Sei sulla pagina 1di 26

YCCD

AIR COOLED
LIQUID CHILLER
AVAILABLE MODELS & NOMINAL COOLING CAPACITIES

TABLE 1

R407C REFRIGERANT
COOLING CAPACITIES
46 kW to 152 kW

Model
Cooling Capacity (kW)
Model

YORK YCCD twin refrigerant circuit air


cooled liquid chillers are a compact design
suitable for chilled water or glycol cooling.
YCCD units are available in three
versions: YCCD (standard); YCCD LN
(low noise operation) and YCCD HT (high
temperature operation). YCCD models 60
- 150 of all three versions are available
with either user friendly standard control or
optional YORK Integrated System
Network (ISN) control. YCCD models 170
- 210 are fitted with YORK ISN control as
standard.
YCCD units are designed to be located
outside on the roof of a building or at
ground level. The units can be converted
into total cooling plants with the field
mounted Hydro Kit option.

CONTENTS
Specification
Accessories and Options
Controls
Operating Limitations
Refrigeration Flow Diagram
Selection Guide
Water Pressure Drops
Cooling Capacities
Glycol Selection Guide
Glycol Cooling Capacities
Sound Power Spectrum
Physical Data
Electrical Data

Cooling Capacity (kW)


Model
Cooling Capacity (kW)

60
46.2

75
53.0

90
62.9

YCCD (Standard)
105
120
150
170
190
210
72.6 88.2 100.5 122.2 135.3 148.6

60
47.9

75
53.4

90
64.3

YCCD LN (Low Noise)


105
120
150
170
190
210
70.1 89.8 102.3 118.9 135.6 143.5

60
49.6

75
57.1

YCCD HT (High Temperature)


90
105
120
150
170
190
210
67.8 77.6 95.6 109.0 124.0 142.9 151.7

Cooling capacities at 7C leaving chilled liquid temperature and 35C condenser


air entering temperature.

FEATURES

BENEFITS

Two refrigerant circuits.

System stand-by security.

Minimum base area/maximum capacity.

Minimum installation space.

Low weight , single power and control supplies.

Easy to install.

Full factory run test.

Operating quality control.

Accessible components.

Ideal for maintenance operations

Residual current circuit breaker.

Operator safety.

Microprocessor control with visual display of temperatures


and alarms.

Simple operation.

Manufactured to ISO 9001/EN 29001.

High standard of quality control.

SPECIFICATION
The chillers shall be completely factory assembled with all interconnecting
refrigerant piping and wiring ready for field installation. After assembly the YCCD
shall have a full test run with water flowing through the evaporator. The YCCD shall
be pressure tested, evacuated and fully charged with refrigerant and include an
initial oil charge.
YCCD LN (Low Noise Version)
Very low noise levels are achieved on YCCD LN units without any impact on unit
performance or operating limits. The noise reduction is obtained using greater
surface area condenser coils and special fan configuration. In addition, on models
60 - 150, the compressor compartment is completely acoustically insulated. Mufflers
are mounted on the compressor discharge lines of all models and each compressor
is also separately enclosed in an acoustic sound blanket.
YCCD HT (High Temperature Version)
YCCD HT units are suitable for operation at higher ambient temperatures. The
higher ambient limit is obtained using greater surface area condenser coils and high
efficiency fans.

Electrical Connections
Dimensions
Space Requirements
Page G.1
Doc. No. PC150/01.04/GB

The unit structure shall be of heavy gauge galvanised steel


fastened with stainless steel screws and bolts. Galvanised steel
parts shall be painted with baked-on powder paint (Desert Sand
(RAL1019)). The unit base is riveted and all internal sheet metal
panels are not painted (60 to 150 only).
Compressors
YCCD models 60-75-120-150 shall have two hermetic
reciprocating compressors with internal motor protection
housed in a separate acoustically lined enclosure.
YCCD models
compressors.

90-105-170-190-210

shall

have

scroll

Compressors on all models shall be mounted on rubber


anti-vibration pads and have direct on line starting.
The compressor motors shall be refrigerant gas cooled, with
integral thermistor protection against overloads. The overload
protection is automatically reset after approximately 8 seconds.
The motor terminal boxes shall have IP-54 weather protection.
The compressors shall be switched On and Off by the unit
microprocessor to provide capacity control.
Evaporator
The evaporator shall be a stainless steel plate type heat
exchangers thermally insulated with flexible closed cell material.
Design working pressure shall be 10 bar g on the water side and
30 bar g on the refrigerant side. An electric heater mat and
evaporator differential pressure switch shall be provided for
freeze protection.
Water connection to the evaporator is via 2 inch gas
connections. A bleed valve is provided on the evaporator
pipework.
Refrigerant Circuits
Two refrigerant circuits shall be provided and each circuit shall
include: service valves for refrigerant charging, discharge and
liquid line isolating valves, a sight glass with moisture indicator, a
filter dryer and a thermostatic expansion valve.

On models 60 - 150 high and low pressure switches shall also be


provided.
On models 170 - 210 transducers and switches shall be included
on the high pressure circuits and transducers shall be provided
on the low pressure circuits.
Air Cooled Condensers
The condenser coils shall be seamless copper tubes, arranged
in staggered rows, mechanically expanded into corrugated
aluminium fins. Design working pressure of the coils shall be
28 bar g.
All YCCD models shall have a stepless fan speed controller
fitted as standard. When standard control is fitted, the controller
operates on the basis of ambient air temperature allowing
operation down to -5C ambient air temperature. When ISN
control is fitted, the controller operates on the basis of
condensing pressure with operation possible down to -18C
ambient air temperature.
The condenser fans shall be direct drive with aluminium aerofoil
blades. Each fan will have a painted galvanised steel protection
guard. The totally enclosed fan motors shall have IP-54 weather
protection and thermocontact protection embedded in their
windings.
Power and Control Panel
All controls and motor starting equipment necessary for full unit
operation shall be factory wired and tested.
Power and control components are accessed via individual
doors on YCCD models 60 to150.
The control compartment shall contain an electronic circuit
board and a soft touch key control panel with display of
operating functions, alarms and stops.
The power compartment shall have a door interlocked isolator
and shall contain compressor and fan contactors, fuses and
supply protection.

ACCESSORIES AND OPTIONS


Integrated System Network (ISN) Control
A YORK Integrated System Network (ISN) control is fitted as standard
on YCCD models 170 - 210 and is available as an option on models 60 150. The ISN control offers Building Management System (BMS)
communication, leaving chilled liquid temperature or entering chilled
liquid temperature control, sequence control, double setpoint, display
and print of unit operational and history data alarm history.

ISN Control - EMS Offset Card (Temperature Reset/Offset)


Additional PCB allowing alternative signals to be used from customer
EMS to unit controls to perform remote liquid leaving temperature
setpoint reset/offset function. Suitable for water and glycol control
ranges (cannot be fitted when a sequence control is fitted).

ISN Control - Sequence and Automatic Lead/Lag Control

The Hydro Kit is fully enclosed and comprises: a buffer tank, pump(s),
expansion tank(s), filter, pressure gauge, shut-off valves, safety valve,
automatic vent valve, drain valve, charge valve, safety valve for system
discharge and electrical panel (if selected, optional water filter is not
available).

Flow Switch
Supplied loose for field installation by contractor.

Water filter
A field mounted water filter for fitting in the customers water circuit (not
available if Hydro Kit is selected).

Anti-vibration Mounts
Open spring isolator mounts with fixing down holes, for field installation.

Sequencing control centre to manage sequencing control of up to eight


units in parallel based on mixed liquid temperature, interconnecting
wiring by others (cannot be fitted when an EMS offset card is fitted).

High Pressure Fans (only available on Standard Units with


ISN Control)

Remote On/Off Kit (YCCD 60 - 150 Standard Control only)

Condenser Coil Protection

The kit allows remote activation of the cooling mode when the YCCD unit
is in stand-by.

Copper Fin Condenser Coils - Condenser coils are constructed with


copper fins (ASTM 287 Test, after 1500 hours 17% weight loss).

The kit contains a remote control with 3 metre cable for wall mounting,
additional PCB for LED control and full installation instructions.

Gold Epoxy Coated Aluminium Condenser Fins - Offers corrosion


resistance in mild seashore locations (Acetic acid spray test ASTM, after
1500 hours 7% weight loss).

Hydro Kit
The field installed YORK Hydro Kit is a hydraulic package complete with
all components required for the correct operation of a liquid distribution
circuit. The Hydro Kit can be combined directly on YCCD models 60 150 or remotely on all models.

Page G.2
Doc. No. PC150/01.04/GB

Alternative fans suitable for external static pressures up to 80 Pa.

Condenser Coil Guards


Painted galvanised steel wire guards mounted on the unit exterior.

Gauge Kit (YCCD 60 - 150 Standard Control only)


Factory fitted mechanical dial gauges for suction and discharge
pressure indication of each refrigerant circuit.

STANDARD CONTROL (YCCD 60 - 150 only)


1

Setpoints

Display

+
SET

IN

OUT

Circuit 1

System

-P

H20

16
P

-P

17

H20

Circuit 2

18

15
14
13
Standard Control Panel
1
2
3
4
5
6
7
8
9

12

11

10

7
Remote On/Off Panel (Optional)

Setpoint selection and display key and LED


Setpoint change key (-). Decreases desired water temperature.
Setpoint change key (+). Increases desired water temperature.
Display
Inlet water display and LED.
Outlet water display and LED.
Start key and LED - Cooling.
Not used.
Voltage ON LED.

10
11
12
13
14
15
16
17
18

External interlock alarm LED.


Antifreeze alarm.
Low pressure alarm LED.
High pressure alarm LED.
Compressor ON LED.
Start-up key and LED.
Voltage ON LED.
Unit alarm activated LED.
Start key and LED - Cooling.

ISN CONTROL (Standard YCCD 170 - 210, optional YCCD 60 - 150)

Millennium Control Center


TM

STATUS

Display/Print

SYS
SYS

1
2

Entry

COMP RUNNI NG
COMP RUNNI NG

Setpoints

OPER DATA

COOLING
SETPOINTS

PRINT

SCHEDULE/
ADVANCE DAY

HISTORY

ENTER
/ADV

ON

Unit
OPTIONS

Display/Print Keys for display of:


Chilled liquid and ambient air temperatures
System pressures (each circuit)
Operating hours and starts (each compressor)
Load and unload timers and cooling demand
Liquid pump, evaporator heater and condenser fan status

Print calls up to the liquid crystal display:

Operating data for the systems


History of fault shutdown data for up to the last six fault

CLOCK

PROGRAM

OFF

shutdown conditions
An RS-232 port, in conjunction with this press-to-print button, is
provided to allow hard copy print-outs via a separate printer.
Entry Keys

To program and modify system values


ISN Millennium Control Center Panel

Setpoints Keys for programming:


Chilled liquid temperature setpoint and range
Remote reset temperature range
Set daily schedule/holiday for start/stop
Manual override for servicing
Cut-outs for low ambient temperature, low liquid temperature,
high discharge pressure and low suction pressure
Number of compressors and anti-recycle timer (compressor
start cycle time)

The panel shall contain:

A 40 character Liquid Crystal Display (LCD) with Light

Emitting Diode (LED) back lighting for outdoor viewing.

