Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
16870 West Bernardo Drive, Suite 330 San Diego, CA 92127 U.S.A.
Copyright 2008 All Rights Reserved
Version 3.10.00
October 2008
WARRANTY INFORMATION
There is no warranty, implied or otherwise, on EDSA software. EDSA software is licensed to you as is. This program license provides a ninety (90) day limited warranty on the diskette that contains the program. This, the EDSA Users Guide, is not meant to alter the warranty situation described above. That is, the content of this document are not intended to, and does not, constitute a warranty of any sort, including warranty of merchantability or fitness for any particular purpose on your EDSA software package. EDSA Micro Corporation reserves the right to revise and make changes to this User's Guide and to the EDSA software without obligation to notify any person of, or provide any person with, such revision or change. EDSA programs come with verification and validation of methodology of calculation based on EDSA Micro Corporation's inhouse software development standards. EDSA performs longhand calculation and checks the programs results against published samples. However, we do not guarantee, or warranty, any program outputs, results, or conclusions reached from data generated by any programs which are all sold "as is". Since the meaning of QA/QC and the verification and validation of a program methodology are domains of vast interpretation, users are encouraged to perform their own inhouse verification and validation based on their own inhouse quality assurance, quality control policies and standards. Such operations - performed at the user's expense will meet the user's specific needs. EDSA Micro Corporation does not accept, or acknowledge, purchase instructions based on a buyer's QA/QC and/or a buyer's verification and validation standards. Therefore, purchase orders instructions are considered to be uniquely based on EDSA's own QA/QC verification and validation standards and test systems.
Please accept and respect the fact that EDSA Micro Corporation has enabled you to make an authorized disk as a backup to prevent losing the contents that might occur to your original disk drive. DO NOT sell, lend, lease, give, rent or otherwise distribute EDSA programs / User's Guides to anyone without prior written permission from EDSA Micro Corporation.
All Rights Reserved. No part of this publication may be reproduced without prior written consent from EDSA Micro Corporation.
TABLE OF CONTENTS
I. II. III. IV. V. VI. VII. VIII. IX. X. 1.0 FOREWORD ..................................................................................................................................................1 CALCULATIONS ..........................................................................................................................................1 DATA TABLES..............................................................................................................................................1 FEATURES.....................................................................................................................................................2 GROUNDING ELECTRODE CONDUCTOR...............................................................................................2 MINIMUM SIZE EQUIPMENT GROUND CONDUCTOR ........................................................................2 GENERAL INFORMATION .........................................................................................................................3 RACEWAY CONFIGURATIONS FOR SIZING AND CONDUCTOR DERATING .................................3 VOLTAGE DROP CALCULATIONS...........................................................................................................4 SUPPLEMENTARY VALIDATION PROBLEMS.....................................................................................10 Network Based NEC Wire Sizing.................................................................................................................14 1.1 Feeder Type Option ........................................................................................................................21 1.2 Adding a Pre-Sized Feeder into an Existing Conduit .....................................................................22 1.3 Copying and Pasting Wire Sizing Studies ......................................................................................26 Standalone NEC Wire Sizing........................................................................................................................28 2.1 Adding a Pre-Sized Feeder into an Existing Conduit (Standalone Method)...................................34 2.2 Accessing Tables and Databases.....................................................................................................36 2.2.1 Wire Tables.......................................................................................................................37 2.2.2 Conductor Properties Tables.............................................................................................41 2.2.3 Raceway Tables ................................................................................................................44 2.3 Creating a New Master Wire Database .......................................................................................45 2.3.1 Assigning a New Default Master Wire Database .............................................................46
2.0
ii
Tables Table 1..........................................................................................................................................................................6 Table 2..........................................................................................................................................................................7 Table 3..........................................................................................................................................................................8 Table 4..........................................................................................................................................................................9 Table 5..........................................................................................................................................................................9
Note:
You can view this manual using your CD as an Adobe Acrobat PDF file. The file name is:
NEC_Wire_Sizing.pdf
You will find the Test/Job files used in this tutorial at the following location: C:\DesignBase\Samples\NECWireSz = NEC Wire Sizing
Test Files:
EDSA_WS, WIRE_SA
iii
I.
