Ladder Diagram
for Festo Controllers
Toolbar
Menubar
Contents
Search
Page
Toolbar
Menubar
Contents
Search
Page
Copyright by Festo KG, 73734 Esslingen, Germany, 1991 All rights, including translation rights, reserved. No part of this document may be reproduced in any form (printing, photocopy, microfilm or any other process) without the prior written permission of Festo KG. 2
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Preface This book is intended as an aid to anyone who has to program programmable logic controllers from Festo. It is not intended as a textbook but as a reference work and an aid to solving problems associated with control technology. All operations and operands that can be used with a Festo PLC are explained and - in most cases - illustrated with examples. You know the sort of question that sometimes occurs when working on a project. "How do you carry out an exclusive OR operation in Ladder diagram?" This is where this book provides help: simply refer to the section "Exclusive Or" and youll find a program example. Its as simple as that. Have you found any errors? Have you found any particular question unanswered? Certainly there will be room for improvement. Help us to improve this book by sending a postcard with a description of the missing solution, the error or with any other comments to: Festo KG Ruiter Str. 82 D-73734 Esslingen Germany Many thanks! 3
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Menu
Search
Page
Contents Chapter 1 Fundamental characteristics of FST software.................................................. 7 1.1 Notes ...................................................... 9 1.2 Structure of FST Software................... 10 1.3 Programming languages ...................... 11 Entering a program..................................... 13 Operands ...................................................... 19 3.1 Notes .................................................... 21 3.2 Bit and word operands ......................... 23 3.3 Bit operands ......................................... 24 3.4 Word operands .................................... 26 3.5 Retentive operands.............................. 29 Structure of a Ladder diagram program . 31 4.1 Notes .................................................... 33 4.2 What is a rung comprised of? ............. 34 4.3 Conditional and executive part ............ 37 4.4 How is a rung processed?................... 38 4.5 How fast is a controller? ...................... 46 Operations - an overview .......................... 47 The operations in detail Examples for reference.............................. 59 Addressing operands ..............................143 7.1 Absolute and symbolic addresses.....145 7.2 Information content of absolute addresses............................153 4
Toolbar Menubar Print Menu Search Page
Chapter 2 Chapter 3
Chapter 4
Toolbar
Menubar
Menu
Search
Page
Chapter 8
Programming timers .................................159 8.1 General ...............................................161 8.2 Timer types.........................................165 8.3 Examples ............................................169 8.4 Evalutation of the individual timer elements ....................................178 Programming counters ............................181 9.1 What is an incremental counter? ......184 9.2 Elements of the counter.....................186 9.3 Programming counters.......................191 Using registers..........................................197 Using flags .................................................201 11.1 Flag bit.................................................203 11.2 Flag word ............................................207 Example programs ....................................209 A.1 Sequence programs...........................211 A.2 Measuring the cycle time ...................220 A.3 Structured programming in Ladder diagram ..................................233 Differences in program execution.........239 B.1 Process image ...................................241 B.2 Multitasking .........................................244 B.3 Multiprocessing ..................................246 B.4 Interrupt capability ..............................247 B.5 Internal inputs and flags .....................248 B.6 Serial data port ...................................251 B.7 Behaviour after battery failure...........253 B.8 Input signal delay ................................255 5
Chapter 9
Chapter 10 Chapter 11
Appendix A
Appendix B
Toolbar
Menubar
Menu
Search
Page
Toolbar
Menubar
Menu
Search
Page
Appendix C
Subroutines, Multitasking and Multiprocessing ........................................257 C.1 Modules ..............................................265 C.2 Multitasking .........................................267 C.3 Multiprocessing ..................................272 The binary and hexadecimal number system ..........................................277 D.1 The structure of number systems .....279 D.2 The binary number system ................282 D.3 Differentiation in Ladder diagram......289 ......................................................................291
Appendix D
Index
6
Toolbar Menubar Print Menu Search Page
Toolbar
Menubar
Contents
Search
Page
7
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Contents 1.1 1.2 1.3 NOTES ................................................... 9 STRUCTURE OF FST SOFTWARE. 10 PROGRAMMING LANGUAGES....... 11
8
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
1.1
NOTES In FST software every self-contained PLC system is called a project. Each project can contain one or more programs, modules and program and module versions. Each project has an allocation list that can contain several (internal and external) parts. Each program or module version has its own error list, which records all errors found by the system. Within a project individual programs and modules can be processed together (crossreference list, load, print). Programs or modules can be imported from other projects. Documentation on a project can be created with a comment header and operating instruction.
9
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
1.2
STRUCTURE OF THE FST SOFTWARE You want to program an automatic assembly machine for pneumatic valves. A rotary indexing table offers 8 automatic work stations and a manual work station. The valve is fully assembled on this rotary indexing table. It is then placed on a conveyor belt which transports the valve to an automatic testing machine and to a packing machine. A programmable logic controller is used for the automatic assembly machine. The entire program for this controller is a project. Each automatic work station and the rotary indexing table are individual programs or modules within this project. The arrangement will depend on the programming method used by the programmer. Sensors and actuators are mounted on the automatic assembly machine. These are connected to the inputs and outputs of the PLC the operands of the PLC. In addition there are internal operands such as flags, timers, counters, registers, programs and modules. A project may not only contain several programs or modules but also - when using the FPC 405 - several processor modules. All of these processor modules access the inputs and outputs. Each processor module can again execute several programs or modules but only within one project.
10
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Documentation is prepared for the entire project. The documentation comprises Cover sheet with the name of the project Text to describe in the project and the individual processor modules, programs, modules, etc., possibly with notes on operation, spare parts, etc. Allocation list with all operands Printout of all programs and modules with comment lines Cross-reference list showing which operand is used at which point in which program or module. 1.3 PROGRAMMING LANGUAGES The FST software comprises a range of programming languages for programming the various PLCs. These include Ladder diagram Statement list BASIC Assembler Matrix programming This book deals only with ladder diagram programming, which is available with all Festo PLCs (FPC 100, FPC 405, IPC, FEC). 11
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Notes
12
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
2. Entering a program
13
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
2. Entering a program
14
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
2. Entering a program
When creating a Ladder diagram program with FST software, we recommend the following procedure: Plan the program as a function chart, sequence diagram, text, structure chart or similar. Call up FST software Create project: The project name must meet the requirements of the MS-DOS operating system, as a subdirectory is created on your mass storage medium (normally the hard disk) for the project. This means that the project name can be up to 8 characters, and must not contain spaces or periods. For MSDOS version 3.0 or later, a subdirectory may also contain special characters such as the German Umlaut (, , etc.). This does not apply to DOS versions prior to 3.0. Enter text for Title page and page header: This makes your printout easier to read. Create an allocation list for inputs and outputs: It makes sense to create the allocation list for inputs and outputs before entering the program and then to print it out immediately. Then it is not necessary to write down inputs and outputs.
15
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
2. Entering a program
Entering the Ladder diagram program: When creating the program you are prompted for some or all of the following entries, depending on the controller type: Central control unit Allows the entry of the processor module number for projects involving several processors (FPC 405). Important: If only one CCU is used, no. 0 must be used. Default value: No. 0 Type program/module Allows you to indicate whether you want to create a program or a module. Important: At least one program must be entered. Default value: Program Prog./module no. Allows entry of the number for the program or module. Important: A program number 0 must always exist, otherwise your processor module cannot start execution. Default value: 0
16
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
2. Entering a program
Version number Allows you to create up to 9 different versions of a program or module. Important: You can only load one version of a program or module into a processor module. Default value: 1 Task Here you can enter a commentary which will help you to relocate this particular program, version or module. This commentary does not appear on any printout and is only intended as a programming aid. You want to start a completely new program? Simple. Leave everything as it is and press the <F1> key for "Create". The default values are such that you can load a controller with a single program and execute it.
17
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
2. Entering a program
Enter program: The Ladder diagram editor for FST software is controlled by means of the function keys and/or mouse (version 3.1 or later). You only use the keyboard of your PC for entering the names of operands. All operations (with the exception of entries in the boxes) are called with the aid of function keys or the mouse. Function key <F9> is the help key. It opens a help window where ever you are in the FST software. Function key <F10> toggles the function key allocation. Save program: Using function key "File menu" (normally <F8>). Test the syntax after program. If necessary, view or print the error list and correct the errors. Print out the program. Load the program into the controller. Test the program with the aid of the online function and with the aid of the status display (version 3.1 or later). Create Documentation.
18
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
3. Operands
Chapter 3 Operands
19
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
3. Operands
Contents 3.1 3.2 3.3 3.4 3.5 NOTES ................................................. 21 BIT AND WORD OPERANDS........... 23 BIT OPERANDS.................................. 25 WORD OPERANDS............................ 27 RETENTIVE OPERANDS .................. 30
20
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
3. Operands
3.1
NOTES The FST software allows the use of bit operands and word operands (no byte and no double/longword operands). The FST software allows the use of absolute and symbolic operand addresses. Only absolute addresses are used in the following. For details on symbolic addresses see Chapter 7, "Addressing the operands". The number of operands of an individual type that can be used depends on the type of Festo PLC.
21
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
3. Operands
F3 . 4 . 12
Number of bit Point separating bit and word Number of word Point separating processor module and word (not for FPC100B/AF, IPC and FEC) Number of CCU (not for FPC100B/AF, IPC and FEC) Operand identifier (here F for flag)
Fig. 3/1: Construction of an absolute operand address The operand address must never contain space characters!
22
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
3. Operands
3.2
BIT AND WORD OPERANDS All Festo PLCs have a word-oriented internal organization. This means that all operands are organized and can be used as words (with the exception of the initialization flag FI, the onebit operands T for Timer and C for Counter and the operands P1 for Program and CMP/CFM for modules). Every word is 16 bits long and can be used for an unsigned decimal number (0 to 65,535), as a signed decimal number (-32,767 to +32,7676) or as a hexadecimal number ($0 to $FFFF). For inputs and outputs not all 16 bits are always available externally, so that in many cases only 8 bits of an input or output word can be used. In the case of input, output and flag words each bit can be addressed individually. In the case of registers, timer preselects, counter words and error word, the words can only be addressed as words. The counter commands increment and decrement can be used with all words, not only counter words. Arithmetic and logic operations can be used for all words.
23
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
3. Operands
3.3
BIT OPERANDS
Designator O Syntax On.n (On) Application Condition Example
O0.3
Operand Output
Output
On.n (On)
Execution O0.3
Module
CMP
CMP n
Execution
CMP 0 Module
Input
In.n (In)
Condition
I3.2
Error
Condition
Function module
CFM
CFM n
Execution
CFM 0 Module
Flag
Fn.n.n (Fn.n)
Condition
F3.2.0
Flag
Fn.n.n (Fn.n)
Execution
F3.2.0
24
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
3. Operands
Designator FI
Syntax FI
Application Condition
Example
FI
Program1
Pn
Condition
P2
Program1
Pn
Execution
P3 S
Timer
Tn
Condition
T9
Timer
Tn
Execution
T0 S
Counter
Cn
Condition
C21
Counter
Cn
Execution
C21 S
Counter
Cn
Execution
C21 INC2
Counter
Cn
Execution
C21 DEC2
Important: There is no Program operand for the FPC 100B/AF. The syntax may vary according to the controller (as shown in brackets). 25
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
3. Operands
3.4
WORD OPERANDS
Designator OW Syntax OWn (OW) Application Condition Example
OW2
>
M_B_OP
Output word
OW
OWn (OW)
Execution
M_B_OP1 TO OW5
Input word
IW
IWn (IW)
Condition
IW3
=
M_B_OP 1
Error word
EW
EW
Condition
EW
=
M_B_OP 1
Error word
EW
EW
Execution
M_B_OP1 TO EW
Function unit
FU
FUnn
Condition
FU12
>
M_B_OP1
Function unit
FU
FUnn
Execution
FU3 TO 2 M_B_OP
Constant
Vnnnnn Condition
M_B_OP1
>
V33441
1. Any multibit operand can be entered here. 2. Any multibit operand can be entered here with the exception of an input word.
26
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
3. Operands
Designator V
Syntax Vnnnnn
Application Execution
V$
V$nnnn
Execution
V$A1C TO M_B_OP2
Vnnnnn
Execution
V-40 TO 2 M_B_OP
Flag word
FW
FWn.3 (FWn)
Condition
FW3
<=
M_B_OP1
Flag word
FW
FWn.3 (FWn)
Execution
FW2 TO 2 M_B_OP
Register
Rn
Condition
M_B_OP1
>
R3 Register R Rn Execution M_B_OP1 TO R1
Timer preselect
TP
TPn
Condition
TP0
<=
M_B_OP 1
1. Any multibit operand can be entered here. 2. Any multibit operand can be entered here with the exception of an input word. 3. See note on page 28.
27
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
3. Operands
Designator TP
Syntax TPn
Application Execution
Timer word
TW
TWn
Condition
TW2
<>
M_B_OP1
Timer word TW TWn Execution TW0 TO 2 M_B_OP
Counter preselect
CP
CPn
Condition
CP28
>
M_B_OP
1
Counter preselect
CP
CPn
Execution
Counter word
CW
CWn
Condition
CW19
>=
M_B_OP 1
Counter word
CW
CWn
Execution
1. Any multibit operand can be entered here. 2. Any multibit operand can be entered here with the exception of an input word.
Important: The syntax of the flag word varies with a greater or lesser number of operands depending on the type of controller used. nn always starts at 0 and goes to the type-dependent maximum value. 28
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
3. Operands
3.5
RETENTIVE OPERANDS Retentiveness is the property of an operand to retain its status even during a power failure. As operands are always stored in RAM, this property is only possible if a buffer battery is installed, or in a flash memory. In the case of Festo PLCs, all operands are retentive where it makes sense, i.e. all flags, registers, counters, counter preselects, counter words and timer words. All outputs are generally volatile. For safety reasons all outputs must not remain ON in the event of a power failure. In the event of power failure and battery failure all operands (except outputs) must be initialized by the application program, setting them to the desired initial value (possibly with the aid of an appropriate module to zero all operands).
29
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
3. Operands
Notes
30
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
31
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Contents 4.1 4.2 NOTES ................................................. 33 WHAT IS A RUNG COMPRISED OF?............................... 34 CONDITIONAL AND EXECUTIVE PART ............................. 37 HOW IS A RUNG PROCESSED? ..... 38 Advantages of the process image method .................................................. 44 Advantages of the direct access method..................................... 45 HOW FAST IS A CONTROLLER?.... 46
4.3
4.4
4.5
32
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
4.1
NOTES A Ladder diagram program consists of Rungs. Each rung has a minimum of one contact set, and a maximum of 12 contacts in series. Each rung also has at least one, and generally at least 6 rung sections. Additionally up to 9 parallel branches can be inserted, resulting in a maximum of 10 contacts in parallel. The parallel branches can be positioned anywhere, except that they must not overlap. Coils can also be configured in parallel, but they must all have one common input. A rung can thus only send a single logical signal to all coil contacts.
33
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
4.2
WHAT IS A RUNG COMPRISED OF? In its simplest form the Ladder diagram is an image of the American circuit diagram. It is similar to the German circuit diagram, but is always read from left to right. First let's look at some terms: The Ladder diagram consists of rungs, parallel paths, rung sections, contacts, boxes, coils and parallel coils.
A Box can be used to replace a contact or a coil. Boxes are used for functions that are difficult or impossible to represent in the Ladder diagram or circuit diagram, for example an arithmetic operation, like the addition of two numbers. Fig. 4/2: Adding two numbers
IW2 + V321 R3
34
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Parallel branches can be used at any point in the rung, as long as their connections do not cross. Parallel branches are called parallel coils.
Parallel coil
Parallel branch
35
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
The rungs displayed so far only contain operations, and therefore represent nothing more than a logical linkage of binary elements. Each operation, that is each contact, coil and box (but not each rung section) requires an operand. If the operand is missing, the FST software will reject the program as containing errors and will not load it into the controller. The operand is written over the contact/coil. This is done with the aid of the function key (or for FST software version 3.1 or later with the mouse) activating the function "Enter operand". In the case of boxes it is quite common for two, three or more operands to be entered. More on that later.
36
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
4.3
CONDITIONAL AND EXECUTIVE PART Like all Boolean or logic operations, the rung can be divided into a conditional part and an executive part. The conditional part (in rung section) contains the condition for a given action; the executive part (coils and parallel coils) contains the action to be carried out if the condition is met. This is the same in an electrical circuit diagram. An electrical "load" represents the executive part of the current path. The contacts in series or parallel, with normally-open and normally-closed contacts, represent the conditional part.
37
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
4.4
HOW IS A RUNG PROCESSED? The rungs are numbered. The numbering is carried out automatically. For this reason there is a clear sequence of rungs. Before loading the ladder diagram program into the controller the program is translated into the machine code used by the controller. The rungs are translated consecutively in their number sequence. Even within a rung the machine code uses the sequence programmed by you. It follows that a second coil in a rung will also appear second in the machine code. In the case of the FPC 405, the second coil is also switched second, with a delay measured in microseconds. In the case of the FPC 100, IPC and FEC, the second coil is written as second in the process image, and transmission to the physical outputs takes place independent of the programmed sequence. The entire program is then executed strictly in sequence (as in every computer with only one processor). When powering up or starting with the run/stop switch each controller begins at the first program line. So when you are programming you always know which operation will be executed first.
38
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
This is utilized in particular when applying the so-called initialization flag. Initialization flag FI is a special one-bit operand which has the value logic 1 for the first cycle of a program. With the aid of FI it is possible to put any operand into the desired initial status for the program (initializing operands). This method is used to reset retentive operands after powering up, but also to set particular outputs to an initial value (displays, for example, showing the operating mode). The initialization flag FI has the value logic 1 from the beginning of the program for one cycle.
FI
O0.1
Fig. 4/4: Interrogation of FI The negated interrogation of FI is an existing 1, which has the value logic 1 as long as the program is executed after the first cycle.
FI
O0.1
Fig. 4/5: Negated interrogation of FI This treatment of the initialization flag FI is the same for all Festo controllers programmed in Ladder diagram. 39
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
However, the internal processing of certain Festo controllers differ slightly: The FPC 100, IPC and FEC controllers (as typical single processor system) use a process image for program execution. The process image represents the status of inputs and outputs. Before processing the first rung this process image is updated. During execution of the program the status of the inputs is never read in, and the status of externally visible outputs is not changed. (The process image is also updated when jumping to an earlier part of the program. It is also updated before processing the first rung of each Ladder diagram program. So, if you use a project with several programs, the process image is updated before commencing the execution of each program.)
Rung 1
Rung 1
Rung 2
Rung 2
Rung 3
Rung 3
Toolbar
Menubar
Contents
Search
Page
The FPC 405 controller (as a typical multiprocessor system) does not use a process image. The status of an input is interrogated immediately following the input signal delay, when the input is interrogated in the program. An output signal is written to an output at exactly the time the appropriate command is executed in the program. What does it mean in practice? The following program could be written for any Festo PLC:
Rung No. 1 I0.1
41
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
The program does not make a lot of sense, as output O0.1 is simply switched on and off again continually. In the case of a controller with process image - for example the FPC 100 - the external output would not be switched on and off in this way. The output remains on if the input is logic 1 or off if the input is logic 0, because the last thing that happens in this command before updating of the process image is setting the output (if the condition is met). On the other hand, a controller that accesses inputs and outputs directly will switch the external output on and off as programmed. This is necessary, so that in an environment with multiple processor modules, all modules have direct access to the inputs and outputs. In the case of the FPC 405, you can see the rapid flashing of the outputs using an oscilloscope. In most cases you can also see that the output light-emitting diode appears less bright.
42
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
I0.1
Fig. 4/8: Program Here an input is interrogated for logic 1 and logic 0. A superfluous program, as a permanent 1 can be much more easily programmed with NOP. At first glance it appears that this condition will always be met as each input can only be logic 0 or logic 1. However, this only applies for a controller with process image (FPC 100, IPC, FEC). Only then can you be sure that the logical status of the input cannot change between the two interrogations of the input. In the case of the controllers with direct access to inputs (FPC 405) it is quite possible that the logical status of input I0.1 could change between the two interrogations. This does not happen very often, but in practice cannot be ignored.
43
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Advantages of the process image On the one hand the process image method ensures that inputs cannot change their logical status during the program cycle. Secondly, it is ensured that the outputs can only adopt the logical status last programmed. This allows safety or checking routines to be written at the end of the program to pick up programming errors. (If such check routines are absolutely necessary for controllers with direct input and output access, they are programmed with flags. Only at the end of the program are these flags written to the outputs as required by the check routines.) And finally, program execution is much faster when a process image is used. However, when creating the process image, the cyclic time of the program must be checked.
