Sei sulla pagina 1di 89

Order No.

MAC0311035C2

Air Conditioner
CS-A18CKE CU-A18CKE CS-A24CKE CU-A24CKE

CONTENTS
Page
1 Features 2 Functions 3 Product Specifications 4 Dimensions 5 Refrigeration Cycle Diagram 6 Block Diagram 7 Wiring Diagram 8 Operation Details 8.1. Indoor Fan Speed Control 8.2. Cooling Mode Operation 8.3. Soft Dry Mode Operation 8.4. Heating Mode Operation 8.5. Automatic Mode Operation 8.6. Random Auto Restart Control 2 3 6 10 12 13 14 15 15 16 20 22 27 28 8.7. Airflow Direction Control 8.8. Delay ON Timer Control 8.9. Remote Control Signal Receiving Sound 8.10. Powerful Mode Operation 8.11. Ionizer Operation 9 Operating Instructions 10 Installation Instructions 10.1. Safety Precautions 10.2. INDOOR UNIT 10.3. OUTDOOR UNIT 11 2-way, 3-way Valve 11.1. Evacuation of the Equipment (For Europe & Oceania Destination) 11.2. Air Purging of the Piping and Indoor Unit 54 60

Page
28 29 29 30 31 35 43 43 46 49 53

2003 Matsushita Industrial Corp. Sdn. Bhd. (11969-T). All rights reserved. Unauthorized copying and distribution is a violation of law.

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

12 Servicing Information 12.1. Indoor Electronic Controllers Removal Procedures 12.2. Cross Flow Fan Indoor and Fan Motor Removal Procedures 13 Troubleshooting Guide 13.1. Refrigeration cycle system 14 Technical Data 15 Exploded View 16 Replacement Parts List 17 Exploded View

66 66

18 Replacement Parts List 19 Electronic Circuit Diagram 19.1. REMOTE CONTROL

79 80 86

67 70 70 72 76 77 78

19.2. PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD 19.3. PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD 19.4. PRINT PATTERN OUTDOOR UNIT PRINTED CIRCUIT BOARD 89 88 87

1 Features
High Efficiency Compact Design Comfort Environment Ionizer control for generate negative ion in discharge air Air filter with function to reduce dust and smoke Wider range of horizontal discharge air New Automatic air swing and manual adjusted by remote control for horizontal airflow Auto Restart Random auto restart after power failure for safety restart operation Removable and Washable Front Panel Remote Control Self-illuminating Button Catechin Air Purifying Filter Trap dust, tobacco smoke and tiny particles Prevent the growth of bacteria and viruses trapped Long Installation Piping Long piping up to 25 meter 24-hour Timer Setting Triple Deodorizing Filter Absorb odours produced by wall paper, construction material and living environment Quality Improvement Gas leakage protection Prevent compressor reverse cycle Noise prevention during soft dry operation. Anti-dew Formation Control (Cooling & Soft Dry) Overload Protection Control (Heating) Outdoor Fan Control Compressor High Pressure Control Blue Coated Condenser High resistance to corrosion Operation Improvement Quiet mode to provide quiet operation Powerful mode to reach the desired room temperature quickly

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

2 Functions
Remote Control

Self illuminating button

OFF / ON I

Operation OFF / ON Operation Mode Selection



AUTO HEAT COOL DRY

TEMP.

Room Temperature Setting


Heating, Cooling, Soft Dry Operation. Temperature Setting (16C to 30C) Automatic Operation Operation with 2C higher than standard temperature. Operation with standard temperature. Operation with 2C lower than standard temperature.

MODE

Automatic Operation Mode Heating Operation Mode Cooling Operation Mode Soft Dry Operation Mode

FAN SPEED

Indoor Fan Speed Selection



FAN FAN FAN AUTO FAN

Low Fan Speed Medium Fan Speed High Fan Speed Automatic Fan Speed

ON-TIMER OFF-TIMER

Timer Operation Selection


24-hour, OFF / ON Real Timer Setting.

TIME AIR SWING

Time / Timer Setting


Hours and minutes setting.

Vertical Airflow Direction Control


Vertical Automatic Airflow Direction Control and Manual Airflow Direction Control (5 stages of adjustment). Horizontal Automatic Airflow Direction Control and Manual Airflow Direction Control (5 stages of adjustment).
SET CANCEL

Timer Operation Set / Cancel


ON Timer and OFF Timer setting and cancellation.

CLOCK

Clock Setting
Current time setting.

POWERFUL

Powerful Mode Operation OFF/ON Quiet Mode Operation OFF/ON

QUIET

Ionizer Operation OFF / ON

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

Indoor Unit

AUTO OFF / ON

Automatic Operation Button


Press for < 5s to operate Automatic operation mode. (Used when the remote control cannot be used.) Press continuously for 5s or < 10s to operate Test Run/Pump down. Beep sound will be heard at the 5th second. (Used when test running or servicing.) Press continuously for 10s and above to omit or resume the remote control signal receiving sound. Beep, beep sound will be heard at the 10th second.

Ionizer Control
Ionizer control for generate negative ion in discharge air.

Indoor Fan Speed Control


High, Medium and Low. Automatic Fan Speed Mode Heating : Fan speed varies from Me SSLo in accordance with indoor heat exchanger. Cooling : Fan rotates at Hi, Me and Lo- speed. Deodorizing control is available. Soft Dry : Fan rotates at Lo- speed. Deodorizing control is available.

Operation Indication Lamps (LED)


POWER (Green) .......... Lights up in operation, blinks in Automatic Operation Mode judging and Hot Start operation. QUIET (Orange) ......... Lights up in Quiet Mode Operation. TIMER (Orange) ......... Lights up in Timer Setting. POWERFUL (Orange) ... Lights up in Powerful Mode Operation. (Green) ............ Lights up in Ionizer Mode Operation.

Airflow Direction Control


Automatic air swing and manual adjusted by remote control for vertical and horizontal airflow.

Time Delay Safety Control


Restarting is inhibited for appro. 3 minutes.

Operation Mode
Heating, Cooling, Soft Dry and Automatic Mode.

7 Minutes Time Save Control


Cooling Operation only.

Powerful Operation
Reaches the desired room temperature quickly.

Anti-Dew Formation Control


Anti-Dew Formation Control for indoor unit discharge area.

Quiet Operation
To provide quiet operation.

Hot-Start Control
At Heating Operation the indoor fan will operate at SLo speed when indoor heat exchanger temperature reaches 30C.

Random Auto Restart Control


Operation is restarted randomly after power failure at previous setting mode.

Anti Cold Draft Control


The indoor fan operates at Lo (30 sec.) after that SSLo when the indoor heat exchanger temperature is low. (During Heating mode thermal off)

Anti-Freezing Control
Anti-Freezing control for indoor heat exchanger. (Cooling and Soft Dry)

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

Outdoor Unit

Compressor Reverse Rotation Protection Control


To protect compressor from reverse rotation when there is a instantaneous power failure.

Deice Control
To prevent frosting at outdoor heat exchanger during Heating Operation.

4-Way Valve Control


When the unit is switched to OFF during Heating Operation, 4-way valve stays at Heating position for 5 minutes.

Overload Protector
Inner protector.

60 Secs. Forced Operation Control


Once the compressor is activated, it does not stop within the first 60 secs. However, it stops immediately with remote control stop signal.

Outdoor Fan Operation Control


6-pole induction motor (2 speed). For Cooling or Soft Dry operation Hi-speed ............. When outdoor temperature reaches to 31C. Lo-speed ............. When outdoor temperature reaches to 29C. For Heating operation Hi-speed ............. When outdoor temperature reaches to 13.5C. Lo-speed ............. When outdoor temperature reaches to 15.5C. For Over-heating Protection, the Fan is switched ON or OFF depending on the piping temperature and the outdoor temperature.

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

3 Product Specifications
Unit Power Source Phase, Voltage, Cycle CS-A18CKE CU-A18CKE Single, 220 - 230, 50 Hz

Cooling Capacity

kW (BTU/h)

5.30 (18,100) - 5.30 (18,100)

Heating Capacity Moisture Removal Airflow Method

kW (BTU/h) l/h (Pint/h) OUTLET

5.65 (19,300) - 5.70 (19,400) 2.9 (6.1) SIDE VIEW TOP VIEW

INTAKE

Air Volume

Indoor Air (Lo) Indoor Air (Me) Indoor Air (Hi) Indoor Air (SHi)

m3/min (cfm) m3/min (cfm) m3/min (cfm) m3/min (cfm) dB (A) dB

Noise Level Power Level Electrical Data Input Power Running Current EER COP Starting Current Piping Connection Port (Flare piping) Pipe Size (Flare piping) Drain Inner diameter Hose Length Power Cord Length Number of core-wire Dimensions Height Width Depth Net Weight Compressor Type Motor Rated Air Circulation Type Output Type Material Motor Type Input Rated Output Fan Speed Low Medium High SuperHigh

kW A W/W (BTU/hW) W/W (BTU/hW) A inch inch inch inch mm mm m inch (mm) inch (mm) inch (mm) lb (kg)

kW

W W rpm rpm rpm rpm

Cooling; 13.1 (460) - 13.1 (460) 28.6 (1,010) - 32.4 (1,140) Heating; 14.0 (500) - 14.0 (500) Cooling; 14.6 (520) - 14.6 (520) Heating; 14.6 (520) - 14.6 (520) Cooling; 15.4 (544) - 15.4 (544) 50.7 (1,790) - 51.7 (1,830) Heating; 15.9 (561) - 15.9 (561) Cooling; 15.9 (561) - 15.9 (561) Cooling; High 43 - 43, Low 38 - 38 Cooling; High 53 - 54 Heating; High 42 - 42, Low 38 - 38 Heating; High 54 - 55 Cooling; 54 - 54 Cooling; 67 - 68 Heating; 53 - 53 Heating; 67 - 68 Cooling; 1.72 - 1.76 Heating; 1.65 - 1.71 Cooling; 8.0 - 7.8 Heating; 7.7 - 7.6 Cooling; 3.08 - 3.01 (10.52 -10.28) Heating; 3.42 - 3.33 (11.70 - 11.35) 44.5 G ; Half Union 1/2 G ; 3-way valve 1/2 L ; Half Union 1/4 L ; 2-way valve 1/4 G ; (gas side) 1/2 G ; (gas side) 1/2 L ; (liquid side) 1/4 L ; (liquid side) 1/4 12 650 1.9 3 (1.5 mm2) 10 - 13/16 (275) 29 - 17/32 (750) 39 - 9/32 (998) 34 - 7/16 (875) 8 - 9/32 (210) 13 - 19/32 (345) 24 (11.0) 132 (60.0) Rotary (1 cylinder) rolling piston type Induction (2-poles) 1.5 Cross-flow Fan Propeller Fan ASHT-18 PP Transistor (8-poles) Induction (6-poles) 44.8 - 53.5 135.7 - 151.2 30 80 Cooling; 1,160 - 1,160 460 - 490 Heating; 1,240 - 1,240 Cooling; 1,290 - 1,290 Heating; 1,290 - 1,290 Cooling; 1,360 - 1,360 815 - 830 Heating; 1,400 - 1,400 Cooling; 1,400 - 1,400

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

Unit Heat Exchanger Description Tube material Fin material Fin Type Row / Stage FPI Size (W H L) Refrigerant Control Device Refrigeration Oil Refrigerant (R-22) Thermostat Protection Device Capillary Tube

mm

(cm3) g (oz)

Air Filter

Length Flow Rate Inner Diameter Material Style

mm l/min mm

Capacity Control Compressor Capacitor Fan Motor Capacitor

F, VAC F, VAC

CS-A18CKE CU-A18CKE Evaporator Condenser Copper Copper Aluminium (Pre Coat) Aluminium (Blue Coat) Slit Fin Corrugated Fin (Plate fin configuration, forced draft) 2 15 2 28 21 16 810 315 25.4 833.2 711.2 44 867.8 Capillary Tube SUNISO 4GDID or ATMOS M60 (700) 1,710 (60.4) Electronic Control Electronic Control Inner Protector Cooling; 970, Heating; 820 Cooling; 11.0, Heating; 27.0 Cooling; 1.6, Heating; 2.2 P.P. Honeycomb Capillary Tube 45 F, 400VAC 3.5 F, 440VAC

Note: Specifications are subject to change without notice for further improvement.

