th ULCode8649 Edition

AnOverviewoftheForemostCode Updates

th 9 EditionofUL864,ANSI/UL864

Latest incarnationof astandard firstpublished in1948

NotethatUL864is anANSIstandard. ANSIisnational Norm. ANYNRTLcan certify. FMandULare equivalent

HONEYWELLCONFIDENTIAL

FileNumber

th UL8649 Edition

WhenpublishedinOctober2003the9thedition hadaneffectivedateofOctober31,2005 ThreesubsequentextensionsbyULhasmovedthe effectivedatetoJune30,2007 ULnolongeracceptsproductsforcertificationto the8thedition

HONEYWELLCONFIDENTIAL

FileNumber

GroundFaultSupervision

June30,2007

December31,2007 December31,2007

Groundfaultsarenolongerjustashorttoground ManufacturerspecifiestheamountofleakagetogroundandUL teststoverifythetrippoint Wiringinstallationworkmanshipisveryimportant!

HONEYWELLCONFIDENTIAL

FileNumber

ProductsinstalledinAirhandlingSpaces

June30,2007

Thisisanissueparticularlyforspeakersandassociatedwiring

HONEYWELLCONFIDENTIAL

FileNumber

DevicesInstalledinanOutletBox

June30,2007

Youcannotjustlayadeviceinanoutletbox!

HONEYWELLCONFIDENTIAL

FileNumber

WiringtheFireAlarm

June30,2007

Itisvitalthattheinstallerfollowminimumwiregagesize specifiedintheinstallationwiringdiagram

HONEYWELLCONFIDENTIAL

FileNumber

AlarmSignalProcessingTime

Thisisamajorchangefrom90secondsthathasbeenthe requirementforfireformorethan30years

HONEYWELLCONFIDENTIAL

FileNumber

TroubleSignalProcessingTime

Troublesignalprocesstimeremainsessentiallyunchanged Provisionisnowmadetodelaytransmissionofabatterytrouble toavoidoverloadingthecentralstationwhenanarealosespower

HONEYWELLCONFIDENTIAL

FileNumber

AlarmandTroubleSignalsAnnunciation

Voicesystemsmusthaveacommandcenterandthislocation mustindicateallalarmandtroublesignalsforthesystem.

10

HONEYWELLCONFIDENTIAL

FileNumber

VisualSignalAnnunciationattheControl

Canbeaholdupalarm!

11

HONEYWELLCONFIDENTIAL

FileNumber

AlarmSignaling

ThisistheTemporalThree
th Synchronizationintroducesnewcomplexitiesinthe9 edition

Compatibilityisacriticalissue Currentcalculationsandwiresizearecritical Powersupplyloading


NotetheexceptionThewholealarmsystemdoesnotneedtobe synchronized!

12

HONEYWELLCONFIDENTIAL

FileNumber

SupervisorySignals

SupervisorySignalsmustbedistinctlydifferentthantrouble signals.Thiscallsforaseparatedevicetobeusedunlessthe soundercanmakedifferentsounds. Notesupervisorysignalsgenerallydonotlatch

13

HONEYWELLCONFIDENTIAL

FileNumber

VoiceAlarmCommandCenter

ControlsActiveLEDonallONYXpanels

14

HONEYWELLCONFIDENTIAL

FileNumber

EmergencyVoice/AlarmFunctionSequence

ThisisconsistentwithNFPA72 Somemajorcommunities(i.e.Chicago)followadifferent sequence ItisvitaltobefamiliarwiththelocalHighRiseCode

15

HONEYWELLCONFIDENTIAL

FileNumber

FireWardenTelephoneCircuit

TheTelephonecircuitmustbesupervisedforopens,shorts andgrounds. Intodaysenvironment,communicationsforthefireservice personnelisavitalfunction.

16

HONEYWELLCONFIDENTIAL

FileNumber

OperationTimeRequirements

th Operatingtimerequirementsaregreatlychangedfromthe8 EditionofULs864Code.

Operatingtimeforalarmandsupervisoryannunciation reducedto10secondsfrom90. Troublesignalsremainat200seconds.

17

HONEYWELLCONFIDENTIAL

FileNumber

ReleasingDeviceService

Falsetrippingofareleasingdevicecircuit,besidesbeingan expensivemishap,canbeverydangerous. Thisrequirementspecificallyaddressesasituationwhenthe alarmpanelisbeingserviced.

