Sei sulla pagina 1di 38

P1433/D5A, July 15, 1999

P1433/D5A A Draft Standard Glossary of Power Quality Terminology

Prepared by the Working Group on Power Quality Definitions of SCC22 - Power Quality

Copyright 1999 by the Institute of Electrical and Electronics Engineers, Inc 345 East 47th Street New York, NY 10017, USA All Rights Reserved This is an unapproved draft of a proposed IEEE Standard, subject to change. Permission is hereby granted for IEEE Standards Committee participants to reproduce this document for purposes of IEEE standardization activities. Permission is also granted for member bodies and technical committees of ISO and IEC to reproduce this document for the purposes of developing a national position. Other entities seeking permission to reproduce this document for standardization or other activities, or to reproduce portions of this document for these or other uses, must contact the IEEE Standards Department for the appropriate license. Use of information contained in this unapproved draft is at your own risk. IEEE Standards Department Copyright and Permissions 445 Hoes Lane, P. O. Box 1331 Piscataway, NJ 08855-1331, USA

Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

P1433/D5A, July 15, 1999

Introduction
An introduction should be supplied by the working group, giving the history of the standard, a description of its purpose, and if the standard if a revision, an explanation of the principal changes from the previous edition. An introduction is not a part of a proposed standard; therefore, the following statement shall appear above the text: (This introduction is not part of IEEE P1433, A Standard Glossary of Power Quality Terminology.)

1
Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

P1433/D5A, July 15, 1999

Participants
At the time this recommended practice was completed, the Working Group on Power Quality Definitions had the following membership: Philip P. Barker, Co-Chair Timothy Unruh, Co-Chair

The following persons were on the balloting committee: (to be supplied by IEEE)

2
Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

P1433/D5A, July 15, 1999

Contents
1. 1.1 1.2 2. 3. 3.1 3.2 4. Overview .............................................................................................................................................................. 4 Scope................................................................................................................................................................ 4 Purpose ............................................................................................................................................................ 4 References ............................................................................................................................................................ 5 Power quality definitions...................................................................................................................................... 6 Introduction...................................................................................................................................................... 6 Definitions and applications............................................................................................................................. 6 Bibliography....................................................................................................................................................... 37

Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

P1433/D5A, July 15, 1999

A Draft Standard Glossary of Power Quality Terminology

1.
1.1

Overview
Scope

This Standard Glossary of Terminology encompasses the power quality terminology to be used to describe the electrical power quality conditions and phenomena occurring on single-phase and polyphase ac power systems. As such, it includes consistent descriptions of electromagnetic phenomena occurring on power systems. The document also presents definitions of nominal conditions and of deviations from these nominal conditions which may originate within the source of supply or load equipment, or from interactions between the source and the load. In addition to the standard definitions which are to be utilized by other documents, this standard contains detailed descriptions of the terminology which includes graphical information, as well as typical occurrence situations. This additional information is to facilitate the introduction to the electrical quality subject and to provide detailed applications information to assist in event categorization. Included in this standard are definitions that range from the expected electrical system delivery quality to the performance of equipment when receiving electrical power. Also included are definitions that cross over from the reliability area, but are not typically associated with electrical quality. Finally, the definitions are solely intended to characterize common electromagnetic phenomena to facilitate communication between various sectors of the power quality community. The definitions are not intended to represent performance standards or equipment tolerances. For example, suppliers of electricity may utilize different thresholds for voltage supply than indicated in these definitions. Further, sensitive equipment may malfunction due to electromagnetic phenomena not outside the thresholds described in this document and thus these definitions do not in themselves constitute a means of achieving trouble free operation of loads and equipment.

1.2

Purpose

The purpose of this standard is to provide a concise listing of definitions to electrical power quality phenomena. The user is provided with the classic definition format, but is also provided with a detailed instructional description of the phenomena previously defined.

Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

P1433/D5A, July 15, 1999

2.

References

This standard shall be used in conjunction with the following publications. When the following standards are superseded by an approved revision, the revision shall apply. [1] IEC 1000-2-1 - Electromagnetic Compatibility (EMC) - Part 2 Environment, "Description of the Environment -- Electromagnetic Environment for Low Frequency Conducted Disturbances and Signaling in Public Power Supply Systems," Section 1, 1990. IEC 50(161)(1990) - International Electrotechnical Vocabulary, Chapter 161: Compatibility. Electromagnetic

[2] [3] [4] [5] [6] [7] [8] [9] [10] [11] [12]

IEEE STD 100-1992, IEEE Standard Dictionary of Electrical and Electronic Terms (ANSI). IEEE Standard 1100-1992, Recommended Practice for Powering and Grounding Sensitive Electronic Equipment. (Emerald Book). IEEE STD 1159-1995, IEEE Recommended Practice for Monitoring Electric Power Quality. IEEE STD 1250-1995, IEEE Guide for Service to Equipment Sensitive to Momentary Voltage Disturbances. IEEE STD 1346-1998, IEEE Recommended Practice for Evaluating Electric Power System Compatibility With Electronic Process Equipment. IEEE STD 519-1992, IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems. IEEE STD 142-1991, IEEE Recommended Practice for Grounding of Industrial and Commercial Power Systems. (Green Book) IEEE STD 446-1995, IEEE Recommended Practice for Emergency and Standby Power Systems for Industrial and Commercial Applications. (Orange Book). IEEE STD 141-1993, IEEE Recommended Practice for Electric Power Distribution for Industrial Plants. (Red Book). IEEE C62.22-1991, IEEE Guide for the Application of Metal-Oxide Surge Arresters for AlternatingCurrent Systems.

IEC Publications are available from IEC Sales Department, Case Postale 131, 3 rue de Varembe, CH 1211, Geneve 20, Switzerland/Suisse. IEC publications are also available in the United States from the Sales Department, American National Standards Institute, 11 West 42nd Street, 13th Floor, New York, NY 10036. Telephone: (212) 642-4900. IEEE publications are available from the Institute of Electrical and Electronics Engineers, Service Center, 445 Hoes Lane, Post Office Box 1331, Piscataway, NJ 08855-1331, USA. Telephone: (212) 705-7900. ANSI publications are available from the Sales Department, American National Standards Institute, 11 West 42nd Street, 13th Floor, New York, NY 10036, USA. Telephone: (212) 642-4900. Federal Information Processing Standards (FIPS) documents are available from the National Technical Information Services (NITS), United States Department of Commerce, 5285 Port Royal Road, Springfield, VA 22161. Telephone: (703) 487-4650.

Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

P1433/D5A, July 15, 1999

UIE publications are available from the Union Internationale de Electrothermie, Tour Atlantiquee F - 92 0A0 Paris Ladefense Cedex 06 France. Telephone: 011 331 41 26 56 48, Fax: 011 331 41 26 56 49. Basic Measuring Instruments publications are available from BMI -- Order Administration, 3250 Jay Street, Santa Clara, CA 95054. Telephone: 1-800-876-5355. Dranetz Technologies publications are available from Dranetz Technologies Incorporated, 1000 New Durham Road, Edison, NJ 08818. Telephone: (908) 287-3580.

3.
3.1

Power quality definitions


Introduction

This section provides the accepted IEEE definition of each power quality term and a brief description of how it is applied. Diagrams are used where appropriate to help clarify the application of the terms. The application description is preceded by the accepted definition.

3.2

Definitions and applications

3.2.1 arrester discharge current The current that flows through an arrester due to a surge. Source: [12] The term arrester discharge current may be used to refer to a condition imposed on an arrester due to either lightning or switching surges occurring on the power system. It may also be in reference to a standard test waveshape which is used to characterize arrester protective levels [the amount of voltage occurring across the arrester during a discharge]. Typically, arresters are tested with various waveshapes such as the 8/20 microsecond IEEE standard test wave as defined in IEEE Standard 4-1992 and C62. For medium and higher voltage arresters, these tests are usually performed at levels of 1.5, 5, 10, 20, and 40 kA. Arrester discharge currents caused by lightning will vary greatly depending location of the arrester, the power system Basic Lightning Impulse Insulation Level (BIL) rating and interconnection configuration, the location of the lightning strike and many other factors. Arrester discharge currents due to lightning on typical medium voltage distribution circuits are typically less than 30 kA. Arrester discharge currents for low voltage circuits [600 volts or less] are usually much less than 10 kA but might occasionally be higher under unusual circumstances. Switching surge currents are ordinarily less than one thousand amperes on distribution circuits. 3.2.2 arrester discharge voltage The voltage that appears across the terminals of an arrester during the passage of discharge current. Source: [12] This is the voltage due to the discharge current encountering the impedance of the device and is measured across the terminals. If the device has series spark gaps which normally flashover as part of its operation, then it is the voltage across the device following flashover of the gap and thus includes only the impedance voltage of the arrester current conducting elements [e.g. the Silicon Carbide (SiC) or Metal-Oxide Varister (MOV) block materials]. Arresters composed of Silicon Carbide have spark gaps and their performance must be defined by a sparkover voltage as well as a discharge voltage. Figure 1 shows an example of an arrester discharge voltage, while Figure 2 shows an ungapped and gapped voltage response.

Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

P1433/D5A, July 15, 1999

2.0

34.5 kV Bus Voltage Capacitor Switching Transien


1.5

Voltage (V pu)

1.0

0.5

0.0

-0.5

-1.0

-1.5 0 20 40 60 80 100

Time (mS)

Figure 1Example of an arrester discharge voltage

Arrester Sparkover Voltage Crest Arrester Discharge Voltage Crest Arrester Discharge Voltage

V Ungapped MOV time Gapped SiC

time

Figure 2Discharge voltage waveforms for gapped and ungapped arresters 3.2.3 basic lightning impulse insulation level (BIL) A specific insulation level expressed in terms of the crest value of a standard lightning impulse. Source: [12] A reference impulse insulation strength expressed in terms of the crest value of withstand voltage of standard full impulse voltage level. The BIL may be either a conventional or a statistical BIL. In the case of conventional BIL the test object must demonstrate that it can survive several consecutive impulse test waves without flashover or damage to the insulation. In the case of statistical BIL, the test object, such as a line post insulator, is subjected to 10 impulse test waves and must not flashover 9 out of 10 times. Thus, an insulator just barely passing the statistical BIL test has a 10% probability of flashover at its rated BIL. Statistical BIL is usually used for air insulated devices and conventional BIL is used for devices such as oil filled transformers. The BIL is evaluated using a 1.2/50 microsecond test wave as shown below in Figure 3. BILs are much higher than 60 Hz rated withstand values due to the short duration nature of the surge voltage. The BIL is intended to provide a test for the response of power system equipment and line insulation to lightning surges. BILs of 15, 25 and 35 kV class distribution line equipment are 95, 125 and 150 kV respectively. Low voltage circuits typically have BILs less than 6 kV and load equipment may often be damaged at much lower surge levels.

Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

P1433/D5A, July 15, 1999

Volts
Vcrest 0.5Vcrest 1.2 50

time in microseconds
Figure 3The BIL 1.2/50 test wave is intended to represent a typical lightning transient voltage and has a virtual front time of 1.2 microseconds and decays to 50% of its crest value in 50 microseconds 3.2.4 charge voltage The voltage difference between the intruder and the receptor just prior to Electrostatic Discharge (ESD). Source: [??] As an example, the classic case is a person walking across a carpeted area, and developing a substantial static charge on the body as shown in Figure 4. Any device that is subsequently contacted by that person, could receive a substantial ESD discharge on the order of 5-30 kV. The charge voltage is the potential difference between the individual and the electronic device at the instant prior to contact with the device or prior to breakdown of the insulating air path leading to the device.
15 kV potential difference

Sensitive Electronic Device

+ + ++ + + + + + + + + + + +

Carpet

Figure 4Classic example of ESD involving carpet and sensitive electronic device 3.2.5 common mode voltage A voltage that appears between current-carrying conductors and ground. Source: [2] The noise voltage that appears equally and in phase from each current-carrying conductor to ground. Source: [4] Consider the case of a power circuit consisting of one or more phases, a neutral and a ground wire. It is possible for the ungrounded current-carrying conductors to assume undesired equal and in phase potentials such that no significant undesired voltage, would be measured between these conductors. However, a substantial undesired voltage could exist between the ungrounded current carrying conductors and ground. Common mode voltages may be steady state and of very long duration, noise or may be short duration transients due to lightning and other surge phenomenon. Figure 5 displays an example of common mode voltage.

Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

P1433/D5A, July 15, 1999

Phase A Phase B Phase C


Common mode voltage on current carrying conductors Vnoise Phase-to-Phase small

Building Service

Neutral Ground

Vnoise Phase-to-Ground large

Figure 5Typical common mode voltage conditions 3.2.6 commercial power Electrical power furnished by the electric power utility company. Source: [4] Commercial power is typically referred to as the normal power that is supplied by the incoming feeders. This in some cases may include some portion of generated power from local generators supplied by natural gas, diesel fuel or coal. Generally, the incoming service power is regarded as commercial power when it is connected to the electric power utility feeders regardless of the percentage of power that is supplied by the electric power utility and the percentage supplied by local generation at the end-users location. The case of non-commercial power would refer to an isolated generation unit supplying power to the end-user site, without the voltage and frequency support inherent in a connection to an electric power utility. In addition, noncommercial power could refer to the case of power supplied through alternate means, such as an uninterruptible power supply or other energy storage system that supplies 100% of the electrical power requirements of a circuit without a connection to the electric power utility. 3.2.7 coupling Circuit element or elements, or network, that may be considered common to the input mesh and the output mesh and through which energy may be transferred from one to the other. Source [4] Often coupling is used in the power quality industry to describe a condition where the electrical characteristics of one circuit are imposed upon another separate circuit. For example, when a communication cable is run with electrical power circuit conductors, there is a possibility that transient phenomena on the electrical power circuit conductors will be imposed (coupled) upon the communication cable. In this case, the imposed transient phenomena may disrupt the communication signal, causing the source to re-send, and lowering data throughput. In another example of coupling, consider a computer monitor placed at a workstation directly below an undercabinet fluorescent lamp. In many cases, the electrical circuit of the fluorescent lamp can impose unwanted steady state variations into the computer monitor circuit, causing the screen to be unsteady. In this case, we could describe the circuits as coupled, as energy is being transferred from one to another. In the uses of coupling related to power quality, generally, it is in reference to an unwanted coupling that occurs. However, in the case where the primary and secondary circuits of a transformer are coupled, this is a desired occurrence of coupling.

Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

P1433/D5A, July 15, 1999

3.2.8

dip

See: sag. 3.2.9 distortion factor (harmonic factor) The ratio of the root-mean-square of the harmonic content to the root-mean-square value of the fundamental quantity, expressed as a percent of the fundamental. Source: [8]

sum of .......... squares of amplitudes of all .......... harmonics .......... .......... .......... ....

DF =

100%

square of amplitude of fundamental

See also: total harmonic distortion. 3.2.10 dropout A loss of equipment operation (discrete data signals) due to noise, sag, or interruption. Source [4] Digital circuits are much more susceptible to being altered by disturbances on the electrical distribution system during what is called transition. This is a brief moment between one binary state and another, when the circuit elements are virtually unclamped in either the true or false state. A disturbance occurring during the moment of transition can either reinforce or reverse the intended signal. Figure 6 shows the transition portion of a digital series of signals, and demonstrates the change due to a dropout. CHANGE THIS FIGURE!!!!! REMOVE THE RIGHT SECTION

Control Circuits
Data Transmission Path

Intended Signal

M
Missing Data Bit

Received Signal

Mechanical Load

Figure 6 An example of dropout on a digital signal to a control circuit 3.2.11 dropout voltage

Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

10

P1433/D5A, July 15, 1999

The voltage at which a device fails to operate. Source: [4] The dropout voltage is not to be confused with a dropout, defined above. Dropout voltage refers to the complete loss of equipment operation due to an event typically described as an undervoltage or sag. Where the term dropout refers specifically to the loss of a discrete digital signal on a communication path, the dropout voltage refers to the voltage at which complete device operation is halted. The device does not necessary need to have a discrete communication function, but it is not excluded. Equipment may cease operation at the dropout voltage for a variety of reasons. Typically, the dropout voltage refers to a low voltage condition. In the case of a voltage sag, often the dropout voltage will be accompanied by a duration that must transpire at the sag voltage for equipment to cease operation. In many cases, where the equipment is electronic in nature, a power supply consisting of diodes and capacitors performs an energy storage function for the equipment. The system components will only continue operation as long as the power supply is able to supply the internal voltage. Therefore, the dropout voltage is often a description of power supply performance for electronic equipment. A common tool that is used to evaluate equipment performance within a certain environment is the Computer Business Equipment Manufacturers Association (CBEMA) curve. While the data shown in the curve was specifically developed for data processing equipment, it provides some insight into the operation of equipment supplied through a switched-mode power supply. Figure 7 shows the CBEMA curve.

