Thermal Insulation
Technical Requirements Definitions Condensation Q/A
HVAC Insulation
HVAC Ins. 01
Thermal Insulation
HVAC Insulation
HVAC Ins. 02
Thermal Insulation, in principal, is the resistance to reduce the heat transfer in a considerable amount. cold lines prevents heat loss heating lines prevents heat gains
The Resistance
HVAC Ins. 03
in Summer time
In HVAC;
is Thermal Insulation
HVAC Lines
Cold Lines Warm Lines Heating Lines
+6 C
+100 C
Where?
HVAC Ins. 05
Glasswool Stonewool Extruded Polistren (XPS) Expanded Polistren (EPS) Polyurathane (PUR) Phenolic Foam Cellular Glass
(EN 13162) (EN 13162) (EN 13164) (EN 13163) (EN 13165) (EN 13166) (EN 13167)
Technical Requirements
HVAC Ins. 08
Thermal Conductivity Coefficient( ) Water Vapor Diffusion Resistance Coefficient( ) Fire Classification (DIN 4102, BS 476, EN 13501) Corrosion Risk Temperature Range(C) Cell Structure Acoustic Performance Density (kg/m3) Weathering Resistance Dimensional Stability Easy Application Economics
NOT: Temperature range is not a selection criteria, it defines the usage area.
1. Thermal Conductivity ()
HVAC Ins. 09
It is the quantatiy of the energy which passes through a m3 of insulating material where there is 1C difference in tempurature between opposite surfaces.
3
WARM T1
1m 1m
COLD T2
Heat Transferred
(W/mK) 1m
HVAC Ins. 10
Thermal Conductivity ()
C 0 10 25 50 75 100
18
0.033
20
24
30
32
0.030
36
48
60
0.030
64
72
0.038 0.036
0.029 0.029
0.030 0.030
0.040 0.038
0.036
0.035
0.031
0.030 0.030
0.031
0.031 0.031
0.044 0.041
0.039
0.038
0.033
0.032 0.031
0.032
0.032 0.032
0.055 0.048
0.044
0.043
0.037
0.036 0.035
0.036
0.036 0.036
0.064 0.059
0.051
0.048
0.040
0.039 0.037
0.038
0.038 0.038
0.074 0.065
0.057
0.053
0.044
0.043 0.041
0.042
0.043 0.043
HVAC Ins. 12
It is the ratio of the resistance to the water vapour diffusion of an insulation material to the resistance of air
HVAC Ins. 13
=1 =
3. Fire Classification
HVAC Ins. 14
15
A Incombustible materials
A1 That does not contain combustible materials A2 That contains combustible materials
B Combustible materials
B1 Hardly combustible materials B2 Normal combustible materials B3 Easily combustible materials
DIN 4102
ClassA (Incombustible) ClassB (Combustible)
A1
A2
B1
XPS PE
B2
PUR EPS Wood
B3
Paper Wood
A1
18
B-s3-d0
4. Corrosion Risk
Thermal
19
According to DIN 1988 Part 7 Section 5:3 Limit Values Steel Pipes ; Chlor (%0,05) Copper Pipes ; Nitrate ve Ammonia (%0,2)
5.Temperature Range
HVAC Ins. 20
Max.Operating Temperature(C)
Ceramic wool Stonewool Cellular Glass Glasswool FEF * Melamine Foam Phenolic Foam Polyurathane Polyethylene
6. Cell Structure
HVAC Ins. 21
=7.000
closed cell
8- Density is the only specification that can be measured in the site. 9- Mechanical Resistance
is the compressive strength at % 10 deflection. 10- Dimensional Stability 11- Easy Application 12- Economics
Question-1
HVAC Ins. 23
HVAC Ins. 24
Glasswool (GW) Stonewool (SW) Flexible Elastomeric Rubber Foam (NBR) Extruded Polyethylene Foam (XPE) Polyurathane Foam (PUF) Phenolic Foam (PF) Cellular Glass (CG)
Question-2
HVAC Ins. 25
OdeCalc Program
For Pipes
Heat loss Temperature drop Surface temperature Freezing time Minumum insulation thickness preventing condensation
To Prevent Condensation
- Minumum insulation thickness preventing condensation for Pipes -
PARAMETERS
