Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
v
DC
(t), if 0 < t < D T
S
V
g
v
DC
(t), if D T
S
< t < T
S
(1)
i
C
(t) =
i
L
(t) i
DC
(t), if 0 < t < D T
S
i
L
(t) i
DC
(t) i
i
(t), if D T
S
< t < T
S
(2)
v
i
(t) =
0, if 0 < t < D T
S
v
DC
(t), if D T
S
< t < T
S
.
(3)
Using small ripple approximation, (1)(3) can be rewritten as
v
L
(t) =
V
DC
, if 0 < t < D T
S
V
g
V
DC
, if D T
S
< t < T
S
(4)
i
C
(t) =
I
L
I
DC
, if 0 < t < D T
S
I
L
I
DC
I
i
, if D T
S
< t < T
S
(5)
v
i
(t) =
0, if 0 < t < D T
S
V
DC
, if D T
S
< t < T
S
.
(6)
Here, V
DC
, I
L
, and I
DC
are dc components in v
DC
(t), i
L
(t),
and i
DC
(t), respectively, and I
i
is the current drawn by inverter
bridge in (1 D) T
S
interval. Under steady state, the average
voltage across the inductor and average current through the
1224 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 28, NO. 3, MARCH 2013
capacitor in one switching cycle should be zero. Using volt-
second balance, we have
V
DC
D + (V
g
V
DC
) (1 D) = 0
V
DC
V
g
=
1 D
1 2D
.
(7)
Similarly, using charge-second balance, one can write
(I
L
I
DC
) D + (I
L
I
DC
I
i
) (1 D) = 0
I
L
=
_
1
1 2D
_
I
DC
+
_
1 D
1 2D
_
I
i
. (8)
The average dc link voltage V
i
can be calculated as
V
i
= 0 D +V
DC
(1 D) = V
DC
(1 D) . (9)
The expression for conversion ratio (V
DC
/V
g
) is plotted in
Fig. 7(d). As shown in the gure, (V
DC
/V
g
) is unity when
D = 0 and it becomes very high as D approaches 0.5. Note that,
similar to a ZSI [7], the shoot-through duty ratio (D) of the SBI
also cannot exceed 0.5 for a positive dc bus voltage, V
DC
.
B. PWM Control of SBI
The SBI utilizes the shoot-through interval of the H-bridge
to invoke the boost operation. So, the traditional PWM tech-
niques of VSI [25], [27] have to be modied to incorporate the
shoot-through state, so that they are suitable for SBI. In [6],
a PWM scheme for SBI is developed based on the traditional
sine-triangle PWM with unipolar voltage switching [25], [27].
This technique has been illustrated in Fig. 8 during positive and
negative half cycles of the sinusoidal modulation signal v
m
(t)
[shown in Fig. 8(a)].
As shown in Fig. 8(b) and (d), during positive half cycle
of v
m
(t) (v
m
(t) > 0), the gate control signals G
S 1
and G
S 2
are generated by comparing the sinusoidal modulation signals
v
m
(t), and v
m
(t) [shown in Fig. 8(a)] with a high-frequency
triangular carrier v
tri
(t) of amplitude V
p
. The frequency f
S
of
the carrier signal is chosen such that f
S
f
O
. Therefore, v
m
(t)
is assumed to be nearly constant in Fig. 8(d). The signals ST
1
and ST
2
are generated by comparing v
tri
(t) with two constant
voltages V
ST
and V
ST
, respectively. The purpose of these two
signals is to insert the required shoot-through interval DT
S
in
the PWM signals of the inverter bridge. Now the gate control
signals for switches S
3
, S
4
, and S can be obtained using the
logical expressions given as follows:
G
S3
=G
S2
+ST
1
; G
S4
=G
S1
+ ST
2
; G
S
= ST
1
+ ST
2
.