Figure 7 The CBEMA Curve, as found in IEEE STD 446-1995. 3.2.12 electromagnetic compatibility The ability of a device, equipment or system to function satisfactorily in its electromagnetic environment without introducing intolerable electromagnetic disturbances to anything in that environment. Source: [2] 3.2.13 electromagnetic disturbance Any electromagnetic phenomena which may degrade the performance of a device, equipment, or system, or adversely affect living or inert matter. Source: [2] This is a very broad term and electromagnetic disturbances may involve both conducted and radiated signals of an electromagnetic origin. Examples include radio frequency signals from broadcast facilities, radio frequency interference from devices with oscillators or digital clocking circuits (computers, digital recording and playback equipment, communications equipment), electric and magnetic fields from power lines, noise which is conducted along conductors or radiated due to corona discharge and partial breakdown, lightning strikes (which have strong fields associated with them), and many other phenomena. As an example, a cloud-to-ground lightning flash involves
Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

11

P1433/D5A, July 15, 1999

a massive electrical breakdown of the air dieletric between cloud and ground. This breakdown and the subsequent flow of charge produces strong localized time changing electric and magnetic fields as well as somewhat weaker radiated electromagnetic waves with a broad band characteristics stretching from a few kilohertz up to hundreds of megahertz. These fields can cause problems for power systems and devices, especially those within 1 km of the flash location. 3.2.14 electromagnetic environment The totality of electromagnetic phenomena existing at a given location. Source: [2] This is the environment to which a system or device is exposed and considers all phenomena likely to be encountered at that location during its lifetime. For example, the electromagnetic environment for outdoor bus support mounted electronic equipment at a substation is radically different than that for an office computer deep within a commercial facility. The substation equipment will need to deal with strong power frequency fields due current flow through nearby bus-work. It may also be exposed to power line carrier signals, lightning fields and surges, and radio frequency noise due to corona discharge. The office computer deep within the office building would not likely be exposed to lightning fields or strong power frequency fields. 3.2.15 electromagnetic susceptibility The inability of a device, equipment, or system to perform without degradation in the presence of an electromagnetic disturbance. NOTESusceptibility is a lack of immunity. Source: [2] This occurs when the fields due to an electromagnetic disturbance couple into the device or system in a manner which produces internal voltages and/or currents which cause it to operate improperly. For a device to properly operate in its intended working environment, it should be capable of handling the electromagnetic environment in which it is to be placed. A careful review of the types of fields and disturbances likely to occur at the equipment location should be performed. As an example, a sensitive monitoring instrument placed in a insulating enclosure (PVC plastic) and mounted near heavy current carrying conductors may not be adequately shielded from the magnetic fields of these conductors to operate properly. Methods to reduce susceptibility of devices usually involve shielding them from externally imposed fields with metal shields or enclosures. It also is important to shield all control, data and power supply entry cables or perhaps use filtering and/or surge suppression at these points to avoid entry of electromagnetic signals into the device. See also: immunity. 3.2.16 electrostatic discharge (ESD) The sudden transfer of charge between bodies of differing electrostatic potentials. Source: [??] See also: charge voltage. 3.2.17 equipment grounding conductor The conductor used to connect the noncurrent-carrying parts of conduits, raceways, and equipment enclosures to the grounded conductor (neutral) and the grounding electrode at the service equipment (main panel) or secondary of a separately derived system (e.g., isolation transformer). Source: [5] When referring to the ground of a system, many physical structures are associated with this term. When referring to the conductor that will carry fault current through a system, typically, the equipment grounding conductor will perform that function. While the term ground often is interpreted as earth ground, in reality, the earth often is not the desired path for conduction of fault current in the event of a fault. Figure 8 shows the various conductors and physical structures associated with a three-phase installation. In many cases, the metal conduit will serve as the equipment grounding conductor for the circuit, while the conduit will contain four conductors in the example. The neutral is termed the grounded conductor, as it is grounded at the service entrance, but still is intentioned to carry normal circuit current. Whereas the equipment grounding conductor is also grounded at the service entrance, it is
Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

12

P1433/D5A, July 15, 1999

not intentioned to carry normal circuit current, but is only to carry fault current to clear a breaker in the event of a fault.
Phase A Phase B Phase C
Unbalanced return current (zero sequence)

Main Service Panel

Neutral (Grounded Conductor) Equipment Grounding Conductor

Figure 8The equipment grounding conductor will connect the ground bus of the main service panel and the equipment chassis 3.2.18 failure mode The effect by which failure is observed. Source: [3] This term essentially is the way, or mode, in which the equipment fails. Where some equipment may fail in a destructive mode, where the equipment itself is destroyed, other equipment may fail by ceasing operations. Properly observing the failure mode of equipment enables further clues to be gathered related to the cause of the equipment failure. For example, when an adjustable speed drive has failed, often, the failure mode is recorded in the system electronics, and displayed to the user. The drive may fail for a number of reasons, including low DC bus voltage, high DC bus voltage, improper frequency, etc., where each failure mode typically will correspond to a particular cause of failure or power quality issue. 3.2.19 flicker Impression of unsteadiness of visual sensation induced by a light stimulus whose luminance or spectral distribution fluctuates with time. Source [2] See also: voltage fluctuation for power quality causes of flicker. Flicker on a power system refers to the varying luminance of light sources under conditions of varying supply voltage levels. Causes of voltage flicker include arc furnaces, motor starts and cycling on/off of large loads. The human eye has the greatest sensitivity to flicker in the range of 5-10 Hertz where even a small change of about 1/2% of nominal voltage can be perceived by the eye. Several curves are used in the industry which plot the human eye sensitivity to flicker versus the frequency of occurrence. A curve known as the GE flicker curve is commonly used as a guide to determine the seriousness of a flicker condition. A typical flicker voltage condition is shown in Figure 9.

Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

13

P1433/D5A, July 15, 1999

RMS Voltage % of nominal


100

System voltage with flicker

Ideal Voltage (no flicker)

0 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0

Time (seconds)

Figure 9Voltage flicker 3.2.20 frequency deviation An increase or decrease in the power frequency. The duration of a frequency deviation can be from several cycles to several hours. Syn.: power frequency variation. Source: [4] Frequency deviations are defined as the deviation of the power system fundamental frequency from its specified nominal value (e.g. 50 Hz or 60 Hz). The power system frequency is directly related to the rotational speed of the generators on the system. At any instant, the frequency depends on the balance between the load and the capacity of the available generation. When this dynamic balance changes, small changes in frequency occur. The size of the frequency shift and its duration depends on the load characteristics and the response of the generation system to load changes. Frequency variations that go outside of accepted limits for normal steady state operation of the power system are normally caused by faults on the bulk power transmission system, a large block of load being disconnected, or a large source of generation going off-line. Frequency variations that affect the operation of rotating machinery, or processes which derive their timing from the power frequency (clocks), are rare on modern interconnected power systems. Frequency variations of consequence are much more likely to occur when such equipment is powered by a generator isolated from the utility system. In such cases, governor response to abrupt load changes may not be adequate to regulate within the narrow bandwidth required by frequency sensitive equipment. NOTEVoltage notching can sometimes cause frequency or timing errors on power electronic machines that count zero
crossings to derive frequency or time. The voltage notch may produce additional zero crossings which can cause frequency or timing errors. A small frequency disturbance is shown in Figure 10.

Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

14

P1433/D5A, July 15, 1999

System Frequency Disturbance

Frequency Hertz

60

50 0 1 2 3 4 5 6 7 8 9 10

Time (seconds)

Figure 10System frequency disturbance 3.2.21 fundamental (component) The component of an order 1 (50 or 60 Hz) of the Fourier series of a periodic quantity. Source: [2] See also: harmonic component. The fundamental component refers to the expected power system signal when referring to power quality issues. For current and voltage in the United State, the fundamental component of the power delivered is 60 hertz. In reality, the delivered voltage and current drawn by a user is often not a pure sine wave. In these cases, mathematics provides the Fourier Transform to describe the components of a non-sinusoidal waveform. The result of a Fourier Transform mathematical operation on a continuous (not discrete) waveform is a Fourier Series. A Fourier Series is a representation of the discrete frequencies that compose the non-sinusoidal waveform. The zero component of the series is the direct current or DC component, and the first component is the fundamental component. 3.2.22 ground A conducting connection, whether intentional or accidental, by which an electric circuit or piece of equipment is connected to the earth, or to some conducting body of relatively large extent that serves in place of the earth. NOTEIt is used for establishing and maintaining the potential of the earth (or of the conducting body) or approximately that
potential, on conductors connected to it, and for conducting ground currents to and from earth (or the conducting body). Source: [3]

The ground is essentially the connection to the earth, or something that takes the place of the earth, such as building steel or metal water piping. A ground connection is typically found at a main service entrance, and at a separately derived system (transformer location). A ground is established for lightning protection and for a zero volt reference. The ground is not to be confused with the equipment grounding conductor, which connects the equipment (end-use equipment such as computers, machinery, etc.) to the ground bus or the neutral-ground bond within a transformer. In a properly installed electrical system, fault current is not carried by the ground, but by the equipment grounding conductor. Therefore, in a properly installed electrical system, fault clearing has no relationship to the ground, or earth connection.

Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

15

P1433/D5A, July 15, 1999

3.2.23 ground loop In a radial grounding system, an undesired conducting path between two conductive bodies that are already connected to a common (single-point) ground. Source: [5] A ground loop consists of a parallel path of return current exists. In Figure 11, an improper neutral-ground bond has been made in the sub-panel. Since this panel is not a separately derived system, this bond is a violation of the National Electrical Code, and establishes a ground loop. When a piece of equipment is operating from the subpanel, return current that should flow on the neutral conductor, instead divides, and flows on both the neutral conductor and the conduit (the ground path in this case). The equipment grounding conductor of the end-use equipment connects to the equipment grounding bus, which in turn connects to the panel frame, and eventually, the conduit. Since the conduit will have an impedance, and current is flowing, the equipment grounding conductor is subjected to a voltage. Normal operation assumes that the equipment grounding conductor is supplying a zero (or near zero) voltage reference to the equipment. Since current is flowing on the ground path for the sub-panel, voltage is present on the equipment grounding conductor. This voltage can and often does cause equipment failure. An additional cause of voltage on the equipment grounding conductor due to a ground loop is noise voltage. Since a complete loop is established from the main panel to the sub-panel (through the conduit, the improper neutral-ground connection, the main panel neutral-ground bond, and the neutral to the sub-panel), current can flow on this loop within the system. This ground loop can have current induced by nearby current flows, and current flows in the earth. This small amount of current flow causes a small amount of voltage to be formed that is non-sinusoidal, and is a noise voltage in nature. This noise voltage can and often does cause equipment failure.
Power Conductor Ground Neutral

Main Service Panel


Service Cable Leg A Leg B Service Neutral Neutral & Ground Bonded at Grounding Bar Main Breaker
Incorrect bonding jumper between neutral & ground

Sub-Panel
Neutral Bar

Load

Subpanel Breaker

Some neutral current flows back through this ground loop Branch Circuit Breakers

Load exposed to raised ground poetetial due to incorrect neutral bonding at Sub-panel!

Service Ground

Branch Circuit Breakers

Figure 11Ground loop example

Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

16

P1433/D5A, July 15, 1999

3.2.24 harmonic (component) A component of order greater than one of the Fourier series of a periodic quantity. Source: [2] Harmonics are sinusoidal voltages or currents having frequencies that are integer multiples of the frequency at which the supply system is designed to operate (termed the fundamental component, usually 50 Hz or 60 Hz). Harmonics combine with the fundamental voltage or current, and produce waveform distortion. Harmonic distortion exists due to the nonlinear characteristics of devices and loads on the power system. Nonlinear devices can usually be modeled as current sources that inject harmonic currents into the power system. Voltage distortion results as these currents cause nonlinear voltage drops across the system impedance. Harmonic distortion is a growing concern for many customers and for the overall power system due to increasing application of power electronics equipment. Harmonic distortion levels can be characterized by the complete harmonic spectrum with magnitudes and phase angles of each individual harmonic component. It is also common to use a single quantity, termed the Total Harmonic Distortion or the Distortion Factor, as a measure of the magnitude of harmonic distortion. Harmonic currents result from the normal operation of nonlinear devices on the power system. Figure 12 illustrates the waveform and harmonic spectrum for a typical adjustable speed drive input current. Current distortion levels can be characterized by a total harmonic distortion value, as described above, but this can often be misleading. For instance, many adjustable speed drives will exhibit high total harmonic distortion for the input current when they are operating at very light loads. This is not a significant concern because the magnitude of harmonic current is low, even though its relative distortion is high. To handle this concern for characterizing harmonic currents in a consistent fashion, IEEE 519-1992 defines another term, the Total Demand Distortion. This term is the same as the total harmonic distortion except that the distortion is expressed as a percent of the maximum demand load current rather than as a percent of the fundamental component of the current. IEEE 519-1992 provides guidelines for harmonic current and voltage distortion levels on distribution and transmission circuits.
PWMASD45>VSRCA -BUSA
70

(Type 9)
Max: Min: Avg: Abs: RMS: CF : FF : 313.907 -171.704 33.5332 313.907 64.3862 4.87537 1.92007

Current (A)

50 30 10 -10 -30 -50 40

50

60

70

80

Time (mS)

DERIVED>VSRCA -BUSA
20

(Type 9)(2)
Freq: Fund: THD : RMSh: RMS : ASUM: TIF : IT : 60 19.4713 41.0054 7.98431 21.0448 37.3698 427.213 8990.61

Current (A)

15

ASD Input Current


10

0 0 600 1200 1800

Frequency (Hz)

Figure 12Current waveform and harmonic spectrum for an adjustable speed drive input current

Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

17

P1433/D5A, July 15, 1999

3.2.25 harmonic content The quantity obtained by subtracting the fundamental component from an alternating quantity. Source: [3] An alternating quantity is expressed in the Fourier Series that describes the frequency components of the system. The series is typically a series of sinusoidal functions of differing frequencies and magnitudes. The harmonic content of the waveform is found by subtracting the fundamental component (order 1 component) from the Fourier series components. Typically, the harmonic content is also considered to have no direct current or DC (order 0) component. 3.2.26 immunity (to a disturbance) The ability of a device, equipment or system to perform without degradation in the presence of an electromagnetic disturbance. Source: [2] Immunity refers to the opposite case of electromagnetic susceptibility. The susceptibility refers to the inability of the device to operate in the presence of an electromagnetic disturbance. See also: electromagnetic susceptibility. 3.2.27 impulse A pulse that, for a given application, approximates a unit pulse. Source: [2] When used in relation to the monitoring of power quality, it is preferred to use the term impulsive transient in place of impulse. Source: [5] See also: transient; impulsive transient. 3.2.28 impulsive transient A sudden non-power frequency change in the steady-state condition of voltage or current that is unidirectional in polarity (primarily either positive or negative). Source: [5] See also: transient; impulse. Impulsive transients are normally characterized by their rise and decay times. These phenomena can also be described by their spectral content. For example, a 1.2/50 microsecond 2,000 V impulsive transient rises to its peak value of 2,000 V in 1.2 microseconds, and then decays to half its peak value in 50 microseconds. See the definition for basic lightning impulse insulation level (BIL) for more information regarding the waveform. 3.2.29 instantaneous A time range from 0.5-30 cycles of the power frequency when used to quantify the duration of a short duration variation as a modifier. Source: [5] An instantaneous variation is of the category of a short duration variation. An instantaneous variation may take the form of an interruption (Source: [6]), sag or swell, depending upon the magnitude of the variation. Table 1 shows the typical magnitudes of various instantaneous variations. See also: voltage variation, short duration.

Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

18

P1433/D5A, July 15, 1999

Table 1Typical magnitudes for instantaneous short duration variations Instantaneous Variation 0.5 cycles < x < 30 cycles Interruption Sag Swell < 0.1 pu 0.1 pu < x < 0.9 pu 1.1 pu < x < 1.8 pu

Magnitudes

3.2.30 interharmonic (component) A frequency component of a periodic quantity that is not an integer multiple of the frequency at which the supply system is designed to operate (e.g., 50 Hz or 60 Hz). Source: [5] See also: waveform distortion. Interharmonics are typically caused by static power converters, induction motors, and arcing devices. The frequency of the interharmonic may appear as a single discrete frequency (induction motors) or could appear as a widespectrum distribution of many frequencies (arcing device). 3.2.31 interruption, forced An interruption that results from conditions directly associated with a component requiring that it be taken out of service immediately, either automatically or as soon as switching operations can be performed, or an interruption caused by improper operation of equipment or human error. NOTEThis definition derives from transmission and distribution applications and does not necessarily apply to generation
interruptions. Source: [??]