A Colour coded 12-button keypad.


Customer terminal block for control inputs and liquid flow
switch.
The microprocessor control will include:
Status Key for display of:
Status of the unit and each refrigerant circuit
System and unit safety fault messages

Unit Keys

To set time and unit options


Unit ON/OFF switch

To activate or deactivate the unit

Page G.3
Doc. No. PC150/01.04/GB

The microprocessor control system is capable of displaying the


following:

Compressor starts & operating hours (each compressor)


Status of evaporator heater and fan operation
Run permissive status
Number of compressors running
Load & unload timer status
Water pump status
Liquid Temperature Reset via a YORK ISN DDC or Building
Automation System (by others)
Provision shall be included for optional remote chilled liquid
temperature reset.

Return and leaving liquid temperature


Low leaving liquid temperature cutout setting
Low ambient temperature cutout setting
Ambient air temperature
Metric or Imperial data
Discharge and suction pressure cutout settings
System suction pressures
System discharge pressures
Anti-recycle timer status
Anti-coincident system start timer condition
Compressor run status
No cooling load condition
Day, date and time
Daily start/stop times
Holiday status
Automatic or manual system lead/lag control
Lead system definition

The operating program will be stored in non-volatile memory


(EPROM) to eliminate chiller failure due to AC power
failure/battery discharge. Programmed setpoints shall be
retained in lithium battery backed RTC memory.

OPERATING LIMITATIONS

TABLE 2

60

YCCD
Chilled
Liquid

Liquid outlet
temperature

Water outlet
Brine outlet
Temperature spread

Flow rate (1)


Pressure drop (1)
Maximum operating pressure
Ambient Air entering
Standard control
Air
temperature
ISN control
External static
Standard fans
pressure
High pressure fans (4)
Recommended system chilled water volume (2)
Minimum capacity step
Power supply voltage (5)

C
C
K
l/s
kPa
bar
C
C
Pa
Pa
l
%
V

Liquid outlet
temperature

Water outlet
Brine outlet
Temperature spread

Max.

1.38
8.4

3.68
54.6

420

C
C
K
l/s
kPa
bar
C
C
Pa
Pa
l
%
V

90
Max. Min. Max.
+6 to +15
-8 to +15
3 to 8
1.58 4.22 1.79 4.77
9.5
62.6
8.9
58.4
10 (6 bar with Hydro Kit)
-5 to + see note (3)
-18 to + see note (3)
0
80
Min.

480

510

2.13
9.9

5.67
65.8

560

210
170
190
Min. Max. Min. Max. Min. Max.
+6 to +15
-8 to +15
3 to 8
2.63 7.02 3.00 8.00 3.64 9.69 4.00 10.67 4.45 11.86
7.9
72.0 19.9 155.4 14.8 105.8 16.1 114.1 19.9 141.7
10 (6 bar with Hydro Kit)
-5 to + see note (3)
Not available
-18 to + see note (3)
-18 to + see note (3)
0
80
800
915
550
475
575
50%
20%
25%
25%
400 V, 3 , 50 Hz (nominal)
150
Min. Max.

Flow rate (1)


Pressure drop (1)
Maximum operating pressure
Ambient Air entering
Standard control
Air
temperature
ISN control
External static
Standard fans
pressure
High pressure fans (4)
Recommended system chilled water volume (2)
Minimum capacity step
Power supply voltage (5)
(1) Total unit flow rate and pressure drop are given
Caution: Minimum flow rates may only be used with brine solutions after reprogramming unit parameters.
(2) Table shows minimum water / brine volume of system
(3) Maximum ambient air temperature depends on coding:
Standard/Low Noise Units: 43C
High Temperature units: 45C
(4) Optional high pressure fans only available on standard YCCD units with ISN control
(5) Voltage 400V +/- 10%

Page G.4
Doc. No. PC150/01.04/GB

105
Min. Max.

50%
400 V, 3 , 50 Hz (nominal)
120
Min. Max.

YCCD
Chilled
Liquid

75

Min.

REFRIGERANT FLOW DIAGRAM


YCCD Models 60 -150

FIGURE 1

YCCD Models 170 -210

Note: Only one refrigerant circuit shown.


YCCD Cooling Mode
Low pressure liquid refrigerant enters the cooler (Evaporator) and is evaporated and superheated by the heat energy absorbed from
the chilled water passing through the cooler plates. Low pressure vapour enters the compressor where pressure and superheat are
increased. Heat is rejected via the air cooled condenser coil and fans. The fully condensed and subcooled liquid refrigerant then
enters the expansion valve where pressure reduction and further cooling takes place before returning to the cooler.

SELECTION GUIDE
DATA REQUIRED
To select a YORK YCCD chiller the following information is
required:
1.
2.
3.
4.

Required cooling capacity.


Design chilled liquid entering and leaving temperatures.
Design chilled liquid flow rate.
Design condenser entering air temperature. This will normally
be the design summer ambient air temperature unless
location or other factors have an influence.
5. Altitude above sea level.
6. Design Cooler fouling factor.
Note: Items 1, 2 and 3 must be linked by the following formulae:
Cooling capacity (kW) = Flow Rate (l/h) x Range (C)
860
Where:
Range = Entering chilled liquid temperature - leaving chilled
liquid temperature.
YCCD SAMPLE SELECTION
A R407C chiller is required to cool water from 13C to 7C
having a cooling capacity of 60 kW.
Other design conditions applying are:
Ambient air entering condenser:
Fouling factor:
Altitude:

35C
0.044 m C/kW
Sea level

FOULING FACTOR
Fouling Factor m C/kW
0.044
0.088
0.176
0.352

TABLE 3
COOLER
Capacity Factor
1.000
0.987
0.964
0.926

ALTITUDE FACTORS
Altitude (m)
0
600
1200
1800
2400

Capacity Factor
1.000
0.987
0.973
0.958
0.943

Comp. Input Factor


1.000
0.995
0.985
0.962

TABLE 4
Comp. Input Factor
1.000
1.010
1.020
1.029
1.038

From a cursory examination of capacity Table 5 a model YCCD


90 gives approximately the required capacity of 60.0 kW.
No correction factors, for fouling factor or altitude, apply
therefore the conditions will be as follows:
Cooling capacity:
Total unit input power:
Water temperature:
Water flow rate

60.0 kW
26.3 kW
13 C to 7 C
= 2.38 l/s
60.0
4.187 x 6
Cooler pressure drop = 16 kPa (see Figure 2).

PRESSURE DROP CALCULATIONS


Model
60
75
90
105
120
150
170
190
210

Pressure Drop Calculation


Pressure Drop [kPa] = 4.5429 x (Flow Rate [l/s]1.9084)
Pressure Drop [kPa] = 3.9487 x (Flow Rate [l/s]1.9192)
Pressure Drop [kPa] = 2.9111 x (Flow Rate [l/s]1.9194)
Pressure Drop [kPa] = 2.2928 x (Flow Rate [l/s]1.9346)
Pressure Drop [kPa] = 0.8962 x (Flow Rate [l/s]2.2508)
Pressure Drop [kPa] = 1.9910 x (Flow Rate [l/s]2.0955)
Pressure Drop [kPa] = 1.1043 x (Flow Rate [l/s]2.0089)
Pressure Drop [kPa] = 1.0120 x (Flow Rate [l/s]1.9959)
Pressure Drop [kPa] = 1.0012 x (Flow Rate [l/s]2.0025)

Item
Pressure Drop Calculation
1.9334
2"/50 mm strainer Pressure Drop [kPa] = 1.0568 x Flow Rate [l/s]

Notes:
The optional strainer limits the unit maximum flow rate to
10.4 litres per second.
The pressure drops given are for the strainer component only.
They do not include the pressure drop of any other piping or
fittings required to mount the strainer. The strainer is to be
installed by others.
For glycol operation, the pressure drop correction factors for
either ethylene or propylene glycol solutions need to be applied
as shown in the pressure drop correction graphs.

Page G.5
Doc. No. PC150/01.04/GB

YCCD WATER PRESSURE DROPS


YCCD MODELS 60 TO 210

FIGURE 2
160
140

150

210
190

120
170

100
90
80
70

120
75

PRESSURE DROP (kPa)

60

105

90

60

50
40
30

20

210
190

10

7
1

10 11 12

FLOW RATE (l/s)

YCCD MODELS 60 TO 210 WITH OPTIONAL STRAINER FITTED

FIGURE 2A
220
200
180
160
140

150
170

120

120
100
90
80
70

105
90

75
60

60

PRESSURE DROP (kPa)

210
190

50
40
210

30

190

20

10

7
1

FLOW RATE (l/s)

Page G.6
Doc. No. PC150/01.04/GB

10 11 12

YCCD COOLING CAPACITIES (Standard Units)

Model

YCCD 60

YCCD 75

YCCD 90

YCCD 105

YCCD 120

YCCD 150

YCCD 170

YCCD 190

YCCD 210

25
LCLT
C
6
7
8
10
12
15
6
7
8
10
12
15
6
7
8
10
12
15
6
7
8
10
12
15
6
7
8
10
12
15
6
7
8
10
12
15
6
7
8
10
12
15
6
7
8
10
12
15
6
7
8
10
12
15

0.0

Condenser Entering Air Temperature C


32
35

30

TABLE 5

40

43

Cool

Power

Cool

Power

Cool

Power

Cool

Power

Cool

Power

Cool

Power

kW
53.4
55.3
57.3
61.1
64.7
70.5
61.2
63.4
65.7
70.1
74.2
80.8
66.8
68.8
70.7
74.7
78.8
85.1
75.7
77.9
79.9
83.7
87.6
93.4
101.9
105.5
109.3
116.6
123.4
134.4
116.1
120.3
124.6
132.8
140.6
153.1
133.1
137.2
140.1
145.7
151.1
158.8
146.6
151.0
155.1
163.3
171.7
184.2
162.0
167.1
170.2
176.7
183.0
191.9

kW
18.5
18.9
19.2
19.8
20.3
21.4
21.6
22.0
22.4
23.2
23.7
25.0
21.6
21.9
22.2
22.9
23.6
24.6
25.2
25.4
26.0
27.2
28.4
30.3
35.6
36.3
37.0
38.2
39.2
41.2
43.7
44.6
45.5
46.9
48.1
50.6
41.7
42.1
43.0
44.7
46.5
49.3
48.5
49.2
50.3
52.5
54.9
58.7
50.4
51.1
52.2
54.5
56.8
60.7

kW
48.9
50.9
52.7
56.4
59.9
65.4
56.1
58.3
60.4
64.7
68.7
75.0
64.1
66.0
67.9
71.8
75.6
81.6
73.3
75.3
77.3
81.1
84.9
90.5
93.3
97.0
100.5
107.6
114.2
124.8
106.3
110.5
114.6
122.6
130.2
142.2
126.0
129.9
132.9
137.9
143.1
150.4
139.0
143.4
147.2
155.1
162.9
174.9
153.3
158.0
161.1
167.2
173.2
181.8