(10)
Similarly, as shown in Fig. 8(c) and (e), during negative half
cycle of v
m
(t) (v
m
(t) < 0), the gate control signals G
S3
and
G
S4
are generated by comparing the modulation signals v
m
(t),
and v
m
(t) with the triangular carrier v
tri
(t). The shoot-through
signals ST
1
and ST
2
are generated in the same manner as in
the positive half cycle. The gate control signals for switches S
1
,
S
2
, and S can be obtained using the logical expressions given as
follows:
G
S1
=G
S4
+ST
1
; G
S2
=G
S3
+ ST
2
; G
S
= ST
1
+ ST
2
.
(11)
Fig. 8. (a) Sinusoidal Modulation Signals v
m
(t) and v
m
(t). (b) Schematic
of the PWM control circuit when v
m
(t) > 0. (c) Schematic of the PWM control
circuit when v
m
(t) < 0. (d) Generation of gate control signals for SBI when
v
m
(t) > 0. (e) Generation of gate control signals for SBI when v
m
(t) < 0.
ADDA et al.: SYNCHRONOUS-REFERENCE-FRAME-BASED CONTROL OF SWITCHED BOOST INVERTER 1225
Fig. 9. Closed-loop control architecture of the dc nanogrid.
It can be observed from Fig. 8 that, during positive half cycle
of v
m
(t), the shoot-through signals ST
1
, ST
2
are logically added
to G
S2
, G
S1
, respectively, while in negative half cycle of v
m
(t),
these signals are logically added to G
S4
, G
S3
, respectively. This
takes care that all four switches of the inverter bridge equally
participate in generating the shoot-through interval.
Note that with this PWMcontrol technique, the shoot-through
state of the inverter bridge will have no effect on the harmonic
spectrum of the inverters output voltage v
AB
, if the sum of
shoot-through duty ratio (D) and the modulation index (M) is
less than or equal to unity [6], i.e.,
M +D 1. (12)
If the values of M and D are chosen according to (12), the
peak value of the ac output voltage v
AC
is given by [6]
V
AC
=
_
V
AB
_
fundmental
= M V
DC
= M
_
1 D
1 2D
_
V
g
.
(13)
Inequality (12) limits the maximum ac-to-dc conversion ratio
of SBI that can be achieved with this PWM control technique.
However, as the operation of SBI is similar to that of a ZSI,
it is possible to extend maximum boost control and maximum
constant boost control techniques of ZSI [15][17] to SBI. With
these techniques, the sum of M and D of SBI can be more than
unity. Thus, the SBI can achieve higher ac-to-dc conversion
ratios with these control techniques.
IV. CLOSED-LOOP CONTROL OF SBI
Fig. 9 shows the closed-loop control architecture of the SBI
supplying both dc and ac loads. In this scheme, the task of the
controller is to generate gate control signals (G
S
, G
S 1
, G
S 2
,
G
S 3
, and G
S 4
) for SBI shown in Fig. 3 such that the volt-
ages at the dc bus (V
DC
) and the ac bus (v
AC
) are regulated
to their respective reference values V
DC
and v
AC
. As shown in
Fig. 9, the controller for the dc nanogrid has been implemented
in digital domain using Texas Instruments TMS320F28335
DSP [30], [31]. This DSP has a built-in 12-bit analog-to-digital
converter that accepts analog feedback signals (V
DC
, v
AC
, and
Fig. 10. Equivalent circuit of SBI referred to ac side (R
Lf
: DCR of the
inductor L
f
, R
AC
: ac load).
Fig. 11. Bode plots of (a) inner current control loop and (b) outer voltage
control loop.
i
Lf
) from SBI and converts them into digital domain. These
feedback signals along with the reference signals for the ac and
dc bus voltages are given as inputs to the controller block. The
controller block has two separate control loops for controlling
the dc bus voltage V
DC
and ac bus voltage v
AC
. The ac bus
voltage controller has a cascaded control structure with an in-
ner current control loop and an outer voltage control loop. Note
that, as the ac bus voltage controller is designed using SRF ap-
proach [20][22], the reference for ac bus voltage v
AC
is directly
given in dq domain (V
d
,V
q
, and frequency ) in Fig. 9, in order
to reduce the extra computational burden on the DSP.
