 700 700 700 900 900 900 900 900 900 900 900 900 900 1200 1200 1200 1200 1200 1200

35 40 45 48 50 65 70 80 80 95 110 120 120 130 135 180 200 220 230 290 310

116 1250 225 1650 265 120 1250 250 1650 290 135 1250 280 1650 315 145 1250 295 1650 350 157 1250 325 1650 390 178 1250 370 1650 435 208 1250 425 1650 485 235 1250 480 1650 540 280 1250 600 1650 700 320 1250 750 1650 850 380 1250 820 1650 960 440 1250 950 1650 1100 520 1250 1100 1650 1250 610 1250 1450 1650 1450 700 1250 1700 1650 1700

200 110 200 130 200 152 200 170 200 210 200 260 200 300

AIR HANDLING UNIT Installation, Operation & Maintenance Instructions


Installation of Air Handling Unit:
Units do not present particular difficulties of installation and we believe that the following information is sufficient. Positioning Client base/foundations must be even and leveled to avoid tension on the panels and frames when coupling sections together . Normally it is not necessary to use vibration isolators exterior to the unit. However, if a particular problem arises, we recommend client consults an anti-vibration specialist . In this instance, it is necessary to provide all water pipe connections with proper flexible joints and to use flexible connections on air inlets and outlets. It is important to ensure that the position for the (AHU) permits easy service and sufficient room for component replacement . Air duct connections It is important to ensure that any flexible joint can operate effectively after connecting the unit to the ductwork. Coil water connections Coil must be connected with the heating or cooling water flowing counter to the treated air . The water inlet is to be piped up to the bottom connection and the water outlet to the top connection. The other two outlets must be closed as shown in figure. The transmission of vibrations through the water system should be avoided as it causes work hardening of the copper pipe and subsequent failure. Drain pipe work should be trapped/siphoned . In humidification system with a pump, check: Pump rotation direction Water level in the pan Water filters position Pan tightness which could have suffered during transportation Check humidification operation and water tightness of the whole unit when running. The electric supply to fan motor must be in accordance with local regulations. During fan starting, it is necessary to check : That the fan rotates freely in the correct direction and the locking devices which were fitted as protection during transportation have been removed . The whole fan section, for any damage which may have occurred during transportation and which could cause unnecessary vibration or unit failure. Do not keep the inspection door open when fan is in operation, as this will cause motor overload. Measure the power absorbed by the motor which should normally be designed for approximately 80% of the motor rating . Assembly of absolute filters and active carbon cells It is advisable to assemble the filter cells after the (AHU) has been running for several hours. By doing this, the ducts are clean from dust and debris accumulated during installation. Only after several hours of operation, should absolute or active carbon filter cells be installed.

AIR FLOW

As for the steam and direct expansion coils, the instructions on the data plates are to be followed. An air vent should be installed in the pipework to each water coil . When tightening coil connections, ensure that the coil pipe is held rigid, thus avoiding damage to header .

Handling for transportation 1) Units which are provided with support feet : Unit handling can be effected by fork lift truck or ropes as shown in figure

Maintenance Instructions
Normal Maintenance

1 Mixing Box Air Dampers: It is recommended 2 3

2) Units which are provided with a profile base in which there are holes for hooks to take tubes or lifting ropes are handled as shown in figure .

5 6

that the drive levers are cleaned and greased annually. Air filters: To be checked and replaced periodically according to the dust content of the air . Metal Filter Cell: To be cleaned with hot water and cleansing agents, or with a caustic soda bath. It will be necessary to spray the cells with mineral oil to ensure efficient operation . Washable Synthetic Material Cells: These filter cells may be cleaned as follows: - By simple shaking - By vacuum cleaner, in this case it is more effective if the suction device is positioned on the air inlet side. - By water spray, (avoiding strong pressure jets) and spraying from the air inlet side. - By water spray, (avoiding strong pressure jets) and spraying from the air inlet side. Auto Roll and Bag Filters: Follow specific factory maintenance instructions Absolute Filters: Check cells are correctly assembled on frame and airtight. The cells are not washable. Follow factory service instructions. Air treatment Coils: It is advisable to purge the pipe of air occasionally. To avoid fouling, it is advisable to clean each coil with water jets at the beginning of summer and winter seasons. If this proves insufficient we suggest the use of a brush or a proprietary brand of chemical agent to be applied as instructed . Humidification Section: With pump and spray header we recommend every month : - To clean the nozzles and check that the spray forms a regular cone . - To clean the copper/stainless steel mesh water filter with a brush . - To clean the pan from slimy impurities using water jet and brush every six months . Evaporating package when cleaning, the following instructions apply : - Stop the pump, shut the check valve and wait for the air flow to dry the evaporating package. - To remove slimy deposits wash down the package with water. - Take off and clean the water filter with a common brush. - Wash the pan and overflow pipe.