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

Unit Power Source Phase, Voltage, Cycle

CS-A24CKE Single, 220 - 230, 50 Hz

CU-A24CKE

Cooling Capacity

kW (BTU/h)

7.03 (24,000) - 7.03 (24,000)

Heating Capacity Moisture Removal Airflow Method

kW (BTU/h) l/h (Pint/h) OUTLET

7.80 (26,600) - 7.80 (26,600) 4.0 (8.5) SIDE VIEW TOP VIEW

INTAKE

Air Volume

Indoor Air (Lo) Indoor Air (Me) Indoor Air (Hi) Indoor Air (SHi)

m3/min (cfm) m3/min (cfm) m3/min (cfm) m3/min (cfm) dB (A) kW A W/W (BTU/hW) W/W (BTU/hW) A inch inch inch inch mm mm m inch (mm) inch (mm) inch (mm) lb (kg)

Noise Level Electrical Data Input Power Running Current EER COP Starting Current Piping Connection Port (Flare piping) Pipe Size (Flare piping) Drain Inner diameter Hose Length Power Cord Length Number of core-wire Dimensions Height Width Depth Net Weight Compressor Type Motor Rated Air Circulation Type Output Type Material Motor Type Input Rated Output Fan Speed Low Medium High SuperHigh

kW

W W rpm rpm rpm rpm

Cooling; 13.5 (480) - 13.5 (480) 28.1 (990) - 31.7 (1,120) Heating; 14.6 (520) - 14.6 (520) Cooling; 15.3 (540) - 15.3 (540) Heating; 15.3 (540) - 15.3 (540) Cooling; 16.4 (580) - 16.4 (580) 49.7 (1,750) - 50.7 (1,790) Heating; 17.4 (610) - 17.4 (610) Cooling; 17.4 (610) - 17.4 (610) Cooling; High 47 - 47, Low 41 - 41 Cooling; High 53 - 54 Heating; High 46 - 46, Low 41 - 41 Heating; High 54 - 55 Cooling; 2.54 - 2.58 Heating; 2.53 - 2.56 Cooling; 12.3 - 12.2 Heating; 12.2 - 12.2 Cooling; 2.77 - 2.72 (9.45 - 9.30) Heating; 3.08 - 3.05 (10.51 - 10.39) 65.0 G ; Half Union 5/8 G ; 3-way valve 5/8 L ; Half Union 1/4 L ; 2-way valve 1/4 G ; (gas side) 5/8 G ; (gas side) 5/8 L ; (liquid side) 1/4 L ; (liquid side) 1/4 12 650 1.9 3 (2.5 mm 2) 10 - 13/16 (275) 29 - 17/32 (750) 39 - 9/32 (998) 34 - 7/16 (875) 8 - 9/32 (210) 13 - 19/32 (345) 26 (12.0) 139 (63.0) Rotary (1 cylinder) rolling piston type Induction (2-poles) 2.0 Cross-flow Fan Propeller Fan ASHT-18 PP Transistor (8-poles) Induction (6-poles) 44.8 - 53.5 171.3 - 190.0 30 80 Cooling; 1,260 - 1,260 460 - 490 Heating; 1,360 - 1,360 Cooling; 1,430 - 1,430 Heating; 1,430 - 1,430 Cooling; 1,530 - 1,530 815 - 830 Heating; 1,610 - 1,610 Cooling; 1,610 - 1,610

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

Unit Heat Exchanger Description Tube material Fin material Fin Type Row / Stage FPI Size (W H L) Refrigerant Control Device Refrigeration Oil Refrigerant (R-22) Thermostat Protection Device Capillary Tube

mm

(cm3) g (oz)

Air Filter

Length Flow Rate Inner Diameter Material Style

mm l/min mm

Capacity Control Compressor Capacitor Fan Motor Capacitor

F, VAC F, VAC

CS-A24CKE CU-A24CKE Evaporator Condenser Copper Copper Aluminium (Pre Coat) Aluminium (Blue Coat) Slit Fin Corrugated Fin (Plate fin configuration, forced draft) 2 15 2 28 21 18 810 315 25.4 833.2 711.2 44.0 867.8 Capillary Tube SUNISO 4GDID or ATMOS M60 (1,130) 2,050 (72.4) Electronic Control Electronic Control Inner Protector Cooling; 730, Heating; 340 Cooling; 12.5, Heating; 21.0 Cooling; 1.6, Heating; 2.0 P.P. Honeycomb Capillary Tube 45 F, 400VAC 3.5 F, 440VAC

Note: Specifications are subject to change without notice for further improvement.

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

4 Dimensions

10

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

11

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

5 Refrigeration Cycle Diagram

12

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

6 Block Diagram

13

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

7 Wiring Diagram

14

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

8 Operation Details
8.1. Indoor Fan Speed Control

Auto Fan Speed Control When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table. Manual Fan Speed Control Basic fan speed adjustment (3 settings, from Lo to Hi) can be carried out by using the Fan Speed selection button at the remote control.

Speed COOL, DRY S Hi Hi Me Lo+ Lo LoS Lo SS Lo Q SHi Q Hi Q Me Q Lo

Heat Hi Me Lo LoS Lo SS Lo Q Hi Q Me Q Lo

CS-A24CKE 1610 1530 1430 1360 1260 1070 830 300 1510 1430 1330 1260 1160

CS-A18CKE 1400 1360 1290 1240 1160 980 760 300 1300 1260 1190 1140 1060

15

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

8.2.

Cooling Mode Operation

Cooling in operation according to Remote Control setting.

Time Delay Safety Control (3 minutes) When the compressor is stopped by Remote Control, it restarts after 3 minutes when the Remote Control is turned ON. When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3 minutes. 7 minutes Time Save Control The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is between the compressor ON temperature and OFF temperature.

Anti-Freezing Control If the temperature of the indoor heat exchanger falls continuously below 2C for 4 minutes or more, the compressor turns off to protect the indoor heat exchanger from freezing. The fan speed setting remains the same. Compressor will restart again when the indoor heat exchanger temperature rises to 10C (Recovery).
3 minutes waiting of Time Delay Safety Control is valid for Cooling Operation.

Compressor Reverse Rotation Protection Control If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and indoor heat exchanger is 2.5C or less for 2 minutes, compressor will stop and restart automatically. (Time Delay Safety Control is valid)

! T = Intake air temperature - Indoor heat exchanger temperature This is to protect reverse rotation of the compressor when there is a instantaneous power failure.

Anti-Dew Formation Control Purpose is to prevent dew formation on indoor unit air discharge area. When room temperature is constant (1C) the following conditions occur for 30 minutes continuously, anti-dew formation will activate: Indoor intake air temperature is more than 24C and less than 30C. Remote Control setting temperature is less than 25C. Compressor is on. Cooling operation mode. Indoor Fan motor operate at Low fan speed or QLo. This control is cancelled immediately when above condition is changed. Anti-Dew formation is control by: 1. Lo fan speed Lo fan is changed to Lo+ fan

16

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

2. QLo fan speed (Transistor Motor)

3. QLo fan speed (Induction Motor)

Automatic Fan Speed Mode

When Automatic Fan Speed is selected at Remote Control during cooling operation. Fan speed rotates in the range of Hi to Me. Deodorizing Control.

17

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

Cooling Operation Time Diagram

Quiet Operation Control

(For Cooling Mode or cooling region of Soft Dry Mode) Purpose of this operation is to provide quite cooling operation compare to normal operation. When the Quiet Mode is set at the remote control, Quiet Mode LED illuminates, the sound level will be automatically decreased 3 dB, against the present sound level operation. Quiet setting of fan speed rpm refer to Indoor Fan Speed Control. Dew formation become severe at Quiet Lo cool, therefore: i) For Transistor Motor Quiet Lo Cool is operated only 1h 30 minute (1h QLo, 30 min QLo+100). After that, it goes back to QLo+180 rpm. (However quiet LED remains on). ii) For Induction Motor Quiet Lo Cool is operated only 1h 30 minute (1h QLo, 30 min QLo+80). After that, it goes back to QLo+170 rpm. (However quiet LED remains on).

18

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

Manual Fan Speed: RPM control during Lo cool

RPM control during Hi & Me cool

Auto Fan Speed:-

Quiet Mode Operation will stop if: Quiet mode button is pressed again. Stopped by ON/OFF switch. Timer OFF activates. Powerful mode button is pressed.

19

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

8.3.

Soft Dry Mode Operation

The unit starts cooling operation until the room temperature reaches the setting temperature set on the Remote Control, and then Soft Dry operation will start. During Soft Dry operation, the Indoor Fan will operate at Lo- speed. Once room temperature reaches below Soft Dry OFF temperature. Indoor Fan, Compressor and Outdoor Fan stop for 6 minutes.

Time Delay Safety Control Once the compressor stops, it will not start for 3 minutes during Cooling operation. Anti-Freezing Control Same as Anti-Freezing Control for Cooling Mode operation. (For Soft Dry region, 6 minutes waiting is valid during compressor stops.)

Compressor Reverse Rotation Protection Control Same as Compressor Reverse Rotation Protection Control for Cooling Mode Operation. (For Soft Dry region, 6 minutes waiting is valid during compressor stops.)

Anti-Dew Formation Control Same as Anti-Dew Formation Control for Cooling Mode operation. Automatic Fan Speed Mode When Automatic Fan Speed is selected at Remote Control during Soft Dry operation. Fan speed off and on at Lo- speed. Deodorizing Control.

20

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

Soft Dry Operation Time Diagram

Quiet Operation Control Same as Quiet Operation Control for Cooling Mode operation.

21

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

8.4.

Heating Mode Operation

Heating in operation according to Remote Control setting. Time Delay Safety Control When the compressor is stopped by Power Switch, Remote Control or there is a power failure, it restarts after 3 minutes when the Power Switch, Remote Control is turned ON or the power supply is resumed. When the setting temperature is reached during heating operation, the compressor stops and it will not start for 4 minutes.

Overload Protection Control (a) Outdoor Fan Control If the temperature of the Outdoor Heat Exchanger less than -3C, Outdoor Fan is ON. The Outdoor Fan stop, when Outdoor Heat Exchanger temperature is Tb or more according to Outdoor Air Temperature region as table below: The Outdoor Fan restarts when the indoor heat exchanger temperature falls to 49C.

During starting of Heating mode and after deice, Outdoor Fan ON for 90 sec. (Hi).

(b) Compressor High Pressure Control If the indoor heat exchanger becomes 68C or more, the compressor will stop and restart automatically. (Time Delay Safety Control - 4 minutes waiting).

4-way Valve Control 4-way valve ON during Heating operation, except deicing operation. When the unit is switched to OFF during Heating operation, 4-way valve stays at Heating position for 5 minutes.

Hot Start Control When Heating operation starts, Indoor Fan will not start until the indoor heat exchanger reaches 30C as diagram shown.

Hot Start is completed when indoor heat exchanger reaches 42C. Maximum Hot start duration = 4 minutes. After 4 minutes, Hot start operation will be shifted to normal Heating operation.

22

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

Automatic Fan Speed Mode When Automatic Fan Speed is selected at Remote Control during heating operation. Fan speed rotates in the range of Me SLo according to the heat exchanger temperature.

Anti Cold Draft Control

Compressor Reverse Rotation Protection Control If the compressor is operating continuously for 5 minutes or longer and the temperature difference between indoor heat exchanger and intake air is 5C or less for 2 minutes, compressor will stop and restart automatically. (Time Delay Safety Control is valid)

! T = Indoor heat exchanger temperature - Intake air temperature This is to protect reverse rotation of the compressor when there is a instantaneous power failure.

