Sei sulla pagina 1di 16

PREPARED BY CHECKED BY APPROVED BY CERTIFIED (PTT) REV. DATE NO.

D1 18-Feb-08 D2 01-Jul-08

PTT PUBLIC COMPANY LIMITED ONSHORE COMPRESSOR STATION 4 PROJECT

REVISED BY

APPROVED BY

DESCRIPTION ISSUED FOR ITB REVISION ISSUED FOR ITB

SPECIFICATION FOR PIPING LAYOUT


SPC-0804.02-50.05 REV.D2
TOTAL 16 PAGES

AREA CODE OF SITE LOCATION GENERAL AREA: 010 PTT PLC. CONTRACT NO.

PTT PLC. PROJECT NO. 0804.02

PIPING LAYOUT

PTT PUBLIC COMPANY LIMITED ENGINEERING SPECIFICATION CONTENTS

SPC-0804.02-50.05 PAGE: 2 of 16 REV: D2

SECTION 1.0 2.0 3.0 4.0 5.0 6.0 SCOPE ................................................................................................. 3 GENERAL LAYOUT REQUIREMENTS ........................................................ 3 BOLT AND NUT, VENT, DRAIN AND SAMPLE CONNECTIONS .................... 7 SERVICE PIPING.................................................................................... 9 INSTRUMENTS ................................................................................... 11 EQUIPMENT PIPING ............................................................................. 13

PIPING LAYOUT 1.0 SCOPE

PTT PUBLIC COMPANY LIMITED ENGINEERING SPECIFICATION

SPC-0804.02-50.05 PAGE: 3 of 16 REV: D2

This Standard covers the requirements for piping design and piping layout. Excluded are a) All instrument control piping downstream of the first piping block valve.

b) All heating, ventilation air and water services within buildings. Where local plant conditions or space limitations dictate that this Standard cannot be applied, proposed deviations shall be submitted for PTT/CONSULTANTS approval. Piping furnished as a regular part of proprietary equipment shall be in accordance with the requirements of this Standard. 2.0 2.1 GENERAL LAYOUT REQUIREMENTS Piping Arrangement Piping shall be arranged in an orderly manner and routed as directly as practical, considering economy, accessibility for operation, maintenance, construction and safety, in established banks or pipe ways. Piping on elevated racks shall run at different elevations designated for north-south and east-west banks, and change elevation when changing direction. Combined changes in direction and level in pipe ways shall normally be made with 90o bends. Where necessary, a 90o bend and a 45o bend may be used. Relative elevations of pipe ways shall be set to provide sufficient clearance between lines at intersections. Flat turns at changes in direction shall be avoided on elevated pipe racks, except lines requiring a slope and/or no pockets (e.g. Flare, Blow Down etc.). Dead ends and pockets in lines are to be avoided.

In pipe tracks and pipe racks hot lines shall be grouped together and expansion loops shall be nested. The number of expansion loops should be kept to a minimum, consistent with the stress requirements.

PIPING LAYOUT

PTT PUBLIC COMPANY LIMITED ENGINEERING SPECIFICATION

SPC-0804.02-50.05 PAGE: 4 of 16 REV: D2

Provision shall be made for the flushing of all lines after hydrostatic testing, and shall normally be done by the use of a removable spool piece or on long lines with a line size flange and blank at the end of the line. Overhead lines for acid, caustic or other corrosive services must not have flanged joints located above access ways or platforms. Where pipe work is laid on overhead structures, (in) tracks or in permanent trenches and requires dismantling for process reasons, the arrangement and clearances should permit removal of any pipe, fitting, or valve without the necessity to disturb adjacent pipe work. Except when required for frequent maintenance or commissioning and testing, the use of flanges in piping shall be limited to connection at flanged equipment.

Generally, lines shall be run horizontally; however, where lines need to be drained completely, the piping shall be sloped and fitted with drainage points. Lines to be sloped shall be indicated on the Piping and Instrument Diagram. All safety valves inlet lines shall slope and free drain towards the process line and all flared lines shall slope towards the knockout drums with the minimum slope as required on PD-10-13240-3515-01. Underground lines shall have means for testing, draining and flushing. Branch connections from horizontal air mains shall be taken from the top of the main. Piping arrangements shall ensure that installed valves are readily accessible and easy to operate. Where valves are secured in position only by being clamped between pipe work flanges, e.g. wafer valves, the effect of removing the adjoining pipe work shall be taken into account. Valves shall not be installed with their stems below the horizontal. Access shall be provided for valves in ground level pipe tracks, the valves being suitably grouped as far as practicable. Valve with extended stems in cold services that may contain liquids shall have their stems located in a vertically upwards position to ensure that cryogenic