FOREWORD
The Wire Sizing program accepts user's information regarding the components to be used for an electrical system. Based on this information, the program computes the smallest allowable wire size which meets user's specifications. The program also computes the conduit size required, and the voltage drop in Volts and in percentages. The program allows the user to define many sets of data and to perform the corresponding calculations on each individual set. Each set is called a "branch". Thus, the program maintains the user's list of branches with the calculations for each branch.
II.
CALCULATIONS
The program can: Size power conductors according to NEC for the following conditions: Any number of conductors in a single conduit or raceway. Additional power conductors can be added to the conduit to affect the derating of the conductor. Circuits involving multiple conductors per phase. Single conductor cables in a cable tray.
Size system grounding electrode conductors. Size equipment grounding conductors. Calculate voltage drop at design load for single-phase two- and three-wire circuits, and three-phase three-wire and four-wire circuits. Size conduits, raceways and cable trays for all power conductor conditions listed above.
III.
DATA TABLES
All data tables used by the program are completely accessible and can be edited by the user. They are as follows: Ampacity tables; Ambient temperature and multiple conductor adjustments; AC resistance and reactance of conductors; Conductor dimensions; Insulation properties; Conduit, raceway, and cable tray dimensions. Multiple wire table data files can be maintained to meet the needs of different projects.
Conduit, raceway and cable tray dimensions can be input by the user to match any desired system. Several generic types are supplied by EDSA.
IV.
FEATURES
The user interface is completely menu driven. Calculations are done on-screen with a Windows spreadsheet style editing screen. Default parameters can be set at two levels to control wire and conduit sizing: MASTER DEFAULTS Master defaults are stored in the wire sizing table file. These values are used to initialize a new job file, and can be customized by the user. JOB DEFAULTS The default parameters can be further customized for each individual job file without affecting the master default settings. All of these defaults may be overridden for each individual circuit in the job file. A wire size can be specified by the user. In this case, the program calculates the voltage drop, and checks the actual derated ampacity against the load. If a conduit size is specified by the user, the actual fill is checked against the allowable fill for the given size. Additional wires of a given size, or type, can be specified as running in the same conduit with the circuit being sized. These wires can be specified as power conductors, in which case they affect both conduit fill and ampacity, or as control wires, in which case they affect only the conduit fill.
V.
VI.
VII.
GENERAL INFORMATION
Ampacities and ambient correction factors are based on the Table #310-16 and #310-17, NEC 2000. Derating due to the number of conductors in a conduit is based on the Table on page 70-166, NEC 2000. Derating due to temperature is based on Table #310-16 and #310-17, NEC 2000. Conduit, raceway, and cable tray selections are based on the total wire area plus insulation based on Table #5, Chapter 9, NEC 2000. Bare wire area is based on Table #8, Chapter 9, NEC 2000. Voltage drops are calculated for single-phase two- or three-wires; three-phase three- or four-wires. See IEEE Std and Beeman. AC resistance and reactance are based on Table #9, Chapter 9, NEC 2000. Types of loads: A = current to be specified, in amps; KW to be specified; KVA to be specified; horsepower with the percentage efficiency to be specified.
KW = KVA = HP =
Note that the current required must be determined. If known, the current can be directly entered. Otherwise, user can enter KW, KVA, or HP. The program will then compute how much current is generated by the specified load and will take 125% of the computed load current for wire size calculations. (125% value can be changed by user to any desired percentage.) For KW, program uses % Power Factor (Job Default). For KVA, user must enter KVA. For HP, user must enter horsepower. Program uses percentage Power Factor and percentage Efficiency (Job Default). The generated current will be computed using these quantities and the above mentioned voltage and phase. Next, user must enter information about the additional conductors which will share the conduit. For each conductor, user will enter its number and type, its wire size, and its type of insulation.