23

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

Heating Operation Time Diagram

Deicing Control Deice starts to prevent frosting at outdoor heat exchanger. Normal Deicing Deice operation detection commences in Heating operation starts or 60 minutes after previous deice operation. If the outdoor piping temperature drops to -4C for 50 sec. continuously during compressor is in operation, deice will start. (There is no detection during Outdoor Fan stops.) Overload Deicing During heating operation, if the outdoor Fan OFF duration (due to overload control) is accumulated up to 60 minutes and after compressor starts for 1 minutes, deicing starts. Deicing ends when (a) 12 minutes after deicing operation starts; (b) The outdoor piping temperature rises to about 12C. After deicing operation, compressor stops for 30 seconds and 4-way valve stays at cooling position for 10 seconds.

24

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

a) Normal Deicing Time Diagram

(b) Overload Deicing Time Diagram

25

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

Quiet Operation Control (For Heating Mode) Purpose of this operation is to provide quite heating operation compare to normal operation. When the Quiet Mode is set at the remote control, Quiet Mode LED illuminates, the sound level will be automatically decreased 3 dB, against the present sound level operation. Quiet setting of fan speed rpm refer to Indoor Fan Speed Control. Manual Fan Speed: Rpm control during Lo, Me & Hi Cool

Auto Fan Speed: Rpm control depends on the piping air temperature sensor of Indoor heat exchanger

Quiet Mode Operation will stop if: Quiet mode button is pressed again. Stopped by ON/OFF switch. Timer OFF activates. Powerful mode button is pressed.

26

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

8.5.

Automatic Mode Operation

1. When the Automatic Mode Operation is selected, the indoor fan operates at SLo fan speed for 25 seconds to sense intake air temperature and determine the 1st operation mode. If indoor intake air temperature is less than 16C, Heating mode will immediate operate.

2. Operation mode will be determine again after 1 hour of operation, if the room temperature reaches to set temperature and compressor off time is over 7 minutes 30 seconds continuously.
The present operation mode will be continued, if the room temperature does not reach to set temperature (Compressor keeps running) eventhough after 1 hour from automatic operation mode started.

Present Mode Cooling 23C

Judgement Cooling O (Judgement: 23C & Above)

Next Mode Soft Dry Not Applicable

Cooling Heating

Heating O (Judgement: Below 23C) O (Judgement: Below 20C) O (Judgement: 25C & below)

Soft Dry

20C

Soft Dry Heating

Not Applicable

O (Judgement: 20C & Above)

Heating 25C

Cooling Heating

O (Judgement: Above 25C)

Not Applicable

Automatic Set Temperature Refer 3. as below.

3. Automatic Set Temperature For each operation, set temperature will automatically set as shown below. However it can be selected 2C higher or 2C lower from standard set temperature by pressing the Room Temperature Setting button.
Operation Cooling Soft Dry Heating Hi (+2C) 27C 24C 23C (Standard) (0C) 25C 22C 21C Lo (-2C) 23C 20C 19C

The mode judging temperature and standard setting temperature can be increased by 2C, by open the circuit of JX1 at indoor electronic controller.

27

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

8.6.

Random Auto Restart Control

If there is a power failure during air conditioner operation, operation will be automatically restarted after 3 to 4 minutes when the power is resumed. It will start with previous operation mode and airflow direction. Restart time is decided randomly using 4 parameter:Intake air temperature, setting temperature, fan speed and Air Swing Blade position. Auto Restart Control is not available when Timer is set. This control can be omitted by open the circuit of JX2. (Refer Circuit Diagram)

8.7.

Airflow Direction Control


Vertical Airflow Direction Auto-Control

When set a Airflow Direction Auto-Control with remote control, the louver swings up and down as shown in the diagram. The louver does not swing when the Indoor Fan Motor stops during operation at the upper limit. When stopped with remote control, the discharge vent is reset, and stopped at the closing position. During Anti-dew condensation prevention, Airflow Direction Auto-control angle change from 0 - 36 to 12 - 28 under Cooling and Soft Dry operation mode.
1. There is no swinging while indoor fan motor is stopped during Cooling, Ion and Soft Dry operation. 2. In Heating operation, when the piping air temperature reaches 38C, the louver is changed from upper to lower limit position. When the piping air temperature falls to 35C, the louver is changed from lower to upper limit position.

Vertical Airflow Direction manual Control When the manual Airflow Direction Selection Button is pressed, the automatic airflow is released and the airflow direction louver move up and down in the range shown in the diagram. The louver can be adjusted by pressing the button to the desired louver position. When the remote control is used to stop the operation, the discharge vent is reset, and stopped at the closing position. During Anti-dew condensation prevention, Airflow Direction Manual control angle change from 14, 19, 24, 30, 36 to 16, 18, 20, 22, 24 under Cooling and Soft Dry operation mode.

28

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

Horizontal Airflow Direction Auto-Control When set a Airflow Direction Auto-Control with remote control, the vanes swings left and right as shown in the diagram. The vanes does not swing when the Indoor Fan Motor stops during operation at 22 angle. When stopped with remote control, the discharge vent is reset, and stopped at the reset position. During Anti-dew condensation prevention, Airflow Direction Auto-control angle change from 0 - 44 to 14 - 30 under Cooling and Soft Dry operation mode.
1. There is no swinging while indoor fan motor is stopped during Cooling, Ion and Soft Dry operation. 2. In Heating operation, when the piping air temperature reaches 38C, the airflow direction is Auto Swing left and right (8-36). When the piping air temperature falls to 35C, the airflow direction is stop at 22 angle.

Horizontal Airflow Direction manual Control When the manual Airflow Direction Selection Button is pressed, the automatic airflow is released and the airflow direction vane move left and right in the range shown in the diagram. The louver can be adjusted by pressing the button to the desired vane position.

When the remote control is used to stop the operation, the vanes is reset, and stopped at reset position. During Anti-dew condensation prevention, Airflow Direction Manual control angle change from 0, 11, 22, 33, 44 to 14, 18, 22, 26, 30 under Cooling and Soft Dry operation mode.

8.8.

Delay ON Timer Control

When the Delayed ON Timer is set by using the remote control, the unit will start operate slightly before the set time, so that the room will reach nearly to the set temperature by the desired time. For Cooling and Soft Dry mode, the operation will start 15 minutes before the set time. For Heating mode, the operation will start 30 minutes before the set time. For Automatic mode, the indoor fan will operate at SLo speed for 25 seconds, 30 minutes before the set time to detect the intake air temperature to determine the operation mode. The operation indication lamp will blink at this time.

8.9.

Remote Control Signal Receiving Sound

Long beep sound will be heard when: Stopping the Air Conditioner using ON/OFF switch. Stopping the Quiet Mode. Stopping the Powerful Mode. Stopping the Ion Mode. Short beep sound will be heard for others. To switch off the beep sound:Press the Automatic Operation Button continuously for 10 seconds or more (beep beep will be heard at the 10th second). Repeat the above if you want to switch ON the beep sound.

However, if the Automatic Operation Button has been pressed the Automatic operation will be activated. If you do not require this operation, you may change it by using the remote control.

29

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

8.10. Powerful Mode Operation


Purpose of this operation is to be obtain the setting temperature quickly. 1. Cooling and Soft Dry Mode When the Powerful Mode is set, the set temperature will be automatically decreased 3C against the present setting temperature (Lower temperature: 16C). This operation automatically will be running under SHi Fan Speed (Cooling), LoFan Speed (Soft Dry). Vertical Airflow Direction:In Manual setting, the vane will automatically shift down 10 lower than previous setting. In Auto setting, the vane will automatically swing up and down. However the upper and lower limit will be shifted 10 downward. 2. Heating Mode When the Powerful Mode is set, the set temperature will be automatically increased 3C against the present setting temperature (Higher temperature: 30C). The Fan Speed will shift as shown below:

Vertical Airflow Direction:In Manual setting, the vane will automatically shift down 5 lower than previous setting. In Auto setting, the vane will automatically shift between upper and lower limit depending on the intake air temperature as Heating Mode, Airflow Direction Auto-Control. However the upper and lower limit will be shifted 5 downward. 3. Powerful mode will operate for 15 minutes only. 4. Powerful Mode will stop if: Powerful mode button is pressed again. Stopped by ON / OFF switch. Timer-off activates. Quiet mode button is pressed. Operating mode button is changed.

30

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

8.11. Ionizer Operation


Purpose To provide fresh air effect to user by discharging minus Ion to air. Control Condition

a. Ionizer Only Operation. 1. When air-conditioner unit is at OFF condition (standby) and ION operation button at remote control is pressed. Fan & ionizer on, ION LED illuminates, but power LED maintain off. (1 2) However, fan speed can be adjusted later by customer during this operation.

Airflow direction (Horizontal Vane) control: Follow vane direction control at cooling mode. Horizontal vane can be changed by customer during ion only operation. 2. Ion only operation can be off by pressed ION button again. (2 1) 3. It can be changed to previous operated mode (Auto, Cool, Dry, Heat) + ion operation by OFF/ON switch. (2 4) 4. During ion only operation, if power failure occur, after power resume, ionizer & air-conditioner resumes immediately. 5. After error = 24 times, (about 11h 30 min.), ion & fan off with Ion LED blinks continuously. (Detail refer to Ionizer Error detection control.) b. Operation Mode + Ionizer Operation. 1. Ionising Operation Start Condition When air-conditioner unit is in ON condition (Cool, Dry, Heat, Auto mode) and ION operation button at remote control is pressed. Ionizer on & ION LED illuminates. (3 4) Power LED also illuminates. 2. Ionising Operation Stop Condition When one of the following condition is satisfied, ION operation stops. a. Stopped by ON/OFF switch. b. Timer OFF activates. c. ION operation button is pressed again. d. ION feedback signal shows error.

31

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

3. Ionizer operation status is not memorised by Micon. After OFF, when operation is ON again, air-conditioner operates without ionizer operation. However, during Cool mode etc + ionizer operation, if there is a power failure & then power resume, air conditioner shall on at that mode + ionizer operation. c. Timer during ionizer operation Refer to case study in next for detail.

8.11.1. Ionizer Operation case study

8.11.2. Ionizer Error Detection Control


A. Purpose To inform user that error occurs at ionizer system so that repairing job can be carried out. B. Two type of error detection control: (a) When Ionizer is ON (example case: Ionizer shorted, ionizer over current protection) During ionizer ON operation, when feed back voltage = Lo (micon input) is detected, Ion is OFF. If feedback = Lo for 11 hrs 30 min, ION LED blinks continuously. To cancel ion LED blinking, press ion button at remote control (or Auto operation switch at air conditioner unit). If ion button is pressed again, ion LED blinks again. The error can be reset by: i) Operation ON/OFF button press to operation OFF. ii) Auto operation switch press to operation OFF. iii) Operation OFF due to Timer OFF reach. iv) Timer set ON & operation from ON to OFF. (b) When Ionizer is OFF (example case: ionizer connecting wire loose) During air conditioner is at standby or ON operation and ionizer at OFF condition, if ionizer feed back voltage = Hi (micon input) is detected, Ionizer breakdown detection control is activated and ion LED immediately blinks. To cancel Ion LED blinking, press ion button at remote control (or Auto operation switch at air conditioner unit). If ion button is pressed again, ion LED blinks again. During ionizer at breakdown condition, if ionizer feedback voltage = Lo (become OK), ion LED will stop blinking.

32

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

Note: 1. 24 times checking: Actual Ion ON for 10s & OFF for 30 min continuously for 24 times. 2. 24 times count will be cleared when either one of the following conditions happen. a) 24 times count over, b) Ionizer cancel if press Ion button or power reset, c) Ion feedback signal is OK. 3. Error protection will be cleared when one of the following conditions happen. a) Power reset, b) Remote control operation ON/OFF button press, c) Auto operation switch press, d) Operation OFF due to Timer OFF 4. Ion auto restart: Ion will auto restart if actual Ion was ON with no error protection control during power shutdown. Otherwise Ion will not auto restart. 5. Ion LED blinking can ON/OFF during error protection by following conditions: a) Press remote control ion button b) Press Auto operation switch to OFF blinking.