kW
19.0
19.4
19.8
20.4
21.0
22.1
22.2
22.6
23.1
23.8
24.5
25.8
23.5
23.8
24.1
24.8
25.5
26.7
27.5
27.8
28.4
29.6
30.9
33.0
36.6
37.3
38.1
39.4
40.5
42.6
45.0
45.9
46.8
48.3
49.7
52.3
45.5
46.0
47.1
48.8
50.6
53.6
52.8
53.4
54.6
56.9
59.4
63.3
54.9
55.6
56.7
59.2
61.7
65.6

kW
47.1
49.0
50.9
54.5
57.9
63.4
54.0
56.2
58.3
62.5
66.4
72.7
62.9
64.7
66.6
70.4
74.2
80.1
72.2
74.2
76.1
79.9
83.6
89.1
89.9
93.4
97.0
103.9
110.5
121.0
102.4
106.5
110.5
118.4
125.9
137.8
123.0
126.8
129.5
134.7
139.7
147.0
135.9
140.1
143.9
151.6
159.3
171.0
149.7
154.3
157.4
163.5
169.1
177.5

kW
19.2
19.5
19.9
20.6
21.5
22.5
22.4
22.8
23.3
24.1
25.1
26.3
24.3
24.6
24.9
25.6
26.4
27.5
28.5
28.8
29.4
30.7
32.0
34.1
36.9
37.7
38.4
39.7
41.4
43.4
45.4
46.3
47.2
48.8
50.8
53.3
47.2
47.6
48.5
50.4
52.4
55.5
54.6
55.2
56.4
58.8
61.4
65.3
56.8
57.4
58.7
61.1
63.7
67.7

kW
44.4
46.2
48.1
51.6
55.0
60.4
50.9
53.0
55.1
59.2
63.1
69.2
61.1
62.9
64.7
68.4
72.2
77.9
70.5
72.6
74.4
78.0
81.6
87.1
84.6
88.2
91.6
98.4
104.9
115.1
96.5
100.5
104.4
112.2
119.5
131.2
118.4
122.2
124.7
129.8
134.7
141.7
131.2
135.3
139.0
146.4
153.8
165.2
144.2
148.6
151.6
157.5
163.1
171.2

kW
19.4
19.8
20.1
20.8
21.5
22.6
22.6
23.1
23.5
24.3
25.1
26.4
25.5
25.8
26.2
26.9
27.6
28.8
30.0
30.3
30.9
32.2
33.6
35.8
37.4
38.1
38.8
40.1
41.4
43.5
45.9
46.8
47.7
49.3
50.8
53.5
49.7
50.2
51.1
53.2
55.2
58.4
57.3
57.9
59.2
61.7
64.2
68.3
59.7
60.4
61.7
64.2
66.8
71.0

kW
39.8
41.5
43.3
46.8
50.0
55.2
45.6
47.6
49.6
53.6
57.3
0.0
54.6
56.2
57.8
61.2
64.5
0.0
64.8
66.6
68.3
71.6
75.0
0.0
75.8
79.2
82.6
89.2
0.0
0.0
86.4
90.2
94.1
101.6
0.0
0.0
108.5
112.0
114.4
119.0
123.5
130.2
120.3
124.0
127.4
134.2
141.1
151.5
132.2
136.3
139.1
144.4
149.7
157.1

kW
19.7
20.0
20.4
21.1
21.8
22.8
23.0
23.4
23.8
24.6
25.2
0.0
27.7
28.0
28.3
29.1
29.8
0.0
32.6
33.0
33.7
35.0
36.5
0.0
38.0
38.6
39.3
40.6
0.0
0.0
46.6
47.5
48.2
49.9
0.0
0.0
54.6
55.1
56.1
58.2
60.4
63.9
62.2
62.8
64.0
66.6
69.3
73.5
65.3
66.0
67.4
70.1
72.9
77.4

kW
37.1
38.9
40.6
44.0
47.1
0.0
42.5
44.6
46.5
50.4
0.0
0.0
50.8
52.3
53.9
0.0
0.0
0.0
61.3
63.0
64.6
0.0
0.0
0.0
70.7
74.2
77.4
0.0
0.0
0.0
80.5
84.5
88.2
0.0
0.0
0.0
102.6
105.9
108.0
112.5
116.7
123.2
113.7
117.2
120.4
126.9
116.7
123.2
125.1
128.9
131.5
136.6
141.6
148.8

kW
20.0
20.4
20.7
23.3
22.2
0.0
23.4
23.8
24.1
27.2
0.0
0.0
29.1
29.3
29.7
0.0
0.0
0.0
34.4
34.7
35.4
0.0
0.0
0.0
38.6
39.2
39.8
0.0
0.0
0.0
47.4
48.2
48.9
0.0
0.0
0.0
57.7
58.1
59.2
61.3
63.5
67.1
65.2
65.9
67.2
69.8
63.5
67.1
68.7
69.4
70.8
73.6
76.5
81.0

Data out of the operating limits

LCLT: Leaving chilled liquid temperature


Cool kW: Cooling capacity
Power kW: Unit power input, including the power input of the compressors, fans, control circuit
and power input of the liquid pump to overcome unit pressure drop.

Page G.7
Doc. No. PC150/01.04/GB

YCCD LN COOLING CAPACITIES (Low Noise Units)

TABLE 6

Model

YCCD 60 LN

YCCD 75 LN

YCCD 90 LN

YCCD 105 LN

YCCD 120 LN

YCCD 150 LN

YCCD 170 LN

YCCD 190 LN

YCCD 210 LN

25
LCLT
C
6
7
8
10
12
15
6
7
8
10
12
15
6
7
8
10
12
15
6
7
8
10
12
15
6
7
8
10
12
15
6
7
8
10
12
15
6
7
8
10
12
15
6
7
8
10
12
15
6
7
8
10
12
15

30

Condenser Entering Air Temperature C


32
35

40

43

Cool

Power

Cool

Power

Cool

Power

Cool

Power

Cool

Power

Cool

Power

kW
55.3
57.3
59.4
63.3
67.1
73.0
61.8
64.0
66.3
70.7
74.8
81.5
68.5
70.4
72.5
76.7
80.8
87.2
73.2
75.3
77.0
80.5
84.0
89.2
103.7
107.5
111.3
118.7
125.7
136.8
118.2
122.5
126.8
135.2
143.2
155.9
129.6
133.6
136.4
141.7
147.0
154.5
146.8
151.3
155.4
163.5
171.8
184.3
156.4
161.2
164.4
170.6
176.7
185.3

kW
18.6
19.0
19.4
20.0
20.5
21.6
21.8
22.3
22.7
23.4
24.0
25.3
22.2
22.4
22.8
23.5
24.2
25.3
26.9
27.2
27.9
29.2
30.6
32.7
35.4
36.1
36.8
38.0
39.0
41.0
43.0
43.9
44.7
46.2
47.3
49.8
43.9
44.3
44.8
45.6
46.6
48.1
48.2
48.9
49.9
52.2
54.6
58.3
52.4
53.2
54.2
56.6
59.1
63.0

kW
50.7
52.7
54.6
58.5
62.1
67.8
56.6
58.8
60.9
65.2
69.3
75.7
65.7
67.5
69.6
73.6
77.5
83.6
70.9
72.7
74.6
78.0
81.4
86.4
95.0
98.7
102.4
109.5
116.3
127.1
108.3
112.5
116.6
124.8
132.5
144.8
122.6
126.4
129.1
134.2
139.2
146.4
139.3
143.6
147.5
155.3
163.1
174.9
148.1
152.5
155.6
161.4
167.3
175.5

kW
19.2
19.5
19.9
20.6
21.2
22.3
22.5
22.9
23.3
24.1
24.8
26.1
24.1
24.3
24.8
25.4
26.2
27.4
29.4
29.7
30.4
31.8
33.3
35.6
36.4
37.1
37.8
39.1
40.3
42.4
44.2
45.1
46.0
47.6
48.9
51.5
47.9
48.4
48.9
49.8
50.8
52.3
52.5
53.1
54.2
56.6
59.1
63.0
57.2
57.9
59.1
61.5
64.2
68.1

kW
48.8
50.8
52.7
56.5
60.0
65.7
54.5
56.7
58.8
63.0
67.0
73.3
64.5
66.2
68.3
72.2
76.1
82.1
69.8
71.7
73.4
76.8
80.2
85.1
91.5
95.2
98.8
105.8
112.5
123.2
104.3
108.4
112.5
120.6
128.2
140.3
119.7
123.4
126.0
131.1
136.0
143.1
136.2
140.4
144.1
151.8
159.4
171.1
144.5
148.9
152.0
157.8
163.3
171.4

kW
19.3
19.7
20.1
20.8
21.7
22.7
22.7
23.1
23.5
24.4
25.4
26.6
24.9
25.2
25.6
26.3
27.1
28.2
30.5
30.8
31.5
33.0
34.5
36.8
36.7
37.5
38.2
39.5
41.2
43.2
44.6
45.5
46.4
48.0
50.0
52.4
49.6
50.2
50.6
51.6
52.6
54.0
54.3
54.9
56.0
58.4
61.0
64.9
59.1
59.8
61.1
63.6
66.2
70.4

kW
46.0
47.9
49.8
53.5
57.0
62.6
51.3
53.4
55.6
59.7
63.6
69.8
62.7
64.3
66.3
70.1
73.9
79.8
68.2
70.1
71.7
75.0
78.3
83.2
86.2
89.8
93.3
100.2
106.8
117.2
98.2
102.3
106.3
114.2
121.7
133.6
115.2
118.9
121.4
126.3
131.1
137.8
131.5
135.6
139.2
146.5
154.0
165.3
139.2
143.5
146.4
152.1
157.5
165.3

kW
19.6
19.9
20.3
21.0
21.7
22.8
22.9
23.4
23.8
24.6
25.4
26.7
26.2
26.4
26.8
27.6
28.3
29.6
32.1
32.5
33.2
34.7
36.2
38.6
37.2
37.9
38.6
39.9
41.2
43.3
45.2
46.0
46.9
48.5
50.0
52.6
52.4
52.9
53.3
54.4
55.3
56.9
57.0
57.6
58.8
61.3
63.8
67.9
62.2
62.9
64.2
66.8
69.5
73.8

kW
41.2
43.0
44.9
48.5
51.8
57.2
46.0
48.0
50.1
54.1
57.8
63.8
56.0
57.5
59.3
62.8
66.1
71.4
62.6
64.3
65.8
74.3
74.3
82.0
77.2
80.6
84.1
90.8
97.1
107.2
88.0
91.9
95.8
103.5
110.7
122.2
105.6
109.0
111.3
115.8
120.2
126.7
120.5
124.3
127.6
134.4
141.2
151.6
127.7
131.7
134.3
139.4
144.5
151.7

kW
19.9
20.2
20.6
21.3
22.0
23.0
23.3
23.7
24.1
24.9
25.7
26.9
28.4
28.6
29.0
29.8
30.6
31.8
34.9
35.3
36.1
34.9
34.9
36.5
37.8
38.4
39.0
40.4
41.7
43.7
45.9
46.7
47.4
49.1
50.7
53.1
57.2
57.8
58.2
59.2
60.3
62.0
61.7
62.3
63.6
66.2
68.9
73.0
68.1
68.9
70.2
73.0
75.9
80.6

kW
38.4
40.3
42.0
45.6
48.8
54.1
42.8
45.0
46.9
50.8
54.5
60.3
52.1
53.6
55.2
60.2
60.2
66.7
59.2
65.3
70.0
65.3
70.0
77.5
72.0
75.5
78.8
85.4
91.5
101.3
82.0
86.1
89.8
97.3
104.2
115.4
99.9
103.0
105.2
109.5
113.7
119.9
113.9
117.4
120.6
127.1
113.7
119.9
120.8
124.5
127.0
131.9
136.7
143.7

kW
20.2
20.5
20.9
23.5
22.4
21.7
23.6
24.1
24.4
27.5
26.2
25.4
29.8
30.0
30.5
29.4
29.4
28.5
36.8
37.3
35.5
37.3
35.5
34.4
38.3
39.0
39.6
44.6
42.5
41.1
46.6
47.4
48.1
54.2
51.6
50.0
60.4
60.8
61.4
62.4
63.5
65.1
64.8
65.4
66.7
69.4
62.9
64.4
71.7
72.4
73.8
76.7
78.9
83.4

0.0

Data out of the operating limits

LCLT: Leaving chilled liquid temperature


Cool kW: Cooling capacity
Power kW: Unit power input, including the power input of the compressors, fans, control circuit
and power input of the liquid pump to overcome unit pressure drop.