3.2.32 interruption, momentary (power quality monitoring) A type of short duration variation. The complete loss of voltage (<0.1 pu) on one or more phase conductors for a time period between 0.5 cycles and 3 s. Source: [5] Momentary interruptions on utility systems are often due to automatic circuit reclosing practices which are employed to clear temporary faults on the power system. With automatic circuit reclosing, a faulted line is de-energized for a short period of time (often referred to as the dead time) and is then re-energized. The dead time period allows the fault to be cleared and all ionization in the air to dissipate. Practices vary greatly from utility to utility with some utilities employing dead times as short as 12 cycles and others employing dead times of up to 1 minute. When dead times are as fast as the reclosing device will allow, these are typically called instantaneous reclose operations and they usually involve a dead time less than 1 second. Note that many utilities employ dead time sufficiently long that these would cause temporary and not momentary interruptions (See: interruption, temporary). Other causes of momentary interruptions include mechanical transfer switches (switching a load from one source to another), poor intermittent connections, and faults adjacent to the load which sag the voltage to essentially zero volts (less than 0.1 pu). 3.2.33 interruption, sustained (electric power systems) Any interruption not classified as a momentary interruption. Source: [5] The decrease of the supply voltage to essentially zero volts (less than 0.1 pu) for a period of time in excess of 1 minute is considered a sustained interruption. A sustained interruption is of the category of a long duration voltage variation. Voltage interruptions longer than one minute are often permanent in nature and require manual
Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

19

P1433/D5A, July 15, 1999

intervention for restoration. Sustained interruptions are a specific power system phenomena and have no relation to the usage of the term outage. Outage, as defined in IEEE-100, does not refer to a specific phenomena, but rather to the state of a component in a system that has failed to function as expected. Also, use of the term interruption in the context of power quality monitoring has no relation to reliability or other continuity of service statistics. 3.2.34 interruption, temporary (power quality monitoring) A type of short duration variation. The complete loss of voltage (<0.1 pu) on one or more phase conductors for a time period between 3 s and 1 min. Temporary interruptions are caused by the same general phenomena as momentary interruptions. Table 2 provides a description of each of the types of interruption. Table 2Comparison of the various types of interruptions Type instantaneous interruption momentary interruption temporary interruption sustained interruption Duration 0.5 cycles < x < 30 cycles 30 cycles < x < 3 seconds 3 seconds < x < 1 minute x > 1 minute

3.2.35 isolated ground An insulated equipment grounding conductor run in the same conduit or raceway as the supply conductors. This conductor may be insulated from the metallic raceway and all ground points throughout its length. It originates at an isolated ground-type receptacle or equipment input terminal block and terminates at the point where neutral and ground are bonded at the power source. Source: [5] An isolated ground is not specifically defined in the national electrical code, but is allowed through exceptions within the code (Section 250-74, Exception #4 and Exception in Section 250-75 in ANSI/NFPA 70-1996). The purpose of an isolated ground is to provide a dedicated ground for equipment. An isolated ground may provide some protection from noise and other voltages on a non-isolated equipment grounding conductor. An isolated ground is allowed to pass through several sub-panels until reaching the main service panel, where connection to the ground bus is completed as shown in Figure 13.

Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

20

P1433/D5A, July 15, 1999

Figure 13Isolated ground description 3.2.36 isolation Separation of one section of a system from undesired influences of other sections. Source: [4] Isolation often occurs in the form of shielding, however, isolation can refer to basic separation of two sections or components by physical distance. 3.2.37 linear load An electrical load device which, in steady state operation, presents an essentially constant load impedance to the power source throughout the cycle of applied voltage. Source: [4] Resistors, capacitors and non-saturable inductors are essentially linear loads. Non-linear loads include devices such as saturable inductors and transformers, solid state switching devices like SCRs (silicon controlled rectifiers), IGBTs (Insulated gate bipolar transistors), and diodes. 3.2.38 See: long duration voltage variation voltage variation, long duration.

3.2.39 loss of service The loss of electrical power, a complete loss of voltage to one or more customers or meters. This does not include any of the power quality issues; sags, swells, impulses, or harmonics. Source: [??] A loss of service implies that no voltage is present at the incoming connection between the energy user and the electric power utility. A sustained interruption is an event that is similar to the loss of service, however, loss of service implies that no voltage is present, where interruption implies that a small, but inconsequential (< 0.1 pu) of voltage may remain on the incoming lines.

Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

21

P1433/D5A, July 15, 1999

3.2.40 momentary (power quality monitoring) A time range at the power frequency from 30 cycles to 3 s when used to quantify the duration of a short duration variation as a modifier. Source: [5] A momentary variation is of the category of a short duration variation. An instantaneous variation may take the form of an interruption, sag or swell, depending upon the magnitude of the variation. Table 3 shows the relative magnitudes of the various momentary variations. See also: voltage variation, short duration. Table 3Typical magnitudes of momentary short duration variations.

Momentary Variation 30 cycles < x < 3 seconds Interruption Sag Swell

Magnitudes

< 0.1 pu 0.1 pu < x < 0.9 pu 1.1 pu < x < 1.8 pu

3.2.41

momentary interruption

See: interruption, momentary. 3.2.42 noise Unwanted electrical signals which produce undesirable effects in the circuits of the control systems in which they occur. (For this document, control systems is intended to include sensitive electronic equipment in total or in part.) Source: [3] See also: waveform distortion. Noise can constitute electrical signals that are propagated on an electrical circuit conductor, or those radiated electromagnetically through the environment. For example, noise may be introduced through coupling of one circuit to another where there is no physical connection between the two circuits. In addition, noise may be found on the equipment grounding conductor of a circuit caused by the operation of a device drawing a large current. 3.2.43 nominal voltage (Vn) A nominal value assigned to a circuit or system for the purpose of conveniently designating its voltage class (as 208/120, 480/277, 600). Source: [1] ANSI/IEEE standard C84.1 specifies common nominal voltage ratings of AC power systems and also includes tolerance limits above and below the nominal voltage for which systems are intended to operate. For example ANSI C84.1 range A standards indicated the voltage should be maintained by the utility at the service entrance within +5% of the nominal system voltage. For a system with a nominal voltage rating of 120 volts, this translates into a 114126 volt range.

Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

22

P1433/D5A, July 15, 1999

3.2.44 nonlinear load Steady state electrical load which draws current discontinuously or whose impedance varies throughout the cycle of the input ac voltage waveform. Source: [4] Non-linear loads include devices such as saturable inductors and transformers, solid state switching devices like SCRs (silicon controlled rectifiers), IGBTs (Insulated gate bipolar transistors), and diodes. Non-linear loads are of particular concern since they produce harmonic currents and voltages that, if not limited to acceptable levels, may cause serious problems for the power system. Examples of loads which are classified as non-linear loads include light ballasts, switch mode power supplies (computers, consumer electronic devices), conventional dc power supplies and arc furnaces. 3.2.45 normal mode voltage A voltage that appears between or among active circuit conductors, but not between the grounding conductor and the active circuit conductors. Source: [5] For example the voltage between phase and neutral on a power system is a normal mode voltage. An in phase voltage component between all three phase conductors and neutral or ground on a power system is considered to be a common mode voltage. See also: common mode voltage. 3.2.46 notch A switching (or other) disturbance of the normal power voltage waveform, lasting less than 0.5 cycles, which is initially of opposite polarity than the waveform and is thus subtracted from the normal waveform in terms of the peak value of the disturbance voltage. This includes complete loss of voltage for up to 0.5 cycles. Source: [5] See also: waveform distortion. A notch is an occurrence within the sinusoidal voltage that has a duration of less than or equal to 0.5 cycles. The notch, however, is not a short duration variation or a transient, but typically refers to a steady state phenomena, occurring in each cycle of a waveform in a similar manner for a period of time that is much greater than one minute. If a phenomena that has the characteristics of a notch occurs for only one cycle, it is termed an impulsive transient. Figure 14 shows a waveform with a notch.

NEED NOTCH WAVEFORM

Figure 14An example of a waveform with a notch 3.2.47 oscillatory transient A sudden, non-power frequency change in the steady state condition of voltage or current that includes both positive or negative polarity value. Source: [5] See also: transient. 3.2.48 overvoltage When used to describe a specific type of long duration variation, refers to a measured voltage having a value greater than the nominal voltage for a period of time greater than 1 min. Typical values are 1.1 to 1.2 pu. Source: [5]

Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

23

P1433/D5A, July 15, 1999

Overvoltages can be the result of load switching (e.g., switching off a large load), or variations in the reactive compensation on the system (e.g., switching on a capacitor bank). Poor system voltage regulation capabilities or controls result in overvoltages. Incorrect tap settings on transformers can also result in system overvoltages. Figure 15 shows a typical overvoltage waveform.

1 minute or longer

Voltage

Overvoltage Peak Magnitude

Time

Figure 15Typical overvoltage waveform 3.2.49 phase shift The displacement in time of one waveform relative to another of the same frequency and harmonic content. Source: [4] The classic definition for power factor involves a phase shift. In a power factor case, often, the current is lagging the voltage. The lagging term refers to the phase shift of the current with respect to the voltage. A phase shift is simply a time delay. In other words, the peak of the current sine wave arrives shortly after (a time delay) the peak of the voltage sine wave. Figure 16 shows a phase shift that may occur on a typical power system with current lagging the voltage.