PIPING LAYOUT

PTT PUBLIC COMPANY LIMITED ENGINEERING SPECIFICATION

SPC-0804.02-50.05 PAGE: 5 of 16 REV: D2

liquids will not come into contact with the stem packing area. Exceptions may be made for vent/ drain and instrumentation block valves. Valves in insulated lines shall be designed to allow unrestricted operation. It may be necessary to install extended stems so that the hand wheel is located clear of the insulation cladding. Valves shall generally be at a preferable working height between 1,000 mm and 1,350 mm to centerline of hand wheel. 2.2 Clearances Piping systems shall be designed and equipment laid out to provide access by mobile equipment. Space shall be left around equipment and piping to facilitate maintenance (tube bundle removal, cleaning, etc). 2.2.1 Clearance between Pipelines and between Pipe and Concrete and Steel Constructions The minimum distance is generally 50mm. When deciding the spacing of the pipes, the thermal expansion and contraction must be considered. Clearance between the outside diameter of flange and the outside diameter of pipe or insulation: 25 mm. The following minimum clearance shall be provided between piping and equipment, considering the thickness of insulation of either one, if any: 1. 2. 3. 4. Passage ways between pumps Passage ways between exchangers Clearance between piping and equipment One side of the control valve piping 800 mm 800 mm 50 mm 600 mm

2.2.2 Clearance to the Bottom of Piping Minimum clearance to the bottom of piping shall generally be as follows: 1. 2. 3. 4. 5. Above platforms and walkways: Inside buildings: Above plant roads: Above mobile lifting equipment access areas: Intersections at pipe ways 2,100 mm 2,100 mm 6,000 mm 6,000 mm 250 mm

PIPING LAYOUT 6. 2.3

PTT PUBLIC COMPANY LIMITED ENGINEERING SPECIFICATION

SPC-0804.02-50.05 PAGE: 6 of 16 REV: D2 4,500 mm

Under main pipe racks:

Inside Process Areas Pipe work shall be carried on overhead pipe racks wherever practicable, and clear ways provided where necessary to allow the operation of cranes and other mobile equipment for maintenance purposes. Battery limit valves, spades and drains may be located in vertical or horizontal, except for the flare and relief systems. Permanent platform access shall be provided. Where more than one unit is located within the same process area battery limit, separate utility headers provided with isolation valves shall be required for any unit which is not fully integrated.

2.4

Outside Process Areas This pipe work shall run on pipe ways at ground level or in overhead pipe racks. When above-ground lines and underground lines run parallel to one another, the above-ground lines shall not be laid directly over the underground lines. Pipes run in culverts shall be accessible for inspection. Lines at ground level shall be grouped together, to form grade tracks and shall be run on supports, to give the lines on the same bottom elevation.

2.5

Piping Flexibility Piping shall be designed with sufficient flexibility to absorb any excessive stresses. Expansion loops shall be used to absorb excess stresses where the normal pipe routing is too rigid. Expansion bellows shall only be used in special cases and shall be subject to written approval from the PTT/CONSULTANT.

2.6

Critical Piping Where dynamic loading, minimal flow conditions, or other severe service conditions apply, piping shall be designed and checked to ensure that its size, configuration, mechanical strength, supports and restraints will prevent excessive stress, pressure drop, vibration or noise.

