Commissioning 5.

5 Commissioning using the BOP

5.5
5.5.1

Commissioning using the BOP


The Basic Operator Panel (BOP)
The Basic Operator Panel (BOP) is used for effective parameterizing and control of the inverter. The control signals and speed reference can easily be set by pressing the appropriate buttons. The BOP has the ability to upload and download parameter sets from an inverter to another inverter.

Basic Operator Panel (BOP), 6SL3255-0AA00-4BA1

Fitting the BOP to the Control Unit


The BOP is fitted to the Control Unit as shown in the figure below. No matter which type of Control Unit is being used, the process is the same.

Fitting the BOP to the CU

Control Units CU240S Operating Instructions, 11/2008 - FW 3.2, A5E00766042B AE

55

Commissioning 5.5 Commissioning using the BOP

5.5.1.1

Function Keys of the BOP

Basic Operator Panel - function keys


Table 5- 3 BOP keys and their functions Function Status display Start motor (Green) Stop motor (Red) OFF2 Direction reversal Jog motor Effects The LCD indicates the settings which the drive inverter is presently using. The display reports faults and alarms. The inverter is started by pressing the key. This key is deactivated in the default setting. Parameter P0700 should be changed as follows to activate the key: BOP: P0700 = 1 OFF1 When this key is pressed, the motor comes to a standstill within the selected ramp-down time. It is deactivated in the default setting; to activate refer to the "Start motor" key. The motor coasts down to a standstill by pressing the key twice (or pressing once for a longer period of time). This function is always activated.

Basic Operator Panel Key

To reverse the direction of rotation of the motor, press this key. The opposing direction is displayed using the minus character (-) or by the flashing decimal point. In the default setting this function is deactivated. To activate it refer to the "Start motor" key. In the "Ready to run" state, when this key is pressed, the motor starts and rotates with the pre-set jog frequency. The motor stops when the key is released. When the motor is rotating, this key has no effect. This key can be used to display additional information. If you press the key during operation, independent of the particular parameter, for two seconds, the following data will be displayed: 1. Voltage of the DC current link (designated by d units V). 2. Output current (A) 3. Output frequency (Hz) 4. Output voltage (designated by o units V). 5. The value, selected in P0005 (if P0005 is configured so that one of the above pieces of data is displayed (1 to 4), then the associated value is not re-displayed). The displays mentioned above are run-through one after the other by pressing again. Step function button briefly makes the display to jump from any parameter (rXXXX or Pressing the PXXXX) to r0000 and vice versa. After quitting an alarm, r0000 will be displayed and the "jumped from parameter" is forgotten. Acknowledgement If alarm and fault messages are present, then these can be acknowledged by pressing key .

Function key

Parameter access Increase value Reduce value

Parameters can be accessed by pressing this key. When this key is pressed, the displayed value is increased. When this key is pressed, the displayed value is decreased.

56

Control Units CU240S Operating Instructions, 11/2008 - FW 3.2, A5E00766042B AE

Commissioning 5.5 Commissioning using the BOP

5.5.1.2

Changing Parameters via BOP

Changing parameter with the BOP


The description below serves as an example that shows how to change any parameter using the BOP.
Table 5- 4 Step 1 2 3 4 5 6 Press Press Press Press Press to access parameters until P0003 is displayed to display the parameter value or to set the required value (set to 3) to confirm and store the value Changing P0003 - parameter access level Result on display

All level 1 to level 3 parameters are now visible to the user.

Table 5- 5 Step 1 2 3 4 5 6 7 8 9 Press Press Press Press Press Press Press Press Press

Changing P0700 an index parameter - setting BOP control Result on display to access parameters until P0700 is displayed to access the parameter value or or to select index 1 to the required value to display actual set value to confirm and store the value until r0000 is displayed to return the display to the standard drive display (as defined by the customer)

Note The BOP sometimes displays "bUSY" when changing parameter values. This means that the inverter is presently handling another higher-priority task.

Control Units CU240S Operating Instructions, 11/2008 - FW 3.2, A5E00766042B AE

57

Commissioning 5.5 Commissioning using the BOP

5.5.2

Overview Commissioning with the BOP

Commissioning overview
A differentiation is made between the following scenarios when commissioning the inverter via BOP:

Single commissioning
Basic commissioning Quick commissioning Calculating the motor data, - automatically via Motor data identification - or manually via P0340 Speed control optimization Commissioning the application Commissioning the fail-safe functions (only in fail-safe applications)

Series commissioning
Uploading the parameter set Downloading the parameter set

Reset parameters to factory settings


Sets the parameter settings of the inverter settings back to the delivery state. When commissioning, initially, a commissioning should be performed. If there is no appropriate parameter set available for series commissioning, a single commissioning must be carried-out. With the function "quick commissioning", the inverter is adapted to the motor and important technological parameters are set. The step "commissioning the application" should only be performed, if the invertermotor combination provides a satisfactory result.

58

Control Units CU240S Operating Instructions, 11/2008 - FW 3.2, A5E00766042B AE