VIII.
raceway data set by selecting the Tables/Raceway Data menu and entering one of the following codes in the type field: C P Single conduit for all conductors; Separate parallel conduits for each set of phase conductors. (Each conduit contains one of each phase conductors, plus neutral.); Raceway; Cable Tray.
R T
The four EDSA supplied raceway data sets provide typical examples of each of the four configuration types.
The selection of each configuration affects the following calculations: 1. For automatic calculation of the area, conduits are assumed to be round and raceways rectangular. Note that the calculated area can be overridden. Conductor derating for conduits follows Note 8, Ampacity Tables in Article 310, NEC 2000. Conductor derating for raceways follows Article 362-5, NEC 2000. Conductor derating for cable trays must be entered directly by the user in the wire detail screen. Refer to Article 318, NEC 2000. Conduit and raceway sizing is based on fill ratio: the ratio of the sum of all wire crosssectional areas to the cross-sectional area of the raceway. Refer to Chapter 9, Table 1, NEC 2000. Cable sizing is based on Article 318-10, NEC 2000.
2. 3. 4.
5.
6.
IX.
The above diagram indicates the magnitude of error when using the following equations: Line-to-neutral voltage drop = I(R cos + X sin ). (11)
Equation 11 can be converted to calculate the percent voltage drop as follows: Percent voltage drop =
(12)
where KVA is three-phase KVA and KV is line-to-line kiloVolts. For single-phase circuits the percentage drop is twice this value. AC resistance is corrected for operating temperatures as follows: Resistance at lower temperature R1 = R 2
I Z R + T1 I Z R + T2
I Z R + T2 I Z R + T1
(13)
Resistance at higher temperature R2 = R1 where: T1 T2 IZR IZR IZR = = = = = Low temperature; High temperature;
(14)
Inferred zero resistance temperature; -234.5 for copper; -236.0 for aluminum.
Conduit, raceway, and cable tray selections are based on Article 300-3b, NEC* 2000. All conductors of the same circuit, plus neutral and equipment grounding conductors, are contained within the same conduit. Conduits are selected according to Article 345-7, NEC 2000. Conductor ampacity derating for conduits is according to Note 8, Article 310 of NEC 2000. Raceways are selected according to Article 362-5, NEC 2000. Cable trays are selected according to Article 318-10, NEC 2000. Conductor ampacity is adjusted according to Article 318-11 (b), NEC 2000.
NOTE: National Electric Code and NEC are registered trademarks of the National Fire Protection Association, Quincy, Massachusetts 02269, U.S.A.
Aluminum Copper A circular mil is a circle 0.001 inch in diameter. A mil is one thousandth of an inch (0.001 inch) C mils = = R where: A d L r R = = = = = Area in C mils; Diameter in mils; Length of wire in feet; Specific resistance of material; Resistance of wire. = square mils 1.273 square mils C mils 0.7854.
r L d
2
= r
L A
(15)
Table 2 CONDUCTOR DERATING FACTORS FOR MORE THAN THREE CONDUCTORS IN A RACEWAY CONDUCTOR DERATING FACTOR WITH LOAD DIVERSITY Factor 0.8 0.7 0.6 0.5 Number of Conductors in Raceway 4 to 6 7 to 24 25 to 42 43 or more
CONDUCTOR DERATING FACTOR WITHOUT LOAD DIVERSITY Factor .8 .7 .5 .45 .40 .35 Number of Conductors 4 to 6 7 to 9 10 to 20 21 to 30 31 to 40 41 to 60
Please read Section 8. Adjustment Factors, on pages 70-196 of NEC Article 310. When you size conductors for loads, if you consider neutral as a conductor, the conductors are derated with regard to the above NEC table.