Page G.8
Doc. No. PC150/01.04/GB

YCCD HT COOLING CAPACITIES (High Temperature Units)

Model

YCCD 60 HT

YCCD 75 HT

YCCD 90 HT

YCCD 105 HT

YCCD 120 HT

YCCD 150 HT

YCCD 170 HT

YCCD 190 HT

YCCD 210 HT

25
LCLT
C
6
7
8
10
12
15
6
7
8
10
12
15
6
7
8
10
12
15
6
7
8
10
12
15
6
7
8
10
12
15
6
7
8
10
12
15
6
7
8
10
12
15
6
7
8
10
12
15
6
7
8
10
12
15

Cool
kW
54.1
56.8
59.6
65.1
69.5
75.7
62.2
65.4
68.6
74.9
80.0
87.1
71.9
74.1
76.3
81.0
85.7
93.0
81.0
83.3
85.7
90.1
94.7
101.4
104.2
109.5
114.8
125.4
133.9
145.8
118.7
124.8
130.8
142.9
152.5
166.1
135.2
139.3
142.3
147.9
153.3
161.2
154.5
159.4
164.0
173.2
182.6
196.7
165.3
170.4
173.8
180.3
186.8
195.9

0.0

30
Power
kW
18.3
18.7
19.0
19.7
20.2
21.2
21.0
21.4
21.8
22.5
23.1
24.3
20.9
21.1
21.4
21.9
22.5
23.4
23.8
23.9
24.4
25.4
26.4
28.1
35.9
36.6
37.3
38.5
39.4
41.5
44.4
45.3
46.1
47.7
48.9
51.4
41.6
41.9
42.8
44.5
46.3
49.1
45.3
45.8
46.8
48.8
50.8
54.2
49.0
49.7
50.8
53.0
55.3
59.0

Cool
kW
50.5
53.1
55.7
60.6
64.3
70.3
58.2
61.1
64.1
69.7
74.0
80.9
68.9
71.1
73.3
77.8
82.2
89.3
78.5
80.5
83.0
87.3
91.7
98.2
97.4
102.3
107.3
116.7
123.9
135.4
110.9
116.6
122.2
133.0
141.2
154.3
127.9
131.5
134.6
140.0
145.2
152.7
146.5
151.4
155.7
164.5
173.3
186.8
156.5
161.2
164.5
170.6
176.8
185.6

Condenser Entering Air Temperature C


32
35
Power
kW
18.8
19.2
19.6
20.2
20.8
21.9
21.6
22.0
22.4
23.2
23.8
25.1
22.7
22.9
23.2
23.7
24.4
25.3
26.0
26.1
26.6
27.7
28.8
30.5
36.9
37.6
38.3
39.6
40.8
42.9
44.4
45.3
46.1
47.7
48.9
51.4
45.2
45.7
46.7
48.5
50.3
53.4
49.2
49.7
50.7
52.7
54.9
58.3
53.3
54.1
55.2
57.4
60.0
63.7

Cool
kW
49.1
51.6
54.1
58.5
62.2
68.1
56.5
59.4
62.3
67.3
71.6
78.4
67.7
69.8
71.9
76.3
80.7
87.6
77.3
79.4
81.7
86.0
90.3
96.7
94.6
99.5
104.3
112.7
119.9
131.2
107.8
113.3
118.8
128.5
136.6
149.5
124.9
128.7
131.4
136.8
141.8
149.2
143.2
148.0
152.2
160.8
169.4
182.7
152.7
157.5
160.6
166.8
172.6
181.2

Power
kW
19.0
19.4
19.7
20.4
21.3
22.3
21.8
22.2
22.6
23.4
24.4
25.6
23.5
23.7
24.0
24.5
25.1
26.1
26.9
27.0
27.6
28.7
29.8
31.5
37.2
37.9
38.7
40.0
41.7
43.7
46.1
47.0
47.9
49.5
51.6
54.1
46.9
47.4
48.2
50.2
52.1
55.1
50.9
51.3
52.4
54.4
56.6
60.1
55.2
55.8
57.0
59.4
61.9
65.8

Cool
kW
47.2
49.6
51.6
55.4
59.1
64.8
54.3
57.1
59.4
63.8
68.0
74.6
65.8
67.8
69.9
74.1
78.5
85.2
75.5
77.6
79.8
84.0
88.2
94.5
91.0
95.6
99.4
106.8
113.8
124.9
103.7
109.0
113.3
121.7
129.6
142.3
120.2
124.0
126.6
131.7
136.7
143.8
138.3
142.9
146.9
155.2
163.6
176.5
147.2
151.7
154.7
160.8
166.5
174.7

Power
kW
19.2
19.6
20.0
20.6
21.3
22.4
22.0
22.4
22.9
23.6
24.4
25.6
24.6
24.8
25.1
25.7
26.3
27.3
28.4
28.4
29.0
30.1
31.3
33.1
37.6
38.4
39.1
40.4
41.7
43.8
46.6
47.5
48.4
50.1
51.6
54.3
49.4
49.9
50.9
52.9
54.8
58.1
53.4
53.9
54.9
57.0
59.2
62.7
57.9
58.7
59.9
62.3
64.9
69.0

Cool
kW
42.7
44.6
46.5
50.2
53.7
59.3
49.1
51.3
53.5
57.8
61.8
68.2
58.7
60.6
62.4
66.3
70.2
76.2
69.3
71.2
73.2
77.1
81.1
86.8
82.3
85.9
89.6
96.7
103.5
114.2
93.7
97.9
102.1
110.2
117.9
130.2
110.2
113.7
116.1
120.8
125.4
132.2
126.8
130.9
134.7
142.4
150.1
161.9
135.0
139.2
142.0
147.4
152.7
160.4

TABLE 7

40

45
Power
kW
19.5
19.9
20.2
20.9
21.6
22.6
22.4
22.8
23.1
23.9
24.7
25.9
26.7
26.9
27.2
27.7
28.4
29.3
30.8
30.9
31.5
32.7
33.9
35.8
38.2
38.9
39.5
40.9
42.2
44.2
47.4
48.2
49.0
50.6
52.3
54.8
54.4
54.8
55.7
57.9
60.0
63.5
57.8
58.3
59.3
61.5
63.8
67.4
63.4
64.0
65.3
68.0
70.7
75.1

Cool
kW
37.8
39.8
41.6
45.2
48.5
53.8
43.5
45.8
47.8
52.0
55.8
61.9
52.0
53.6
55.3
58.7
62.2
67.4
63.0
64.9
66.7
70.2
73.8
83.6
72.9
76.7
80.1
87.0
93.4
103.7
83.0
87.4
91.3
99.1
106.4
118.2
104.2
107.5
109.7
114.2
118.6
125.1
115.2
119.0
122.4
129.4
136.5
147.2
127.7
131.6
134.2
139.5
144.5
151.9

Power
kW
20.3
20.3
20.6
21.4
22.2
23.3
23.3
23.3
23.6
24.5
25.4
26.6
28.9
29.1
29.4
30.0
30.6
31.6
33.4
33.5
34.1
35.3
36.5
37.8
39.8
39.8
40.4
42.0
43.4
45.5
49.3
49.3
50.0
52.0
53.7
56.4
57.3
57.7
58.9
61.0
63.3
66.7
62.0
62.4
63.5
65.6
67.9
71.4
66.8
67.3
68.7
71.4
74.2
78.7

Data out of the operating limits

LCLT: Leaving chilled liquid temperature


Cool kW: Cooling capacity
Power kW: Unit power input, including the power input of the compressors, fans, control circuit
and power input of the liquid pump to overcome unit pressure drop.

Page G.9
Doc. No. PC150/01.04/GB

GLYCOL SELECTION GUIDE


DATA REQUIRED
To select a YORK YCCD glycol chiller, the following information
is required.

SAMPLE SELECTION
A chiller is required for cooling propylene glycol from 4C to -1C
having a required duty of 48 kW.

1. Required cooling capacity.

The following design conditions apply:

2. Design chilled liquid entering and leaving temperatures.

Fouling Factor:
Altitude:
Ambient air:
Glycol Strength:

3. Design chilled liquid flow rate.


4. Design condenser entering air temperature. This will normally
be the design summer ambient air temperature unless
location or other factors have an influence.
5. Altitude above sea level.
6. Design cooler fouling factor.
7. Static pressure resistance against condenser entering and
leaving airflow where ducts, louvres, attenuators, etc., are
used, at full unit air flow.

0.088m C/kW
1200m
30C
27% w/w

For propylene glycol leaving at - 1C the recommended


concentration from Figure 5 is 27%. The specified strength is
therefore suitable.
From ratings using an "Ethylene Glycol" temperature of "-2C"
leaving temperature (Propylene Glycol capacity = Ethylene
Glycol capacity at 1C lower temperature) at 30C air a
YCCD 105 gives 49,6 kW capacity and 20,4 kW power (table 9).

Note: Items 1, 2 and 3 must be linked by the following formulae:

From the design fouling factor, corrections of Capacity x 0.987


and power x 0.995 apply (Table 3).

Cooling capacity (kW) = Range (C) x Flow (l/s)


Glycol Factor

From the design altitude, corrections of Capacity x 0.973 and


power x 1.020 apply (Table 4).

Where:
Range = Entering chilled liquid temperature - leaving chilled
liquid temperature.

From the design glycol strength, corrections of Capacity x 1.040


and power x 1.010 apply, (Interpolation from Table 9).