44
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Advantages of the direct access method Direct access makes it possible to operate several processor modules in parallel, that is to use a multiprocessor system. Furthermore, the direct access method ensures that only the current status of an input is used. The cycle time does not need to take the time for updating the process image into account. Finally, the rapid switching of outputs can be used for driving electronic peripherals (for example stepper motors, electronic counters, electronic displays, electronic multiplexers). Which of the two methods is better for a specific application will depend on a number of criteria. In case of doubt it is good to know: FPC 100, IPC and FEC are single processor systems and use the process image method. FPC 405 is a multiprocessor system and works with direct access to inputs and outputs.
45
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
4.5
HOW FAST IS A CONTROLLER? Each contact and each coil involve time. Therefore it follows that the cycle time of a controller will increase with program length. This is the case with all modern PLCs. In order to avoid excessively long cycle times, modern controllers offer the jump command. This allows unnecessary program parts to be skipped. This command is also available in Ladder diagram for the Festo controllers. The cycle times of controllers vary greatly. In addition, as the time taken to process various commands can vary greatly (an arithmetic operation takes longer than simply switching an output), it is difficult to make a global statement about the cycle time of a controller. Brochure statements such as "6 milliseconds per 1000 statements" look good but have no value, as different statements require a different length of time for execution. For this reason the example programs in Appendix A contain simple programs with which you can measure the actual cycle time, the longest and shortest cycle time of the program and the reaction time (that is cycle time and input signal delay). Use one of these programs if you want to check the cycle time for a specific application.
46
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
5. Overview of operations
47
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
5. Overview of operations
Contents ARITHMETIC/LOGIC BOX .......................... 50 MODULE ........................................................ 50 SWAP ............................................................. 50 FUNCTION MODULE ................................... 50 INVERTING .................................................... 50 CREATING COMPLEMENT ........................ 50 LOAD TO ....................................................... 50 LOGIC ............................................................ 51 Exclusive OR (EXOR) ................................... 51 Exclusive OR (EXOR) with 3 outputs............ 51 Exclusive OR (EXOR) with words................. 51 Identity............................................................. 52 NOT (at output) .............................................. 52 NOT (at input)................................................. 52 OR ............................................................... 53 OR with words ................................................ 53 AND ............................................................... 53 AND with words.............................................. 53 NOP ............................................................... 53 ARITHMETIC FUNCTIONS Adding ............................................................. 54 Dividing ........................................................... 54 Multiplying ....................................................... 54 Subtracting...................................................... 54 ROTATING To left.............................................................. 54 To right............................................................ 54 SHIFTING To left.............................................................. 54 To right............................................................ 54 LATCHING (memory) ................................... 55 48
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
5. Overview of operations
JUMPING to a flag ....................................... 55 ENTERING a jump destination ................. 55 COILS ............................................................. 55 RESET (delete).............................................. 55 SET ............................................................... 55 Assignment..................................................... 55 Negated assignment...................................... 55 COMPARATORS.......................................... 55 Equal 55 Greater than ................................................... 55 Greater than or equal..................................... 56 Less than........................................................ 56 Less than or equal ......................................... 56 Unequal........................................................... 56 NUMBERS Conversion BCD to BINARY......................... 56 Conversion BINARY to BCD......................... 56 COUNTING Interrogated preselect achieved? ................. 57 Interrogated preselect not achieved? ........... 57 Decrement...................................................... 57 Increment........................................................ 57 Set counter ..................................................... 57 TIME Start switch-off delay ..................................... 57 Switch-off delay time expired? ...................... 57 Switch-off delay time running?....................... 58 Start switch-on delay...................................... 58 Switch-on delay time expired?....................... 58 Switch-on delay time running?....................... 58 Start pulse timer ............................................. 58 Pulse timer running? ...................................... 58 49
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
5. Overview of operations
Function This box allows arithmetic or logic word operations to be carried out.
CMP 0 Module
Swap
FW4 SWAP R3
Swap the high and low byte of the upper word (here FW4) and write them to the lower word (here R3).
Function module
CFM 0 Module
Invert
R2 INV R2
Invert every bit of the upper word (here R2) individually and write the result to the lower word (here R2).
Complement
R2 CPL R2
Write the two's complement of the upper word (here R2) (i.e. change sign).
LOAD TO
V12 TO CW4
Load the value from the upper word (here 12) into the lower word (here CW4).
50
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
5. Overview of operations
Symbol
Function
I0.1
I0.2
I0.1
I0.2
I0.1
I0.2
I0.3
I0.1
I0.2
I0.3
I0.1
I0.2
I0.3
R2 X IW0 FW1
EXOR each individual bit of the upper word (here R2) with each bit of the middle word (here IW0) and write the result to the lower word (here FW1).
51
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
5. Overview of operations
Function Direct transfer of the logic status of a bit to the output bit
I0.1
O0.1
I0.1
O0.1
I0.1
O0.1
52
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
5. Overview of operations
Operation Logic: OR
Symbol
Function
I0.1
I0.2
I0.3
NOP
Toolbar
Menubar
R2 IW0 FW1
NOP
53
Contents Search Page
Toolbar
Menubar
Contents
Search
Page
5. Overview of operations
Function The addition of two whole numbers and storing the result
Rotation: left
Rotation: right
Shift: left
Shift: right
Toolbar
Menubar
Arithmetic: Subtraction
Arithmetic: Multiplication
Arithmetic: Division
CW5 V2 CW5
CW5 CW1 R4
Multiplies two whole numbers (places beyond decimal point are ignored)
V244 R4 TW5
54
Contents Search Page
Toolbar
Menubar
Contents
Search
Page
5. Overview of operations
Symbol
Function Jump to label clearly indicated at some point in the program (here the label is DESTINATION).
Destination >>
Jump destination
Destination L
Coils: RESET
O0.1 R
Coils: SET
O0.1 S
Coils: Assignment
O3.2
The output bit must always have the same logical status as the result of the previous condition.
O3.2
The output bit must always have the negated logical status of the result of the previous condition.
Comparison: Equal
CW7
=
CW12
55
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
5. Overview of operations
Symbol
Function
CW3
>
V3467
The rung carries a logic 1 if the upper word (here CW3) is greater than the lower word (here the value 3467). The rung carries a logic 1 if the upper word (here CW3) is greater than or equal to the lower word (here the value 34777). The rung carries a logic 1 if the upper word (here IW4) is less than the lower word (here FW12).
CW3
>=
V34777
Comparison: Less
IW4
<
FW12
TW5
<=
V332
The rung carries a logic 1 if the upper word (here TW5) is equal to or less than the lower word (here the value 332). The rung carries a logic 1 if the two words (here CW4 and OW1) are unequal.
Comparison: Unequal
CW4
<>
OW1
The upper word (here FW4) is interpreted as a decimal number and converted into binary. The result is written to the lower operand (here OW3). The upper word (here FW4) is interpreted as binary and converted into BCD-code. The result is written into the lower word (here OW3).
56
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
5. Overview of operations
Operation Counting: Preselect interrogation achieved? Counting: Preselect interrogation not achieved? Counting: Decrement
Symbol
Function
C4
Rung is logic 1, if the counter (here No. 4) has reached or exceeded the preselect of has not yet been started. Rung is logic 1, if the counter (here No. 4) has not reached the preselect.
C4
CW4 DEC
1
Counting; Increment
R5 INC 1
Counting: Set counter Time: Start switch-off delay Time: Switch-off delay Time expired?
C4 7663 Counter
The counter preselect (here for No. 4) is set to the value indicated (here 7663), and the counter bit (here C4) becomes logic 1. The timer (here No. 30) is set as a delay timer with the duration indicated (here 200 seconds).
TOFF30
57
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
5. Overview of operations
Operation Time: Switch-off delay Time running? Time: Start switch-on delay Time: Switch-on delay Time expired? Time: Switch-on delay Time running Time: Start pulse timer Time: Pulse timer Time expired?
Symbol
Function
TOFF30
The rung is logic 1, if the preselect time has not yet expired.
The timer (here No. 5) is set as a switch-on delay with the duration indicated (here 3.4 seconds).
TON5
TON5
T0 4s Timer
The timer (here No. 0) is started as a pulse timer with the preselect indicated (here 4 seconds).
T0
Rung is logic 1, if the preselect time has expired or the timer has not been started.
T0
58
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
59
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Contents ARITHMETIC/LOGIC BOX .......................... 62 MODULE ........................................................ 65 SWAP ............................................................. 67 FUNCTION MODULE ................................... 69 INVERTING .................................................... 71 CREATING COMPLEMENT ........................ 73 LOAD TO ....................................................... 75 LOGIC Exclusive OR (EXOR) ................................... 76 Exclusive OR (EXOR) with 3 outputs............ 77 Exclusive OR (EXOR) with words................. 79 Identity............................................................. 81 NOT (at output) .............................................. 82 NOT (at input)................................................. 83 OR ............................................................... 84 OR with words ................................................ 85 AND ............................................................... 87 AND with words.............................................. 88 NOP ............................................................... 90 ARITHMETIC FUNCTIONS Adding ............................................................. 91 Dividing ........................................................... 93 Multiplying ....................................................... 95 Subtracting...................................................... 97 ROTATING To left.............................................................. 99 To right..........................................................101 SHIFTING To left............................................................103 To right..........................................................105 LATCHING (memory) .................................107 60
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
JUMPING to a flag .....................................110 ENTERING a jump destination ...............111 COILS RESET (delete)............................................113 SET .............................................................114 Assignment...................................................115 Negated assignment....................................116 COMPARATORS Equal .............................................................117 Greater than .................................................119 Greater than or equal...................................121 Less than......................................................123 Less than or equal .......................................125 Unequal.........................................................127 NUMBERS Conversion BCD to BINARY.......................129 Conversion BINARY to BCD.......................131 COUNTING Interrogated preselect achieved? ...............133 Interrogated preselect not achieved? .........135 Decrement....................................................137 Increment......................................................138 Set counter ...................................................139 TIME Start pulse timer ...........................................141 Interrogate pulse timer.................................142
61
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
The Arithmetic/Logic Box The Arithmetic/Logic Box is only used in the executive part. It allows coherent programming of word operations in contrast to the multi-bit boxes which only allow one command each. The Arithmetic/Logic Box is indicated in the rung as a box. In the printout the contents of the box are printed immediately following the rung containing the Arithmetic/Logic Box. During programming you can examine the contents of the box by positioning the cursor on the box and pressing the <Enter> key. The contents of the box are then displayed on the screen. You can cancel the display of contents by pressing the <ESC> or <Enter> key. Independent of the number of command lines within the box, the Arithmetic/Logic Box is only regarded as a single box. Up to 16 lines can be entered into the Arithmetic/Logic Box. As only 5 boxes can be used in a rung, only 4 other boxes can be used in addition to an Arithmetic/Logic Box. Within the Arithmetic/Logic Box, multi-bit commands are entered as text and therefore not always the same as the commands otherwise entered in Ladder diagram boxes. In addition, there is a space for comments below the Arithmetic/Logic Box.
62
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Each field of the Arithmetic/Logic Box may only contain one entry. Example:
Fig. 6/1: Logic, EXOR using words The same operation in an Arithmetic/Logic Box has the following structure:
Rung No. 67 Condition Arithm. /logic
Boxes in Rung No. 67 Arithmetic/logic LOAD EXOR TO R2 IW0 FW1 Contents of Register 2 EXOR with Input word 0 Write result to Flag word 1
63
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Figures 6/1 and 6/2 show an EXOR operation on two words. 6/1 in a multi-bit box and 6/2 in the Arithmetic/Logic Box. (For details of this operation see "Exclusive OR with words".) In the Arithmetic/Logic Box the multi-bit operation begins with the LOAD command. This indicates that the entered multi-bit operand is loaded into the processor module's multi-bit accumulator. The required operation is carried out in this multi-bit accumulator. The result is loaded from the multi-bit accumulator into any other multi-bit operand of your choice (command: TO). In the multi-bit box, EXOR is indicated by an x. In the Arithmetic/Logic Box EXOR is indicated by EXOR. The result of the operation in the multi-bit box and in the Arithmetic/Logic Box is completely identical. The Arithmetic/Logic Box is better when you want to use several multi-bit operations in a single rung, and/or when you want to enter comments.
64
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
MODULE Modules (also called program modules) are MODULES created by the user that can be called up at any point in a Ladder diagram program. Modules must be clearly identified as a module when calling them from the Ladder diagram editor. These modules or program MODULES are nothing more than subroutines. Subroutines allow repetitive procedures in a program to be written once but called up many times. The individual controllers support the following number of modules: FPC 100B/AF: 8 program modules IPC: 100 program modules FEC: 100 program modules FPC 405: 32 program modules (The program modules for the FPC 405 may only be written in assembler if they are to be called from the Ladder diagram program.) For example, a text display may be connected to a controller. The transmission of data to this text display can be programmed by means of a program module.
65
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
The contents of a text display need to be updated from various parts of the program: from the automatic program as well as from the manual program. An error message changes the text, as does an operator entry. At this point in your program you call the MODULE that handles data transmission to the text display. This makes the program shorter and easier to read.
Rung No. 1 Condition CPM0 Module
66
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
SWAP All operands in the Festo controllers are structured as 16-bit words. Each word consists of two 8-bit bytes, the low byte (right) and the high byte (left). Sometimes it may be necessary to swap the two bytes of a word. This can be done with the Ladder diagram command SWAP. The command SWAP changes:
0 1 1 1 0 1 1 0 0 1 1 0 0 1 1 1
to:
0 1 1 0 0 1 1 1 0 1 1 1 0 1 1 0
67
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Boxes in Rung No. 2 Arithmetic/logic LOAD SWAP TO FW3 FW4 Load contents of Flag word 3 SWAP BYTES Write result to Flag word 4
68
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
FUNCTION MODULE Function modules as opposed to program modules are sub-programs pre-programmed into the controller by Festo. So these are subroutines in the accepted sense, or to be more precise procedures, as generally used in higher programming languages. These subroutines are supplied with the controller or can be ordered separately from Festo. One example of a function module (CFM) is for opening a network for the FPC 405. Function module CFM 70 is used for this purpose. The station number of the calling processor module and the desired timeout are passed to CFM 70 as parameters. CFM 70 leaves the message in function unit 32 indicating whether network setup was successful or not. Fig. 6/6: Function module CFM 70
Rung No. 1 Condition CFM 70 Module
Boxes in Rung No. 1 CFM 70 / Initialize network Network connection for this processor module is established V1 V12 Station 1 of the network 120 ms timeout
69
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Another typical function module is CFM 0 for the FPC 100B/AF. This function module facilitates deletion of all retentive operands, as required for many applications. The following application is typical:
Boxes in Rung No. 1 CFM 0 / Delete function units Delete retentive function units V3 Delete timers and counters
Fig. 6/7: Function module CFM 0 The function modules offered depend on the controller type. For details please see the system manual for the appropriate controller type.
70
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
INVERTING INVERT is an operation for use with multi-bit operands. INVERT negates each bit of a word.
Fig. 6/8: Inverting The same result can be achieved by using INVERT in the Arithmetic/Logic Box:
Rung No. 59 Condition Arithm. &Logic
Boxes in Rung No. 59 Arithmetic/logic LOAD INV TO R2 R2 Contents of Register 2 INVERT Write result to Register 2
Fig. 6/9: Inverting in arithmetic box In this example register 2 is inverted and the result is written back to register 2.
71
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
becomes -3031210, 3522410 or 899816. Any multi-bit operand can be entered as the operand to be inverted (the upper operand in the box). The result can be returned to any multi-bit operand (the lower operand in the box) with the exception of input words. If the operand at the top is not the same as the operand at the bottom, the contents of the upper operand are not changed.
72
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
COMPLEMENT COMPLEMENT is an operation for use with multi-bit operands. The COMPLEMENT operation is used to change the sign of a number. The value -5 becomes 5, the value 2734 becomes -2734. The COMPLEMENT operation only makes sense if you are working with signed numbers.
Fig. 6/10: Creating the complement The same function is programmed in the
Rung No. 57 Condition Arithm. &Logic
Boxes in Rung No. 57 Arithmetic/logic LOAD CPL TO R2 OW4 Contents of Register 2 COMPLEMENT Write result to Output word 4
Arithmetic/Logic Box as follows: Fig. 6/11: Creating the complement in arithmetic box
73
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
In this example the COMPLEMENT of register 2 is written to output word 4 (register 2 remains unchanged). 3031110, 3031110 or 766716
0 1 1 1 0 1 1 0 0 1 1 0 0 1 1 1 1 0 0 0 1 0 0 1 1 0 0 1 1 0 0 0
becomes -3031110, 3522510 or 899916. The COMPLEMENT operation can be used for all multi-bit operands. The destination (lower operand) can be any multi-bit operand with the exception of an input word. If the upper operand (source) and lower operand (destination) are different, the upper operand is left unchanged.
74
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
LOAD TO LOAD TO is an operation for use with multi-bit operands. LOAD TO allows the contents of a multi-bit operand to be loaded into another multi-bit operand. The source can be any multi-bit operand, the destination can also be any multi-bit operand with the exception of an input word.
Rung No. 2 Condition V12 T0 CW4
Fig. 6/12: Load to The identical function is programmed using the Arithmetic/Logic Box as follows: Fig. 6/13: Load to (Arithmetic/Logic Box)
Rung No. 3 Condition Arithm. &Logic
Boxes in Rung No. 3 Arithmetic/logic LOAD TO V12 CW4 Value 12 (decimal) Write to counter word 4
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
LOGIC: EXCLUSIVE OR (EXOR) EXOR is one of the common logic operations. The logic module is shown thus:
I1 I2
=1
O1
Fig. 6/14: Logic module The truth table for EXOR is as follows:
I1 0 0 1 1 I2 0 1 0 1 O1 0 1 1 0
Ladder diagram does not offer an independent operation for EXOR. The EXOR must be constructed using a combination of parallel and series circuits and negations.
Rung No. 4 I0.1 I0.2 Execution
I0.1
I0.2
76
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
LOGIC: EXCLUSIVE OR (EXOR) with 3 inputs There are different views on the truth table for an EXOR with three inputs. In many cases particularly when programming with statement list the EXOR can only be used with a maximum of two inputs. Here the EXOR with three inputs is shown for the sake of completeness and to demonstrate how you can expand the logical function of EXOR (and any other logical function) to meet your requirements. The logic element for EXOR with three inputs is shown thus:
I1 I2 I3
=1
O1
Fig. 6/16: Logic module The truth table can also be expanded:
I1 0 0 0 0 1 1 1 1 I2 0 0 1 1 0 0 1 1 I3 0 1 0 1 0 1 0 1 O1 0 1 1 0 1 0 0 0
77
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
I0.1
I0.2
I0.3
I0.1
I0.2
I0.3
78
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
LOGIC: EXCLUSIVE OR (EXOR) with words The EXOR that can be used with multi-bit operands is used in the executive part of the Ladder diagram. Thus, this EXOR does not represent a condition for an action, but is only called if the condition is met (the rung evaluated to logic 1).
Rung No. 66 Condition R2 X IW0 FW1
Fig. 6/18: LOGIC: Exclusive OR using words This operation can be programmed identically with the Arithmetic/Logic Box as follows:
Rung No. 67 Condition Arithm. &Logic
Boxes in Rung No. 67 Arithmetic/logic LOAD EXOR TO R2 IW0 FW1 Contents of Register 2 EXOR with Input word 0 Write result to Flag word 1
79
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
In this example an EXOR operation is carried out on each of the bits from register 2 with the corresponding bits of input word 0. This is carried out 16 times, each time with two inputs. The result is written to flag word 1, so that register 2 and input word 0 remain unchanged. Register 2:
0 1 1 1 0 1 1 0 0 1 1 0 0 1 1 1
X X X X X X X X X X X X X X X X
becomes:
1 0 0 1 1 1 1 0 1 0 1 0 0 1 1 1
and is written to flag word 1. The EXOR can be used for any multi-bit operands and the result can be written to any multibit operands with the exception of an input word.