18

HONEYWELLCONFIDENTIAL

FileNumber

NetworkedReleasingDevicePanels

Concernforfalsedumpscarriesovertonetworkedsystems. Ifmultiplesystemscantriggeradumpinthesamesystem,the statusofanypanelonthesystemmustbeannunciatedatthe otherpanelsconnectedtothesystem.

19

HONEYWELLCONFIDENTIAL

FileNumber

PreDischargeNotification

Releasingdevicecontrolpanelsmustprovideapredischarge warningtoalertthebuildingoccupants.

20

HONEYWELLCONFIDENTIAL

FileNumber

TemporalThree

NotethepanelmusthavethecapabilityofTemporalThree SomemunicipalitiesdonotpermittheTemporalThree therefore,therequirementisonemusthavethecapacity.

21

HONEYWELLCONFIDENTIAL

FileNumber

DeactivatingAlarmandDischarge

22

HONEYWELLCONFIDENTIAL

FileNumber

AbortSwitches

AbortSwitchesmustbemanuallyoperated. AbortSwitchesmustbeselfrestoring. AbortSwitchesmustNOTbeusedwithpreactionordeluge watersystems.

23

HONEYWELLCONFIDENTIAL

FileNumber

AbortSwitchCircuitSupervision

Theabortswitchcircuitmustmeetthesupervisionandstyle requirementsapplicabletoinitiatingcircuits.

24

HONEYWELLCONFIDENTIAL

FileNumber

AbortSwitchOperation

Operationoftheabortswitchduringafirealarmrequiresa distinctivevisualandaudibletroublesignal. Thevisualindicatormustbededicatedtotheabortfunction. Theaudiblemaybethecontrolpanelcommontroublesounder oradedicatedaudible

25

HONEYWELLCONFIDENTIAL

FileNumber

ManualReleaseSwitch

Manualreleaseswitchmustoverridealldelaysexceptmanual releasedelayperiod Releasemustoccurwithin30seconds Themanualabortswitchisnotrequiredtooverridethemanual releaseswitch.Thiscanbeaprogrammingfunction. Operatorsmanualmustspecifyifmanualoverrideisprovided.

26

HONEYWELLCONFIDENTIAL

FileNumber

ProtectedPremiseControlsTiming#1

27

HONEYWELLCONFIDENTIAL

FileNumber

ProtectedPremiseControlsTiming#2

Reporttimecanbe1minuteto4hoursbasedonFCCregulations.

Batterytroublesignalshallbetransmittedwithin4hours. Batterytroublesignalshallbetransmittedfor7days.

Immediatelocalannunciation.
Transmissionofsignalwithin60to180minutedelay. Immediatelocalannunciation. Transmissionoverworkingpathwithin4minutes.

28

HONEYWELLCONFIDENTIAL

FileNumber

ProtectedPremiseSignalAnnunciation

Ifthesignalssenttoaremotesupervisorystationdonot includezoneinformationforamultizonepanel,zone informationmustbeindicatedatthepanel. Ifindicationisnotlampperzone,itmustinclude: Signalprioritization Indicationbytype Indicationbyzone

29

HONEYWELLCONFIDENTIAL

FileNumber

DigitalRadioAlarmTransmitters

Mechanicallyprotectedmeansconduit Ifthetransmittingantennaoftransmitter/antennacombination areremote,conduitisrequired

30

HONEYWELLCONFIDENTIAL

FileNumber

DACTDualLineRequirement

Requirementincludes:

Indicationoffaultsubscriberlocation Cannotinhibitothersubscriber Faultsincludesingleopen,ground,wiretowireshort&noise Signalrestorationofservice Faultconditionandrestorationsmustbeannunciatedatthe


supervisingstationwithin200seconds

31

HONEYWELLCONFIDENTIAL

FileNumber

NewTransmissionTechnologies

NFPA72,includingthe2007edition,isbasicallyaprescriptive standard Eachtechnologyistreateddifferently

Thereisnocorrelationbetweentechnologies Technologiesarenotratedastotheirstrength
NFPAtechnicalcommitteerecognizedthislimitationand createdtheOtherTechnologiesTransmissionsection ThisiswhereInternetbasedrequirementsoriginated

32

HONEYWELLCONFIDENTIAL

FileNumber

Timetotransmitanalarmsignal

The10secondsappliestoallsignalprocessingatthe protectedpremise. Troubleannunciationorsignalretransmissionremainsat200.