Type R RH RHH
Material and Characteristics Rubber Heat-resistant rubber Higher-temperature, heatresistant rubber Heat- and moisture-resistant rubber Thermoplastic Heat-resistant thermoplastic Heat- and moisture-resistant thermoplastic
Dry Locations Dry or Wet Locations Dry Locations Dry Locations Dry or Wet Locations Dry or Wet Locations
194
RHW
T TH THW
167
167
Table 4 Table 5
AMPACITY OF SINGLE INSULATED CONDUCTORS IN FREE AIR. AMPACITY OF THREE (OR FEWER) CONDUCTORS IN A CABLE OR RACEWAY
14 12 10 8 6 4 3 2 1 0 00 000 0000
250 300 350 400 500 MCM 600 700 750 800 900 1000
340 375 420 455 515 575 630 655 680 730 780
405 445 505 545 620 690 755 785 815 870 935
265 290 330 355 405 455 500 515 535 580 625
315 350 395 425 485 545 595 620 645 700 750 MCM
250 300 350 400 500 600 700 750 800 900 1000
215 240 260 280 320 355 385 400 410 435 455
255 285 310 335 380 420 460 475 490 520 545
170 190 210 225 260 285 310 320 330 355 375
205 230 250 270 310 340 375 385 395 425 445
X.
A.
select the appropriate conductor, and calculate the voltage drop for insulations rated at 60c, 75c, 85c and 90c. a. 60c (insulation TW) We wish to limit our selection to 500 kcmil to smaller cable. This will require two cables per phase since the design ampacity of 500 amps is greater than the capacity of a single 500 kcmil cable. Multi-conductor derating from note 8, Article #310, NEC 2000: 0.80 Try 2-400 kcmil: (ampacities from Article 310-16), NEC 2000 280 x 2 x 0.80 = 448 Try 2-500 kcmil: 320 x 2 x 0.80 = 512 THIS WILL WORK (not enough)
Voltage drop: (impedance from Table # 9, Chapter # 9, NEC 2000) Z = 0.050 x (60 + 234.5) / (75 + 234.5) = 0.0476 vd = 200 x (.0476 /1000) x 500 = 4.76 Volts (Program result: 2-500 kcmil cables, voltage drop of 4.87 Volts)
b. 75c (insulation THWN) Try 2-400 kcmil: 335 x 2 x 0.80 = 536 THIS WILL WORK
10
Voltage drop: VD = 200 X (.056 / 1000) X 500 = 5.6Volts (Program result: 2-400 kcmil cables, voltage drop of 5.56 Volts)
c. 85c (insulation V) Try 2-350 kcmil: 340 x 2 x 0.080 = 540 Try 2-300 kcmil: 310 x 2 x 0.80 = 496 Voltage drop: Z = 0.60 x (85 + 234.5) / 75 + 234.5) = 0.062 vd = 200 x (.056 /1000) x 500 = 6.2 Volts (Program result: 2-350 kcmil cables, voltage drop of 6.06 Volts) (not enough) THIS WILL WORK
d. 90c (insulation V) Try 2-300 kcmil: 320 x 2 x 0.80 = 512 Try 2-250 kcmil: 290 x 2 x 0.80 =464 Voltage drop: Z = 0.065 x (90 + 234.5) / (75 + 234.5) = 0.068 vd = 200 x (.056 / 1000) x 500 = 6.8 Volts (Program result: 2-300 kcmil cables, voltage drop of 6.7 Volts) The above results for cable selection exactly match the program results. This is to be expected since the program uses a table look-up method that follows the manual procedure for using Table # 310 in NEC 2000. Voltage drops calculated by the program are within 2 percent, or less, of the manual calculations. (not enough) THIS WILL WORK
11
B.