Figure 16Typical phase shift on a power system

Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

24

P1433/D5A, July 15, 1999

3.2.50 power disturbance Any deviation from the nominal value (or from some selected thresholds based on load tolerance) of the input ac power characteristics. Source: [4] When monitoring electric power, with many devices, thresholds are established to define what constitutes a power disturbance. Often, these thresholds are determined by the type of problem that is occurring. For example, if a certain piece of equipment is failing, device specific thresholds will be used (i.e. voltage limitations and noise limitations from the manufacturer) to establish the definition of a power disturbance. 3.2.51 power quality The concept of powering and grounding sensitive equipment in a manner that is suitable to the operation of that equipment. Source: [4] NOTEWithin the industry, alternate definitions or interpretations of power quality have been used, reflecting different points
of view. Therefore, this definition might not be exclusive, pending development of a broader consensus.

A point of view of an equipment designer or manufacturer might be that power quality is a perfect sinusoidal wave, with no variations in the voltage, and no noise present on the grounding system. A point of view of an electrical utility engineer might be that power quality is simply voltage availability or outage minutes. Finally, a point of view of an end-user, is that power quality or quality power is simply the power that works for whatever equipment the end-user is applying. While each hypothetical point of view has a clear difference, it is clear that none is properly focused. An environment where the equipment designer or manufacturer clearly states the equipment needs, and the electrical utility engineer indicates the system delivery characteristics, and the end-user then predicts and understands the equipment operational disturbances that will likely be encountered on a yearly basis is a better scenario. This allows a cost justification to be performed by the end-user to either improve equipment operation by installing additional components or improve the electrical supply system through installation of additional, or alteration of existing components. 3.2.52 pulse An abrupt variation of short duration of an electrical quantity followed by a rapid return to the initial value. Source: [5] See also: waveform distortion. 3.2.53 sag A decrease to between 0.1 and 0.9 pu in rms voltage or current at the power frequency for durations of 0.5 cycle to 1 min. Typical values are 0.1 to 0.9 pu. Source: [5] To give a numerical value to sag, the recommended usage is a sag to 20%, which means that the line voltage is reduced down to 20% of the normal value, not reduced by 20%. Using the preposition of (as in a sag of 20%, or implied by a 20% sag) is deprecated. A sag is a decrease in rms voltage or current at the power frequency for durations from 0.5 cycles to 1 minute. Typical values are between 0.1 pu and 0.9 pu. Terminology used to describe the magnitude of a voltage sag is often confusing. A 20% sag can refer to a sag which results in a voltage of 0.8 pu, or 0.2 pu. This Recommended Practice will indicate the remaining voltage throughout. Just as an unspecified voltage designation is accepted to mean line to line potential, so an unspecified sag magnitude will refer to the remaining voltage. For example, an 80% sag refers to a disturbance which resulted in a voltage of 0.8 pu. Where possible, also specify the nominal, or base, voltage level. Voltage sags are usually associated with system faults but can also be caused by switching of heavy loads or starting of large motors. Figure 17 shows a typical voltage sag that can be associated with a single line-to-ground (SLG) fault. Also, a fault on a parallel feeder circuit will result in a voltage drop at the substation bus which affects all of
Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

25

P1433/D5A, July 15, 1999

the other feeders until the fault is cleared. Typical fault clearing times range from three to thirty cycles, depending on the fault current magnitude and the type of overcurrent detection and interruption.

RMS Variation
120 100 80 60 40 20 0 0 150 100 50 0 -50 -100 -150 0 25 50 75 100 125 Time (mSeconds) 150 175 200 0.05 0.1 0.15 0.2 0.25 Time (Seconds) 0.3 0.35

Voltage (%)

Voltage (%

Figure 17Instantaneous voltage sag caused by a SLG fault Voltage sags can also be caused by large load changes or motor starting. An induction motor will draw six to ten times its full load current during starting. This lagging current causes a voltage drop across the impedance of the system. If the current magnitude is large relative to the system available fault current, the resulting voltage sag can be significant. Figure 18 illustrates the effect of a large motor starting.

RMS Variation 115


Voltage (%)

110 105 100 95 90 85 80 75 0 0.5 1 1.5 2 2.5 3 3.5 4


Time (Seconds)

Figure 18Temporary voltage sag caused by motor starting The term sag has been used in the power quality community for many years to describe a specific type of power quality disturbance, a short duration voltage decrease. Clearly, the notion is directly borrowed from the literal

Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

26

P1433/D5A, July 15, 1999

definition of the word sag. The IEC definition for this phenomenon is dip. The two terms are considered interchangeable, with sag being preferred in the United States power quality community. Previously, the duration of sag events has not been clearly defined. Typical sag duration defined in some publications ranges from two milliseconds (about one-eighth of a cycle) to a couple of minutes. Undervoltages that last less than one-half cycle cannot be characterized effectively as a change in the rms value of the fundamental frequency value. Therefore, these events are considered transients. Undervoltages that last longer than one minute can typically be controlled by voltage regulation equipment and may be associated with a wide variety of causes other than system faults. Therefore, these are classified as long duration variations in the following section. Sag duration is subdivided here into three categories -- instantaneous, momentary and temporary -- which coincide with the three categories of interruptions and swells. These durations are intended to correlate with typical protective device operation times as well as duration divisions recommended by international technical organizations. 3.2.54 shield A conductive sheath (usually metallic) normally applied to instrumentation cables, over the insulation of a conductor or conductors, for the purpose of providing means to reduce coupling between the conductors so shielded and other conductors that may be susceptible to, or that may be generating unwanted electrostatic or electromagnetic fields (noise). Source: [4] Figure 19 depicts the configuration of a shield on a typical communication cable.

A Shielded Signal Cable Outer Insulating Sheathing Foil and/or braided Shield Insulated Signal Conductors

Figure 19Diagram of the shield within a communication cable 3.2.55 shielding The use of a conducting and/or ferromagnetic barrier between a potentially disturbing noise source and sensitive circuitry. Shields are used to protect cables (data and power) and electronic circuits. They may be in the form of metal barriers, enclosures, or wrappings around source circuits and receiving circuits. Source: [4] 3.2.56 short duration voltage variation

See: voltage variation, short duration. 3.2.57 slew rate Rate of change of ac voltage, expressed in volts per second. Source: [3] 3.2.58 surge A transient wave of current, potential, or power in an electric circuit. Source: [3]

Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

27

P1433/D5A, July 15, 1999

The use of the term surge is deprecated within the general power quality context. It is included in this text due to its extensive use within the IEEE C62 collection, Surge Protection. For the purposes of power quality definitions, surge is not to be used to describe transient electromagnetic phenomena, but the term transient shall be used. See also: transient. 3.2.59 surge response voltage The voltage profile appearing at the output terminals of a surge-protective device and applied to downstream loads, during and after a specified impinging surge, until normal, stable conditions are reached. Source: [??] 3.2.60 swell An increase in rms voltage or current at the power frequency for durations from 0.5 cycles to 1 min. Typical values are 1.1 - 1.8 pu. Source: [5] Swell magnitude is also described by its remaining voltage, in this case, always greater than 1.1. As with sags, swells are usually associated with system fault conditions, but they are much less common than voltage sags. A swell can occur due to a single line-to-ground fault on the system resulting in a temporary voltage rise on the unfaulted phases. Swells can also be caused by switching off a large load or switching on a large capacitor bank. Figure 20 illustrates a voltage swell caused by a SLG fault.

RMS Variation
120 115 110 105 100 95 90 0 150 100 50 0 -50 -100 -150 0 25 50 75 100 125 Time (mSeconds) 150 175 200 0.05 0.1 0.15 0.2 0.25 Time (Seconds) 0.3 0.35

Voltage (%)

Voltage (%

Figure 20Instantaneous voltage swell caused by a SLG fault Swells are characterized by their magnitude (rms value) and duration. The severity of a voltage swell during a fault condition is a function of the fault location, system impedance, and grounding. On an ungrounded system, the lineto-ground voltages on the ungrounded phases will be 1.73 per unit during a line-to-ground fault condition. Close to the substation on a grounded system, there will be no voltage rise on the unfaulted phases because the substation transformer is usually connected delta-wye, providing a low impedance zero-sequence path for the fault current. In some previous publications, the term momentary overvoltage is used as a synonym for the term swell. A formal definition of swells in C62.41 is: "A momentary increase in the power-frequency voltage delivered by the mains, outside of the normal tolerances, with a duration of more than one cycle and less than a few seconds." This definition is not preferred by the power quality community.

Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

28

P1433/D5A, July 15, 1999

3.2.61

temporary interruption

See: interruption, temporary. 3.2.62 tolerance The allowable variation from a nominal value. 3.2.63 total harmonic distortion This term has come into common usage to define either voltage or current distortion factor. Source: [8] See also: distortion factor; harmonic (component). 3.2.64 transient Pertaining to or designating a phenomenon or a quantity which varies between two consecutive steady states during a time interval that is short compared to the time scale of interest. A transient can be a unidirectional impulse of either polarity or a damped oscillatory wave with the first peak occurring in either polarity. Source: [2] Broadly speaking, transients can be classified into two categories, impulsive and oscillatory. These terms reflect the waveshape of a current or voltage transient. An impulsive transient is a sudden, non-power frequency change in the steady state condition of voltage, current, or both, that is unidirectional in polarity (primarily either positive or negative). Impulsive transients are normally characterized by their rise and decay times. These phenomena can also be described by their spectral content. For example, a 1.2/50 s 2000-V impulsive transient rises to its peak value of 2000 V in 1.2 s, then decays to half its peak value in 50 s. The most common cause of impulsive transients is lightning. Figure 21 illustrates a typical current impulsive transient caused by lightning. Table 4 defines the spectral content and the duration of impulsive transients. Table 4Descriptions of impulsive transients

Impulsive Transients Nanosecond Microsecond Millisecond

Spectral Content 5 ns rise 1 s rise 0.1 ms rise

Duration < 50 ns 50 ns 1 ms > 1 ms

Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

29

P1433/D5A, July 15, 1999

Need picture here


Figure 21Lightning stroke current that can result in impulsive transients on the power system Due to the high frequencies involved, impulsive transients are damped quickly by resistive circuit components and are not conducted far from their source. There can be significant differences in the transient characteristic from one location within a building to another. Impulsive transients can excite power system resonance circuits and produce the following type of disturbance, oscillatory transients. An oscillatory transient is a sudden, non-power frequency change in the steady state condition of voltage, current, or both, that includes both positive and negative polarity values. An oscillatory transient consists of a voltage or current whose instantaneous value changes polarity rapidly. It is described by its spectral content (predominant frequency), duration, and magnitude. The spectral content subclasses defined in Table 5 are high, medium, and low frequency. The frequency ranges for these classifications are chosen to coincide with common types of power system oscillatory transient phenomena. Table 5Descriptions of oscillatory transients

Oscillatory Transient Low Frequency Medium Frequency High Frequency

Spectral Content x < 5 kHz 5 kHz < x < 500 kHz 500 kHz < x < 5 MHz

Duration 0.3 50 ms 20 s 5 s

Voltage Magnitude 0 4 pu 0 8 pu 0 4 pu

As with impulsive transients, oscillatory transients can be measured with or without the fundamental frequency component included. When characterizing the transient, it is important to indicate the magnitude with and without the fundamental component. Oscillatory transients with a primary frequency component greater than 500 kHz and a typical duration measured in microseconds (or several cycles of the principal frequency) are considered high frequency oscillatory transients. These transients are almost always due to some type of switching event. High frequency oscillatory transients are often the result of a local system response to an impulsive transient. Power electronic devices produce oscillatory voltage transients as a result of commutation and RLC snubber circuits. The transients can be in the high kilohertz range; last a few cycles of their fundamental frequency; and have repetition rates of several times per 60-Hz cycle (depending on the pulse number of the device) and magnitudes of 0.1 pu (less the 60-Hz component). A transient with a primary frequency component between 5 and 500 kHz with duration measured in the tens of microseconds (or several cycles of the principal frequency) is termed a medium frequency transient. Back-to-back capacitor energization results in oscillatory transient currents in the tens of kilohertz. This phenomenon occurs when a capacitor bank is energized in close electrical proximity to a capacitor bank already in service. The energized bank sees the de-energized bank as a low impedance path (limited only by the inductance of
Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

30

P1433/D5A, July 15, 1999

the bus to which the banks are connected. Figure 22 below illustrates the resulting current transient due to back-toback capacitor switching. Cable switching results in oscillatory voltage transients in the same frequency range. Medium frequency transients can also be the result of a system response to an impulsive transient.
7500

5000

Current (A)

2500

-2500

-5000

-7500 8 10 12 14

Time (mS)

Figure 22Oscillatory transient caused by back-to-back capacitor switching A transient with a primary frequency component less than 5 kHz, and a duration from 0.3 ms to 50 ms, is considered a low frequency transient. This category of phenomena is frequently encountered on subtransmission and distribution systems and is caused by many types of events, primarily capacitor bank energization. The resulting voltage waveshape is very familiar to power system engineers and can be readily classified using the attributes discussed so far. Capacitor bank energization typically results in an oscillatory voltage transient with a primary frequency between 300 and 900 Hz. The transient has a peak magnitude that can approach 2.0 pu, but is typically 1.3 - 1.5 pu lasting between 0.5 and 3 cycles depending on the system damping (see Figure 23).
2.0 1.5 1.0 0.5 0.0 34.5 kV Bus V oltage C apacitor Sw itching T ransient

V ol tag - 0.5 e (V
- 1.0 0 - 1.5 20 40 60 80 100

Figure 23Low frequency oscillatory transient caused by capacitor-bank energization Oscillatory transients with principal frequencies less than 300 Hz can also be found on the distribution system. These are generally associated with ferroresonance and transformer energization. Transients involving series capacitors could also fall into this category. They occur when the system resonance results in magnification of low frequency components in the transformer inrush current (2nd, 3rd harmonic) or when unusual conditions result in ferroresonance as illustrated in Figure 24. IEEE Standard C62.41 deals with defining standard impulsive and oscillatory transient test waves for the purpose of testing electrical equipment susceptibility and transient suppression technologies. This standard specifies voltage and current levels that certain pieces of power system equipment should be able to withstand.

Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

31

P1433/D5A, July 15, 1999

600000

400000

Voltage (V)

200000

-200000

-400000

-600000 0 200 400 600 800 1000

Time (mS)

Figure 24Low frequency oscillatory transient caused by ferroresonance of an unloaded transformer 3.2.65 undervoltage A measured voltage having a value less than the nominal voltage for a period of time greater than 1 min when used to describe a specific type of long duration variation. Typical values are 0.8 - 0.9 pu. Source: [5] Undervoltages are the result of the events which are the reverse of the events that cause overvoltages. A load switching on or a capacitor bank switching off can cause an undervoltage until voltage regulation equipment on the system can bring the voltage back to within tolerances. Overloaded circuits can result in undervoltages also. The term brownout is sometimes used to describe sustained periods of low power-frequency voltage initiated as a specific dispatch strategy to reduce power delivery. The type of disturbance described by brownout is basically the same as that described by the term undervoltage defined here. Because there is no formal definition for the term brownout, and because the term is not as clear as the term undervoltage when trying to characterize a disturbance, the term brownout should be avoided in future power quality activities in order to avoid confusion. 3.2.66 voltage change A variation of the rms or peak value of a voltage between two consecutive levels sustained for definite but unspecified durations. Source: [2] 3.2.67 voltage dip

See also: sag. 3.2.68 voltage distortion Any deviation from the nominal sine wave form of the ac line voltage. Source: [5] 3.2.69 voltage fluctuation A series of voltage changes or a cyclical variation of the voltage envelope. Source: [2] Voltage fluctuations are systematic variations of the voltage envelope or a series of random voltage changes, the magnitude of which does not normally exceed the voltage ranges specified by ANSI C84.1 of 0.95 pu to 1.05 pu. IEC 555-3 [this document has been revised as IEC 1000-3-3] defines various types of voltage fluctuations. The reader is referred to this document for a detailed breakdown of these types. The remainder of this discussion on voltage fluctuations will concentrate on the IEC 555-3 Type (d) voltage fluctuations. This type is characterized as a series of random or continuous voltage fluctuations. Any load that has significant time variations, especially in the reactive component, can cause voltage fluctuations. Loads which exhibit continuous, rapid variations in load current magnitude can cause voltage variations erroneously referred to as flicker. The term flicker is derived from the impact of the voltage fluctuation on lighting intensity. Voltage fluctuation is an electromagnetic phenomenon and flicker is an undesirable result of that phenomenon. Even
Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

32

P1433/D5A, July 15, 1999

though there is a clear distinction between these terms -- cause and effect -- they are often confused to the point that the term voltage flicker is used in some documents. Such incorrect usage should be avoided.
100DN>NC35KA(Type 1)
1.5

1.0

Voltage (V pu)

0.5

0.0

-0.5

-1.0

-1.5 0 50 100 150 200

Time (mS)