To determine Glycol Factor refer to Figure 3 for ethylene glycol


or Figure 5 for propylene glycol. For the design leaving
temperature look up the recommended concentration of glycol
and the Glycol Factor at this concentration. This is the minimum
concentration which should be used for the design leaving
temperature. If a higher concentration is desired the Glycol
Factor can be determined from Figure 4 for the ethylene glycol
or Figure 6 for propylene glycol.
SELECTION METHOD
1. Determine the correct model of chiller by selecting the model
which most closely matches the required capacity at the
design conditions of leaving chilled liquid temperature and
entering air temperature.
2. Apply the relevant correction factors for fouling factor and
altitude (Tables 3 and 4) and glycol concentration (Figures 3
or 5), to the capacity and power values from the capacity
tables. Ensure the corrected capacity is still sufficient for
requirements.
3. Using the corrected capacity of the selected chiller, adjust the
design temperature range, or flow rate, to balance the
formulae shown in Data Required.
4. Physical and electrical data can now be determined from
Tables 12 and 13.
5. Always re-check that selections fall within the design
limitations specified (Table 2).

Page G.10
Doc. No. PC150/01.04/GB

Applying these factors to the selection: YCCD 105


Capacity = 49.6 x 0.987 x 0.973 x 1.040 = 49.5 kW
Compressor Power = 20.4 x 0.995 x 1.020 x 1.010 = 20.9 kW
For the glycol concentration specified and a leaving chilled liquid
temperature of - 1C, Figure 6 shows a Glycol Factor of 0.243.
The flow rate can be determined, therefore, from the formula
shown in "Data Required".
49.6 kW = (4 - (-1)) x Flow (l/s)
0.243
Flow rate = 49.6 x 0.243 = 2.4 (l/s)
5
This satisfies the Operating Limits.
Cooler pressure drop can be found by taking the value of water
pressure drop Figure 2, for a YCCD 105 and multiplying by the
correction factor (Figure 8), for 27% strength and a mean
temperature of 1.5C,
i.e.

(4 + (-1))/2C:
12.5 kPa x 1.25 = 15.6 kPa

0.26

0.25
RECOMMENDED
CONCENTRATION

0.24

0.23

FREEZING
TEMPERATURE

CONCENTRATION BY WEIGHT %

CONCENTRATION BY WEIGHT %

0.27

LEAVING LIQUID TEMPERATURE C

LEAVING LIQUID TEMPERATURE C

0.24

0.23
RECOMMENDED
CONCENTRATION

FREEZING
TEMPERATURE

CONCENTRATION BY WEIGHT %

CONCENTRATION BY WEIGHT %

0.25

LEAVING LIQUID TEMPERATURE C

PRESSURE DROP
CORRECTION FACTORS FOR
ETHYLENE GLYCOL SOLUTIONS

FIGURE 6

GLYCOL FACTOR (l/s) C / kW

0.26
GLYCOL FACTOR AT
RECOMMENDED
CONCENTRATION

FACTORS AT OTHER
CONCENTRATIONS FOR
PROPYLENE GLYCOL SOLUTIONS

FIGURE 5

GLYCOL FACTOR (l/s) C / kW AT


RECOMMENDED CONCENTRATION

RECOMMENDED CONCENTRATIONS
FOR PROPYLENE GLYCOL SOLUTIONS

FIGURE 4

GLYCOL FACTOR (l/s) C / kW

0.28

GLYCOL FACTOR AT
RECOMMENDED
CONCENTRATION

FACTORS AT OTHER
CONCENTRATIONS FOR
ETHYLENE GLYCOL SOLUTIONS

FIGURE 3

GLYCOL FACTOR (l/s) C / kW AT


RECOMMENDED CONCENTRATION

RECOMMENDED CONCENTRATIONS
FOR ETHYLENE GLYCOL SOLUTIONS

LEAVING LIQUID TEMPERATURE C

PRESSURE DROP
CORRECTION FACTORS FOR
PROPYLENE GLYCOL SOLUTIONS

FIGURE 7

FIGURE 8

MEAN LIQUID TEMPERATURE C

% CONCENTRATION

CORRECTION FACTOR

% CONCENTRATION

CORRECTION FACTOR

1.50

MEAN LIQUID TEMPERATURE C

Page G.11
Doc. No. PC150/01.04/GB

YCCD COOLING CAPACITIES (35% ETHYLENE GLYCOL)

TABLE 8

Model

25

LCLT

YCCD 60

YCCD 75

YCCD 90

YCCD 105

YCCD 120

YCCD 150

YCCD 170

YCCD 190

YCCD 210

30

Cool
kW

Power
kW

Cool
kW

-8
-6
-4
-2
0
4
-8
-6
-4
-2
0
4
-8
-6
-4
-2
0
4
-8
-6
-4
-2
0
4
-8
-6
-4
-2
0
4
-8
-6
-4
-2
0
4
-8
-6
-4
-2
0
4
-8
-6
-4
-2
0
4
-8
-6
-4
-2
0
4

27.3
30.2
33.3
36.5
39.9
47.2
31.3
34.6
38.1
41.8
45.7
54.2
33.9
37.5
41.3
45.3
49.6
58.7
38.5
42.5
46.8
51.4
56.2
66.5
52.1
57.6
63.4
69.6
76.1
90.1
59.4
65.6
72.3
79.3
86.7
102.7
67.7
74.9
82.5
90.5
98.9
117.2
74.5
82.4
90.7
99.5
108.9
128.9
82.5
91.2
100.4
110.1
120.4
142.6

13.3
13.9
14.6
15.3
16.0
17.4
15.5
16.3
17.1
17.9
18.7
20.3
15.4
16.2
17.0
17.8
18.6
20.2
17.9
18.8
19.7
20.6
21.6
23.5
25.6
26.9
28.2
29.5
30.8
33.6
31.5
33.0
34.6
36.2
37.9
41.2
29.7
31.1
32.6
34.2
35.7
38.9
34.7
36.4
38.1
39.9
41.7
45.4
36.0
37.8
39.6
41.4
43.3
47.2

25.1
27.7
30.6
33.5
36.7
43.4
28.8
31.8
35.0
38.4
42.0
49.8
32.6
36.0
39.6
43.5
47.5
56.3
37.2
41.1
45.3
49.6
54.3
64.3
47.9
52.9
58.3
63.9
69.9
82.8
54.5
60.3
66.4
72.8
79.6
94.3
64.1
70.9
78.0
85.6
93.6
110.9
70.8
78.2
86.1
94.5
103.3
122.4
78.0
86.2
94.9
104.1
113.9
134.8

LCLT: Leaving chilled liquid temperature

Condenser Entering Air Temperature C


32
35
40
Power
Cool
Power
Cool
Power
Cool
Power
kW
kW
kW
kW
kW
kW
kW
13.7
14.3
15.0
15.7
16.4
17.9
15.9
16.7
17.5
18.4
19.2
20.9
16.8
17.6
18.4
19.3
20.2
22.0
19.6
20.5
21.5
22.5
23.5
25.6
26.3
27.6
28.9
30.3
31.7
34.5
32.3
33.9
35.5
37.2
38.9
42.4
32.4
34.0
35.6
37.3
39.0
42.5
37.7
39.5
41.4
43.3
45.3
49.4
39.2
41.1
43.1
45.1
47.1
51.3

24.2
26.7
29.4
32.3
35.3
41.8
27.7
30.6
33.8
37.0
40.5
48.0
31.9
35.3
38.9
42.7
46.7
55.2
36.6
40.5
44.6
48.9
53.5
63.4
46.1
51.0
56.1
61.6
67.4
79.8
52.6
58.1
64.0
70.2
76.8
90.9
62.6
69.2
76.2
83.6
91.4
108.2
69.2
76.5
84.2
92.4
101.0
119.6
76.1
84.2
92.7
101.7
111.2
131.7

13.8
14.5
15.2
15.9
16.6
18.1
16.1
16.9
17.7
18.5
19.4
21.1
17.3
18.2
19.1
19.9
20.9
22.7
20.3
21.3
22.3
23.3
24.4
26.6
26.6
27.9
29.2
30.6
31.9
34.8
32.6
34.2
35.9
37.5
39.2
42.8
33.6
35.2
36.9
38.6
40.4
44.0
38.9
40.9
42.8
44.8
46.8
51.0
40.5
42.5
44.5
46.6
48.7
53.0

22.8
25.2
27.8
30.5
33.3
39.5
26.2
28.9
31.8
34.9
38.2
45.2
31.0
34.3
37.8
41.4
45.3
53.7
35.8
39.6
43.6
47.8
52.3
61.9
43.5
48.1
53.0
58.1
63.5
75.2
49.6
54.8
60.4
66.2
72.4
85.7
60.3
66.7
73.4
80.5
88.1
104.3
66.8
73.8
81.3
89.2
97.5
115.5
73.4
81.1
89.3
98.0
107.1
126.9

13.9
14.6
15.3
16.0
16.8
18.3
16.3
17.1
17.9
18.7
19.6
21.3
18.2
19.1
20.0
20.9
21.9
23.8
21.4
22.4
23.5
24.6
25.7
28.0
26.9
28.2
29.5
30.9
32.3
35.2
33.0
34.6
36.3
38.0
39.7
43.2
35.4
37.1
38.9
40.7
42.6
46.4
40.8
42.8
44.9
47.0
49.1
53.5
42.6
44.7
46.8
49.0
51.2
55.8

20.5
22.7
25.0
27.4
29.9
35.5
23.5
26.0
28.6
31.4
34.3
40.6
27.7
30.7
33.8
37.0
40.5
48.0
32.9
36.3
40.0
43.9
48.0
56.9
39.1
43.2
47.6
52.2
57.1
67.6
44.5
49.2
54.2
59.5
65.0
77.0
55.3
61.1
67.3
73.9
80.8
95.6
61.2
67.7
74.5
81.8
89.4
105.9
67.3
74.4
81.9
89.9
98.3
116.4

14.1
14.8
15.5
16.3
17.0
18.5
16.5
17.3
18.1
19.0
19.9
21.6
19.7
20.7
21.7
22.7
23.7
25.8
23.2
24.4
25.6
26.7
28.0
30.5
27.2
28.6
29.9
31.3
32.8
35.7
33.5
35.1
36.8
38.5
40.2
43.8
38.8
40.7
42.7
44.7
46.7
50.9
44.3
46.4
48.7
50.9
53.2
58.0
46.5
48.8
51.2
53.5
56.0
61.0

Cool kW: Cooling capacity

Power kW: Unit power input, including the power input of the compressors, fans, control circuit

and power input of the liquid pump to overcome unit pressure drop.