80
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
LOGIC: IDENTITY1 The IDENTITY (yes function) is one of the basic logic operations. It has one input and one output (like negation). The logic symbol for IDENTITY is shown thus:
I1
O1
Fig. 6/20: Logic symbol for IDENTITY The truth table for IDENTITY is as follows:
I1 0 1 O1 0 1
81
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
LOGIC: NOT1 (at output) The NOT or negation is the inversion of identity. The logic signal of an input is negated. In Ladder diagram this negation can be used for the input or the output. For this reason the two methods are described separately. The logic symbol for the NOT function (at output) is shown thus: Fig. 6/22: Logic symbol for NOT function
I1
O1
The NOT function is programmed in Ladder diagram as follows: Fig. 6/23: NOT (at output) The slant (oblique stroke) within the coil
Rung No. 6 I0.1 O0.1
82
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
LOGIC: NOT1 (at input) NOT or negation is the inverse of identity. The logic signal of an input is negated. In Ladder diagram this negation can be used for the input or the output. For this reason the two methods are described separately here. The logic symbol for a NOT function (at input) is shown thus: Fig. 6/24: Logic symbol for NOT function
I1
O1
The NOT function is programmed in Ladder diagram as follows: Fig. 6/25: LOGIC: NOT (at input)
Rung No. 6 I0.1 O0.1
83
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
LOGIC: OR OR is one of the basic logic operations (like AND and NOT). The logic symbol for OR is shown thus: Fig. 6/26: Logic symbol OR
I1 I2
>1 _
O1
I0.2
84
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
LOGIC: OR with words The OR operation can be used for multi-bit operands. In this case it is not a condition for the command in the executive part. When carrying out an OR operation using words, we speak of "masking". If for example you want the fifth bit of a word (counting from the least significant bit) to have the value logic 1 you OR this word with another word in which only the fifth bit has the value logic 1. The resulting word contains all the bits of the output word and guarantees that the fifth bit has the value 1. Register 2:
0 1 v v v 1 v 1 0 v v 1 1 v v 0 0 v v 1 v 1 0 v v 0 1 v v 1 v 1 v
OR value 16
0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0
becomes:
0 1 1 1 0 1 1 0 0 1 1 1 0 1 1 1
85
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
In Ladder diagram you can OR-mask in the multi-bit box or in the Arithmetic/Logic Box:
Rung No. 64 Condition R2 v V16 FW1
Fig. 6/28: LOGIC: OR using words The same function can be programmed with the Arithmetic/Logic Box:
Rung No. 65 Condition Arithm. &Logic
Boxes in Rung No. 65 Arithmetic/logic LOAD OR TO R2 V16 FW1 Contents of Register 2 OR with the value 16 Write result to Flag word 1
Fig. 6/29: LOGIC: OR using words in arithmetic box Masking does not have the same significance for programmable logic controllers as it does in other areas of computing. You could simply set the fifth bit of the word by loading the word into a flag or output word. There you could change the fifth bit to logic 1 using the set command and, if required, load the word back. You can OR any two multi-bit operands. The destination for the result can be any multi-bit operand with the exception of an input word. 86
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
LOGIC: AND AND belongs to the basic logic operations (like OR and NOT). The logic symbol for AND is as follows (shown
I1 I2 I3
&
O1
here with three inputs): Fig. 6/30: Logic symbol AND The truth table for AND is as follows:
I1 0 0 0 0 1 1 1 1 I2 0 0 1 1 0 0 1 1 I3 0 1 0 1 0 1 0 1 O1 0 0 0 0 0 0 0 1
In Ladder diagram AND is represented by seRung No. 10 I0.1 I0.2 I0.3 Execution
87
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
LOGIC: AND with words The AND operation can also be used for multibit operands. In this case it is not a condition but a command in the executive part. When carrying out an AND operation with words, we speak of "masking". For example, if you want to establish whether the fifth bit of a word (counting from the least significant bit) has the value logic 1, you AND this word with another word in which only the fifth bit has the value logic 1. If the result is 0, the fifth bit in the word you are testing is 0. If the result is greater than 0, the fifth bit has the value 1. Register 2:
0 1 ^ ^ 1 ^ 1 0 ^ ^ 1 1 ^ ^ 0 0 ^ ^ 1 ^ 1 0 ^ ^ 0 1 ^ ^ 1 ^ 1 ^
AND value 16
0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0
becomes:
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
88
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
In Ladder diagram you can AND in the multi-bit box or in the Arithmetic/Logic Box:
Rung No. 63 Condition R2 ^ V16 FW1
Fig. 6/32: LOGIC: AND with words The same function can be programmed with the Arithmetic/Logic Box:
Rung No. 63 Condition Arithm. &Logic
Boxes in Rung No. 63 Arithmetic/logic LOAD AND TO R2 V16 FW1 Load contents of Register 2 AND-mask with value 16 Write result to Flag word 1
Fig. 6/33: LOGIC: AND with words in arithmetic box Masking does not have the same significance for programmable logic controllers as it does in other areas of computing. You could simply interrogate the fifth bit of a word by loading the word into a flag or output word. From a flag or output word you can interrogate the fifth bit in binary as Fx.4 or Ox.4. You can AND any multi-bit operands. The destination for the result can be any multi-bit operand with the exception of an input word.
89
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
NOP NOP is the null operation, that is, an operation that "does nothing". All programming languages have null operations. In Ladder diagram, NOP can be used as an operand designation or contact but not for coils. If NOP is used, this contact is always switched through, which has the same effect as the negated interrogation of the initialization flag FI after the first cycle of the program.
Rung No. 6 NOP O0.1
Fig. 6/34: NOP In this example, output O0.1 is always switched through. If NOP is used, this means that the rung is always active and that signal-edge recognition is switched off. In the following example counting takes place for each cycle, not only for the 0Rung No. 12 NOP CW3 CP
90
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Arithmetic function: ADDING The four basic arithmetic functions ADDING, subtracting, multiplying and dividing are available for all Festo controllers. These arithmetic functions can also be used in Ladder diagram. In the Festo controller, these arithmetic functions are always used for whole, signed numbers in the range 32767. The overflow cannot be interrogated. If you use these numbers outside this range, no error message is given. Overflow is simply truncated (not rounded). The FPC 405 also allows the use of function module 20 to program arithmetic operations with an overflow that can be interrogated. ADDITION can be programmed as follows:
91
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
The same operation with the same function can be programmed with the Arithmetic/Logic Box as follows:
Rung No. 13 Condition Arithm. &Logic
Boxes in Rung No. 13 Arithmetic/logic LOAD + TO CW5 V12 CW6 Contents of Counter word 5 Add value 12 Write result to counter word 6
Fig. 6/37: Arithmetic: Adding in the arithmetic box Please note that you always need at least three operands for an arithmetic operation. The first two operands are added and the result is written to the third operand. The contents of the first operands (or other operands included with arithmetic functions) are not changed, if neither of these operands is given in the result field. Any multi-bit operand can be used as a source; any multi-bit operand with the exception of an input word may be used as a destination.
92
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Arithmetic function: DIVIDING The four basic arithmetic functions adding, subtracting, multiplying and DIVIDING are available for all Festo controllers. These arithmetic functions can also be used in Ladder diagram. In the Festo controller, these arithmetic functions are always used for whole, signed numbers in the range 32767. The overflow cannot be interrogated. If you use these numbers outside this range, no error message is given. Overflow is simply truncated (not rounded). The FPC 405 also allows the use of function module 20 to program arithmetic operations with an overflow that can be interrogated. DIVISION can be programmed as follows:
Rung No. 14 Condition CW5 / V2 CW5
93
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
The same operation with the same function can be programmed with the Arithmetic/Logic Box as follows:
Rung No. 15 Condition Arithm. &Logic
Boxes in Rung No. 15 Arithmetic/logic LOAD / TO CW5 V2 CW5 Contents of Counter word 5 Divide by 2 Write result to counter word 5
Fig. 6/39: Arithmetic function: Dividing in the arithmetic box Please note that you always need at least three operands for an arithmetic operation. The first two operands are divided and the result is written to the third operand. The contents of the first operands (or other operands included with arithmetic functions) are not changed, if neither of these operands is given in the result field. Any multi-bit operand can be used as a source; any multi-bit operand with the exception of an input word may be used as a destination.
94
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Arithmetic function: MULTIPLYING The four basic arithmetic functions adding, subtracting, MULTIPLYING and dividing are available for all Festo controllers. These arithmetic functions can also be used in Ladder diagram. In the Festo controller, these arithmetic functions are always used for whole, signed numbers in the range 32767. The overflow cannot be interrogated. If you use these numbers outside this range, no error message is given. Overflow is simply truncated (not rounded). The FPC 405 also allows the use of function module 20 to program arithmetic operations with an overflow that can be interrogated. MULTIPLYING can be programmed as follows:
95
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
The same operation with the same function can be programmed with the Arithmetic/Logic Box as follows:
Boxes in Rung No. 17 Arithmetic/logic LOAD * TO CW5 CW1 R4 Contents of Counter word 5 Multiply by contents of Counter word 1 Write result to Register 4
Fig. 6/41: Arithmetic function: Multiplying in the arithmetic box Please note that you always need at least three operands for an arithmetic operation. The first two operands are multiplied and the result is written to the third operand. The contents of the first operands (or other operands included with arithmetic functions) are not changed, if neither of these operands is given in the result field. Any multi-bit operand can be used as a source; any multi-bit operand with the exception of an input word may be used as a destination.
96
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Arithmetic function: SUBTRACTING The four basic arithmetic functions adding, SUBTRACTING, multiplying and dividing are available for all Festo controllers. These arithmetic functions can also be used in Ladder diagram. In the Festo controller, these arithmetic functions are always used for whole, signed numbers in the range 32767. The overflow cannot be interrogated. If you use these numbers outside this range, no error message is given. Overflow is simply truncated (not rounded). The FPC 405 also allows the use of function module 20 to program arithmetic operations with an overflow that can be interrogated. SUBTRACTING can be programmed as folRung No. 18 Condition * V244 R4 TW5
97
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
The same operation with the same function can be programmed with the Arithmetic/Logic Box as follows:
Rung No. 19 Condition Arithm. &Logic
Boxes in Rung No. 19 Arithmetic/logic LOAD TO V244 R4 TW5 Value 244 Subtract contents of Register 4 Write result to Timer word 5
Fig. 6/43: Arithmetic function: Subtracting in the arithmetic box Please note that you always need at least three operands for an arithmetic operation. The first two operands are subtracted and the result is written to the third operand. The contents of the first operands (or other operands included with arithmetic functions) are not changed, if neither of these operands is given in the result field. Any multi-bit operand can be used as a source; any multi-bit operand with the exception of an input word may be used as a destination.
98
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
ROTATE LEFT ROTATE is one of the commands that shifts the individual bits of a word. In contrast to shift, ROTATE ensures that no bits are lost. The bit pushed off one end of the word is inserted at the other end. So if a 16-bit word is rotated 16 times, it returns to its original value. In the case of ROTATE LEFT (ROL) the bits are shifted left (in the Festo controllers all 16 bits are always shifted). The most significant bit (extreme left) is inserted on the extreme right as the least significant bit.
0 1 1 1 0 1 1 0 0 1 1 0 0 1 1 1
ROL
1 1 1 0 1 1 0 0 1 1 0 0 1 1 1 0
99
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
The same operation programmed with the Arithmetic/Logic Box looks like this:
Rung No. 21 Condition Arithm. &Logic
Boxes in Rung No. 21 Arithmetic/logic LOAD ROL TO OW4 OW4 Contents of Output word 4 ROTATE LEFT Write result to Output word 4
Fig. 6/45: Rotate left in arithmetic box The ROTATE operation can be used for any multi-bit operand. The result can be written to any multi-bit operand except an input word.
100
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
ROTATE RIGHT ROTATE is one of the commands that shifts the individual bits of a word. In contrast to shift, ROTATE ensures that no bits are lost. The bit pushed off one end of the word is inserted at the other end. So if a 16-bit word is rotated 16 times, it returns to its original value. In the case of ROTATE RIGHT (ROR) the bits are shifted to the right (in the Festo controller all 16 bits are always shifted). The least significant bit (extreme right) is inserted on the extreme left as the most significant bit.
0 1 1 1 0 1 1 0 0 1 1 0 0 1 1 1
ROR
1 1 1 0 1 1 0 0 1 1 0 0 1 1 1 0
ROTATE RIGHT is programmed in Ladder diagram as follows: Fig. 6/46: Rotate right
Rung No. 22 Condition OW4 ROR OW4
101
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
The same operation programmed with the Arithmetic/Logic Box looks like this:
Rung No. 23 Condition Arithm. &Logic
Boxes in Rung No. 23 Arithmetic/logic LOAD ROR TO OW4 OW4 Contents of Output word 4 ROTATE RIGHT Write result to Output word 4
Fig. 6/47: Rotate right in arithmetic box The ROTATE operation can be used for any multi-bit operand. The result can be written to any multi-bit operand except an input word.
102
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
SHIFT LEFT SHIFT is one of the commands that allows the individual bits of a word to be shifted. In contrast to rotate, SHIFT shifts one bit off the end of the word this bit is lost. A 0 is inserted at the other end of the word. If a 16-bit word is shifted 16 times, all bits are set to 0. In the FPC 405 the bit shifted out can be interrogated with the local flag FI7. SHIFT LEFT (SHL) shifts the bits to the left (in the Festo controller all 16 bits are always shifted). The most significant bit (extreme left) is shifted out, and a 0 is inserted at the extreme right.
0 1 1 1 0 1 1 0 0 1 1 0 0 1 1 1
SHL
1 1 1 0 1 1 0 0 1 1 0 0 1 1 1 0
103
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
The same operation programmed with the Arithmetic/Logic Box looks like this:
Rung No. 25 Condition Arithm. &Logic
Boxes in Rung No. 25 Arithmetic/logic LOAD SHL TO FW2 OW0 Load contents of Flag word 2 SHIFT LEFT Write result to Output word 0
Fig. 6/49: Shift left in arithmetic box The SHIFT operation can be used to change any multi-bit operand. The result can be written to any multi-bit operand except an input word.
104
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
SHIFT RIGHT SHIFT is one of the commands that allows the individual bits of a word to be shifted. In contrast to rotate, SHIFT shifts one bit off the end of the word this bit is lost. A 0 is inserted at the other end of the word. If a 16-bit word is shifted 16 times, all bits are set to 0. In the FPC 405 the bit shifted out can be interrogated with the local flag FI7. SHIFT RIGHT (SHR) shifts the bits to the right (in the Festo controller all 16 bits are always shifted). The least significant bit (extreme right) is shifted out, and a 0 is inserted at the extreme left.
0 1 1 1 0 1 1 0 0 1 1 0 0 1 1 1
SHR 0
0 0 1 1 1 0 1 1 0 0 1 1 0 0 1 1
105
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
The same operation programmed with the Arithmetic/Logic Box looks like this:
Rung No. 27 Condition Arithm. &Logic
Boxes in Rung No. 27 Arithmetic/logic LOAD SHR TO FW2 OW0 Load contents of Flag word 2 SHIFT RIGHT Write result to Output word 0
Fig. 6/51: Shift right in arithmetic box The SHIFT operation can be used to change any multi-bit operand. The result can be written to any multi-bit operand except an input word.
106
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
LATCH (memory) The LATCH is the electrician's traditional method of constructing a one-bit memory with a relay. In the Festo controllers, the relay is replaced by a flag, allowing any LATCH to be constructed. In programmable logic controllers, a one-bit memory can also be implemented with set and reset commands. However, the LATCH has not lost its significance. We differentiate two types of latch: dominantly resetting and dominantly setting latches. The dominant resetting latch has the value logic 0 when switched on and off. The logic symbol for the latch is shown by the flipflop:
S 1 0 A
107
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Fig. 6/53: Dominant resetting latch The following method is also possible and probably more familiar to the electrician:
Rung No. 2 RESET I1.2 SET I2.3 Flag F0.12 Flag F0.12
108
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
The dominantly setting latch is logic 1 at the output when switched on and off. The flipflop of the dominantly setting latch differs only from the dominant resetting latch in that it has a 1 at the output at the flipflop.
S 1 1 A
Fig. 6/55: Flipflop dominant setting latch In Ladder diagram the resetting input is located in the latch itself in order to force dominant setting behaviour:
Rung No. 2 SET I2.3 Flag F0.12 RESET I1.2 Flag F0.12
109
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
JUMPING to a label The JUMP command is one possibility of shortening the program cycle time by jumping over unneeded parts of the program. In Festo FST, any number of jumps may be programmed. JUMPS have a jump label as their destination, not a rung number. A label, that is a jump destination, is entered at the beginning of the conditional part of a rung. The jump command is inserted in the executive part of the rung and must contain the name of a jump label. This jump label must be contained in the program, or else a syntax error will be reported when translating in the program. The JUMP command in Ladder diagram looks like this:
DESTINATION
110
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Many texts on programming differentiate between a conditional and unconditional JUMP. The jump command shown here is a conditional JUMP, but it can be easily converted into an unconditional jump:
Rung No. 69 NOP Execution
DESTINATION
Fig. 6/58: Unconditional jump Important: A jump command does not replace a contact. There must be at least one entry in each contact. If you only require a jump as a result of a condition, you must enter an (otherwise) unused flag as the operand in the contact.
111
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
ENTERING A JUMP LABEL The JUMP command is one possibility of shortening the program cycle time by jumping over unneeded parts of the program. In Festo FST, any number of jumps may be programmed. JUMPS have a jump label as their destination, not a rung number. A label or jump destination, is entered at the beginning of the conditional part of a rung. The jump command is inserted in the executive part of the rung and must contain the name of a jump label. This jump label must be contained in the program, or else a syntax error will be reported when translating in the program. In Ladder diagram the JUMP label is entered as follows:
Fig. 6/59: Entering a jump label Important: A jump command does not replace a contact. Every rung must have at least one contact, and a condition and executive part must be entered.
112
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Coils: RESET (cancel) When coils are energised, basically we differentiate between stored and non-stored commands. The non-stored commands transfer the logic status of the condition (of the rung) directly to the coil. A coil reflects each change of the logic status of the rung. In the case of stored commands RESET and set, the command is executed precisely if (and only if) the rung has logic status 1, i.e. the condition is therefore fulfilled. If the rung assumes logic 0, i.e. the condition is not fulfilled, the coil which is programmed with a stored command is not changed. The status of the coil is only changed when the rung containing the opposite command becomes logic 1. RESETTING of a coil is indicated by an R in the coil symbol:
Rung No. 28 Condition O0.1 R
113
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Coils: SET When coils are energised, basically we differentiate between stored and non-stored commands. The non-stored commands transfer the logic status of the condition (of the rung) directly to the coil. A coil reflects each change of the logic status of the rung. In the case of stored commands SET and reset, the command is executed precisely if (and only if) the rung has logic status 1, i.e. the condition is therefore fulfilled. If the rung assumes logic 0, i.e. the condition is not fulfilled, the coil which is programmed with a stored command is not changed. The status of the coil is only changed when the rung containing the opposite command becomes logic 1. SETTING of a coil is indicated by an S in the coil symbol:
Rung No. 29 Condition O0.1 S
114
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Coils: ASSIGNMENT When coils are energised, basically we differentiate between stored and non-stored commands. The non-stored commands that is ASSIGNMENT or negated assignment transfer the logic status of the condition (of the rung) directly to the coil. A coil reflects each change of the logic status of the rung. In the case of stored commands set and reset, the command is executed precisely if (and only if) the rung has logic status 1, i.e. the condition is therefore fulfilled. If the rung assumes logic 0, i.e. the condition is not fulfilled, the coil which is programmed with a stored command is not changed. The status of the coil is only changed when the rung containing the opposite command becomes logic 1. ASSIGNMENT, that is the non-stored adoption of the logic status of the rung, is simply programmed by using the coil symbol.
Rung No. 30 Condition O3.2
115
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Coils: NEGATED ASSIGNMENT When coils are energised, basically we differentiate between stored and non-stored commands. The non-stored commands that is assignment or NEGATED ASSIGNMENT transfer the logic status of the condition (of the rung) directly to the coil. A coil reflects each change of the logic status of the rung. In the case of stored commands set and reset, the command is executed precisely if (and only if) the rung has logic status 1, i.e. the condition is therefore fulfilled. If the rung assumes logic 0, i.e. the condition is not fulfilled, the coil which is programmed with a stored command is not changed. The status of the coil is only changed when the rung containing the opposite command becomes logic 1. In the case of NEGATED ASSIGNMENT the negation of the logic status of the rung is transferred to the coil (see also Logic: NOT). NEGATED ASSIGNMENT, that is the nonstored adoption of the negated logic status of the rung, is programmed by using the negated coil symbol.
