Short circuit protection calculations Site Name March Crematorium Contract Number C4???

Tag No DB Use Distribution board Incomer Supply fault rms current level (KVA) % Reactance Protective device Range Short circuit rating Short circuit release Max energy let through Max short circuit setting Operating voltage Tripping time Phases Panel symmetrical fault level Conductor Copper Insulation Tri Rated Mineral Table 43A "k" value Temperature coefficient

349 (taken from FGT short circuit calculations) 1 MGI125N 125 125 25 kA 10 * Range max
75 KA2s 1250 Amps 400 V 25 milliseconds

3
349 KVA

Y Y N 143

143.00 Conductor Cable test csa mm2 Maximum current available Current Voltage drop 35 151117 Passed Passed Heating time (t) seconds = (k2*s2)/I2 16.0320 Seconds 16032.02 milliseconds Conductor energy let through capability 25050025 A2s 25050.03 KA2s Conductor short circuit energy capability Passed Device tripping speed Passed Note device OK

Page 1 of17 135554903.xls.ms_office

circuit calculations)

Page 2 of17 135554903.xls.ms_office

Short circuit protection calculations Site Name March Crematorium Contract Number Tag No EES166201 Use No1 Coanda Fan Supply fault rms current level (KVA) % Reactance Protective device Range Short circuit rating Short circuit release Max energy let through Max short circuit setting Operating voltage Tripping time Phases Panel symmetrical fault level Conductor Copper Insulation Tri Rated Mineral Table 43A "k" value Temperature coefficient

C4???

349 1 MG18463 C60HC316 16 16 20 kA 10 * Range max


60 KA2s 160 Amps 400 V 25 milliseconds

3
111 KVA

Y Y N 143

143.00 Conductor Cable test csa mm2 Maximum current available Current Voltage drop 2.5 47997 Passed Passed Heating time (t) seconds = (k2*s2)/I2 4.9924 Seconds 4992.43 milliseconds Conductor energy let through capability 127806.25 A2s 127.81 KA2s Conductor short circuit energy capability Passed Device tripping speed Passed Note device OK

Page 3 of17 135554903.xls.ms_office

Short circuit protection calculations Site Name March Crematorium Contract Number Tag No EES266201 Use No2 Coanda Fan Supply fault rms current level (KVA) % Reactance Protective device Range Short circuit rating Short circuit release Max energy let through Max short circuit setting Operating voltage Tripping time Phases Panel symmetrical fault level Conductor Copper Insulation Tri Rated Mineral Table 43A "k" value Temperature coefficient

C4???

349 1 MG18463 C60HC316 16 16 20 kA 10 * Range max


60 KA2s 160 Amps 400 V 25 milliseconds

3
111 KVA

Y Y N 143

143.00 Conductor Cable test csa mm2 Maximum current available Current Voltage drop 2.5 47997 Passed Passed Heating time (t) seconds = (k2*s2)/I2 4.9924 Seconds 4992.43 milliseconds Conductor energy let through capability 127806.25 A2s 127.81 KA2s Conductor short circuit energy capability Passed Device tripping speed Passed Note device OK

Page 4 of17 135554903.xls.ms_office

Short circuit protection calculations Site Name March Crematorium Contract Number Tag No EES126101 Use No1 Combustion Fan Supply fault rms current level (KVA) % Reactance Protective device Range Short circuit rating Short circuit release Max energy let through Max short circuit setting Operating voltage Tripping time Phases Panel symmetrical fault level Conductor Copper Insulation Tri Rated Mineral Table 43A "k" value Temperature coefficient

C4???