VERIFY CABLE TRAY SELECTION Note that the cable tray selection capability in the current version on NEC wire sizing is a very basic, first effort at providing automated cable tray selection. Of the many possible configurations of cable in cable trays, only the fill configuration of Article 318-10 (a) NEC 2000 and the ampacity calculation of 318-11 (b) (1) and (2) NEC 2000 are supported. Note that for ampacity calculations, the user must select the appropriate derating factor from 318-11 (b) NEC 2000 depending on conductor size and decide whether the tray is covered. Refer to jobfile "CBLTRAY" for examples.
a. Select a cable tray for the following cables: 8 - 500 kcmil XHHW 6 - 4-0 XHHW 3 - 250 kcmil XHHW
Since there are conductors in the 1-0 to 4-0 range, selection is governed by Article 318-110 (a) (4) NEC 2000. The sum of diameters of all cables is: Number and Size 8 - 500 kcmil XHHW 6 - 4-0 XHHW 3 - 250 kcmil XHHW Diameter 0.955 0.646 0.716 Total 7.64 3.876 2.148 13.664 inches
This requires a cable tray larger than 12 inches, and the next size in our catalog is 18 inches. ( Calculation agrees with program result.)
b. Select a cable tray for the following cables: 4 - 750 kcmil XHHW 4 - 1000 kcmil XHHW 4 - 1750 kcmil XHHW Since there are conductors both larger than, and smaller than 1000 kcmil, Article 310-10 (a) (3) of NEC 2000, governs.
12
Try 12 inch cable tray. From Table # 318-10, NEC 2000, the maximum fill for cables less than 1000 kcmil is: 13.0 - (1.1 [5.32 = 6.96]) = 5.99 in Try 18 inch cable tray: 19.5 - (1.1[5.32 = 6.96]) = 5.99 in2 Since this is greater than the 4.374 square inch area to be accommodated, 18 inch is OK. (This agrees with the program result.)
2
13
1.0
Step 3. Once the Wire Sizing Tools command is invoked, the tools menu will appear in this position.
Step 1. Proceed to open the file EDSA_WS.axd located in the Design Base 2.0 NECwiresz Samples folder.
14
The Analysis pick-list, allows the user to select the type of wire sizing methodology to be used.
The Defaults command sets the base calculation parameters for the analysis (Voltage, etc.).
The Edit command allows the user to enter and/or edit data for the selected feeder.
The Delete command allows the user to delete the cable sizing data for the selected feeder.
The Copy command allows the user to copy the cable sizing data from the selected feeder.
The Paste command allows the user to assign previously copied data to the selected feeder.
The View command allows the user to view a list of all the feeders assigned to the job file.
The Store command allows the user to save the cable sizing data being added to the selected feeders.
15
Step 4. Proceed to size a 3-phase / 3-wire feeder for MCC-1 as shown here. To begin, click on the cable once to select it.
Step 5. Proceed to define the default analysis parameters by selecting the Defaults icon.
16
Step 7. Proceed to specify the voltage, phase/wire configuration, cable temperature rating, ambient temperature, and maximum allowable voltage drop as applicable. For this example, use the values suggested here.
Step 9. Define the load diversity factor, cable tray derating factor, load power factor, and motor efficiency defaults. For this example, use the values suggested here. Step 10. Select the Conduit tab.
Step 8. Define the wire material, insulation type and maximum wire gauge to be used in the design. For this example, use the values suggested here.
Step 11. From the pick-lists, select the type of conduit to be used and its respective material. Also specify the maximum fill limit for the conduit. For this example, use the values suggested here.
17
Step 15. The connectivity data is automatically loaded from the single line diagram as shown in these fields.
Step 14. Before proceeding, make sure that the feeder under study is still selected in the single line diagram (verify Step 4). Select the Edit icon.
Step 16. From the pick list, select the category of the cable based on the NEC classification. For this example, select Feeder.
Step 17. Enter and/or verify the length of the feeder under study.
Step 18. Enter the load value and select its respective units as indicated.
Step 19. Once all the data has been entered, press the Tab button on your keyboard to run the analysis. The required cable size and number of conductors per phase are shown here. Also the actual design ampacity, voltage drop in volts/% are shown in the gray boxes. Step 20. Select Wire Detail.
18
Step 21. The results of the wire and conduit sizing exercise are shown here.