33

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

34

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

9 Operating Instructions

PRODUCT OVERVIEW Outdoor Unit

Your device can...


Air intake

Cooling
Air outlet

Heating

Dehumidifying

Piping, connecting cable

Filters under front panel, see page 38

Indoor Unit

Indicator & Auto operation button

Direction louver Ionizer Under front panel

Remote Control
AUTO HE AT COOL DR Y
AUTO

Open front panel If Remote Control malfunctions/is misplaced...

see page

ON OFF

AUTO AUTO UT FAN AN

see page

Press to START

36 Set TEMPERATURE 37 Activate 36 Select MODE 37 Activate 37 TIMER functions


Open
MODE

TEMP

Switch OFF/ON of the device


OFF/ ON

AUTO-Mode only

QUIET

AIR SW ING

POWERFUL FAN SPEE D

Very fast cooling/heating 37 Select Fan Speed 37 Select air flow direction 37 Set CLOCK 39
Press again to STOP

1 ON
OFF

3 SET
CANCEL

TIMER
RESET CLOCK

Memory reset!

35

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

Find on page

OPERATION
Press button

Automatic Internal Function

Switch on

Room temperature

39
Select... Automatic PREPARATIONS According to the room temperature the system automatically chooses

40

Set temperature

TROUBLESHOOTING

Select... Heating Choose the right temperature to be comfortably warm! Recommended:

41

Set temperature
Select... Cooling Choose the right temperature to be comfortably cool! Recommended:

SAFETY PRECAUTIONS

38
Select... HELPFUL INFORMATION Dehumidifying Very gentle cooling and dehumidifying operation. Recommended: Room temperature

Set temperature

IO

* automatic during
dehumidifying (DRY)

Switch off

Additional comfort

36

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

Press button

Air Flow

Vertical direction

Horizontal direction

Fan speed (air volume)

Direction / volume Select automatic / manual

Select

TIMER Operation

ON Timer

Set time Confirm or

OFF Timer

Set time Confirm or

ON & OFF Set time Confirm Timer

cancel

Active every day

Current time OK? > Setting : page 39

Start before ON time Provide quiet operation

COOL/DRY : 15 min. AUTO/HEAT : 30 min.

QUIET Operation
Activate / Deactivate

Air flow sound Air flow sound will reduce during operation

Produce negative ion for fresh air

IONIZER
Activate / Deactivate

Air-conditioner
If Blinking Still Blinking press twice Call Service

Provide negative Provide negative ion during operation ion with FAN operation

Fast cooling/heating

Automatic Internal Function


Set temperature
Automatic

POWERFUL
Activate / Deactivate

Fan speed (air volume)

Super high

COOL /DRY

37

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

CARE & CLEANING


Indoor Unit
Wipe gently

Filters

Soaps Neutral household detergents

Benzine / Thinner Scouring powder

Filter cleaning see below Ionizer

Front Panel
Remove

Wash gently.. + dry Reinstall every 6 months Open manually Clean with cotton bud

Purifying filters
Vacuum refresh every 6 months Remove

REPLACE every 3 years!

Damaged > replace! Reinstall

Expose to direct sunlight

hrs

Air filters
Vacuum every 2 weeks Remove Wash Dry Damaged > replace!
CWD 001049

Reinstall

Catechin

Triple Deodorizing Filter

DIRTY FILTERS cause: unpurified air, low cooling/heating capacity, more unpleasant smells, higher energy consumption!

HELPFUL INFORMATION
Automatic Operation
If remote control malfunctions / is misplaced

Thunder / Lightning
see page 34
Built-in surge protection, BUT UNPLUG in case of very strong lightning!

Save cost
Better performance!
Close Vacuum see page 36

Power Failure
When power resume

Random restart automatically Restored

Use...

Deleted > set again!

38

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

Press button

PREPARATIONS
Indoor Unit

Plug/breaker refer page 42

Installation: see enclosed installation instruction!

OPEN front panel

Remove AIR filters

Place PURIFYING filters

Place AIR filters

CLOSE front Panel

Plug in

Insert batteries Set Clock

Use

Year

check

Same type! Rechargeable

Open / remove

Insert batteries / close

Press Set time

Set current time immediately

Confirm

Pre-season inspection
Batteries
14 HEAT

Fans obstructed? check START cooling/heating Check performance Call Service

For extended non-operation

START

dry internal parts

OFF

Unplug

Remove batteries

Recommended Inspections

After several seasons and due to operational conditions, performance may be reduced by dust or there may be unpleasant smells.

Consult an authorized distributor for inspection!

39

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

TROUBLESHOOTING
No problem

In case of...
Self protection procedure Abnormal noise during operation

Operation delayed for 3 minutes after successful restart It sounds like water flowing...

Caused by refrigerant flow inside

Water / foreign particles have entered the Remote Control Water leak from Indoor Unit

Mist seems to emerge from the indoor unit

Condensation effect due to cooling

Switches / buttons do not operate properly

Circuit breaker switches off frequently Outdoor unit emits water / steam Condensed moisture due to cooling Power plug / cord become unnaturally warm flashes, no warm air discharge Defrosting at outdoor unit, max. 12 min. TURN OFF/UNPLUG

CALL authorized distributor

No Operation

Circuit breaker tripped?

Power plug OK?

TIMER used correctly?

Remote control / display doesnt work

Batteries empty?

Batteries correctly inserted? See page 39

Noise too loud

Installation work slanted?

Front grille / panel closed properly?

Cooling/heating efficiency low

Temperature set correctly?

Windows / doors closed?

Filters cleaned / replaced?

Outdoor unit obstructed?

Intake / outlet ventilators obstructed?

40

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

SAFETY PRECAUTIONS
Operation

Before operating, read the safety precautions thoroughly

EMERGENCY! Immediately isolate from the mains supply (e.g. if there is a smell of burning) Use only for... Cooling NEVER use this unit for purposes other than those listed in these Operating Instructions. In particular, do not use it for the preservation of food.

NEVER use the plug to switch on/off

Do NOT stay long in the stream of cold air

Heating

Do NOT operate with wet hands

Dehumidifying Ventilate the room periodically Installation NEVER install, remove or reinstall yourself NOT in potentially explosive atmosphere Engage dealer / specialist NEVER modify / damage mains cables / connectors Connect drain hose properly Do NOT pull out the plug by the cable Mains connection Engage dealer / specialist for mains connection including... NEVER shared Place nothing on the unit --> covered openings may cause overheating

Used connectors / breakers easy reachable! Connect protective earth!

Plug in properly Do NOT insert finger or other objects into the unit! --> especially dangerous for children!

Unused for a long time? --> OFF / unplug

If the supply cord is damaged or needed to be replaced, it must be replaced by the manufacturer or its service agent or a similarly qualified person in order to avoid a hazard.

41

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

SAFETY PRECAUTIONS & FEATURES


refer page Defects Defect / suspicion of defect? > Attend defects before use! Automatic Operation: indoor temp. is gauged to select the optimum mode
36 35

Luminous button: convenient in the dark!

Do NOT repair yourself

Engage dealer / specialist

Ionizer Mode: produce negative ion for fresh air

37

Cleaning
OFF and unplug (connector or breaker) Quiet Mode: to provide quiet operation
37

Do NOT wash!

Powerful Mode: reaches the desired room temperature quickly 37

Waste disposal Uninstalling and disposal of the unit ONLY by dealer / specialist Auto Restart Control: after power failure, restart automatically when power resume

38

Removable Front Panel: for quick and easy cleaning, washable Packaging recyclable

38

38 / 39

Catechin Filter: Trapping dust, tobacco, smoke / tiny particles, it inhibits the growth of bacteria / viruses
38 / 39

Triple Deodorizing Filter: absorb odours produced by wall paper, construction material and living environment
Indoor Unit Outdoor Unit Wet Bulb

Temperature

Dry Bulb

Operational Condition

42

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

10 Installation Instructions
1. Philips screw driver 2. Level gauge Required tools for Installation Works 5. Spanner 9. Gas leak detector 6. Pipe cutter 10. Measuring tape 13. Multimeter 14. Torque wrench 18 N.m (1.8 kgf.m) 55 N.m (5.5 kgf.m) 65 N.m (6.5 kgf.m) 15. Vacuum pump 16. Gauge manifold

3. Electric drill, hole core drill 7. Reamer (70 mm) 4. Hexagonal wrench (4 mm) 8. Knife

11. Thermometer 12. Megameter

10.1. Safety Precautions


Read the following SAFETY PRECAUTIONS carefully before installation. Electrical work must be installed by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model to be installed. The caution items stated here must be followed because these important contents are related to safety. The meaning of each indication used is as below. Incorrect installation due to ignoring of the instruction will cause harm or damage, and the seriousness is classified by the following indications.
This indication shows the possibility of causing death or serious injury. This indication shows the possibility of causing injury or damage to properties only.

The items to be followed are classified by the symbols:


Symbol with background white denotes item that is PROHIBITED from doing.

Carry out test running to confirm that no abnormality occurs after the installation. Then, explain to user the operation, care and maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference.

1. Engage dealer or specialist for installation. If installation done by the user is defective, it will cause water leakage, electrical shock or fire. 2. Install according to this installation instruction strictly. If installation is defective, it will cause water leakage, electrical shock or fire. 3. Use the attached accessories parts and specified parts for installation. Otherwise, it will cause the set to fall, water leakage, fire or electrical shock. 4. Install at a strong and firm location which is able to withstand the sets weight. If the strength is not enough or installation is not properly done, the set will drop and cause injury. 5. For electrical work, follow the local national wiring standard, regulation and this installation instruction. An independent circuit and single outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire. 6. Use the specified cable (2.5 mm2) and connect tightly for indoor/outdoor connection. Connect tightly and clamp the cable so that no external force will be acted on the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at the connection. 7. Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will cause heat-up at connection point of terminal, fire or electrical shock. 8. When carrying out piping connection, take care not to let air substances other than the specified refrigerant go into refrigeration cycle. Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle, explosion and injury. 9. Do not damage or use unspecified power supply cord. Otherwise, it will cause fire or electrical shock. 10. Do not modify the length of the power supply cord or use of the extension cord, and do not share the single outlet with other electrical appliances. Otherwise, it will cause fire or electrical shock.

43

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

1. The equipment must be earthed. It may cause electrical shock if grounding is not perfect. 2. Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at surrounding of the unit, it may cause fire. 3. Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the furniture.

ATTENTION
1. Selection of the installation location. Select a installation location which is rigid and strong enough to support or hold the unit, and select a location for easy maintenance. 2. Power supply connection to the room air conditioner. Connect the power supply cord of the room air conditioner to the mains using one of the following method. Power supply point shall be the place where there is ease for access for the power disconnection in case of emergency. In some countries, permanent connection of this room air conditioner to the power supply is prohibited. 1. Power supply connection to the receptacle using a power plug. Use an approved 16A power plug with earth pin for 2.0HP (C18CK, A18CK, RS-C18CK) and 20A for 2.5HP (C24CK, A24CK, RSC24CK) for the connection to the receptacle. 2. Power supply connection to a circuit breaker for the permanent connection. Use an approved 16A circuit breaker 2.0HP (C18CK, A18CK, RS-C18CK) and 20A for 2.5HP (C24CK, A24CK, RS-C24CK) for the permanent connection. It must be a double pole switch with a minimum 3 mm contact gap. 3. Do not release refrigerant. Do not release refrigerant during piping work for installation, reinstallation and during repairing a refrigeration parts. Take care of the liquid refrigerant, it may cause frostbite. 4. Installation work. It may need two people to carry out the installation work. 5. Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.