349 1 MG18463 C60HC316 16 16 20 kA 10 * Range max


60 KA2s 160 Amps 400 V 25 milliseconds

3
111 KVA

Y Y N 143

143.00 Conductor Cable test csa mm2 Maximum current available Current Voltage drop 2.5 47997 Passed Passed Heating time (t) seconds = (k2*s2)/I2 4.9924 Seconds 4992.43 milliseconds Conductor energy let through capability 127806.25 A2s 127.81 KA2s Conductor short circuit energy capability Passed Device tripping speed Passed Note device OK

Page 5 of17 135554903.xls.ms_office

Short circuit protection calculations Site Name March Crematorium Contract Number Tag No EES226101 Use No2 Combustion Fan Supply fault rms current level (KVA) % Reactance Protective device Range Short circuit rating Short circuit release Max energy let through Max short circuit setting Operating voltage Tripping time Phases Panel symmetrical fault level Conductor Copper Insulation Tri Rated Mineral Table 43A "k" value Temperature coefficient

C4???

349 1 MG18463 C60HC316 16 16 20 kA 10 * Range max


60 KA2s 160 Amps 400 V 25 milliseconds

3
111 KVA

Y Y N 143

143.00 Conductor Cable test csa mm2 Maximum current available Current Voltage drop 2.5 47997 Passed Passed Heating time (t) seconds = (k2*s2)/I2 4.9924 Seconds 4992.43 milliseconds Conductor energy let through capability 127806.25 A2s 127.81 KA2s Conductor short circuit energy capability Passed Device tripping speed Passed Note device OK

Page 6 of17 135554903.xls.ms_office

Short circuit protection calculations Site Name March Crematorium Contract Number Tag No EES132002 Use No1 Analytical supply Supply fault rms current level (KVA) % Reactance Protective device Range Short circuit rating Short circuit release Max energy let through Max short circuit setting Operating voltage Tripping time Phases Panel symmetrical fault level Conductor Copper Insulation Tri Rated Mineral Table 43A "k" value Temperature coefficient

C4???

349 1 MG19270 C60HC116 16 16 20 kA 10 * Range max


20 KA2s 160 Amps 230 V 25 milliseconds

1
37 KVA

Y Y N 143

143.00 Conductor Cable test csa mm2 Maximum current available Current Voltage drop 1.5 27712 Passed Passed Heating time (t) seconds = (k2*s2)/I2 1.7973 Seconds 1797.28 milliseconds Conductor energy let through capability 46010.25 A2s 46.01 KA2s Conductor short circuit energy capability Passed Device tripping speed Passed Note device OK

Page 7 of17 135554903.xls.ms_office

Short circuit protection calculations Site Name March Crematorium Contract Number C4??? Tag No EES11001 Use No1 Cremator panel supply Supply fault rms current level (KVA) % Reactance Protective device Range Short circuit rating Short circuit release Max energy let through Max short circuit setting Operating voltage Tripping time Phases Panel symmetrical fault level Conductor Copper Insulation Tri Rated Mineral Table 43A "k" value Temperature coefficient

349 1 MG19270 C60HC116 16 16 20 kA 10 * Range max


20 KA2s 160 Amps 230 V 25 milliseconds

1
37 KVA

Y Y N 143

143.00 Conductor Cable test csa mm2 Maximum current available Current Voltage drop 1.5 27712 Passed Passed Heating time (t) seconds = (k2*s2)/I2 1.7973 Seconds 1797.28 milliseconds Conductor energy let through capability 46010.25 A2s 46.01 KA2s Conductor short circuit energy capability Passed Device tripping speed Passed Note device OK

Page 8 of17 135554903.xls.ms_office

Short circuit protection calculations Site Name March Crematorium Contract Number C4??? Tag No EES21001 Use No2 Cremator panel supply Supply fault rms current level (KVA) % Reactance Protective device Range Short circuit rating Short circuit release Max energy let through Max short circuit setting Operating voltage Tripping time Phases Panel symmetrical fault level Conductor Copper Insulation Tri Rated Mineral Table 43A "k" value Temperature coefficient

349 1 MG19270 C60HC116 16 16 20 kA 10 * Range max


20 KA2s 160 Amps 230 V 25 milliseconds

1
37 KVA

Y Y N 143

143.00 Conductor Cable test csa mm2 Maximum current available Current Voltage drop 1.5 27712 Passed Passed Heating time (t) seconds = (k2*s2)/I2 1.7973 Seconds 1797.28 milliseconds Conductor energy let through capability 46010.25 A2s 46.01 KA2s Conductor short circuit energy capability Passed Device tripping speed Passed Note device OK