Rung No. 30 Condition O3.2
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Comparison: EQUAL Comparison operations are basic to every programmable logic controller. Comparisons allow processing of simple analogue values, multiple evaluation of counters, comparison of size etc. Festo controllers allow all comparison operations to be programmed in Ladder diagram: EQUAL Greater than Greater than or equal Less than Less than or equal Unequal
Comparison operations compare positive whole numbers between 0 and 65,535. If a negative value (for example V-10) is entered, the positive whole binary number corresponding to the bit pattern (of V-10) is compared. This does not apply to the FPC 405 if processing has been switched previously to signed numbers (from 0 to 32,767) with CFM20. Comparison operations are always entered into a box in the conditional part.
117
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
The value of the upper operand is always compared to the value of the lower operand. If the expression evaluates to true, the rung has the logic status 1. If the expression evaluates to false, the rung has the logic status 0. The EQUAL operation is programmed as follows:
Fig. 6/64: Comparison: Equal In this example the rung evaluates to logic 1 if counter word 7 has a value that is exactly equal to the value in counter preselect 12.
118
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Comparison: GREATER THAN Comparison operations are basic to every programmable logic controller. Comparisons allow processing of simple analogue values, multiple evaluation of counters, comparison of size etc. Festo controllers allow all comparison operations to be programmed in Ladder diagram: Equal GREATER THAN Greater than or equal Less than Less than or equal Unequal
Comparison operations compare positive whole numbers between 0 and 65,535. If a negative value (for example V-10) is entered, the positive whole binary number corresponding to the bit pattern (of V-10) is compared. This does not apply to the FPC 405 if processing has been switched previously to signed numbers (from 0 to 32,767) with CFM20. Comparison operations are always entered into a box in the conditional part.
119
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
The value of the upper operand is always compared to the value of the lower operand. If the expression evaluates to true, the rung has the logic status 1. If the expression evaluates to false, the rung has the logic status 0. The operation GREATER THAN is programmed as follows:
Rung No. 32 CW3 > V3467 Execution
Fig. 6/65: Comparison: Greater than In this example the rung evaluates to logic 1 if counter word 3 has a value that is greater than 3467 (for example 3468 or even 22341).
120
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Comparison: GREATER THAN OR EQUAL Comparison operations are basic to every programmable logic controller. Comparisons allow processing of simple analogue values, multiple evaluation of counters, comparison of size etc. Festo controllers allow all comparison operations to be programmed in Ladder diagram: Equal Greater than GREATER THAN OR EQUAL Less than Less than or equal Unequal
Comparison operations compare positive whole numbers between 0 and 65,535. If a negative value (for example V-10) is entered, the positive whole binary number corresponding to the bit pattern (of V-10) is compared. This does not apply to the FPC 405 if processing has been switched previously to signed numbers (from 0 to 32,767) with CFM20. Comparison operations are always entered into a box in the conditional part.
121
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
The value of the upper operand is always compared to the value of the lower operand. If the expression evaluates to true, the rung has the logic status 1. If the expression evaluates to false, the rung has the logic status 0. The GREATER THAN OR EQUAL operation is programmed as follows:
Fig. 6/66: Comparison: Greater than or equal In this example the rung evaluates to logic 1 if counter word 3 has a value that is greater than or equal to 34777 (for example 34777, 34778 or greater).
122
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Comparison: LESS THAN Comparison operations are basic to every programmable logic controller. Comparisons allow processing of simple analogue values, multiple evaluation of counters, comparison of size etc. Festo controllers allow all comparison operations to be programmed in Ladder diagram: Equal Greater than Greater than or equal LESS THAN Less than or equal Unequal
Comparison operations compare positive whole numbers between 0 and 65,535. If a negative value (for example V-10) is entered, the positive whole binary number corresponding to the bit pattern (of V-10) is compared. This does not apply to the FPC 405 if processing has been switched previously to signed numbers (from 0 to 32,767) with CFM20. Comparison operations are always entered into a box in the conditional part.
123
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
The value of the upper operand is always compared to the value of the lower operand. If the expression evaluates to true, the rung has the logic status 1. If the expression evaluates to false, the rung has the logic status 0. The LESS THAN operation is programmed as follows:
Rung No. 35 IW4 < FW12 Execution
Fig. 6/67: Comparison: Less than In this example the rung evaluates to logic 1 if input word 4 has a value that is less than the content of flag word 12.
124
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Comparison: LESS THAN OR EQUAL Comparison operations are basic to every programmable logic controller. Comparisons allow processing of simple analogue values, multiple evaluation of counters, comparison of size etc. Festo controllers allow all comparison operations to be programmed in Ladder diagram: Equal Greater than Greater than or equal Less than LESS THAN OR EQUAL Unequal
Comparison operations compare positive whole numbers between 0 and 65,535. If a negative value (for example V-10) is entered, the positive whole binary number corresponding to the bit pattern (of V-10) is compared. This does not apply to the FPC 405 if processing has been switched previously to signed numbers (from 0 to 32,767) with CFM20. Comparison operations are always entered into a box in the conditional part.
125
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
The value of the upper operand is always compared to the value of the lower operand. If the expression evaluates to true, the rung has the logic status 1. If the expression evaluates to false, the rung has the logic status 0. The LESS THAN OR EQUAL operation is programmed as follows:
Fig. 6/68: Comparison: Less than or equal In this example the rung evaluates to logic 1 if timer word 5 has a value that is less than or equal to 332 (that is 332, 331 or less).
126
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Comparison: UNEQUAL Comparison operations are basic to every programmable logic controller. Comparisons allow processing of simple analogue values, multiple evaluation of counters, comparison of size etc. Festo controllers allow all comparison operations to be programmed in Ladder diagram: Equal Greater than Greater than or equal Less than Less than or equal UNEQUAL
Comparison operations compare positive whole numbers between 0 and 65,535. If a negative value (for example V-10) is entered, the positive whole binary number corresponding to the bit pattern (of V-10) is compared. This does not apply to the FPC 405 if processing has been switched previously to signed numbers (from 0 to 32,767) with CFM20. Comparison operations are always entered into a box in the conditional part.
127
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
The value of the upper operand is always compared to the value of the lower operand. If the expression evaluates to true, the rung has the logic status 1. If the expression evaluates to false, the rung has the logic status 0. The UNEQUAL operation is programmed as follows:
Rung No. 37 CW4 <> OW1 Execution
Fig. 6/69: Comparison: Unequal In this example the rung evaluates to logic 1 if counter word 4 has a value that is unequal to the value of output word 1.
128
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
BCD
to
BINARY
When connecting coding switches to PLCs or when 7-segment displays are used, inputs and outputs require BCD-coded decimal numbers. Festo controllers have commands that allow conversion to and from BCD: the BID command for binary into decimal (that is, into BCD code) and the DEB command from decimal into binary (that is, from BCD code). Please note that this operation always involves 16-bit words. An output word in BCD code consists of 4 digits each of which can be 0 -9. The DEB command has the following effect: 7667BCD
0 1 1 1 0 1 1 0 0 1 1 0 0 1 1 1
becomes 76672
0 0 0 1 1 1 0 1 1 1 1 1 0 0 1 1
The conversion commands BID and DEB can be used in a multi-bit box or in the Arithmetic/Logic Box.
129
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Fig. 6/70: Numbers: Convert BCD to binary The following programming has exactly the same effect:
Rung No. 41 Condition Arithm. &Logic
Boxes in Rung No. 41 Arithmetic/logic LOAD DEB TO IW4 R3 Contents of Input word 4 CONVERT DECIMAL (BCD) TO BINARY Write result to Register 3
Fig. 6/71: Numbers: Convert BCD to binary in arithmetic box The conversion commands allow conversion of the content of all multi-bit operands. The result can be written to any multi-bit operand except an input word. In online mode you cannot display numerical values in BCD code. A BCD code is evaluated in binary (as a binary decimal number, a signed decimal number or as a hexadecimal number depending on the display mode). 130
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Numbers: CONVERSION BINARY to BCD (BID command) When connecting coding switches to PLCs or when 7-segment displays are used, inputs and outputs require BCD-coded decimal numbers. Festo controllers have commands that allow conversion to and from BCD: the BID command for binary into decimal (that is, into BCD code) and the DEB command from decimal into binary (that is, from BCD code). Please note that this operation always involves 16-bit words. An output word in BCD code consists of 4 digits each of which can be 0 -9. The BID command has the following effect: 303112
0 1 1 1 0 1 1 0 0 1 1 0 0 1 1 1
The conversion commands BID and DEB can be used in a multi-bit box or in the Arithmetic/Logic Box.
131
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Fig. 6/72: Numbers: Convert digital to BCD The following programming has exactly the same effect:
Rung No. 39 Condition Arithm. &Logic
Boxes in Rung No. 39 Arithmetic/logic LOAD BID TO FW4 OW3 Contents of Flag word 4 CONVERT BINARY TO DECIMAL (BCD) Write result to Output word 3
Fig. 6/73: Numbers: Convert binary to BCD in arithmetic box The conversion commands allow conversion of the content of all multi-bit operands. The result can be written to any multi-bit operand except an input word. In online mode you cannot display numerical values in BCD code. A BCD code is evaluated in binary (as a binary decimal number, a signed decimal number or as a hexadecimal number depending on the display mode). 132
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Counting: ?
INTERROGATED
PRESELECT
ACHIEVED
The counters supplied in all Festo controllers are preselect counters. They consist of three elements: the counter preselect (nominal value), the counter word (actual value) and the counter bit (status of the counter). Normally a counter counts from its initial value to its end value. The one-bit operand C (counter) can be interrogated for logic 0 or logic 1. The counter is logic 0 as soon as the counter word and the counter preselect (actual and nominal value) are identical or the counter word (actual value) becomes 0 (decremental counter) or the counter is not started. C is logic 1 if after starting a counter by a set command or the counter box or by loading a value into the preselect the preselect has not been reached (incremental counter) or the actual value has not reached 0 (decremental counter).
133
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Interrogating whether the preselect has been reached (PRESELECT ACHIEVED) is therefore the same as interrogating whether the counter is inactive: Compared to an electromechanical preselect counter the counter module has a normally closed contact (not a normally open contact or changeover contact) to indicate that the preselect has been reached. Important: The condition of the rung shown is also fulfilled if the counter was not started.
Rung No. 44 C4 Execution
134
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Counting: INTERROGATED PRESELECT NOT ACHIEVED? The counters supplied in all Festo controllers are preselect counters. They consist of three elements: the counter preselect (nominal value), the counter word (actual value) and the counter bit (status of the counter). Normally a counter counts from its initial value to its end value. The one-bit operand C (counter) can be interrogated for logic 0 or logic 1. The counter is logic 0 as soon as the counter word and the counter preselect (actual and nominal value) are identical or the counter word (actual value) becomes 0 (decremental counter) or the counter is not started. C is logic 1 if after starting a counter by a set command or the counter box or by loading a value into the preselect the preselect has not been reached (incremental counter) or the actual value has not reached 0 (decremental counter).
135
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Interrogating whether the preselect has not been reached (PRESELECT NOT ACHIEVED) is the same as interrogating whether the counter is active: Compared to an electromechanical preselect counter the counter module has a normally closed contact (not a normally open contact or changeover contact) to indicate that the preselect has been reached.
Rung No. 45 C4 Execution
136
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Counting: DECREMENT Counters can count forwards or backwards: incrementing or decrementing. Both of these types are supported by Festo Ladder diagram. The counting commands can be used for any word except for inputs. The one-bit operand C can be used during counting. In reality, the counter word (actual value) is changed. The counter command changes the value of the operand by 1: +1 for incrementer, -1 for decrementer. The counting command is only executed when the logic status of the rung changes from 0 to 1, that is, only on a rising signal edge. This means that a Ladder diagram imitates the classical electromechanical counter which also counts the rising signal edge. In Festo Ladder diagram, the counting commands are coil commands, not boxes. In Ladder diagram, DECREMENT is programmed as follows: Fig. 6/76: Counting: Decrement
Rung No. 42 Condition C4 DEC
137
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Counting: INCREMENT Counters can count forwards or backwards: incrementing or decrementing. Both of these types are supported by Festo Ladder diagram. The counting commands can be used for any word except for inputs. The one-bit operand C can be used during counting. In reality, the counter word (actual value) is changed. The counter command changes the value of the operand by 1: +1 for incrementer, -1 for decrementer. The counting command is only executed when the logic status of the rung changes from 0 to 1, that is, only on a rising signal edge. This means that a Ladder diagram imitates the classical electromechanical counter which also counts the rising signal edge. In Festo Ladder diagram, the counting commands are coil commands, not boxes. In Ladder diagram, INCREMENT is programmed as follows: Fig. 6/77: Counting: Increment
Rung No. 43 Condition C5 INC
138
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Numbers: SET COUNTER With a preselect counter it must be possible to set a definite starting value. It must be established whether it is an incrementer (0 to preselect) or decrementer (preselect to 0). A counter must be set at least once during the program and can then be reset to initial value any number of times with a simple set command. The simplest case is the incremental counter. The nominal value is loaded into the preselect and the actual value set to 0. This can be done as follows:
Rung No. 46 Condition C4 7663 Counter
Fig. 6/78: Counting: Set incremental counter A simple set of command now sets the counter (actual value) to this initial value. A reset command stops the counter, setting it to logic 0.
139
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Resetting the actual value (counter word) to 0 again is done with the SET command in the executive part of the rung, whereby the counter bit C becomes logic 1 (the normally closed contact closes again).
Rung No. 43 Condition C4 S
Fig. 6/79 In the case of a decrementer, the counter word must be loaded with the initial value as it will count from this initial value to 0:
Rung No. 46 Condition 7663 TO CW4
Fig. 6/80: Counting: Set decrementer counter For more detailed examples, please see Chapter 9, "Programming of counters".
140
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Time: Start pulse timer Each processor module of a Festo controller has a number of timer modules. Each of these timer modules can be used as a pulse timer. In addition, the FPC 100B/AF, IPC, FEC and FPC 405 controllers enable the incorporation of a switch-on and switch-off delay similar to the classic time relay. A timer module consists of two elements: One element which is START TIMER. Another element which is interrogate timer. START TIMER is an executive function, that is, a box, which replaces a coil. Interrogate timer is a conditional function realized as a contact. STARTING of a pulse timer is programmed, for example, as follows:
Fig. 6/81: Time: Start pulse timer For details of timer programming see Chapter 8, "Programming of timers"
141
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
6. Operations in detail
Time: Interrogate pulse timer Each processor module of a Festo controller has a number of timer modules. Each of these timer modules can be used as a pulse timer. In addition, the FPC 100B/AF, IPC, FEC and FPC 405 controllers enable the incorporation of a switch-on and switch-off delay similar to the classic time relay. A timer module consists of two elements: One element which is start timer. Another element which is INTERROGATE TIMER. Start timer is an executive function, that is, a box, which replaces a coil. INTERROGATE TIMER is a conditional function realized as a contact. INTERROGATION of a pulse timer is programmed, for example, as follows:
Rung No. 48 T0 Execution
Fig. 6/82: Time: Pulse timer expired? For details of timer programming see Chapter 8, "Programming of timers"
142
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
7. Addressing operands
143
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
7. Addressing operands
Contents 7.1 ABSOLUTE AND SYMBOLIC ADDRESSES.....................................145 Absolute address ...............................145 Symbolic address...............................148 Mixing symbolic and absolute addresses............................150 INFORMATION CONTENT OF THE ABSOLUTE ADDRESS...........153
7.2
144
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
7. Addressing operands
When using a programmable logic controller, operands must be addressed. 7.1 ABSOLUTE AND SYMBOLIC ADDRESSES The FST software differentiates between absolute and symbolic addresses. Absolute address Absolute addresses are the designators required by the hardware and operating system of a PLC. Generally these are addresses that are incorporated by the manufacturer and used by the operator with the aid of LEDs, digits and selector switches. An absolute operand address comprises an operand identifier and an operand parameter.
Operand address
Operand identifier
Operand parameter
Fig. 7.1
145
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
7. Addressing operands
The absolute operand identifiers are automatically recognized by the FST software.
146
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
7. Addressing operands
Most operand identifiers require an additional operand parameter, a number, which allows the specific input to be addressed. A few operands do not allow an additional parameter:
FI E NOP Flag Initialization Error Null Operation
When using FST software, there must be no space between the operand identifiers and the appropriate parameter. The FST software automatically recognizes a valid absolute operand address and handles it appropriately.
147
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
7. Addressing operands
Symbolic address During programming it is often very difficult and tedious to remember all operand addresses. A whole range of operands are used in various different applications. Commentaries could also help to make a program easier to read and understand. This is the purpose of symbolic operands. These are the names given to operands by the user. In FST software symbolic operands may have up to 9 characters, no spaces, no period and a limited range of special characters. FST software symbolic operands therefore consist essentially of letters and numbers. Some examples of useful names for symbolic operands are: Start Stop Left Right Motor1on Motor1off GRIPCLOSE GRIPOPEN
148
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
7. Addressing operands
Naturally, a symbolic operand name must be unique within a project. Unique means also that a name given to a symbolic operand cannot be given as a jump label. Important: Symbolic operands must be clearly differentiated from absolute operands. The identifiers used for absolute operands (such as V, Y, F, etc.) must not be used as symbolic operand identifiers. For example, V12 or Y1 are absolute addresses. VALVE1, for example, would be permissible as a symbolic address.
149
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
7. Addressing operands
Mixing symbolic and absolute addresses FST software allows mixing of symbolic and absolute operand addresses. An allocation list into which you enter all the names can be created either before starting programming or during programming. You can also switch off the allocation list function during programming and program without allocation list entry. This can be useful if you want to program a routine that is to be valid for various machines for which the absolute addresses are not yet known. The following must always be taken into account however: As the FST software automatically recognizes absolute addresses, symbolic addresses must be selected that do not conflict with absolute addresses. A typical conflict in Ladder diagram is the use of the symbol "V" for a coil. As "V" is the identifier for the absolute operand Constant, "V12" is not interpreted by the FST software as a symbolic address but as an absolute address.
150
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
7. Addressing operands
Apart from this limitation, symbolic and absolute addresses can be mixed in FST programs. As an additional aid in Ladder diagram programming for FST software version 3.1 and later, both absolute and symbolic addresses are automatically shown where a symbolic address has been entered.
Rung No. 2 I0.0 S1 O0.0 I1.0 O0.0
Fig. 7/2: Symbolic and absolute operands In this example S1 was entered as a symbolic address for the latch, whereas in the output the absolute operand (O0.0) address has been entered.
151
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
7. Addressing operands
The allocation list lists all absolute and symbolic operands. The allocation list is sorted alphabetically by absolute operand identifier.
Operands of the allocation list Absolute O0.0 I0.0 I1.0 Symbolic H1 Start Stop Indicate machine started S1: Start pushbutton S2: Stop pushbutton Comment
Practice has shown that only specific symbolic addresses such as "Start" are useful. The symbolic address "SV1CCS3bk" for "Solenoid valve 1 for cylinder C at station 3 back" is just as inconclusive as the absolute address "O3.2".
152
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
7. Addressing operands
7.2 INFORMATION CONTENT OF THE ABSOLUTE ADDRESS The absolute address for Festo controllers always has the same structure of the operand parameter (number). The absolute address has the following structure:
Operand address
Operand identifier
Operand parameter
Fig. 7/3 Please note that the three parts of the operand parameter are separated by a period. Spaces are not permissible.
153
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
7. Addressing operands
Example Addressing flags: As the FPC 100B/AF, IPC and FEC have only one processor module in a system (singleprocessor system), it does not make sense to allocate a number for the processor module. Therefore, in these controllers flags can be addressed from F0.0 to Fn.n. On the other hand, the FPC 405 controller can manage several processor modules and processor modules can access the flag of other CCUs. For this reason addressing is from F0.0.0 to Fn.n.n. As these flags are one-bit operands, each bit is numbered individually. However, if you are using a flag word, it is incorrect to give a bit number. For this reason the flag words for FPC 100B/AF, IPC and FEC are addressed from FW0 to FWn. In the case of the FPC 405 controller, flag words are addressed from FW0.0 to FWn.n as 6 processor modules can be used in one system.
154
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
7. Addressing operands
The following table provides an overview of the absolute addresses possible with the various Festo controllers.