The outputs of the controller block are shoot-through duty
ratio D and modulation signal (m =v
m
(t)) of the SBI. These are
1226 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 28, NO. 3, MARCH 2013
Fig. 12. Block diagram of the ac bus voltage controller, (a) outer voltage
controller, and (b) inner current controller.
given as inputs to the enhanced pulsewidth modulation (ePWM)
modules [31] of DSP which are the key peripherals to generate
the PWM signals of SBI. Now the gate control signals (G
S
,
G
S 1
, G
S 2
, G
S 3
, and G
S 4
) for SBI are generated by the ePWM
modules using the modied unipolar sine-triangle PWM tech-
nique of SBI described in the previous section.
A. AC Bus Voltage Controller
Fig. 10 shows the equivalent circuit of SBI referred to the ac
side, in which the ac load is represented by an equivalent resistor
R
AC
. From this gure, one can write
di
Lf
dt
=
R
Lf
L
f
i
Lf
+
1
L
f
(v
inv
v
AC
) (14)
dv
AC
dt
=
1
C
f
i
Lf
v
AC
R
AC
C
f
. (15)
Equations (14) and (15) can be written in dq domain [20][22]
as (using the transformation matrix T given in (22))
d
dt
_
I
d
I
q
_
=
R
Lf
L
f
R
Lf
L
f
_
I
d
I
q
_
+
1
L
f
Fig. 13. Simplied equivalent circuit of SBI referred to dc side.
Fig. 14. Bode plots of dc bus voltage control loop.
_
V
invd
V
d
V
invq
V
q
_
(16)
d
dt
_
V
d
V
q
_
=
1
R
AC
C
f
1
R
AC
C
f
_
V
d
V
q
_
+
1
C
f
_
I
d
I
q
_
. (17)
Transforming these equations into s-domain, the control to
output transfer functions of inner current control loop and outer
voltage control loop are given by
I
d
(s)
U
id
(s)
=
I
q
(s)
U
iq
(s)
=
1
s L
f
+R
Lf
(18)
V
d
(s)
U
vd
(s)
=
V
q
(s)
U
vq
(s)
=
R
AC
s R
AC
C
f
+ 1
(19)
where
U
id
=V
invd
V
d
+ L
f
I
q
; U
iq
= V
invq
V
q
L
f
I
d
;
U
vd
= I
d
+ C
f
V
q
; and U
vq
= I
q
C
f
V
d
.
Fig. 11 shows open-loop (uncompensated) and loop (compen-
sated) bode plots of the inner current and outer voltage control
loops with the plant parameters given in Table II. Fig. 12(a) and
(b) show the detailed block diagrams of the outer voltage con-
troller and inner current controller, respectively. The complete
ADDA et al.: SYNCHRONOUS-REFERENCE-FRAME-BASED CONTROL OF SWITCHED BOOST INVERTER 1227
Fig. 15. Complete Block diagram of the DSP-based controller for the SBI supplying both dc and ac loads.
block diagram of the ac bus voltage control loop is given in
Fig. 15.
B. DC Bus Voltage Controller
Fig. 13 shows the simplied equivalent circuit of SBI, in
which the dc load is represented by an equivalent resistor R
DC
,
and the inverter bridge is represented by parallel combination of
a switch S
i
and a resistor R
i
[24]. Using state-space averaging
approach [26], [27], the small-signal state-space model of the
SBI can be obtained as follows:
K.
x = A. x +B. u
y = E. x +F. u (20)
where
x =
_
i
L
v
DC
T
; u =
_
d v
g
T
;
y = [ v
DC
] ; and K =
_
L 0
0 C
_
.
The matrices A, B, E, and F of (20) are given in Appendix
A. From this state-space model, the control to output transfer
function of the dc bus voltage controller ( v
DC
/
d) can be obtained
as
v
DC
d
=
b
1
s +b
0
a
2
s
2
+a
1
s +a
0
. (21)
The coefcients a
x
(x = 0 to 2) and b
y
(y = 0, 1) of (21) are
given in Appendix A. Fig. 14 shows the open-loop (uncompen-
sated) and loop (compensated) bode plots of the dc bus voltage
control loop with the parameters given in Table II. Note that
the transfer function ( v
DC
/
DC
.
