NOX EMA data sheets

Content may change without prior notice. edited by NOX Systems AG Alvierweg 17 9490 Vaduz Principality of Liechtenstein Tel Fax +423 370 25 25 +423 370 25 26

e-mail info@noxsystems.com www.noxsystems.com EN 50130-4

NOX data sheets, December 03, p 1 of 12

central unit data sheet


NOX central

NOXPSU power supply

NOXCPU

NOXMIO

2x 17 Ah accumulators

a) NOXCPU power in / bus 3 bus 3 bus 2 backup battery NOXCPU main board with bus input from power supply, MMC card slot, Ethernet RJ-45 socket and three NOX bus outputs to connect all other NOX Systems devices.

bus 1 Ethernet MMC slot

NOX data sheets, December 03, p 2 of 12

technical data:
supply voltage (VBUS) power consumption at 15 VDC operating temperature range air humidity at +40C (non condensing) dimensions (L x B x H): fuses (F1 to F4) maximum bus output current (bus 1 to 3) min. nom. max. VDC 14.25 15.0 15.75 mA ? ? C 0 25 40 % rel. h 93 mm 640 x 404 x 105 1A slow-blow order no.: 154.001T A 2.5

terminal assignment:
plugs terminal P1 terminal P2 BAT1 S1 terminal P7 pin description terminal P3 pin description terminal P4 pin description terminal P6 pin description terminal P5 pin description + 15 5% VDC description MMC connector RJ45 Ethernet connection Lithium battery CR2032 CPU reset button A GND Bus A input from PSU device B Bus B

+ 15 5% VDC GND supply voltage (VBUS) + 15 5% VDC GND supply voltage (VBUS) + 15 5% VDC C GND supply voltage (VBUS) 1 GND 2 TX send

A B Bus A Bus B bus connection A B Bus A Bus B bus connection A B Bus A Bus B bus connection 3 RX receive

P5 for special purpose only!

NOX data sheets, December 03, p 3 of 12

CPA data sheet


NOXCPA The NOXCPA is the operating panel for the NOX alarm system with 128 x 64 pixels LCD graphic display, white back light, integrated alarm buzzer, a numeric key pad with clear C and enter E keys and two scroll keys with variable function.

technical data:
supply voltage (VBUS) power consumption at 15 VDC operating temperature range air humidity at +40C (non condensing) dimensions (L x B x H): protection class VDC mA C % rel. h mm Min. 9.0 15 0 Max. 15.5 50 25 40 93 on wall 175 x 110 x 24 in wall 212 x 148 x 23 IP30 Nom. 15.0

terminal assignment:
terminal P2 pin description + 9-15.5 VDC GND supply voltage (VBUS) A B Bus A Bus B bus connection

NOX data sheets, December 03, p 4 of 12

MIO data sheet


NOXMIO NOXMIO is an input and output module with eight relay outputs plus four resistance monitored inputs with driver for connected flash lights or sirens. Although flexible in the programming, the outputs are often used to interface to alarm transmission devices.

technical data:
supply voltage (VBUS) power consumption 15 VDC operating temperature air humidity at +40C (non condensing) input impedance range 1-4 electrical data relay 1-4 each contact fuses (F1 to F4) dimensions (L x B): VDC mA C % rel. h k min. 9.0 15 0 3.5 nom. 15.0 25 max. 15.5 83 40 93 50

12 max. 30VDC/1A 500mA slow-blow order no.: 154.500T mm 47.5 x 65

terminal assignment:
terminal P2 pin description terminal P3 pin description pin description terminal P4 pin description pin description terminal P5 pin description pin description + 9-15.5 VDC GND supply voltage (VBUS) 1 VBUS 7 VBUS 2 Input 1 input 1 8 Input 3 input 3 2 COM (3) relay 1 8 COM (3) relay 3 2 COM (3) relay 5 8 COM (3) relay 7 3 O.C. (1) 9 O.C. (1) A B Bus A Bus B bus connection 4 VBUS 10 VBUS 5 Input 2 input 2 11 Input 4 input 4 5 COM (3) relay 2 11 COM (3) relay 4 5 COM (3) relay 6 11 COM (3) relay 8
4

6 O.C.

(1)

12 O.C. (1)

1 NO (2) 7 NO (2)

3 NC (4) 9 NC (4)

4 NO (2) 10 NO (2)

6 NC (4) 12 NC (4)

1 NO (2) 7 NO (2)

3 NC (4) 9 NC (4)

4 NO (2) 10 NO (2)

6 NC (4) 12 NC (4)

O.C.: open collector, NO: normally open, COM: common,

NC: normally closed

NOX data sheets, December 03, p 5 of 12

IN4 data sheet


NOXIN4 NOXIN4 is a universal input module connectable to the NOX alarm bus with four resistance monitored inputs.

technical data:
supply voltage (VBUS) power consumption 15 VDC operating temperature air humidity at +40C (non condensing) input impedance range 1-4 dimensions (L x B x H): protection class VDC mA C % rel. h k mm min. 9.0 12 0 3.5 nom. 15.0 25 12 85 x 66 x 27 IP30 max. 15.5 16 40 93 50

terminal assignment:
terminal P2 pin description terminal P3 pin description pin description + 9-15.5 VDC GND supply voltage (VBUS) 1 VBUS 7 VBUS 2 Input 1 input 1 8 Input 3 input 3 3 GND 9 GND A B Bus A Bus B bus connection 4 VBUS 10 VBUS 5 Input 2 input 2 11 Input 4 input 4 6 GND 12 GND