PIPING LAYOUT

PTT PUBLIC COMPANY LIMITED ENGINEERING SPECIFICATION

SPC-0804.02-50.05 PAGE: 7 of 16 REV: D2

Dynamic loading may be expected when pulsation flow (such as at reciprocating compressors), high-velocity flow, flashing fluid, fluctuating temperature or pressure, or mechanical vibration (including wind) conditions exist. Limited pressure drop conditions may be expected in large vapor lines, heater transfer lines, re-boiler circuits, pump suctions, safety valve in- and outlet lines, and gravity flow lines. Such piping to be routed as directly as practical. 2.7 Pipe Supports, Anchors and Guides All piping must be adequately supported and restrained to prevent undue vibration, deflection and stresses or loads on equipment. All pipe supports, guides, etc, are to be located on the isometrics and piping plan. Piping sections requiring frequent dismantling shall be provided with permanent support for the dismantled condition. During maintenance shutdowns temporary supports shall be used. As a last resort, 1 inch or smaller diameter lines may be supported by large diameter lines where support spacing exceeds allowable spans for small lines. Intermediate supports consisting of a horizontal member bolted to clamps on large lines shall be provided. Small lines shall be grouped to run on this member between the two larger lines. The operating temperature of the supporting lines shall not exceed 65oC. 3.0 3.1 BOLT AND NUT, VENT, DRAIN AND SAMPLE CONNECTIONS Bolt and Nut After bolt and nut had been tighten at correct torque (prior to insulate, if required), they shall be degreased to remove any contaminated fat, grease or oil by using degreaser then two pack surface tolerant-high solid epoxy ( Jotamastic 87) shall be applied to the bolt and nut at least two layers: 1st- Jotamastic 87 with 25% thinner solvent 2nd-Jotamastic 87 with less thinner solvent Bolt and nut which serviced at temperature (design temperature) higher than 100 deg C or lower than -10 deg C, CONTRACTOR shall propose other appropriate paint for such temperature to PTT for prior approval.

PIPING LAYOUT

PTT PUBLIC COMPANY LIMITED ENGINEERING SPECIFICATION

SPC-0804.02-50.05 PAGE: 8 of 16 REV: D2

After painting, uninsulated flange ( size 4 and above )shall be protected with CORROSHIELD flange protection system. Nut, bolt shall be protected by using metal or UV stabilized prolypropylene cap ,with special grease , flange and gap between flange shall also be protected. Protection system including grease shall be from HDRATIGHT SWEENY (UK) or NUT-SEAL (USA). Bolt and nut shall be Fluoropolymer Coating. For ease of bolt and nut removal, flange shall not be connected directly to elbow. A minimum of 5D short pieces shall be provided between flange and elbow. 3.2 Vents and Drains Vents and drains shall be located as follows: All high points of lines shall be vented. Process vents to be indicated on the piping and instrument diagram. Vents for pressure tests shall be indicated by the Contractor. All vents to be fitted with valves and blind flange, clearance for insulation is to be considered. Under no circumstances are half couplings or similar, plugged and back-welded after testing, to be used. All low points of lines shall be drained. Drains shall be fitted with valve (s) and blind flange and have a minimum clearance of 250 mm below the drain. Only flanged valve shall be used for amine service or line where Post Weld Heat Treatment is required. Casing vents and drains for pumps in non-volatile services shall be valved and piped to the pump base plate or into a gutter or sewer. Casing vents and drains for pumps in services handling material near the flash point shall be piped to a cooler and from the cooler to a sewer; or alternatively piped to an operating line, relief or blow-down line or to a safe location. Note that where the drain is to a closed system, facilities shall be provided for installing blinds for test purposes.

PIPING LAYOUT 3.3 Sample Connections

PTT PUBLIC COMPANY LIMITED ENGINEERING SPECIFICATION

SPC-0804.02-50.05 PAGE: 9 of 16 REV: D2

Requirements for sample connections and sample coolers shall be indicated on the Piping and Instrument Diagram. The effect on the area classification shall be considered when arranging the position of the sample point. Cooling shall be provided for sample outlets in piping or equipment operating at 66oC or higher. One cooler may be used for grouped sample outlets. Sample connection inlet lines, which are tapped from a horizontal main pipeline, shall be connected from the top of pipe for vapour contents and from the bottom of pipe for liquid(with isolation valve). All sampling vents/drains shall be arranged as a close system as follow : (with isolation valve) Connection to the same system but lower pressure destination. Connection to flare or other appropriate drainage system shall be subjected to PTT for approval.

All operational parts of the sampling system shall be easily accessible, including the primary isolation valve. Sample points shall either be approximately 1 m above ground level or 1 m above a platform level, which shall be provided with a stairway access but subject to PTT approval. Length of sample piping shall be kept as minimum length. Connection between sampling storage with process piping shall be locking dog mechanism with large contract area used to stem retention stainless steel quick coupling. 4.0 4.1 SERVICE PIPING Steam Piping Steam piping shall be designed for complete condensate removal. Drip legs shall be provided on all steam lines at low points and dead ends. Branch connections shall be taken off the top of the headers and shall be 1 minimum size.