The output of this controller is the shoot-through duty ratio D
of the SBI. The ac bus voltage controller has a cascaded control
structure with an inner current controller block and an outer
voltage controller block, as shown in Fig. 15. The detailed view
of these two controllers is given in Fig. 12. Note that, as the ac
bus voltage controller is implemented using SRF approach, the
feedback signals (v
AC
, i
Lf
) should also be transformed from
single phase (1) to dq domain. This transformation involves
the following two steps.
Step 1: 1 to transformation
The sensed sinusoidal voltage v
AC
of SBI is passed
through a quadrature signal generator (QSG) that is based on
second-order generalized integrator (SOGI) [23]. The tuning
1228 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 28, NO. 3, MARCH 2013
TABLE II
PARAMETERS USED FOR EXPERIMENT
TABLE III
COMPONENTS USED FOR EXPERIMENT
Fig. 16. Photograph of the power stage of SBI.
frequency of the SOGI is set to the input frequency , as
shown in Fig. 15. The outputs of the SOGI-QSG are two in-
quadrature sinusoidal signals v
and v
such that
V
=
V
AC
and
V
= (j1).
V
AC
. A similar technique is used to transform
the sensed sinusoidal current i
Lf
into domain, as shown
in Fig. 15.
Step 2: to dq transformation
In this step, the sinusoidal signals (v
, v
) and (i
, i
) are
premultiplied by the transformation matrix, T [21], as given in
the following equation:
_
V
d
V
q
_
= T
_
v
_
;
_
I
d
I
q
_
= T
_
i
_
Fig. 17. Gate control signals of SBI generated by the DSP (a) during positive
half cycle of v
m
(t) and (b) during negative half cycle of v
m
(t).
TABLE IV
EXPERIMENTAL VERIFICATION OF BUCKBOOST CAPABILITY OF THE SBI
where T =
_
sin cos
cos sin
_
. (22)
Note that as the controller is designed for a standalone system,
is generated by integration of the input frequency , as
shown in Fig. 15. As a result of the transformation given in
(22), these sinusoidal signals are transformed into dc signals
(V
d
, V
q
) and (I
d
, I
q
), respectively. Now the sensed feedback
signals are in dq domain and can be given as inputs to the ac
ADDA et al.: SYNCHRONOUS-REFERENCE-FRAME-BASED CONTROL OF SWITCHED BOOST INVERTER 1229
Fig. 18. Experimental results of SBI with different values of rms ac-to-dc conversion ratios and input voltages. (a) Boost mode with V
g
= 24 V. (b) Buck mode
with V
g
= 24 V. (c) Boost mode with V
g
= 48 V. (d) Buck mode with V
g
= 48 V.
bus voltage controller, as shown in Fig. 15. The outputs of the
ac bus voltage controller are the modulation signals of the SBI
in dq domain, i.e., M
d
and M
q
. From these two dc signals in
dq domain, the sinusoidal modulation signal, m (= v
m
(t)) of
SBI can be obtained using dq to 1 transformation given in the
following equation:
v
m
(t) = m = M
d
. sin +M
q
. cos . (23)
The outputs of the controller block (D and m) are given as
inputs to the ePWM modules [31] of DSP in order to generate
the gate control signals (G
S
, G
S 1
, G
S 2
, G
S 3
, and G
S 4
) for
SBI, using the PWMcontrol technique described in the previous
section.
V. EXPERIMENTAL VERIFICATION
A 500-W laboratory prototype of the SBI supplying both dc
and ac loads, shown in Fig. 3, is developed to verify the the-
oretical analysis given in the paper. Tables II and III list the
parameters and components used for the experimental veri-
cation. Fig. 16 shows the photograph of power stage of the
SBI prototype used for experimentation. The closed-loop con-
trol strategy has been implemented using the Texas instruments
TMS320F28335 DSP as mentioned in previous sections.
A. Gate Signals Generated by the DSP
Fig. 17 shows the gate control signals of SBI during positive
and negative half cycles of the modulation signal v
m
(t), gener-
ated using TMS320F28335 DSP. It can be observed that these
gate signals are consistent with the PWM control signals given
in Fig. 8(d) and (e).