44

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

Attached accessories

Indoor/Outdoor Unit Installation Diagram

Applicable piping kit CZ-4F5, 7, 10AN (C18CK, A18CK, RS-C18CK) CZ-52F5, 7, 10AN (C24CK, A24CK, RS-C24CK)

SELECT THE BEST LOCATION INDOOR UNIT There should not be any heat source or steam near the unit. There should not be any obstacles blocking the air circulation. A place where air circulation in the room is good. A place where drainage can be easily done. A place where consideration. noise prevention is taken into

Do not install the unit near the door way. Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles. Recommended installation height for indoor unit shall be at least 2.3 m. OUTDOOR UNIT If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the condenser is not obstructed. There should not be any animal or plant which could be affected by hot air discharged. Keep the spaces indicated by arrows from wall, ceiling, fence or other obstacles. Do not place any obstacles which may cause a short circuit of the discharged air. If piping length is over 7.5m, additional refrigerant should be added as shown in the table. This illustration is for explanation purposes only. The indoor unit will actually face a different way.

45

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

10.2. INDOOR UNIT


10.2.1. SELECT THE BEST LOCATION (Refer to Select the best location section) 10.2.2. HOW TO FIX INSTALLATION PLATE
The mounting wall is strong and solid enough to prevent it from the vibration.

10.2.3. TO DRILL A HOLE IN THE WALL AND INSTALL A SLEEVE OF PIPING


1. Insert the piping sleeve to the hole. 2. Fix the bushing to the sleeve. 3. Cut the sleeve until it extrudes about 15 mm from the wall. Caution
When the wall is hollow, please be sure to use the sleeve for tube assy to prevent dangers caused by mice biting the connecting cable.

4. Finish by sealing the sleeve with putty or caulking compound at the final stage.

The centre of installation plate should be at more than 550 mm at right and left of the wall. The distance from installation plate edge to ceiling should more than 67 mm. From installation plate left edge to units left side is 47 mm. From installation plate right edge to units right is 73 mm.
: For left side piping, piping connection for liquid should be about 126 mm from this line. : For left side piping, piping connection for gas should be about 174 mm from this line. : For left side piping, piping connecting cable should be about 984 mm from this line.

10.2.4. INDOOR UNIT INSTALLATION


1. For the right rear piping

1. Mount the installation plate on the wall with 5 screws or more. (If mounting the unit on the concrete wall consider using anchor bolts.) Always mount the installation plate horizontally by aligning the marking-off line with the thread and using a level gauge. 2. For the right and right bottom piping 2. Drill the piping plate hole with 70 mm hole-core drill. Line according to the arrows marked on the lower left and right side of the installation plate. The meeting point of the extended line is the centre of the hole. Another method is by putting measuring tape at position as shown in the diagram above. The hole centre is obtained by measuring the distance namely 150 mm and 125 mm for left and right hole respectively. Drill the piping hole at either the right or the left and the hole should be slightly slanted to the outdoor side. 3. For the embedded piping

46

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

(This can be used for left rear piping & left bottom piping also.)

47

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

10.2.5. CONNECT THE CABLE TO THE INDOOR UNIT


1. The inside and outside connecting cable can be connected without removing the front grille. 2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 3 2.5 mm2 (C18CK, C24CK, RS/RU-C18/24CK) or 5 2.5 mm2 (A18CK, A24CK) flexible cord, type designation 245 IEC 57 or heavier cord. Ensure the color of wires of outdoor unit and the terminal Nos. are the same to the indoors respectively. Earth lead wire shall be longer than the other lead wires as shown in the figure for the electrical safety in case of the slipping out of the cord from the anchorage.

Secure the cable onto the control board with the holder (clamper).

INSTALLATION OF AIR PURIFYING FILTERS 1. Open the front panel. 2. Remove the air filters. 3. Put air purifying filters (left) and triple refreshing deodorizing filter (right) into place as shown in illustration below.

48

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

HOW TO TAKE OUT FRONT GRILLE Please follow the steps below to take out front grille if necessary such as when servicing. 1. Open the intake grille and remove the screw at the front of the front grille. 2. Set the vertical airflow direction louver to the horizontal position. 3. Slide down the 3 caps on the front grille as shown in the illustration below, and then remove the 3 mounting screws. 4. Pull the lower section of the front grille towards you to remove the front grille.
When reinstalling the front grille, first set the vertical airflow direction louver to the horizontal position and then carry out above steps 2 - 3 in the reverse order.

AUTO SWITCH OPERATION The below operations will be performed by pressing the AUTO switch. 1. AUTO OPERATION MODE The Auto operation will be activated immediately once the Auto Switch is pressed. 2. TEST RUN OPERATION (FOR PUMP DOWN/SERVICING PURPOSE) The Test Run operation will be activated if the Auto Switch is pressed continuously for more than 5 sec. to below 10 sec.. A beep sound will occur at the fifth sec., in order to identify the starting of Test Run operation 3. REMOTE CONTROLLER RECEIVING SOUND ON/OFF The ON/OFF of Remote Controller receiving sound can be change over by pressing the AUTO Switch continuously for 10 sec. and above. A beep, beep sound will occur at the tenth sec., in order to indicate the ON/OFF change over of remote control receiving sound.

10.3. OUTDOOR UNIT


10.3.1. SELECT THE BEST LOCATION (Refer to Select the best location section) 10.3.2. INSTALL THE OUTDOOR UNIT
After selecting the best location, start installation according to Indoor/Outdoor Unit Installation Diagram. 1. Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut. (10 mm). 2. When installing at roof, please consider strong wind and earthquake. Please fasten the installation stand firmly with bolt or nails.

10.3.3. CONNECTING THE PIPING


Connecting The Piping To Indoor Unit Please make flare after inserting flare nut (locate at joint portion of tube assembly) onto the copper pipe. (In case of using long piping) Connect the piping Align the center of piping and sufficiently tighten the flare nut with fingers. Further tighten the flare nut with torque wrench in specified torque as stated in the table.
MODEL C18CK, A18CK, RS-C18CK C24CK, A24CK, RS-C24CK Piping size (Torque) Gas Liquid 1/2 (55 N.m) 1/4 (18 N.m) 5/8 (65 N.m) 1/4 (18 N.m)

49

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

Connecting The Piping To Outdoor Unit Decide piping length and then cut by using pipe cutter. Remove burrs from cut edge. Make flare after inserting the flare nut (located at valve) onto the copper pipe. Align center of piping to valves and then tighten with torque wrench to the specified torque as stated in the table. CUTTING AND FLARING THE PIPING 1. Please cut using pipe cutter and then remove the burrs. 2. Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused. Turn the piping end down to avoid the metal powder entering the pipe. 3. Please make flare after inserting the flare nut onto the copper pipes.

10.3.4. EVACUATION OF THE EQUIPMENT (FOR EUROPE & OCEANIA DESTINATION)


WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the following procedure.

1. Connect a charging hose with a push pin to the Low and High side of a charging set and the service port of the 3-way valve. Be sure to connect the end of the charging hose with the push pin to the service port. 2. Connect the center hose of the charging set to a vacuum pump with check valve, or vacuum pump and vacuum pump adaptor. 3. Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes. 4. Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the gauge does not move after approximately five minutes. Note: BE SURE TO FOLLOW THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE. 5. Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve. 6. Tighten the service port caps of the 3-way valve at torque of 18 N.m with a torque wrench. 7. Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to OPEN using a hexagonal wrench (4 mm). 8. Mount valve caps onto the 2-way valve and the 3-way valve. Be sure to check for gas leakage.

50

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

CAUTION

If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step 3 above take the following measure:

If the leak stops when the piping connections are tightened further, continue working from step 3. If the leak does not stop when the connections are retightened, repair the location of leak. Do not release refrigerant during piping work for installation and reinstallation. Take care of the liquid refrigerant, it may cause frostbite.

10.3.5. AIR PURGING OF THE PIPING AND INDOOR UNIT


1) Checking a gas leakage 1. Remove the service-port cap from the 3-way valves. 2. Connect the Manifold gauge set to the service port of Liquid side 3-way valve. 3. Connect the Charging Cylinder to the Manifold gauge set and open the valve of the Cylinder. 4. Open the low pressure side valve of the Manifold gauge for approx. 10 seconds and then close. 5. Check gas-leakage of the connecting portion of pipings with the gas-leak detector.

<For the left pipings>


1) Measure the pressure. 2) Keep it for 5-10 minutes Ensure if the pressure indicated on the gauge is as same as that of measured at first time

2) Air purging The air remaining in the Refrigeration cycle which contains moisture may cause malfunction on the Compressor. 1. To purge the air, push the pin on the Gas side 3-way valve for three seconds with a Hexagonal wrench and set it free for one minute. Repeat this for three times. 2. To balance the refrigerant, close the low pressure side valve on the Manifold gauge and release refrigerant from the piping through service port until the gauge indicates 0.5 - 0.3 MPa. 3. Set both 3-way valves to open position with the Hexagonal wrench for the unit operation.

51

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

10.3.6. CONNECT THE CABLE TO THE OUTDOOR UNIT


1. Remove the control board cover from the unit by loosening the screw. 2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 3 2.5 mm2 (C18CK, C24CK, RS/RU-C18/24CK) or 5 2.5 mm2 ( A18CK, A24CK) flexible cord, type designation 245 IEC 57 or heavier cord.

3. Secure the cable onto the control board with the holder (clamper). 4. Attach the control board cover back to the original position with the screw.

10.3.7. PIPE INSULATION


1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap the insulated piping end to prevent water from going inside the piping. 2. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-E FOAM with thickness 6 mm or above.

DISPOSAL OF OUTDOOR UNIT DRAIN WATER If a drain elbow is used, the unit should be placed on a stand which is taller than 3 cm. If the unit is used in an area where temperature falls below 0C for 2 or 3 days in succession, it is recommended not to use a drain elbow, for the drain water freezes and the fan will not rotate.

EVALUATION OF THE PERFORMANCE Operate the unit at cooling operation mode for fifteen minutes or more. Measure the temperature of the intake and discharge air. Ensure the difference between the intake temperature and the discharge is more than 8C.

CHECK ITEMS
Is there any gas leakage at flare nut connections? Has the heat insulation been carried out at flare nut connection? Is the connecting cable being fixed to terminal board firmly? Is the connecting cable being clamped firmly? Is the drainage OK? (Refer to Check the drainage section) Is the earth wire connection properly done? Is the indoor unit properly hooked to the installation plate? Is the power supply voltage complied with rated value? Is there any abnormal sound? Is the cooling operation normal? Is the thermostat operation normal? Is the remote controls LCD operation normal? Is the air purifying filter installed?

CHECK THE DRAINAGE Open front panel and remove air filters. (Drainage checking can be carried out without removing the front grille.) Pour a glass of water into the drain tray-styrofoam. Ensure that water flows out from drain hose of the indoor unit.

52

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

11 2-way, 3-way Valve


2-way Valve (Liquid Side) 3-way Valve (Gas Side)

Works

Shaft Position

Shaft Position

Service Port

Shipping

Close (With valve cap)

Close (With valve cap)

Close (With cap)

Evacuation (Installation and Re-installation)

Close (Counter-Clockwise)

Close (Clockwise)

Open (Push-pin)

Operation

Open (With valve cap)

Open (With valve cap)

Close (With cap)

Pumping down (Transferring)

Close (Clockwise)

Open (Counter-Clockwise)

Open (Connected manifold gauge)

Evacuation (Servicing)

Open

Open

Open With vacuum pump

Gas charging (Servicing)

Open

Open

Open (With charging cylinder)

Pressure check (Servicing)

Open

Open

Open (Connected manifold gauge)

Gas releasing (Servicing)

Open

Open

Open (Connected manifold gauge)

53

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

11.1. Evacuation of the Equipment (For Europe & Oceania Destination)


11.1.1. Evacuation of Installation
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the following procedure. If air remain in the indoor unit and refrigeration pipes, it will affect the compressor, reduce to cooling capacity, and could lead to a malfunction.

Procedure: 1. Connect a charging hose with a push pin to the Low side of a charging set and the service port of a 3-way valve. Be sure to connect the end of the charging hose with the push pin to the service port. 2. Connect the centre hose of the charging set to a vacuum pump. 3. Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from 0 MPa (0 cmHg) to -0.1 MPa (-76 cmHg). Then evacuate the air for approximately ten minutes. 4. Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the gauge does not move after approximately five minutes. BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID GAS LEAKAGE. 5. Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve. 6. Tighten the service port cap at a torque of 18 N.m with a torque wrench. 7. Remove the valve caps of the 2-way valve and the 3way valve. Position both of the valves to open using a hexagonal wrench (4 mm). 8. Mount the valve caps onto the 2-way and 3-way valves. Be sure to check for gas leakage.

