SPECIFICATION HIGH VOLTAGE CIRCUIT BREAKER

I. SCOPE : This specification is applicable to high voltage circuit breaker for ouutdoor installation. II. STANDARD OF MANUFACTURE AND TEST : IEC 56 : High voltage AC circuit breakers III. DESCRIPTIONS : A. SERVICE CONDITIONS : The circuit breaker shall be designed and fabricated, suitable for outdoor service in Ho Chi Minh City, Vietnam under the following conditions: + + + + + + + + Altitude : Up to 40m above sea level Maximum ambient air temperature : 40 C Mean annual ambient air temperature : 30 C Maximum relative humidity : 95% Climate : Tropical, salty atmosphere, industrial contamination. Solar radiation : 1000W/m 2 Maximum wind velocity : 30m/s Lightning stroke expectancy : 120 thunderstorm days per year.

B. CONSTRUCTION : Type of circuit breaker : SF6 type, outdoor service. Rated voltage : 123KV Rated continuous current : 1250 A Rated frequency : 50 Hz Rated short-circuit symmetrical breaking current : 31.5 KA Rated power frequency withstand voltage : + Dry for 1 minute : 230 KV + Wet for 10 seconds : 230KV Rated lightning impulse (1.2/50s wave) withstand voltage : 550KV Rated short time withstand current for 3 seconds : 31.5KA Rated withstand peak current : 80KA. Rated short circuit making current : 80 KA Rated operation duty cycle : O-0.3s-CO-3min.-CO First-pole-to-clear factor : 1.5 Rated out-of-phase making or breaking line charging current : 31.5A Maximum opening time : 0.05s

/var/www/apps/conversion/tmp/scratch_4/137134851.doc

1/7

HCMC PC

SPECIFICATION HIGH VOLTAGE CIRCUIT BREAKER

Maximum closing time : 0.1s Operating mechanism type : + Closing : spring + Opening : spring Method of manual charging of closing spring for checking and maintenance : Hand crank Protection class : IP54 Rated voltage of trip and opening coil : 220VDC Rated voltage of motor : 220VAC Motor protective device : Miniature circuit breaker. Number of operations before interrupter maintenance required : 50 times at rated short circuit current of 31.5KA Auxiliary contacts : 10NO+10NC The circuit breaker is equipped with anti-pumping device. Maximum dimension as the attached drawing : + A : 3300mm + B : 3900mm Accessories for 01 circuit breaker : + 06 Pcs of straight bolted terminal connectors for connection ACSR of 400mm2 to circuit breaker terminals + 02 Pcs of copper bolted clamps for earthing with 120mm2 conductor 01 Set of SF6 gas bottle for first filling 01 Set of spring charger motor 01 Set of auxiliary contacts 10NO+10NC 01 Set of SF6 density gauge + 01 Operating handle. + 01 trip coil 110VDC. + 01 opening coil 110VDC. + 01 Set of steel supporting structure

+ + + +

- Accessories for all circuit breakers : + 23 set of SF6 gas bottle 10Kg + 01 set of valves + 01 set of pressure gauge IV. TESTING REQUIREMENTS : 1. Testing items : a. Routine tests : - Power frequency voltage withstand dry tests on the main circuit - Voltage withstand tests on control and auxiliary circuits

/var/www/apps/conversion/tmp/scratch_4/137134851.doc

2/7

HCMC PC

SPECIFICATION HIGH VOLTAGE CIRCUIT BREAKER

- Measurement of the resistance of the main circuit - Mechanical operation tests - Design and visual checks b. Type tests : Dielectric tests Radio interference voltage (RIV) tests Temperature-rise tests Measurement of the resistance of the main circuit Short-time and peak withstand current tests Mechanical and environmental tests Miscellaneous provisions for making and breaking tests Test circuit for short circuit making and breaking tests Short-circuit test quantities Short-circuit test procedure Basic short-circuit test-duties Critical current tests Single-phase short-circuit tests Short-line fault tests Out-of-phase making and breaking tests Capacitive current switching tests Magnetizing and small inductive current switching tests

2. Requirements : In order to ensure the quality of supplied goods , in case of bid winning , the Tenderer shall supply routine test and copies of type test reports met the following requirements : a. Routine test shall be performed for each equipment. b. Type test report shall be approved by an lawful, reputable, independent testing laboratory with the following content : - Testing sample : the same as the supplied item (manufacturer, country of origin, manufactures code as specified in tender document). - Testing items : Including at least testing items as specified Section IV.1 of this specification. in

- Testing values shall be corresponding values as stated in Section III of this specification. If in section III, there are no corresponding values, testing values will be selected according to the standard specified in section II of this specification.