TABLE 9

COOLING CAPACITY CORRECTION FACTORS


FOR OTHER GLYCOL CONCENTRATIONS
% By Weight
10
20
30
35
40
50

Ethylene Glycol
Capacity
Compressor
Factor
Input Factor
1.061
1.025
1.036
1.015
1.015
1.005
1.000
1.000
0.985
0.995
0.954
0.985

Propylene Glycol
Capacity
Compressor
Factor
Input Factor
1.097
1.033
1.067
1.023
1.026
1.008
1.000
1.000
0.974
0.992
0.923
0.977

If a selection at different glycol percentage is required, multiply the capacity and input power values
table 8 (35% ethylene glycol) by the capacity and input factors for the new glycol percentages.
Page G.12
Doc. No. PC150/01.04/GB

43
Cool
kW

Power
kW

19.2
21.2
23.4
25.6
28.0
33.2
22.0
24.3
26.8
29.4
32.1
38.1
25.8
28.6
31.4
34.5
37.7
44.7
31.1
34.4
37.9
41.6
45.4
53.8
36.6
40.5
44.6
48.9
53.5
63.3
41.7
46.1
50.8
55.7
60.9
72.2
52.3
57.8
63.6
69.8
76.3
90.4
57.9
64.0
70.4
77.3
84.5
100.1
63.6
70.4
77.5
85.0
92.9
110.1

14.4
15.1
15.8
16.5
17.3
18.8
16.8
17.6
18.4
19.3
20.2
22.0
20.7
21.7
22.7
23.8
24.9
27.1
24.5
25.7
26.9
28.2
29.4
32.1
27.7
29.0
30.4
31.8
33.3
36.2
34.0
35.6
37.3
39.1
40.9
44.5
41.0
43.0
45.1
47.2
49.3
53.7
46.5
48.7
51.1
53.5
55.9
60.9
48.9
51.3
53.8
56.3
58.9
64.1

YCCD LN COOLING CAPACITIES (35% ETHYLENE GLYCOL)


Model

YCCD 60 LN

YCCD 75 LN

YCCD 90 LN

YCCD 105 LN

YCCD 120 LN

YCCD 150 LN

YCCD 170 LN

YCCD 190 LN

YCCD 210 LN

25

30

Codenser entering Air Temperature C


32
35
40
Power
Cool
Power
Cool
Power
Cool
Power
kW
kW
kW
kW
kW
kW
kW

LCLT
C

Cool
kW

Power
kW

Cool
kW

-8
-6
-4
-2
0
4
-8
-6
-4
-2
0
4
-8
-6
-4
-2
0
4
-8
-6
-4
-2
0
4
-8
-6
-4
-2
0
4
-8
-6
-4
-2
0
4
-8
-6
-4
-2
0
4
-8
-6
-4
-2
0
4
-8
-6
-4
-2

28.3
31.3
34.5
37.8
41.3
49.0
31.6
34.9
38.4
42.2
46.1
54.6
34.7
38.4
42.3
46.4
50.7
60.1
37.1
41.1
45.2
49.6
54.2
64.2
53.1
58.6
64.6
70.9
77.5
91.7
60.4
66.8
73.6
80.7
88.3
104.5
65.9
72.9
80.2
88.0
96.3
114.0
74.7
82.6
90.9
99.7
109.1
129.2
79.6
88.0
96.9
106.3

13.4
14.1
14.7
15.4
16.1
17.6
15.7
16.5
17.3
18.1
18.9
20.6
15.8
16.6
17.4
18.2
19.0
20.7
19.2
20.2
21.1
22.1
23.1
25.2
25.5
26.7
28.0
29.3
30.6
33.4
31.0
32.5
34.0
35.6
37.2
40.6
30.5
32.1
33.6
35.2
36.7
40.0
34.4
36.1
37.9
39.6
41.4
45.1
36.5
38.3
40.1
42.0

26.0
28.7
31.7
34.7
38.0
45.0
29.0
32.1
35.3
38.8
42.4
50.2
33.3
36.8
40.6
44.5
48.7
57.6
35.9
39.7
43.7
47.9
52.4
62.1
48.7
53.9
59.3
65.1
71.2
84.3
55.5
61.4
67.6
74.2
81.1
96.0
62.4
69.0
75.9
83.3
91.1
107.9
70.9
78.4
86.3
94.7
103.5
122.6
75.3
83.2
91.6
100.5

13.8
14.5
15.2
15.9
16.6
18.1
16.1
16.9
17.7
18.6
19.4
21.2
17.2
18.0
18.9
19.7
20.6
22.5
21.0
22.0
23.0
24.1
25.2
27.5
26.2
27.5
28.8
30.1
31.5
34.3
31.8
33.4
35.0
36.6
38.3
41.7
33.6
35.3
37.0
38.7
40.4
44.0
37.4
39.2
41.1
43.0
45.0
49.0
39.9
41.9
43.9
46.0

25.1
27.7
30.5
33.5
36.6
43.3
28.0
30.9
34.0
37.3
40.8
48.4
32.7
36.1
39.8
43.7
47.7
56.5
35.4
39.1
43.1
47.2
51.6
61.2
47.0
51.9
57.2
62.7
68.6
81.2
53.5
59.2
65.1
71.5
78.1
92.5
60.9
67.3
74.1
81.3
88.9
105.3
69.3
76.6
84.4
92.6
101.2
119.9
73.5
81.3
89.5
98.2

13.9
14.6
15.3
16.0
16.7
18.2
16.3
17.1
17.9
18.7
19.6
21.3
17.7
18.6
19.5
20.4
21.3
23.3
21.7
22.8
23.9
25.0
26.1
28.5
26.4
27.7
29.0
30.4
31.8
34.6
32.1
33.7
35.3
36.9
38.6
42.1
34.9
36.6
38.4
40.1
42.0
45.7
38.7
40.6
42.5
44.5
46.5
50.7
41.4
43.4
45.5
47.6

23.6
26.1
28.8
31.6
34.5
40.9
26.4
29.2
32.1
35.2
38.5
45.6
31.8
35.1
38.7
42.4
46.4
54.9
34.6
38.2
42.1
46.2
50.5
59.8
44.3
49.0
53.9
59.2
64.7
76.6
50.5
55.8
61.4
67.4
73.7
87.3
58.7
64.9
71.4
78.4
85.7
101.5
66.9
74.0
81.4
89.4
97.7
115.7
70.8
78.3
86.2
94.6

14.1
14.8
15.5
16.2
16.9
18.4
16.5
17.3
18.1
19.0
19.8
21.6
18.6
19.5
20.5
21.4
22.4
24.4
22.9
24.0
25.2
26.3
27.5
30.0
26.7
28.0
29.4
30.7
32.1
35.0
32.5
34.1
35.7
37.4
39.1
42.5
36.8
38.6
40.5
42.4
44.3
48.2
40.6
42.6
44.6
46.7
48.8
53.2
43.7
45.8
48.0
50.2

21.2
23.5
25.9
28.4
31.0
36.7
23.7
26.2
28.8
31.7
34.6
41.0
28.4
31.4
34.6
37.9
41.5
49.1
31.7
35.1
38.6
42.4
46.4
54.9
39.8
44.0
48.5
53.2
58.1
68.8
45.4
50.1
55.2
60.6
66.2
78.4
53.8
59.5
65.5
71.9
78.6
93.1
61.3
67.8
74.7
81.9
89.6
106.1
65.0
71.8
79.1
86.8

0
4

116.2
137.6

43.9
47.8

109.9
130.2

48.1
52.4

107.4
127.1

49.8
54.2

103.4
122.5

52.5
57.2

94.9
112.4

TABLE 10

43
Cool
kW

Power
kW

14.3
15.0
15.7
16.4
17.2
18.7
16.7
17.5
18.4
19.2
20.1
21.9
20.2
21.2
22.2
23.2
24.3
26.4
24.9
26.1
27.4
28.7
30.0
32.7
27.1
28.4
29.8
31.2
32.6
35.5
32.9
34.5
36.2
37.9
39.6
43.1
40.4
42.4
44.4
46.5
48.6
52.9
44.0
46.1
48.3
50.6
52.9
57.6
48.0
50.4
52.8
55.2

19.9
22.0
24.2
26.6
29.1
34.4
22.2
24.5
27.0
29.6
32.4
38.4
26.4
29.2
32.2
35.3
38.6
45.7
29.3
32.4
35.7
39.1
42.8
50.7
37.3
41.2
45.4
49.8
54.4
64.5
42.5
47.0
51.7
56.7
62.0
73.5
50.9
56.2
61.9
67.9
74.3
88.0
58.0
64.1
70.6
77.4
84.7
100.3
61.5
67.9
74.8
82.1

14.5
15.2
15.9
16.7
17.4
19.0
17.0
17.8
18.6
19.5
20.4
22.2
21.2
22.2
23.3
24.4
25.5
27.7
26.2
27.5
28.8
30.2
31.6
34.4
27.5
28.9
30.2
31.6
33.1
36.0
33.4
35.1
36.7
38.4
40.2
43.8
42.6
44.7
46.8
49.0
51.2
55.8
46.1
48.4
50.7
53.1
55.5
60.5
50.6
53.0
55.6
58.2

57.7
62.9

89.7
106.3

60.8
66.3

LCLT: Leaving chilled liquid temperature


Cool kW: Cooling capacity
Power kW: Unit power input, including the power input of the compressors, fans and control circuit
and power input of the liquid pump to overcome unit pressure drop.

Page G.13
Doc. No. PC150/01.04/GB

TABLE 11

Model
60
75
90
105
120
150
170
190
210

Model
60
75
90
105
120
150
170
190
210

Model
60
75
90
105
120
150
170
190
210

Page G.14
Doc. No. PC150/01.04/GB

SOUND POWER LEVELS (FREQUENCY ANALYSIS (SPECTRUM))

125
86
86
87
88
89
89
86
87
87

125
77
77
77
80
78
81
76
78
78

125
87
87
90
90
92
92
87
88
88

250
84
84
85
86
87
87
90
91
91

YCCD STD
FREQUENCY (Hz)
500
1000
2000
83
82
80
83
82
80
84
83
81
85
84
82
86
85
83
86
85
83
87
87
85
88
88
86
88
88
86

4000
70
70
71
72
73
73
81
82
82

8000
59
59
60
61
62
62
72
73
73

250
75
75
75
78
76
79
80
82
82

YCCD LN
FREQUENCY (Hz)
500
1000
2000
74
73
71
74
73
71
74
73
71
77
76
74
75
74
72
78
77
75
77
77
75
79
79
77
79
79
77

4000
61
61
61
64
62
65
71
73
73

8000
50
50
50
53
51
54
62
64
64

250
85
85
88
88
90
90
91
92
92

YCCD HT
FREQUENCY (Hz)
500
1000
2000
84
83
81
84
83
81
87
86
84
87
86
84
89
88
86
89
88
86
88
88
86
89
89
87
89
89
87

4000
71
71
74
74
76
76
82
83
83

8000
60
60
63
63
65
65
73
74
74

dB(A)
87
87
88
89
90
90
93
94
94

dB(A)
78
78
78
81
79
82
83
85
85

dB(A)
88
88
91
91
93
93
94
95
95

PHYSICAL DATA (Standard Units)

TABLE 12

YCCD
Number of refrigerant circuits
Total capacity steps
Compressor
Number
Theoretical displacement
m/h
No. of cylinders
Nominal speed
rpm
Oil charge (per compressor)
l
Oil type
No. of loading stages
%
Evaporator
Number
Type
Water volume
l
Air
Total coil face area
m
cooled
Number of coils
Condenser
Number of rows
Fans
Number of fans
Nominal speed
rpm
Total airflow
m/s
Total power (standard fans)
kW
Total power (high pressure fans) kW
Refrigerant
Circuit 1
kg
Charge
Circuit 2
kg
Weight
Operating
kg
Shipping
kg
(aluminum fins)
Additional weight for copper fin coils
kg
dB(A)
Sound power level (2)
(3)
dB(A)
Sound pressure level at 10 m
Dimensions
Length
mm
Width
mm
Height
mm