Caution
If gauge needle does not move from 0 cmHg to -76 cmHg in step (3) above, take the following measures: If the leaks stop when the piping connections are tightened further, continue working from step (3). If the leaks do not stop when the connections are retightened, repair the location of the leak.

54

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

11.1.2. Pumping down

Procedure: 1. Confirm that both the 2-way and 3-way valves are set to the opened position. Remove the valve stem caps and confirm that the valve stems are in the opened position. Be sure to use a hexagonal wrench to operate the valve stems. 2. Operate the unit for 10 to 15 minutes. 3. Stop operation and wait for 3 minutes, then connect the charge set to the service port of the 3-way valve. Connect the charge hose with the push pin to the Gas service port. 4. Air purging of the charge hose. Open the low-pressure valve on the charge set slightly to purge air from the charge hose. 5. Set the 2-way valve to the closed position. 6. Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 0 MPa (0 kg/cm 2G). If the unit cannot be operated at the cooling condition (weather is rather cool), short the Pumping Down pins on the Main Control P.C.B. (Simply press the pumping down button if it is equipped.) So that the unit can be operated. 7. Immediately set the 3-way valve to the closed position. Do this quickly so that the gauge ends up indicating 0.1 MPa (1 kg/cm2G) to 0.3 MPa (3 kg/cm2G). 8. Use refrigerant reclaiming equipment refrigerant from indoor unit and pipes. to collect

9. Disconnect the charge set, and mount the 2-way and 3way valves stem caps and the service port caps. Use a torque wrench to tighten the service port cap to a torque of 18 N.m. Be sure to check for gas leakage. 10. Disconnect pipes from indoor unit and outdoor unit.

55

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

11.1.3. Evacuation of Re-installation


WHEN REINSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the following procedure. If air remain in the indoor unit and refrigeration pipes, it will affect the compressor, reduce to cooling capacity, and could lead to a malfunction.

Procedure: 1. Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way valve. Be sure to connect the end of the charging hose with the push pin to the service port. 2. Connect the centre hose of the charging set to a vacuum pump. 3. Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from 0 MPa (0 cmHg) to -0.1 MPa (-76 cmHg). Then evacuate the air for approximately ten minutes. 4. Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the gauge does not move after approximately five minutes. BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID GAS LEAKAGE. 5. Disconnect the charging hose from the vacuum pump. 6. Charge the pipes and indoor unit with gas refrigerant from 3-way valve service port, and then discharge the refrigerant until low side (gas side) gauge needle indicates 0.3 MPa (3 kg/cm 2). 7. Tighten the service port cap at a torque of 18 N.m with a torque wrench. 8. Remove the valve caps of the 2-way valve and the 3way valve. Position both of the valves to open using a hexagonal wrench (4 mm). 9. Mount the valve caps onto the 2-way and 3-way valves. BE SURE TO USE REFRIGERANT RECLAIMING EQUIPMENT WHILE DISCHARGING THE REFRIGERANT. Purge the air from charge sets centre hose. Be sure to check for gas leakage. Caution
If gauge needle does not move from 0 MPA (0 cmHg) to -0.1 MPa (-76 cmHg) in step (3) above, take the following measures: If the leaks stop when the piping connections are tightened further, continue working from step 3. If the leaks do not stop when the connections are retightened, repair the location of the leak.

56

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

11.1.4. Balance refrigerant of the 2-way, 3-way valves


(Lack of refrigerant in the refrigeration cycle)

Procedure: 1. Confirm that both the 2-way and 3-way valves are set to the open position. 2. Connect the charge set to the 3-way valves service port. Leave the valve on the charge set closed. Connect the charge hose with the push-pin to the service port. 3. Connect the charge sets centre hose to refrigerant reclaiming equipment. Purge the air from charge hose. 4. Open the valve (Low side) on the charge set and discharge the refrigerant until the gauge indicates 0.05 MPa (0.5 kg/cm 2G) to 0.1 MPa (1 kg/cm 2G). If there is no air in the refrigeration cycle (the pressure when the air conditioner is not running is higher than 0.1 MPa (1 kg/cm2G), discharge the refrigerant until the gauge indicates 0.05 MPa (0.5 km/cm2G) to 0.1 MPa (1 kg/cm2G). If this is the case, it will not be necessary to apply a evacuation. Discharge the refrigerant gradually; if it is discharged too suddenly, the refrigeration oil will also be discharged. 5. Turn on refrigerant reclaiming equipment.

57

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

11.1.5. Evacuation
(No refrigerant in the refrigeration cycle)

Procedure: 1. Connect the vacuum pump to the charge sets centre hose. 2. Evacuation for approximately one hour. Confirm that the gauge needle has moved toward -0.1 MPa (-76 cmHg) [vacuum of 4 mmHg or less.] 3. Close the valve (Low side) on the charge set, turn off the vacuum pump, and confirm that the gauge needle does not move (approximately 5 minutes after turning off the vacuum pump). 4. Disconnect the charge hose from the vacuum pump. Vacuum pump oil If the vacuum pump oil becomes dirty or depleted, replenish as needed.

58

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

11.1.6. Gas charging


(After Evacuation)

Procedure: 1. Connect the charge hose to the charging cylinder. Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder. 2. Purge the air from the charge hose. Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be careful of the liquid refrigerant). 3. Open the valve (Low side) on the charge set and charge the system with liquid refrigerant. If the system cannot be charged with the specified amount of refrigerant, it can be charged with a little at a time (approximately 150 g each time) while operating the air conditioner in the cooling cycle; however, one time is not sufficient, wait approximately 1 minute and then repeat the procedure. (pumping down-pin) 4. Immediately disconnect the charge hose from the 3way valves service port. Stopping partway will allow the refrigerant to be discharged. If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air conditioner before disconnecting the hose. 5. Mount the valve stem caps and the service port cap. Use torque wrench to tighten the service port cap to a torque of 18 N.m. Be sure to check for gas leakage.
This is different from previous procedures. Because you are charging with liquid refrigerant from the gas side, absolutely do no attempt to charge with large amount of liquid refrigerant while operating the air conditioner.

59

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

11.2. Air Purging of the Piping and Indoor Unit


11.2.1. Air purging (Installation)
Required tools: hexagonal wrench, adjustable wrench, torque wrenches, wrench to hold the joints and gas leak detector. The additional gas for air purging has been charged in the outdoor unit. However, if the flare connections have not been done correctly and there gas leaks, a gas cylinder and the charge set will be needed. The air in the indoor unit and in the piping must be purged. If air remains in the refrigeration pipings, it will affect the compressor, reduce the cooling capacity, and could lead to a malfunction.

Service port cap Be sure, using a torque wrench to tighten the service port cap (after using the service port), so that it prevents the gas leakage from the refrigeration cycle.

Procedure: 1. Recheck the piping connections. 2. Open the valve stem of the 2-way valve counterclockwise approximately 90, wait 10 seconds, and then set it to closed position. Be sure to use a hexagonal wrench to operate the valve stem. 3. Check for gas leakage. Check the flare connection for gas leakage. 4. Purge the air from the system Set the 2-way valve to the open position and remove the cap from the 3-way valves service port. Using the hexagonal wrench to press the valve core pin, discharge for three seconds and then wait for one minute. Repeat this three times. 5. Use torque wrench to tighten the service port cap to a torque of 1.8 kg.m. (18 N.m). Caution
If gas leakage is discovered in step (3) above, take the following measures: If the leaks stop when the piping connections are tightened further, continue working from step (4). If the gas leaks do not stop when the connections are retightened, repair the location of the leak, discharge all of the gas through the service port, and then recharge with the specified amount of gas from a gas cylinder.

6. Set the 3-way valve to the opened position. 7. Mount the valve stem nuts to the 2-way and 3-way valves. 8. Check for gas leakage. At this time, especially check for gas leakage from the 2way and 3-ways stem nuts, and from the service port cap.

60

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

11.2.2. Pumping down (Re-installation)

Procedure: 1. Confirm that both the 2-way and 3-way valves are set to the opened position. Remove the valve stem caps and confirm that the valve stems are in the opened position. Be sure to use a hexagonal wrench to operate the valve stems. 2. Operate the unit for 10 to 15 minutes. 3. Stop operation and wait for 3 minutes, then connect the charge set to the service port of the 3-way valve. Connect the charge hose with the push pin to the Gas service port. 4. Air purging of the charge hose. Open the low-pressure valve on the charge set slightly to purge air from the charge hose. 5. Set the 2-way valve to the close position. 6. Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 1 kg/cm 2G (0.1 MPa). 7. Immediately set the 3-way valve to the closed position. Do this quickly so that the gauge ends up indicating 3 to 5 kg/cm2G (0.3 to 0.5 MPa). 8. Disconnect the charge set, and mount the 2-way and 3way valves stem nuts and the service port caps. Use a torque wrench to tighten the service port cap to a torque of 1.8 kg.m (18 N.m). Be sure to check for gas leakage.

61

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

11.2.3. Re-air purging (Re-installation)

Procedure: 1. Confirm that both the 2-way and 3-way valves are set to the closed position. 2. Connect the charge set and a charging cylinder to the service port of the 3-way valve. Leave the valve on the charging cylinder closed. 3. Air purging. Open the valves on the charging cylinder and the charge set. Purge the air by loosening the flare nut on the 2-way valve approximately 45 for 3 seconds then closing it for 1 minute; repeat 3 times. After purging the air, use a torque wrench to tighten the flare nut on the 2-way valve. 4. Check for gas leakage. Check the flare connections for gas leakage. 5. Discharge the refrigerant. Close the valve on the charging cylinder and discharge the refrigerant until the gauge indicates 3 to 5 kg/cm2G (0.3 to 0.5 MPa) 6. Disconnect the charge set and the charging cylinder, and set the 2-way and 3-way valves to the open position. Be sure to use a hexagonal wrench to operate the valve stems. 7. Mount the valve stem nuts and the service port cap. Be sure to use a torque wrench to tighten the service port cap to a torque 1.8 kg.m (18 N.m). Be sure to check for gas leakage.

62

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

11.2.4. Balance refrigerant of the 2-way, 3-way valves


(Gas leakage)

Procedure: 1. Confirm that both the 2-way and 3-way valves are set to the open position. 2. Connect the charge set to the 3-way valves service port. Leave the valve on the charge set closed. Connect the charge hose with the push pin to the service port. 3. Open the valves (Low side) on the charge set and discharge the refrigerant until the gauge indicates 0.5 to 1 kg/cm 2G (0.05 to 0.1 MPa) . If there is no air in the refrigeration cycle [the pressure when the air conditioner is not running is higher than 1 kg/cm2G (0.1 MPa)], discharge the refrigerant until the gauge indicates 0.5 to 1 kg/cm2G (0.05 to 0.1 MPa). If this is the case, it will not be necessary to apply a evacuation. Discharge the refrigerant gradually; if it is discharged too suddenly, the refrigeration oil will be discharged.

63

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

11.2.5. Evacuation (Installation)


(No refrigerant in the refrigeration cycle)

Procedure: 1. Connect the vacuum pump to the charge sets centre hose. 2. Evacuation for approximately one hour. Confirm that the gauge needle has moved toward -0.1 MPa (-76 cmHg) [vacuum of 4 mmHg or less.] 3. Close the valve (Low side) on the charge set, turn off the vacuum pump, and confirm that the gauge needle does not move (approximately 5 minutes after turning off the vacuum pump). 4. Disconnect the charge hose from the vacuum pump. Vacuum pump oil If the vacuum pump oil becomes dirty or depleted, replenish as needed.