/var/www/apps/conversion/tmp/scratch_4/137134851.doc

3/7

HCMC PC

SPECIFICATION HIGH VOLTAGE CIRCUIT BREAKER

V. REQUIREMENT OF TENDER TECHNICAL DOCUMENTS : - Detailed summary of deviations to inquiry specification. - Completed inquiry data sheet expressed at section VI of this specification. - Catalogues containing outline dimensions, electrical data and installation details. - Certificate of quality management. - The following drawings : + Dimension. + Straight bolted terminal connectors for connection ACSR of 795MCM to disconector terminals + Bolted clamps for earthing with 120mm2 copper conductor + Stainless steel structure for 3-pole DS - The proposal bidding has Type Test Report which meets the requirements as specified in item IV 2.b will be preferable .

VI. DATA SHEET : N o 1. 2. 3. 4. 5. 6. 7. 8. SPECIFICATION Item No. Manufacturer Country Manufacturers code Standards of factory and test Standards of quality management Member approve of certificate of management In case of bid winning , the Tenderer shall supply routine test and copies of type test report met the requirements of section IV . A. SERVICE CONDITIONS : The circuit breaker shall be designed and fabricated, suitable for outdoor service in Ho Chi Minh City, Vietnam under the following UNIT REQUIREMENTS TENDER

IEC 56

Yes

/var/www/apps/conversion/tmp/scratch_4/137134851.doc

4/7

HCMC PC

SPECIFICATION HIGH VOLTAGE CIRCUIT BREAKER

9.

conditions : + Altitude : C C %

10. + Maximum ambient air temperature 11. + Mean annual ambient air temperature 12. + Maximum relative humidity 13. + Climate

Up to 40m above sea level 40 30 95 Tropical, salty atmosphere, industrial contamination. 1000 30 120 thunderstorm days per year. SF6 type, outdoor service. 123 1250 50 31.5

14. + Solar radiation 15. + Maximum wind velocity 16. + Lightning stroke expectancy B. CONSTRUCTION : 17. Type of circuit breaker : 18. 19. 20. 21. 22. Rated voltage Rated continuous current Rated frequency Rated short-circuit symmetrical breaking current Rated power frequency withstand voltage : + Dry for 1 minute + Wet for 10 seconds Rated lightning impulse (1.2/50s wave) withstand voltage Rated short time withstand current for 3 seconds Rated withstand peak current Rated short circuit making current Rated operation duty cycle First-pole-to-clear factor Rated out-of-phase (making or breaking) capacity : + Line charging current + Cable charging current + Capacitor current

W/m2 m/s

KV A Hz KA

23.

KV KV KV

230 230 550

24. 25. 26. 27. 28. 29.

KA KA KA

31.5 80 80 O-0.3s-CO-3min.-CO 1.5

A A A

31.5 Tenderer must describe these parameters

/var/www/apps/conversion/tmp/scratch_4/137134851.doc

5/7

HCMC PC

SPECIFICATION HIGH VOLTAGE CIRCUIT BREAKER

30. Maximum opening time 31. Maximum closing time from energisation of close coil to latching of circuit breaker in fully closed position 32. Circuit break operating mechanism type : + Closing + Opening 33. Method of manual charging of closing spring for checking and maintenance 34. Protection class 35. Rated voltage of trip and opening coil 36. Rated voltage of motor 37. Motor protective device 38. Number of operations before interrupter maintenance required 39. Auxiliary contacts 40. The circuit breaker is equipped with anti-pumping device 41. Maximum dimension as the attached drawing : +A +B 42. Accessories for 01 circuit breaker : + Straight bolted terminal connectors for connection ACSR of 400mm2 to circuit breaker terminals + Copper bolted clamps for earthing with 120mm2 conductor + SF6 gas bottle for first filling + Spring charger motor + Auxiliary contacts 10NO+10NC + SF6 density gauge + Hand crank + Trip coil 110VDC. + Opening coil 110VDC.

s s

0.05 0.1

spring spring Hand crank IP54 VDC VAC 220 220 Miniature circuit breaker 50 times at rated short circuit current of 31.5KA 10NO+10NC Yes

mm mm Pcs

3300 3900 06

Pcs Set Set Set Set Pcs Pcs Pcs Set

02 01 01 01 01 01 01 01 01

/var/www/apps/conversion/tmp/scratch_4/137134851.doc

6/7

HCMC PC

SPECIFICATION HIGH VOLTAGE CIRCUIT BREAKER

+ Stainless steel supporting structure 43. Accessories for all circuit breakers : + SF6 gas bottle 10Kg + Valves + Pressure gauge