NOX data sheets, December 03, p 6 of 12

RE4 data sheet


b) NOXRE4 The NOXRE4 offers four programmable relay outputs to transmit alarms or the status of detector groups to supervising systems.

technical data:
supply voltage (VBUS) power consumption at 15 VDC operating temperature range air humidity at +40C (non condensing) electrical data relay 1-4 each contact dimensions (L x B x H): protection class VDC mA C % rel. h mm Min. 9.0 12 0 Nom. 15.0 25 max. 30 VDC/1A 85 x 66 x 27 IP30 Max. 15.5 30 40 93

terminal assignment:
terminal P2 pin description terminal P3 pin description pin description
1

+ 9-15.5 VDC GND supply voltage (VBUS) 1 NO (1) 7 NO (1) 2 COM (2) relay 1 8 COM (2) relay 3
3

A B Bus A Bus B bus connection 4 NO (1) 10 NO (1) 5 COM (2) relay 2 11 COM (2) relay 4 6 NC (3) 12 NC (3)

3 NC (3) 9 NC (3)

NO: normally open,

COM: common,

NC: normally closed

NOX data sheets, December 03, p 7 of 12

CRD data sheet


NOXCRD with Wiegand 26 Bit interface The NOXCRD is a universal input/output module connected to the NOX alarm bus with one resistance monitored input, one relay output and a card reader port with Wiegand 26 Bit interface.

technical data:
supply voltage (VBUS) power consumption at 15 VDC operating temperature range air humidity at +40C input impedance range (non condensing) electrical data relay dimensions (L x B x H): protection class VDC mA C % rel. h k mm min. 9.0 12 0 3.5 nom. 15.0 25 12 max. 30VDC/1A 85 x 66 x 27 IP30 max. 15.5 18 40 93 50

terminal assignment:
terminal P2 pin description terminal P3 pin description pin description
1

+ 9-15.5 VDC GND supply voltage (VBUS) 1 VBUS 7 LED 2 2 Input input 8 Data 0 card reader
3

A B Bus A Bus B bus connection 4 5 VDC 10 NO (1) 5 GND card reader 11 COM (2) relay 6 LED 1 12 NC (3)

3 GND 9 Data 1

NO: normally open,

COM: common,

NC: normally closed

NOX data sheets, December 03, p 8 of 12

RPT data sheet


NOXRPT The NOXRPT is a universal module configurable as repeater (RS485) or as serial gateway (RS232) to connect a personal computer to the NOX alarm bus.

technical data:
supply voltage (VBUS) power consumption at 15 VDC operating temperature range air humidity at +40C (non condensing) dimensions (L x B x H) protection class VDC mA C % rel. h mm min. 9.0 13 0 nom. 15.0 25 85 x 66 x 27 IP30 max. 15.5 14 40 93

terminal assignment:
terminal P1 pin description terminal P2 pin description terminal P3 pin description 1 5 VDC reserve 2 GND 3 RX serial interface (RS232) 4 TX

+ 9-15.5 VDC GND supply voltage 1 (VBUS1) + 9-15.5 VDC GND supply voltage 2 (VBUS2)

A B Bus 1 A Bus 1 B bus 1 - input A B Bus 2 A Bus 2 B bus 2 - output

jumper assignment:
JP1 function output 1-2 repeater Bus 2 output 2-3 serial interface RS232 JP2 function ON VBUS1=VBUS2 OFF VBUS2 external

NOX data sheets, December 03, p 9 of 12

THS data sheet


NOXTHS The NOXTHS module connects an internal or external combined sensor for temperature and humidity to the NOx bus. The module contains a freely programmable relay output on the board. This device is not approved by the SVV.

technical data:
supply voltage (VBUS) power consumption at 15 VDC operating temperature range air humidity at +40C electrical data relay dimensions (L x B x H) protection class VDC mA C % rel. h mm min. 9.0 12 0 nom. 15.0 25 max. 30VDC / 1A 85 x 66 x 27 IP30 max. 15.5 14 40 93

terminal assignment:
terminal P2 pin description terminal P3 pin description pin description
1

+ 9 - 15.5VDC GND supply voltage (VBUS) 1 X 7 Data2 Sensor


2

A B Bus A Bus B bus connection 4 Sensor 5V 10 NO (1) 5 GND Sensor 11 COM (2) relay 6 Data1 12 NC (3)

2 3 X X X= not used 8 9 X X X= do not use


3

NO: normally open,

COM: common,

NC: normally closed

NOX data sheets, December 03, p 10 of 12

technical data sensor (SHT71)

Tested for temperature range from: -25 to +75 C for the external sensor Tested for temperature range from: 0 to +40 C for the internal sensor

Tested for humidity range from: 0 to 100% RH for both, the internal and the external sensor

NOX data sheets, December 03, p 11 of 12

M31 data sheet


NOXM31 NOXM31 is a compact module with one output and three inputs for integration into the housing of a detector.

technical data:
supply voltage (VBUS) power consumption 15 VDC operating temperature air humidity at +40C (non condensing) electrical data open collector output dimensions (L x B x H): VDC mA C % rel. h mm max. 15.5 16 25 40 93 max. 15 VDC/ 50 mA (to GND) 16 x 23 x 10 min. 9.0 12 0 nom. 15.0

terminal assignment:
terminal P? pin description wire pin description wire pin description A B Bus A Bus B bus connection black supply voltage green 2 green 3 IN 2 IN 3 input red + yellow OUT output green 1 IN 1 input

All three input are equipped with a 10k pull up resistor. The inputs are triggered by tying them down to GND. attention: It is not allowed to lengthen the pre-connected wires!

NOX data sheets, December 03, p 12 of 12