Step 22. Select the Settings tab to review and/or modify the default settings for the file.
Step 23. Select the Conduit tab to review and/or modify the selected conduit data.
Step 25. Select the OK to accept and return to the Edit Wire Segment dialog box. Once there, select OK to return the single line diagram.
Step 24. Select the Detail tab to add additional wires into the newly sized conduit. This feature will be explained in subsequent sections of this tutorial.
19
Step 26. To add additional cables, repeat the same procedure shown in steps 1 through 26. To view all the cables in the job file, select the View icon.
Step 27. All the wire segments in the file would be listed here. To view a report on a specific segment, select it and press View. To view all of the listed segments, select View All. To edit a specific wire segment, select it and press Edit.
20
1.1
F Feeder This option will automatically size a feeder branch cable based on the latest NEC requirements. The program will calculate the cable size, number of conductors per phase required, design amps, and voltage drop. PF Pre-sized Feeder This option allows the user to manually enter (pre-size) a cable for the branch feeder under study. The program will calculate design amps, and voltage drop based on the cable and load specified by the user. S Service Entrance This option will automatically size a service entrance cable based on the latest NEC requirements. The program will calculate the cable size, number of conductors per phase required, design amps, and voltage drop. PS Pre-Sized Service Entrance This option allows the user to manually enter (pre-size) a cable for the service entrance under study. The program will calculate design amps, and voltage drop based on the cable and load specified by the user. SG System Ground This option will automatically size a ground conductor for a specified service entrance cable based on the latest NEC requirements. The user enters the ampacity of the service entrance cable, and the program will calculate the size of an NEC compliant ground cable. EG Equipment Ground This option will automatically size a ground conductor for a specified service feeder cable based on the latest NEC requirements. The user enters the ampacity of the feeder cable, and the program will calculate the size of an NEC compliant equipment ground cable. CW Control Wire This option allows the user to specify a control wire cable.
21
1.2
Step 1. In this example, we will manually add an additional pre-sized feeder cable into the feeder/conduit previously sized in section 1.0 of this tutorial. Proceed by clicking on this feeder once, in order to select it.
Step 2. Once the existing feeder has been selected, press the Edit icon.
22
Step 5. From the pick-list, select a 4 AWG, THHN single conductor. From the Type menu select PF-Pre-sized Feeder to indicate that this cable is being entered manually by the user. Select OK.
23
Step 7. To update the wire count and the conduit size if necessary, select OK.
Step 6. The newly added cable is now listed on the table. The cable can be edited or deleted, by simply selecting it from the table and pressing either the Edit or Delete buttons.
24
25
1.3
Step 1. In this example, we will copy the wire sizing study performed on MCC-1 Feeder and paste it onto MCC-2 Feeder. The assumption here is that both cables will be designed as identical feeders.
COPY
Step 2. Select the feeder to be copied, by clicking on it once as indicated here. Select MCC-1 Feeder.
Step 3. Once the existing feeder has been selected, press the Copy icon.
26
Step 6. The operation has now been completed. To verify the successful addition of the new study, select the View icon.
27
2.0
Step 6. Proceed to assign the default analysis parameters by selecting Edit/Job Defaults.
28
Step 8. Proceed to specify the voltage, phase/wire configuration, cable temperature rating, ambient temperature, and maximum allowable voltage drop as applicable. For this example, use the values suggested here.
Step 10. Define the load diversity factor, cable tray derating factor, load power factor, and motor efficiency defaults. For this example, use the values suggested here. Step 11. Select the Conduit tab.
Step 9. Define the wire material, insulation type and maximum wire gauge to be used in the design. For this example, use the values suggested here.
Step 12. From the pick-lists, select the type of conduit to be used and its respective material. Also specify the maximum fill limit for the conduit. For this example, use the values suggested here.
29
Step 14. Select the Save icon in order to save the new settings.
Step 15. Proceed to add the required wire segments by selecting Edit/Wire Segments.
30
Step 17. Specify the labels for the From Node, To Node and the wire Segment. Proceed as indicated here.