Ambient temperature ( TaC) Medium temperature( Tm C) Tube diameter (mm) Insulation material Relative Humidity (%) 30 6 114 R-Flex-ST 70
RESULTS
Thermal Conductivity (W/mK) Dew point temperature ( Td C) Minimum insulation thickness (mm) K-Flex dimension 0.0375 23.9 11.4 13 x 114
E.g. Ambient Temperature ( Ta) Medium Temperature ( Tm) Pipe Diameter (inch) Relative Humidity (%) RESULT
: 35C : : : 6 C 2 60
Question-3
HVAC Ins. 27
= % 65
Ts = 24.1C Tm = 6C
Td = 22.8C Ta = 30C
R-Flex ST Tube diameter = 25.4 mm
Thickness =9mm
Minimum insulation thickness = 7.6 mm
Ts = 24.1C
>
Td = 22.8C
Parameters of Condensation
HVAC Ins. 31
Ambient Temperature ( Ta = C ) Relative Humidity ( = % ) medium temperature ( Tm = C ) Air flow The heat transfer coefficient ( ) Thermal Conductivity ( ) Water vapour diffusion resistance coefficient ( )
Parameters of Condensation.1
HVAC Ins. 32
Parameters of Condensation.2
HVAC Ins. 33
= Heat Transfer Coefficient of the Surface It is being changed according to the material structure
1) If no thermal insulation is applied, 2) If an nsufficient thermal nsulation thickness is applied, Condensation on the Surface ! 3) Sufficient thermal insulation thickness 3.1 Thermal insulation material with a low value Condensation within the Insulation Material ! 3.2 Thermal insulation material with a high value No Condensation !
= % 65
Ts = 6.1C Tm = 6C
Td = 22.8C Ta = 30C
Tube diameter = 25.4 mm
Ts = 6.1C
<
Td = 22.8C
HVAC Ins. 36
18
Ts = 21.3C Tm = 6C
Td = 22.8C Ta = 30C
R-Flex ST Thickness =6 mm Tube diameter = 25.4 mm
Ts = 21.3C
<
Td = 22.8C
HVAC Ins. 37
HVAC Ins. 38
Ts = 23.6C Tm = 6C
Thickness =6 mm
Minimum insulation thickness = 7.6 mm
Td = 22.8C Ta = 30C
Tube diameter = 25.4 mm
Ts = 23.6C
>
Td = 22.8C
Thermal insulation material with a low value Condensation within the Insulation Material !
HVAC Ins. 39
Ts = 23.6C Tm = 6C
Td = 22.8C Ta = 30C
R-Flex ST Tube diameter = 25.4 mm
kalnlk=9 mm
Minimum insulation thickness = 7.6 mm
Ts = 23.6C
>
Td = 22.8C
Thermal insulation material with a high value No Condensation ! (a diffusion tight application is a must !)
HVAC Ins. 41
GLASSWOOL
HVAC Ins. 42
GLASSWOOL
HVAC Ins. 43
Produced with the transformation of silica sand into fiber by melting in high temperature
HVAC Ins. 44
Board,
Blanket,
Prefabricated Pipe
HVAC Ins. 46
HVAC Ins. 47
Quality Certificates
HVAC Ins. 48
EN 13162
Quality Certificates
HVAC Ins. 49
European Certificate
Technical Requirements
HVAC Ins. 50
1m HOT T1
(W/mK)
COLD T2
HVAC Blanket
HVAC Ins. 52
one side is covered with alu foil Density : 24 kg/m3 Usage area : Insulation of ventilation ducts from outside Insulation of air conditioning ducts from outside
HVAC Board
HVAC Ins. 53
Usage area : air ducts insulation boiler rooms and generator rooms
Radiator Panel
HVAC Ins. 54
Used as thermal insulator and reflector behind sources of heat such as radiators, stoves and ovens
Prefabricated Pipe
HVAC Ins. 55
none or alu foil covered Density : 60-100 kg/m3 Usage area : Radiator and central heating systems Solar energy systems
56
Thermal
57
Technical Requirements
HVAC Ins. 58
HOT T1 1m
(W/mK)
COLD T2
Thermal Conductivity Coefficient: 0,036 W/ mK (0C) Water vapour Diffusion Resistance Coefficient: 7000
HVAC Ins. 61
68
No command
HVAC Ins. 62
69
No command
HVAC Ins. 63
Applications
HVAC Ins. 65
71
Applications
HVAC Ins. 66
72
Applications
HVAC Ins. 67
Applications
HVAC Ins. 68