33

HONEYWELLCONFIDENTIAL

FileNumber

MultiZoneSystems

Note: Aholdup alarmcan havesame priorityas fire

Burglar Alarm

34

HONEYWELLCONFIDENTIAL

FileNumber

ComponentReliability

th In8 edition,50%deratingwasrequired. th In9 edition,864adoptsaprocessfirstintroducedinUL217.

Thischangepermitsmoredesignflexibility.

35

HONEYWELLCONFIDENTIAL

FileNumber

Software

Softwarehasbecomeamajorconcern. ItiscriticalthattheA&Eandinstallerbefamiliarwiththe programmingfunction. Itisparticularlycriticalthateachoftheprogrammingoptionsbe understoodwithregardtostandardcompliance.

36

HONEYWELLCONFIDENTIAL

FileNumber

Softwarecompliancewiththestandard

Softwarehasmadepossibletheconceptofauniversalpanel. AllfeaturesandoptionsmaynotbecompliantwithUL864or NFPA72. ItisvitalthattheA&Ereviewtheoptionsselectedtoassure compliance.


37 HONEYWELLCONFIDENTIAL
FileNumber

ExecutiveSoftwaretracking

KnowingtheRev.levelofthesoftwareisveryimportant particularlywhenaproblemoccurs.

38

HONEYWELLCONFIDENTIAL

FileNumber

UserAccessandProgramming

Mappingofoutputcircuitsispermitted. Mappinginputcircuitstosupervisingstationisnotpermitted. Theexecutiveprogramdoesautomaticmappingofcritical functions.


39 HONEYWELLCONFIDENTIAL
FileNumber

CombinationSystems

Anythingnonfireconnectedtoafirealarmsystemcannot causeanydegradationofsupervisionoralarmfunctions. Testingisconductedbyplacingopens,shorts,groundson thesecircuitstoverifyNOTHINGhasbeencompromised.

40

HONEYWELLCONFIDENTIAL

FileNumber

InterconnectedFireAlarmControlUnits

ThisisaconcernforA&EandInstallerhowandwhereyou installisveryimportant. Unlessyoucanseethedisplaysonallofthealarmpanelsat thesametime,ALLpanelsmustconcurrentlydisplay:

Alarm Supervisory Trouble Reset AlarmSilence TroubleSilence


41 HONEYWELLCONFIDENTIAL
FileNumber

PowerSupplyCapacity

Thepowersupplyshallbecapableofoperatingthesystem underfullloadwithsupplyvoltageat85%ofratedwithbattery disconnected. Thesystemmustbecapableoffullychargingthebatterywhen thesupplyvoltageisreducedto85%(ortransfervoltage)of ratedvoltage.

42

HONEYWELLCONFIDENTIAL

FileNumber

NotificationApplianceCircuits
CompatibilityofNotificationApplianceswithspecificpanels isnowcritical Voltagecalculationsareveryimportantonecantaddjust onemoredevice Synchronizationisacriticalfactorasthesteadystateload canbeverymuchlessthenthepeakload Greatcaremustbetakeninselectingnotificationappliances forusewithaparticularpanel. Thepanelinstallationinstructionsandwiringdiagramsare yourprimaryguide.

43

HONEYWELLCONFIDENTIAL

FileNumber

RatingDesignations


44

AllNACcircuitsmustbeidentifiedbyoneofthesedesignations AllNACcircuitsmustoperatewithinthespecifiedvoltagerange Notethespecialapplicationcategory


HONEYWELLCONFIDENTIAL
FileNumber

RegulatedNACCircuits

45

HONEYWELLCONFIDENTIAL

FileNumber

SpecialApplicationNACCircuits

46

HONEYWELLCONFIDENTIAL

FileNumber

RegulatedNACSurgeCurrentLoading

Loadingforfirstsurgeis10Xsteadystateratingofcircuit Loadingforrepetitivesurgesis5Xsteadystaterating

47

HONEYWELLCONFIDENTIAL

FileNumber

SpecialApplicationSurgeCurrentLoading

Onlydevicesspecifiedinthepanelinstallationdocumentation arepermitted!
48 HONEYWELLCONFIDENTIAL