60
75
2
2
2
2
2
2
36.16
43.16
3
3
2950
2950
2.8
2.8
098L00565-000
50-100
50-100
1
1
Plate
Plate
5.5
6
4.3
4.3
2
2
2
2
2
2
910
910
5.3
5.3
0.96
0.96
1.96
1.96
6.0
6.5
6.0
6.5
719
744
698
725
61
64
87
87
56
56
2110
2110
1110
1110
1810
1810

90
105
2
2
2
2
2
2
37.7
43.5
SCROLL
SCROLL
2950
2950
4
6.6
098L00637-000
50-100
50-100
1
1
Plate
Plate
6.5
7.9
4.3
4.3
2
2
3
3
2
2
910
910
6.1
6.1
0.96
0.96
1.96
1.96
8.5
12.0
8.5
12.0
912
957
891
935
80
85
88
89
57
58
2110
2110
1110
1110
1810
1810

YCCD
Number of refrigerant circuits
Total capacity steps
Compressor
Number
Theoretical displacement
m/h
No. of cylinders
Nominal speed
rpm
Oil charge (per compressor)
l
Oil type
No. of loading stages
%
Evaporator
Number
Type
Water volume
l
Air
Total coil face area
m
cooled
Number of coils
Condenser
Number of rows
Fans
Number of fans
Nominal speed
rpm
Total airflow
m/s
Total power (standard fans)
kW
Total power (high pressure fans) kW
Refrigerant
Circuit 1
kg
Charge
Circuit 2
kg
Weight
Operating
kg
Shipping
kg
(aluminum fins)
Additional weight for copper fin coils
kg
(1)
dB(A)
Sound power level
dB(A)
Sound pressure level at 10 m (2)
Dimensions
Length
mm
Width
mm
Height
mm

120
150
2
2
2
2
2
2
76.85
88.94
6
6
2950
2950
6.6
6.6
098L00565-000
50-100
50-100
1
1
Plate
Plate
9.4
11.3
6.1
6.1
2
2
3
4
3
3
910
910
7.5
7.2
1.44
1.44
2.94
2.94
10.5
11.5
10.5
11.5
1021
1099
992
1067
90
98
90
90
59
59
2760
2760
1110
1110
1810
1810

170
2
4
4
72.5
SCROLL
2950
10.4
20-50-70-100
1
Plate
12.4
8.7
4
3
3
910
12.3
2.94
4.2
18.5
18.5
1434
1422
133
93
62
3450
1110
2170

190
2
4
4
81.2
SCROLL
2950
10.6
098L00637-000
25-50-75-100
1
Plate
14.6
8.7
4
3
3
910
12.3
2.94
4.2
19.5
19.5
1473
1458
137
94
63
3450
1110
2170

210
2
4
4
87
SCROLL
2950
13.2
25-50-75-100
1
Plate
14.6
8.7
4
4
3
910
11.7
2.94
4.2
25.0
25.0
1578
1563
147
94
63
3450
1110
2170

(1) Sound levels are at fully loaded conditions. Sound power level values refer to ISO standard 3744 and Eurovent 8/1
(2) Sound pressure level values refer to ISO standard 3744

Page G.15
Doc. No. PC150/01.04/GB

TABLE 12

PHYSICAL DATA (Low Noise Units)

YCCD LN
Number of refrigerant circuits
Total capacity steps
Compressor
Number
Theoretical displacement
No. of cylinders
Nominal speed
Oil charge (per compressor)
Oil type
No. of loading stages
Evaporator
Number
Type
Water volume
Air
Total coil face area
cooled
Number of coils
Condenser
Number of rows
Fans
Number of fans
Nominal speed
Total airflow
Total power
Refrigerant
Circuit 1
Charge
Circuit 2
Weight
Operating
Shipping
(aluminum fins)
Additional weight for copper fin coils
Sound power level (1)
(2)
Sound pressure level at 10 m
Dimensions
Length
Width
Height
YCCD LN
Number of refrigerant circuits
Total capacity steps
Compressor
Number
Theoretical displacement
No. of cylinders
Nominal speed
Oil charge (per compressor)
Oil type
No. of loading stages
Evaporator
Number
Type
Water volume
Air
Total coil face area
cooled
Number of coils
Condenser
Number of rows
Fans
Number of fans
Nominal speed
Total airflow
Total power
Refrigerant
Circuit 1
Charge
Circuit 2
Weight
Operating
Shipping
(aluminum fins)
Additional weight for copper fin coils
Sound power level (1)
(2)
Sound pressure level at 10 m
Dimensions
Length
Width
Height

m/h
rpm
l
%

l
m

rpm
m/s
kW
kg
kg
kg
kg
kg
dB(A)
dB(A)
mm
mm
mm

m/h
rpm
l
%

l
m

rpm
m/s
kW
kg
kg
kg
kg
kg
dB(A)
dB(A)
mm
mm
mm

60
75
2
2
2
2
2
2
36.16
43.16
3
3
2950
2950
2.8
2.8
098L00565-000
50-100
50-100
1
1
Plate
Plate
5.5
6
4.3
4.3
2
2
2
2
2
2
580
580
4.2
4.2
1.4
1.4
6.0
6.5
6.0
6.5
763
790
743
770
65
68
78
78
47
47
2110
2110
1110
1110
1890
1890

90
105
2
2
2
2
2
2
37.7
43.5
SCROLL
SCROLL
2950
2950
4
6.6
098L00637-000
50-100
50-100
1
1
Plate
Plate
6.5
7.9
4.3
4.3
2
2
3
3
2
2
580
680
4.1
4.2
1.4
1.4
8.5
12.0
8.5
12.0
956
968
935
945
85
85
78
81
47
50
2110
2110
1110
1110
1890
1890

120
150
2
2
2
2
2
2
76.85
88.94
6
6
2950
2950
6.6
6.6
098L00565-000
50-100
50-100
1
1
Plate
Plate
9.4
11.3
6.1
6.1
2
2
3
4
3
3
580
680
5.6
7.0
2.1
2.1
11.0
11.5
11.0
11.5
1086
1111
1056
1080
97
99
79
82
48
51
2760
2760
1110
1110
1890
1890

170
2
4
4
72.5
SCROLL
2950
10.4
20-50-70-100
1
Plate
12.4
8.7
4
4
3
500
7.9
4.2
21.0
21.0
1524
1512
142
83
52
3450
1110
2170

(1) Sound levels are at fully loaded conditions. Sound power level values refer to ISO standard 3744 and Eurovent 8/1
(2) Sound pressure level values refer to ISO standard 3744

Page G.16
Doc. No. PC150/01.04/GB

190
2
4
4
81.2
SCROLL
2950
10.6
098L00637-000
25-50-70-100
1
Plate
12.4
8.7
4
4
3
500
9.6
4.2
22.0
22.0
1563
1548
146
85
54
3450
1110
2170

210
2
4
4
87
SCROLL
2950
13.2
25-50-75-100
1
Plate
14.6
8.7
4
4
3
700
9.6
4.2
25.0
25.0
1596
1581
149
85
54
3450
1110
2170

PHYSICAL DATA (High Temperature Units)


YCCD HT
Number of refrigerant circuits
Total capacity steps
Compressor
Number
Theoretical displacement
No. of cylinders
Nominal speed
Oil charge (per compressor)
Oil type
No. of loading stages
Evaporator
Number
Type
Water volume
Air
Total coil face area
cooled
Number of coils
Condenser
Number of rows
Fans
Number of fans
Nominal speed
Total airflow
Total power
Refrigerant
Circuit 1
Charge
Circuit 2
Weight
Operating
Shipping
(aluminum fins)
Additional weight for copper fin coils
Sound power level (1)
(2)
Sound pressure level at 10 m
Dimensions
Length
Width
Height
YCCD HT
Number of refrigerant circuits
Total capacity steps
Compressor
Number
Theoretical displacement
No. of cylinders
Nominal speed
Oil charge (per compressor)
Oil type
No. of loading stages
Evaporator
Number
Type
Water volume
Air
Total coil face area
cooled
Number of coils
Condenser
Number of rows
Fans
Number of fans
Nominal speed
Total airflow
Total power
Refrigerant
Circuit 1
Charge
Circuit 2
Weight
Operating
Shipping
(aluminum fins)
Additional weight for copper fin coils
Sound power level (1)
(2)
Sound pressure level at 10 m
Dimensions
Length
Width
Height

m/h
rpm
l
%

l
m

rpm
m/s
kW
kg
kg
kg
kg
kg
dB(A)
dB(A)
mm
mm
mm

m/h
rpm
l
%

l
m

rpm
m/s
kW
kg
kg
kg
kg
kg
dB(A)
dB(A)
mm
mm
mm

TABLE 12

60
75
2
2
2
2
2
2
36.16
43.16
3
3
2950
2950
2.8
2.8
098L00565-000
50-100
50-100
1
1
Plate
Plate
5.5
6
4.3
4.3
2
2
2
2
2
2
910
910
5.2
5.2
0.96
0.96
6.5
7.5
6.5
7.5
755
784
735
763
64
67
88
88
57
57
2110
2110
1110
1110
1810
1810

90
105
2
2
2
2
2
2
37.7
43.5
SCROLL
SCROLL
2950
2950
4
6.6
098L00637-000
50-100
50-100
1
1
Plate
Plate
6.5
7.9
4.3
4.3
2
2
3
3
2
2
910
910
7.2
6.9
1.96
1.96
8.5
12.0
8.5
12.0
923
968
901
946
81
86
91
91
60
60
2110
2110
1110
1110
1890
1890

120
150
2
2
2
2
2
2
76.85
88.94
6
6
2950
2950
6.6
6.6
098L00565-000
50-100
50-100
1
1
Plate
Plate
9.4
11.3
6.1
6.1
2
2
3
4
3
3
910
910
10.0
9.4
2.94
2.94
12.5
14.0
12.5
14.0
1040
1115
1011
1085
92
100
93
93
62
62
2760
2760
1110
1110
1890
1890

170
2
4
4
72.5
SCROLL
2950
10.4
20-50-70-100
1
Plate
12.4
8.7
4
4
3
900
15.2
4.2
18.5
18.5
1458
1443
135
94
63
3450
1110
2170

190
2
4
4
72.5
SCROLL
2950
10.6
098L00637-000
25-50-70-100
1
Plate
12.4
8.7
4
3
3
900
15.2
4.2
19.5
19.5
1497
1482
139
95
64
3450
1110
2170

210
2
4
4
87
SCROLL
2950
13.2
25-50-75-100
1
Plate
14.6
8.7
4
4
3
900
14.4
4.2
25.0
25.0
1596
1581
149
95
64
3450
1110
2170

(1) Sound levels are at fully loaded conditions. Sound power level values refer to ISO standard 3744 and Eurovent 8/1
(2) Sound pressure level values refer to ISO standard 3744

Page G.17
Doc. No. PC150/01.04/GB

ELECTRICAL DATA

TABLE 13

Compressor Data
Operating Condition
Current per
Power Input at
Comp.
Maximum(2) per

Power Input at
YCCD

System

60
75
90
105
120
150
170
190
210

Sys. 1+ 2
Sys. 1+ 2
Sys. 1+ 2
Sys. 1+ 2
Sys. 1+ 2
Sys. 1+ 2
Sys. 1+ 2
Sys. 1+ 2
Sys. 1+ 2

