Crack Control
Three reasons for limiting crack widths in concrete
Crack Control
Appearance limit crack widths on surface
locate reinforcement as close as possible to surface.
< 175 kips/in for interior exposures < 145 kips/in for exterior exposures
fs = calculated stress in the reinforcement at service loads (ksi), which may be taken as 0.6fy. dc = thickness of the concrete cover measured from the extreme tension fiber to the center of the bar or wire located closest to it (inches) A = effective tension area of concrete surrounding the flexural tension reinforcement and having the same centroid as that reinforcement, divided by the number of bars or wires square inches)
6
Equivalent no. of #9 bars = (3 x 1.00 + 2x 0.79) / 1.00 = 4.58 A = 2dcg x b / 4.58 dcg = distance from extreme tension fiber to center of gravity of steel
8
540 s 2 .5 c c fs s 12 (36 / f s )
(10-5)
12
13
14
15
40,000 ) s 12 ( fs
17
18
20
fy
bw d
200 bw d fy
21
22
M n 1.2 M cr
23
Width of cracks in the web may exceed crack widths at level of flexural tension reinforcement.
25
26
27
Changed
From: To:
Ab = Area of individual bar or wire, in.2 Above expressions are mathematically identical
28
29
Skin reinforcement over h/2 from tension face Spacing per 10.6.4 (cc to side face) May include skin reinforcement contribution to Mn
based on compatibility analysis