Page 9 of17 135554903.xls.ms_office

Short circuit protection calculations Site Name March Crematorium Contract Number C4??? Tag No EES101 Use No1 Control panel isolator Supply fault rms current level (KVA) % Reactance Protective device Range Short circuit rating Short circuit release Max energy let through Max short circuit setting Operating voltage Tripping time Phases Panel symmetrical fault level Conductor Copper Insulation Tri Rated Mineral Table 43A "k" value Temperature coefficient

37 1 PKZM0-16 16 16 25 kA 10 * Range max


25 KA2s 160 Amps 230 V 25 milliseconds

1
37 KVA

Y Y N 143

143.00 Conductor Cable test csa mm2 Maximum current available Current Voltage drop 1.5 27712 Passed Passed Heating time (t) seconds = (k2*s2)/I2 1.7973 Seconds 1797.28 milliseconds Conductor energy let through capability 46010.25 A2s 46.01 KA2s Conductor short circuit energy capability Passed Device tripping speed Passed Note device OK

Page 10 of17 135554903.xls.ms_office

Short circuit protection calculations Site Name March Crematorium Contract Number C4??? Tag No MCB 1 Use PLC and Instrument supplies Supply fault rms current level (KVA) % Reactance Protective device Range Short circuit rating Short circuit release Max energy let through Max short circuit setting Operating voltage Tripping time Phases Terminal symmetrical fault level Conductor Copper Insulation Tri Rated Mineral Table 43A "k" value Temperature coefficient

37 1 MG19264 6 6 10 kA 8 * Range max


10 KA2s 48 Amps 230 V 25 milliseconds

1
11 KVA

Y Y N 143

143.00 Conductor Cable test csa mm2 Maximum current available Current Voltage drop 1.5 8314 Passed Passed Heating time (t) seconds = (k2*s2)/I2 19.9697 Seconds 19969.73 milliseconds Conductor energy let through capability 46010.25 A2s 46.01 KA2s Conductor short circuit energy capability Passed Device tripping speed Passed Note device OK

Page 11 of17 135554903.xls.ms_office

Short circuit protection calculations Site Name March Crematorium Contract Number C4??? Tag No MCB 2 Use Underpressure and sockets Supply fault rms current level (KVA) % Reactance Protective device Range Short circuit rating Short circuit release Max energy let through Max short circuit setting Operating voltage Tripping time Phases Terminal symmetrical fault level Conductor Copper Insulation Tri Rated Mineral Table 43A "k" value Temperature coefficient

37 1 MG19264 6 6 10 kA 8 * Range max


10 KA2s 48 Amps 230 V 25 milliseconds

1
11 KVA

Y Y N 143

143.00 Conductor Cable test csa mm2 Maximum current available Current Voltage drop 1.5 8314 Passed Passed Heating time (t) seconds = (k2*s2)/I2 19.9697 Seconds 19969.73 milliseconds Conductor energy let through capability 46010.25 A2s 46.01 KA2s Conductor short circuit energy capability Passed Device tripping speed Passed Note device OK

Page 12 of17 135554903.xls.ms_office

Short circuit protection calculations Site Name March Crematorium Contract Number Tag No MCB 3 Use Burner supplies Supply fault rms current level (KVA) % Reactance Protective device Range Short circuit rating Short circuit release Max energy let through Max short circuit setting Operating voltage Tripping time Phases Terminal symmetrical fault level Conductor Copper Insulation Tri Rated Mineral Table 43A "k" value Temperature coefficient

C4???

