Supplemental C-8A

Parkingstand Lightning Arrester


Distribution Class 200Amp 15kV Arrester

The right direction for safety

Hubbell Power Systems, Inc. 1850 Richland Avenue, East Aiken, SC 29801 USA Phone: 573-682-5521 Fax: 573-682-8714 http://www.hubbellpowersystems.com E-mail: hpsliterature@hubbell.com

www.hubbellpowersystems.com

Never Compromise TM

Cable Accessories
NOTE: Because Hubbell has a policy of continuous product improvement, we reserve the right to change design and specifications without notice.

Page 1 | June 2012

Copyright 2012 Hubbell Incorporated

Supplemental C-8A

Parkingstand Lightning Arrester


Hubbell Parkingstand Lightning Arresters are gapless, metal oxide varistor (MOV) surge arresters. They are designed to provide shielded, dead-front arrester protection for 15 kV underground systems. Hubbell Parkingstand Lightning Arresters limit over-voltages to acceptable levels, protecting equipment and extending life. The critical values for arresters are the discharge voltage (IR) and the IEEE Std. 386 interface class. In general, the lower the discharge voltage, the better the protection margin. Hubbell parking stand arresters are non-fragmenting and they fully conform to the safe-failure mode per IEEE Std. C62.11. The standard requires that should the arrester blocks fail they will not be ejected through the body or side wall of the housing. The MOV blocks should exit out the bottom, down and away from equipment and personnel.

Application:
Hubbell Parkingstand Lightning Arresters contain a 200 amp loadbreak interface that conforms to IEEE Std. 386 Fig 5 (15kV). A Hubbell arrester installed at the end of a radial system or at both ends of an open point in a loop circuit will provide excellent protection against high voltage surges resulting from lightning or switching. When combined with an Ohio Brass PVR (Riser Pole) arrester, optimum protection can be achieved. They are fully shielded and submersible, either continuously or intermittently, to a depth of 6 feet (2m).

Installation:
The Hubbell Parkingstand Lightning Arrester should be installed utilizing a shotgun type hotstick.

Performance Characteristics
Tests were performed in accordance with applicable sections of IEEE Std. C62.11 (Metal Oxide Surge Arresters for Alternating Current Power Circuits) with test levels chosen that represent typical underground distribution systems.

Features:
The insulating rubber body consists of peroxide-cured EPDM rubber that offers reliability and the molded shield consists of conductive peroxide-cured EPDM that meets the requirements of IEEE Std. 592 for exposed semi-conducting shields. The drain wire tab provides a contact point to attach a #14 ground wire to ensure the shield is at ground potential and maintains deadfront construction. The fiberglass wrap ensures that the MOV block stack (same MOV blocks found in Ohio Brass overhead arresters) remains in one piece and prevents the blocks from breaching the side wall should the arrester fail. An ID band around the body of the arrester provides clear visual identification of arrester MCOV and duty cycle ratings. The flexible lead is #4 AWG copper rope lay conductor, featuring a soldered end to prevent fraying. A 36 inch length is standard, however, other lead lengths are available. Please contact your Hubbell sales representative for other lead length options. Page 2 | June 2012

Supplemental C-8A

Parkingstand Lightning Arrester

Design Tests
High Current, Short Duration Low Current, Long Duration Operating Duty Cycle Safe Failure Mode 2 discharges of 65kA Crest 20 Surges of 75A for 2,000 msec 22 Operations of 5kA Crest 8 x 20 msec Verify blocks do not breach sidewall

Production Tests Polymer Housing Only per IEEE Std. 386


Partial Discharge Voltage Level (3 pC sensitivity) AC 60Hz, 1 minute withstand or BIL impulse lightning withstand Periodic Fluoroscope Analysis

Production Tests Complete Unit per IEEE Std. C62.11


Partial Discharge Voltage Level (10 pC sensitivity) Reference Voltage Power Frequency

reliability
Page 3 | June 2012

Parkingstand Lightning Arrester


Protective Characteristics
Catalog Number 215PLA03 215PLA06 215PLA09 215PLA10 215PLA12 MCOV kV Rating kV 0.5 usec 5 kA Max IR-kV 2.55 5.1 7.65 8.4 10.2 3 6 9 10 12 12.5 25 33.5 36 50 1.5kA 9.8 19.5 26 27 39 Maximum Discharge Voltage (kV Crest) 8x20 usec Current Wave 3.0kA 5.0kA 10kA 10.3 11 12.3 20.5 22 24.5 28 30 33 29.5 31.5 36 41 44 49 20kA 14.3 28.5 39 41.5 57

Dimensionals
Catalog IEEE Std. 386 Number Interface 215PLA03 215PLA06 215PLA09 215PLA10 215PLA12 MCOV Rated (kV) Voltage (kV) 2.55 5.1 7.65 8.4 10.2 3 6 9 10 12 Weight lbs (kg) 5.6 7.4

15kV Class

4.6

(2.09)

System L-L Voltage (kV)


Nominal 2.40 4.16 4.80 6.90 12.00 12.47 13.20 13.80 Maximum 2.54 4.37 5.04 7.26 12.70 13.20 13.97 14.52

Arrester MCOV (kV)


Grounded Neutral 2.55 2.55 5.10 5.10 7.65 7.65 8.40 8.40 Impedance Grounded or Ungrounded 2.55 5.10 5.10 7.65 12.70 15.30 15.30 15.30 7.0

Catalog Number Ordering Information

215PLA _ _
MCOV 2.55 5.1 7.65 8.4 10.2 RATING = 03 = 06 = 09 = 10 = 12

Page 4 | June 2012