Technical reference documentation. Configuration of Master using GX-configurator DP.

In GX-Configurator DP start a new project and select the QJ71PB92V.

The master settings can be left as default for easier setup, however these can be changed if necessary, in this case the Baud rate is 1.5Mbps, FDL Address is 0 and Start I/O Address is 0000. Click next.

Created on Version: Created By: Checked: Certified by:

11/02/2011 1 Christian J Warren Andy Esworthy 11/02/2011

Technical reference documentation.

In this window, the head addresses for buffering I/O and diagnostics are set. For easier setup these have been left as the default settings of Block transfer with Input data starting at D1000 and Output data starting at D2000. The diagnostic data areas have not been set in this case. It is important that the Consistency box is checked. Other settings have been left at their default setting.

Created on Version: Created By: Checked: Certified by:

11/02/2011 1 Christian J Warren Andy Esworthy 11/02/2011

Technical reference documentation.

Click Finish.

The main window should now be in view and should look similar to the following image.

Created on Version: Created By: Checked: Certified by:

11/02/2011 1 Christian J Warren Andy Esworthy 11/02/2011

Technical reference documentation.


Under Global GSD data select PLC and then drag and drop FX3U-32DP into the PROFIBUS Network window.

The following window will appear, in this window the slave settings are entered, in this case FDL Address is set to 1 for slave number 1 and slave is selected as active.

Created on Version: Created By: Checked: Certified by:

11/02/2011 1 Christian J Warren Andy Esworthy 11/02/2011

Technical reference documentation.

Click next. Drag and drop the required I/O to the project slave modules area.

Created on Version: Created By: Checked: Certified by:

11/02/2011 1 Christian J Warren Andy Esworthy 11/02/2011

Technical reference documentation.

Click next. In the main window it should look similar to the following image.

Created on Version: Created By: Checked: Certified by:

11/02/2011 1 Christian J Warren Andy Esworthy 11/02/2011

Technical reference documentation.


In the PROFIBUS Configuration Tasks window select I/O mapper.

In the I/O Mapper area, enter the head devices for user data for each of the blocks set for the slave module.

Created on Version: Created By: Checked: Certified by:

11/02/2011 1 Christian J Warren Andy Esworthy 11/02/2011

Technical reference documentation. Program written in ladder for Master.


In GX developer, set the following program for the QJ71PB92V.

This program check the status of the module and initialises the data exchange, the program also transfers data between the user areas and the buffer areas. The I/O signal for the QJ71PB92V are bases on the module being in head address 0, on this basis the following table shows all I/0 with details for the module relative to this position. For more details on this module

Created on Version: Created By: Checked: Certified by:

11/02/2011 1 Christian J Warren Andy Esworthy 11/02/2011

Technical reference documentation.

Inputs and Outputs for the QJ71PB92V

For more details on the QJ71PB92V please refer to the users manual ref: QJ71PB92V PROFIBUS/DP MASTER, Art. No. 166558, SH(NA)-080572, VERSION C.

Created on Version: Created By: Checked: Certified by:

11/02/2011 1 Christian J Warren Andy Esworthy 11/02/2011

Technical reference documentation. Program for FX3U Written in ladder for slave 1.
Open a new FX3U project in GX-Developer and enter the following program for the slave station.

Created on Version: Created By: Checked: Certified by:

11/02/2011 1 Christian J Warren Andy Esworthy 11/02/2011

Technical reference documentation.

This program sets the station number of the slave, checks the consistency and data exchange status. The program also writes data to the master and reads data from the master for 64 words each way. The method uses U/G instructions in this case as they are supported in the FX3U.

Created on Version: Created By: Checked: Certified by:

11/02/2011 1 Christian J Warren Andy Esworthy 11/02/2011

Technical reference documentation.

Program for FX3G Written in ladder for slave 1.


Open a new FX3G project in GX-Developer and enter the following program for the slave station.

Created on Version: Created By: Checked: Certified by:

11/02/2011 1 Christian J Warren Andy Esworthy 11/02/2011

Technical reference documentation.

This program sets the station number of the slave, checks the consistency and data exchange status. The program also writes data to the master and reads data from the master for 64 words each way. The method uses TO/FROM instructions in this case as the U/G instructions are NOT supported in the FX3G.

Created on Version: Created By: Checked: Certified by:

11/02/2011 1 Christian J Warren Andy Esworthy 11/02/2011

Technical reference documentation. Buffer memory areas used in FX3U-32DP

Created on Version: Created By: Checked: Certified by:

11/02/2011 1 Christian J Warren Andy Esworthy 11/02/2011

Technical reference documentation.

For more detail please refer to the FX3U-32DP users manual ref: FX3U-32DP PROFIBUS-DP INTERFACE BLOCK. Art. No JY997D25201, 01032007, Version A.