37 1 MG19264 6 6 10 kA 8 * Range max


10 KA2s 48 Amps 230 V 25 milliseconds

1
11 KVA

Y Y N 143

143.00 Conductor Cable test csa mm2 Maximum current available Current Voltage drop 1.5 8314 Passed Passed Heating time (t) seconds = (k2*s2)/I2 19.9697 Seconds 19969.73 milliseconds Conductor energy let through capability 46010.25 A2s 46.01 KA2s Conductor short circuit energy capability Passed Device tripping speed Passed Note device OK

Page 13 of17 135554903.xls.ms_office

Short circuit protection calculations Site Name March Crematorium Contract Number C4??? Tag No MCB 4 Use 230/24V Transformer supply Supply fault rms current level (KVA) % Reactance Protective device Range Short circuit rating Short circuit release Max energy let through Max short circuit setting Operating voltage Tripping time Phases Terminal symmetrical fault level Conductor Copper Insulation Tri Rated Mineral Table 43A "k" value Temperature coefficient

37 1 MG19264 6 6 10 kA 8 * Range max


10 KA2s 48 Amps 230 V 25 milliseconds

1
11 KVA

Y Y N 143

143.00 Conductor Cable test csa mm2 Maximum current available Current Voltage drop 1.5 8314 Passed Passed Heating time (t) seconds = (k2*s2)/I2 19.9697 Seconds 19969.73 milliseconds Conductor energy let through capability 46010.25 A2s 46.01 KA2s Conductor short circuit energy capability Passed Device tripping speed Passed Note device OK

Page 14 of17 135554903.xls.ms_office

Short circuit protection calculations Site Name March Crematorium Contract Number Tag No MCB 5 Use Analytical supply Supply fault rms current level (KVA) % Reactance Protective device Range Short circuit rating Short circuit release Max energy let through Max short circuit setting Operating voltage Tripping time Phases Terminal symmetrical fault level Conductor Copper Insulation Tri Rated Mineral Table 43A "k" value Temperature coefficient

C4???

37 1 MG19266 10 10 10 kA 8 * Range max


10 KA2s 80 Amps 230 V 25 milliseconds

1
18 KVA

Y Y N 143

143.00 Conductor Cable test csa mm2 Maximum current available Current Voltage drop 1.5 13856 Passed Passed Heating time (t) seconds = (k2*s2)/I2 7.1891 Seconds 7189.10 milliseconds Conductor energy let through capability 46010.25 A2s 46.01 KA2s Conductor short circuit energy capability Passed Device tripping speed Passed Note device OK

Page 15 of17 135554903.xls.ms_office

Short circuit protection calculations Site Name March Crematorium Contract Number Tag No EES14101 Use Insertion door supply Supply fault rms current level (KVA) % Reactance Protective device Range Short circuit rating Short circuit release Max energy let through Max short circuit setting Operating voltage Tripping time Phases Terminal symmetrical fault level Conductor Copper Insulation Tri Rated Mineral Table 43A "k" value Temperature coefficient

C4???

37 1 MG19266 10 10 10 kA 8 * Range max


10 KA2s 80 Amps 230 V 25 milliseconds

1
18 KVA

Y Y N 143

143.00 Conductor Cable test csa mm2 Maximum current available Current Voltage drop 1.5 13856 Passed Passed Heating time (t) seconds = (k2*s2)/I2 7.1891 Seconds 7189.10 milliseconds Conductor energy let through capability 46010.25 A2s 46.01 KA2s Conductor short circuit energy capability Passed Device tripping speed Passed Note device OK

Page 16 of17 135554903.xls.ms_office

Short circuit protection calculations Site Name March Crematorium Contract Number Tag No EES13101 Use Deash door supply Supply fault rms current level (KVA) % Reactance Protective device Range Short circuit rating Short circuit release Max energy let through Max short circuit setting Operating voltage Tripping time Phases Terminal symmetrical fault level Conductor Copper Insulation Tri Rated Mineral Table 43A "k" value Temperature coefficient

C4???

37 1 MG19266 10 10 10 kA 8 * Range max


10 KA2s 80 Amps 230 V 25 milliseconds

1
18 KVA

Y Y N 143

143.00 Conductor Cable test csa mm2 Maximum current available Current Voltage drop 1.5 13856 Passed Passed Heating time (t) seconds = (k2*s2)/I2 7.1891 Seconds 7189.10 milliseconds Conductor energy let through capability 46010.25 A2s 46.01 KA2s Conductor short circuit energy capability Passed Device tripping speed Passed Note device OK

Page 17 of17 135554903.xls.ms_office