Step 18. From the pick list, select the category of the cable based on the NEC classification. For this example, select Feeder.
Step 19. Enter and/or verify the length of the feeder under study.
Step 20. Enter the load value and select its respective units as indicated.
Step 21. Once all the data has been entered, press the Tab button on your keyboard to run the analysis. The required cable size and number of conductors per phase are shown here. Also the actual design ampacity, voltage drop in volts/% are shown in the gray boxes. Step 22. Select Wire Detail.
31
Step 23. The results of the wire and conduit sizing exercise are shown here.
Step 24. Select the Settings tab to review and/or modify the default settings for the file.
Step 25. Select the Conduit tab to review and/or modify the selected conduit data.
Step 27. Select the OK to accept and return to the Edit Wire Segment dialog box. Once there, select OK to return the single line diagram.
Step 26. Select the Detail tab to add additional wires into the newly sized conduit. This feature will be explained in subsequent sections of this tutorial.
32
Step 29. Next, lets add an equipment ground for the previously sized feeder MCC-1 Feeder
Step 28. The newly sized cable is listed in the Wire Segment table, as shown here.
Step 30. Repeat steps 1 through 28, using the entries shown here for an Equipment Ground wire.
Step 33. The newly added Equipment Ground wire is shown here.
33
2.1
Step 5. From the pick-list, select a 4 AWG, THHN single conductor. From the Type menu select PF-Pre-sized Feeder to indicate that this cable is being entered manually by the user. Select OK.
34
Step 6. The newly added cable is now listed on the table. The cable can be edited or deleted, by simply selecting it from the table and pressing either the Edit or Delete buttons.
Step 7. To update the wire count and the conduit size if necessary, select OK.
35
2.2
WARNING This section (2.2) shows how to modify the data in the current database. The current database is designated as the Master Database for the program. The default Master database is called WIRETBLS.NEC and contains the most current NEC compliant data. Any changes to this database will affect the NEC compliance of the results.
36
The Wire Tables database, allows the user to view and modify, if required, values for all the parameters shown here.
The Wire Parameters table allows the user to modify base parameters for the wire and conduit sizing calculations. Refer to section 2.0, steps 7 to 13 for details.
The Ambient Correction Factors table, allow the user to view the current code compliant data. By selecting Add, Edit or Delete the user can make modifications to the existing data as required.
37
The Multi-Conductor table allows the user to verify and/or edit the ampacity based on the number of conductors within a raceway. Two tables are available for this purpose; with and without taking into account diversity factors.
38
The Insulation Classes table allows the user to view and/or edit the temperature rating for each type of insulation.
The Equipment Ground table allows the user to view and/or edit the ground wire size required for a feeder based on the over-current protection setting.
39
The Small Motors table allows the user to specify current ratings for motors based on 120 V and 240 V voltage applications.
40
In the Base Ampacities table, the user can view and/or modify the current rating for each cable for different insulation temperatures. Both Copper and Aluminum cables are included in the table.
41
The Conductor Dimensions table allows the user to view and/or modify the cross section area of all insulated conductor sizes. Aluminum and Copper are included.
The Impedance table allows the user to view and/or modify the AC Resistance and AC Reactance of the cables in the database. Aluminum and Copper are included.
42
The System Ground table allows the user to view/modify the ground conductor sizes that correspond to specific service entrance ampacity ratings. Both Aluminum and Copper are included.
43
The Raceway Tables allow the user to designate numbers and ids to different types of raceways that are to be used in different design applications.
The Data Set table allows the user to view, add or modify the physical dimensions of conduits based on their trade size designation.
44
2.3
Step 3. Select in sequence Wire Tables, Conductor Properties & Raceway Tables and populate the empty tables of the new database with the new default data. Proceed as indicated in section 2.2 of this document.
45
Step 1. To assign a new default database, select File/Select Master Wire Table.
Step 2. From the list, select the new table to use, and press Open.
46