64

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

11.2.6. Gas charging


(After Evacuation)

Procedure: 1. Connect the charge hose to the charging cylinder. Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder. 2. Purge the air from the charge hose. Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be careful of the liquid refrigerant). 3. Open the valve (Low side) on the charge set and charge the system with liquid refrigerant. If the system cannot be charged with the specified amount of refrigerant, it can be charged with a little at a time (approximately 150 g each time) while operating the air conditioner in the cooling cycle; however, one time is not sufficient, wait approximately 1 minute and then repeat the procedure. (pumping down-pin) 4. Immediately disconnect the charge hose from the 3way valves service port. Stopping partway will allow the refrigerant to be discharged. If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air conditioner before disconnecting the hose. 5. Mount the valve stem caps and the service port cap. Use torque wrench to tighten the service port cap to a torque of 18 N.m. Be sure to check for gas leakage.
This is different from previous procedures. Because you are charging with liquid refrigerant from the gas side, absolutely do no attempt to charge with large amount of liquid refrigerant while operating the air conditioner.

65

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

12 Servicing Information
Caution:
Pb free solder has a higher melting point than standard solder; Typically the melting point is 50 - 70F (30 - 40C) higher. Please use a high temperature soldering iron. In case of the soldering iron with temperature control, please set it to 700 20F (370 10C). Pb free solder will tend to splash when heated too high (about 1100 F/600C).

12.1. Indoor Electronic Controllers Removal Procedures


1. The Electronic Controller, a Signal Receiver and an Indicator (Fig. 3) can be seen by the below steps: Open the Intake Grille and remove the screw at the front of the Front Grille. (Fig. 1). Remove the 3 caps and 3 screws at the bottom of the Front Grille. (Fig. 1) Remove the Front Grille by releasing the 3 hooks at the top of the Front Grille. (Fig. 1)
Fig. 1

Unhook the tabs at the Control Board to remove the Control Board Cover. (Fig. 2)

Fig. 2

2. To remove the Electronic Controllers: Release the 2 Particular Piece. (Fig. 3) Release the CN-REC/DISP connectors. (Fig. 4) Release the CN-TH connector. (Fig. 4) Release the CN-MAIN connector. (Fig. 4) Release the CN-001 connector. (Fig. 4) Release the CN-002 connector. (Fig. 4) Release the CN-STM1 connector. (Fig. 4) Release the CN-STM2 connector. (Fig. 4) Release the CN-ION connector. (Fig. 4) Release the hooks that hold the Electronic Controller. (Fig. 3)
Fig. 3

Fig. 4

66

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

12.2. Cross Flow Fan Indoor and Fan Motor Removal Procedures
1. In order to remove the Cross Flow Fan and Indoor Fan Motor, Control Board need to be taken out by releasing all the connectors as indicated below. a. Release the Earth Wire screw. (Fig. 5) b. Release the Intake Air Sensor. (Fig. 5) c. Release the Piping Sensor. (Fig. 5) d. Release the CN-REC/DISP connectors. (Fig. 5) e. Release the CN-STM1 connector. (Fig. 5) f. Release the CN-ION connector. (Fig. 5)

Fig. 5

2. Pull out the Drain Hose from outlet to remove the Discharge Grille. (Fig. 6)

Fig. 6

3. Removing the right and left screws. (Fig. 7) 4. By pressing down the hook at the left and pushing up the hook at the right, you will be able to remove the Control Board. (Fig. 7)

Fig. 7

5. Remove the screw at the Cross Flow Fan. (Fig. 8)

Fig. 8

67

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

6. Remove the Bearing. (Fig. 9) 7. Remove the screws at the left of the Evaporator. (Fig. 9)

Fig. 9

8. Push up the Evaporator and pull out the Cross Flow Fan from shaft. By then, Fan Motor can be taken out. (Fig. 10).

REMINDER - To reinstall the Fan Motor, put it back in place, adjust the position of the Fan Motors leadwire appropriately as shown in the Fig. 8 before installing the Cross Flow Fan.
Fig. 10

68

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

Remote Control Reset When the batteries are inserted for the first time, or the batteries are replaced, all the indications will blink and the remote control might not work. If this happen, remove the cover of the remote control and you will find a resetting terminal, and by shorting it with a minus screwdriver, it will return to normal.

Changing the wireless remote control transmission code When two indoor units are installed in the same room, in order to prevent operating errors caused by using two remote controls, cut a jumper wire at the remote control printed circuit board (J - A) and cut a jumper wire at the indoor printed circuit board (JX4). It is possible to select from 4 types of transmission codes including one at time of delivery condition (0).

69

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

13 Troubleshooting Guide
13.1. Refrigeration cycle system
In order to diagnose malfunctions, make sure that there are no electrical problems before inspecting the refrigeration cycle. Such problems include insufficient insulation, problem with the power source, malfunction of a compressor and a fan. The normal outlet air temperature and pressure of the refrigeration cycle depends on various conditions, the standard values for them are shown in the table on the right.

70

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

13.1.1. Relationship between the condition of the air conditioner and pressure and electric current
Cooling Mode Condition of the air conditoner Low Pressure High Pressure Electric current during operation Low Pressure Heating Mode High Pressure Electric current during operation

Insufficient refrigerant (gas leakage)

Clogged capillary tube or Strainer

Short circuit in the indoor unit

Heat radiation deficiency of the outdoor unit

Inefficient compression

Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.

13.1.2. Diagnosis methods of a malfunction of a compressor and 4-way valve


Nature of fault Symptom

Electric current during operation becomes approximately 20% lower than the normal value. Insufficient compressing of a compressor The discharge tube of the compressor becomes abnormally hot (normally 70 to 90C). The difference between high pressure and low pressure becomes almost zero.

Electric current reaches a high level abnormally, and the value exceeds the limit of an ammeter. In some cases, a breaker turns off. Locked compressor The compressor is a humming sound.

Electric current during operation becomes approximately 80% lower than the normal value. Insufficient switches of the 4-way valve The temperature different between from the discharge tube to the 4-way valve and from suction tube to the 4-way valve becomes almost zero.

71

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

14 Technical Data

72

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

230V Indoor wet bulb temp. 17.0C 19.0C 19.5C 22.0C 220V Indoor wet bulb temp. 17.0C 19.0C 19.5C 22.0C

Outdoor Temp. (C) TC 5.26 5.77 6.29 30 SHC 3.99 4.17 4.33 IP 1.61 1.64 1.67 TC 4.91 5.30 5.40 5.88 35 SHC 3.82 4.01 4.16 IP 1.73 1.76 1.77 1.80 TC 4.57 5.02 5.47 40 SHC 3.67 3.86 4.01 IP 1.86 1.89 1.92 TC 4.16 4.56 4.97 46 SHC 3.49 3.67 3.83 IP 2.00 2.04 2.08

Outdoor Temp. (C) TC 5.26 5.77 6.29 30 SHC 3.99 4.17 4.33 IP 1.58 1.60 1.63 TC 4.91 5.30 5.40 5.88 35 SHC 3.82 4.01 4.16 IP 1.69 1.72 1.73 1.76 TC 4.57 5.02 5.47 40 SHC 3.67 3.86 4.01 IP 1.81 1.85 1.88 TC 4.16 4.56 4.97 46 SHC 3.49 3.67 3.83 IP 1.96 1.99 2.03

230V Indoor wet bulb temp. 17.0C 19.0C 19.5C 22.0C 220V Indoor wet bulb temp. 17.0C 19.0C 19.5C 22.0C

Outdoor Temp. (C) TC 6.97 7.66 8.34 30 SHC 5.29 5.54 5.74 IP 2.21 2.25 2.29 TC 6.52 7.03 7.16 7.80 35 SHC 5.07 5.32 5.52 IP 2.37 2.41 2.42 2.46 TC 6.06 6.66 7.25 40 SHC 4.87 5.12 5.33 IP 2.54 2.59 2.63 TC 5.51 6.05 6.59 46 SHC 4.63 4.87 5.08 IP 2.74 2.79 2.84

Outdoor Temp. (C) TC 6.97 7.66 8.34 30 SHC 5.29 5.54 5.74 IP 2.15 2.19 2.23 TC 6.52 7.03 7.16 7.80 35 SHC 5.07 5.32 5.52 IP 2.31 2.35 2.36 2.40 TC 6.06 6.66 7.25 40 SHC 4.87 5.12 5.33 IP 2.48 2.52 2.57 TC 5.51 6.05 6.59 46 SHC 4.63 4.87 5.08 IP 2.67 2.72 2.77

73

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

74

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

75

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

15 Exploded View

Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.

76

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

16 Replacement Parts List


<Model: CS-A18CKE / CS-A24CKE>
REF. NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 PART NAME & DESCRIPTION CHASSY COMPLETE FAN MOTOR CROSS FLOW FAN COMPLETE SCREW - CROSS FLOW FAN BEARING ASSY EVAPORATOR FLARE NUT FLARE NUT INTAKE AIR SENSOR HOLDER DISCHARGE GRILLE COMPLETE VERTICAL VANE CONNECTING BAR AIR SWING MOTOR LEAD WIRE - AIR SWING MOTOR AIR SWING MOTOR LEAD WIRE - AIR SWING MOTOR HORIZONTAL VANE CAP - DRAIN TRAY PARTICULAR PIECE CONTROL BOARD TERMINAL BOARD COMPLETE POWER SUPPLY CORD ELECTRONIC CONTROLLER - MAIN ELECTRONIC CONTROLLER - POWER P.C.B. RECEIVER ELECTRONIC CONTROLLER - INDICATOR LEAD WIRE - INDICATOR INDICATOR HOLDER SENSOR COMPLETE CONTROL BOARD TOP COVER CONTROL BOARD FRONT COVER REMOTE CONTROL COMPLETE FRONT GRILLE COMPLETE INTAKE GRILLE GRILLE DOOR CONTROL PANEL DECORATION BASE (R) DECORATION BASE (L) AIR FILTER SCREW - FRONT GRILLE CAP - FRONT GRILLE DRAIN HOSE AIR PURIFYING FILTER TRIPLE DEODORIZING FILTER BAG COMPLETE - INSTALLATION SCREW INSTALLATION PLATE FULCRUM ELECTRONIC CONTROLLER - IONIZER CASING - IONIZER ION - GENERATOR QTY. 1 1 1 1 1 1 1 1 1 1 15 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 4 3 1 1 1 1 1 2 1 1 1 CS-A18CKE CWD50C1293 CWA981056 CWH02C1010 CWH4580304 CWH64K007 CWB30C1391 CWT25078 (1/4) CWT25007 (1/2) CWH32142 CWE20C2254 CWE241088 CWE261025 CWA98260 CWA67C3731 CWA981041 CWA67C3731 CWE241136 CWH52C1001 CWD932162 CWH102103 CWA28C2095 CWA20C2348 CWA743140 CWA743348 CWA742724 CWE39C1089 CWA67C4947 CWD932163 CWA50C2122 CWH131091 CWH131090 CWA75C2424 CWE11C2967 CWE22C1105 CWE141033 CWE312274 CWE351067 CWE351068 CWD001049 XTT4+16C CWH521062 CWH851044 CWMD00C0001 CWMD00C0004 CWH82C067 CWH36K1007 CWH621013 CWA743099 CWD932228 CWH94C0001 CS-A24CKE CWD50C1343 CWB30C1406 CWT25004 (5/8) CWA28C2096 CWA20C2349 CWA743138 CWE11C2842 REMARKS 0

0 0

0 0 0 0

0 0

(Note) All parts are supplied from MAICO, Malaysia (Vendor Code: 061). 0 marked parts are recommended to be kept in stock.

77

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

17 Exploded View

Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.