AIR HANDLING UNIT Installation, Operation & Maintenance Instructions


9 Fan section: Warning: Before opening the fan motor assembly make sure that the main power switch has been isolated Check belt drive tension after the first week of operation and adjust if necessary as follows : - Loosen the electric motor from the main base. - Move the motor until the belt tension can be seen to give about 2 cm deflection between the two pulleys . Excessive tension of the belts causes damage to the bearings. - Check that the fan and motor shafts are parallel and the pulleys are correctly aligned. - Fans provided with open bearing housing need to be lubricated periodically. - Check that all fixing screws are correctly tight after first week of operations, retighten if necessary and to be checked periodically each month . 10 Motor - Ambient temperature, changing with seasons but not exceeding 40 degrees centigrade. - Voltage, 220/380 V, 380/660 V - Check if the data on the name-plate the requirements. - Motor should be earthed properly. There is an earthing device at the low right part of the terminal box - There are 6 terminals on the terminal plate marked with : U1, V1, W1, U2, V2, W2 respectively. Connection should be done according to the diagram on the name-plate . When power phase sequences A, B, C are corresponding to mounting marks of U1, V1, W1 respectively, looking from the end of the main shaft, the rotating of motor is regarded as clockwise. If changing the phase sequence, the rotation of the motor is counter to its original one. Check motor rotation before test-run. - Abnormal sound or vibration should not occur during operation. The temperature of bearings should not exceed 95 degrees centigrade. 11 Various checks Check for air leaks from panels and inspection doors. Check the condition of the electric cables. 12 Safety provisions All the units are provided with the following safety devices: Fan access door with locking handles. Upon request belt guard for fan/motor drive protection.

A.H.U ORDER FORM


CUSTOMER MODEL CS FINISH External Internal INSULATION Double skin Uninsulated single skin SUPPLY FAN Capacity (mt3/hr) Air Orientation RETURN FAN Capacity (mt3/hr) Inspection Door A B C D E F Insulated single skin

Sheet QU. No. QTY. UNIT No. Galvanized Galvanized

of

Plastified Plastified

Thickness (mm) Internal Static Pressure (Pa) External Static Pressure (Pa) Inspection Door Internal Static Pressure (Pa) External Static Pressure (Pa) Direct Expansion Header Side Leaving Temp. (DB) (F/C) Leav. Relative Humidity (%) R L R L

COOLING COIL SECTION Chilled Water Load (B.T.U/KW)

Air Side
Entering Temp. (DB) (F/C) Ent. Relative Humidity (%) Air pressure Drop (in. wg./Pa)

Water Side
Water Flow (GPM - L/S) Entering W. Temp. (F/C)

W. Press. Drop (in. wg./Pa) Leaving W. Temp. (F/C)

Refrigerant side
Suction Temp. (F/C) HEATING SECTION Hot Water Steam Electric Heater Header side Leav. Air Temp. (DB) (F/C) Leaving W. Temp. Header side Leav. Air Temp. (DB) (F/C) No. of steps No. of phase Relative Humidity Bag Filter Efficiency (%) Absolute Filter Efficiency (%) R L R L

Hot Water Coil


Load (B.T.U./K.Cal.) Entering Air Temp. (DB) (F/C) Water Flow (GPM - L/S) Entering W. Temp. (F/C)

Steam
Load (B.T.U./K.Cal.) Entering Air Temp. (DB) (F/C)

Electric Heater
Capacity (KW) Voltage (volt) HUMIDIFICATION SECTION Water (Lit./hr) FILTER SECTION Pre-Filter efficiency (%) SOUND ATTENUATORS SECTION Supply S.A. Insertion Loss (db) at 250 Hz Return S.A. Insertion, Loss (db) at 250 Hz ADDITIONAL SECTIONS Max Pressure Drop (Pa) Max Pressure Drop (Pa)

Input by :

Date

Signature