PIPING LAYOUT

PTT PUBLIC COMPANY LIMITED ENGINEERING SPECIFICATION

SPC-0804.02-50.05 PAGE: 10 of 16 REV: D2

Block valves shall be installed in the horizontal run of each branch line unless otherwise shown on Piping and Instrument Diagrams. 4.2 Steam Traps Steam traps shall be provided at low points and drip legs of steam lines. Traps shall be located adjacent to the equipment they serve. They shall be accessible for maintenance from grade or platform firmly supported. No steam trap shall be connected to more than one steam line nor to more than one section of the same line. Valves shall be located on each side of a steam trap for trap removal on closed systems. Steam traps discharging to the atmosphere shall have upstream block valves only. 4.3 Utility Stations Utility hose stations shall be installed throughout the process area to provide water, air and inert gas (normally will be Filtered water, Utility air, Nitrogen). Demin water and Steam utility may be provided additionally in some utility station where necessary. These utility stations shall be located so that working areas at grade, vessels or structures can be reached with a 15m length of hose. Utility stations shall be installed such that they remain in service during unit shutdown. Each utility type in station shall be clearly marked. Two (2) hoses (15 meter length each, size) and hose rack shall be provided per each utility station. Stainless steel quick coupling shall be furnished, hose ends shall be male and female, station end shall be male. One utility station shall be provided at each manhole of pressure vessel, tank, furnace, WHRU. Utility for vessel man hole shall be provided air and inert gas.

PIPING LAYOUT 4.4 Air System Piping

PTT PUBLIC COMPANY LIMITED ENGINEERING SPECIFICATION

SPC-0804.02-50.05 PAGE: 11 of 16 REV: D2

Air system piping design shall allow for good drainage. Drain valves and drip legs shall be provided at the low points of systems. Branch connections shall be from the top of the header. 4.5 Emergency Showers Eye-washing fountains and emergency showers shall be provided near equipment or pipe manifolds in acid, caustic, phenol, or other hazardous services. They shall be made from stainless steel. The fixtures shall be installed at locations conveniently accessible for emergency use. Emergency showers shall be arranged for overhead delivery of water spray. Water for eye-washing fountains and emergency showers shall be supplied from the drinking water system and shall be maintained at suitable constant temperature. Self-closing valves and self-draining hydrants shall be furnished. 5.0 5.1 INSTRUMENTS Control Valves Where control valves size are less than line sizes; reducers shall be placed adjacent to the valve. Concentric reducers shall be used on socket weld and screwed fittings, eccentric reducers (bottom flat) on butt-weld fittings. Spools or reducers between flanged block and control valves shall be made long enough to permit bolt removal. Control valves shall be adequately supported to avoid pipe loads or movements being transmitted to the control valves. Supports shall be located so that the assembly is self-supporting when control valve is removed. All control valves shall be accessible and preferably be located at grade level for operation and maintenance convenience. The actuators shall be installed in a vertical position in horizontal lines. Where possible, control valves operated in conjunction with remote instruments, should be located so that gauge or transmitter is visible from the control valve position. Control valve manifolds shall be designed to allow for easy removal of the control valve. Sufficient clearance shall also be provided above and below the control valve for removal of the actuator plug.

PIPING LAYOUT

PTT PUBLIC COMPANY LIMITED ENGINEERING SPECIFICATION

SPC-0804.02-50.05 PAGE: 12 of 16 REV: D2

A depressurizing valve is to be located between the upstream block valve and the control valve. All above requirements shall be applicable to all other automatic valve; e.g. emergency shut down valve etc. 5.2 Flow Instruments Horizontal metering runs shall be provided for liquid flow measurement and in all cases where segmental orifices are used. Vertical runs with downward flow may be used for steam and condensibles, and upward flow for liquids near their boiling points. Orifice flange taps (in horizontal pipelines) shall be orientated as follows: Liquid service: Gas service: 45o below the horizontal 45o below the vertical

Steam/ condensation service: horizontal A minimum clearance of 750mm shall be allowed above and to one side of orifice flanges to allow for the installation of impulse piping, manifold and instrument housing. 5.3 Level Instruments The level in level gauges shall be visible from grade ladder or a platform and its associated level control instrument and level switches, where possible. Level gauges and control instruments shall not penetrate platforms. 5.4 Temperature Instruments Connection for dial thermometers in piping or equipment shall be located so that the instrument can be easily read from grade or platform or ladder, and so that the thermowell element can be easily withdrawn. 5.5 Pressure Instruments Connection for local pressure gauge shall be located so instruments can easily be read from the grade or platform or ladder.

