Sei sulla pagina 1di 10

Guide for electrical design engineers

Power Quality
Katarzyna Strzalka-Goluszka
Doctoral Student of Faculty of Electrical Engineering, Automatics, IT & Electronics AGH University of Science & Technology
kstrzalka@op.pl

Overload Capacity of Power Transformers


t

Load factor

K2

K1 0 Time of day 24 h

Power Quality

Power Quality
www.leonardo-energy.org

1. Introduction
For over three decades, since the early seventies, the principles of sizing oilimmersed transformers and evaluation their overload capacity have been defined in standard PN-71/E-81000 [1]. These principles are presented in the course book [3], and examples of practical calculations and transformers sizing are provided in the course book [4]. The basic criterion adopted in standard [1] for determining power transformers loading limits is the thermal life of insulation. The standard defines transformer overload capacity assuming nominal transformer insulation life and reduced insulation life expectancy corresponding to overloading a transformer under disturbed conditions. The basis for consideration in standard [1] was a representative two-step load cycle determined from the known or expected ordered 24-hour load curve of a transformer, described by:

equivalent initial load Sp, equivalent final load Sk, duration of the final load tk.

The above equivalent load values should be computed as a root mean square average according to the relation:

S=
where:

S t t
2 i i

(1)

Si load over the time interval ti, ti the considered time interval. The initial and final equivalent loads are determined from the representative load:

Kp =

Sp S nt

Kk =
2

Sk S nt

(2)

Overload Capacity of Power Transformers


www.leonardo-energy.org

where: Snt transformer nominal power. The permissible equivalent final load Kk = f(Kp, tk) is given in standard PN-71/E81000 [1] in the form of curves and tables, assuming the following parameters:

ambient temperature o = - 10, 0, 10, 20 and 30C equivalent initial load Kp = 0.251.0 duration of the final load tk = 0.5, 1, 2, 4, 8, 12 and 24h.

Standard PN-IEC 60354 [2] implemented in 1999 considerably alters the principles of determining the overload capacity of oil-immersed transformers. The most important changes are discussed further in this paper.

2. Main assumptions of the standard PN-IEC 60354 methodology


The normal service life of transformer is a conventional reference basis for continuous operation in normal ambient temperature under nominal operating conditions. Loading beyond nameplate rating and/or higher ambient temperature involves a risk and results accelerated insulation ageing. Both the loading and temperature rise above the rated values will result in risk of premature failure of a transformer that may occur either immediately or after certain time, due to deterioration of the transformer components. The standard gives guidelines on transformer loading in relation to the operating temperature rise and thermal ageing of insulation; the insulation relative ageing rate is assessed using the hot spot temperature. Since the transformer sensitivity to overloading depends evidently on its size, the standard specifies three categories of transformers:

Distribution transformers (with maximum power of 2500 kVA), for which only the hot-spot temperature and thermal deterioration have to be considered; Medium power transformers (not exceeding 100 MVA), in which the cooling modes shall be considered; Large power transformers (exceeding 100 MVA), where the effects of stray leakage flux are significant and the consequences of failure are severe.

For each category the standard defines separate requirements. Table 1 shows limit currents and temperatures for the above transformer categories, applicable to loading beyond nameplate rating.
3

Power Quality
www.leonardo-energy.org

Table 1 : Currents and temperature limits applicable to loading beyond nameplate rating
TYPE OF LOADING Normal cyclic load: Current Hot-spot temperature Top-oil temperature Long-time emergency cyclic loading: Current Hot-spot temperature Top-oil temperature DISTRIBUTION TRANSFORMERS [p.u.] [C] [C] 1.5 140 105 MEDIUM POWER TRANSFORMERS 1.5 140 105 LARGE POWER TRANSFORMERS 1.3 120 105

[p.u.] [C] [C]

1.8 150 115

1.5 140 115

1.3 130 115

Short-time emergency loading: Current Hot-spot temperature Top-oil temperature

[p.u.] [C] [C]

2.0 -

1.8 160 115

1.5 160 115

As can be seen from table 1, the standard recommendations apply to three types of transformer loading:

continuous loading, cyclic loading, long-time emergency cyclic loading.