Operand Output (word) O OW Function module CFM Program module CMP Input (word) I I IW IW 2 Error (word) E EW Function unit FU FU Initialization flag FI Flag (word) F FW FI3
1
FPC 100B/AF
FEC
IPC
FPC 405
CFM0
CFM0 - CFM99
CFM0 - CFM99
CFM0 - CFM75
E EW
E EW
E EW
1, 2, 3 see following page * On FEC and IPC we are using logical addresses. Value range from 0 ... 255
155
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
7. Addressing operands
Operand Null operation NOP Program P Register R Timer T TOFF TON TP TW Counter C CP CW
FPC 100B/AF
FEC
IPC
FPC 405
NOP P0 R0 - R63
T0 - T31 TOFF0-TOFF31 TON0 - TON31 TP0 - TP31 TW0 - TW C0 - C15 CP0 - CP15 CW0 - CW
T0 - T255 TOFF0-TOFF255 TON0-TON255 TP0 - TP255 TW0 - TW255 C0 - C255 CP0 - CP255 CW0 - CW255
T0 - T255 TOFF0TOFF255 TON0TON255 TP0 - TP255 TW0 - TW255 C0 - C255 CP0 - CP255 CW0 - CW255
T0 - T63 TOFF0-TOFF63 TON0 - TON63 TP0 - TP63 TW0 - TW63 C0 - C63 CP0 - CP63 CW0 - CW63
1. These refer to the internal inputs of the interrupt processor module of the FPC 405. These inputs are local to one processor module and can be interrupted, have practically no input signal delay and can be addressed as I0 to I7. 2. If internal inputs of the interrupt processor module of the FPC 405 are to be processed as a word, the absolute address is IW. 3. Each FPC 405 program has local flags addressed from FI0 to FI7.
156
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
7. Addressing operands
Naturally this comparison table is not of great interest if you are programming other makes of controller. This table is more relevant if you wish to use programs written for one type of Festo controller on another type. Depending on which type of controller a program has been developed, it will be necessary to modify the operand parameters.
157
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
7. Addressing operands
Notes
158
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
8. Programming timers
159
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
8. Programming timers
Contents 8.1 GENERAL..........................................161 Timers ................................................161 Timer errors ......................................162 Shortest and longest time .............163 Components of a timer module ....164 Activating timer initialization .......164 TIMER TYPES ...................................165 Switch-on delay timer.....................166 Switch-off delay timer ....................167 Pulse timer ........................................168 EXAMPLES........................................169 Switch-on delay ...............................169 Programming with TON......................170 Programming with TOFF....................171 Programming with T............................171 Stairwell lighting .............................172 Programming with TON......................172 Programming with TOFF....................173 Programming with T............................174 Flashing lamp ..................................175 Programming with TON......................175 Programming with TOFF....................176 Programming with T............................177 EVALUATING THE INDIVIDUAL TIMER ELEMENTS...........................178 Programming flashing lamp with comparison .......................................180 160
Toolbar Menubar Print Contents Search Page
8.2
8.3
8.4
Toolbar
Menubar
Contents
Search
Page
8. Programming timers
8.1
GENERAL
Timers Timer modules are incorporated in all modern programmable logic controllers. All Festo controllers offer several timer modules for each processor module. Depending on the controller type, the number of timer modules range between 16 (FPC 100B/AF) and 64 (FPC 405) per processor module. The timer modules are counters which count an internal clock pulse. Timer modules of Festo controllers use a clock pulse of 10 milliseconds, that is, 0.01 seconds. This clock pulse is fully process-independent and is available as soon as the processor module is powered up. If a time is programmed, the preset counter is loaded with a number. The preset counter decrements by one for each clock pulse. When 0 is reached the time has expired. This time measurement technique works very well and is widely used. The same technique is used in modern quartz clocks and watches: a counter counts clock pulses from a quartz crystal. This is known as digital time measurement.
161
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
8. Programming timers
Timer errors Digital time measurement has a systematic minimum error of one clock pulse. This error results from the fact that the clock pulse is process-independent.
Counter expired
Counter = 1sec
Clock
Start signal
Fig. 8/1: Example of timer In the above example the timer counts each trailing edge of the clock pulse. As the input signal changes to logic 1 "sometime", this means that if 3 pulses are programmed, it counts approximately 2 pulses up to the end of the time period. This systematic error of event-driven time measurement has a maximum value of one clock pulse.
162
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
8. Programming timers
Shortest and longest time The shortest time that can be measured by a timer of this type is two clock pulses. In this case the maximum error is 50%. (If a time of one clock pulse were programmed, the possible error would be 100%. If that were permissible, programming of the timer would be redundant.) The longest time that can be measured with a timer of this type is dependent on the size of the counter. The counters in Festo controllers are all multi-bit operands of 16 bits. This type of counter can count up to a maximum of 65535. 65535 times 10 milliseconds is 655 seconds or 10 minutes and 55 seconds. A single timer module in a Festo controller can measure a time between 0.02 seconds and approx. 10 minutes. Longer time periods can be measured by cascading. Using this technique a single counter and a single timer module can be used to measure a period of up to 65,000 x 10 minutes.
163
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
8. Programming timers
Components of a timer module Every timer must be started and interrogated. In Ladder diagram, timers are started in a timer box, which replaces a coil. Interrogation of the time is undertaken by a contact, just as in the circuit diagram. Activating timer initialization Timer initialization is a box replacing a coil in the Ladder diagram, that is, in the executive part of the rung (just as a coil of a time relay is the load in a circuit diagram). The box is activated via a signal edge unless activated by a rung in which the contact is a NOP, i.e. the box operates once when the condition defined in the rung changes from 0 to 1. The condition can then remain logic 1 for any length of time the timer continues to run. If the condition switches from 1 to 0, the switch-on delay timer module (TON) switches to logic 0 and the switch-off delay (TOFF) timer begins time measurement.
164
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
8. Programming timers
8.2
TIMER TYPES Festo differentiates three different types of timer module: switch-on delay timer (TON), switch-off delay timer (TOFF) and pulse timer (T).
165
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
8. Programming timers
Switch-on delay timer This timer is permanently set as long as the condition is not fulfilled (0 level), that is, the timer word is constantly loaded into the timer preselect. The timer is active (TON=0). When the condition is fulfilled (level 1) it is not reset, but begins running. When the word is 0, the timer is inactive (TON=1). The timer only becomes active again (TON=0) when the condition is no longer fulfilled.
Status of the condition 1 0 t Status od switch-on delayed timer 1 0 Preselect t
The condition is fulfilled (see level 1) The timer remains active (TON=0) and running. After a short time the condition is no longer fulfilled. The timer preset is reloaded into the timer word. The timer remains active (TON=0).
Here the condition is filled repeatedly. The timer remains active (TON=0) and runs down from the start value of the timer preselect.
At this point the timer is expired. The timer word now has the value zero (TW=0) and the timer is inactive.
From this point the timer reset is permanently reloaded into the timer word. The timer is actice from this point (TE=0). It is restarted on the next level 1.
Toolbar
Menubar
Contents
Search
Page
8. Programming timers
Switch-off delay timer This timer reacts to level 1. This means that it is permanently set as long as the condition is fulfilled. The timer word is constantly loaded with the timer preselect; the timer is active (TOFF=1). When the condition is no longer fulfilled this timer is not reset, but begins to run. When the timer has expired (TW=0), it becomes inactive (TOFF=0). A timer does not become active again until the next level 1.
Status of the condition 1 0 t Status od switch-on delayed timer 1 0 Preselect t
The condition is fulfilled (see level 1). The timer becomes active (TOFF=1) and the timer is permanently loaded.with TP. After a short time the condition is no longer fulfilled and the timer runs down from the start value.
Here the condition is fulfilled repeatedly. The timer remains active (TOFF=1), as the timer word has not yet reached zero. Now the timer word is permanently loaded with the timer preselect.
At this point the condition is no longer fulfilled. The timer remains active and runs down again from the start value(Timer preselect).
At this point the timer is expired, i.e. the timer word is zero. The timer becomes inactive (TOFF=0). On the next level 1 the timer word is loaded permanently with the timer preselect. The timer becomes active again.
Toolbar
Menubar
Contents
Search
Page
8. Programming timers
Pulse timer This timer reacts to the rising edge of a condition. If the condition is fulfilled, the timer runs. As long as the condition is not fulfilled, the timer preselect is permanently loaded into the timer word.
Status of the condition 1 0 t Status od switch-on delayed timer 1 0 Preselect t
The condition is fulfilled(rising edge). The pulse timer starts (T=1) and at this moment TW=TP. The timer word is decremented from now. The timer runs down from the start value of the timer preselect.
Here the condition is fulfilled repeatedly. The pulse timer remains active (T=1). Here only the timer preset is reloaded into the timer word. The timer again runs down from the start value of the timer preselect.
After the last rising edge there are no more within the timer preselect that is, the timer is fully expired. The timer word is zero (TW=0) and the timer is expired. From here, the timer is always inactive.
168
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
8. Programming timers
8.3
EXAMPLES The following examples are typical of time delays in control technology. All examples are shown with three solutions: with switch-on delay timer, switch-off delay timer and pulse timer. Pick the solution that you like best.
Switch-on delay A lamp is to illuminate after a push button has been pressed for 5 seconds. The lamp is not to illuminate if the push button is not pressed.
169
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
8. Programming timers
Fig. 8/5: Switch-on delay programming with TON The circuit diagram for the same function with a time relay looks like this:
170
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
8. Programming timers
Sta rt switch-on dela y TOFF0 5s Timer Interrog ate switch-on dela y Lamp O0.1
Programming using TOFF Fig. 8/7: Start and interrogate switch-off delay timer
Rung No. 1 Start I0.0 Rung No. 2 I0.0 Start timer module T0 5s Timer Interrogate time, switch output T0 Lamp O0.1
Programming using T Fig. 8/8: Start timer module/interrogate time, switch output
171
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
8. Programming timers
Stairwell lighting A lamp is to illuminate as soon as the push button is pressed. When the push button is released, the lamp is to remain on for a further 5 seconds. Programming using TON
Rung No. 1 Start I0.1 Rung No. 2 TON0 Start switch-on delay TON0 5s Timer Interrogate switch-on delay Lamp O1.0
172
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
8. Programming timers
Start switch-on delay TOFF0 5s Timer Interrogate switch-on delay Lamp O1.0
Fig. 8/10: Start and interrogate switch-off delay timer The circuit diagram for the same function but with a timer relay looks like this:
Toolbar
Menubar
Contents
Search
Page
8. Programming timers
Programming using T
Rung No. 1 Start time Pushbutton I0.1
T0 5s Timer
TOFF0
174
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
8. Programming timers
Flashing lamp A lamp is to flash on and off at one second intervals as long as the push button is pressed. Programming using TON
Rung No. 1 Start I0.1 Start ON time as soon as OFF expired TON1 TON0 1s Timer
175
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
8. Programming timers
176
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
8. Programming timers
Programming using T
Rung No. 1 Switch on lamp T0 T0 5s Timer Lamp O1.0 S
Rung No. 2
177
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
8. Programming timers
8.4
EVALUATING THE INDIVIDUAL TIMER ELEMENTS All of the previous examples assume that the timer module consists of two elements: coil (to start the time) and contact (to interrogate the time). In practice however the structure of timer modules offers other possibilities. Each timer module consists of a timer word, timer preselect and timer bit. Timer word: The time is actually counted in the timer word. The timer word is the counter that is decremented by 1 for each 0.01 second clock pulse. The timer word is the only multi-bit operand in a Festo PLC that cannot be used freely as a multi-bit operand, as it is always counting the clock pulses. Timer preselect: The timer preselect is a word into which the initial value of the timer module is stored. It therefore represents the period of the timer module. The timer preselect is retentive in all Festo controllers, that is, the contents remain unchanged when the power is switched off (if the back-up battery is functioning). The timer preselect can be calculated, counted, converted etc. like any other multi-bit operand.
178
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
8. Programming timers
Timer bit: The timer bit can be interrogated for 1 and 0 like any one-bit operand, but can also be set and reset. Interrogation for logic 1 and logic 0 results in an answer as described under the pulse timers, switch-on delay timer and switch-off delay timer. SETTING to logic 1 causes restart of the timer using the period stored in the timer preselect. RESETTING to logic 0 stops the timer as if the time had expired. A good understanding of these individual elements enables very flexible and convenient timer programming. For example, the previous example of the flashing lamp could also be implemented with the aid of a comparative interrogation of the timer word:
179
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
8. Programming timers
Fig. 8/16: Start timer module/evaluate timer word Here the timer is set for 2 seconds and restarted as soon as it expires. The timer is interrogated to see if the timer word is "greater than 100", that is whether the timer word is counting from 200 to 100 (this takes exactly 1 second). As soon as the timer word reaches 100, the lamp is switched off. The possibility of directly accessing all elements of a timer module allows any time construction to be programmed. The only limitation is your imagination.
180
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
9. Programming counters
181
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
9. Programming counters
Contents 9.1 WHAT IS AN INCREMENTAL COUNTER?.......................................184 ELEMENTS OF THE COUNTER ....186 PROGRAMMING COUNTERS........191 Programming incremental counters ............................................191 Programming decremental counters ............................................193 Programming a car parking system................................................195
9.2 9.3
182
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
9. Programming counters
Festo PLCs can all be programmed with incremental or decremental counters in Ladder diagram. In addition, each element of the counter module can be accessed directly. Similarly, all word operands with the exception of input words and the timer word can be used for counting. These are then not incremental counters but event counters whose value is compared to other values.
183
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
9. Programming counters
9.1
WHAT IS AN INCREMENTAL COUNTER? Normally we speak of an incremental counter when we are using a counter that: Counts pulses and stores the result in its own memory (actual value). Offers the possibility of setting the actual value to an initial value (reset input). Has its own memory for a preselect (nominal value). Has a result output that can be interrogated to see whether the actual value has reached the nominal value.
184
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
9. Programming counters
In practice this could be: A machining centre which is to manufacture 14,000 screws of a particular type. The preselect (nominal value) is set to 14,000. At the beginning of the operation, the operator (or an automatic mechanism) sets the counter to 0. The counter is reset. During the operation the counter is incremented by 1 for each screw. The result is shown on the display. The counter is reset. The incremental counter shows the number of parts manufactured. As soon as 14,000 screws have been manufactured, the machine is stopped. A new type, possibly with a new nominal value is entered. A reaction takes place when nominal and actual values are equal.
185
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
9. Programming counters
9.2
ELEMENTS OF THE COUNTER In order to allow flexibility in counter programming, Ladder diagram for a Festo PLC offers the following operands for counters: The counter word is the operand in which the actual value is stored and is changed with each counting pulse. The counter word must be reset at the beginning of the counting operation. Counter words are retentive in all Festo PLCs (as long as the buffer battery is working). The counter preselect is the operand in which the nominal value is stored. The counter bit returns: Logic 0: The counter has expired or reached the preselect or reached the value 0. Logic 1: The counter is still counting, the preselect has not yet been reached. Compared to an electromechanical counter, the counter bit is a normally closed contact (not a normally open contact or a changeover contact), with which the count can be output.
186
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
9. Programming counters
The counter bit is retentive in all Festo PLCs (as long as the back-up battery is working). This means that all counts are retained even in the case of a power failure. The following operations facilitate use of the operands: Counter initialization is called as a box instead of a coil. The counter number is entered as the operand and the number to which the counter is to count. This number is automatically loaded into the counter preselect (nominal value), the counter bit is set to logic 1 (the normally closed contact remains closed).
Condition
Fig. 9/1: Counter initialization Counter set is a simple coil command. When this command is executed, the counter word (actual value) is set to 0 and the counter bit to logic 1 (the counter is active).
Co ndition Co unter 0 C0 S
187
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
9. Programming counters
Counter reset like set is a simple coil command. If this command is executed, the counter bit has the value logic 0.
Con dition Co un ter 0 C0 R
Fig. 9/3: Resetting a counter Load counter word is a coil operation (in the executive part). The load counter word command loads the counter word (actual value) with a number and sets the counter bit to logic 1 (the normally closed contact opens). The counter bit reverts to logic 0 (the normally closed contact closes), when 0 is reached
Co nditio n
V3 00 TO CW0
188
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
9. Programming counters
The counting operation is a typical executive operation and is entered in the coil of a Ladder diagram. When using INC (increment) the counter is incremented by 1 and when using DEC (decrement) the counter is decremented by 1. Important: Only the signal edge is counted, not the continuous signal.
Signal I0.3 Counter 0 C0 INC
Fig. 9/5: Counting Interrogating the counter for 1 is a contact operation. This condition is fulfilled (the normally closed contact is closed) when the counter is still counting, i.e. the preselect has not yet been reached.
C ounter 0 C0 Lamp O0.1
189
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
9. Programming counters
Interrogating a counter for 0 is the opposite contact operation. The condition is fulfilled (the normally closed contact is opened) if the preselect has been reached, i.e. the counter is no longer counting or if the counter has reached the value 0.
C ounter 0 C0 Lamp O0.1
Fig. 9/7: Interrogating a counter for logic 0 Compare counter word or counter preselect are boxes which replace a contact. The actual value (counter word) or the nominal value (counter preselect) is compared with a number (constant) or with another word operand, inC _Word 0 CW 0 >= V15 Lamp O0.1
cluding other counter words. Fig. 9/8: Compare counter word or counter preselect
190
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
9. Programming counters
9.3
PROGRAMMING COUNTERS
Programming incremental counters The incremental counter is probably the most commonly used type of counter. The following program counts the signals at input I0.3 (symbolic name: Signal). After 10 signals, output O0.1 (symbolic name: Lamp) is switched on. A signal at input I0.1 (symbolic name: Reset) resets the current value of the counter to 0 and sets the counter bit back to logic 1.
Rung No. 1 FI Counter preset to 15 in first cycle Counter C0 10 Counter Counter word to 0 Counter0 C0 S Increment Counter0 C0 CP Evaluate counter status Lamp O0.1
Rung No. 2 Reset I0.1 Rung No. 3 Signal I0.3 Rung No. 4 Counter0 C0
191
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
9. Programming counters
Note: The first rung initializes the counter immediately after power-up (with FI). This is necessary because the interrogation in rung 4 whether the counter is "inactive" would otherwise be fulfilled immediately after power-up (for the FPC 405). The counter would only be set to logic 1 (and therefore the lamp out) after the first reset command (rung 2). The circuit diagram for an electromechanical counter for the same function as the above program looks like this:
192
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
9. Programming counters
Programming decremental counters In the case of the decremental counter, the actual value (counter word) must not be set to 0, but must start at the desired number. The counter bit then becomes logic 0 as soon as 0
Rung No. 1 FI start co unter in first cycle V10 TO C_W ord 0 set co unter word (Ist) to 10 V 10 TO C_ Wo rd0 Co untin g Co un ter0 C0 DE C Eva lu ate cou nte r status La mp O0.1
193
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
9. Programming counters
Note: As the counter is a decremental counter, it cannot be reset by simply using the set command. A box (the Arithmetic/Logic Box can also be used) must be used to load the start value into the counter word. Furthermore, in this example the initialization flag ensures that the counter is active immediately after power-up of the controller. Otherwise the condition in rung 4 would be met immediately after power-up, and the lamp would be switched on.
194
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
9. Programming counters
Programming a car parking system The car park is a classic example of this type of counter: A car park has space for 10 cars. In front of the car park is a traffic light. The traffic light shows green as long as there is still space in the car park (and the counting system is working). The traffic light shows red as soon as the car park is full.
Rung No. 1 I0 .1 Rung No. 2 E nte r I0 .5 Rung No. 3 Set I0.7 Rung No. 4 Counte r 0 CW 0 V1 0 Switch traffic lig ht CW 0 V0 Green O0.2 Red O0 .3 Ca r exitin g Co un ter0 C0 DEC Ca r entering C ounte r0 C0 IN C Se t Cou nte r word to 0 Coun te r0 C0 10 Coun te r
195
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
9. Programming counters
Please note: The only purpose of rung 1 is to set the counter to 0 if necessary (for example, if the counter still contains a count from a test, the controller is brand-new or the battery has just been replaced). As only counting commands and a comparison are used there is no reason to use a counter here. One could just as well use a flag word, a register, an output word etc. (anything except an input word).
196
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
197
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
198
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
In the Festo controllers registers are 16-bit word operands. Their contents can therefore be between 0 and 65,535 (unsigned), between 0 and 32,767 (signed), between $0 and $FFFF (hexadecimal) or between 0 and 9999 (BCD). Arithmetic operators (+, -, /, *) assume unsigned numbers unless the FPC 405 is switched to signed numbers with CFM20. In the case of comparison operations (=, >, >=, <, <=, <>) unsigned numbers are assumed unless the FPC 405 is switched to signed numbers with CFM20. All bit-manipulating operations (ROL, ROR, SHL, SHR, INV, CPL) manipulate all 16 bits of the registers. All bit-comparison operations (AND, OR, EXOR) compare all 16 bits. A single bit cannot be accessed directly. If, for example, the 6th bit of a register is to be set to logic 1 it must either be OR masked or the register must be loaded into a flag word, the bit manipulated and the contents of the flag word reloaded into the register.