PIPING LAYOUT 6.0 6.1 EQUIPMENT PIPING

PTT PUBLIC COMPANY LIMITED ENGINEERING SPECIFICATION

SPC-0804.02-50.05 PAGE: 13 of 16 REV: D2

Vessel and Column Piping Piping and platforms around columns and vertical vessels shall be arranged so that, where necessary, there is a clear space for lowering equipment to the ground. Piping shall be arranged so that, blinds can be readily installed at vessel nozzles for maintenance. Where possible, block valves shall be located directly against the vessel nozzles. Valves and flanges are not to be located inside vessel skirts. Platforms on towers and vessels shall be kept to a minimum consistent with adequate access to man-way, hand-holes, blinds, blinds installed during maintenance to ensure that vessels are completely isolated, davit operation, control valves, hand valves (size 2 inch and above) and relief valves. To access 1.5 valves and smaller, and 2 and smaller or instruments should be from a permanent ladder. Man-way centerline elevations above platform levels shall be between 600mm and 1,200mm, where practicable. Man-way hinges shall be orientated so that the man-way cover opens away from ladder and instrument access. Man-way shall be located to give reasonable access to tower drop out areas so that tower internals require minimum handling to the davit lifting tackle.

6.2

Exchanger Piping

6.2.1 Shell and Tube Exchangers Process and water piping to shell and tube exchangers shall be arranged to permit easy removal of shell covers, channel covers, channels and bundles. Adequate clearance shall be allowed for mobile handling equipment. Piping shall be adequately supported such that bundles can be removed without the use of additional supports. 6.2.2 Air Cooled Exchangers Piping on mixed phase duty to air coolers shall be arranged symmetrically in order to provide an even distribution to the header.

PIPING LAYOUT

PTT PUBLIC COMPANY LIMITED ENGINEERING SPECIFICATION

SPC-0804.02-50.05 PAGE: 14 of 16 REV: D2

Piping should not be routed in air fin areas in such a way that would obstruct maintenance. Platforms shall be provided to cover all bundle and header areas. Unless otherwise specified piping header for air cooler shall be arranged as below.

Note: When thermal expansion have been taken into account, the headers which serviced at high temperature or having long distance may be split into two or more separated symmetrical headers 6.2.2 Plate fin heat exchanger Inlet piping shall be provided inline strainer with isolation valve and spectacle blind. Pipe shot spool on that point shall be provided.

PIPING LAYOUT

PTT PUBLIC COMPANY LIMITED ENGINEERING SPECIFICATION

SPC-0804.02-50.05 PAGE: 15 of 16 REV: D2

Outlet piping shall be provided pipe shot spool with inert gas connection 2 inch with valve and provide isolated valve with spectacle blind. Accessibility to remove pipe shot spool like lifting advise equipment and platform shall be provided. 6.3 Compressor Piping

6.3.1 Suction Piping Suction piping shall slope continuously downward from the knockout vessel to the compressor inlet. An alternate arrangement depending on compressor suction valve location, piping shall slope from the valve to compressor suction inlet on one side from the valve to the knockout vessel on the other side. If pocketing of the suction line is unavoidable, i.e. when centrifugal compressors have bottom inlet nozzle, provision shall be made for the drainage of the liquid to a collection pot. Centrifugal compressor piping shall be designed and supported such that the load on the nozzle is in accordance with that allowed by the compressor VENDOR. A length of straight pipe specified by the compressor VENDOR shall be used at the centrifugal compressor suction inlet to ensure stable flow to the compressor. Valves in suction lines shall be located only in horizontal piping. 6.3.2 Removable Piping for Maintenance Removable spool pieces are to be provided at compressors where needed to permit maintenance without major piping disassembly. 6.4 Pump and Turbine Piping Piping at pumps and turbines shall be designed to allow for sufficient flexibility of the equipment nozzles and supported so that the equipment can be dismantled or removed without adding temporary supports or dismantling valves and piping other than spool piece or reducers adjacent to the equipment connections. 6.4.1 Pump Piping Subject to requirements for sufficient flexibility, suction lines shall be as short as possible and drain towards the pump nozzle without pockets.

PIPING LAYOUT

PTT PUBLIC COMPANY LIMITED ENGINEERING SPECIFICATION

SPC-0804.02-50.05 PAGE: 16 of 16 REV: D2

Block valves in suction and discharge shall be located as close to the pump nozzles as possible. Pump suction piping is to be arranged with particular care to avoid unnecessary pressure drop and vapour pockets. If vapour pockets cannot be avoided they shall be vented. Concentric reducers are preferred where size changes are necessary in pump suction lines. Eccentric reducers are to be used only where unvented pockets cannot otherwise be avoided. Eccentric reducers in horizontal lines shall have straight side up. Piping shall be designed to avoid interference with operation or maintenance access. Removable spool piece is to be provided at suction and discharge to permit maintenance without major piping disassembly.

Potrebbero piacerti anche