B. Verication of BuckBoost Capability of SBI
One of the main advantages of SBI over the traditional VSI is
that it can generate an ac output voltage that is either higher or
lower than the source voltage V
g
. To verify this experimentally,
1230 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 28, NO. 3, MARCH 2013
Fig. 19. Steady-state operation of SBI (a) input voltage V
g
, dc load voltage
V
DC
, ac output voltage of SBI v
AC
, and ac load voltage, and (b) dc load voltage
V
DC
, switch node 1 voltage V
sn1
, input voltage of the inverter bridge V
i
, and
output voltage of H-Bridge V
AB
.
TABLE V
COMPARISON OF ACTUAL VOLTAGES OF THE SBI IN FIG. 19(a) WITH THEIR
REFERENCE SIGNALS (N = 5)
the SBI has been tested for different conversion ratios and input
voltages given in Table IV, and the corresponding experimental
results are given in Fig. 18. From these results, it is clear that
the rms ac-to-dc conversion ratio can vary between 0.5 and 2.
This veries the buckboost capability of the SBI.
Note that, in this paper, the SBI has been tested with the
PWM technique proposed in [6], where the maximum value of
modulation index M is limited by the shoot-through duty ratio
D [see inequality (12)]. However, as the operation of SBI is
similar to ZSI, it is possible to extend most of the PWM control
techniques of ZSI [15][17] to SBI. These techniques help to
further improve the rms ac-to-dc conversion ratio of the SBI.
C. Operation of SBI With an Isolation Transformer
Most of the residential and commercial ac loads require either
110 V or 230 V rms ac supply. In order to generate 230-V
AC
output using SBI, one can either increase input voltage level to
120 V
DC
(since the maximumpractical rms ac-to-dc conversion
ratio of SBI is 2 with the PWM technique used in this paper) or
use a step-up transformer at the ac output of the SBI. The use of
transformer also provides galvanic isolation between the power
converter stage and loads, which increases protection level and
reliability of the system.
In the previous section (see Fig. 18 and Table IV), it is already
shown that both the dc and ac output voltages of SBI can be
increased by increasing the input voltage V
g
. In this section, the
operation of SBI has been tested with an isolation transformer
connected between the ac output and the ac load of the converter.
This section also veries the capability of SBI to supply both dc
and ac loads simultaneously.
Fig. 19(a) shows the steady-state waveforms of the SBI sup-
plying a 250-W dc load and a 250-W ac load simultaneously,
with an input voltage V
g
= 48 V. The ac load is isolated from
the power converter stage using a 1:5 isolation transformer. The
reference signals for the closed-loop control system of SBI are
V
DC
= 130 V, v
AC
= 46 V (rms), V
d
= 65 V, V
q
= 0 V, and
= 100 rad/s. Note that the reference value for v
AC
is chosen
such that the ac load voltage is equal to 230 Vrms (=5 46 V).
Table V compares the actual voltages at various nodes of the
SBI with their respective reference values. From Fig. 19(a) and
Table V, it is clear that the actual voltages are matching well
with their respective reference signals. These results verify the
operation of SBI with an isolation transformer at the ac output
of the converter. Also these results show that the SBI can supply
both dc and ac loads simultaneously from a single input V
g
.
Fig. 19(b) shows the dc bus voltage V
DC
, switch node voltage
V
sn1
, inverter input voltage V
i
, and inverter output voltage V
AB
of the SBI. It is important to note that as the VSI is connected
at the switch node V
i
of the CIWJ topology, the input voltage
of the inverter bridge V
i
in SBI is a switching waveform that
varies from 0 to V
DC
. Also, it can be observed from Fig. 19(b)
that the width of the shoot-through interval (when V
sn1
= V
DC
,
V
i
= 0) is less than the width of zero-interval (when v
AB
= 0)
which proves that inequality (12) is satised.