Standard [2] provides the method for determining thermal behaviour of transformers with various cooling modes and comprises computation results in the form of thermal characteristics for adopted assumptions, among which the most important are:

ambient temperature a = 20C, hot-spot temperature rise hr = 78C.

As the basis for analysis of transformer insulation thermal ageing the rule of 6C is taken, i.e. the rate of insulation ageing doubles for every increment of approximately 6C. Assuming the relative rate of ageing V at the hot-spot temperature h = 98C equals unity V = 1, thus at the temperature h = 104C V = 2, and at h = 110C V = 4. Standard [2] provides the method for calculation of transformer daily loss-oflife, expressed in terms of "normal" days, i.e. equivalent days of operation with rated power at the ambient temperature 20C.

Overload Capacity of Power Transformers


www.leonardo-energy.org

3. Method of representing an actual load by an equivalent two-step load cycle


t

Load factor

K2

K1 0 Time of day 24 h

Fig. 1. Equivalent two-step load cycle The load steps in figure 1 shall be K1 and K2, where K2 is the peak load. The duration of the peak load is t hours. Standard [2] describes the method of determining this duration for different shapes of actual load cycles. In the case of a load cycle with one peak the value of t should be selected on the equal areas basis as indicated in Fig. 2. For the off-peak portion of the load cycle, the value of K1 is selected to correspond to the average off-peak load.

Fig. 2. Load cycle with one peak In the case where there are two peaks of nearly equal amplitude but different duration (Fig. 3), the value of time t is determined for the peak of a longer duration and the value of K1 is selected to correspond to the average of the remaining daily load.

Power Quality
www.leonardo-energy.org

Fig. 3. Load cycle with two peaks of equal amplitude and different duration For the load cycle where two peaks occur in close succession (Fig. 4), the value of t is made long enough to enclose both peaks, and K1 is selected accordingly to the average load during the remaining portion of the day.

Fig. 4. Load cycle with peaks in close succession

4. Determining permissible transformer load for various types of loadings


For a normal continuous loading, which shows no pronounced variation over a day, the standard [2] recommends the use of a constant equivalent load current. Table 2 gives an acceptable load factor K = K24 for continuous duty and different ambient temperatures.

Overload Capacity of Power Transformers


www.leonardo-energy.org

Table 2 Acceptable load factor K24 for continuous duty at different ambient temperatures (ON, OF and OD cooling)
AM BIENT TEM PER ATU RE , C Hot-spot temperature rise, C -25 123 -20 118 -10 108 0 98 10 88 20 78 30 68 40 58

K24

Distribution transformers Medium and large power transformers

ONAN

1.37 1.33 1.31 1.24

1.33 1.30 1.28 1.22

1.25 1.22 1.21 1.17

1.17 1.15 1.14 1.11

1.09 1.08 1.08 1.06

1.00 1.00 1.00 1.00

0.91 0.92 0.92 0.94

0.81 0.82 0.83 0.87

ON OF OD

For normal cycling loading and various types of transformers and eight different ambient temperatures (a = -25, -20, -10, 0, 10, 20, 30 and 40C) standard PN-IEC 60354: 1999 [2] gives curves that can be used to determine the permissible peak load K2 for a given duration t and a given initial load K1. If the ambient temperature value falls between two values, the standard recommends interpolation between the two nearest curves. Figure 5 shows an example of relations K2 = f(K1, t) for distribution transformers with ONAN cooling, and the ambient temperature a = +20C.

Fig. 5. Permissible loading of distribution transformers at the ambient temperature 20C