Nominal(1) per
comp (kW)
@400 V
9.3
11.0
12.7
15.0
18.1
22.4
9.6
15.0
12.7
15.0
15.0
15.0

comp (kW)
@400 V
11.0
14.0
13.8
16.8
24.0
29.0
11.1
16.8
13.8
16.8
16.8
16.8

Nominal(1) (A)
@400 V
14.9
18.2
21.5
26.5
31.4
37.8
16.9
26.5
21.5
26.5
26.5
26.5

Current per
Comp.
Maximum(2) (A)
@400 V
17.8
22.5
23.0
29.0
39.8
47.5
18.8
29.0
23.0
29.0
29.0
29.0

LRA
DOL Starting
Current per
Comp. (A)
@400 V
80
126
135
175
190
215
120
175
135
175
175
175

(1) Nominal conditions taken at 7oC leaving chilled water temperature and 35oC ambient temperature
(2) Maximum conditions for the compressor taken at 15oC leaving chilled water temperature and 43oC ambient temperature

Fan Data
YCCD
Number of fans

60
2

Power input per fan (kW)


Full load Amps per fan (A)

0.48
0.93

Power input per fan (kW)


Full load Amps per fan (A)

120
3

150
3

170
3

190
3

210
3

0.48
0.93

0.48
0.93

0.98
1.75

0.98
1.75

0.98
1.75

0.98
1.75

90
105
2
2
Standard Fans
0.48
0.48
0.48
0.93
0.93
0.93
High Pressure Fans
0.98
0.98
0.98
1.75
1.75
1.75

0.98
1.75

0.98
1.75

1.4
2.9

1.4
2.9

1.4
2.9

YCCD LN
Number of fans
Power input per fan (kW)
Full load Amps per fan (A)

60
2
0.70
1.15

75
2
0.70
1.15

90
2
0.70
1.15

105
2
0.70
1.15

120
3
0.70
1.15

150
3
0.70
1.15

170
3
0.81
1.70

190
3
0.81
1.70

210
3
0.81
1.70

YCCD HT
Number of fans
Power input per fan (kW)
Full load Amps per fan (A)

60
2
0.48
0.93

75
2
0.48
0.93

90
2
0.98
1.75

105
2
0.98
1.75

120
3
0.98
1.75

150
3
0.98
1.75

170
3
1.40
2.90

190
3
1.40
2.90

210
3
1.40
2.90

Page G.18
Doc. No. PC150/01.04/GB

75
2

ELECTRICAL CONNECTIONS (YCCD Models 60 -150 Standard Control)

YCCD TERMINAL BOARD

EXTERNAL TERMINAL BOARD

MAIN SWITCH

KEY

L1
L2
L3

EXTERNAL EQUIPMENT TERMINALS


LINE
400-3+PE-50Hz

VOLTAGE FREE CONTACT


UNIT ELECTRICAL TERMINALS
CUSTOMER WIRING

1
2
3

FLOW SWITCH OR
EXTERNAL INTERLOCK

INTERLOCK
(OPTIONAL)
CIRC PUMP ETC

(COMMON)

(NO)

10
11
35
36

REMOTE INDICATION
GENERAL ALARM

COOL

REMOTE
ON/OFF CONTROL

REMOTE INDICATION
VOLTAGE ON

37
COMPRESSOR '1' ON
38

REMOTE
INDICATION

39
COMPRESSOR '2' ON
40
103
8

14

PUMP RELAY
MAX 0.5 AMP 230V

ANTIFREEZE RELAY
MAX 0.5 AMP 230V

104
PUMP 1 ON
105
106
PUMP 2 ON
107
REMOTE
INDICATION
ANTIFREEZE
HEATER ON

PUMP MOTOR 1 OR 2
THERMAL OVERLOAD
CUTOUT

108
109
110
111

The following connections are required:

One 400-3-50 Hz supply plus earth.


Control interlocks if required.
The power connections and interlocks can be made to a single terminal strip. Supply cables should enter the unit via a hole
provided.
Mains isolator switches should be located adjacent to the unit and should incorporate provision for locking in the off position.
Installation of differential safety cut-outs is recommended to prevent damage due to phase failure.

Page G.19
Doc. No. PC150/01.04/GB

ELECTRICAL CONNECTIONS (YCCD Models 60 -150 Optional ISN Control)


YCCD TERMINAL BOARD

EXTERNAL TERMINAL BOARD

MAIN SWITCH

KEY

L1
L2
L3

EXTERNAL EQUIPMENT TERMINALS


LINE
400-3+PE-50Hz

VOLTAGE FREE CONTACT


UNIT ELECTRICAL TERMINALS
CUSTOMER WIRING

1
2
3

FLOW SWITCH OR
EXTERNAL INTERLOCK

INTERLOCK
(OPTIONAL)
CIRC PUMP ETC

COMMON

N.O. SYSTEM 1 GENERAL ALARM

N.O. SYSTEM 2 GENERAL ALARM

10
11
18

REMOTE
COOL

MODE
ICE
BUILDING SELECTION

19
PWM TEMP RESET
20
35
36

REMOTE INDICATION
VOLTAGE ON

37
COMPRESSOR '1' ON
38

REMOTE
INDICATION

39
COMPRESSOR '2' ON
40
103

PUMP RELAY
MAX 0.5 AMP 230V

ANTIFREEZE RELAY
MAX 0.5 AMP 230V
14
104
PUMP 1 ON
105
106
PUMP 2 ON
107
REMOTE
INDICATION
ANTIFREEZE
HEATER ON

PUMP MOTOR 1 OR 2
THERMAL OVERLOAD
CUTOUT

108
109
110
111

The following connections are required:

One 400-3-50 Hz supply plus earth.


Control interlocks if required.
The power connections and interlocks can be made to a single terminal strip. Supply cables should enter the unit via a hole
provided.
Mains isolator switches should be located adjacent to the unit and should incorporate provision for locking in the off position.
Installation of differential safety cut-outs is recommended to prevent damage due to phase failure.

Page G.20
Doc. No. PC150/01.04/GB

ELECTRICAL CONNECTIONS (YCCD Models 170 -210 Standard ISN Control)


YCCD TERMINAL BOARD

EXTERNAL TERMINAL BOARD

MAIN SWITCH

KEY

L1
L2
L3

EXTERNAL EQUIPMENT TERMINALS


LINE
400-3+PE-50Hz

VOLTAGE FREE CONTACT


UNIT ELECTRICAL TERMINALS
CUSTOMER WIRING

01
REMOTE START/STOP
02
1

FLOW SWITCH OR
EXTERNAL INTERLOCK

2
3
4

INTERLOCK
(OPTIONAL)
CIRC PUMP ETC

COMMON

N.O. SYSTEM 1 GENERAL ALARM

N.O. SYSTEM 2 GENERAL ALARM

10
11
COOL

18

ICE
BUILDING

REMOTE
MODE
SELECTION

19
PWM TEMP RESET
20
35

REMOTE INDICATION
VOLTAGE ON

36
37

SYS. 1
COMPRESSOR '1' ON

38

REMOTE
INDICATION

39

SYS. 1
COMPRESSOR '2' ON

40
41

SYS. 2
COMPRESSOR '1' ON

42

REMOTE
INDICATION

43

SYS. 2
COMPRESSOR '2' ON

44
103

PUMP RELAY
MAX 0.5 AMP 230V

ANTIFREEZE RELAY
MAX 0.5 AMP 230V
14

HYDRO KIT TERMINAL BOARD (OPTIONAL)

LINE
400-3+PE-50Hz

MAIN SWITCH
L1
L2
L3

103
8

COMMON
PUMP MOTOR RELAY
ANTIFREEZE RELAY

14
104
PUMP 1 ON
105
106
PUMP 2 ON
107
108
109
110
111

REMOTE
INDICATION
ANTIFREEZE
HEATER ON

PUMP MOTOR 1 OR 2
THERMAL OVERLOAD
CUTOUT

The following connections are required:

One 400-3-50 Hz supply plus earth.


Control interlocks if required.
The power connections and interlocks can be made to a single terminal strip. Supply cables should enter the unit via a hole
provided.
Mains isolator switches should be located adjacent to the unit and should incorporate provision for locking in the off position.
Installation of differential safety cut-outs is recommended to prevent damage due to phase failure.
Page G.21
Doc. No. PC150/01.04/GB

DIMENSIONS
YCCD Models 60, 75, 90 and 105
35 mm
ONLY FOR
TRANSPORT

C
Lifting Point

Cable Entry

Lifting Point

177

177

36,5

36,5

1037
1110

VIEW A

~778

~456

1100

2" Female

B
(+35 mm ONLY FOR TRANSPORT)

~378

VIEW B

MODEL
YCCD 60

YCCD 75

YCCD 90

YCCD 105

Page G.22
Doc. No. PC150/01.04/GB

VERSION

DIMENSION 'A'
(mm)

DIMENSION 'B'
(mm)

VIEW C

DIMENSION 'C'
(mm)

NUMBER
OF FANS

STANDARD

1756

2110

1810

LOW NOISE

1756

2110

1890

HIGH TEMPERATURE

1756

2110

1810

STANDARD

1756

2110

1810

LOW NOISE

1756

2110

1890

HIGH TEMPERATURE

1756

2110

1810

STANDARD

1756

2110

1810

LOW NOISE

1756

2110

1890

HIGH TEMPERATURE

1756

2110

1890

STANDARD

1756

2110

1810

LOW NOISE

1756

2110

1890

HIGH TEMPERATURE

1756

2110

1890

DIMENSIONS
YCCD Models 120 and 150
35 mm
ONLY FOR
TRANSPORT

C
Lifting Point

Lifting Point

Cable Entry

177

177

36,5

36,5

1037
1110

VIEW A

~778

~456

1100

2" Female

B
(+35 mm ONLY FOR TRANSPORT)

~378

VIEW B

MODEL
YCCD 120

YCCD 150

VERSION

DIMENSION 'A'
(mm)

DIMENSION 'B'
(mm)

VIEW C

DIMENSION 'C'
(mm)

NUMBER
OF FANS

STANDARD

2406

2760

1810

LOW NOISE

2406

2760

1890

HIGH TEMPERATURE

2406

2760

1890

STANDARD

2406

2760

1810

LOW NOISE

2406

2760

1890

HIGH TEMPERATURE

2406

2760

1890

Page G.23
Doc. No. PC150/01.04/GB

DIMENSIONS (continued)
YCCD Models 170, 190 and 210
3450

2170

1110

2"
Female

519

173

2"
Female

1498

1558

1017

VIEW A

Page G.24
Doc. No. PC150/01.04/GB

SPACE REQUIREMENTS
Single Unit Applications

3000 mm

1000 mm (Models 60 - 150)


1500 mm (Models 170 - 210)

A
1300 mm

1000 mm

1000 mm (Models 60 - 150)


1500 mm (Models 170 - 210)

VIEW A

Multi Unit Applications


A

1300 mm
A=

1000 mm (Models 60 - 150)


1500 mm (Models 170 - 210)

B=

1500 mm (Models 60 - 150)


2000 mm (Models 170 - 210)

1300 mm

1300 mm

1000 mm

1000 mm

Page G.25
Doc. No. PC150/01.04/GB

NOTES

Page G.26
Doc. No. PC150/01.04/GB