TRANE - Human Comfort Solutions Air - Cooled Liquid Chiller

CGAT Air-Cooled Liquid Chiller 5-18 Tons

Mechanical Specification
General
Unit shall be assembled on heavy gauge steel mounting/lifting rails and shall be weather proofed, Units shall include a hermetic scroll compressor (s), slit fin condenser coil, fans and motors, controls and fully charge of R-22. Operating range shall be between 120F and 35F in cooling as standard from the factory. Units rated in accordance with ARI Standard 210 and 270.

Refrigeration System Dual Compressor


CGAT135-215 shall have two separate and independent refrigeration circuits. Each refrigeration circuit shall have an integral subcooling circuits. CGAT135-215 Models shall have two direct drive hermetic scroll compressors with centrifugal oil pump and provide positive lubrication to all moving parts. Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of nameplate voltage. Internal temperature and current-sensive motor overloads shall be included for maximum protection. External high low pressure cutout devices shall be provided.

Controls
The chiller shall be completely factory-wired with necessary capacity and safety controls, contactor pressure lugs or terminal block for power wiring in a weather-tight enclosure with knockouts for jobsite installation. Control wiring shall be 220V. Safety controls shall include high and low pressure cutouts, and time delay relays. Independent chiller freezing protection shall be provided as standard. The unit shall have a single point power connection.

Chilled Water Air Handling Unit BDHA/CB Model 2,000 - 8,000 CFM

CGAT 065-215 Air - Cooled Liquid Chiller 5-18 TONS 50 Hz

Casing
Besides CGAT chillers, Trane offers a complete range of chilled water terminals to be integrated in any type of installation
Unit casing shall be constructed of 18 gauge zinc coated heavy gauge, galvanized steel. Exterior surfaces shall be cleaned, phosphatized and finished with a polyester powder painting and weather-resistant baked enamel finish. Units surface shall be tested 500 hours in salt spray test. Units shall have removable end panels which allow access to all major components and controls.

Time Delay Relay


Shall prevent compressors in single and dual compressor unit from coming on line simultaneously. Timer shall be 220 volt, with three minutes timing period for single compressor. Timer will be three minutes and four and a half minutes for dual circuit in the first and second compressor, respectively.

Evaporator
The evaporator shall have independent refrigerant circuit. The evaporator shall be brazed plate heat exchanger. For units with two evaporators, the connecting water manifold shall be provided. Evaporator shall be insulated with a 3/4" closed-cell insulation.

CFEA Convertible Chilled Water Fan Coil 400-2,000 CFM Tall Floor: Yukon HFWB 1,500-4,000 cfm HFCC/HFCD Chilled Water Fan Coil HFCC 400-1,200 CFM HFCD 1,400-2,000 CFM

Refrigeration System Single compressor


CGAT065-105 model shall have a single refrigeration circuit with an intergral subcooling circuit. CGAT065-105 shall have both a liquid line and suction gas line access valve with gauge port and one direct drive hermetic scroll compressor with centrifugal oil pump providing positive lubrication to moving parts. Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of nameplate voltage. Internal temperature and current-sensitive motor overloads shall be included for maximum protection. Scroll type compressor shall provide inherently low vibration and noise by having no suction and discharge valves. External high, low pressure cutout devices and filter drier shall be provided.

Accessories
Copper fin/Blue fin shall protect corrosion on sea coast application.

Condenser Coil
Coil shall be internally finned of smooth bore 3/8 copper tubes mechanically bonded to configured aluminum plate fin as standard. Factory pressure and leak tested to 375 psig air pressure.

Evaporator water pressure drop (feet of water)


100.00 Pressure Drop, feet of water

Condenser Fan and Motor (S)


Direct-drive, statically and dynamically balanced 28 inch propeller fan (s) with aluminum blades and electrocoated steel hubs shall be used in draw through vertical discharge position. Either permanently lubricated totally enclosed or open construction motors shall be provided and shall have built in current and thermal overload protection. Motor (s) shall have either ball or sleeve bearing type.