199
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
All registers of Festo controllers (except for the FEC) are retentive, as long as the back-up battery is functioning. For the FEC only registers 0 ... 127 are retentive. Register 63 of the FPC 100B/AF cannot be used for general register applications. This register serves only for setting the input signal delay for the input of the FPC 100B/AF (see Appendix B.8).
200
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
201
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
202
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
11.1 FLAG BIT Flags fulfill the same function as the auxiliary relay in the circuit diagram: a relay that is not switched externally but only fulfills a function within the controller. Flags can be used as outputs, except that outputs have an external connection and an external LED, where as flags are only present and visible within the system. All operations that can be used on outputs can also be used on flags, for example assignment, setting, resetting, interrogating etc. Flags are differentiated from outputs by the following points: Every Festo controller has retentive (nonvolatile) flags whose status is retained after power loss or power failure (assuming the back-up battery is functioning). The status of the flag remains unchanged even if the appropriate processor group is switched to stop. Outputs, on the other hand, are set to logic 0 (depending on the controller type).
203
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Like outputs, flags are organized as words with 16 bits each. For this reason an absolute flag address always consists of an indication of the flag word and the flag bits, for example:
F12 . 3
Bit no. 3 (this is the fourth bit!) Use a period to separate word and bit. Under no circumstances use a space! Flag word no. 12 Operand identifier is F for Flag. No space allowed between F and the number of the flag word!
Fig. 11/1
204
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
In the case of the multiprocessor controller FPC 405 the processor module can be indicated in addition to the flag word. Each program in each processor module can access the global flag of other processor modules by including the processor module number in the absolute address, for example:
F3 . 0 . 14
Bit no. 14 of the inicated word (this is the 15th bit) Use a period to separate word and bit. Under no circumstances use a space! Flag word no. 0 Use a period to separate processor module and word. Under no circumstances use a space CCU no. 3 (this is the 4th CCU) Operand identifier is F for Flag. No space may appeare between the F and the following parameters.
Fig. 11/2
205
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
In the case of the FPC 405 there are an additional 8 flags for local use within the processor module. These flags are only available for the local program and are always set to logic 0 when the program is started. The flags are addressed as FI0 to FI7. FI0 to FI5 are freely usable within the program. FI6 becomes logic 1 if a mathematical operation using CFM20 results in an overflow. FI7 is used for the storage of a bit shifted out in a SHIFT operation. It can be interrogated. As this flag is a local flag it is not entered in the allocation list. The allocation list belongs to the project and can only manage local operands that belong to a processor module.
206
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
11.2 FLAG WORD As flags are organized in words of 16 bits, these words can also be addressed as words. In the absolute address the bit number and the period before it are not required. The operand identifier is FW for flag word, for example:
FW4
Flag word no. 4 (this is the 5th word)
Operand identifier FW for Flag word No space may occur between FW and the parameter.
Fig. 11/3
207
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Like flag bits, flag words of remote processor modules can be manipulated when using a multi-processor system (FPC 405). In this case the CCU number is added to the absolute address, for example:
FW 4 . 15
This means Flag word no. 15 (this is the 16th word!) A period (not a space) separates word number and CCU number (not for IPC / FEC) Number of the processor module (not for IPC or FEC) FW for Flag word No space may appear between FW and the parameters (4.15).
Fig. 11/4 Flag words can be manipulated with all operations used for words: Interrogation operations are comparison operations (=, >, >=, <, <=, <>); LOAD TO is an example of a wordmanipulating operation; all arithmetic operations (+, -, *, /); the bit-manipulating operations AND, OR, EXOR, CPL, INV; and the counter operations INC and DEC (increment and decrement).
208
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
209
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Contents A.1 SEQUENCE PROGRAMS ...............211 Sequence program with existing flag chain, with storing commands ..........................................214 Sequence program with existing flag chain and latching........................215 Sequence program with resetting sequence ............................................217 Sequence program with counter........219 MEASURING THE CYCLE TIME ....220 Number of cycles every 3 seconds ..221 Absolute duration of a cycle in 0.1 ms .............................................223 Measuring reaction time ....................225 Measurement and display of the absolute reaction time........................227 Display of the longest cycle time .......229 STRUCTURED PROGRAMMING IN LADDER DIAGRAM ....................233
A.2
A.3
210
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
A.1
SEQUENCE PROGRAMS Research shows that sequence programs occur in 80% of all automation systems. In most cases where programmable logic controllers are used a sequence program is likely to be at the heart of the system. Using a simple and very well known example it will be demonstrated how a sequence program can be programmed using Ladder diagram. A "bedside lamp controller" is to be programmed. Press the pushbutton lamp on; press the button again lamp off. In your bedside lamp the problem is probably solved mechanically. The switch has a mechanism that causes the current to be switched on and off. The electrician knows the problem of the hall way light. There a latching relay is used which also solves the problem mechanically. What does the diagram of the bedside lamp control look like?
211
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
The function diagram in accordance with DIN 40719 part 6 has the following structure:
P ushb utto n 1 L amp off P ushb utto n relea se d? 2 C on tinu e P ushb utto n 3 L amp off P ushb utto n relea se d? 4 Jump S Co ntinu e in first step S La mp o n S Co ntinu e S La mp o n
Fig. A/1: Function diagram to DIN 40719 There are several ways in which a sequence program can be programmed in Ladder diagram. Here, four systematic methods will be presented. The aim is the systematic development of a sequence program, not the shortest, most elegant or most popular means. If you don't have your own "preferred method", select the one that you like best. If you have to write a sequence program, write the basic structure, copy the rungs with which the steps are to be constructed, for as many steps as required and complete the rest. That's it!
212
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
You should consider the counter method only if you have to program longer sequences. It may be that your controller has too few flags available. The FPC 100, for example, has 256 flags available. If your sequence has 150 steps, the number of flags required could be a problem. Please note that in all examples the programs are such that after power-up the controller begins at the first step (even after a power failure). In order to ensure this even when retentive flags or a retentive counter word are used, the first step in the rung is always a reset with the aid of the initialization flag FI. Please also note that the following program examples often use operand designations. The absolute designations are automatically added so that the symbolic designators act as a type of commentary in the program.
213
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Sequence program with existing flag chain, with storing commands This programming method assumes that each step requires a flag. An additional flag is switched on (this is the reason for the name "existing flag chain", as in the last step all flags are "existing"). The outputs are storing and directly connected to the appropriate flags.
Rung No. 1 FI Reset all flags V0 TO FW3 First step Lamp O1.0 S Step 1 F3.1 S
Pushbutton I0.1
Step 1 F3.1 S
Third step Step 3 F3.3 Pushbutton I0.1 Lamp O1.0 R Step 3 F3.3 S
Pushbutton I0.1
Toolbar
Menubar
Contents
Search
Page
Sequence program with existing flag chain and latching This programming method is similar to the existing flag chain with storing commands. The difference is that no storing commands are used but latching. This method requires the separation of the step chain from the switching of outputs. The entire Ladder diagram is thus separated into a "Control part" and a "Power part". The control part only contains the step chain, the outputs are switched in the power part.
215
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
FI
Rung No. 2 Step1 F3.1 Step1 F3.1 Rung No. 3 Step 2 F3.2 Step 2 F3.2 Rung No. 4 Step 3 F3.3 Step 3 F3.3 Rung No. 5 Step 4 F3.4
Pushbutton I0.1
Pushbutton I0.1
Pushbutton I0.1
Pushbutton I0.1
216
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Sequence program with resetting sequence The resetting sequence is very popular in relay technology and has therefore been adopted by many electricians in Ladder diagram programming. Here too the "Control part" and "Power part" are separated (not entirely necessary) and (in this programming example) programming is done entirely with latching. Please note in the case of the resetting sequence that at the start of the sequence the last step must be set (if necessary a step without action). For this reason the initialization flag is used in the first rung to load value 16 into the flag word. This sets flag F3.4.
217
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Rung No. 1 FI
Reset all flags V0 TO FW3 First step Step 2 F3.2 Step 1 F3.1
Rung No. 2 Step 4 F3.4 Step 1 F3.1 Rung No. 3 Step 1 F3.1 Step 2 F3.2
Pushbutton I0.1
Pushbutton I0.1
Rung No. 4 Third step Step 2 Pushbutton Step 4 F3.4 F3.2 I0.1 Step 3 F3.3 Rung No. 5 Step 3 F3.4 Step 4 F3.4 Rung No. 6 Step 1 F3.1 Lamp O1.0 Lamp switching Step 3 F3.3 Last step Step 1 F3.3
Step 3 F3.3
Pushbutton I0.1
Step 4 F3.4
Lamp O1.0
Toolbar
Menubar
Contents
Search
Page
Sequence program with counter Programming of a sequence with a counter is totally unknown in relay technology as a counter cannot be interrogated for its current status. On the other hand the counter method allows significantly more flexible programming particularly jumps can be very elegantly solved.
Rung No. 1 FI Rung No. 2 V1 First S tep Step z CW 0 CP La mp O1.0 S St ep z CW 0 CP C ounter to 1 V1 TO Step z Pu shb utto n I0 .1
Se co nd Ste p
Pu sh bu tton I0.1
CW 0 Step z Rung No. 4 T hird Step Pushbutton V3 I0 .1 CW 0 Step z Rung No. 5 V4 CW 0 End of La dder d iag ram
L ast S te p
Step z CW 0 CP La mp CW 0 R V1 TO Step z
219
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
A.2
MEASURING THE CYCLE TIME It is often interesting to know the cycle time of a processor module. Although Festo gives data on the time requirement of individual commands for each controller type, it is almost impossible to calculate the cycle time of a particular program. It is a lot easier to write a small program in which the cycle time is written to a register. With the aid of the on-line function this register can then be examined. There are only two restrictions that need to be taken into account. On the one hand the measuring program also has a cycle time. The cycle time is easy to evaluate by doubling the measuring program and comparing the new cycle time with the previous cycle time. The cycle time increase caused by the measuring programs are given. Deduct the time required for the measuring program from the measured result. Secondly, data transfer for online mode also adds to the cycle time. But you need online mode to read the result of the cycle time measurement. This is also the reason why you can set the dynamic display in online mode to slower or faster. By changing this display speed you can clearly see the influence on the cycle time. Select a slow display speed when displaying dynamically, otherwise the values will be totally unrealistic.
220
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Number of cycles every 3 seconds This program counts how many cycles are executed within 3 seconds. The result is stored in register 1 and is updated every 3 seconds.
Rung No. 1 Rese t of Re gisters a nd Timers Rung No. 2 Cycle counting Rung No. 3 Eva lu ate resu lt Rung No. 1 FI R eset of Reg iste rs an d Timers Arithm. & Logic
T0 3s Timer
Boxe s in Ru ng No. 1 A rith me tic/logic L OAD TO TO V0 R0 R1 S et to 0 T he cou nte r register T he display register
221
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Rung No. 3 T0
Boxes in Ru ng No. 3 Arithmetic/lo gic L OAD TO L OAD TO R0 R1 V0 R0 Total nu mber a fter 3 secon ds Display in d isplay re gister Re set to 0 o f the cou nter register
Fig. A/7: Ladder diagram continued This measurement program increases the actual cycle time for each processor module as follows: FPC 100B/AF IPC FEC FPC 405 by 0.1 ms by *** ms by *** ms by 0.15 ms
222
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Absolute duration of a cycle in 0.1 ms As in the first program, this program counts how many cycles are executed in 3 seconds. This value is then converted into the absolute time per cycle. The value stored in register 2 must be multiplied by 0.1 ms in order to find the duration of an individual cycle.
Rung No. 1 Rese t of Re gisters a nd Timers Rung No. 2 Cycle counting Rung No. 3 Eva lu ate resu lt Rung No. 1 FI R eset of Reg iste rs an d Timers Arithm. & Logic
T0 3s Timer
Boxe s in Ru ng No. 1 A rith me tic/logic L OAD TO TO V0 R0 R1 S et to 0 T he cou nte r register T he display register
223
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Rung No. 3 T0
Boxes in Ru ng No. 3 Arithmetic/log ic L OAD / TO L OAD TO V300 00 R0 R1 V0 R0 30 .00 0 (that is 3 secon ds) Numbe r of cycle a fter 3 seco nds Disp la y cycle time p er 0.1 m s Reset to 0 An d restart counting
Fig. A/9: Ladder diagram continued This measuring program increases the actual cycle time of a processor module by approx. 1.0 ms.
224
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Measuring reaction time Often the actual reaction time is of much greater interest than the cycle time. This is because the reaction time of a PLC includes the input signal delay. As a result, the reaction time is the time that expires between the presence of a signal at an input and of the appropriate signal at an output. The input signal is delayed by the input signal delay. Depending on the controller type, updating of the process image may be required in addition. Only then can the program with the cycle time of a processor module take affect. For this reason the following two programs do not use a flag for the edge to be counted but an input signal that is taken from the output of the controller.
Rung No. 1 Rung No. 2 Rung No. 3 Rung No. 4 Rung No. 1 FI Reset registers / start timer Interrogate input / switch output Counting Evaluate counter after 3 sec. Reset Arithm. & Logic
T0 3s Timer
Boxes in Rung No. 1 Arithmetic/logic LOAD TO TO V0 R0 R1 Set to 0 The counter register The display register
Toolbar
Menubar
Contents
Search
Page
Boxe s in Ru ng No. 4 Arithmetic/log ic L OAD TO L OAD TO R0 R1 V0 R0 Actu al count Disp la y cycles pe r 3 se c. Numbe r 0 Se t cou nte r register to 0
Fig. A/11: Ladder diagram continued This measuring program increases the actual cycle time of a processor module as follows: FPC 100B/AF by 0.2 ms IPC *** FEC *** FPC 405 negligible compared to input signal delay
226
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Measurement and display of the absolute reaction time This program measures the reaction time in the same way as the previous program. The result is converted into the absolute time for a reaction cycle, whereby the value in register 2 must be multiplied by 0.1 ms.
Rung Rung Rung Rung No. No. No. No. 1 2 3 4 Rese t re gisters / start timer Interrogate inpu t / sw itch ou tpu t Counting Eva lu ate counter after 3 sec. R eset Arithm. & Logic
Rung No. 1 FI
T0 3s Timer
Boxe s in Ru ng No. 1 A rith me tic/logic L OAD TO TO V0 R0 R1 S et to 0 Re gister 0 (actual coun te r) Re gister 1 (display cycles p er 3 sec.)
227
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Ge nerate flag ed ge for co untin g O0.7 Co untin g I0.7 Evalua te co unter a fter 3 se c A rithm. & L ogic T0 S R0 CP
Boxe s in Ru ng No. 4 A rith me tic/logic L OAD TO L OAD TO L OAD / TO R0 R1 V0 R0 V300 00 R1 R2 Actu al count Disp la y cycles pe r 3 se c. Numbe r 0 Se t cou nte r register to 0 30.00 0 Divide d b y R1 Cycle tim e in 0.1 ms
228
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
This measurement program increases the actual cycle time of a processor module as follows: FPC 100B/AF by 0.2 ms IPC *** FEC *** FPC 405 negligible compared to input signal delay Display of the longest cycle time In many cases the cycle time varies considerably. For example if jump commands or modules are used in a program, if parallel programming of the FPC 405 is used or if the interrupt capability of the FPC 405 is used or if a BASIC program is used for this controller for process visualization or operator guidance, the cycle time can fluctuate considerably. In order to be able to measure the cycle time properly in such cases a register is used for the maximum value. This allows cycle time measurement to run in the background while the machine executes all possible program variants. Later the longest cycle time can be read from the registers.
229
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
1 2 3 4
Rese t re gisters and timer Counting cycles Eva lu ate resu lt Eva lu ate resu lt R eset Arithm. & Logic
Rung No. 1 FI
T0 3s Timer
Boxe s in Ru ng No. 1 A rith me tic/logic L OAD TO L OAD TO V0 R0 V100 00 R1 Se t to 0 co unt reg iste r Th eoretical max. value Memo ry for sma llest value
230
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Rung No . 2 NOP
Run g No. 3 T0
Boxe s in Run g No. 3 Arithme tic / logic L OAD TO L OAD TO R0 R1 V0 R0 Current n umbe r of cycles Smallest numbe r of cycles Numb er 0 Start cou ntin g aga in
231
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Rung No . 4 T0
Boxe s in Ru ng No. 4 Arith me tic / logic LOAD TO V0 R0 Value 0 Start cou ntin g aga in
Fig. A/16: Ladder diagram continued 2 Use of this measurement program increases the actual cycle time for a processor module as follows: FPC 100B/AF IPC FEC FPC 405 by 0.24 ms by *** ms by *** ms by 0.30 ms
232
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
A.3
STRUCTURED PROGRAMMING IN LADDER DIAGRAM Commonly used control programs for automation technology are very similar in their structure. For this reason a structure for a Ladder diagram program is shown here. This structure is not standardized and is not particularly elegant but helps to make a program easy to write and read. For this reason we suggest: 1st Rung
Run g No. 1 FI
Rese t at sta rt
Fig. A/17: Ladder diagram This rung carries out all settings that need to be carried out once when the controller is powered up. Often this means that retentive flags, counters etc. need to be reset, and an output with a ready lamp has to be switched on and that possibly a READY MESSAGE needs to be displayed on a text display.
233
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
2nd Rung
Rung No . 2 EMERGENCY OFF
Boxes in Run g N o. 2
Fig. A/18: Ladder diagram continued 1 The first entry here is the flag "Begin". This serves as a jump destination from any point in the program. The second entry is interrogation of the EMERGENCY OFF, the most important error monitoring function. EMERGENCY OFF normally requires (in addition to hardware monitoring of EMERGENCY OFF in accordance with DIN VDE 57 113 part 1, IEC 204-1 or EN 60204 part 1) switching off of nearly all outputs, possibly switching on of a display lamp for EMERGENCY OFF etc. In addition, in this example, the program jumps back to "Begin". Nothing else needs to be done in the event of an EMERGENCY OFF.
234
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
AUTO O1.1
MANUAL
Fig. A/19: Ladder diagram continued 2 This part of the program allows selection of the automatic/manual mode. If necessary, further error messages are monitored here. It is important that operating mode selection takes place in such a way that control can pass immediately to the rung containing the selected operating mode.
235
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Group: automatics
Rung No . 5 F irst run g o f AUTO mod e
V1 TO Step z
Fig. A/20: Ladder diagram continued 3 Automatic operation is programmed in this rung group. This is normally a sequence program, for which reason a step counter is used. At the end of this section, control returns to the "Begin" flag.
236
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Group: manual
Rung No . 7 Man ual mo de I1 .1 Run g No. 8 NOP Last ru ng of MANUAL mod e CFM0 Mod ule BEGIN F irst run g o f MANUAL mode Motor O0 .1
Boxes in Rung No 8
Fig. A/21: Ladder diagram continued 4 This rung group has a similar structure to "automatic", except that there is no step counter as the manual mode is normally implemented as a parallel logic program. The last rung of this group also passes control back to the "Begin" flag. The more clearly a program is structured, the easier it is to find and eliminate errors. Only a well structured program is a help when searching for a defective sensor, a defective valve or a sticking relay.
237
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Notes
238
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
239
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Contents B.1 PROCESS IMAGE.............................241 Safety routines ...................................242 Cycle time ...........................................243 MULTITASKING................................244 MULTIPROCESSING........................246 INTERRUPT CAPABILITY...............247 INTERNAL INPUTS AND FLAGS...248 Internal inputs of the FPC 405...........248 FPC 405 local flags............................249 Local and global allocation list ...........250 SERIAL DATA PORT.......................251 Hardware ............................................251 Active/passive interface ....................252 BEHAVIOUR AFTER BATTERY FAILURE ............................................253 INPUT SIGNAL DELAY....................255 FPC 100B/AF .....................................255 FPC 405 .............................................257 IPC ......................................................257 FEC.....................................................257
B.6
B.7
B.8
240
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
This appendix examines the differences between the controllers offered by Festo. The list does not claim to be complete and is not any strict order. Nonetheless it should provide a useful source of information. B.1 PROCESS IMAGE The FPC 100B/AF, IPC and FEC controllers work with a process image of the inputs and outputs. The FPC 405 controller writes and reads directly to the appropriate input or output in each program line. In practice this means that before processing the entire Ladder diagram, the FPC 100B/AF reads the status of all inputs into a memory area and the status of all outputs is read from a memory area to outputs. This updating of the process image also occurs after each backward jump, so that there are no programs in which the process image is not updated. If updating of a process image is required at a particular point in the program, a backward jump is inserted.