Figure 25Example of voltage fluctuations caused by arc furnace operation Arc furnaces are the most common cause of voltage fluctuations on the transmission and distribution system. The voltage signal is defined by its rms magnitude expressed as a percent of the fundamental. Lighting flicker is measured with respect to the sensitivity of the human eye. An example of a voltage waveform which produces flicker is shown in Figure 25. Voltage fluctuations generally appear as a modulation of the fundamental frequency (similar to amplitude modulation of an am radio signal). Therefore, it is easiest to define a magnitude for the voltage fluctuation as the rms magnitude of the modulation signal. This can be obtained by demodulating the waveform to remove the fundamental frequency and then measuring the magnitude of the modulation components. Typically, magnitudes as low as 0.5% can result in perceptible light flicker if the frequencies are in the range of 6 8 Hz. 3.2.70 voltage imbalance (unbalance), polyphase systems The maximum deviation among the three phases from the average three-phase voltage divided by the average threephase voltage. The ratio of the negative or zero sequence component to the positive sequence component, usually expressed as a percentage. Source: [3] Voltage imbalance (or unbalance) is defined as the ratio of the negative or zero sequence component to the positive sequence component. The negative or zero sequence voltages in a power system generally result from unbalanced loads causing negative or zero sequence currents to flow. Figure 26 shows an example of a one-week trend of imbalance measured at one point on a residential feeder. Imbalance can be estimated as the maximum deviation from the average of the three phase voltages or currents, divided by the average of the three phase voltages or currents, expressed in percent. In equation form:

Voltage Imbalance =

maximum deviation from average voltage .................... .......... .......... .......... .......... ................ 100 average voltage

For example, with phase-to-phase voltage readings of 230, 232, and 225, the average is 229. The maximum deviation from the average among the three readings is 4. The percent imbalance is 100 * 4/229 = 1.7%.

Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

33

P1433/D5A, July 15, 1999

3 2.5 2 1.5 1 0.5 0 Mon Tue

V0/V1 V2/V1

Wed

Thu

Fri

Sat

Sun

Mon

Figure 26Imbalance trend for a residential feeder The primary source of voltage imbalance less than two percent is unbalanced single phase loads on a three-phase circuit. Voltage imbalance can also be the result of capacitor bank anomalies, such as a blown fuse on one phase of a three-phase bank. Severe voltage imbalance (greater than 5%) can result from single-phasing conditions. Figure 26 illustrates an imbalance trend for a residential feeder. 3.2.71 voltage interruption Disappearance of the supply voltage on one or more phases. Usually qualified by an additional term indicating the duration of the interruption (e.g., momentary, temporary, or sustained). Source: [5] 3.2.72 voltage regulation The degree of control or stability of the rms voltage at the load. Often specified in relation to other parameters, such as input-voltage changes, load changes, or temperature changes. Source: [4] Voltage regulation is calculated different ways depending on how the term is applied. As an example the voltage regulation at a customer service is often calculated in percent of nominal voltage and is: %Regulation = 100 [Vmax-Vmin]/Vnominal The above equation shows the percent change in voltage occurring relative to the nominal voltage. In some applications, it is chosen to compare the change in voltage relative to the average voltage which will yield a slightly different answer than the above formula. Regulation is also often calculated based on conditions of no load and maximum load which will yield an even greater variation. 3.2.73 voltage variation, long duration A variation of the rms value of the voltage from nominal voltage for a time greater than 1 min. Usually further described using a modifier indicating the magnitude of a voltage variation (e.g., undervoltage, overvoltage, or voltage interruption). Source: [5] 3.2.74 variation, short duration A variation of the rms value of the voltage from nominal voltage for a time greater than 0.5 cycles of the power frequency but less than or equal to 1 minute. Usually further described using a modifier indicating the magnitude of

Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

34

P1433/D5A, July 15, 1999

a voltage variation (e.g., sag, swell, or interruption) and possibly a modifier indicating the duration of the variation (e.g., instantaneous, momentary or temporary). Source: [5] The short duration variation is the general category of events that last for a time period that is greater than 0.5 cycles, but less than or equal to 1 minute. It is not to be confused with steady state changes in the waveform such as harmonics, notching or noise, which can have a duration within the range of a short duration variation, but typically repeat for each cycle of the sinusoidal waveform. Short duration variations are almost always caused by fault conditions, such as the energization of large loads that require starting current that is a multiple of the operating current (motors), or conditions such as loose connections in the current carrying circuit conductors. In addition, while most short duration variations are described as voltage variations in nature, current variations can also fall into the short duration variation as well. Figure 27 shows the time frame of the types of short duration variations. See also: instantaneous; interruption, momentary; interruption, temporary; momentary; sag; swell.

Figure 27Time scale of short duration variations 3.2.75 waveform distortion A steady state deviation from an ideal sine wave of power frequency principally characterized by the spectral content of the deviation. Source: [5] There are five primary types of waveform distortion: DC Offset Harmonics (See harmonic for details) Interharmonics Notching Noise

DC offset is the presence of a dc voltage or current in an ac power system is termed dc offset. This phenomenon can occur as the result of a geomagnetic disturbance or due to the effect of half-wave rectification. Incandescent light bulb life extenders, for example, may consist of diodes that reduce the rms voltage supplied to the light bulb by halfCopyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

35

P1433/D5A, July 15, 1999

wave rectification. Direct current in alternating current networks can be detrimental due to an increase in transformer saturation, additional stressing of insulation and other adverse effects. Interharmonics are voltages or currents having frequency components that are not integer multiples of the frequency at which the supply system is designed to operate (e.g., 50 Hz or 60 Hz) are called interharmonics. They can appear as discrete frequencies or as a wide-band spectrum. Interharmonics can be found in networks of all voltage classes. The main sources of interharmonic waveform distortion are static frequency converters, cyclo-converters, induction motors and arcing devices. Power line carrier signals can also be considered as interharmonics. The effects of interharmonics are not well known, but have been shown to affect power line carrier signaling, and induce visual flicker in display devices such as CRTs. The IEC [1] places background noise phenomenon in the interharmonic category. This document discusses noise separately as a distinct electromagnetic phenomenon later in this section. Notching is a periodic voltage disturbance caused by the normal operation of power electronics devices when current is commutated from one phase to another. Voltage notching represents a special case that falls between transients and harmonic distortion. Since notching occurs continuously (steady state), it can be characterized through the harmonic spectrum of the affected voltage. However, the frequency components associated with notching can be quite high and may not be readily characterized with measurement equipment normally used for harmonic analysis. Three-phase converters that produce continuous dc current are the most important cause of voltage notching (Figure 28). The notches occur when the current commutates from one phase to another. During this period, there is a momentary short circuit between two phases. The severity of the notch at any point in the system is determined by the source inductance and the isolating inductance between the converter and the point being monitored. Notching is described in detail in IEEE 519-1992.

NEED FIGURE HERE Figure 28Example of voltage notching caused by converter operation Noise is defined as unwanted electrical signals with broadband spectral content lower than 200 kHz superimposed upon the power system voltage or current in phase conductors, or found on neutral conductors or signal lines. Noise in power systems can be caused by power electronic devices, control circuits, arcing equipment, loads with solid-state rectifiers, and switching power supplies. Noise problems are often exacerbated by improper grounding. Basically, noise consists of any unwanted distortion of the power signal that cannot be classified as harmonic distortion or transients.

Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

36

P1433/D5A, July 15, 1999

The frequency range and magnitude level of noise depend on the source which produces the noise and the system characteristics. A typical magnitude of noise is less than one percent of the voltage magnitude. Noise disturbs electronic devices such as microcomputer and programmable controllers. The problem can be mitigated by using filters, isolation transformers, and some line conditioners.

4.
1.

Bibliography
Dugan, Roger C., Mark F. McGranaghan and H. Wayne Beaty. 1996. Electrical power systems quality. New York: McGraw Hill.

2.

Whitaker, Jerry C. 1991. AC power systems handbook. Boca Raton, Florida: CRC Press.

3.

Simmons, J. Philip. 1996. IAEI Soares book on grounding, Sixth edition. Richardson, Texas: International Association of Electrical Inspectors.

4.

Heydt, G.T. 1991. Electric power quality. West LaFayette, Indiana: Stars in a Circle Publications.

5.

Greenwood, Allan. 1991. Electrical transients in power systems. New York: John Wiley and Sons.

6.

National Fire Protection Association, 1996, National Electrical Code, ANSI/NFPA 70-1996, Quincy, Massachusetts; National Fire Protection Association.

BIBLIOGRAPHY NEEDS CLEANUP BASED UPON DOCUMENT

Copyright 1999 IEEE. All Rights Reserved. This is an unapproved IEEE Standards Draft, subject to change.

37

Potrebbero piacerti anche