CGAT065 CGAT085 CGAT105 CGAT135 CGAT175 CGAT215

10.00

1.00 10.0
CGAT-SLB001-0303

Water flowrate, gpm

100.0

Trane Thailand 7th Floor, Ploenchit Center Building 2 Sukhumvit Road, Klongtoey Bangkok 10110 Amair Limited 35 Mu 8, Poochaosamingprai Road Samrong Tai, Samutprakarn 10130 http://www.trane.com An American Standard Company

Literature Order Number: New Stocking Location:

CGAT-SLB001-0303

CGAT-SLB001-0303
Bangkok, Thailand

Since The Trane Company has a policy of continuous product and product data improvement, it reserves the right to change design and specifications without notice.

CGAT - Human Comfort Solutions

General Data

General Data

Performance Data -Cooling capacity CGAT065D CGAT085D CGAT105D CGAT135D CGAT175D CGAT215D 75 deg.F Model LWT deg.F 42 44 45 46 48 50 42 44 45 46 48 50 42 44 45 46 48 50 42 44 45 46 48 50 42 44 45 46 48 50 42 44 45 46 48 50 Entering air temperature on condensing coil 85 deg.F 95 deg.F 105 deg.F

An answer to all your needs...


We at TRANE have listened to our customers. After many surveys and studies we have identified very strong demands in terms of installation acoustics energy efficiency reliability maintenance for chilled water applications. That is why we have redesigned our water chillers and have come up with a new concept CGAT

Maximum Efficiency and Reliability


Lower noise operation and higher efficiency with the new generation higher EER Scroll Compressor. 64% fewer parts than a comparable capacity reciprocating compressor. Single rotating assembly minimizes the friction and mechanical losses. Smooth operation, similar to a centrifugal compressor, give low torque variation and extend motor life, and minimal vibration reducing wear. Solid mount with no internal suspension to be worn out. Integral inlet dirt separator removes contaminants. Rolling element bearings for higher efficiency reduced friction. No suction or discharge valves for improved efficiency compared to a reciprocating compressor.

With CGAT chillers, you will find an answer to fit all your applications, whether it is comfort or process cooling.

Installation
All chillers are completely factory-wired with necessary capacity and safety controls, enclosed in a weather-tight control panel with knockouts for jobsites fully assembled, tested, charged and ready to provide chilled water. No messy field assembly or refrigerant charging is required. Further, the unit has been designed for a single power and water connection.

Easy Service
Our design allows you to remove any or all panels for service. We have paid careful attention to service details, and all units feature coded wiring, hinged control boxes, and mechanical controls for easy service.

Unit Performance Cooling Capacity (1) MBH Main Power supply V/Ph/Hz Min.Brch.Cir.Ampacity A No.of Independent circuits Compressor Type Speeds number Motors Number Rated Amps (2) A Locked rotor Amps (2) A Motor RPM rpm Evaporator Type Water flowrate GPM Water Connections Type Diameter Outdoor Coil Type Tube size inch Tube type Face Area Ft2 Rows # Fins per inch (fpf) # Outdoor Fan Type Number Diameter inch Drive type Speeds number Air flow CFM Motors Number Motor HP (1) hp Rated Amps (1) A Locked rotor Amps (1) A Motor RPM rpm Dimensions Height mm Length mm Width mm Weight uncrated kg R-22 Refrigerant Charge (2) kg Notes: (1) per motor (2) per circuit

65.2 86.3 104.4 133.1 175.4 214.9 380-415/3/50 380-415/3/50 380-415/3/50 380-415/3/50 380-415/3/50 380-415/3/50 22.45 25.82 26.87 40.8 46.84 48.84 1 1 1 2 2 2 Hermetic Scroll 1 1 1 2 19.6 16.4 125 95 2900 2900