241
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Safety routines With the FPC 100B/AF, IPC and FEC (that is, with process image) an output is not switched directly as a result of a rung but only prior to the next execution of the program. For this reason it is both possible and useful to write monitoring routines at the end of the program which eliminate problems caused by a programming error earlier in the program. It is normal practice to first program rungs that prevent "the worst" from happening: a cylinder may only extend if another one has already retracted; a motor may only be switche on if it is disengaged; the direction of rotation of a motor must be unambiguous etc. All further rungs are written before these last monitoring rungs. If a similar safety routine is to be used with a multiprocessor system (FPC 405), flags are programmed first instead of outputs. At the end of the program the flags are then transferred to the outputs taking the safety routines into account.
242
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Cycle time The example programs show several programs that measure cycle time. Where these do not measure reaction time but the pure cycle time, the time taken to execute a complete program is measured. In the case of controllers with process image the reaction time is calculated from the input signal delay, the (comparatively short) output signal delay and twice the cycle time. In the case of controllers without process image the single cycle time is sufficient. The reason for this is that the change of a signal at an input can take place immediately after updating of the process image. The following cycle works with the old logic status. The process image is then updated (after one complet cycle) and the program continues executing with the new logic status and writes the new update to the output during the next cycle (the second cycle is complete).
243
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
B.2
MULTITASKING The FPC 100B/AF, FEC, IPC and FPC 405 can store several programs (with different program numbers) in their program memory. Of these stored programs, several programs can be identified as a task and processed simultaneously (quasi-parallel processing). The controllers support multitasking as follows: FPC 100B/AF: 1program and 8 program modules IPC: up to 64 programs FEC: up to 64 programs FPC 405: up to 64 programs can be stored. Of these up to 8 Ladder diagram programs can be processed simultaneously. If only 1 Ladder diagram program is processed, an additional 48 Statement list programs can be processed. For further combinations see the FPC 405 manual.
244
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
All Festo controllers can process program modules, that is subroutines, created by the user. The controllers support program modules as follows: FPC 100B/AF: 8 modules IPC: 100 modules FEC: 100 modules FPC 405: 32 modules (can only be written in Assembler if they are to be called from a Ladder diagram program) All processor modules contain function modules provided by Festo as follows: FPC 100B/AF: IPC: FEC: FPC 405: CMP0 - CMP7 CMP0 - CMP99 CMP0 - CMP99 CMP0 - CMP31
245
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
B.3
MULTIPROCESSING The FPC 405 allows several processor modules to work together via a system bus. Communication takes place with the aid of flags. If a program is to be imported from an FPC 405 into FPC 100,FEC or IPC, absolute adddressing of flags must be adapted accordingly (in addition to other changes). This is because in the FPC 405 the flag addresses contain the processor module number. Each processor module can access the global inputs and outputs and global flags via the system bus. The Festo multiprocessor operating system manages bus access to the processor modules. If two processor modules access the bus simultaneously, the operating system allows access in the order of priority: processor module number 0 (highest priority) to processor module number 5 (lowest priority). Processor module 0 also tests the system bus on power-up. For this reason, each configuration must contain a CCU number 0. The remaining CCUs can then each be given a unique number in the range of 1 to 5.
246
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
B.4
INTERRUPT CAPABILITY In order to allow rapid reaction to external signals, Festo controllers have inputs that allow an interrupt program to be called. This reaction is considerably faster than would be possible with other inputs and normal program execution. The controllers have interrupt inputs as follows: FPC 100B/AF: 1 input with max. 3 kHz IPC: Input module FEC: 2 inputs with max. 4 kHz FPC 405: 8 interrupt inputs on the interrupt processor module
247
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
B.5
INTERNAL INPUTS AND FLAGS The FPC 405 has so-called internal inputs and internal flags.
Internal inputs of the FPC 405 The interrupt processor module of the FPC 405 has 8 inputs directly on the CCU module. These 8 inputs are called internal inputs, as they are only available to the local processor module. In contrast to these internal inputs, all other inputs can be addressed by any processor module (if they are working together via the system bus). The internal inputs are fast inputs with an input signal delay of approx. 60 s (in contrast to approx. 5 ms for "normal" inputs). The absolute addresses of these inputs are I0 to I7 or IW. When using these 8 inputs for "normal' purposes, take into account that there is practically no input signal delay available. For this reason, these inputs must be connected via a shielded cable or an input signal delay must be programmed with a timer module.
248
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
FPC 405 local flags The FPC 405 processor modules offer 640 local flags and 384 global flags. The local flags can only be addressed within the local processor module. The global flags can be addressed by any processor module via the system bus. Addressing of FPC 405 flags is as follows: F0.0.0 to F.23.15 are global flags. F24.0 to F63.15 are local flags. In this context, local means that these flags can only be addressed within the local processor module. In addition there are 8 flags that are programinternal and are addressed as FI0 to FI7. These 8 flags always have the status logic 0 when the program is started. The first 6 of these flags are available for use within the program. Flags FI6 and FI7 have the following functions: FI6 becomes logic 1 in the event of an overflow when using a mathematical operation with CFM20. FI7 is used to store the bit shifted out during a SHIFT operation. Only absolute addressing can be used for these 8 program-internal flags. They are not entered into the allocation list.
249
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Local and global allocation list Because of these inputs and flags (and other "local" operands such as the registers) FST software for the FPC 405 differentiates between the global allocation list that contains operands accessible to all processor modules and the local allocation list, containing operands for the local processor modules. Note: If you exchange programs between different systems (file import), then the different types of addressing of local operands must be observed.
250
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
B.6
Hardware All Festo PLCs are equipped with a port for serial data transmission, the command interpreter port. The port types are as follows: FPC 100B/AF: RS232C data port IPC: RS232C data port FPC 405: RS232C data port FEC: RS232C data port These data ports (the IPC and FPC 405 also have serial data ports) allow connection of the programming and test device to the controller (industry-standard personal computer).
251
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Active/passive interface All Festo PLCs have a common command set for the serial data interface. This means that external addressing of all Festo PLCs is identical. Festo also offers PLC modules to drive various text displays. These allow Festo PLCs to drive text displays, printers etc. directly from a Ladder diagram program with the aid of the serial interface. In addition, the FPC 405 controller allows active control of the interface from the program. This controller can send data to or request data from another computer system. This can be done using Festo BASIC and the serial port belonging to the BASIC equipment of the controller. This is done by calling a simultaneously executing BASIC program from Ladder diagram. For details see the BASIC manual.
252
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
B.7
BEHAVIOUR AFTER BATTERY FAILURE The FPC 100B/AF and the FPC 405 can be equipped with lithium batteries. The batteries back up the contents of the Random Access Memory of the processor module when the controller is switched off or following a power failure. In practice this means that the battery is required to: back up the user program loaded in RAM (when you are not using an EPROM or EEPROM) and back up the status of flags, timer preselects, counters and registers. When the controller is powered up the charge status of the battery is checked. An error message is generated in the event of the battery failure. In the case of the FPC 103 and FPC 405 controllers, a message is generated if the battery is "weak" and must be replaced as soon as possible. Depending on the condition of the battery and the duration of a battery failure, a power failure can lead to a change or loss of contents of the RAM. The degree of change is random. Contents of memory are unreliable after a battery failure. However, as soon as the controller is powered up again, change of RAM contents is shown by means of a system error message.
253
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
For this reason application programs must be written to set all internal operands (flags, counters, timers and registers) to a defined state following a voltage and battery failure. A module that sets all internal operands to 0 is enabled for each controller. In the case of the IPC, the user programs can be stored in a flash memory. The variable data (R, CW etc.) are written to a RAM memory safe against power failure. Because of these measures, the IPC does not require a battery. In the case of the FEC, the user programs are stored in a flash memory. The variable data (R, CW etc.) are also written to the flash memory safe against power failure. Because of these measures, the FEC does not require a battery.
254
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
B.8
INPUT SIGNAL DELAY Input signal delay is implemented for all Festo PLCs in order to prevent the user from having to take extensive interference protection measures for all the input signal ports.
FPC 100B/AF In the case of the FPC 100B/AF input signal delay is software-implemented. The delay program is integrated into the operating system. Software implementation means that the input signal delay can be changed. The value for the input signal delay is stored in register 63. Changing the value of this register changes the delay for all inputs of the FPC 100B/AF. In this instance only the low byte, i.e. the 8 loworder bits of the register, are evaluated. This means that the value can be set to between 1 and 255, with 1 as the shortest delay and 255 as the longest delay. The contents of the high byte are ignored.
R 63 0 1 10 Delay Longest delay (as 255), approx. 25 ms Shortest delay, less than 1 ms Default delay (sets automatically after power on and battery failure), approx. 1 ms Longest delay (as 0!), approx. 25 ms
255
Important: Increasing the input signal delay also increases the cycle time for the processor module. If a particular input really does have to be considerably delayed, programming of a timer is recommended rather than the use of register 63.
255
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
FPC 405 In the case of the FPC 405 input signal delay for the normal I/O modules is hardwareimplemented (see FPC405 manual). IPC In the case of the IPC input signal delay is software-implemented (debounce time according to the cycel time can be switched ON/OFF by software). FEC In the case of the FEC input signal delay is software-implemented (5ms, additional debounce time according to the cycle time can be set by software).
256
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Appendix C - Subroutines
257
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Appendix C - Subroutines
Contents C.1 MODULES .........................................265 Which controller uses modules? .......265 What are modules?............................266 MULTITASKING................................267 Which controller supports multitasking? .......................................267 What is multitasking? .........................267 MULTIPROCESSING........................272 What is multiprocessing?...................272
C.2
C.3
258
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Appendix C - Subroutines
The possible applications of programmable logic controllers are countless. Cleaning machines for turned parts, baking machines for bread rolls, grinding machines for a coal-fired power station, burner controller for a gasheated power station, handling equipment for tubs of margarine, automatic welding machines for hermetic compressors, automatic testing devices for heat exchangers. The majority of these machines have features in common. If you examine the hardware and software of such systems, you will find similar structures even if one system bakes bread rolls and the other manufactures pneumatic cylinders. Similarly there are common features in the operation of the systems. To some extent operation is based on national and international standards and to some extent on simple generally recognized principles for sensible operator interfaces. In most cases automated machines have control elements such as EMERGENCY OFF Start Stop Automatic Manual Acknowledge fault Select type (large or small rolls, large or small valves) etc.
259
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Appendix C - Subroutines
In most cases these automated systems have devices that assist the operators. Examples are displays and signals (lamps, acoustic signals, text displays, screens, flasher lamps, flashing lights, sirens etc.) that indicate Ready Machine error Controller error Manual mode Automatic mode Type being produced etc. A program for a programmable logic controller can be regarded as a series of rungs that are translated in a programming device to a series of program lines. Let us assume that your program for the bread making machine is 2000 rungs long. The machine works well with your program, the customer is happy, the rolls are wonderfully golden brown and taste delicious.
260
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Appendix C - Subroutines
A baker must also get up early in the morning to start work. After producing many thousand rolls there is a fault: when the first batch of dough is to be processed a fault indicator illuminates, the machine stops and has to be repaired. It is 5.15 a.m. What is to be done? Our master baker fetches the printout of your program to find out why the fault indicator is on. Somewhere in the 2000-rung program must be an output called "Error" ... We can leave the rest to your imagination. Of course it would be helpful to give the master baker a list of all possible errors which would assist in providing a solution to our example. But even when the operating instruction and error list are written with greatest care and attention, at some stage it will be necessary to refer to the program to find the fault.
261
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Appendix C - Subroutines
When this is necessary, it would be useful to have a program that is easy to read and understand, in which rungs which might be associated with the error can be located quickly. FST software offers several aids in this respect. You can enter a short comment for each rung. A list of all rungs with these comments is printed out at the beginning of your program forming a sort of table of contents for the program. Rung number 1 Reset registers/start time Rung number 2 Generate flag edge for counting Rung number 3 Count Rung number 4 Interrogate counter after 3 seconds You can print out a cross-reference list of all operands. This indicates which operands are used in which rungs of the program.
262
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Appendix C - Subroutines
FST cross-reference list FPC 100 100 100 100 100 100 CCU 0 0 0 0 0 0 P/B P00 P00 P00 P00 P00 P00 REF 5 5 5 5 5 5
TYPE
Line/Rung/Comment 2 3 5 4 4 3 3 4 5 5 4 4 5 4 5 4 4
You can set jump labels in your program to indicate the beginning of a section. For example, the label "AUTO" is set at the beginning of the section for automatic sequencing. "MANUAL" indicates the beginning of the manual program section,
Motor O0.1
Ma nual
I1.1
"ERROR" the error messages etc. Fig. C/1: Manual operation You can use modules, which can be called up as subroutines at any point in your program.
263
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Appendix C - Subroutines
Within a project you can use various program numbers and program names (as symbolic addresses for a program), and call this as required. You can have several processor modules working together in one PLC as part of a project. A large system can be divided up into several individual projects interconnected with the aid of a network. The use of subroutines is described in the section modules. Structuring a project using several programs is described under the heading "Multitasking". The use of several processor modules within a project is described under the heading "Multiprocessing". The use of a network is described in a separate hand book.
264
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Appendix C - Subroutines
C.1
MODULES
Which controller uses modules? Modules can be used in all Festo PLCs. The number, selection and type of module is dependent on the type of controller:
Controller FPC 100 B/AF IPC FEC FPC 405 Program module 8 in any programming language 100 in any programmig language 100 in any programming language 32 written in LDR or Assembler CFM0 to CFM75 Function module CFM0
265
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Appendix C - Subroutines
What are modules? Modules are subroutines. This means that modules are programs that can be called from another program. When a processor module calls a module, control passes from the calling program to the module and returns to the calling program after processing of the module. Nesting of modules calling one module from another module is not allowed with the Festo PLCs. However, the FPC 405 does allow calling of the same module from simultaneously executing programs. Modules are created, edited, tested and loaded independently to great advantage. Various versions of a module can be created and loaded as required. Note that the use of JUMP commands within a module1 can result in control never being passed back to the calling program. Particular care must be taken when using backward jumps within a module.
1 and with the aid of a Step command or the PW command within a module written in Statement list.
266
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Appendix C - Subroutines
C.2
MULTITASKING
Which controller supports multitasking? Multitasking is the execution of several programs in parallel within a project. Multitasking is supported by the following controllers: FPC 100B/AF: 1 program 8 program modules IPC: 64 programs FEC: 64 programs FPC 405: Up to 8 programs simultaneously out of 64 stored programs What is multitasking? A conveyer system is to be operable in two modes "Manual" and "Automatic". A selector switch on the control console allows the operating mode to be selected. Within a FST project we give the programs for these two operating modes two different numbers, for example program number 1 for automatic mode and program number 2 for manual mode. Program number 0 is the organization program: dependent on the position of the selection switch and of the machine it manages which operating mode is active. For example, it must only be possible to switch the machine to automatic mode when it is in its initial position.
267
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Appendix C - Subroutines
Therefore we have three programs: Fig. C/2: Programs The two programs for automatic and manual mode are typical of programs that are mutually exclusive. A machine must never operate in both manual and automatic mode the result would be chaotic. The organization program must monitor the selector switch to see if the operating mode setting has been changed. This means that the organization program must be executing continuously, in parallel to either the manual or automatic mode program.
268
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Appendix C - Subroutines
Additional Ladder diagram programs are always started from program 0. For this reason program 0 is generally the organization proAUTO P1 S
Co ndition
gram. Fig. C/3: Organization program The automatic program with the address P1 (absolute address) can be used like any other one-bit operand. It can be set, reset, or interrogated for logic 1 or logic 0. Please note that control of the program in the above rung is signal-edge controlled. In the above rung the program is set from logic 0 to logic 1 the first time the condition changes. Switching on again for example after having been switched off from somewhere else only takes place when the condition changes to logic 0 and then changes back to logic 1.
269
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Appendix C - Subroutines
When program P1 is set, programs P1 and P0 execute simultaneously. Switchover occurs after each complete cycle through the Ladder diagram program. In reality, the processor first executes one program completely, then the simultaneous program, then the first again etc. In practice the most common case is a Ladder diagram program working in parallel with a BASIC program either for data transmission to a host computer or for driving a terminal for operator control. FPC 405 This controller allows 64 programs to be stored in the processor module. Up to 8 Ladder diagram programs can be executed simultaneously. The FPC 405 manual contains a matrix indicating how many of which programs in which language mix can be executed simultaneously. In practice it is likely there would be several Ladder diagram programs executing simultaneously with a BASIC program for operator guidance or a network. FPC 100B/AF This controller allows 1 program and 8 program modules can be stored in the processor module. Up to 1 Ladder diagram programs and 8 Ladder diagram program modules can be executed simultaneously.
270
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Appendix C - Subroutines
IPC This controller allows 64 programs to be stored in the processor module. Up to 64 Ladder diagram programs can be executed simultaneously. FEC This controller allows 64 programs to be stored in the processor module. Up to 64 Ladder diagram programs can be executed simultaneously.
271
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Appendix C - Subroutines
C.3
MULTIPROCESSING The following controller supports multiprocessing, that is the operation of multiple processor modules within a system (connected via a system bus): FPC 405 up to 6 processor modules on one bus
What is multiprocessing? Each processor module of a programmable logic controller consists basically of a microprocessor system. This includes the microprocessor itself and storage and peripheral modules. In addition there are the connections to inputs and outputs, to the programmer etc. This then represents a system with a single processor. This processor executes each program line in turn in the order prescribed by the program. In addition the processor must handle administrative tasks, counting for counter modules, reacting to requests from programmers and test equipment etc. All this takes time.
272
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Appendix C - Subroutines
The result: the processor module needs time to cycle through a program once. Several measuring programs to measure the cycle time of a processor module are shown in Appendix B, "Example programs". Depending on the program size and CCU type, this time problem can be significant. The problem can be alleviated by allowing several processor modules to work in parallel. In computer technology this method is used in parallel processors. But in the case of parallel processors, a single program is compiled in such way that it is automatically distributed to the various processors. The Festo PLCs offer you the possibility of allowing several processor modules to work within a common system. Distribution of tasks and programs to the various processor modules is undertaken by the application program, that is by you.
273
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Appendix C - Subroutines
General tasks Organization Operator guidance with screen control Connection of other CCU
Processor module No. 1 Control Program 0: Organization Program 1: Manual Program 2: Automatic Type A Program 3: Automatic Type B
Processor module No. 3 Fieldbus Fieldbus control and addition control tasks
Processor module No. 4 Statistics / Collection of operating data Evaluation and compression of operating data, data transfer to the host computer
274
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Appendix C - Subroutines
Of course it is necessary for the various processor modules to be able to "talk to each other" in other words exchange information. This information exchange takes place in the Festo PLC with the aid of flags. The FPC 405 operand parameter consists of:
F3 . 4 . 12
Number of bit Point separating bit and word Number of word Point separating processor module and word (not for FPC100B/AF, IPC and FEC) Number of CCU (not for FPC100B/AF, IPC and FEC) Operand identifier (here F for flag) Fig. C/5: Operand parameters Each processor module can access all flags of all processor modules (with the exception of the local flags of the FPC 405 processor module). This allows quick and easy data exchange.
275
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Appendix C - Subroutines
In addition, the FPC 405 allows each processor module to start and stop programs executing on other processor modules directly (that is without the use of flags). This represents a simple and convenient way of dividing a machine project into various subtasks and distributing these to various processor modules, all of which can access the same inputs and outputs. With the FPC 405 you can select a certain type of processor module to fit the task (e.g. field bus connection, additional serial interface, networking etc.).
276
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
277
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Contents D.1 THE STRUCTURE OF NUMBER SYSTEMS ..........................................279 THE BINARY NUMBER SYSTEM ..282 BCD code ...........................................284 The hexadecimal number system......286 Signed numbers..................................288 DIFFERENTIATION IN LADDER DIAGRAM ..........................................289
D.2
D.3
278
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
D.1
THE STRUCTURE OF NUMBER SYSTEMS The history of numbers and mathematics has resulted in a wide range of number systems. The oldest known written number is supposed to be 30,000 years old. A general characteristic of the most widespread system the decimal system is the structure of places and the significance of these places. For example the number 4344 has the following structure: 4 x 1000 plus 3 x 100 plus 4 x 10 plus 4 x 1 This means that the digit "4" on the left has a completely different meaning to the digit "4" on the right (9301 is significantly more than 1309). This is not the only type of number structure. The Roman number system worked in a completely different way. In the Roman system, a new symbol was used as soon as the number became too large. For example CXXI = 121. On the other hand, IXXC is incorrect as the sequence does not coincide with the meaning of the symbol.
