Aditya Birla Cellulosic Fiber Reserch Center Dept:- Electrical LT Motor Specification

Sr No Particulars Specification

Date:- 0 1 2 3 4 5 6 7 8 9 10 11 12 13 Envirment Condition Voltage Variation Frequency Variation Performance Dimensions Rating Enclosure Frame Insulation Rotor Type Of Construction Cooling & Ventillation External Cooling Fan Highly Corrosive, Caustic & Acid Fumes 415V +/- 10% 50 Hz +/- 5% Performance should Confirm to IS:325, IEC 34-PART-1 Dimensions should confirm to IS:4691 , (For Foot Mounted), IS: 2223 ( For Flange Mounted) Cont.Duty at 50 deg C Ambient Duty-S1 IP55 degree of protection as a standard, feature IS:4691 & IEC 34 part - 5 Rugged Construction Class 'F' with temperature rise restricted, to Class 'B' Winding.Overheating to be, coated with EPOXY GEL COAT-Dr.Beck DIE CAST, Shaft center should be provided with tapped hole as per standards IMB as per IS 2253 & IEC 34 part 7, with single shaft CONSTRUCTION Type of cooling is IC 0141and as per IS:6362 Al.Die Cast Aluminium Location Of Terminal Box is on top of the Housing. The Terminal boxes should be rotated in steps of 90 deg & should be suitable for proper Aluminium cable termination. Six Winding leads to be brought out & terminated on a suitable terminal block. Tin Plated Material. Terminal Plate DMC only. Terminal Box Size should be considered one size Higher to the standard size Re-arranging facility should be provided for DE & NDE Bearings, with nipple at the top of the end cover. All motors should be provided with minimum 3 earthing terminal one in the terminal box and two on the stator Housing. Efficiency values of motors at 100% rated o/p should remain unchanged up to 60% of rated o/p utilisation. The Motor should have the maximum Efficiency (Efficiency Figures to be approved before placement of the order.) Acid and Alkali resistant. 631 Test Certificates and Performance Curves Should be supplied alogn with Motors IE 3 Class

14

Terminal Box

15 16 17

Terminal Box Bearing System Earthing Systems

18

Efficiency

19 20 21

Paint Test Certificates Efficiency

22 23 26 28

Routine Test Service Factor

For all Motors 1-1.2

Foundation Arrangement Suitable for Both Frame T/S speed curve For Inverter duty motors-1/20 base speed of IGBT Power/ Constant torque at any speed For Inverter Duty Motors 63 Series required on DE & NDE side Extra Cooling Fan Required.

30 31 32

Speed Range Bearing Series-63 Inverter Duty Motors

33

Accessories

SS hardware, SS name plate with DE & NDE bearing details

Center

Date:- 02.02.2013
Vendor Remarks

OK, ACP 631 PAINT OK OK OK OK OK OK OK OK OK OK OK OK OK, TERMINAL PALTE WILL NOT BE DMC .IT WILL BE OF GLASS FIBER. HIGHER SIZE TB IS NOT POSSIBLE SOR SMALL FRAME - TILL 160 FRAME. CONSIDER FOR 160 FRAME & ABOVE OK

AS PER IS 12615 - 2011

OK OK IE 2 CLASS

RTC WILL BE PROVIDED.IF WITNESS REQUIRED THEN IT WILL BE AT EXTRA COST. SERVICE FACTOR 1.0 SUITABLE FOR FRAME GIVEN IN OUR OFFER FOR INVERTER DUTY MOTORS 40% SPEED VARIATION IS OK. FOR INVERTER DUTY MOTORS 40% SPEED VARIATION IS OK. AS PER CGL STANDARD HIGHER FRAME IS CONSIDERED.SO NO EXTRA COOLING FAN REQUIRED. SS HARDWARE ,SS NAME PLATE DE & NDE BEARING CONSIDERED.

Aditya Birla Cellulosic Fiber Reserch Center Dept:- Electrical Summary Of Motors For 2TPD Project
Date:- 06/12/2012

General Motors
Sr. No
1 2 3 4 5 6 7 8 9

HP
1 2 3 5 5 7.5 10 12.5 20

RPM
1440 2900 1440 1440 2900 2900 2900 1440 2900

Mounting
FT FT FT FT FT FT FT FT FT

Pole
4 2 4 4 2 2 2 4 2

Starter
DOL DOL DOL DOL DOL DOL DOL DOL DOL

Quantity
1 4 4 7 1 3 1 3 1

25 Inverter Duty Motors


Sr. No
1 2

HP
3 3

RPM
2900 960

Mounting
FT FT

Pole
2 6

Starter
VFD VFD

Quantity
2 1

3 Total Motors

28