Cooling Water flow Cooling Water flow Cooling Water flow Cooling Water flow Capacity rate Capacity rate Capacity rate Capacity rate MBH US gpm MBH US gpm MBH US gpm MBH US gpm 68.2 70.5 72.4 74.3 75.1 78.5 90.6 94.4 96.3 98.2 98.9 102.4 111.1 114.9 116.0 116.0 119.0 122.8 140.3 145.6 147.5 149.4 153.2 157.0 186.1 192.2 195.2 197.1 204.0 208.1 223.7 229.7 233.5 237.3 241.9 249.1 13.6 14.1 14.5 14.9 15.0 15.7 18.1 18.9 19.3 19.6 19.8 20.5 22.2 23.0 23.2 23.2 23.8 24.6 28.1 29.1 29.5 29.9 30.6 31.4 37.2 38.4 39.0 39.4 40.8 41.6 44.7 45.9 46.7 47.5 48.4 49.8 66.7 68.2 69.0 70.9 71.7 75.1 87.2 91.0 92.1 92.1 95.2 98.9 104.3 108.0 109.9 111.8 115.6 119.4 135.0 138.8 140.7 142.5 146.3 150.1 177.8 183.1 185.8 189.6 194.1 197.9 213.4 219.5 223.3 227.1 231.6 238.8 13.3 13.6 13.8 14.2 14.3 15.0 17.4 18.2 18.4 18.4 19.0 19.8 20.9 21.6 22.0 22.4 23.1 23.9 27.0 27.8 28.1 28.5 29.3 30.0 35.6 36.6 37.2 37.9 38.8 39.6 42.7 43.9 44.7 45.4 46.3 47.8 63.3 64.8 65.2 67.5 68.2 71.7 83.8 85.3 86.3 88.0 91.7 92.1 100.8 103.5 104.4 105.8 108.8 112.6 128.1 131.9 133.1 135.7 139.5 146.7 169.1 172.9 175.4 179.3 183.9 187.7 203.2 209.3 214.9 216.0 221.0 225.2 12.7 13.0 13.0 13.5 13.6 14.3 16.8 17.1 17.3 17.6 18.3 18.4 20.2 20.9 20.9 21.2 21.8 22.5 25.6 26.4 26.6 27.1 27.9 29.3 33.8 34.6 35.1 35.9 36.8 37.5 40.6 41.9 43.0 43.2 44.2 45.0 59.9 61.4 62.2 64.1 64.8 68.2 78.5 80.8 82.6 84.5 85.3 88.7 94.0 97.8 99.7 101.6 105.4 105.8 121.3 125.1 127.0 128.9 132.7 136.5 158.8 164.9 167.9 169.8 173.6 177.4 191.5 196.8 199.4 203.2 207.8 215.0 12.0 12.3 12.4 12.8 13.0 13.6 15.7 16.2 16.5 16.9 17.1 17.7 18.8 19.6 19.9 20.3 21.1 21.2 24.3 25.0 25.4 25.8 26.5 27.3 31.8 33.0 33.6 34.0 34.7 35.5 38.3 39.4 39.9 40.6 41.6 43.0

1 1 16.4 95 2900 Brazed-plate 13.0 Male 1 1/2" Slit Fin 3/8 Smooth 15.10 2 16 (192) Propeller 1 28 Direct 1 4900 1 3/4 1.95 2.33 700 1050 1060 950 181 5.0

1 1 19.2 125 2900

1 2 19.2 125 2900

1 2 19.6 125 2900

CGAT065

Brazed-plate Brazed-plate 17.3 20.9 Male 1 1/2" Slit Fin 3/8 Smooth 20.00 2 16 (192) Propeller 1 28 Direct 1 5800 1 3/4 1.82 3.07 800 1050 1060 950 204 5.2 Male 1 1/2" Slit Fin 3/8 Smooth 25.00 2 16 (192) Propeller 1 28 Direct 1 6800 1 3/4 2.37 7.46 950 1050 1260 1050 250 7.5

Brazed-plate Brazed-plate Brazed-plate 26.6 35.1 43.0 Male 1 1/2" Slit Fin 3/8 Smooth 30.20 2 16 (192) Propeller 2 28 Direct 1 9800 2 3/4 1.95 2.33 700 1050 2200 1050 406 5.3 Male 1 1/2" Slit Fin 3/8 Smooth 40.00 2 16 (192) Propeller 2 28 Direct 1 11600 2 3/4 1.82 3.07 800 1050 2200 1050 452 5.5 Male 1 1/2" Slit Fin 3/8 Smooth 42.50 2 16 (192) Propeller 2 28 Direct 1 13600 2 3/4 2.37 7.46 950 1050 2200 1050 472 7.8

CGAT085

CGAT105

CGAT135

CGAT175

CGAT215

Notes : 1. Ratings based on ARI Standard 590-92 2. Data based on 10 deg.F water temperature rise 3. LWT - Leaving Water Temperature