Power Quality
www.leonardo-energy.org

If the supply voltage remains constant the curves K2 = f(K1, t) can also be used for determining the rated power of a transformer (with normal life duration) for a given rectangular load profile defined as the ratio K2/K1. For this purpose it is necessary is to find the intersection of the curve corresponding to the duration of the load K2 with the line of constant slope K2/K1, which can be found by marking corresponding points on ordinate K2 = 1 and abscissa K1 = 1. Figure 1 shows the line for K2/K1 = 1.75, which allows determining the factors K2 = 1.15 and K1 = 0.66 for duration t = 8h. For emergency cyclic loading the standard PN-IEC 60354: 1999 [2] gives tables that can be used to ascertain whether a load characterized by particular values K1 and K2 is permissible for a given ambient temperature, and determine a daily loss of life expressed in "normal" days. These tables correspond to six duration values t (0.5 to 24 h) and four types of transformers. The below example table 4 determines relative ageing rates V and winding hotspot temperature rise h for distribution transformers with ONAN cooling and duration t = 4 h. Table 3 Conversion factor related to the ambient temperature
40C AMBIENT TEMPERATUREC Conversion factor kp 10 3.2 1 0.32 0.1 0.032 0.01 0.0055 30C 20C 10C 0C -10C -20C -25C

In order to determine whether a daily load diagram characterized by particular values of K1 and K2 is permissible and to evaluate the daily loss of life entailed, the following steps should be preceded: - From table 4 find the hot-spot temperature rise h and determine the hot-spot temperature h from the formula: h = h + a where: a - ambient temperature - If the resulting hot-spot temperature exceeds the limit stated in table 1, the loading is not permissible. (3)

Overload Capacity of Power Transformers


www.leonardo-energy.org

- From table 4 find relative ageing rate V and determine the daily insulation loss of life L from the formula: L = V . kp (4)

where: kp the conversion factor related to the ambient temperature according to table 3.

Table 4 relative ageing rate V (daily loss of life) and winding hot-spot temperature rise Dqh for distribution transformers with ONAN cooling and duration t = 4 h.

K2
0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0

K1
V h V h V h V h V h V h V h V h V h V h V h V h V h V h

0.25 0.003 43 0.005 51 0.010 59 0.023 68 0.056 77 0.154 87 0.455 98 1.45 109 4.94 120 17.9 132 69.0 144 282 157 1220 171 5540 184

0.50 0.080 46 0.012 53 0.020 61 0.039 70 0.091 73 0.236 89 0.677 100 2.11 111 7.09 122 25.5 134 97.3 147 394 160 1690 173 + +

0.70 0.032 48 0.040 56 0.056 64 0.091 73 0.178 83 0.417 92 1.12 103 3.36 114 11.00 125 38.8 137 146 149 587 162 2500 176 + +

0.80

0.90

1.00

1.10

1.20

1.30

1.40

1.50

0.093 57 0.117 66 0.170 74 0.294 84 0.621 94 1.56 104 4.50 115 14.4 127 50.1 139 187 151 745 164 3150 177 + + 0.292 67 0.377 76 0.566 86 1.04 95 2.36 106 6.38 117 19.7 128 66.8 140 246 153 971 166 4080 179 + + 1.00 78 1.32 87 2.06 97 4.02 108 9.76 119 28.2 130 93.7 142 334 155 1300 167 5410 180 + + 3.72 89 5.00 99 8.13 110 16.8 121 43.7 132 135 144 470 157 1790 169 7370 183 + + 14.9 101 20.5 112 34.7 123 76.1 134 211 146 694 159 1560 172 + + + + 64.7 114 90.6 125 160 137 371 149 110 161 3830 174 + + + + 302 127 431 139 790 151 1950 163 6110 176 + + + + 1510 141 2200 153 4190 166 + 179 + + + +

Power Quality
www.leonardo-energy.org

5. Conclusion
The standard PN-IEC 60354 implemented in 1999, introduced considerable changes to the principles of assessing thermal effects of transformers overloading under various types of load. An essential advantage of the recommended methods of verification of overloading capacity of transformers is that the size and cooling modes of transformers are considered. The tables and curves, provided in this standard, being the result of thermal calculations allow determining permissible loading of transformers under different operating conditions.

References
[1] PN-71/E-81000 Transformers. Loading of oil-immersed transformers. [2] IEC 60354: Loading guide for oil immersed transformers. [3] Strojny J., Strzaka J.: Design of Electric Power Equipment, (in Polish), SU1609, AGH-UST Publisher, Krakow 2001. [4] Strzaka J.: Electric Power Equipment Problem Book, (in Polish), SU1674, AGH-UST Publishers Krakow 2005.

10

Potrebbero piacerti anche