279
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Back to the decimal number system. The basis for the decimal number system is the presence of 10 different digits (for this reason decimal, decimum (Latin) = 10). It follows that we can use 10 different symbols to count from 0 to 9. As soon as we want to go past 9, we carry over to the next position. This next position has the significance 10 (=101). In this next position we can again count up to 9 (that is 9 x 101 = 90). Then we need to carry over again to the next position with the significance 100 (=102). If we take the number 71718711 as an example:
107 = 10 Mil 7 106 = 1 Mil 1 105 = 100000 7 104 = 10000 1 103 = 1000 8 102 = 100 7 101 = 10 1 100 =1 1
The table makes it clear that the 7 "on the left" means 7 times 10 million = 70 million, while the 7 in the third position from the right means 7 times 100 = 700.
280
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
The position on the extreme right is called the least significant position (because its value is least significant) and the position on the extreme left is called the most significant position (because its value is most significant). Using the 8 positions as in our example the highest number we can create is 999999999, that is nearly 100 million. If we want to see the maximum number that can be represented with a given number of positions, we can simply take the value of the next highest position, subtract 1 and that is the answer. Example: The maximum number that can be represented by a 6-digit decimal number is 106-1 = 1000000-1 = 999999. (106 is the seventh position as 100 not the 101 is the first position). What does this mean for the Festo PLC? Each word (for example, a register) can store a 4-digit decimal number with the aid of BCD code. A 4-digit decimal number enables you representing numbers up to 104-1 = 10000-1 = 9999. We could use this same pattern to develop any amount of number systems. The basic structure of the decimal number system can be transferred to number systems with any number of digits. So it follows that all arithmetic operations and methods that we use for decimal number systems can be also used for other number systems.
281
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
D.2
THE BINARY NUMBER SYSTEM Back in 1679 G. W. von Leibnitz fulfilled one of the basic conditions for the development of the computer by transferring the characteristics of the decimal number system to a form of calculation using only two digits. This is because the computer only operates with two digits: "current on", "current off". These two states can be represented as numbers: "1" and "0". Unless analogue signals are used, no other numbers can be represented. If we limit ourselves to two digits (0 and 1) the number system has the following structure:
27 = 128 1
26 = 64 0
25 = 32 1
24 = 16 1
23 =8 0
22 =4 0
21 =2 0
20 =1 1
The principle is the same as for the decimal number. But as only two digits are available, the significance of a position is not calculated by 10x but by 2x. The least significant digit (extreme right) has the value 1 (exactly as in the decimal system), the next position has the value 21 = 2 as opposed to 101 = 10 in the decimal system.
282
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Using 8 positions (as in our decimal number example) we can represent a number of up to a maximum of 28-1 = 255. This would be represented by the number 111111112. Each position of the binary number can be occupied by the digit 0 or 1. The smallest unit of the binary system is a bit. In the above example a number has been created from 8 bits, that is, the bits have been joined together to form a byte (represented in the computer as 8 electrical signals, each of which denotes "current on" or "current off"). In the Festo PLCs, words generally have a width of 16 bits, meaning that they can count from 00000000000000002 to 11111111111111112. The highest possible number that can be represented with 16 bits in the binary system is 216-1 = 6553610-1 = 6553510. This is the reason why a timer can only measure a time of up to 65535 times 10 milliseconds = 655.35 seconds = 10 minutes and 55.35 seconds. This is also the reason why an individual counter can only count from 0 to 65536 (or from 65535 to 0).
283
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
BCD code Normally, binary numbers are displayed to you as decimal numbers. The easiest method for this is to use the BCD code. In BCD code, each individual digit of the decimal number system is represented by the corresponding binary number: 010 110 210 310 410 510 610 710 810 910 = = = = = = = = = = 02 12 102 112 1002 1012 1102 1112 10002 10012
It follows that 4 positions of the binary number system are required for the 9 digits of the decimal number system. This wastes space as 4 positions in the binary number system allow numbers up to 24-1 = 1510 to be represented. However, this is acceptable to achieve greater clarity.
284
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
The number 713310 is represented in BCD code as: 0111 0001 0011 0011BCD.
This 4-digit decimal number therefore requires 16 bits for representation in BCD code. BCDcoded numbers of this type are often used in 7-segment displays or in encoding switches which pass numbers to the control system. For this reason the command set of the Festo PLCs contains the conversion commands DEB and BID. BID converts from binary to decimal and DEB converts from decimal to binary. Please note that only 16 bits are available in each case. This allows the representation of a 4-digit decimal number in BCD code, i.e. a maximum of 999910 = 1001 1001 1001 1001BCD.
If you convert a larger number into BCD code, the most significant positions that don't fit will be lost without a warning and without an error message. Example: DEB converts 2400010 to BCD code 0100 0000 0000 0000BCD, which represents the last 4 decimal digits of 24000, namely 400010.
285
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
In FPC on-line mode this number 0100 0000 0000 0000BCD is still understood as a binary number (only decimal and hexadecimal numbers can be displayed, not BCD), and this is therefore interpreted as 1638410. If we convert this back with DEB (decimal to binary) the number 400010 is written as a binary number, namely 00001111101000002. This is also displayed in FPC on-line mode as 400010. The hexadecimal number system Reading binary numbers is very difficult for the inexperienced user. Reading numbers in BCD code is much simpler but wastes a lot of space. For this reason the octal and hexadecimal number system were developed. In the octal number system, 3 bits are joined together. 3 bits allow representation of numbers from 010 to 710, 8 different digits. In the hexadecimal number system, 4 bits are joined together. 4 bits allow the representation of numbers from 010 to 1510. This requires 16 different digits. The well known digits 0 to 9 are used, followed by the letters A, B, C, D, E and F. F16 = 1510 = 11112 = 0001 0110BCD. 286
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
In the same way as the decimal and binary system, a hexadecimal number is read as:
163 = 4096 8 which means: 8 163 + 7 162 + 11 161 + 12 160 = 3474810 162 = 256 7 161 = 16 B 160 =1 C
As each hexadecimal digit consists of 4 bits, the 16 bits of a word of the Festo PLC can represent the hexadecimal number of up to 4 positions. Therefore the highest number that can be represented with 16 bits is FFFF16 = 6553510 = 11111111111111112. In order to differentiate between decimal and hexadecimal numbers, hexadecimal numbers are prefixed with a $ when programming the Festo PLC. Example: V$1A2 = V418 1000BCD or V$2210 = V8720 = 00100010000100002 = 1000 0111 0010 0000BCD = 00000001101000102 = 0000 0100 0001
287
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Signed numbers Up to now we have assumed positive whole numbers. We haven't taken into account that there is such a thing as negative numbers. In order to work with negative numbers there is a convention that the most significant bit of a binary number is used to indicate the sign: 1 corresponds to 0 corresponds to +. As the most significant bit is used for the sign, signed numbers consist of one bit less, in our case maximum of 15 bits. It follows that the largest number that can be represented in a Festo PLC with a signed number is 215 = +32767... -32768.
288
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
D.3
DIFFERENTIATION IN LADDER DIAGRAM Ladder diagram for Festo PLCs has the following conventions for differentiation of number systems: 1. In comparison operations (>, <, =, >=, <=, <>) an unsigned positive binary number between 0 and 65535 is assumed. Negative numbers must be converted for comparison, unless the FPC 405 is switched to signed numbers with CFM20. 2. All arithmetic operators (+, -, /, *) assume signed binary numbers between 0 and 32767. 3. All bit-manipulating operations (BID, DEB, INV, CPL, AND, OR, EXOR) take all 16 bits of a word into account. They do not treat the most significant bit as a sign, but as a bit. 4. Hexadecimal numbers are only unsigned, as only positive numbers are possible.
289
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Notes
290
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Index
Index
291
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Index
!
0-1 signal edge..................................... 164 ; 189 7-segment display ....................... 129 ; 131 ; 285
292
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Index
A
Active serial port ........................................... 252 Address Absolute .................. 21 ; 145 ; 147 ; 153 ; 248 Absolute (list of all possible) ...................... 155 Absolute operands (rules for)..................... 147 Counter ..................................................... 157 Error (word)............................................... 155 Flag (word) ................................................ 156 Function module ........................................ 155 Function unit.............................................. 155 Initialization flag......................................... 155 Input (word) ............................................... 155 Mixing absolute and symbolic .................... 150 Null operation ............................................ 157 Output (word)............................................. 155 Program .................................................... 157 Program module ........................................ 155 Register .................................................... 157 Representation in printout.......................... 150 Rules for symbolic addresses.................... 148 Symbolic.................................... 21 ; 145 ; 148 Timer......................................................... 157 Allocation list ................... 9 ; 15 ; 150 ; 152 ; 250 AND, see Logic ............................................... 86 Application program....................................... 273 Arithmetic Adding ......................................................... 91 Dividing ....................................................... 93 Functions .................................................. 208 Multiplying.................................................... 95 Operators.................................. 23 ; 199 ; 289 Subtracting .................................................. 97 Arithmetic/Logic Box........................................ 62 Assembler ....................................................... 11 Automatic ...................................................... 233 Auxiliary relay................................................ 203
293
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Index
B
BASIC .................................................... 11 ; 252 Battery Buffering...................................................... 33 Failure....................................... 33 ; 213 ; 253 BCD code ............................................ 199 ; 281 Binary number ............................. 129 ; 131 ; 282 Bit ........................................................ 153 ; 283 Manipulation .............................................. 289 Operand, see one-bit operand ..................... 24 Boolean operation........................................... 37 Boxes................................................ 34 ; 36 ; 62 Maximum number......................................... 34 Bus access ................................................... 246 Byte .............................................................. 283
C
CCU ................................................................ 10 Central control unit .......................................... 16 Check routine......................................... 44 ; 242 Circuit diagram ..... 34 ; 37 ; 170 ; 172 ; 192 ; 203 Coding switches.................................... 129; 131 Coil ......................................................... 33; 177 Assignment................................................ 115 Negated assignment.................................. 116 Resetting................................................... 113 Setting....................................................... 114 Command interpreter port.............................. 251 Comment......................................... 17 ; 64 ; 262 Comparison................................................... 208 Equal......................................................... 117 Greater than.............................................. 119 Greater than or equal ................................ 121
294
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Index
Less than .................................................. 123 Less than or equal..................................... 125 Operations ....................................... 199 ; 289 Unequal ..................................................... 127 Complement .................................................... 73 Conditional part ............................................... 37 Contact .................................................. 33 ; 177 Control part .......................................... 215 ; 216 Counter ......................................... 23 ; 183 ; 283 Actual value...................................... 185 ; 186 Bit ............................................................. 186 Compare ................................................... 185 Counting.................................................... 189 Decremental............ 23 ; 183 ; 188 ; 193 ; 195 Event......................................................... 183 Incremental....................... 23 ; 183 ; 191 ; 195 Initialize ..................................................... 187 Interrogate................................................. 190 Load counter word..................................... 188 Nominal value............................................ 185 Possible operands..................................... 187 Preselect................................... 31 ; 185 ; 186 Programming .................................... 191 ; 193 Pulse......................................................... 186 Reset ............................................... 185 ; 188 Set ............................................................ 187 Setting preselect ....................................... 139 Word ................................. 23 ; 31 ; 186 ; 190 Zero actual value....................................... 187 Counting Interrogate................................................. 189 Cross-reference list................................... 9; 262 Cycle time ............ 45 ; 46 ; 218 ; 221 ; 243 ; 273 Cycle time measurement ................................. 46
295
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Index
D
Decimal number............................................... 23 Decrementing................................................ 137 Direct access Advantages ................................................. 45 Disadvantages ............................................ 44 Documentation ........................................... 9 ; 18 Double-word.................................................... 21
E
EEPROM ...................................................... 253 EMERGENCY OFF ....................................... 232 Encoding switch ............................................ 285 EPROM......................................................... 253 Error....................................................... 24 ; 147 List ......................................................... 9 ; 18 Word .................................................... 23 ; 27 Executive part ................................................. 37 Existing flag chain ......................................... 214
296
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Index
F
FI ................ 23 ; 39 ; 192 ; 194 ; 213 ; 216 ; 231 Flag............................................. 203 ; 213 ; 275 Bit .................................................... 203 ; 204 Word ................................................ 204 ; 207 Flashing outputs .............................................. 42 Function Chart ........................................................... 15 Diagram..................................................... 212 Key ............................................................. 18
<F1> ..................................................................... 17 <F10> ................................................................... 18 <F9> ..................................................................... 18
G
Global allocation list ...................................... 250
H
Help key .......................................................... 18 Hexadecimal......................... 29 ; 199 ; 286 ; 289 Number........................................................ 23 High byte......................................................... 67
297
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Index
I
Import of data........................................... 9 ; 246 Incrementing......................................... 137 ; 138 Initialization flag............. 23 ; 39 ; 213 ; 216 ; 231 Input signal delay................ 200 ; 223 ; 248 ; 255 Input word ................................................ 23 ; 27 Internal Flags ......................................................... 248 Inputs ........................................................ 248 Operands .................................................. 248 Interrupt................................................ 227 ; 247 Capability .................................................. 247 Inverting .......................................................... 71
J
Jump ............................................. 46 ; 110 ; 227 Backward .................................................. 241 Label .............................. 110 ; 112 ; 149 ; 263
298
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Index
L
Ladder diagram ............................... 11 ; 33 ; 270 Editor .......................................................... 18 Program ...................................................... 16 Latch............................................................. 107 Dominant resetting .................................... 108 Dominant setting........................................ 109 Latching ............................................... 215 ; 216 Least significant position...................... 281 ; 282 Line crossing................................................... 33 Lithium battery............................................... 253 Load............................................................ 9; 37 LOAD command .......................................... 64 LOAD TO..................................................... 75 Local Allocation list ............................................. 250 Input .......................................................... 248 Logic AND............................................................. 86 AND with words ........................................... 88 Exclusive OR............................................... 76 EXOR.......................................................... 76 EXOR with three inputs ............................... 77 EXOR with words ........................................ 79 Identity ........................................................ 81 Identity with words, see "LOAD TO"............. 81 Negation...................................................... 82 Negation with words ............................. 71 ; 82 NOT (at input).............................................. 83 NOT (at output)............................................ 82 NOT with words ........................................... 71 Operation ............................................. 23 ; 37 OR .............................................................. 83 OR with words............................................ 85 Long-word ....................................................... 21 Low byte ......................................................... 67
299
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Index
M
Machine code.................................................. 38 Manual .......................................................... 233 Masking.................................................... 85 ; 88 Matrix programming ......................................... 11 Module ....................... 9 ; 23 ; 65 ; 69 ; 263 ; 265 /Program ..................................................... 16 Nesting...................................................... 266 Number........................................................ 16 Most significant bit ........................................ 288 MS-DOS.......................................................... 15 Multi-bit operand, see Word operand............. 183 Multiprocessing ........................... 205 ; 246 ; 272 Multiprocessor system .................................... 45 Multitasking ................................. 227 ; 244 ; 267
N
Negation Of words..................................................... 71 Network......................................................... 264 NOP ................................................................ 90 NOT, see Logic ............................................... 82 Null operation .................................................. 90 Numbering ....................................................... 38 Numbers Conversion BCD to digital ......................... 129 Conversion digital to BCD ......................... 131 Interrogation preselect achieved ............... 133
300
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Index
O
Octal ............................................................. 286 One-bit operand .............................................. 21 On-line mode.......................................... 18 ; 218 Operand ................................................. 10 ; 186 Address............................................ 145 ; 153 Enter ........................................................... 36 Identifier .................................. 145 ; 147 ; 153 Missing........................................................ 36 Parameter ........................................ 145 ; 153 Retentive..................................................... 39 Operating mode............................................. 267 Operation ........................................................ 36 OR, see Logic ................................................. 83 Organization program .................................... 267 Output ............................................................. 24 Word .................................................... 23 ; 27
P
Page header ................................................... 15 Parallel Branch........................................... 33 ; 35 ; 84 Coil....................................................... 33 ; 35 Connection.................................................. 37 Maximum number......................................... 33 Processor ................................................. 273 Programs................................................... 267 Parameter ....................................................... 69 PC................................................................. 251 Power Failure....................................... 33 ; 213 ; 253 Part .................................................. 215 ; 216 Up ...................................................... 38 ; 246 Preselect, see Counter ................................... 31 Print .................................................................. 9 Printer drive .................................................. 252
301
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Index
Priority for bus access .................................. 246 Procedure ....................................................... 69 Process image ....................... 38 ; 40 ; 223 ; 241 Advantages ................................................. 44 Disadvantages ............................................ 45 Method ........................................................ 44 Processor module10 ; 205 ; 218 ; 246 ; 248 ; 264 Program ................................... 9 ; 23 ; 244 ; 264 Load............................................................ 18 Module ............................. 65 ; 245 ; 263 ; 265 Number........................................................ 16 Save ........................................................... 18 Structure ................................................... 231 Programming and test device ........................ 251 Project ................................... 9 ; 149 ; 264 ; 267 Name........................................................... 15 Pulse timer, see Time.................................... 168
Q
Quasi-parallel processing .............................. 244
302
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Index
R
Reaction time................................................ 223 Absolute in 0.1 ms ..................................... 225 Longest possible time................................ 227 Measuring .......................................... 46 ; 223 Register .......................................... 23 ; 29 ; 199 Register 63 (FPC 100) .................................. 255 Resetting sequence ...................................... 216 Retentiveness .... 33 ; 177 ; 186 ; 200 ; 203 ; 213 ROL ................................................................ 99 ROR.............................................................. 101 Rotate Left.............................................................. 99 Right.......................................................... 101 RS232C interface ......................................... 251 Run/Stop switch ..................................... 38 ; 203 Rung ........................................................ 33 ; 34 Number........................................................ 38 Section........................................................ 33
303
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Index
S
Safety routine......................................... 44 ; 242 Sequence Program ............................................. 15 ; 211 Program with counter................................. 217 Program with jump ..................................... 217 Sequencer..................................................... 216 Serial data transmission................................ 251 Series connection .................................... 37 ; 87 Shift Left (SHL).................................................. 103 Register ........................................... 103 ; 105 Right (SHR) ............................................... 105 Sign........................................................ 73 ; 288 Signal-edge recognition................................. 164 Signed.................................................... 23 ; 199 Significance ......................................... 280 ; 282 Simultaneous................................................. 244 Execution, see Multitasking ....................... 267 Standing 1................................................ 39 ; 43 Start/Stop switch.................................... 38 ; 203 Statement list .................................................. 11 Structure chart ................................................ 15 Subdirectory.................................................... 15 Subroutine................................... 245 ; 263 ; 265 Nesting...................................................... 266 Subroutines.............................................. 65 ; 69 SWAP ............................................................. 67 Switch-off delay, see Time ............................ 165 Switch-on delay, see Time ............................ 165 Symbolic address, see address.............. 21 ; 145 Syntax test...................................................... 18 System bus ................................................... 246
304
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Index
T
Task.............................................................. 244 Text display................................................... 252 Time.............................................................. 283 Box............................................................ 164 Clock pulse................................................ 162 Compare timer word .................................. 178 Digital time measurement .......................... 162 Error in measurement ................................ 162 Flashing lamp ............................................ 174 Initialization ............................................... 164 Longest time.............................................. 163 Module ...................................................... 177 Preselect................................................... 177 Pulse timer ....................................... 165 ; 168 Quartz ....................................................... 161 Requirement for operations ....................... 218 Shortest time............................................. 163 Start ................................................. 141 ; 142 Switch-off delay.............. 164 ; 165 ; 167 ; 172 Switch-on delay..... 164 ; 165 ; 166 ; 169 ; 171 Word ......................................................... 177 Timer............................................................... 23 Bit ............................................................. 178 Preselect..................................................... 29 Word ........................................................... 31 Timer, see Time .......................... 141 ; 142 ; 161 Title page ........................................................ 15 TO................................................................... 64 Twos complement............................................ 73
305
Toolbar Menubar Print Contents Search Page
Toolbar
Menubar
Contents
Search
Page
Index
U
Unsigned ....................................................... 199
V
Version.............................................................. 9 Number........................................................ 17
W
Word ...................................................... 23 ; 283 Operand ............................. 21 ; 27 ; 183 ; 199 Operation .................................................... 62
Y
Yes function .................................................... 81
306