D. Performance of the Closed-Loop Control SystemWith a Step
Change in the Load
To test the dynamic performance of the closed-loop control
system, a 20% step change has been applied in both ac and dc
ADDA et al.: SYNCHRONOUS-REFERENCE-FRAME-BASED CONTROL OF SWITCHED BOOST INVERTER 1231
Fig. 20. Performance of the controller with (a) 20% step-down change in ac load current, (b) 20% step-up change in ac load current, (c) 20% step-down change
in dc load current, and (d) 20% step-up change in dc load current.
loads of SBI separately, and the results are presented in Fig. 20.
In all these gures, the signal shown in channel 1 (orange)
represents the ac or dc load current. It can be observed fromthese
gures that both the dc bus and ac bus voltages are maintained
to be constant by the closed-loop controller even during a step
change in either ac load or dc load. This conrms that the DSP-
based closed-loop control system presented in this paper shows
excellent dynamic performance as well as low cross regulation
of ac and dc bus voltages of SBI.
E. Performance of SBI With an RL and Rectier Loads
Fig. 21(a) shows the experimental results of SBI supplying an
RL load: (18+j14) , 125 W, 0.8 pf lag. As shown in Fig. 21(a),
with an input voltage V
g
of 48 V, the SBI generates a dc bus
voltage of 150 V and an output ac voltage v
AC
of 60 V rms.
Channel 1 (Orange) shows the ac load current i
AC
of SBI. It
can be observed from this gure that the ac load current lags
the load voltage, which is the characteristic of an RL Load. This
veries the performance of SBI with RL loads.
Fig. 21(b) shows the experimental results of SBI supplying a
single-phase diode bridge rectier with RC load: 150- resistor
in parallel with a 470-F capacitor. Channel 1 (Orange) shows
the current i
AC
drawn by the rectier bridge from SBI, and
Channel 3 (Pink) shows the output voltage of the rectier bridge
V
Rect
. It can be observed that the output ac voltage v
AC
of
SBI is distorted due to the harmonics in the current drawn by
rectier. Note that this distortion happens even with a regular
VSI supplying a rectier load [28], [29]. However, it is possible
to improve the quality of output voltage by modifying the closed-
loop control technique of the inverter [28], [29].
VI. CONCLUSION
This paper presents a novel power electronic interface called
switched boost inverter (SBI) for dc nanogrid applications. It is
1232 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 28, NO. 3, MARCH 2013
Fig. 21. (a) Experimental results of SBI supplying an RL load. (b) Experi-
mental results of SBI supplying a rectier load.
shown that the SBI is a single-stage power converter that can
supply both dc and ac loads simultaneously from a single dc
input. It is also proven that the SBI can generate an ac output
voltage that is either higher or lower than the available source
voltage. This paper also describes the advantages and limitations
of SBI when compared to the ZSI and the traditional two-stage
dc-to-ac conversion system. The steady-state and small-signal
analysis of the SBI supplying both dc and ac loads, and a PWM
control technique suitable for SBI are also described in this
paper. Also, the analysis and design of a SRF-based controller
that regulates both the dc and ac bus voltages of SBI to their
respective reference values has been discussed in this paper.
The steady state and dynamic performance as well as the low
cross regulation of the closed-loop control strategy have been
experimentally validated using a 0.5-kW laboratory prototype
of SBI supplying both dc and ac loads. The performance of SBI
has been tested experimentally with an isolation transformer and
also with three different types of ac loads: R, RL, and nonlinear
loads. It can be concluded from the experimental results that
the control strategy of SBI shows excellent performance during
steady state as well as during a step change in either dc or ac load
in the system. These results conrm the suitability of SBI and
its closed-loop control strategy for dc nanogrid applications.
APPENDIX A
The matrices A, B, E, and F in (20) are
A =
0 2D 1
1 2D
D
R
DC
1 D
R
eq
B =
_
2 V
DC
V
g
1 D
V
DC
_
1
R
e q
1
R
D C
_
2 I
L
0
_
E = [ 0 1 ] ; F = [ 0 0 ] ; and R
eq
=
R
DC
R
i
R
DC
+R
i
.
The coefcients of ( v
DC
/