78

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

18 Replacement Parts List


<Model: CU-A18CKE / CU-A24CKE>
REF. NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 39 40 41 42 43 44 PART NAME & DESCRIPTION CHASSY ASSY COMPRESSOR ANTI - VIBRATION BUSHING NUT - COMPRESSOR MOUNT CONDENSER SOUND PROOF BOARD FAN MOTOR BRACKET SCREW - FAN MOTOR BRACKET FAN MOTOR SCREW - FAN MOTOR MOUNT PROPELLER FAN ASSY NUT - PROPELLER FAN HOLDER COUPLING ASSY 2-WAY VALVE (LIQUID) TUBE ASSY (CAPILLARY TUBE & CHECK VALVE) 3-WAY VALVE (GAS) TERMINAL COVER NUT - TERMINAL COVER CONTROL BOARD CAPACITOR - FAN MOTOR CAPACITOR - COMPRESSOR HOLDER CAPACITOR TERMINAL BOARD ASSY CABINET SIDE PLATE HANDLE CABINET SIDE PLATE HANDLE CABINET FRONT PLATE WIRE NET CABINET TOP PLATE CONTROL BOARD COVER CONTROL BOARD COVER OPERATION INSTRUCTIONS INSTALLATION INSTRUCTIONS ELECTRONIC CONTROLLER 4-WAY VALVE ASSY V-COIL COMPLETE SOUND PROOF MATERIAL STRAINER SENSOR COMPLETE INSTALLATION INSTRUCTION INSTALLATION INSTRUCTION HOLDER SENSOR QTY. 1 1 3 3 1 1 1 2 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 CU-A18CKE CWD50K2087 2JS324D3AB07 CWH50055 CWH4582065 CWB32C1349 CWH151051 CWD541055 CWH551060 CWA951287 CWH55252 CWH03K1017 CWH561038 CWH351036 CWB021173 CWT01C2933 CWB011212 CWH171012 CWH7080300 CWH102206 DS441355NPQA CWA312079 CWH30060 CWA28K1021 CWE041082A CWE161010 CWE041083A CWE16000E CWE06K1043 CWD041041A CWE03K1009A CWH131168 CWH131169A CWF564159 CWF612455 CWA743367 CWB00K1025 CWA43C2121 CWG302110 CWB11025 CWA50C618 CWF612456 CWF612457 CWH32089 CU-A24CKE 2JS438D3JA02 CWB32C1350 CWT01C2865 CWB011213 CWB00K1026 REMARKS 0

0 0

0 0

(Note) All parts are supplied from MAICO, Malaysia (Vendor Code: 061). 0 marked parts are recommended to be kept in stock.

79

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

19 Electronic Circuit Diagram


CS-A18CKE CU-A18CKE CS-A24CKE CU-A24CKE
SCHEMATIC DIAGRAM 1/5

ELECTRONIC CONTROL UNIT


TEMPERATURE FUSE BLU DEICE (BLU)
BLU

R50 47k

C16 0.01

1 2

PC01

4 3

R52 1.82k

C40 1000p

1 2 3 4
YLW
BLK/BLU

1 2 3 4

C09 10 50V
+

RED

RY-HOT

HOT (RED) C41 1000p

TO OUTDOOR

R51 47k

WHT

BLK/BLU

FUSE (T 2A L 250V)

RY-DEICE

RED

BLU

C13

RY-HOT

ELECTRONIC CONTROLLER

COMP (VLT) AC (WHT) HOT 1 (RED) DEICE (GRY) HOT 2 (BLK)

COMPRESSOR

COIL (4-WAYS VALVE)

GRY

RED

VLT

BLU

WHT

AC01 (WHT) RY-PWR

ZNR2

RY-OFF

SENSOR (AIR TEMP.)

TF 1

CAPACITOR

CN-TH (WHT)

TF 2

RY-H/L

Fig. 4

RED

ORG POWER SUPPLY BRW or YLW

BLU

BLU

FAN MOTOR

CAPACITOR

SENSOR (PIPE TEMP.)

FM2 (ORG)

FM1 (BRW)

1 2 3 4

ZNR4

ZNR3

(XH4) HA Fig. 3
4 3 2 1

C13 0.01

R58 10k R59 1k

BLK

AC02 (BLK) AC03 (WHT) C38 0.01 C39 0.01

WHT

(GRN/YLW)

FG1

(GRN/YLW)

FG2

RECEIVER
R203 1k R202 1k
1 2 3

IC201 1 2 3

(MX-3) CN-RCV

+ C201
22 16V

INDICATOR
Auto SW101 1 POWER(GRN) QUIET(ORG) TIMER(ORG) ION2(GRN) ION1(GRN) POWERFUL(ORG) 2 D101 D102 D103 D105 D104 D106 (PH) CN-DISP
1 2 3 4 5 6 7 10 9 8 7 6 5 4 3 2 1

(KR-10) CN-DISP

80

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

SCHEMATIC DIAGRAM 2/5

TEST

R54 1k R48 10k R55 1k c Q001 b R11 1k e R12 1k R35 5.1k C02 0.01 C01 0.01 R34 10k

BZ BZ01

R10 10k

R18 R19 R20 R21 R22

D05 D06 D07 D08 D09 D10 D11 D12 64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49 R65 1k

R53 1k

R64 6.2k

Q02

R23 R24 R25

b
R63 6.2k

P47/A07

P67

P66

P65

P64

P75

P74

P73

P46/A06

P45/A05

P44/A04

P43/A03

P42/A02

P41/A01

P40/A00

P72

1 2

P71

P50/A8 P51/A9 P52/A10 P53/A11 P54/A12 P55/A13 P56/A14

48

RY-PWR DRIVE SIGNAL

R13 220
3

R14 330
4

STEPPING MOTOR DRIVE SIGNAL BUZZER

AUTO OPERATION TEST RUN REMOTE CONTROL SOUND TIMER SHORTEN POWER CLOCK INPUT REMOTE-CONTROL COMMAND INPUT

P70 47 P03/NTP3 46 P02/NTP2 P01/NTP1


45 44

R15 330
5

DISPLAY

R16 110
6

P00/NTP0 43 Vss1 42 X1 41

R17 330
7

R06 24k

8 P57/A15 9 Vss0 10 VDD0 11 P30 12 P31

IC01 A52D0022GB93

OSC

X2 40 IC 39 XT1 38 XT2 37

C03 + 0.01 1.6V

C22 0.01

R68 10k

13 P32 14 15

P33 P34 P35


P36
17

STEPPING MOTOR DRIVE SIGNAL AUTO RESTART


P22/SCX P20/S1 P21/S0

INTAKE AIR TEMP PIPE TEMP GROUND


P17/AN7 P16/AN6 P15/AN5 P14/AN4

RESET POWER

Reset 36 AVd0 35 AVref


34 33

P13/AN3

P12/AN2

VDD1

P23

P24

P25

18

19

20

21

22

23

24

Vss

R66 1k

R26 1k

16

P11/AN1

P10/ANO

25

26

27

28

29

30

31

32

1 2 3 4 5 6 7

16 15

R08

R028
43 /2W

RY-PWR

14 43 /2W 13 12 11 10 9

1 2 3 RY-HOT 4 5 6 7

8 16 15 14 13 12 11 10 9
5 DI

SK 4 CS 3

R09 10k R57 20k

JX2
6 DO

7 GND Vcc 2 8 RS

IC05 A52A2003GR

IC06 A52A2003GR2

R/B 1

C05 0.1

IC02 A52BR9020F

C04 0.1

R30 20k

R33 15k

C08 0.1

5 4 3 2 1

5 4 3 2 1

4 3 2 1

CN-STM1
5 4 3 2 1 (ZH5)

CN-STM2
5 4 3 2 1 (ZH5)

(PH)

CN-TH

PIPE TEMP. SENSOR (20k 3950) VERTICAL HORIZONTAL

AIR TEMP. SENSOR (15k 3950)

81

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

SCHEMATIC DIAGRAM 3/5

1 2 3 4 5 6 7

CN-MAIN

C17 + 47 25V

C14 0.1

C24 0.01

D01 C25 0.01

C20 + 100 16V R03 100 R02 20k

C11 0.01 R62 1k

R61 10k

22k 22k

R47 510 R29 1k C06 1000p (MB)

C23 0.1

R42 20k

R07 20k

R08 5.1k

C18 R01 0.022 100

R32 150k

X01

4.096 MHz (47pF X 2)

IC04 C3EBDG000021

R49 100k C21 + 2.2 50V


+

C12 0.01

C07 1.00 16V

C28 0.01

R56 24k

CN-ION
JX1 R43 RX1 JX4 R41 24k R37 10k R40 10k 1k 4 3 2 1

JX3

R38 24k C15 0.01

82

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

SCHEMATIC DIAGRAM 4/5


ELECTRONIC CONTROL UNIT

R020 F001 CN001


11 10 9 8 7 6 5 4 3 2 1

R026 L001 C003


R052

T02

D101 R105

R016 R031 R017


G D

R027
4 10

Z001

C002 C004

C005 DB004

R051 + R050

C007 R013 R014

ZD002

Q004

C012 R015
1 8 7

L101 C103 +

R048

ZD003 C010

R025
2

TH001 D007 (XH7-5) CN002 R030 R046

TH002 C009 C008


+

R012 C018 R057 R019 ZD004 R021


3

ZD101

FAN MOTOR

1 2 3 4 5 6 7

R003

L002 R033 R023 R053 C016


b

IC101 I 5V O C016

C015
e

R018 Q005 D006


c b e

Q003 c
b

D045 + C105 D013 C011

R114 1

PC001

ZD005

R008 R024
1

R002 R116
2 4 3

R034 IC001

R054

PC004

PC002

R001 R004
3 2 2 3

R032 C014

R055 C017

D014

R048 ZD006 ZD007

R047

Q006

feedback PC003

R118 R115
c b

R005 D002

Q102 R117

2 e

R006 D003 R007

(PH) CN103
1 2 3 4 5 6 7

R028
e

(PH) CN101
1 2 3 4 5

b c

R029 4

PC005
1

Q002
3 2

R009 ZD001 C066 R011 +


e

R113 Q001 PC006


4 1

10k 4.7k b

R010

c 3 2

R112

HIGH VOLTAGE TRANSFORMER

F1 CH1
4 3 2 1

T01 R2 R3 R6 Q4 b D3 Q5 C3 R4 R3 b 4.7k 10k e R14 C6 D1 c Z02 C9 R10

D101 R101 D102

CN2 HV

VIN GND ERR

R16 Q1 c b Q2 e C2 C1 c b e C3 D1 e R15 C10 c R13 R9 C5 D6 D5 R102 C101

EH-4P

-4.2kV

R12

C7 CN3 GND

D2

Z01

83

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

SCHEMATIC DIAGRAM 5/5

84

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

How to use electronic circuit diagram

TIMER TABLE
Name Real Timer Time 1 hr. 10 min. 1 min. 2 min. 58 sec. 60 sec. 7 min. 4 min. 25 sec. 6 min. 10 min. 40 sec. 70 sec. 20 sec. 180 sec. 40 sec. 360 sec. 5 min. 2 min. 1.6 sec. 15 min. 0 ~ 62 sec. 5 min. 30 sec. 4 min. 2 min. 30 min. 10 sec. 1 hr. 30 min. Test Mode (When test point Short-circuited) 1 min. 10 sec. 1 sec. 0 sec. 0 sec. 42 sec. 0 sec. 0 sec. 36 sec. 60 sec. 4 sec. 7 sec. 2 sec. 18 sec. 4 sec. 36 sec. 30 sec. 0 sec. 0 sec. 15 sec. 0 ~ 6.2 sec. 30 sec. 3 sec. 0 sec. 0 sec. 180 sec. 1 sec. 9 sec. Remarks

Time Delay Safety Control Forced Operation Time Save Control Anti-Freezing Auto Mode Judgement Soft Dry OFF ON Cooling Deodorizing Control Soft Dry Comp. Reverse Rotation Detection Comp./ Fan Motor Delay Timer Powerful Mode Operation Random Auto Restart Control 4 Way Valve After Deice Ended Hotstart Delay Times Hotstart Finish Times Ion OFF Timer Ion ON Timer Quiet operation timer

Soft Dry: 10 min. operation

Comp. ON 5 min. and above

Comp. OFF after deice

85

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

19.1. REMOTE CONTROL

86

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

19.2. PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD

87

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

19.3. PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD

88

CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE

19.4. PRINT PATTERN OUTDOOR UNIT PRINTED CIRCUIT BOARD

89

[MAICO] Printed in Malaysia